电子工程世界电子工程世界电子工程世界

产品描述

搜索
 

ZEN-BAT01 OMS

器件型号:ZEN-BAT01 OMS
器件类别:热门应用    机电/工控/自动化   
文件大小:27487.19KB,共35页
厂商名称:All Sensors
标准:
下载文档

器件描述

控制器 zen battery

参数
制造商: Omron
产品种类: 控制器
RoHS:
零件号别名: ZENBAT01

ZEN-BAT01 OMS器件文档内容

Programmable Relay                                                                                                                CSM_ZEN_DS_E_4_1

ZEN V2 Units                                                         Refer to Safety Precautions on page 33

Even Broader Applications with Increased
Functionality and Higher Precision

Increased functionality in a compact body (70 mm wide 90 mm
high).

Easy programming is available using the LCD and operation
buttons. (See note 1.)

This single Unit easily provides relay, timer, counter, and time
switch functions.

Expansion is easy with Expansion I/O Units, allowing up to 44
I/O points. (See note 2.)

Economy-type and Communications-type CPU Units have been
added to series.

Improved Weekly Timers (See note 1.)
Increased timing accuracy with a monthly deviation of 15 s
max. Multiple-day operation and pulse output operation have
been added.

Select from two power supply options:
100 to 240 VAC or 12 to 24 VDC.

Note: 1. Not supported for ZEN-@C2@@-@-V2 models.
        2. When using CPU Units with 20 I/O points.

The information in this document applies to V2 Units.
Refer to page 28 for details on differences with previous
products.

Features

Easy and Simple Programming for Automatic Small-scale Control

Saves Space, Wiring, and Installation Steps                          Easy Programming

Versatile functionality in a compact body (70 mm wide 90 mm      The LCD screen comes with 8 operation buttons on the front panel to
  high).                                                             enable programming in ladder view format. The LCD screen also has
                                                                     a backlight, making it easier to see when the ZEN is used in dark
This single Unit easily provides relay, timer, counter, and time   locations.
  switch functions. Wiring work is greatly reduced because separate
  wiring is not required for devices such as timers and counters.    Note: Not supported for ZEN-@C2@@-@-V2 models.

                          90 mm
          70 mm

                                                                                                                                                     1
Flexible Expansion Enables Up to 44 I/O                                                         ZEN V2 Units
Points
                                                                      Support Software with Simulation Function
Up to three Expansion I/O Units can be connected if there are not
enough I/O points. Expansion I/O Units are only 35 mm wide.            Programs can be easily written, saved, and monitored by personal
                                                                        computer.
Note: CPU Units with 10 I/O points can be expanded to 34 I/O points.
        Expansion I/O Units cannot be connected to Economy-type       Programs can be simulated on the personal computer without
        CPU Units.                                                      connecting to the ZEN.

                                                                      Note: For notebook computers that do not have an RS-232C serial
                                                                              port, connect the computer to the ZEN by connecting an
                                                                              OMRON CS1W-CIF31 USB-Serial Conversion Cable to the
                                                                              ZEN-CIF01 Connecting Cable.

                                                                      Other Versatile Functions

                                                                      Use of a Memory Cassette makes it easy to copy and save
                                                                        programs.

                                                                      Equipped with two analog input channels (CPU Units with DC
                                                                        power supply only).

                                                                      Password function ensures security. (See note.)
                                                                      Multi-language display in six languages (English, Japanese,

                                                                        German, French, Spanish, Italian). (See note.)
                                                                      Display user-set messages or analog-converted values. (See note.)

                                                                      Note: Not supported for ZEN-@C2@@-@-V2 models.

Enhanced Features of V2 CPU Units

Improved Weekly Timer and Calendar Timer                              RS-485 Communications Model Added to
Functions                                                             Series

Note: Not supported for ZEN-@C2@@-@-V2 models.                        Production line conditions can be remotely monitored by monitoring
                                                                      the ZEN control status.
The time precision has been increased.
  Conventional model: 2-min difference/month
                                   
  -V2 models: 15-s difference/month (at 25C)

Multiple-day operation and pulse-output operation are now
  possible.

These improved functions are convenient for time-controlled
  applications such as lighting and air conditioning control.

                                                                              Production line

                                                                      Office

Lighting control  Air conditioning control                            More Precise Analog Input

                                                                      Conventional model: 10% FS  -V2 models: 1.5% FS
                                                                      DC power supply models are equipped with two analog inputs (0 to
                                                                      10 V). There are four analog comparators. The increased precision
                                                                      makes it even easier to use the Unit in simple control applications
                                                                      with voltage, current, temperature, and other analog values.

Economy-type Added to the Series                                      8-digit Counter, 150-Hz Counter

Economy-type CPU Units with a more affordable price have been       An 8-digit counter and 8-digit comparator have been added.
  added to the series, although Expansion I/O Units cannot be          The maximum count for DC power supply models is 150 Hz.
  added.

12 to 24 VDC Line Voltage Operation                                   Twin-timer Operation Added

Operation is now possible with 12 VDC.                                Twin-timer operation allows you to set ON and OFF times separately,
                                                                      greatly simplifying intermittent operation.

Expansion I/O Units have been reduced to
half-size (35 mm wide).

                                                                                                                                           2
                                                                                              ZEN V2 Units

Series Configuration                                                                         LED type

CPU Units

Power supply voltage: 100 to 240 VAC, 12 to 24 VDC, Output: Relay, transistor output

                      With LCD display, operation buttons, and calendar/clock function

           10 I/O points                                20 I/O points                         10 I/O points          20 I/O points

                                                                                              ZEN-10C2@                 ZEN-20C2@

                                                                                                                     This CPU Unit has no LCD,
                                                                                                                     operation buttons, or
                                                                                                                     calendar/clock function.

Standard LCD type Economy type   Communications type Standard LCD type  Economy type

ZEN-10C1@  ZEN-10C3@             ZEN-10C4@              ZEN-20C1@       ZEN-20C3@             (10 I/O points)

           Expansion I/O Units   RS-485 communications                  Expansion I/O Units
           cannot be connected.  type.                                  cannot be connected.

Expansion I/O Units              Power Supply Unit                                            Support Software

Only 35-mm wide.                 Same shape and design as ZEN.                                Allows easy programming and
4 input, 4 output points
                                 24 VDC, 30 W                                                 operation simulation.

                                                                                                                                                3
                                                                                            ZEN V2 Units

Model Number Structure

Model Number Legend

Note: This model number legend includes combinations that are not available.
        Please check List of Models on page 5 for availability.

CPU Units

ZEN-@C@@@-@-V2                                                      3. Input type
                                                                        A: AC input
          1 234 5                                                       D: DC input

1. Number of I/O points                                             4. Output type
    10: 6 inputs and 4 outputs (See note.)                              R: Relay
    20: 12 inputs and 8 outputs                                         T: Transistor

2. Type classifier                                                  5. Supply voltage
    1: Standard LCD type with display                                   A: AC power supply
    2: LED type without display                                         D: DC power supply
    3: Economy type with display
        (Expansion I/O Units cannot be connected.)
    4: Communications type with display

Note: The Communications-type CPU Unit has 6 inputs and 3 outputs.

Expansion I/O Units

ZEN-8E1@@                                                           3. Input type
                                                                        A: AC input
         1 234                                                          D: DC input

1. Number of I/O points                                             4. Output type
    8: 4 inputs and 4 outputs                                           R: Relay
                                                                        T: Transistor
2. Unit version classifier
    E1: Can connect to V2 CPU Units (See note.)

Note: Use a ZEN-8E@@/-4E@ to connect to pre-V1 and V1 CPU Units.

This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.

ZEN Operation Manual (Cat. No. Z211)
ZEN Communications Manual (Cat. No. Z212)
ZEN Support Software Operation Manual (Cat. No. Z184-E1-03)

The PDF versions of these manuals can be downloaded from the following website.
ZEN Website http://www.fa.omron.co.jp

                                                                                  4
                                                                                                                        ZEN V2 Units

Ordering Information

List of Models

CPU Units and Expansion I/O Units

Unit     Name           No. of LCD     Power supply  Inputs                            Outputs  Buttons,                Analog            Model
                          I/O display      voltage                                              calendar,                input
                                                                                                and clock                       ZEN-10C1AR-A-V2
                        points                                                                                                  ZEN-10C1DR-D-V2
                                                                                                                                ZEN-10C1DT-D-V2
CPU      Standard       10  Yes        100 to 240 VAC 6 100 to 240 VAC 4 Relays                 Yes                     No      ZEN-20C1AR-A-V2
                                                                                                                                ZEN-20C1DR-D-V2
Units    LCD type                      12 to 24 VDC  12 to 24 VDC                                                       Yes     ZEN-20C1DT-D-V2
                                                                                                                                ZEN-10C2AR-A-V2
                                                                            Transistors                                         ZEN-10C2DR-D-V2
                                                                                                                                ZEN-10C2DT-D-V2
                        20             100 to 240 VAC 12 100 to 240 VAC 8 Relays                                        No      ZEN-20C2AR-A-V2
                                                                                                                                ZEN-20C2DR-D-V2
                                       12 to 24 VDC  12 to 24 VDC                                                       Yes     ZEN-20C2DT-D-V2
                                                                                                                                ZEN-10C3AR-A-V2
                                                                            Transistors                                         ZEN-10C3DR-D-V2
                                                                                                                                ZEN-20C3AR-A-V2
         LED type 10        No         100 to 240 VAC 6 100 to 240 VAC 4 Relays                 No                      No      ZEN-20C3DR-D-V2

         without                       12 to 24 VDC  12 to 24 VDC                                                       Yes     ZEN-10C4AR-A-V2
         display                                                                                                                ZEN-10C4DR-D-V2
                                                                                                                                ZEN-KIT01-EV4
         (See note 1.)                                                      Transistors                                         ZEN-KIT02-EV4
                                                                                                                                ZEN-8E1AR
                        20             100 to 240 VAC 12 100 to 240V AC 8 Relays                                        No      (See notes 2, 3.)
                                                                                                                                ZEN-8E1DR
                                       12 to 24 VDC  12 to 24 VDC                                                       Yes     (See note 2.)
                                                                                                                                ZEN-8E1DT
                                                                            Transistors                                         (See note 2.)

         Economy 10         Yes        100 to 240 VAC 6 100 to 240 VAC 4 Relays                 Yes                     No

         type                          12 to 24 VDC  12 to 24 VDC                                                       Yes
         (Expansion

         I/O Units      20             100 to 240 VAC 12 100 to 240 VAC 8 Relays                                        No

         cannot be                     12 to 24 VDC  12 to 24 VDC                                                       Yes
         connected)

         Communica- 9                  100 to 240 VAC 6 100 to 240 VAC 3 Relays                                         No

         tions type                    12 to 24 VDC  12 to 24 VDC                                                       Yes

ZEN Kit                 Set containing CPU Unit (ZEN-10C1AR-A-V2), Connecting Cable, ZEN Support Software, and manual.

                        Set containing CPU Unit (ZEN-10C1DR-D-V2), Connecting Cable, ZEN Support Software, and manual.

Expansion I/O Units     8   ---        100 to 240 VAC 4 100 to 240 VAC 4 Relays                 ---

                                       12 to 24 VDC  12 to 24 VDC

                                       ---                                  Transistors

Note: 1. Programming is not possible using only the CPU in the LED-type CPU Unit. ZEN Support Software or a Memory Cassette is required.
        2. Cannot be connected to pre-V1 and V1 CPU Units.
        3. The ZEN-8E1AR cannot be connected to a CPU Unit with DC power supply.

Power Supply Unit

        Power ratings                Input voltage          Output voltage                    Output current                          Model
30 W                        100 to 240 VAC           24 VDC                            1.3 A                            ZEN-PA03024

Note: Refer to the ZEN-PA03024 Datasheet (Cat. No. L103) for detailed specifications.

                                                                                                                                                   5
                                                                                                             ZEN V2 Units

Accessories (Order Separately)

Name             Specifications                                              Remarks                                              Model

Memory Cassette EEPROM (for data                 Enables programs and parameter settings to be saved or copied to another ZEN-ME01
                          security and copying)  ZEN. (See note 1.)

                                                                             LCD-type CPU Unit with LED-type CPU Unit without
                                                                             display (See note 2.) display (See note 3.)

                                                 Transfer from ZEN to Supported         Not supported
                                                 Memory

                                                 Transfer from Memory Supported         Automatic transfer when
                                                 Cassette to ZEN                        power turned ON

                                                 Memory Cassette             Supported  Not supported
                                                 initialization

Connecting Cable 2 m RS-232C (9-pin D- ---                                                                                        ZEN-CIF01
                          sub connector)

Battery Unit     10 years min. Battery life Ladder programs and parameter settings are saved to the CPU Unit EEP-ROM ZEN-BAT01

                 (at 25C)                       but calendar, clock, and holding timer bits and holding timer/counter present

                                                 values are held by the capacitor. Therefore, if the power supply is interrupted

                                                 for 2 days or more (at 25C), this data will be reset. Use a Battery Unit for

                                                 systems where the power supply may be interrupted for long periods.

ZEN Support      Runs on Windows 95, 98, Specifically designed for the ZEN (CD-ROM).                                              ZEN-SOFT01-V4
Software         2000, ME, XP, NT 4.0,
                 Vista or 7.

Note: 1. Memory Cassettes created using a CPU Unit can be read to other CPU Units, regardless of which model is used. Restrictions, apply, however, to
             the functions that can be used, depending on the CPU Unit version combination. For details, refer to Memory Cassette and CPU Unit Combinations
             on page 31.

         2. Standard LCD-type, Economy-type, and Communications-type CPU Units (i.e., excluding ZEN-@C2@@-@-V2 models).
         3. LED-type CPU Unit without display (i.e., ZEN-@C2@@-@-V2 models).

Mounting Accessories (Order Separately)

           Name       Specifications                        Model
Mounting Track   50 cm (l) 7.3 mm (t)          PFP-50N
                 1 m (l) 7.3 mm (t)            PFP-100N
End Plate        1 m (l) 16 mm (t)             PFP-100N2
Spacer                                           PFP-M
                                                 PFP-S

System Configuration

              Power Supply Unit                                    CPU Unit             Expansion I/O Units

                                 Battery Unit

                                                                                                              Connecting Cable

                                                                                                              Memory Cassette
                                                                                                                                                     Support Software

Note: 1. Up to 3 Expansion I/O Units can be connected to any type of CPU Unit except for Economy-type CPU Units. Expansion I/O Units with AC Inputs,
             however, cannot be connected to CPU Units with DC Power Supplies.

         2. The Connecting Cable and Memory Cassette cannot be connected to the ZEN at the same time.
         3. Programs cannot be written to LED-type CPU Units (i.e., ZEN-@C2@@-@-V2 models) without the ZEN Support Software or a Memory Cassette.

                                                                                    6
                                                                                                ZEN V2 Units

Specifications

Ratings

Item                                                                 Specification

                           ZEN-@C@AR-A-V2/ZEN-8E1AR                                          ZEN-@C@D@-D-V2/ZEN-8E1D@

Rated supply voltage       100 to 240 VAC, 50/60 Hz                           12 to 24 VDC (DC ripple rate: 5% max.)

Operating voltage range    85 to 264 VAC                                      10.8 to 28.8 VDC

Power consumption          CPU Units without Expansion I/O Units              CPU Units without Expansion I/O Units
                            ZEN-10C1AR-A-V2/ZEN-10C2AR-A-V2/                  ZEN-10C@DR-D-V2

                             ZEN-10C3AR-A-V2                                    12/24 V DC: 3 W max.
                             100 V AC: 5 VA max.                                (ZEN-10C3DR-D-V2: 2.8 W max.)
                             240 V AC: 7 VA max.
                                                                               ZEN-10C@DT-D-V2
                            ZEN-10C4AR-A-V2                                    12/24 V DC: 2 W max.
                             100 V AC: 6 VA max.
                             240 V AC: 8 VA max.                               ZEN-20C@DR-D-V2
                                                                                12/24 V DC: 4 W max.
                            ZEN-20C@AR-A-V2
                             100 V AC: 7 VA max.                               ZEN-20C@DT-D-V2
                             240 V AC: 10 VA max.                               12/24 V DC: 2 W max.

                           CPU Units with three Expansion I/O Units           CPU Units with three Expansion I/O Units
                            ZEN-10C1AR-A-V2/ZEN-10C2AR-A-V2                   ZEN-10C@DR-D-V2

                             100 V AC: 6 VA max.                                12/24 V DC: 4 W max.
                             240 V AC: 8 VA max.
                                                                               ZEN-10C@DT-D-V2
                            ZEN-10C4AR-A-V2                                    12/24 V DC: 3 W max.
                             100 V AC: 7 VA max.
                             240 V AC: 9 VA max.                               ZEN-20C@DR-D-V2
                                                                                12/24 V DC: 5 W max.
                            ZEN-20C@AR-A-V2
                             100 V AC: 8 VA max.                               ZEN-20C@DT-D-V2
                             240 V AC: 11 VA max.                               12/24 V DC: 3 W max.

                           Expansion I/O Units                                Expansion I/O Units
                            ZEN-8E1AR                                        ZEN-8E1DR

                             100 V AC: 3 VA max.                                12/24 V DC: 2 W max.
                             240 V AC: 4 VA max.

Inrush current             ZEN-10C@AR-A-V2: 4.5 A max.                        ZEN-10C@D@-D-V2: 30 A max.

                           ZEN-20C@AR-A-V2: 4.5 A max.                        ZEN-20C@D@-D-V2: 30 A max.

                           ZEN-8E1AR:          4 A max.                       ZEN-8E1DR:        15 A max.

Ambient temperature        0 to 55C (-25 to 55C for ZEN-@C2@@-@-V2 models)

Ambient storage temperature -20 to 75C (-40 to 75C for ZEN-@C2@@-@-V2 models)

Ambient humidity           10% to 90% (with no condensation)

Ambient conditions         No corrosive gases

Mounting method            Surface mounting, DIN track mounting (standard (vertical) installation and horizontal installation) (See notes 1
                           and 2.)

Terminal block             Solid-line terminal block (use solid wire or fine-stranded wire)

Terminal screw tightening  0.565 to 0.6 Nm (5 to 5.3 in-lb)
torque

Degree of protection       IP20 (Mounted inside a control panel)

Note: 1. Can be mounted to 35-mm DIN Track.
        2. Standard (Vertical) installation Horizontal installation

                                                                                                                                             7
                                                                                                               ZEN V2 Units

Characteristics

            Item                                                              Specification

Control method             Stored program control

I/O control method         Cyclic scan

Programming language       Ladder diagram

Program capacity           96 lines (3 input conditions and 1 output per line)

Max. No. of control I/O points 44 points (See note 1.)
                                             CPU Units with 20 I/O points: 12 inputs and 8 outputs
                                             Expansion I/O Units: 4 inputs and 4 outputs each, up to 3 Units.

LCD display (See note 2.)  12 characters 4 lines, with backlight

Operation buttons (See note 2.) 8 (4 cursor buttons and 4 operation buttons)

User program backup        Internal EEPROM, Memory Cassette (optional)

Power interruption hold    Internal holding bit status, holding timer/counter present values, calendar and clock (year, month, day of month,

                           day of week, time)

                            Super capacitor backup time:2 days min. (25C)
                                                        10 years min. (25C)
                            Life of optional battery:

Calendar and clock function Accuracy: 15 s/month (at 25C)
(See note 2.)

Timer accuracy             0.01 s unit: -0.05% -10 ms max. (rate for set value)
                           min/s unit: -0.05% -1 s max. (rate for set value)
                           h/min unit: -0.05% -1 min max. (rate for set value)

Maximum counting speed     150 Hz: 8-Digit counter (F) set to high-speed operations (CPU Units with DC power supplies only)
                           (The counting speed may be less than 150 Hz depending on the cycle time of the program. See page 21.)

Insulation resistance      20 M (at 500 VDC) min.:
                           Between power supply terminals and all output terminals.
                           Between terminals of different output circuits.
                           Between all terminals of CPU Unit and all terminals of Expansion I/O Unit.

Insulation                  Reinforced insulation
                             Between power supply or input terminals and output terminals.
                             Between terminals of different output circuits.
                             Between all terminals of CPU Unit and all terminals of Expansion I/O Unit.

                            No separation
                             Between power supply and input terminals of the same unit.
                             Between power supply terminals of CPU Unit and computer connector,
                             Battery Unit connector, or all Expansion Unit connectors (all interfaces are live parts).

Dielectric strength        2,300 VAC, 50/60 Hz for 1 min (leakage current 1 mA max.):
                           Between power supply terminals and all output terminals.
                           Between terminals of different output circuit.
                           Between all terminals of CPU Unit and all terminals of Expansion I/O Unit.

Vibration resistance       Conforms to IEC60068-2-6, 5 to 9 Hz with 3.5-mm single amplitude, 9 to 150 Hz acceleration 9.8 m/s2,
                           10 sweeps each in X, Y, and Z directions (1 octave/min)

Shock resistance           Conforms to IEC60068-2-27, 147 m/s2, 3 times each in X, Y, and Z directions.

Weight                     CPU Unit with 10 I/O points: Approx. 300 g max.

                           CPU Unit with 20 I/O points: Approx. 350 g max.

                           Expansion I/O Unit:          Approx. 120 g max.

Note: 1. Up to 34 points for CPU Units with 10 I/O points. With Communications-type CPU Units, however, the CPU Unit has 6 inputs and 3 outputs, for a maximum
              of 33 I/O points.

         2. Not provided for LED-type CPU Unit without display (i.e., ZEN-@C2@@-@-V2 models).

Communications Specifications (Communications-type CPU Units)

                   Item                                                              ZEN-10C4@R-@-V2
Communications             RS-485 (two-wire, half duplex)
Synchronization method     Start-stop synchronization
Baud rate                  4800, 9600, or 19200 bps
Transmission code          ASCII
Data bit length            7 or 8 bits
Stop bit length            1 or 2 bits
Error detection            Vertical parity (none, even, odd), Block check character (BCC)
Flow control               None
Interface                  RS-485
Retry function             None
Node number                0 to 99 (default: 1), XX (broadcasting)

                                                                                                                                                                8
                                                                                                  ZEN V2 Units

Approved Standards

                 Item                                            Specification
Safety standards
                       cULus: UL508/CSA C22.2 No.142 Class I Div2
EMC                    Conforms to EN/IEC 61131-2 clause 11, excluding 11.7.2.2 (Overvoltage category 2 and Pollution degree II
(See note.)            conforms to IEC 60664-1)

                       Radiation Field Emission                  CISPR11        Class A, Group 1
                       Noise Terminal Voltage Emission           CISPR11        Class A, Group 1

                       Electrostatic Discharge Immunity          IEC61000-4-2 In air: 8 kV, In contact: 6 kV

                       Electromagnetic Field Immunity            IEC61000-4-3 10 V/m

                       Electrical Fast Transient/Burst Immunity  IEC61000-4-4 Power line

                                                                                             AC I/O: 2 kV

                                                                                             DC I/O: 1 kV

                       Surge Immunity                            IEC61000-4-5 Normal Noise

                                                                                             AC power supply, AC I/O: 1 kV

                                                                                             DC power supply, DC I/O: 0.5 kV

                                                                                Common Noise

                                                                                             AC power supply, AC I/O: 2 kV

                                                                                             DC power supply: 1 kV

                                                                                             DC I/O: 0.5 kV

                       Immunity to Conducted Disturbances Induced by Radio-frequency Fields

                                                                 IEC61000-4-6 3 V

                       Momentary Power Interruption Immunity     IEC61131-2     CPU Units with AC Power Supplies:

                                                                                10 ms max.

                                                                                CPU Units with DC Power Supplies:

                                                                                2 ms max. (level: PS1)

Note: EMC conforms to EN 61131-2 clause 8 except in the following cases.

         When Expansion I/O Units with DC inputs are connected to a CPU Unit with an AC power supply, the burst immunity between power
          supplies will be 1 kv.

         When the signal wire for transistor outputs exceeds 10 m, the surge immunity of DC output signal lines will not conform.

Input Specifications

CPU Units

AC Inputs (Not Isolated)

                 Item                            Specifications                              Circuit drawing
Input voltage          100 to 240 VAC +10%, -15%, 50/60 Hz
Input impedance        680 k                                                                 IN 330 k 300 k
Input current          0.15 mA/100 VAC, 0.35 mA/240 VAC
ON voltage             80 VAC min.                                                           IN                                      Internal
OFF voltage            25 VAC max.                                                                                                   circuit
ON response time       50 ms or 70 ms at 100 VAC (See note.)                                                 51 k
OFF response time      100 ms or 120 ms at 240 VAC (See note.)
                                                                             100 to 240 VAC

                                                                                             N
                                                                                             L

Note: Can be selected using the filter settings.

DC Inputs: I0 to I3 for Units with 10 I/O points, I0 to I9 for Units with 20 I/O Points (Not Isolated)

                 Item                            Specifications                              Circuit drawing
Input voltage          12 to 24 VDC +20%, -10%
Input impedance        5.3 k                                                 12 to 24 VDC    IN 5.1 k 1.8 k
Input current          4.5 mA (typ.)/24 VDC                                                  IN
ON voltage             8 VDC min.
OFF voltage            5 VDC max.                                                                                                    Internal
ON response time       15 ms or 50 ms (See note.)                                                                                    circuit
OFF response time
                                                                                             COM

Note: Can be selected using the input filter settings, except when I0 is being used for an 8-digit counter with a high-speed input.

                                                                                                                                               9
                                                                                                               ZEN V2 Units

DC Inputs: I4 and I5 for Units with 10 I/O points, Ia and Ib for Units with 20 I/O Points
(Not Isolated)

        Item                                            Specifications                            Circuit drawing

DC Inputs Input voltage    12 to 24 VDC +20%, -10%

        Input impedance    PNP:        5.5 k/14 VDC min.
                           NPN:
                                       100 k/14 VDC max.
                                       5.2 k

        Input current      PNP:        4.3 mA (typ.)/24 VDC                                                                        150 k
                           NPN:        4.6 mA (typ.)/24 VDC
                                                                                                           IN                      27 k
                                                                                          +                                        6.2 k
        ON voltage         8 VDC min.                                             Analog voltage                      47 k
                                                                                     output device
        OFF voltage        3 VDC max.
                                                                                                                                                     Internal
        ON response time 15 ms or 50 ms (See note.)                                                                                                     circuit220 k

        OFF response time

Analog  Input range        0 to 10 V                                              -               COM
Inputs                     100 k min.
        External input                                                                    12 to 24 VDC                                  47 k
        impedance                                                                                                           5.6 k

        Resolution         0.1 V (1/100 FS)

        Accuracy           1.5% FS (at ambient operating temperature within
                           rated range)

        AD conversion data 0 to 10.5 V (in increments of 0.1 V)

Note: Can be selected using the input filter settings.

Expansion I/O Units

AC Inputs (Not Isolated)

                 Item                              Specifications                                 Circuit drawing
Input voltage            100 to 240 VAC +10%, -15%, 50/60 Hz
Input impedance          680 k                                                                IN                                   Internal
Input current            0.15 mA/100 VAC, 0.35 mA/240 VAC                                          330 k 300 k                        circuit
ON voltage               80 VAC min.
OFF voltage              25 VAC max.                                                 100 to   IN
ON response time         50 ms or 70 ms at 100 VAC (See note.)                       240 VAC                          51 k
Off response time        100 ms or 120 ms at 240 VAC (See note.)
                                                                                              N
                                                                                               L

Note: Can be selected using the input filter settings.

DC Inputs (ZEN-8E1DR: Not Isolated, ZEN-8E1DT: Photocoupler Isolated)

                 Item                              Specifications                                 Circuit drawing
Input voltage            12 to 24 VDC +20%, -10%
Input impedance          6.5 k                                                                IN
Input current            3.7 mA (typ.)/24 VDC
ON voltage               8 VDC min.                                                           IN               6.2 k        1.8 k
OFF voltage              5 VDC max.
ON response time         15 ms or 50 ms (See note 1.)                             12 to       (See                                           Internal
OFF response time                                                                 24 VDC          note 2.)                                     circuit

                                                                                          COM

Note: 1. Can be selected using the input filter settings.
        2. The ZEN-8E1DT has no +/- terminals. There is no need to supply power.

                                                                                                                                                                 10
                                                                                                                                        ZEN V2 Units

Output Specifications (CPU Units and Expansion I/O Units)

Units with Relay Outputs

            Item                         Specifications                                                                              Circuit drawing

Maximum switching capacity 250 VAC/8 A (resistive load: cos = 1)

                        24 VDC/5 A (resistive load)

                        Use the following values for the total of all outputs.

                        CPU Units with 10 I/O points: 20 A max.                                                                         Q0 to Q3/OUT0 to OUT3
                                                                                                                                             L
                        (15 A max. for Communications-type CPU Units)

                        CPU Units with 20 I/O points: 40 A max.

                        Expansion I/O Units:                                    20 A max.

Minimum switching capacity 5 VDC/10 mA (resistive load)                                                               Internal          Q4/Q6
                                           (failure level: P, reference value)                                           circuit               L

Relay life  Electrical  Resistive load: 50,000 times (cos = 1)                                                                          COM                                      Models with
                        Inductive load: 50,000 times (cos = 0.4)                                                                                                                 20 I/O points
                                                                                                                                               L                                 only
            Mechanical 10 million times                                                                                                 Q5/Q7

ON response time        15 ms max.

OFF response time       5 ms max.

The life under the worst conditions, of the output contacts used in                        Life-test Curve (Reference Value)
ZEN relay outputs is given in the above table. Guidelines for the
normal life of the relays are shown in the diagram on the right.                           Usage: 360 times/hour

Note: The switching capacity, switching durability, and applicable                         Life ( 103)  1,000                       250-VAC resistive load
        load area when actually using the relay depend on the type of                                      500                       24-VDC resistive load/
        load, environmental conditions, and switching conditions.                                          300                       250-VAC inductive load
        Therefore, be sure to confirm these conditions for the actual                                                                24-VDC inductive load
        machine before use.                                                                                                          (t = 7 ms)

                                                                                                         100

                                                                                                         50
                                                                                                         30

                                                                                                         10

                                                                                                                0  2              4  6            8                              10

                                                                                                                                        Contact current (A)

Units with Transistor Outputs

            Item                         Specifications                                                                           Circuit drawing

Maximum switching capacity 24 VDC +20%, 500 mA                                                           Each circuit is configured with an independent common
                                                                                                         circuit

Leakage current         0.1 mA max.                                                                                          390        Q0 to Q3/OUT0 to OUT3
                                                                                                                                            L 28.8 VDC max.

                                                                                                                                                                              L
                                                                                                                                     1 k

Residual voltage        1.5 V max.

                                                                                                                   Internal             COM                                      28.8 VDC max.
                                                                                                                   circuit                     +

ON response time        1 ms max.                                                                                                             L                                  Models with
                                                                                                                                                                                 20 I/O points
                                                                                                                                        Q4/Q6                                    only

OFF response time       1 ms max.

                                                                                                                                              L

                                                                                                                                        Q5/Q7

                                                                                                                                                                                                11
                                                                                                                      ZEN V2 Units

Connections

Input Connections

Units with AC Power Supply

Note: 1. Supply power to both the CPU Unit and Expansion I/O Units from the same power supply and turn them ON and OFF at the same time.
        2. The input circuit commons for CPU Units with AC power supply are internally connected to the N terminal of the power supply circuit.
            Wire the L terminal to the power supply of the input device.

        3. The input circuit commons for Expansion I/O Units with AC power supply are internally connected to the N terminal of the power supply
            circuit. Wire the L terminal to the power supply of the input device.

CPU Units with 10 I/O Points and Expansion I/O Units

100 to 240 VAC, 50/60 Hz                               Input device
             LN

   Circuit
   protector

           LN     NC I0 I1 I2 I3 I4 I5                 L N IN0 IN1 IN2 IN3

           CPU Unit with 10 I/O points                 ZEN-8E1AR Expansion
                                                       I/O Unit (AC input type)

CPU Units with 20 I/O Points and Expansion I/O Units

100 to 240 VAC, 50/60 Hz                                                         Input device
            LN

  Circuit
  protector

           LN     NC I0 I1 I2 I3 I4 I5  NC I6 I7 I8 I9 Ia Ib                     L N IN0 IN1 IN2 IN3

                          CPU Unit with 20 I/O points                            ZEN-8E1AR
                                                                                 Expansion I/O Unit
                                                                                 (AC input type)

Connecting Expansion I/O Units with DC Inputs

           100 to 240 VAC, 50/60 Hz                    DC power supply

L              N

Circuit
protector

                                                                                 Input                        Input
                                                                                 device                       device

           LN     NC I0 I1 I2 I3 I4 I5                 COM IN0 IN1 IN2 IN3               COM IN0 IN1 IN2 IN3

CPU Unit with 10 I/O points                            ZEN-8E1DR                 ZEN-8E1DT
                                                       Expansion I/O Unit        Expansion I/O Unit
                                                       (DC inputs and            (DC inputs and
                                                       relay outputs)            transistor outputs)

Note: When connecting Expansion I/O Units with DC inputs to a CPU Unit with an AC power supply, the burst noise immunity will be 1 kV
        (IEC 61000-4-4).

                                                                                                                                                  12
                                                                             ZEN V2 Units

Units with DC Power Supply

Note: 1. Be sure to connect the COM terminal before turning ON the power supply. If the COM terminal is disconnected, or if the wiring is changed
            after turning ON the power supply, a malfunction may occur.

        2. Apply the power supply voltage through a relay or switch in such a way that the voltage reaches the rated value within 4 s. If the voltage
            is applied gradually, the power may not be reset or unstable output operations may result.

CPU Units with 10 I/O Points

For Connections to Negative (-) Common (PNP Connection)

             12 to 24 VDC

                                                                   Input device

                                     COM

                   CPU Unit with 10 I/O points

For Connecting Analog Input Devices to Input Terminals I4 and I5

           12 to 24 VDC

                                    COM I0 I1 I2 I3 I4 I5

                 CPU Unit with 10 I/O points

Note: When connecting an analog input device, always connect the negative side to the COM terminal.

For Connections to Positive (+) Common (NPN Connection)

           12 to 24 VDC

+-                                       Input
                                         device

    COM I0 I1 I2 I3 I4 I5

                   CPU Unit with 10 I/O points

Note: When connected to the positive (+) common, I4 and I5 cannot be used as analog inputs.

                                                                                                     13
                                                                                                                                 ZEN V2 Units

CPU Units with 20 I/O Points

For Connections to a Negative Common (PNP Connection)

         12 to 24 VDC

                                                                                                           Input device

                                    COM I0 I1 I2 I3 I4 I5 NC I6 I7 I8 I9 Ia Ib

                                       CPU Unit with 20 I/O points

For Connecting Analog Input Devices to Input Terminals Ia and Ib

        12 to 24 VDC

                                    COM I 0 I 1 I 2 I 3 I4 I5 NC I6 I 7 I 8 I 9 I a Ib

                                        CPU Unit with 20 I/O points

Note: When connecting an analog input device, always connect the negative side to the COM terminal.

For Connections to Positive (+) Common (NPN Connection)

           12 to 24 VDC

+-  COM I0 I1 I2 I3 I4 I5                                         Input device
                             NC I6 I7 I8 I9 Ia Ib

                                        CPU Units with 20 I/O points

Note: When connected to the positive (+) common, Ia and Ib cannot be used as analog inputs.

Expansion I/O Units

Note: 1. Supply power to both the CPU Unit and Expansion I/O Units from the same power supply and turn them ON and OFF at the same time.
        2. ZEN-8E1AR Expansion I/O Units with AC inputs cannot be connected to CPU Units with DC power supply.
        3. The input circuit commons for ZEN-8E1DR Expansion I/O Units with relay outputs are each internally connected to one side of the power
            supply circuit (COM terminal).
        4. ZEN-8E1DT Expansion I/O Units with transistor outputs do not need to be connected to a power supply.

For Connections to Negative (-) Common

           12 to 24 VDC

                                                       Input                                                             Input
                                                       device                                                            device

+-  COM I0 I1 I2 I3 I4 I5    COM IN0 IN1 IN2 IN3              NC COM IN0 IN1 IN2 IN3

CPU Unit with 10 I/O points  ZEN-8E1DR                 ZEN-8E1DT
                             Expansion I/O Unit        Expansion I/O Unit
                             (DC input, relay output)  (DC input, transistor output)

For Connections to Positive (+) Common

           12 to 24 VDC

                                                       Input                                                             Input
                                                       device                                                            device

+-  COM I0 I1 I2 I3 I4 I5    COM IN0 IN1 IN2 IN3              NC COM IN0 IN1 IN2 IN3

CPU Unit with 10 I/O points  ZEN-8E1DR                 ZEN-8E1DT
                             Expansion I/O Unit        Expansion I/O Unit
                             (DC input, relay output)  (DC input, transistor output)

                                                                                                                                                  14
                                                                                                                                                                       ZEN V2 Units

Output Connections

Units with Relay Outputs

All four relay output circuits in both CPU Units with 10 I/O points and Expansion I/O Units have independent contacts. CPU Units with 20 I/O points
have 4 independent contacts (Q0 to Q3) and the remaining four (Q4 to Q7) have 2 points/common. There are no restrictions for polarity.

Standard LCD-type CPU Units, LED-type CPU Units, and Economy-type CPU Units

        CPU Unit with 10 I/O Points                                                CPU Unit with 20 I/O Points

Q0      Q1        Q2                    Q3                          Q0   Q1   Q2   Q3   Q4      Q5 Q6                         Q7

     Load                                                                Load
                   Load                                                                Load
                                  Load                                                                Load
                                                Load                                                                 Load
                                                                                                                                 Load
                                                                                                                                            Load
                                                                                                                                                       Load
                                                                                                                                                                 Load

Communications-type CPU Units                                                      Expansion I/O Units

               Communications-type CPU Unit                                                               Expansion I/O Unit

Q0      Q1        Q2                    B (+) A (-)                                         OUT OUT
                                                                                                2               3

     Load                               RS-485                                              OUT OUT
                   Load                                                                      01
                                  Load

                                                                                        Load
                                                                                                       Load
                                                                                                                          Load
                                                                                                                                          Load

Units with Transistor Outputs

For CPU Units with 10 I/O points and Expansion I/O Units, all 4 outputs in the transistor output circuits have independent circuits. The terminals of
output have polarity given on the terminal block, but no problem will result from reversing the connection positions of the power supply and load.

For CPU Units with 20 I/O points, outputs Q0 to Q3 in the transistor output circuits have independent circuits and outputs Q4 to Q7 have 2 points
per common. The terminals of output Q0 to Q3 have polarity given on the terminal block, but no problem will result from reversing the connection
positions of the power supply and load.

Note: Do not exceed a cable length of 10 m when connecting transistor outputs.

Standard LCD-type CPU Units and LED-type CPU Units without Display

        CPU Unit with 10 I/O Points                                                CPU Unit with 20 I/O Points

+-      +-        +-                    +-                          +-   +-   +-   +-   -+ -                    -+ -
Q0      Q1        Q2                    Q3                          Q0   Q1   Q2   Q3   Q4 Q5                   Q6 Q7

                                                      Q0 to Q3                                                                                                         Q0 to Q3
    Load
                  Load
                                 Load
                                                Load
                                                                Load
                                                                                             Load
                                                                                                            Load
                                                                                                                           Load
                                                                                                                                          Load
                                                                                                                                                       Load
                                                                                                                                                                  Load
                                                                                                                                                                            Load
                                                                                                                                                                                       Load
                                                                                                                                                                                                         Load

Expansion I/O Units

               Expansion I/O Unit

     +      -+        -
     OUT2         OUT3

     +      -  +      -                               OUT0 to OUT3
      OUT0        OUT1

Load
               Load
                              Load
                                             Load
                                                            Load

                                                                                                                                                                                                               15
                                                                                                                                                          ZEN V2 Units

Nomenclature

Standard LCD-type, Economy-type, and Communications-type CPU
  Units (Except for ZEN-@C2@@-@-V2 Models)

CPU Units with 10 I/O Points

Left side                                   Front                                                               Right side

                                     Power supply Input
                                       terminals terminals

                            Display                                Operation                                                                    Display Screen
                            screen                                 buttons

                                                                    Output terminals                            Expansion Unit connector        RUN ERR
                                                                    (See note 1.)                               cover (See note 2.)
Battery Unit connector                                                                                          Do not remove this cover until  Icon Meanings
(Remove the seal to                                ZEN Support Software connector                               connecting an Expansion Unit.
connect the Battery Unit.)                         (also used for Memory Cassette.)

CPU Units with 20 I/O Points                                                                                                                        Icon              Meaning
                                                                                                                                                RUN
Left side                                          Front                                                        Right side                      ERR       Display while in RUN mode.
                                                                                                                                                
                                     Power supply    Input terminals                                                                                      Indicates an error.
                                       terminals                                                                                                
                                                                                             I6 I7 I8 I9 Ia Ib                                            Displayed when there is a
                                                                                                                                                          higher-level menu or ladder
                                     20C1AR-A-V2                                                                                                          program line than the one
                                                                                                                                                          currently displayed.
                            Display                         Operation
                            screen                          buttons                                                                                       Displayed when there is a
                                                                                                                                                          lower-level menu or ladder
                                                                                                                                                          program line than the one
                                                                                                                                                          currently displayed.

                                                                                                                                                          Displayed when a password
                                                                                                                                                          had been set.

                                                   Q4       Q5 Q6  Q7

Battery Unit connector                     Output terminals                                                     Expansion Unit connector
(Remove the seal to                                                                                             cover (See note 2.)
connect the Battery Unit.)           ZEN Support Software connector                                             Do not remove this cover until
                                     (also used for Memory Cassette.)                                           connecting an Expansion Unit.

Note: 1. With Communications-type CPU Units, the Q3 terminal is used as the RS-485 terminal. For details, refer to Output Connections on page
            15.

        2. Economy-type CPU Units are not provided with an Expansion Unit connector. Do not remove the cover.

                                                                                                                                                                                       16
                                                                                                                            ZEN V2 Units

Operation Buttons                                       Operation Button Names and Operations

DEL Button ALT Button                                   Button                                                    Function
                                                                                        Writing ladder program
                                               Cursor                Menus                                                   Setting parameters     Button input
                                               Buttons                            Deletes inputs, outputs, connection       ---                            bit
                                                        DEL     ---               lines, and blank lines.
                                                                                                                                                   (See page 24.)

                                                                                                                                                   B6 ON

                                                        ALT     ---                Switches between normally open ---                             B7 ON
                                                        Up
                                                        Down                      and normally closed conditions.

                                                                                  Changes to connection line write

ESC Button OK Button                                                              mode.

                                                                                  Inserts a line.

                                                                Moves the cursor Moves the cursor up and down.             Moves the cursor up B5 ON
                                                                up and down. Selects bit types and functions.               and down.

                                                                                                                            Changes numerals
                                                                                                                              and parameters.

                                                                                                                                                           B2 ON

                                                        Left    ---               Moves the cursor right and left.          Moves the cursor right B3 ON
                                                                                                                            and left.

                                                        Right                                                                                      B4 ON

                                                        ESC     Returns to the Cancels the setting and returns to           Cancels the setting    B0 ON
                                                        OK      previous screen. the previous operation.                    and returns to the     B1 ON
                                                                                                                            previous operation.
                                                                Selects the       Confirms the setting.
                                                                                                                            Confirms the setting.

                                                                menu item at the

                                                                cursor position.

                                                                                                                                                                   17
                                                                                                                                                               ZEN V2 Units

LED-type CPU Units without Display (ZEN-@C2@@-@-V2)

CPU Units with 10 I/O Points

Left side                                    Front                                                       Right side

                                            Power supply Input
                                              terminals terminals

                            LED indicators

                                                                                                                                         LED Indicators

Battery Unit connector                                         Output terminals                          Expansion Unit connector           Name   LED               Status
(Remove the seal to connect                                                                              cover                           POWER    Green Lit
the Battery Unit.)                           ZEN Support Software connector                              Do not remove this cover until  RUN                           Power is ON.
                                             (also used for Memory Cassette.)                            connecting an Expansion Unit.                      Not lit
                                                                                                                                         ERROR    Green Lit            Power is OFF.
CPU Units with 20 I/O Points
                                                                                                                                                            Not lit    Operating
Left side                                    Front                                                       Right side                                                    (RUN)
                                                                                                                                                  Red Lit
                             Power supply      Input terminals                                                                                                         Stopped
                               terminals                                                                                                                    Not lit    (STOP)
                                                                                      I6 I7 I8 I9 Ia Ib
                                                                                                                                                                       Error
                                                                                                                                                                       occurred.

                                                                                                                                                                       Normal

                             20C2AR-A-V2

                                                           Q4  Q5 Q6  Q7

                                            Output terminals

Battery Unit connector                      ZEN Support Software connector                               Expansion Unit connector cover
(Remove the seal to                         (also used for Memory Cassette.)                             Do not remove this cover until
connect the Battery Unit.)                                                                               connecting an Expansion I/O
                                                                                                         Unit.
                             LED indicators

Expansion I/O Units (ZEN-8E1@@)

Left side                                      Front                                                     Right side

                             Power supply terminals Input terminals

                                                                      Output terminals

                             Expansion I/O Unit connector                     Expansion I/O Unit connector cover
                                                                              Do not remove this cover until connecting
                                                                              an Expansion I/O Unit.

Precaution when Using Expansion I/O Units:                                                                                               Phillips screwdriver        Flat-blade screwdriver

Up to three Expansion I/O Units can be connected.

When removing the Expansion Unit connector cover from the side of the CPU Unit, use a
Phillips screwdriver to remove the cover screw, and then insert a flat-blade screw driver in
the cover gap to remove the cover, as shown at the right.

                                                                                                                                                                                             18
                                                                                                                              ZEN V2 Units

Operation

Bits

           Name          Symbol              Bit           No. of                                     Operation                                  Details
Input bits                                                                                                                                         (See
Expansion input bits                     addresses points
Output bits                                                                                                                                      note 1.)
Expansion output bits
Work bits                I               I0 to Ib          12 Reflect the ON/OFF status of the input devices connected to the input
Holding bits
Timers                                   (See note 2.)             terminals on the CPU Unit.                                                    ---

Holding timers           X               X0 to Xb 12 Reflect the ON/OFF status of the input devices connected to the input
Counters
                                                                   terminals on the Expansion I/O Units.

                         Q               Q0 to Q7 8                The ON/OFF status of these output bits is used to control the output devices

                                         (See note 2.)             connected to the output terminals on the CPU Unit.

                         Y               Y0 to Yb 12 The ON/OFF status of these output bits is used to control the output devices

                                                                   connected to the output terminals on the Expansion I/O Units.                 1

                         M               M0 to Mf 16 Work bits can be used only within the ZEN program. I/Os for external devices

                                                                   cannot be made (i.e., all I/O is internal).

                         H               H0 to Hf          16 Used the same as the work bits. However, if the power to the ZEN is turned

                                                                   OFF, these bits also maintain the previous ON/OFF status.

                         T               T0 to Tf          16 X: ON-delay timer Functions are                    Time units can be selected

                                                                   : OFF-delay timer       selected from the     from the following:
                                                                                           screen when           0.01-s unit: 0.01 to 99.99 s

                                                                   O: One-shot pulse parameter settings min/s unit: 00 min 01 s to               2
                                                                      timer                are made.
                                                                                                                       99 min 59 s

                                                                   F: Flashing pulse                             h/s unit: 00 h 01 min to
                                                                       timer                                                     99 h 59 min

                                                                   W: Twin timer

                         #               #0 to #7          8       3 Hold the present value being counted even if the trigger input or power supply

                                                                   is turned OFF and continue timing when the trigger input or power is restored.

                         C               C0 to Cf          16 Reversible 4-digit counters that can be incremented and decremented.               4

8-digit counter          F               F0                1       Reversible 8-digit counters that can be incremented and decremented.

                                                                   5 CPU Units with DC power supply support a high-speed counter up to 150 Hz.

                                                                   For details, refer to 8-digit Counter Operation on page 21.

Weekly timers            @               @0 to @f 16               Turn ON and OFF during specified times on specified days.                     6

(See note 3.)

Calendar timers          *               *0 to *f          16      Turn ON and OFF between specified dates.                                      7

(See note 3.)

Display bits             D               D0 to Df          16      Display user-specified messages, times, timer/counter present values, or      8
                                                                   analog-converted values.
(See note 3.)

Analog comparator bits A                 A0 to A3 4                Used as program input conditions to output analog comparator comparison       9
                                                                   results. These bits can be used only for CPU Units with DC power supply.

Timer/counter            P               P0 to Pf          16      10 Compare the present values of timers (T), holding timers (#), and counters

comparator bits                                                    (C). Comparison can be made between the same two counters or timers, or
                                                                   with constants.

8-digit counter          G               G0 to G3 4                Used to compare the present values of 8-digit counters (F) and output the     11
                                         B0 to B7 8                comparison results.
comparator bits

Button input bits        B                                         Used as program input conditions and turn ON when operation buttons are       12
                                                                   pressed in RUN Mode.
(See note 3.)

Note: 1. For details, refer to the indicated item numbers on the following pages.
        2. CPU Units with 10 I/O points have 6 input bits (I0 to I5) and 4 output bits (Q0 to Q3). Output bit Q3 of Communications-type CPU Units,
            however, cannot be output externally. It can be used as a work bit.
        3. These input bits are not supported by LED-type CPU Units without display.

1. Additional Bit Output Functions

         [: Normal                                            S: Set  Set/Reset operation                                         A: Alternate
                                                                                                      R: Reset
    I0                                                                                                                        I3
                                    [Q0                I1                                  I2                                                                 AQ2

                                                                      SQ1                                       RQ1

I0                                                 I1                                  I2                              I3

Q0                                           Q1                                       Q1                                     Q2

Q0 will turn ON or OFF depending Q1 will stay ON once the execution Q1 is forced OFF when the                          Q2 alternates between turning ON
                                                                                                                       and OFF when the execution
on the ON/OFF status of the              condition I1 has turned ON once. A execution condition I2 is turned           condition I3 turns ON.

execution condition I0.                  reset is used to turn Q1 OFF.            ON.

                                                                                                                                                                   19
                                                           ZEN V2 Units

2. Using Timers and Holding Timers  Turns ON after set delay after the trigger input turns ON.
                                    Basic Operation
X: ON-delay timer
                                    Trigger input
               Trigger input
                Reset input                        Timing
                      Setting
                                                                    Output
             Present value
                              0     Main Applications
                                    When delayed operation or a time lag is required.
                    Timer bit
                                    Stays ON while the trigger input is ON and turns OFF after a set delay
: OFF-delay timer                   after the trigger input has turned OFF.
                                    Basic Operation
              Trigger input
                Reset input                                 Trigger input
                      Setting
                                                                                                     Timing
             Present value
                              0                                     Output

                    Timer bit       Main Applications
                                    Useful for OFF delay circuits for lights or fans
O: One-shot pulse timer
                                    Turns ON for a set period after the trigger input turns ON and regardless
              Trigger input         of how long the trigger input remains ON.
                Reset input         Basic Operation
                      Setting
                                                            Trigger input
            Present value
                              0                                                               Timing

                   Timer bit                                        Output

F: Flashing pulse timer             Main Applications
                                    Useful for set operations where operation is always required during a
              Trigger input         regular period only.
                Reset input
                      Setting       Repeatedly turns ON and OFF in a set cycle while the trigger input is ON.
                                    Basic Operation
            Present value
                              0                           Trigger input
                                                                                      Timing Timing Timing Timing
                   Timer bit
                                                                  Output
W: Twin timer
                                    Main Applications
              Trigger input         Useful for flashing emergency lights or sounding buzzers as the output
                Reset input         for an alarm circuit.
                    ON-time
                   OFF-time         Repeatedly turns ON and OFF in a set cycle while the trigger input is ON.
                                    Independent ON- and OFF-time settings are possible.
            Present value
                              0     Basic Operation

                   Timer bit        Trigger input

3. Using Holding Timers                              Timing Timing Timing Timing
                                                   (OFF-time) (ON-time) (OFF-time) (ON-time)
X: ON-delay timer
                                                                 Output
              Trigger input
                Reset input         Main Applications
                      Setting       Useful for intermittent (ON/OFF) operation, such as that used for fans.

            Present value           Turns ON after set delay after the trigger input turns ON. The present
                                0   value is held while the trigger input is OFF.

                   Timer bit        Main Applications

                                    To continue operation after momentary power loss or power interruptions.
                                    Also can be used when delayed operation or a time lag is required.

                                                                                                                   20
4. Counter Operation                                                                                          ZEN V2 Units

Counter direction                                                                The counter bit turns ON when the counter value (present value)
specification input                                                              reaches the set value (present value  set value). The counter returns to
                                                                                 0 and the counter bit turns OFF when the reset input turns ON. Count
     Counter input                                                               inputs are not accepted while the reset input is turned ON. The counter
                                                                                 present value and counter bit (ON/OFF) are held even if the operating
        Reset input                                                              mode is changed or the power supply is interrupted.

     Set value                                                                      Operation
Present value
                                                                                                      The counter bit turns ON when the counter value (present value)
           0000                                                                                       reaches the set value (present value  set value). The counter
   Counter bit                                                                                        returns to 0 and the counter bit turns OFF when the reset input
                                                                                                      turns ON. Count inputs are not accepted while the reset input is
5. 8-digit Counter Operation                                                                          turned ON. The counter present value and counter bit (ON/OFF)
                                                                                                      are held even if the operating mode is changed or the power supply
Count speed                                                                                           is interrupted.
                                                                                                      High-speed Operation
H High               Counter direction                                                                For CPU Units with DC power supply, high-speed operation is
     speed           specification input                                                              possible for input I0 only. (Maximum counting speed: 150 Hz)

                          Counter input

                          Reset input

L Low                     Set value
     speed           Present value

                          00000000
                        Counter bit

Counting Speed of the 8-digit Counter

The maximum counting speed of the 8-digit counter is 150 Hz. When the ladder program volume is large, however, this speed will be less than 150
Hz. Calculate the cycle time and confirm the maximum counting speed using the following formula. The calculation serves as a guide only, so allow
a suitable margin in the actual machine.

Maximum counting speed = 1,000,000 Hz/ Cycle time (s) 2.2 Hz
Note: Even if the calculated maximum counting speed exceeds 150 Hz using this formula, the maximum counting speed will be 150 Hz.

Cycle Time Calculation Method

Cycle =     Common +                      Processing time taken +  Ladder program +  Communications
time        processing                    when Expansion I/O       execution time    processing time (only
(s)        time                          Units are connected                        for CPU Units with
                                                                                     communications)

Refer to the following table for ZEN execution times. The execution times are provided as a guide. External factors, button operations, execution of
ZEN Support Software operations, and timing of the processing affects the actual processing times.

Common Processing Time                                                               Ladder Program Execution Time

                  Unit type                      Common processing time              Per line                        30 s: Line containing program *1
                                          850 s                                                                     7 s: Empty lines
Standard LCD-type CPU Units,
Economy-type CPU Units, and               200 s                                     Per output CPU Unit output bits (Q) 4 s                        *2
Communications-type CPU Units
                                                                                               Expansion I/O Unit
LED-type CPU Units                                                                             output bits (Y)

Expansion I/O Unit Processing Time                                                             Work bits (M)

                                                                                               Holding bits (H)

               Unit type                     Expansion I/O Unit processing time                Timers (T)/Holding    15 s                           *3
Expansion I/O Units                       160 s per Unit
                                                                                               timers (#)

                                                                                               Counters (C)/8-Digit  13 s
                                                                                               Counters (F)
Communications Processing Time (only for CPU Units with
Communications)                                                                                Display bits (D)      Hour and minute (CLK)/Year and

Reading information                       170 s                                                                     month (DAT)/Month and day
Writing set values                                                                                                   (DAT1): 21 s
                                          Twin timer: 11,000 s                                                      Timers (T)/Holding timers (#)/
Writing time information                  Others: 6,000 s
                                                                                                                     Counters (C)/Analog
                                          820 s                                                                     comparators: 28 s
                                                                                                                     Characters (CHR)/8-Digit
                                                                                                                     Counters (F): 38 s

                                                                                     Weekly timers (@)               4 s                            *4

                                                                                     Calendar timers (*)             1 s

                                                                                     Analog comparators (A)          3 s

                                                                                     Comparators (P)                 7 s                            *5

                                                                                     8-Digit Comparators (G)         4 s

                                                                                                                                                         21
                                                                                                                       ZEN V2 Units

Example Calculation of Ladder Program Execution Time

    I0          I1                   I2                 Ladder program execution time =

00                                               [Q0               (30 5) + (4 3) + 15 + 4 + 7 = 188 (s)

01  Q0

    I3                                                                                                 *5: P0

02                                               [Q1                                              *4: @0

03  I4                                           TT0                                          *3: T0 (output)
                                                                                     *2: Q (outputs) for 3 points
04  @0 P0 T0                                     [Q2                     *1: For 5 lines

6. Weekly Timer Operation (Only for Standard LCD-type, Economy-type, and Communications-

    type CPU Units)

Weekly timer                                                                                           Operation
     mode
                                                                         Date setting                                  Between Tuesday and Friday every week, the
N Normal Typical Timer Operation                                                                                       weekly timer bit turns ON from 08:15 until
     operation                                                                                                         17:30.

                                                              Mon  Tues  Wed Thurs                Fri  Sat        Sun  Between Tuesday and Friday every week, the
                                                 24:00                                                                 weekly timer bit turns ON from 23:00 until 05:00
                                                                                                                       the following day.
                       Time setting  Stop time   17:30

                                     Start time  8:15
                                                 0:00

                                     Weekly timer bit

                Timer Operation Extending Past Midnight

                                                                         Date setting

                                                 24:00 Mon         Tues  Wed Thurs                Fri  Sat        Sun
                                                 23:00
                       Time setting  Start time

                                     Stop time   5:00
                                                 0:00

                                     Weekly timer bit

D Multiple-                                                              Date setting                                  The weekly timer bit turns ON from Tuesday
     day                                                                                                               08:15 until Friday 17:30 every week.
     operation                                   24:00  Mon        Tues  Wed Thurs                Fri  Sat        Sun
                                                                                                                       Every week, from Tuesday through Friday, the
P Pulse-               Time setting  Stop time   17:30                                                                 weekly timer bit turns ON for 15 minutes and
     output                                                                                                            thirty seconds from 08:15.
     operation                       Start time  8:15
                                                 0:00

                                     Weekly timer bit

                                                                         Date setting

                                                 24:00  Mon        Tues  Wed Thurs                Fri  Sat        Sun

                       Time setting  Start time  8:15
                                                 0:00

                                     Weekly timer bit

                                     Operation time setting:
                                     15 minutes, 30 seconds

7. Calendar Timer Operation (Only for Standard LCD-type, Economy-type, and

    Communications-type CPU Units)

               Dec 31
End date Sep 1
Start date Apr 1

               Jan 1

Calendar timer bit

                                     The calendar timer bit is ON between 1 April and 31 August.

                                                                                                                                                                         22
                                                                                                                                     ZEN V2 Units

8. Display Settings (Only for Standard LCD-type, Economy-type, and Communications-type

    CPU Units)

Backlight/display L0: No backlight; No switching to display function screen (See note 1.)

function screen L1: Backlight; No switching to display function screen (See note 1.)
switching
                       L2: No backlight; Switching to display function screen (See note 2.)

                       L3: Backlight; Switching to display function screen (See note 2.)

Display start          X (digit): 00 to 11                                      X00  X11
position               Y (line): 0 to 3
                                                  Y0 to Y3

Display object         CHR  Characters (Up to 12 characters - English, numerals, symbols)
Monitoring
                       DAT  Month/day (5 digits @@/@@)

                       CLK  hour/minute (5 digits @@:@@)

                       I4 to I5 Analog-converted value (4 digits @@:@)

                       T0 to Tf Timer present value (5 digits @@.@@)

                       #0 to #7 Holding timer present value (5 digits @@.@@)

                       C0 to Cf Counter present value (4 digits @@@@)

                       F0   8-digit counter present value(8 digits @@@@@@@@)

                       A: Can read settings during operation.
                       D: Cannot read settings during operation.

Note: 1. When L0 or L1 are selected to disable the display function screen, the display function screen will not be displayed automatically. Use
            operation buttons to move to the display function screen.

        2. When L2 or L3 are selected, the ZEN switches to the display function screen if the display function is enabled and the specified data is
            displayed. The Main Screen will no longer be displayed. To display the Main Screen, change the CPU Unit to STOP mode.

9. Analog Comparator Operation

Example 1                                        Example 2
  (When comparison shows analog input               (When comparison shows analog input 1 is
  1  5.2 V)                                         analog input 2)

          Setting                                         Converted value
              10.5                                              10.0
              10.0
                                                                                                                     Analog input 1
               5.2
                                                                                                                     Analog input 2

             00.0                   10.5 V                      00.0
                  0.0       10.0 V Input voltage
                                                  Analog
Analog                                            comparator bit
comparator bit

10. Timer/Counter Comparator Operation

Example 1                                        Example 2
  (When comparison setting is holding               (When comparison setting is counter 1 (C1)
  timer #0  12 min 34 s)                            counter 2 (C2))

                            #0 present value                                              C1 present value

Setting

12 min 34 s

                                                                                          C2 present value

            0                                     Comparator
                                                  bit
Comparator
bit

11. 8-digit Counter Comparator Operation

When comparison setting is
  8-digit counter F0  12000000

                                                              F0 present value

12000000

                 0
8-digit counter
comparator
bit

                                                                                                                                                     23
                                                                             ZEN V2 Units

12. Specifications for Button Input Bits (Only for Standard LCD-type, Economy-type, and

     Communications-type CPU Units)

The operation buttons are used to perform operations for input bits. They are useful when checking program operations or forcefully resetting
holding timers or counters.

                                                                 ALT

                                                                                       Button input 7 (B7)

                                                                 DEL

                                                                                       Button input 6 (B6)
                                                                                       Button input 5 (B5)
                                                                                       Button input 4 (B4)
                                                                                       Button input 3 (B3)
                                                                                       Button input 2 (B2)

                                                                 OK

                                                                                       Button input 1 (B1)

                                                                 ESC

                                                                                       Button input 0 (B0)

Password Function (Only for Standard LCD-type, Economy-type, and
  Communications-type CPU Units)

The ZEN has a password function to prevent incorrect manipulation of ladder programs or settings data by other operators. When the password
(0000 to 9999) is set, the following operations will not be possible unless the password is input correctly.
Editing ladder program
Program all clear
Monitoring ladder programs
Changing/clearing password
Changing backlight OFF time
Setting input filter
Setting RS-485 communications

                                                                                   24
                                                                             ZEN V2 Units

ZEN Support Software Functions

Note: Always use ZEN-SOFT01-V4 as the Support Software for the V2 CPU Unit.

Creating Ladder Programs                                                  Simulating Ladder Programs

ZEN ladder programs can be created with ease.                             The simulation function makes it possible to check whether correct
                                                                          operation is performed without connecting to the ZEN.

Note: The Edit Input Dialog Box is displayed when an input bit is         Printing Ladder Programs
        inserted. Timer, counter, and other parameter settings are also
        set in the Edit Input Dialog Box. They cannot be set in the Edit  Ladder programs and I/O comments, as well as timer, counter and
        Output Dialog Box.                                                other parameter settings can be printed.

Monitoring Ladder Programs

The operating status can be monitored from the Support Software by
connecting to the ZEN using a Connecting Cable (ZEN-CIF01).

Note: Both RS-485 communications and the ZEN monitoring function cannot be used at the same time with Communications-type CPU Units.

The Support Software can also be used
to save files and edit comments.

Refer to the ZEN Support Software Operation Manual (Cat. No. Z184-E1-03) for details.

                                                                                                                                              25
Dimensions                                                                                                                                                  ZEN V2 Units

Note: All units are in millimeters unless otherwise indicated.                                                                                                            Unit Mounting Holes

CPU Units                                                                                                                                                                            4.5
                                                                                                                                                                                                   5.5
CPU Units with 10 I/O Points                                                   70                                             56
                                                                                                                                                                                   Note: Use M4 screws
ZEN-10C@@@-@-V2                                                                60                                             44                                                            for mounting.

                 90 80                                                                                 45                                                            Mounting Hole Dimensions

                                                                     4.7                        122.5                                                                                    Two, M4
                                                           (Sliding: 13 max.)                   112.5
                                                                                                                                                                              80
CPU Units with 20 I/O Points                                                                                                                       56
ZEN-20C@@@-@-V2                                                                                                                                     44

                                                                                                           I6 I7 I8 I9 Ia Ib                                                                       60 (112.5) *
                                                                                                                                                                            * The dimensions in parentheses
                                                                               20C1AR-A-V2
                                                                                                                                                                              refer to models with 20 I/O points.

                 90 80                                                                                                            45

                                                                                                Q4     Q5 Q6      Q7

                          4.7
                 (Sliding: 13 max.)

Dimensions with Battery Unit

                 CPU Units with 10 I/O Points                                                                         CPU Units with 20 I/O Points

                                                                               87.5                                                                140
                                                                                                                                                        122.5
44                      17.5                                                                70                        17.5

                                                                                                                                                               I6 I7 I8 I9 Ia Ib

    ZEN-BAT01                                                                                                                         20C1AR-A-V2

                 45                                                                                           45

                                                                                                                                                   Q4          Q5 Q6  Q7

                                                                                                                                                                                                                   26
Expansion I/O Units                                                                                        ZEN V2 Units

ZEN-8E1@@                                     DIN Track Hook                                                                Mounting Hole Dimensions
                                                (Using Slide)
                                                                                                    54
                                              7.6                                Two, 3.5 dia.                                               17.5 Two, M3

              2                   35                                                                44

              90                          97                                                    45  90                                                97

              2
                                                                        7.6

Power Supply Unit

ZEN-PA03024                           70                                         56                             Mounting Hole Dimensions

                                      60                                         44                                               Two, M4

                  90 80                                                      45                                        80

                       4.7                                                                                                                        60
              (Sliding: 13 max.)
                                                                                                    Connecting Cable
Accessories (Order Separately)
                                                                                                    ZEN-CIF01
Battery Unit                          Memory Cassette
                                                                                                    Cable length: 2m
ZEN-BAT01                             ZEN-ME01

                                                                                                                                                          27
                                                                                                                                  ZEN V2 Units

Track Mounting Accessories (Order Separately)

Mounting Track                                                                          PFP-100N2

PFP-100N
PFP-50N

                                                             7.30.15                                                                                    16

4.5                                                                                     4.5

                                                             350.3    270.15                                                    350.3 27 24                    29.2
                                                                                                                                                      1           1.5
     15 25  10  25                 25  10  25  15 (5) *                1                     15 25      25         25      25 15

                    1,000 (500) *                                                                   10      1,000      10

                    * The numbers in parentheses () are dimensions for the PFP-50N.

End Plate                                                    10                         Spacer                             5                    16
                                                                   6.2                                                                         12
PFP-M                  M4 8                                                 1.8       PFP-S
                       pan-head                                                                                                                             34.8
                       screw                                        1                                                             44.3
                     50                                                      35.5 35.3
                                                                                                                                               16.5
                       11.5                                           1.8

                                       10                    1.3

                                           M4 spring washer  4.8

Precautions when Selecting ZEN Programmable Relays

Changes in Comparison with Previous Models

The power supply and transistor output voltage ranges for CPU Units and Expansion I/O Units with DC power supply has been expanded to
  10.8 to 28.8 VDC.

The width of Expansion I/O Units has been reduced by half and only 8-point models are available.
The connection method between the CPU Unit and Expansion I/O Units has changed.
Twin timer operation has been added to timers.
Multiple-day operation and pulse-output operation has been added to weekly timers.
An 8-digit counter and 8-digit comparators have been added.
The accuracy of analog inputs has been increased to 1.5% FS.
The timing accuracy of weekly timers and calendar timers has been increased to 15 s or less per month (at 25C).
Australia and New Zealand Daylight Saving Time (DST) settings have been added.
CPU Units with RS-485 communications and economic CPU Units have been added.
The heat slits in the cases of CPU Units and Expansion I/O Units have been removed to prevent foreign matter from entering.

Model numbers have been changed to reflect the improved functionality.

     Previous Model Numbers

     ZEN-@C@@@-@                           (Pre-V1 CPU Units)
     ZEN-@C@@@-@-V1                        (V1 CPU Units)
     ZEN-@E@@                              (4E/8E-type Expansion I/O Units)

     New Model Numbers                     (V2 CPU Units)
                                           (8E1-type Expansion I/O Unit)
     ZEN-@C@@@-@-V2
     ZEN-8E1@@

Memory Cassettes, Connecting Cables, and Battery Units have not been changed and can be used as they are with the new models.

                                                                                                                                                                        28
                                                                                                                            ZEN V2 Units

Precautions when Switching from Previous Units

Previous models of Expansion I/O Units cannot be connected to V2 CPU Units.
ZEN-8E1@R Expansion I/O Units with relay outputs need to be connected to a power supply.
A ZEN-@C@D@-D-V2 CPU Unit with DC power supply cannot be connected to an Expansion I/O Unit with AC inputs.
When connecting Expansion I/O Units with DC inputs to a CPU Unit with an AC power supply, the burst noise immunity will be 1 kV (IEC 61000-

  4-4).
There is no change to the 8 A per contact for relay output, but the total output for all contacts must be as follows:

     Units with 10 I/O Points: 20 A max. (15 A max. for Communications-type CPU Units)
     Units with 20 I/O Points: 40 A max.
     Expansion I/O Units: 20 A max.
Always use the ZEN-SOFT01-V4 Support Software for V2 CPU Units.
Input wiring for CPU Units with DC power supplies differs from that for Pre-V1 CPU Units. Refer to the following diagrams.

                          V2 and V1 CPU Units                                                                          Pre-V1 CPU Units

COM wiring depends on whether a negative common or positive common is being used.                         The input circuit common terminal is connected
                                                                                                          internally to the negative (-) side of the power
Negative (-) COM Wiring                           Positive (+) COM Wiring                                 supply circuit.

       24 VDC                                                 24 VDC                                                      24 VDC

                         COM wiring required.                              COM wiring required.

                         Analog inputs possible.

                                      Input                                           Input                                     Analog inputs possible.
                                      devices                                         devices
                                                                                                                                                Input
         + - COM                                              + - COM                                                                           devices

                                                                                                                      +-    NC

         CPU Unit with 10 I/O Points                                        CPU Unit with 10 I/O Points

                                               Note: I4 and I5 (Ia and Ib for CPU Units with 20 I/O                    CPU Unit with 10 I/O Points
                                                       points) cannot be used as analog input terminals.

Changes

Ratings and Specifications

CPU Units

                Item                                                  V2 Units                            V1 Units                            Pre-V1 Units

Rated power Models with DC 10.8 to 28.8 VDC                                                               20.4 to 26.4 VDC
supply voltage power supply

Power           Models with AC See Ratings on page 7.                                                     30 VA max.
                                                                                                          (with 3 Expansion I/O Units connected)
consumption power supply

                Models with DC                                                                            6.5 W max.
                power supply                                                                              (with 3 Expansion I/O Units connected)

Inrush current Models with AC Models with 10 I/O points: 4.5 A max.                                       40 A max.

                power supply                   Models with 20 I/O points: 4.5 A max.

                Models with DC Models with 10 I/O points: 30 A max.                                       20 A max.

                power supply                   Models with 20 I/O points: 30 A max.

DC inputs       Input impedance                5.3 k                                                      5 k                   4.8 k
I0 to I3        ON voltage                     8 VDC min.                                                 16 VDC min.
(See note 1.)   Input common                   Independent common terminal                                                      Internally connected to
                                                                                                                                power supply terminal

DC inputs       Input impedance                5.2 to 5.5 k                                               5 k
I4 to I5        ON voltage                     8 VDC min.                                                 16 VDC min.
(See note 2.)   OFF voltage                    3 VDC max.                                                 5 VDC max.

Analog inputs Input impedance                  100 k min.                                                 150 k min.

I4 to I5        Accuracy                       1.5% FS (at ambient operating temperature within          10% FS (at ambient operating temperature
(See note 2.)                                  rated range)                                               within rated range)

Control         Relay outputs                  8 A per output                                             8 A per output
outputs                                        Total for all outputs must be as follows:
                                               Units with 10 I/O Points: 20 A max.
                                               (15 A max. for Communications-type CPU Units)
                                               Units with 20 I/O Points: 40 A max.

                Transistor outputs 28.8 V max.                                                            26.4 V max.

Timing accuracy of weekly and                  15 s or less per month (at 25C)                          2 min per month
calendar timers

Mounting direction                             Standard (vertical) installation and horizontal installation Standard (vertical) installation

Terminal block tightening torque 0.565 to 0.6 Nm (5 to 5.3 in-lb)                                        0.5 to 0.6 Nm

Connectable Expansion I/O Units ZEN-8E1@ (See note 3.)                                                    ZEN-4E@ and ZEN-8E@

Case structure                                 No heat slits                                              Heat slits

Note: 1. Units with 20 I/O Points: I0 to I9
        2. Units with 20 I/O Points: Ia to Ib
        3. Refer to page 31 for details on compatible combinations of CPU Units and Expansion I/O Units.

                                                                                                                                                            29
                                                                                                               ZEN V2 Units

Expansion I/O Units

           Item                                              8E1 type                                          4E/8E type

Model      Input impedance                 Unit with 8 I/O Points                            Units with 4 input, 4 output, or 8 I/O points
AC inputs  Isolation
           Input common                    680 k                                             83 k
DC inputs  Input voltage
           Input impedance                 No isolation                                      Photocoupler
           Isolation
                                           Internally connected to power supply terminal     Independent common terminal
           ON voltage
           Input common                    10.8 to 28.8 VDC                                  20.4 to 26.4 VDC

                                           6.5 k                                             4.7 k

                                           ZEN-8E1DR: No isolation                           Photocoupler
                                           ZEN-8E1DT: Photocoupler

                                           8 VDC min.                                        16 VDC min.

                                           ZEN-8E1DR: Internally connected to power supply Independent common terminal
                                                             terminal

                                           ZEN-8E1DT: Independent common terminal

Control output Relay outputs               8 A per output                                    8 A per output
                                           Total for all outputs must be as follows:
                                           Units with 10 I/O Points: 20 A max.
                                           Units with 20 I/O Points: 40 A max.

                       Transistor outputs  28.8 V max.                                       26.4 V max.
Mounting screws
Connectable CPU Unit                       M3 (mounting holes on DIN Track hooks)            M4 (mounting holes on Unit)
Dimensions (H W D)
Case structure                             V2 CPU Units (See note.)                          V1 or Pre-V1 CPU Units

                                           90 35 56 mm                                   90 70 56 mm

                                           No heat slits                                     Heat slits

Note: Refer to page 31 for details on compatible combinations of CPU Units and Expansion I/O Units.

Other Functions

           Item                                                        V2 Units                     V1 Units               Pre-V1 Units

Bits       Timer operation                 ON-delay, OFF-delay, one-shot pulse, flushing     ON-delay, OFF-delay, one-shot pulse, flushing
                                           pulse, twin timer operation                       pulse

           Weekly timer                    Timer operation, multiple-day operation, pulse-   Timer operation
           operation                       output operation
                                                                                             ---
           Addition of bits                8-digit counter (1 counter, up to 150 Hz)
                                           8-digit comparators (4 comparators)
Daylight Saving Time (DST) Setting                                                           Manual, EU, US
                                           Manual, EU, US.
Items set for password                     Australia, New Zealand                                                    Ladder program editing
                                                                                                                     Ladder monitoring
                                           Ladder program editing                                                    Password change/clear
                                           Program all clear                                                         Backlight shut-off time
                                           Ladder monitoring                                                         Input filter settings
                                           Password change/clear                                                     Node number setting
                                           Backlight shut-off time
LCD contrast adjustment                    Input filter settings                             Possible
                                           Node number setting (See note.)                   Node number setting window displayed.
Menus      Node number
           setting window                  Not possible

           Modem                           Node number setting window deleted (except for    Modem initialization window displayed.
           initialization                  Units with communications).
           window
                                           Modem initialization window deleted (except for
                                           Units with communications).

RS-485 communications                      Models added with communications.                 ---

                                           ZEN-10C4@R-@-V2

Economy-type CPU Units                     Economy-type models added.                        ---

                                           ZEN-@C3@R-@-V2

                                           Expansion I/O Units cannot be connected.

                                           Other functions are the same as the standard LCD

                                           models.

Note: Not displayed for V2 CPU Units except for Units with Communications.

                                                                                                                                              30
                                                                                                                     ZEN V2 Units

Bits

                 Name                                                                   CPU Unit

                                                          V2 Units                                V1 Units                          Pre-V1 Units
                                                                                                                                    10 I/O points
                                          10 I/O points             20 I/O points       10 I/O points       20 I/O points       6 points
                                                                                                                                4 points
Input bits                     I 6 points                     12 points            6 points            12 points                8 points
                                                                                                                                4 points
Output bits                    Q 4 points (See note.) 8 points                     4 points            8 points                 8 points
                                                                                                                                8 points
Timers                         T 16 points                                                                                      8 points
                                                                                                                                8 points
Holding timers                 # 8 points

Counters                       C 16 points

Weekly timers                  @ 16 points

Calendar timers                * 16 points

Display bits                   D 16 points

Work bits                      M 16 points

Holding bits                   H 16 points

Expansion input bits           X 12 points

Expansion output bits          Y 12 points

Analog comparator bits         A 4 points

Timer/counter comparator bits P 16 points

8-digit counter                F 1 point                                           ---
                                                                                   ---
8-digit counter comparator bits G 4 points

Note: Output bit Q3 of Communications-type CPU Units cannot be output externally. It can be used as a work bit.

Compatible Combinations of CPU Units and Expansion I/O Units

The Expansion I/O Units that can be connected to V2 CPU Units are different from those that can be connected to V1 CPU Units and previous
CPU Units. Expansion I/O Units with AC Inputs cannot be connected to V2 CPU Units with DC Power Supplies. Expansion I/O Units cannot be
connected to Economy-type CPU Units.

                               CPU Units                                                      Supported
                                                                                        Expansion I/O Units
       Version         CPU Unit type                  Power supply       Model
V2                                                                                      ZEN-8E1AR
                 Standard LCD type                    AC            ZEN-@C1AR-A-V2      ZEN-8E1DR
V1 and Pre-V1                                                       ZEN-@C2AR-A-V2      ZEN-8E1DT
                 LED type                                           ZEN-10C4AR-A-V2
                                                                                        ZEN-8E1DR
                 Communications type                                                    ZEN-8E1DT

                 Standard LCD type                    DC            ZEN-@C1D@-D-V2      Not supported.
                                                                    ZEN-@C2D@-D-V2
                 LED type                                                               ZEN-4EA
                                                                                        ZEN-4ED
                 Economy type                         AC            ZEN-@C3AR-A-V2      ZEN-4ER
                                                                                        ZEN-8EAR
                                                      DC            ZEN-@C3DR-D-V2      ZEN-8EDR
                                                                                        ZEN-8EDT
                 Standard LCD type                    AC            ZEN-@C1AR-A-V1
                                                                    ZEN-@C1AR-A
                 LED type                                           ZEN-@C2AR-A-V1
                                                                    ZEN-@C2AR-A

                                                      DC            ZEN-@C1D@-D-V1

                                                                    ZEN-@C1D@-D

                                                                    ZEN-@C2D@-D-V1

                                                                    ZEN-@C2D@-D

Memory Cassette and CPU Unit Combinations

Be aware of the following restrictions when using a Memory Cassette containing a program that was stored from a CPU Unit with a different version
of system software.

System software version                                   System software version of CPU Unit used to read the Memory Cassette
of CPU Unit used to write
                               Ver. 1.0                       Ver. 1.1             Ver. 2.0 (V1 CPU Units)           Ver. 3.0 (V2 CPU Units)
  the Memory Cassette

                                                                                   10 I/O points 20 I/O points 10 I/O points 20 I/O points

Ver. 1.0                   OK                             OK             OK                  OK                  OK             OK

Ver. 1.1                   Restrictions (See note OK                     OK                  OK                  OK             OK
                           1.)

Ver. 2.0      10 I/O points Restrictions                  Restrictions   OK                  OK                  OK             OK
(V1 CPU
Units)                     (See notes 1 and 2.) (See note 2.)

              20 I/O points Restrictions                  Restrictions   Restrictions        OK                  Restrictions   OK

                           (See notes 1, 2, and 3.) (See notes 2 and 3.) (See note 3.)                           (See note 3.)

Ver. 3.0      10 I/O points Restrictions                  Restrictions   Restrictions        Restrictions        OK             OK
(V2 CPU
Units)                     (See notes 1, 2, and 4.) (See notes 2 and 4.) (See note 4.) (See note 4.)

              20 I/O points Restrictions                  Restrictions   Restrictions        Restrictions        Restrictions   OK
                                 (See notes 1 to 4.)
                                                          (See notes 2, 3, and 4.) (See note 4.) (See note 4.) (See note 3.)

Note: 1. The display functions (display clear: -CD@ and day/month display: DAT1) cannot be used and will be ignored.

         2. Only the memory area ranges supported by the pre-V1 CPU Units can be used for Timers, Holding Timers, Counters, Weekly Timers, Calendar Timers, and
              Displays (i.e., only half of each).

         3. Only 6 inputs and 4 outputs can be used in the CPU Unit I/O bits. Any others will be ignored.

         4. Twin timer operation for timers, multiple-day operation and pulse operation for weekly timers, the 8-digit counter, and 8-digit comparators cannot be used.
              New Zealand and Australia cannot be set for Daylight Saving Time (DST).

                                                                                                                                                   31
                                                                                                                                  ZEN V2 Units

Support Software and CPU Unit Combinations

        CPU Unit system software                                                                 Support Software
Ver. 1.0 (Pre-V1 Units)
                                                        Ver. 1.0                          Ver. 2.0                    Ver. 3.0                    Ver. 4.1
                                                    ZEN-SOFT01                      ZEN-SOFT01-V2               ZEN-SOFT01-V3               ZEN-SOFT01-V4

                                            OK                                  OK                          Restrictions              Restrictions
                                                                                                                                      (See notes 1, 2, and 3.)
                                                                                                            (See notes 1 and 2.)
                                                                                                                                      Restrictions
Ver. 1.1 (Pre-V1 Units)                     Restrictions                        OK                          Restrictions              (See notes 2 and 3.)
Ver. 2.0 (V1 CPU Units)                     (See note 1.)
                                                                                                            (See note 2.)             Restrictions
Ver. 3.0 (V2 CPU Units)  10 I/O points Restrictions                                                                                   (See note 3.)
                                            (See notes 1 and 2.)                Restrictions                OK
                                                                                                                                      Restrictions (See note 3.)
                         20 I/O points Not applicable.                          (See note 2.)
                                                                                                                                      OK
                                            Not applicable.                     Not applicable.             OK

                                                                                Not applicable.             Not applicable.

Note: 1. The display functions (display clear: -CD@ and day/month display: DAT1) cannot be used and will be ignored.

         2. Only the memory area ranges supported by the pre-V1 CPU Units can be used for Timers, Holding Timers, Counters, Weekly Timers, Calendar Timers, and
              Displays (i.e., only half of each).

         3. Twin timer operation for timers, multiple-day operation and pulse operation for weekly timers, the 8-digit counter, and 8-digit comparators cannot be used.
              New Zealand and Australia cannot be set for Daylight Saving Time (DST).

Difference between ZEN Programmable Relays and PLC Ladder
  Program Execution

ZEN Programmable Relays                                                             OMRON SYSMAC PLCs

           I0  I1 I2                        ZEN executes the entire                              I0 I1 I2                         PLCs execute ladder
    0                                 [ Q0  ladder program (up to 96
                                            lines) from the first to last line                   0                        [ Q0    programs one rung (circuit) at
          Q0                          [ Q1  at one time. Each row is                                   Q0
    1                                 TT0   executed in order from left to                                                        a time, starting with the top
                                      [ Q2  right starting from the left bus                     1
           I3  Executed sequentially        bar.                                                                                  rung and executing it in order
    2          from the bus bar.                                                                        I3
                                                                                                 2                        [ Q1    from the left. When the END
           I4
    3                                                                                                   I4                TT0     instruction is reached, the
                                                                                                 3
           T0                                                                                                                     program is executed again
    4                                                                                                  T0
                                                                                                 4                        [ Q2    from the first rung.
Bus bar
                                                                                                                   END

The ON/OFF status produced by an output contact will not be used                    When the following instructions are executed, Q0 turns ON/OFF
as the input contact status in the same cycle, but it can be used in                at the same time as the other bits.
the next cycle.

                                            I0                                                          I0                        I0
                                                                                                 0
       I0                [ M0                                                                                      [ M0           M0
0                                                                                                      M0
                                            M0                                                   1                 [ Q0
      M0
1                        [ Q0               Q0                                                                                    Q0

                                                1 cycle  1 cycle

                                                                                                                                                                         32
Safety Precautions                                                                                   ZEN V2 Units

Refer to Safety Precautions for All Timers.                                 Disconnect the output lines from the system before testing
                                                                             operation in any system in which incorrect operation can result in
                           !WARNING                                          injury or equipment damage.

Serious human hazard may occasionally occur due to ignition or             Confirm safety before attempting any of the following operations.
rupture of the lithium battery used in the Battery Unit. Do not short the       Changing the operating mode (RUN/STOP).
battery terminals or charge, disassemble, deform under pressure, or
incinerate the battery.                                                         Using the button switches.
Never use any battery that has been dropped on the floor or otherwise
subjected to excessive shock.                                                   Changing bit status or parameter settings.

                            !CAUTION                                        Double-check all wiring before turning ON the power supply.
                                                                            Refer to Cycle Time Calculation Method on page 21 and confirm
Electric shock, fire, or malfunction may occur. Do not disassemble,
modify, or repair the ZEN or touch any of the internal parts.                that the increase in the cycle time will not affect operation. If the
                                                                             cycle time is too long, it may become impossible to read input
Electric shock may occur. Never touch the I/O terminals, computer            signals accurately. The increase in the cycle time will be particularly
connector, or Battery Unit connector while power is being supplied.          noticeable when set values are written in RUN mode for a CPU Unit
                                                                             with communications (ZEN-10C4@R-@-V2).
Electric shock may occur. Do not remove the Expansion Unit
connector cover unless an Expansion I/O Unit will be permanently           Installation and Wiring
installed.
                                                                            Do not allow the ZEN to fall during installation.
Fire may occasionally occur. Tighten the terminal screws to a torque       Be sure that the DIN Track mounting levers, Memory Cassettes,
of 0.565 to 0.6 Nm (5 to 5.3 in-lb).
                                                                             Battery Units, cable connectors, and other items with locking
Precautions for Safe Use                                                    devices are properly locked into place. Improper locking may result
                                                                             in malfunction.
Please observe the following precautions for safe use of this product.      For surface mounting, tighten mounting screws to the following
                                                                             torque.
Circuit Design                                                               CPU Units: 1.03 Nm max.
                                                                             Expansion I/O Units: 0.46 Nm max.
All interface connectors and battery connectors are live parts. They      Use wires with cross-sectional areas of 0.2 to 2.5 mm2 (equivalent
  may not be directly connected to a Safety Extra Low Voltage                to AWG24 to AWG14) for wiring and strip them for 6.5 mm.
  (SELV) circuit or to accessible conductive parts.
  For programming units and personal computers use only the                Handling
  connecting cable ZEN-CIF01 (optional accessory) manufactured by
  OMRON.                                                                   The environment of use for the ZEN is "Pollution degree 2" and
  ZEN-CIF01 provides safe (reinforced) insulation between personal           "Overvoltage category II" specified in IEC60664-1.
  computers and ZEN.
                                                                            Always use the ZEN within the rated ambient operating
Provide emergency stop circuits, external interlock circuits, limit        temperature and humidity. The rated ambient operating
  circuits, and other safety circuits in addition to any provided within     temperature is 0 to 55C (-25 to 55C for LED-type CPU Units).
  the ZEN control circuits to ensure safety of the overall system in the     If the ZEN is used near sources of heat, such as a power supply,
  event of ZEN failure or external factors.                                  the internal temperature of the ZEN may increase, lowering the
                                                                             durability of the ZEN.
If the ZEN discovers an error during self-diagnosis, operation will
  be stopped and all outputs will be turned OFF. As a                      Discharge static electricity from your body, e.g., by touching a
  countermeasure for such problems, external safety measures must            grounded metal plate, before touching any Unit.
  be provided to ensure safety in the overall system.
                                                                            The exterior of the Units will be damaged if it comes into contact
Outputs from the ZEN may remain ON or OFF due to faults in                 with organic solvents (e.g., benzene or paint thinner), strong
  internal circuits such as output relay fusing or burning, or output        alkalies, or strong acids. Never allow such substances to come into
  transistor destruction. As a countermeasure for such problems,             contact with the Units.
  external safety measures must be provided to ensure safety in the
  overall system.                                                          Do not apply voltages exceeding the rated voltages. Internal
                                                                             elements may be destroyed.
Fail-safe measures must be taken by the user to ensure overall
  system safety in the event of broken signal lines or momentary            Short failures or open failures may result from the destruction of
  power interruptions.                                                       output elements. Do not use loads that exceed the rated output
                                                                             current.
The durability of the output relays is largely affected by the
  switching conditions. Confirm the operation of the system under          Maintenance
  actual operating conditions and set the switching frequency to
  ensure that adequate performance will be provided. Insulation            When replacing a CPU Unit, transfer to the new Unit and confirm all
  faults and burning in the ZEN may result if relays are used after        settings for clock data, internal holding bits, holding timers, and
  their performance has deteriorated.                                      counters before starting operation again.

Connecting Expansion I/O Units                                             Transportation and Storage

Supply power to both the CPU Unit and Expansion I/O Units from            Use special packing boxes when transporting the ZEN and do not
  the same power supply and turn them ON and OFF at the same                 subject it to excessive shock or vibration or drop it during shipment.
  time.
                                                                            Store the ZEN within the rated ranges. If the ZEN has been stored
When connecting Expansion I/O Units with DC inputs to a CPU                at -10C or lower, allow it to stand at room temperature for
  Unit with an AC power supply, the burst noise immunity will be 1 kV        three hours or longer before turning ON the power supply.
  (IEC 61000-4-4).
                                                                            Precautions for Correct Use
Expansion I/O Units with AC inputs (ZEN-8E1AR) cannot be
  connected to a CPU Unit with a DC power supply.                          Installation Environment

System Startup and Program Changes                                          Do not install the ZEN in the following locations.
                                                                               Locations subject to radical changes in temperature
Check the user program for proper execution before actually
  running it on the Unit.

                                                                           33
                                                                         ZEN V2 Units

    Locations with high humidity subject to condensation

    Locations subject to excessive dust or dirt

    Locations subject to corrosive gas

    Locations subject to direct sunlight

Do not install the ZEN in locations subject to shock or vibration.
  Extended use in such locations may cause damage from stress.

In environments subject to static electricity (e.g., close to pipes
  conveying forming materials, powders, or fluid materials), separate
  the ZEN as far as possible from the source of static electricity.

The ZEN is neither waterproof nor oil-proof. Do not use it in
  locations subject to water or oil.

Use the ZEN within the allowable power supply voltage range. Be
  particularly careful in locations with bad power supply conditions,
  e.g., large fluctuations in the power supply voltage.

Do not install the ZEN in locations subject to excessive noise,
  which may cause the ZEN to fail.

Take appropriate and sufficient countermeasures when installing
  systems in the following locations:
    Locations subject to strong electromagnetic fields

    Locations subject to possible exposure to radioactivity

Power Supply

Always turn OFF the power supply to the ZEN before attempting
  any of the following.
    Assembling the ZEN

    Connecting or disconnecting any cables or wiring

    Attaching or removing the Memory Cassette

    Attaching or removing the Battery Unit

If the power supply is interrupted for two days or more (at 25C),
  the internal capacitor will discharge and internal bit status and the
  contents of PV areas will be lost or corrupted and dates and times
  will be reset. When restarting operation after the power supply has
  been interrupted for an extended period of time, check the system
  in advance to confirm that no errors will occur.

Handling

Connect connectors only after confirming that the direction or
  polarity is correct.

Failures could result if dust or dirt enters the ZEN. Always connect
  the connector cover to the computer connector whenever it is not
  being used.

Do not remove the label from the left side of the CPU Unit if a
  Battery Unit is not mounted.

Other

The execution of the ladder program in the ZEN is different from
  that for other PLCs. Refer to Difference between ZEN
  Programmable Relays and PLC Ladder Program Execution on
  page 32.

Abide by all local ordinances and regulations when disposing of the
  ZEN.

The Battery Unit (ZEN-BAT01, sold separately) contains a lithium
  battery. Observe all applicable legal requirements for your area
  when disposing of the lithium battery.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                  In the interest of product improvement, specifications are subject to change without notice.

                                                                                                                34
                                                       Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.

                                                      Warranty and Limitations of Liability

WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.

In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

                                                            Application Considerations

SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.

At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:

       Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.

       Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
           safety equipment, and installations subject to separate industry or government regulations.

       Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.

                                                                       Disclaimers

CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.

DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.

ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.

OMRON Corporation                                                                                                                                      2010.10
                               In the interest of product improvement, specifications are subject to change without notice.
Industrial Automation Company
                                                                                   (c)Copyright OMRON Corporation 2010 All Right Reserved.
http://www.ia.omron.com/
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2020 EEWORLD.com.cn, Inc. All rights reserved