General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 00
from 10 to 160 A
• BLADE-STYLE FUSES: WITH BLOWN FUSE INDICATOR
• COMPLYING WITH IEC 269.1 and 2.1 NF EN 60269.1 & 2 NF C 63210 AND DIN 43620 STANDARDS
• DIMENSIONS:
52
2.5
44
6
59
15
14.5
78
Weight: 150 g
30
10
46
Main Characteristics
Voltage
Size
rating
(VAC)
Current
rating
IN(A)
Watts
loss
(W)
With BLOWN FUSE indicator
Designation
Reference Number
Catalog Number
00
500
10
16
20
25
32
35
40
50
63
80
100
125
160
1
1.4
1.8
2.1
3
3
3.3
4.5
6
7
7.5
13
15
gG
gG
gG
gG
gG
gG
gG
gG
gG
gG
gG
gG
gG
00 L / 10
00 L / 16
00 L / 20
00 L / 25
00 L / 32
00 L / 35
00 L / 40
00 L / 50
00 L / 63
00 L / 80
00 L / 100
00 L / 125
00 L / 160
M098290
N098291
P098292
Q098293
R098294
S098295
T098296
V098297
X098299
Z098301
A098302
B098303
D098305
NH00GG50V10-3
NH00GG50V16-3
NH00GG50V20-3
NH00GG50V25-3
NH00GG50V32-3
NH00GG50V35-3
NH00GG50V40-3
NH00GG50V50-3
NH00GG50V63-3
NH00GG50V80-3
NH00GG50V100-3
NH00GG50V125-3
NH00GG50V160-3
Accessories:
Neutral link Z218269
Pull-out handle - PMP - Part # P215592
GPEU
44
General Purpose IEC Fuses
General Purpose IEC Fuses
NH Fuses (Plain Blades)
gG Plastic body with/without French striker
gG 500V Size 00
from 10 to 160 A
Total Clearing I
2
t
10
6
Current Limitation Curves
Ic (kA)
I
2
t (A
2
S)
100
10
5
10
4
160
125
10
10
3
100
80
63
50
40
32
25
20
35
10
2
16
10
10
1
10 16 20 25 32 35 40 50 63 80100125160
Rating (A)
1
1
10
100
Ip (kA)
b: total clearing I
2
t @ 500 V
Ic = Peak let-through current
Ip = Available fault current
a: pre-arcing I
2
t
Time VS. Current Characteristics
20
32 40
125
10
4
t (s)
t (s) = Pre-arcing duration
10
16
25
35 50
63 80 100 160
Breaking
capacity
100 kA
10
3
10
2
10
1
10
-1
10
-2
10
100
1 000
GPEU
45
10 000
Ip (A)
Ip (A) = R.M.S.
AVAILABLE
FAULT CURRENT