https://www.phoenixcontact.com/us/products/2782135
Surge protection device - RF-TRAB - 2782135
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Attachment plug with replaceable surge protection for coaxial signal interfaces, transmission capacity ≤200 W.
Connection: UHF female/female.
Key commercial data
Packing unit
GTIN
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
79.89 GRM
85363010
Germany
1 pc
Technical data
Dimensions
Height
Width
Length
40 mm
60.5 mm
18.1 mm
Ambient conditions
Ambient temperature (operation)
Degree of protection
-40 °C ... -90 °C
IP20
General
Housing material
Color
Mounting type
Type
Direction of action
Nickel-plated brass
silver
Connection-specific intermediate plugging
Attachment plug
Line-Shield/Earth Ground
09/09/2014 Page 1 / 5
https://www.phoenixcontact.com/us/products/2782135
Surge protection device - RF-TRAB - 2782135
Technical data
Protective circuit
IEC test classification
C2
C3
D1
Maximum continuous operating voltage U
C
Maximum continuous voltage U
C
(wire-ground)
Maximum continuous voltage U
C
(wire-shield)
Nominal current I
N
Operating effective current I
C
at U
C
Residual current I
PE
Nominal discharge current I
n
(8/20) µs (Core-Earth)
Nominal discharge current I
n
(8/20) µs (Core-Shield)
Total surge current (8/20) µs
Output voltage limitation at 1 kV/µs (Core-Earth) spike
Output voltage limitation at 1 kV/µs (Core-Shield) spike
Output voltage limitation at 1 kV/µs (Core-Earth) static
Output voltage limitation at 1 kV/µs (Core-Shield) static
Voltage protection level U
P
(Core-Earth)
Voltage protection level U
P
(Core-Shield)
Response time tA (Core-Earth)
Response time tA (Core-GND)
Input attenuation aE, asym.
Cut-off frequency fg (3 dB), asym. (shield) in 50 Ohm system
Standing wave ratio SWR in a 50 Ω system
Permissible HF power P
max
at VSWR = xx (50 ohm system)
Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth)
130 V AC
130 V AC
130 V AC
10 A (25 °C)
≤ 1 µA
≤ 1 µA
10 kA
10 kA
10 kA
≤ 600 V
≤ 600 V
≤ 600 V
≤ 600 V
≤ 600 V
≤ 600 V
≤ 100 ns
≤ 100 ns
0.3 dB (≤ 250 MHz)
typ. 950 MHz
≤ 1.2 (≤ 80 MHz)
300 W (VSWR = 1.1)
80 W (VSWR = ∞)
C2 - 10 kV / 5 kA
D1 - 2,5 kA
Connection data
Connection method
Connection type IN
Connection type OUT
UHF connector
UHF connector, female
UHF connector, female
Connection, equipotential bonding
Connection method
Screw terminal block
Standards and Regulations
Standards/regulations
IEC 61643-21
09/09/2014 Page 2 / 5
https://www.phoenixcontact.com/us/products/2782135
Surge protection device - RF-TRAB - 2782135
Diagram
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
09/09/2014 Page 5 / 5