https://www.phoenixcontact.com/us/products/2862000
Bus coupler - IBS IL 24 BK-T/U-2MBD-PAC - 2862000
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Inline, Bus coupler, INTERBUS remote bus, Inline shield connector, Transmission speed in the local bus 2 MBit/s,
Degree of protection IP20, including Inline connectors and marking fields
Product Features
■
■
■
Remote bus connections using copper technology
Electrical isolation
Approved for use in potentially explosive areas (refer to data sheet)
Key Commercial Data
Packing unit
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
1 pc
260.0 g
85389091
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
Height
Depth
48.8 mm
135 mm
71.5 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
Permissible humidity (operation)
-25 °C ... 55 °C
-25 °C ... 85 °C
75 % ... 85 % (in the range of -25°C ... +55°C, appropriate measures
against increased humidity (> 85%) must be taken.)
04/27/2016 Page 1 / 6
https://www.phoenixcontact.com/us/products/2862000
Bus coupler - IBS IL 24 BK-T/U-2MBD-PAC - 2862000
Technical data
Ambient conditions
Permissible humidity (storage/transport)
Air pressure (operation)
Air pressure (storage/transport)
Degree of protection
75 % ... 85 % (Slight temporary condensation may sometimes appear on
the housing, e.g. when the terminal block is brought out of a vehicle into an
enclosed room.)
80 kPa ... 106 kPa (up to 3000 m above sea level)
70 kPa ... 106 kPa (up to 3000 m above sea level)
IP20
General
Mounting type
Net weight
DIN rail
142 g
Interfaces
Fieldbus system
Designation
Connection method
Transmission speed
Transmission physics
Fieldbus system
Designation
Connection method
Transmission speed
INTERBUS
INTERBUS
Inline shield connector
2 MBit/s
Copper
Lokalbus
Inline local bus
Inline data jumper
2 MBit/s
System limits of the bus coupler
Number of local bus devices that can be connected
Number of devices with parameter channel
Number of supported branch terminals with remote bus branch
63 (without additional power terminal block, observe allowable total current
consumption)
62
max. 15
Power supply for module electronics
Connection method
Supply voltage
Supply voltage range
Current consumption
Inline connector
24 V DC (via Inline connector)
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
max. 1.25 A (with max. number of connected I/O terminal blocks)
Inline potentials
Communications power U
L
Power supply at U
L
Main circuit supply U
M
Power supply at U
M
Segment circuit supply U
S
Power supply at U
S
7.5 V DC ±5 %
max. 2 A DC (observe derating)
24 V DC -15 % / +20 % (acc. to EN 61131-2)
max. 8 A DC (Sum of U
M
+ U
S
)
24 V DC -15 % / +20 % (acc. to EN 61131-2)
max. 8 A DC (Sum of U
M
+ U
S
)
04/27/2016 Page 2 / 6
https://www.phoenixcontact.com/us/products/2862000
Bus coupler - IBS IL 24 BK-T/U-2MBD-PAC - 2862000
Technical data
Inline potentials
I/O supply voltage U
ANA
Power supply at U
ANA
24 V DC -15 % / +20 %
max. 0.5 A DC (observe derating)
Standards and Regulations
Test section
5 V supply, incoming remote bus/5 V supply outgoing remote bus 500 V
AC 50 Hz 1 min.
5 V supply, incoming remote bus/7.5 V logics supply, 24 V analog supply,
24 V bus terminal module supply 500 V AC 50 Hz 1 min.
5 V supply, incoming remote bus/24 V main supply, 24 V segment supply
500 V AC 50 Hz 1 min.
5 V supply incoming remote bus / functional earth ground 500 V AC 50 Hz
1 min.
5 V supply, outgoing remote bus/24 V main supply, 24 V segment supply
500 V AC 50 Hz 1 min.
5 V supply, outgoing remote bus/7.5 V logics supply, 24 V analog supply,
24 V bus terminal module supply 500 V AC 50 Hz 1 min.
5 V supply outgoing remote bus / functional earth ground 500 V AC 50 Hz
1 min.
7.5 V logics supply, 24 V analog supply, 24 V bus terminal module supply/
functional earth ground 500 V AC 50 Hz 1 min.
7.5 V logics supply, 24 V analog supply, 24 V bus terminal module supply /
24 V main supply, 24 V segment supply 500 V AC 50 Hz 1 min.
24 V main supply, 24 V segment supply/functional earth ground 500 V AC
50 Hz 1 min.
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27250203
27250203
27250203
27242608
27242608
27242608
27242608
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC001434
EC001604
EC001604
EC001604
04/27/2016 Page 3 / 6
https://www.phoenixcontact.com/us/products/2862000
Bus coupler - IBS IL 24 BK-T/U-2MBD-PAC - 2862000
Classifications
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
43172015
43201404
43172015
43201404
43201404
Approvals
Approvals
Approvals
UL Listed / cUL Listed / cULus Listed
Ex Approvals
ATEX
Approvals submitted
Approval details
UL Listed
cUL Listed
cULus Listed
Accessories
Accessories
Connector set
04/27/2016 Page 4 / 6
https://www.phoenixcontact.com/us/products/2862000
Bus coupler - IBS IL 24 BK-T/U-2MBD-PAC - 2862000
Accessories
Connector set - IB IL BK-PLSET/CP - 2860374
Connector set for Inline bus coupler, color-coded
End block
End clamp - E/UK - 1201442
End clamp, Width: 9.5 mm, Height: 35.3 mm, Length: 50.5 mm, Color: gray
Labeling panel
Labeling field - IB IL FIELD 2 - 2727501
Labeling field, width: 12.2 mm
Terminal marking
Insert strip - ESL 62X10 - 0809492
Insert strip, Sheet, white, unlabeled, can be labeled with: Office printing systems, Plotter: Laser printer, Mounting type:
Insert, Lettering field: 62 x 10 mm
Drawings
04/27/2016 Page 5 / 6