General Purpose US
US Fuses
Fuses
General Purpose
American Power Fuses
AMP-TRAP 2000
®
A2D and A6D (Class RK1 TD)
Upgrade yesterday’s circuits to today’s
Type 2 protection
Amp-trap 2000
®
SmartSpot
®
A2D, A6D fuses now
provide a visual open fuse indicator. With advanced materi-
al technology added to the existing product line the A2D,
A6D fuses provide IEC Type “2” (No Damage) protection to
main, feeder, and branch circuits, for all types of loads —
A2D, A6D’s time delay characteristics for handling harmless
in-rush currents, its current limiting ability and wide range
of ratings (from 1 to 600 Amperes) — give excellent
protection for all your applications.
Features /Benefits
• Solid State SmartSpot Indicator
• Time delay for motor starting and transformer inrush
currents without nuisance opening
• 300kA interrupting rating - self-certified,
UL witnessed tests
• Extremely Current Limiting for low peak let-thru
current
• Easy 2-to-1 selectivity for prevention of nuisance
shut downs and “black outs”
• Rejection-style design prevents replacement errors
(when used with recommended fuse blocks)
• High-visibility orange label gives instant
recognition
• Reduced inventory by taking the place of RK5,
K, and H fuses
• Metal-embossed date and catalog number for easier
traceability and lasting identification
• Fiberglass body provides dimensional stability in harsh
industrial settings
• Brass end-caps (blade-style) for cooler operation and
superior performance
Ratings
A2D AC: 1/10 to 600A 250VAC, 200kA I.R.
(self certified for250VAC, 300kA I.R.,
UL witnessed)
A6D AC: 1/10 to 600A 600VAC, 200kA I.R.
(self certified for 600VAC, 300kA I.R.)
Highlights
•
•
•
•
SmartSpot Indicator
Time Delay
Current Limiting
Plated Terminals
Applications
•
•
•
•
•
•
•
Motors
Safety Switches
Transformers
Branch Circuit Protection
Disconnects
Control Panels
All General-purpose Circuits
Approvals
• UL Listed to Standard 248-12
• CSA Certified to Standard
C22.2 No. 248.12
GPUS
11
12/04
General Purpose US
US Fuses
Fuses
General Purpose
American Power Fuses
AMP-TRAP 2000
®
A2D and A6D (Class RK1 TD)
A6D 1/10 to 8
MELTING TIME – CURRENT DATA, 600V FUSES
TIME IN SECONDS
Peak Let-Thru Current Data
A2D 30 to 600, 250 Volts AC
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data
A6D 30 to 600, 600 Volts AC
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
NOTE:
SEE APPLICATION INFORMATION SECTION OF CATALOG (LOW VOLTAGE FUSES FOR MOTOR PROTECTION) FOR GUIDE-
LINES ON THREE PHASE MOTOR FUSE SELECTION, CLASS RK1 A2D & RK1 A6D FUSES
GPUS
15
CURRENT IN AMPERES
12/04