Limitor
®
- NF/UTE Back-up Fuses
7,2kV to 24kV - Type FR
NF/UTE HV Back-up Fuses for Transformers
FR-type fuses are designed to protect HV/LV power distribution transformers.
Designed to be coordinated with other equipment, these current limiting fuse-links
interrupt fault currents before they reach their peak. The fault current is interrupted
inside the fuse-link body and although this is very fast, there is no sign of it outside.
The main elements in these fuses are: a barrel of class F insulating synthetic
material, nickel plated aluminium end contacts, pure silver fuse elements and a
composite material fuse element holder to withstand high temperatures.
Thanks to their structure, based on a synthetic material, FR fuse-links are the
perfect answer to the stress involved in use inside HV bays and fuse-link chambers.
Features Benefits
Superior mechanical strength
Outstanding withstand to operating stresses
100% synthetic structure
Average type striker: force 1 ±0.5 Joules
Back-up fuse links
High breaking capacity
High current limitation
EDF Approval which guarantees high performances and quality of fuses mani-
factured (24kV)
z
In accordance with:
IEC 62271-105
IEC 62271-107
IEC 60787
IEC/TR 62655
z
z
z
z
z
z
z
z
Standards
IEC 60282-1
UTE C64-210
Applications
MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
z
z
z
z
z
HV Transformers protection
Fused switch gear combination
Best used in SF6 insulated switch gear and compact switch gear
For indoor use
Operating temperature: -25°C to +40°C
Technical Data
7,2kV
520mm
Rated current
Rated voltage U
n
Rated voltage of transformer
Breaking capacity I
1
Peak arc voltage
Package
12kV
520mm
24kV
520mm
6.3 ... 125 A 6.3 ... 100 A 6.3 ... 63 A
7.2 kV
6 kV
12.5 kA
20 kV
3
12 kV
10 kV
12.5 kA
34 kV
3
24 kV
20 kV
12.5 kA
58 kV
3
High Voltage IEC Fuses / DS-NF/UTC-04-0415_EN
www.ep.mersen.com
1
Limitor
®
- NF/UTE Back-up Fuses
7,2kV to 24kV - Type FR
Product range
Rated voltage 7.2kV, length 520mm, Ø 55mm
Catalog
number
Reference Rated voltage
number
AC (IEC)
Minimum
Rated current
breaking
I
n
current I
3
= I
min
Power dissi-
pation at I
n
Operating I²t at
Rated Voltage
Weight
without striker
FR72V6,3
FR72V16
FR72V32
FR72V43
FR72V63
55AL72V80
55AL72V100
55AL72V125
Z227584
A227585
B227586
C227587
D227588
H087982
K088927
N088953
7.2 kV
7.2 kV
7.2 kV
7.2 kV
7.2 kV
7.2 kV
7.2 kV
7.2 kV
6.3 A
16 A
32 A
43 A
63 A
80 A
100 A
125 A
31.5 A
80 A
160 A
215 A
315 A
360 A
450 A
582 A
12 W
26 W
44 W
61 W
71 W
100 W
130 W
130 W
0.3 kA²s
1.6 kA²s
6 kA²s
12 kA²s
24 kA²s
45 kA²s
80 kA²s
200 kA²s
0.6833 kg
0.6833 kg
2.8 kg
2.8 kg
2.3333 kg
2.1 kg
2.1 kg
2.1 kg
with striker
FR72V6,3P
FR72V16P
FR72V32P
FR72V43P
FR72V63P
55AL72V80P
E227589
F227590
G227591
H227592
J227593
J085453
7.2 kV
7.2 kV
7.2 kV
7.2 kV
7.2 kV
7.2 kV
7.2 kV
7.2 kV
6.3 A
16 A
32 A
43 A
63 A
80 A
100 A
125 A
31.5 A
80 A
160 A
215 A
315 A
360 A
450 A
582 A
12 W
26 W
44 W
61 W
71 W
100 W
130 W
130 W
0.3 kA²s
1.6 kA²s
6 kA²s
12 kA²s
24 kA²s
45 kA²s
80 kA²s
200 kA²s
2.2666 kg
2.3333 kg
2.0333 kg
0.6833 kg
2.3333 kg
2.1 kg
2.1 kg
2.1 kg
55AL72V100P K085454
55AL72V125P M085456
Rated voltage 12kV, length 520 mm, Ø 55mm
Catalog
number
Reference
EDF Number
number
Rated
voltage AC
(IEC)
Rated
current I
n
Minimum
breaking
current I
3
= I
min
Power
dissi-
pation
at I
n
Operating
I²t at Rated
Voltage
Weight
FR120V6,3
FR120V16
FR120V32
FR120V43
FR120V63
55AL120V80
55AL120V100
X210240
Y210241
Z210242
A210243
B210244
K088973
L088974
-
73.02.136
73.02.137
-
73.02.138
-
-
12 kV
12 kV
12 kV
12 kV
12 kV
12 kV
12 kV
6.3 A
16 A
32 A
43 A
63 A
80 A
100 A
31.5 A
80 A
160 A
215 A
315 A
360 A
450 A
25 W
53 W
89 W
123 W
142 W
100 W
130 W
0.3 kA²s
1.6 kA²s
6 kA²s
12 kA²s
24 kA²s
100 kA²s
180 kA²s
2.0666 kg
2.2233 kg
2.0333 kg
2.0666 kg
0.7666 kg
2.1 kg
2.1 kg
with striker
FR120V6,3P
FR120V16P
FR120V32P
FR120V43P
FR120V63P
55AL120V80P
D210246
E210247
F210248
G210249
H210250
Q085436
-
73.02.136
73.02.137
-
73.02.138
-
-
12 kV
12 kV
12 kV
12 kV
12 kV
12 kV
12 kV
6.3 A
16 A
32 A
43 A
63 A
80 A
100 A
31.5 A
80 A
160 A
215 A
315 A
360 A
450 A
25 W
53 W
89 W
123 W
142 W
100 W
130 W
0.3 kA²s
1.6 kA²s
6 kA²s
12 kA²s
24 kA²s
100 kA²s
180 kA²s
2.05 kg
2.3333 kg
2.1666 kg
2.34 kg
2.3333 kg
2.1 kg
2.1 kg
55AL120V100P R085437
High Voltage IEC Fuses / DS-NF/UTC-04-0415_EN
www.ep.mersen.com
MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
without striker
2
Limitor
®
- NF/UTE Back-up Fuses
7,2kV to 24kV - Type FR
Product range
Rated voltage 24kV, length 520 mm, Ø 55mm
Catalog
number
Reference
EDF Number
number
Rated
voltage AC
(IEC)
Rated
current I
n
Minimum
breaking
current I
3
= I
min
Power
dissi-
pation
at I
n
Operating
I²t at Rated
Voltage
Weight
without striker
LOT-FR240V6.3
LOT-FR240V16
LOT-FR240V32
LOT-FR240V43
LOT-FR240V63
A210795
B210796
G226234
C210797
D210798
73.02.132
73.02.133
73.02.133
73.02.134
73.02.135
24 kV
24 kV
24 kV
24 kV
24 kV
6.3 A
16 A
32 A
43 A
63 A
31.5 A
80 A
160 A
215 A
315 A
25 W
53 W
89 W
123 W
142 W
0.63 kA²s
3.3 kA²s
13 kA²s
25 kA²s
50 kA²s
2.1 kg
2.1 kg
2.1 kg
2.1 kg
2.1 kg
with striker
LOT-FR240V6.3P G227430
LOT-FR240V16P
LOT-FR240V32P
LOT-FR240V43P
LOT-FR240V63P
H227431
J227432
K227433
L227434
73.02.132
73.02.133
-
73.02.134
73.02.135
24 kV
24 kV
24 kV
24 kV
24 kV
6.3 A
16 A
32 A
43 A
63 A
31.5 A
80 A
160 A
215 A
315 A
25 W
53 W
89 W
123 W
142 W
0.63 kA²s
3.3 kA²s
13 kA²s
25 kA²s
50 kA²s
2.1 kg
2.1 kg
2.1 kg
2.1 kg
2.1 kg
Characteristics of trip indicator
Strength (N)
40
20
40
Trip (mm)
High Voltage IEC Fuses / DS-NF/UTC-04-0415_EN
www.ep.mersen.com
MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
20
3
Limitor
®
- NF/UTE Back-up Fuses
7,2kV to 24kV - Type FR
Time current characteristic curves
Limitor
®
NF/UTE 7.2kV, 12kV, 24kV 6.3 - 63A without striker
10000
7000
5000
3000
2000
1000
700
500
300
200
100
70
50
30
20
10
7
5
3
2
1
0.7
0.5
0.3
0.2
0.1
0.07
0.05
0.03
0.02
0.01
0.007
0.005
Pre-arcing time (s)
6,3 A
16 A
32 A
43 A
63 A
0.002
0.001
0.0007
0.0005
0.0003
0.0002
0.0001
100
10
20
30
50
70
500
700
1000
2000
3000
5000
7000
200
300
10000
RMS value of prearc current (A) +/-10%
High Voltage IEC Fuses / DS-NF/UTC-04-0415_EN
www.ep.mersen.com
MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
0.003
4
Limitor
®
- NF/UTE Back-up Fuses
7,2kV to 24kV - Type FR
Time current characteristic curves
Limitor
®
NF/UTE 7.2kV, 12kV, 24kV 6.3 - 63A with striker
10000
7000
5000
3000
2000
1000
Pre-arcing time (s)
700
500
300
200
100
70
50
30
20
10
7
5
3
2
1
0.7
0.5
0.3
0.2
0.1
0.07
0.05
0.03
0.02
0.01
0.007
0.005
0.003
6,3 A
16 A
32 A
43 A
63 A
0.001
0.0007
0.0005
0.0003
0.0002
0.0001
10000
1000
2000
3000
5000
7000
100
200
300
500
700
10
20
30
50
70
RMS value of prearc current (A) +/-10%
High Voltage IEC Fuses / DS-NF/UTC-04-0415_EN
www.ep.mersen.com
MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
0.002
5