General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 00
from 16 to 125 A
• BLADE-STYLE FUSES: WITH BLOWN FUSE INDICATOR
• COMPLYING WITH IEC 269.1 and 2.1 NF EN 60269.1 & 2 NF C 63210 AND DIN 43620 STANDARDS
• DIMENSIONS:
52
2.5
44
6
59
15
14.5
78
46
Weight: 150 g
30
10
Size
Voltage
rating
(VAC)
Current
rating
IN(A)
Watts
loss
(W)
With blown fuse indicator
Designation
Ref. Number
Catalog Number
00
500
400
16
20
25
32
35
40
50
63
80
100
125
0.8
1.1
1.3
1.8
2.0
2.5
3.0
3.6
5.2
6.0
7.0
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
00 L /16
00 L /20
00 L /25
00 L /32
00 L /35
00 L /40
00 L /50
00 L /63
00 L /80
00 L /100
00 L /125
F098307
G098308
H098309
J098310
K098311
L098312
M098313
N098314
P098315
Q098316
R098317
NH00AM50V16-3
NH00AM50V20-3
NH00AM50V25-3
NH00AM50V32-3
NH00AM50V35-3
NH00AM50V40-3
NH00AM50V50-3
NH00AM50V63-3
NH00AM50V80-3
NH00AM50V100-3
NH00AM40V125-3
Accessories: Neutral link BS00 - Reference Number F097709
Pull-out handle - PMP - Reference Number P215592
GPEU
52
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 00
from 16 to 125 A
Total Clearing I
2
t
I
2
t (A
2
S)
107
Ic (kA)
Current Limitation Curves
106
100
105
104
10
125
100
80
63
50
40
32
25
20
16
35
103
102
16 20 25 32 35 40 50 63 80
100 125
Rating (A)
b: total clearing I
2
t @ 500 V
a: pre-arcing I
2
t
1
10
100
Ip (kA)
Ic = Peak let-through current
Ip = Available fault current
Time VS. Current Characteristics
t (s)
103
t (s) =
Pre-arcing duration
Breaking
capacity
100 kA
35
20
50
25 32 40
100
63 80
125
102
16
10
1
10-1
10-2
10
100
1 000
GPEU
53
10 000
Ip (A)
Ip (A) = R.M.S.
AVAILABLE
FAULT CURRENT