https://www.phoenixcontact.com/us/products/2742599
Inline terminal - IB IL 24 EDO 2 - 2742599
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Inline digital output terminal block, without accessories, 2 outputs, 24 V DC, 500 mA, 4-wire connection method,
extended diagnostics, outputs can be parameterized
Product description
The terminal is designed for use within an Inline station. It serves to output signals and provides the possibility of channel for channel extended
diagnostics for overload, short-circuit or line interrupt faults.
Features
- Connections for 2 digital actuators
- Connection of the actuators using 2 , 3 or 4-wire system
- Nominal current per output: 500 mA
- Total current of terminal: 1 A
- Short-circuit and overload protected outputs
- Line interrupt detection
- Diagnostics and status indicators
- Individual channel diagnostics
- Parameterizable behavior of outputs in the case of an INTERBUS reset
Key commercial data
Packing unit
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
1 pc
65.4 GRM
85389091
Germany
Technical data
Dimensions
Width
Height
Depth
Note on dimensions
12.2 mm
119.8 mm
71.5 mm
Housing dimensions
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
Permissible humidity (operation)
-25 °C ... 55 °C
-25 °C ... 85 °C
10 % ... 95 % (according to DIN EN 61131-2)
09/08/2014 Page 1 / 5
https://www.phoenixcontact.com/us/products/2742599
Inline terminal - IB IL 24 EDO 2 - 2742599
Technical data
Ambient conditions
Permissible humidity (storage/transport)
Air pressure (operation)
Air pressure (storage/transport)
Degree of protection
10 % ... 95 % (according to DIN EN 61131-2)
70 kPa ... 106 kPa (up to 3000 m above sea level)
70 kPa ... 106 kPa (up to 3000 m above sea level)
IP20
Interfaces
Designation
Connection method
Inline local bus
Inline data jumper
Digital outputs
Output name
Output description
Connection method
Number of outputs
Protective circuit
Output voltage
Nominal output voltage
Maximum output current per channel
Maximum output current per module
Nominal load, inductive
Nominal load, lamp
Nominal load, ohmic
Digital outputs
Extended diagnostics, parameterizable outputs
Spring-cage connection
2, 3, 4-wire
2
Short-circuit and overload protection
24 V DC (U
S
- 1 V)
24 V DC (voltage difference at I
nom
≤ 1 V)
500 mA
1A
12 W
12 W
12 VA
Power supply for module electronics
Supply voltage
Supply voltage range
Communications power U
L
Current consumption
24 V DC (via voltage jumper)
19.2 V DC ... 30 V DC
7.5 V (via voltage jumper)
max. 40 mA (from the local bus)
General
Weight
Note on weight specifications
Mounting type
Protection class
Test section
41 g
Without plug
DIN rail
III, IEC 61140, EN 61140, VDE 0140-1
5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz
1 min
5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz
1 min
7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
09/08/2014 Page 2 / 5
https://www.phoenixcontact.com/us/products/2742599
Inline terminal - IB IL 24 EDO 2 - 2742599
Technical data
General
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Diagnostics messages
Short-circuit / overload of the digital outputs Error message in the
diagnostic code (bus) and display (2 Hz) via the LED (D) on the module
Inline potentials
Communications power U
L
Current consumption from U
L
Main circuit supply U
M
Segment supply voltage U
S
Current consumption from U
S
7.5 V DC
max. 40 mA
24 V DC
24 V DC (nominal value)
max. 1 A
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
27250302
27250302
27250302
27242604
27242604
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC001430
EC001599
EC001599
EC001599
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
43172015
43201404
43172015
43201404
43201404
Drawings
09/08/2014 Page 3 / 5
https://www.phoenixcontact.com/us/products/2742599
Inline terminal - IB IL 24 EDO 2 - 2742599
Connection diagram
Dimensioned drawing
140,5
1.1
2.1
119,8
1.2
2.2
1.3
2.3
1.4
2.4
OUT 1
OUT 2
+24 V
+24 V
71,5
09/08/2014 Page 4 / 5
https://www.phoenixcontact.com/us/products/2742599
Inline terminal - IB IL 24 EDO 2 - 2742599
Block diagram
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
09/08/2014 Page 5 / 5