Y92F-71器件文档内容

Ground Fault Relay

K6EL

                                                                                                                     CSM_K6EL_DS_E_2_1

Economical, Compact, High-performance,
DIN 48 48-mm Ground Fault Relay for Low
Voltages

Performs continuous monitoring and detection of ground faults
in low-voltage circuits due to the deterioration of insulation in
electrical devices.

Higher reliability ensured with improved resistance to high-fre-
quency noise when used for inverter loads.

Remote monitoring of cubicles is possible with automatic-reset
models.

Ground Fault Relays and through-type ZCTs (zero-phase cur-
rent transformers) are mutually compatible.

The through-type ZCTs are equipped with test terminals, allow-
ing operation tests for Ground Fault Relays to be performed with
ease.

Model Number Structure

Model Number Legend                                                     3. Sensed Current
                                                                             30: 30 mA (fixed)
K6EL-@@                                                                      50: 50 mA/150 mA (switchable)
                                                                             100: 100 mA/200 mA (switchable)
     1 23                                                                    200: 200 mA/500 mA (switchable)
1. Ground Fault Relay                                                        500: 500 mA/1,000 mA (switchable)
2. Operating Time and Reset Method

    None: 0.1 s manual reset
    A: 0.3/0.8 s (switchable) manual reset

Ordering Information

List of Models

Manual-reset Ground Fault Relays

                                                  Type High-sensitivity                         Medium-sensitivity models
                                                                    models

                                           Sensed current 30 mA (fixed)         100 mA/200 mA       200 mA/500 mA         500 mA/1,000 mA
                                                                                  (switchable)        (switchable)           (switchable)
Type               Operating time
High-speed models                                                           K6EL-100            K6EL-200               K6EL-500
Delayed models     Less than 0.1 s                K6EL-30
                                                                            K6EL-A100           K6EL-A200              K6EL-A500
                   0.3/0.8 s (switchable)         ---

ZCTs (Zero-phase Current Transformers)

                   Type                    Indoor through-type models                           Indoor separate-type models

Rated current  Sensed current              Model       Diameter of through-hole                 Model           Diameter of through-hole
50 A
100 A                          OTG-L21            21 mm                          ---                            ---
200 A
400 A                          OTG-L30            30 mm                          ---                            ---
600 A
1,000 A                        OTG-L42            42 mm                          OTG-CN52                       52 mm

                               OTG-L68            68 mm                          OTG-CN77                       77 mm

                               OTG-L82            82 mm                          OTG-CN112                      112 mm

                               OTG-L156           156 mm                         ---                            ---

                                                                                                                                           1
                                                                                                                              K6EL

Ground Fault Relay and ZCT Combinations

(OK: Compatible)

                   Ground Fault Relay                K6EL-30          K6EL-100, -200, -500
ZCT                                                               K6EL-A100, -A200, -A500
                                                                OK
OTG-L21 (50 A)                         OK                       OK
                                                                OK
OTG-L30 (100 A)                        OK                       OK
                                                                OK
OTG-L42 (200 A)                        OK                       OK
                                                                OK
OTG-L68 (400 A)                        ---                      OK
                                                                OK
OTG-L82 (600 A)                        ---

OTG-L156 (1,000 A)                     ---

OTG-CN52 (200 A)                       ---

OTG-CN77 (400 A)                       ---

OTG-CN112 (600 A)                      ---

Note: 1. "OK" indicates groupings that can be combined freely.
         2. Combinations with the OTG-LA@@ are also possible.

Options

Flush Mounting Adapters                                                            Front Cover

                  Model                                                                                       Model
                                                                                   Y92A-48B (Hard Cover)
Y92F-30                                                                            Y92A-48D(Soft Cover)
Y92F-71

Specifications

Ground Fault Relay Ratings

                               Type                           High-speed models                            Delayed models       Delayed high-sensitivity
                                                                                                                                            models
Item
                                                                                                                              100 VAC
Control power supply                        100/110 VAC or 200/220 VAC, 50/60 Hz (same for all)
                                                                                                                              SPDT
Rated current                               Depends on the ZCT                                                                3A
                                                                                                                              cos = 1
Sensed current                              50% to 100% of the rated sensed current (50 mA 10%, 150 mA 20%)                 220 VAC, 3 A

Non-operating current                       0% to 50% of the rated sensed current

Rated short-time current                    2,500 A

Ground fault indication method              LED (red)

Test method                                 Relay operation confirmed using a test button. (Independent of ZCT connection.)

Reset method Manual                         Either press the reset button or turn the control power supply OFF and ON again.

                 Automatic                  Automatically resets when the ground fault is cleared.

Built-in         Contact form               SPDT+SPST-NO
contacts
                 Carrying current 5 A

                 Rated load                                     cos = 1                             cos = 0.4 (L/R = 7 ms)

                                            240 VAC             5A                                  2A

                                            110 VDC             0.3 A                               0.2 A

                                            30 VDC              5A                                  3A

Power (VA) consumption                      3 VA max.

Weight                                      Approx. 110 g

                                                                                                                                                          2
                                                                                                                                K6EL

Ground Fault Relay Characteristics

Item               Type           High-speed models                    Delayed models                     Delayed high-sensitivity models

Operating time           Less than 0.1 s                    0.3 s/0.8 s (switchable)           Less than 0.5 s

Inertial non-operating ---                                  0.1 s when set to 0.3 s
time                                                        0.5 s when set to 0.8 s

Control power supply 80% to 110% of the control power supply voltage
range

Operating temperature -10 to 55 C (with no icing)
range

Operating humidity       45% to 85% (with no condensation)
range

Insulation resistance 5 M min. at 500 VDC (between charged parts and the mounting panel)

Dielectric strength      1,500 VAC, 50/60 Hz for 1 min (between charged parts and the mounting panel)

Lightning impulse        1.2/50 s, 7,000 V (between control power supply terminals)
dielectric strength

Lightning impulse        1.2/50 s, 7,000 V (primary side of ZCT)
operation failure

Vibration resistance Destruction: 16.7 Hz, 4-mm double amplitude for 1 min

Shock resistance         98 m/s2

Note: The range for an operating time of 0.3 s is 0.15 to 0.45 s and the range for an operating time of 0.8 s is 0.6 to 1.2 s.

ZCT (Zero-phase Current Transformer)

Item Structure                             Indoor through-type models                                     Indoor separate-type models

            Model    OTG-L21 OTG-L30 OTG-L42 OTG-L68 OTG-L82 OTG-L156 OTG-CN52 OTG-CN77 OTG-
                                                                                                                                                                       CN112

Rated current        50 A         100 A    200 A            400 A      600 A          1,000 A 200 A       400 A                 600 A

Diameter of          21 mm        30 mm    42 mm            68 mm      82 mm          156 mm 52 mm        77 mm                 112 mm
through-hole

Rated voltage        600 VAC max., 50/60 Hz, single-phase/three-phase

Output terminal      None (The ZCT's output terminals k and l can be connected to either input terminals 3 or 4 of the Relay.) (See note.)
polarity

Insulation           100 M min. (between charged metal parts and ground)
resistance

Dielectric strength 2,200 VAC, 50/60 Hz for 1 min (between charged metal parts and ground)

Ambient operating -10 to 60 C (with no icing)
temperature

Weight               Approx.      Approx.  Approx.          Approx.    Approx.        Approx.  Approx.    Approx.               Approx.
                     90 g         130 g    230 g            480 g      700 g          6.6 kg   1.3 kg     2.5 kg                3.5 kg

Note: Do not connect ZCT output terminals k and l to ground. Doing so may result in damage to the Relay.

                                                                                                                                                                              3
                                                                                                                                                              K6EL

Internal Block Diagram

                                                           Delayed models only                              X/c

                                                              Operating time                                           9
                                                              selection switch                                         8
                                                                                                                      11
                                                           Operating time
                                                            setting circuit                                 X/a

                                                                                Reset button                           6
                                                                                                                       7

                3            Input        Operating        Amplifier            Switching                   X
                          protection     value setting      circuit               circuit
From OTG ZCT
                            circuit          circuit
                4

                                             Sensitivity   Test button                               Ground fault             Operation at
                                         selection switch                                            indicator (red)          200/220 V
                                         (not provided on
                                          the K6EL-30)                                                            2       Operation at
                                                                                                                          100/110 V
                                                                                     Power       Shock-wave           1
                                                                                     supply
                                                                                     circuit         absorption

                                                                                                     circuit

                                                                                                                      10

                                                                                      Power supply indicator (green)

Nomenclature                                               POWER LEAKED               K6EL-A100                Ground fault indicator (red)

                  Power supply indicator (green)           TEST RESET                 EARTH LEAKAGE            Reset button (black)
                                                                                      RELAY                    (not provided on automatic-reset models)
                                     Test button (red)
                        Sensitivity selection switch       SENSITIVITY                                         Operating time selection switch
                   (not provided on the K6EL-30)                                                               (delayed models only)
                                                           100                  200
                                                           mA                   mA

                                                           0.3S                 0.8S

                                                           OPERATING TIME

Connections                                                Ground Fault Relay with P3GA-11 Ground Fault Relay with P2CF-11

Ground Fault Relay                                         (from Terminal Side)                                           (from Terminal Side)
(from Pin Side)

                                                                                              5 6 78                      87                65
                                                                                              4                                                  4
             567                                                        From ZCT                                                                    From ZCT
                                                                        From ZCT
From ZCT  4        8

          3        9                                                                          3      9

          2  1 11  10                                                                                                     9                 3       From ZCT

                                                                                              2 1 11 10                   10 11             12

                 100 VAC                                                                           100 VAC                   100 VAC
          200 VAC                                                                             200 VAC
                          Control power                                                                                          200 VAC Control power supply
                          supply

                                                                                                                                                                    4
                                                                                                                                      K6EL

Connection Examples

Installation on the Electrical Path                                       Installation on a Ground Bus Bar

             Molded case                                                                    Molded case
                                                                                           circuit-breaker
             circuit-breaker           ZCT

Transformer                                                               Transformer

                                                                    Load
                                                                                                                                                                                                           Load

                               kt      lt                      Y/b                     OTG ZCT                                                         Y/b
                                                                                             kt                         Auxiliary relay
                      OTG ZCT      kl                                                               k
                                                                                                                             Y

                                       Auxiliary relay                                           l             5 67     Alarm buzzer
                                                                                           lt
                                           Y                                                                4        8     BZ
                                                                                                ZCT
                                       Alarm buzzer                                                    3             9

                                          BZ                                                                2 1 11 10

                                                                          Ground bus bar               K6EL Ground      100/110 VAC
                                                                                                       Fault Relay      200/220 VAC

                5 67                                                                Do not, under any circumstances, connect the k and l
                                                                                    lines to ground.
             4        8
                                                                          Note: When not using the kt and lt terminals (test terminals), leave
             3        9                                                           them unconnected. The Relay may not be able to attain its
                                                                                  performance characteristics if used with the kt and lt terminals
K6EL         2 1 11 10                                                            connected.
Ground
Fault Relay

                                   100/110 VAC
                                   200/220 VAC

Dimensions

Note: All units are in millimeters unless otherwise indicated.

Ground Fault Relay

                                                                    1  6  78
                                                                                      0.7
                                                                          63.7             13.6

                                       48                                                              44.8 44.8  Applicable Connecting Sockets
                                                           48                                                       P2CF-11 Front Connecting Socket
                                                                                                                    P3GA-11 Back Connecting Socket
                                                                                                                    PL11 Back Connecting Socket

                                                                                                                                                                                                                 5
                                                                                                                                                                                        K6EL

Dimensions with Adapter Mounted

Y92F-30 Flush Mounting Adapter                                               15                                          Panel                                       Mounting Hole
                                                                                                                                                                  Cutout Dimensions
(Sold Separately)                                                                                                                         P3GA-11
                                                                                                                                          Back Connecting Socket
                                                                                                                                                                  R0.5 max.
                                                                                                                                                                              45  +0.5
                                                                                                                                                                                   0

                                                     58                                                                                                           45  +0.5
                                                                                                                                                                       0

                                                                             48                                                                                   Note: Recommended panel
                                                                                       56                                                                                  thickness: 1 to 3.2 mm.

                                                                                                      7                         91.4

Y92F-71 Flush Mounting Adapter                                                                                                  Panel
(Sold Separately)
                                                                                                                                          P3GA-11                        Mounting Hole
                                                                                                                                          Back Connecting Socket      Cutout Dimensions

                                                                                                                                                                  R0.5 max.   45  +0.5
                                                                                                                                                                                   0

                                                                  58 450.2                           68                                                              +0.5
                                                                                                                                                                       0
                                                                                                                                                                  55

                                                                                                                                          91.4                    Note: Recommended panel
                                                                                                                                                                           thickness: 1 to 3.2 mm.

                                                                                  450.2
                                                                                  500.2

Dimensions for Socket Mounting

                                                                                                      Y92F-30

                                                                                                                              P3GA-11

                   K6EL                                                                                K6EL                     (sold separately)
103                                                                                                       +
                                                                             Y92H-1 Hook
                                                     K6EL                                             Adapter

                         77

                                                                                                   7      91.4                         Note: The same dimensions apply
                                                                                                                                               when using the Y92F-71 Adapter.
                                                 16                          PL11
P2CF-11 (sold separately)                                                    (sold separately)

Connecting Sockets

P2CF-11 Front Connecting Socket

                                                     Eleven, M3.57.5                           3              4.5

                                                     sems screws             7.8                                                Terminal Arrangement     Mounting Holes
                                                                                                                                (Top View)               Two, 4.5-dia. holes

                                                                                                                                        8765                  400.2
                                                                                                                                                      4

                         70 max.                                       Two, 4.5-dia.                                    35.4           9          3
                           4                                           holes                          31.2 max.
                                                                                                                                       10 11 1 2
                                                     50 max.

P3GA-11 Back Connecting Socket                                                                                     25.6         Terminal Arrangement
                                                                                                4.5 16.3 6.2                    (Top View)
                                                                    27 dia.
                                                     45                                                                               56 78
                                                                                                                                    4
                                                                      45
                                                                                                                                3         9

                                                                                                                                       2 1 11 10

                                                                                                                                                                                                    6
                                                                                                                                                                                                                                      K6EL

PL11 Back Connecting Socket                                                               4                1                         Terminal Arrangement                                                          Mounting Holes
                                                                                   30 dia.                                           (Bottom View)
                                                                              3.5                                   3.9                                                                                Two, 3.5-dia. holes or
                                                                                                                Two, 2-dia. holes                                                                      two, M3 socket mounting holes
                                                                                                                                                                                  567

                 51 max. 40                                                                                                          4                                                  8

                                                                                                                                     3                                                  9

                                                                                                                                        2                                         1 11  10             31 dia.  400.3
                                                                                                                                                                                                        holes

                                35 max.                                                  Approx. 20.5

Front Cover                                                                        9.3

                         Model
Y92A-48B (Hard Cover)
Y92A-48D (Soft Cover)

ZCT

Indoor Through-type Models
OTG-L21 (50 A)

                                                                                     11                          20       Terminal symbols                                                                Mounting Hole
                                                                                   50                     13              (protrude 0.3 mm)                                                            Cutout Dimensions
                                                                                         Label and caution
                                   6                                                                                                                              kt k l lt             Nameplate            Two, 5.5-dia. holes or
                                66                                                                                                                                                                           two, M5 screw holes
                                                                                                                                                                         21 dia.
                                   6                                                                                                                                                                              64
                                                                                   74
OTG-L30 (100 A)                                                                                   5.2 20

                                                                                   64

                                                                                       9.3

                                                                                      11                              20                                                                    Nameplate        Mounting Hole
                                                                                   63                                                                                                                    Cutout Dimensions
                                                                                                                                Terminal symbols
                                                                                                   6                                                                                                          Two, 5.5-dia. holes or
                                                                                                                      13 (protrude 0.3 mm)                                                                    two, M5 screw holes

                                                                                                                                                                             kt k l lt                               76

                                                                                                    79                               30 dia.                                                              Mounting Hole
                                                                                                                                                                                                       Cutout Dimensions
                                                                                                   6
                                                                                   86                                                                                                                    Two, 5-dia. holes or
                                                                                                                                                                                                         two, M4 screw holes
                                                                                                   5.2 20
                                                                                   76                                                                                                                             97

OTG-L42 (200 A)                                                                              11
                                                                                   9.3

                                                                                                                 5.2

                                                                                   88                                 17

                                                                                                      42 dia.

                                109

OTG-L68 (400 A)                                                                         97                          25
                                                                                   (mounting pitch)
                                                                                                                          6.1                                                                             Mounting Hole
                                                                                       107                                       17                                                                    Cutout Dimensions
                                                                                                     11                                                                                                Two, 5-dia. holes or
                                                                                                               68 dia.                                                                                 two, M4 screw holes
                                                                                          9.3
                                                                                                                                                                                                                   131
                                                                                                118

                                         136

                                                                                         13                               31

                                                                                         (mounting pitch)

                                                                                         143

                                                                                                                                                                                                                                            7
OTG-L82 (600 A)                                                                            11                                                   K6EL
                                                                                9.3
                                                                                                                6.2                   Mounting Hole
                                                                                     138                                    17     Cutout Dimensions
                                                                                                                                Two, 5-dia. holes or
                                                                                                        82 dia.                 two, M4 screw holes

                                                                       158                                                                      160

                                          160 (mounting pitch)                                              28
                                                      172                                                   33

OTG-L156 (1,000 A)                               156 dia.
                                                      L
                                                                                                                 138                      M5 terminal screws
                    263                                                                                     3.2
                                                                                                                                                                        Mounting Hole
                                                    230                                                                                                             Cutout Dimensions
                                                    270
                                                                                                                                                                         Four, 8.5-dia. holes or
                     9                                                                                                                                                   four, M8 screw holes

                                                                                                                                                                                                            90
                                                                                                                                60

                                                                                                                                                                                  230

                                                                                                            90 130

                                                                            20                          40

Indoor Separate-type Models                                                                    52 dia.
OTG-CN52 (200 A)
                                                                                K              M4 terminal screws
                                                            141
                                                                   79           K                                                  Mounting Hole
                                                                                                                                Cutout Dimensions

                                                                                                                                     Two, 6.5-dia. holes or
                                                                                                                                     two, M6 screw holes

                                                                                                                                           170

                                                       170

                    30
                           7
                                                       200

                                                                                                                                                                                                                8
OTG-CN77 (400 A)                               77 dia.                                                                                      K6EL
                                                   K
                                                                                                         M4 terminal screws     Mounting Hole
                                                                                                                             Cutout Dimensions
                               157
                                                                                                84                                Four, 6.5-dia. holes or
                                                                                                                                  four, M6 screw holes
                                                K195
                                               K                                                                                                                53
                                                                                                                                          195

                               70 53

OTG-CN112 (600 A)                         7
                                                        230

                                                                      112 dia.

                                                 K                                                       M4 terminal screws

                               200                                                                                              Mounting Hole
                                     107                                                                                     Cutout Dimensions

                                                                                                                                  Four, 6.5-dia. holes or
                                                                                                                                  four, M6 screw holes

                                                                                                                                                                   53

                                                                                                                                            225

                                               225

                               70 53

                                                                                     7
                                                                                                    260

Maximum Wire Sizes for ZCTs

                                   Wire/cable           600-V vinyl-insulated wire (IV)                                                 Cable (VVR)
                                 Through-hole
         Model         Rated                            2-wire                                           3-wire              2-wire                  3-wire
                      current       diameter
OTG-L21            50 A        21 dia.         22 mm2                                                    14 mm2              8 mm2      5.5 mm2
OTG-L30            100 A       30 dia.         60 mm2                                                    38 mm2              38 mm2     38 mm2
OTG-L42            200 A       42 dia.         100 mm2                                                   100 mm2             100 mm2    60 mm2
OTG-L68            400 A       68 dia.         400 mm2                                                   325 mm2             325 mm2    250 mm2
OTG-L82            600 A       82 dia.         500 mm2                                                   500 mm2             400 mm2    400 mm2
OTG-L156           1,000 A     156 dia.        500 mm2                                                   500 mm2             1,000 mm2  1,000 mm2
OTG-CN52           200 A       52 dia.         200 mm2                                                   200 mm2             150 mm2    100 mm2
OTG-CN77           400 A       77 dia.         500 mm2                                                   400 mm2             400 mm2    325 mm2
OTG-CN112          600 A       112 dia.        500 mm2                                                   500 mm2             1,000 mm2  1,000 mm2

                                                                                                                                                                       9
                                                                                                     K6EL

Test Circuit

Switch              100 VAC                                                   200 mA: 500 , 50 W
                                                                              500 mA: 200 , 100 W
                                                                              1,000 mA: 100 , 200 W

Slidac

           mA                          K6EL

           Ammeter           kt
                                   k
R
                                    l
                             lt

                                  OTC

Select the resistance R shown in the test circuit diagram according to
the K6EL's rated sensed current. Change the current using the slidac
and ascertain the K6EL's operating value each time by reading the
ammeter.

For example, R could take the values shown below:
30 mA: 3.3 k, 6 W
100 mA: 1 k, 20 W

Safety Precautions                                                            Switching the Operating Time

Correct Use                                                                  1. With the K6EL-A100, A200, and A500, the operating time can be
                                                                                  switched using a flat-bladed screwdriver.
Installation and Wiring
                                                                              2. The operating time for the K6EL-30, 100, 200, and 500 is fixed
Do not, under any circumstances, connect the ZCT's output termi-                and hence cannot be switched.
  nals k and l to ground. Doing so may result in damage to the
  Relay's internal circuits.                                                                      Sensed current selection switch
                                                                                        Operating time selection switch
Pass the primary conductor through the ZCT once.
The Relay detects ground faults in internal wiring of devices due to        Testing

  insulation deterioration and so install the ZCT as close to the power       If the ground fault indicator (red) lights when the Relay's test button
  supply side as possible.                                                      is pressed, it means that the internal circuits are operating nor-
                                                                                mally.
ZCT Installation
                                                                               To make an overall test, run a simulated ground fault current.
Install the ZCT at an outdoor cable inlet or on a ground bus bar at a
  location allowing easy inspection.                                          Resetting

When installing on the electrical path, use a ZCT with a value               Once manual-reset models operate, they continue to operate until
  greater than the electrical path's rated current.                             they are reset. Reset them either by pressing the reset button
                                                                                (black) or by turning the control power supply OFF and ON again.
If the secondary lines run in parallel to a circuit carrying a large cur-
  rent, either separate the lines as far as possible or use a shield line.    Automatic-reset models reset automatically when the ground fault
                                                                                is cleared (i.e., the current drops below the sensed current).
                        Run the secondary lines
                        close to each other.
      ZCT

                                                              K6EL

                              Primary conductor
Separate by 20 cm min.

                                              Circuit carrying large current

When installing a separate-type ZCT with current flowing along the
  primary conductors, short the secondary terminals using clips or
  some other method.

Switching the Sensed Current

1. With the K6EL-@100, 200, and 500 the sensed current can be
    switched using a flat-bladed screwdriver.

2. The sensed current for the K6EL-30 is fixed and hence cannot be
    switched.

                                                                                                                                                         10
                                                                                                                                  K6EL

Q&A

Q: How does the K6EL operate when used for inverter loads (e.g., inverter motors and inverter air conditioners)?

A: The influence of high-frequency noise generated by the inverter has been reduced by combining a special ground
    fault relay IC and a capacitor for cutting out high-frequencies. The possibility of malfunctions due to the influence
    of the inverter is much less than with the existing ESA Ground Fault Relay.

R

S           Inverter                         M

T

                                         Rg
            K6EL

Q: What connection method should be used for ungrounded electrical paths?

A: With ungrounded electrical paths, connect the capacitor or resistor for detection in the way shown in the diagram.
    The table shows the formulas for calculating the resistance or capacitance as well as the formulas for calculating
    ground currents for complete ground faults. (Depending on the location, the allowable ground fault current may be
    restricted. In this case, use values of R and C that do not exceed the restrictions.)

                             Connection method                  Formula for resistor or capacitor  Formula for ground              Formula for
                                                                                                           current                safety ground

                                                                                                                                        fault

Single-                                                         Resistor:   It: Ground Fault

phase       Isolating        OTG ZCT                            R= V ()         Relay's set
electrical                                                           2It        value
path        transformer                                                                                 Ig= V (A)                 Ig= V (A)
                                                                P=5V2 (W)   V: Line voltage                  2Rg + R                   R
                                                 Y/b      Load       R
                                                                            f: Frequency
            Resistor (R) or  kt l k lt
                                                                            P: Allowable
            capacitor (C)                             Rg                        power for the
                                                                                resistor used
                                             K6EL Y             Capacitor:

                                             Ig                 C= 2It (F)  (A tolerance is                      V
                                                                            included in the
                                                                2fV                                Ig=                       (A)  Ig = 2fCV (A)
                                                                            formulas on the                          1
                                                                                                        (2Rg)2+  (  2fC  )2
                                                                Dielectric strength left.)

                                                                > 2 V (V)

            ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
            To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                              In the interest of product improvement, specifications are subject to change without notice.

                                                                                                                                                 11
                                                       Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.

                                                      Warranty and Limitations of Liability

WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.

In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

                                                            Application Considerations

SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.

At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:

       Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.

       Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
           safety equipment, and installations subject to separate industry or government regulations.

       Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.

                                                                       Disclaimers

CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.

DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.

ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.

OMRON Corporation                                                                                                                                        2009.5
                               In the interest of product improvement, specifications are subject to change without notice.
Industrial Automation Company
                                                                                   (c)Copyright OMRON Corporation 2009 All Right Reserved.
http://www.ia.omron.com/
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

器件索引   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2020 EEWORLD.com.cn, Inc. All rights reserved