https://www.phoenixcontact.com/us/products/2800406
Type 2 surge protection replacement module - VAL-SQ SE 200-277/480Y-
H /D - 2800406
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge protection device for 277/480 V AC Wye configurations with a high-resistance ground typically used as
service entry protection. NEMA rated enclosure provides a monitor with surge counter, status LEDs and audible
alarm with remote monitor capability. Hybrid Sine Wave Tracking provides 200 kA surge protection.
Product Description
Surge protection device for service entrance protection of 277/480 V AC high resistance ground systems with 200 kA protection
Product Features
■
■
■
■
Optional disconnect switch
UL 1449, 3rd edition, September 2009
Optional 10-mode protection for sensitive electronics
Filter for sine wave tracking
Key Commercial Data
Packing unit
Custom tariff number
Country of origin
1 pc
85363090
United States
Technical data
Note
Trade restriction
The products are offered exclusively for export outside the EU and the
European Economic Area.
Dimensions
Width
Depth
418 mm
562 mm
Ambient conditions
Degree of protection
Ambient temperature (operation)
NEMA 3R/12
-20 °C ... 65 °C
04/18/2016 Page 1 / 4
https://www.phoenixcontact.com/us/products/2800406
Type 2 surge protection replacement module - VAL-SQ SE 200-277/480Y-
H /D - 2800406
Technical data
Ambient conditions
Ambient temperature (storage/transport)
Altitude
Permissible humidity (operation)
-20 °C ... 65 °C
3658 m
0 % ... 95 %
General
IEC power supply system
NEMA power supply system
Housing material
Mounting type
Type
Surge protection fault message
TN-S
TT
277/480 V Wye
Metal
Wall mounting
Parallel MOV
Phase LEDs
Audible alarm
Remote indicator contact
Direction of action
3L-N & N-GND
Protective circuit
Maximum continuous operating voltage U
C
Response time t
A
550 V
< 1 ns
Connection, protective circuit
Connection method
Tightening torque
Conductor cross section AWG min.
Conductor cross section AWG max.
Screw terminal blocks
4-wire + Gnd
4 Nm
12
2
Remote indicator contact
Connection method
Conductor cross section AWG min.
Conductor cross section AWG max.
Screw connection
22
14
NEMA / UL data
UL type
Maximum Continuous Operating Voltage (MCOV without reference
direction)
Voltage protection rating VPR (L-L)
Voltage protection rating (VPR L-PE)
Nominal discharge current I
n
(without reference direction)
type 2
550 V
2000 V
1800 V
20 kA
04/18/2016 Page 2 / 4
https://www.phoenixcontact.com/us/products/2800406
Type 2 surge protection replacement module - VAL-SQ SE 200-277/480Y-
H /D - 2800406
Technical data
NEMA / UL data
Maximum Surge Current per Phase
Short-circuit current rating (SCCR)
EMI/RFI filtering
200 kA
200 kA
-30 dB @ 100 kHz
Standards and Regulations
Standards/regulations
UL 1449 3 edition, Sept. 2009
UL 1283
IEEE C62.41
IEEE C62.45
rd
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27140201
27130801
27130801
27130801
27130802
27130802
27130805
ETIM
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC000942
EC001473
EC000941
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30212010
39121610
39121610
39121610
39121620
Drawings
04/18/2016 Page 3 / 4
https://www.phoenixcontact.com/us/products/2800406
Type 2 surge protection replacement module - VAL-SQ SE 200-277/480Y-
H /D - 2800406
Dimensional drawing
411
318
L1
L2
Circuit diagram
L3
N
GND
C NC NO
J
J
J
J
J
J
J
550
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
535