General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 0 and 1
from 40 to 315 A
• BLADE-STYLE FUSES: WITH BLOWN FUSE INDICATOR
• COMPLYING WITH IEC 269.1 and 2.1 NF EN 60269.1 & 2 NF C 63210 AND DIN 43620 STANDARDS
• DIMENSIONS:
D
G
B
F
e
H
N
L
J
K
A C
H
N
L
J
e
A C
M
D1
D2
D
G
B
D1
M
With trip-indicator
With blown fuse indicator
Size
A
B
C
D
D1
D2*
F*
G
H
J
K
L
M
N
e
Wgt.
0
1
46
52
62
64
59
64
67
74
36
47
39
47
14
14
2,5
3
15
21
14,5
16
14,5
14,5
125
135
10
10
14,5
14,5
6
6
230g
400g
* For fuses with trip-indicator
Voltage Current
Size
rating rating
IN(A)
(VAC)
Watts
loss
(W)
With blown fuse indicator
Designation Ref. Number
Catalog Number
Designation
With trip-indicator
Ref. Number
Catalog Number
0
500
1
500
40
50
63
80
100
125
160
200
80
100
125
160
200
250
315
2,7
3,2
3,9
5,5
6,5
8,5
11,5
13,5
5,5
6,5
8,5
11,5
13,5
17
24
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
0 / 40
0 / 50
0 / 63
0 / 80
0 / 100
0 / 125
0 / 160
0 / 200
1 / 80
1 / 100
1 / 125
1 / 160
1 / 200
1 / 250
1 / 315
K095114
L095115
M095116
P095118
R095120
T095122
Y095126
R088519
R095166
T095168
C095130
D095131
E095132
H095135
T088521
NH0AM50V40-3
NH0AM50V50-3
NH0AM50V63-3
NH0AM50V80-3
NH0AM50V100-3
NH0AM50V125-3
NH0AM50V160-3
NH0AM50V200-3
NH1AM50V80-3
NH1AM50V100-3
NH1AM50V125-3
NH1AM50V160-3
NH1AM50V200-3
NH1AM50V250-3
NH1AM50V315-3
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
aM
0 / 40 P
0 / 50 P
0 / 63 P
0 / 80 P
0 / 100 P
0 / 125 P
0 / 160 P
0 / 200 P
1 / 80 P
1 / 100 P
1 / 125 P
1 / 160 P
1 / 200 P
1 / 250 P
1 / 315 P
N095232
R095235
X095240
Z095242
A095243
B095244
M095254
F088509
P095256
E095270
V095330
W095331
X095332
A095335
B095336
NH0AM50V40-4
NH0AM50V50-4
NH0AM50V63-4
NH0AM50V80-4
NH0AM50V100-4
NH0AM50V125-4
NH0AM50V160-4
NH0AM50V200-4
NH1AM50V80-4
NH1AM50V100-4
NH1AM50V125-4
NH1AM50V160-4
NH1AM50V200-4
NH1AM50V250-4
NH1AM50V315-4
Accessories: Neutral link BS0 Reference Number G097710 - BS1 Reference Number H097711
Pull-out handle - PMP Reference Number P215592
GPEU
54
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
aM Plastic body with/without French striker
aM 500V Size 0 and 1
from 40 to 315 A
Total Clearing I
2
t
I
2
t (A
2
S)
107
Ic (kA)
Current Limitation Curves
106
100
105
315
250
200
160
125
100
80
63
50
40
104
10
103
102
40 50 63 80
100 125 160 200 250 315
Rating (A)
b: total clearing I t @ 500 V
a: pre-arcing I
2
t
2
1
10
100
Ip (kA)
Ic = Peak let-through current
Ip = Available fault current
Time VS. Current Characteristics
t (s)
103
t (s) =
Pre-arcing duration
Breaking
capacity
100 kA
50
80
125
250
315
102
40
63
100
160 200
10
1
10-1
10-2
10
100
1 000
GPEU
55
10 000
Ip (A)
Ip (A) = R.M.S.
AVAILABLE