Protistor DC
Protistor DC fuses
fuses
DC Ferrule Fuses
36x250
gR 2000V DC
gRB from 0.8 to 40 A
Dimensions
255
43
20
ø 36
CC 209P ...
ø12
Weight 667 g
Trip force: 15 N at 20 mm
250
ø 36
CC 2000 ...
Weight 610 g
Main Characteristics
Size
Current
rating
IN( A )
Breaking
Capacity
Watts loss
0.8 IN IN
(W)
(W)
Designation
Reference
Number
Catalog Number
0.8
1
1.5
2
3.15
4
5
6
8
10
12
36x250 16
20
25
32
40
10
12
20
25
32
40
@ 2000 V DC
30 kA
L/R = 20 ms
1
1.1
1.8
2
2.8
4
5
5.3
6
7
7.6
10.5
10
12
15.2
19.6
7.0
7.6
10
12
15.2
19.6
1.8
2
3
3.3
5
7
8.8
9
10
12
13
18
17.5
21
26
33.6
12
13
17.5
21
26
33.6
CC 2000 CP gRB 36x250/0.8
CC 2000 CP gRB 36x250/1
CC 2000 CP gRB 36x250/1.5
CC 2000 CP gRB 36x250/2
CC 2000 CP gRB 36x250/3.15
CC 2000 CP gRB 36x250/4
CC 2000 CP gRB 36x250/5
CC 2000 CP gRB 36x250/6
CC 2000 CP gRB 36x250/8
CC 2000 CP gRB 36x250/10
CC 2000 CP gRB 36x250/12
CC 2000 CP gRB 36x250/16
CC 2000 CP gRB 36x250/20
CC 2000 CP gRB 36x250/25
CC 2000 CP gRB 36x250/32
CC 2000 CP gRB 36x250/40
CC 209P CP gRB 36x250/10
CC 209P CP gRB 36x250/12
CC 209P CP gRB 36x250/20
CC 209P CP gRB 36x250/25
CC 209P CP gRB 36x250/32
CC 209P CP gRB 36x250/40
P 221135
R 093096
S 093097
T 093098
V 093099
N 084951
Q 221136
S 084955
V 090339
H 093157
W 093100
X 093101
H 086257
Y 081441
X 081440
W 081439
L 084949
M 098497
M 084950
R 087461
L 081131
W 087373
FD36GB200V0,8
FD36GB200V1
FD36GB200V1,5
FD36GB200V2
FD36GB200V3,15
FD36GB200V4
FD36GB200V5
FD36GB200V6
FD36GB200V8
FD36GB200V10
FD36GB200V12
FD36GB200V16
FD36GB200V20
FD36GB200V25
FD36GB200V32
FD36GB200V40
FD36GB200V10K
FD36GB200V12K
FD36GB200V20K
FD36GB200V25K
FD36GB200V32K
FD36GB200V40K
Minimum trip indicator operating voltage: 90 V
See Fuse Blocks, Fuse Holders and Fuse clips
Pack:
1 piece
SCDC
16
12/04
Protistor DC fuses
DC Ferrule Fuses
36x250
gR 2000V DC
Protistor DC fuses
gRB from 0.8 to 40 A
Electrical characteristics
DC applications data
L/R (ms)
Peak arc voltage
vs. working voltage
Um(V)
1
4000
2
90
80
70
60
50
40
30
20
10
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
0
3000
2000
1600
500
1000
1500
2000
U (V)
U (V)
Above: Curve indicates the maximum permissible
value of time constant L/R as a function of DC working
voltage
1 : L/R = 45 ms
2 : L/R = 15 ms
Above: Curves indicate for various time constants L/R
the peak arc voltage which may appear across fuse
terminals, vs. DC working voltage
Max. AC voltage (50/60 Hz):
3000 V with breaking capacity of 50 kA
Time vs. current characteristics
25
20
a= 130
A2=0.6
B1= 1.25
B2= 0.6
Cf3= 0.8
10
3.15
1.5
0.8
12
16
10 4
10 3
10 2
a= 130
A2=0.6
B1= 1.25
B2= 0.6
Cf3= 0.8
32
5
6
8
40
1
2
4
t (s)
a= 130
A2=0.6
B1= 1.25
B2= 0.6
Cf3= 0.8
10
1
10 -1
10 -2
10 -3
10 -4
1
10
10 2
10 3 1
10
10 2
10 3 1
10
10 2
10 3
Above: These curves indicate, for each rated current, pre-arcing time vs.
R.M.S. pre-arcing current.
12/04
SCDC
17
± 10% tolerance for mean
pre-arcing current
I (A)