电子工程世界电子工程世界电子工程世界

关键词

搜索

型号

搜索
 

UMP1T-S2E-S2E-S2E-S2L-S2L-63-A

器件型号:UMP1T-S2E-S2E-S2E-S2L-S2L-63-A
器件类别:电源/电源管理   
厂商名称:Artesyn
厂商官网:http://www.artesyn.com
标准:
下载文档

器件描述

UMP CONFIGURABLE POWER SUPPLY

文档预览

Embedded Power for
Business-Critical Continuity
µMP Series
Up to 1200 Watts
Total Power:
Up to 1200 Watts
Input Voltage:
85 - 264 Vac
120-300 Vdc
# of Outputs:
Up to 12
MicroMP 1U Multi Output
Rev. 12.12.2013
µMP
Series
1 of 6
Special Features
Full Medical EN60601 approval
• PMBus
• High efficiency
• Current limit modification
(foldback or constant current)
• High power density.
uMP4: 10.8 W/cu-in
uMP1: 15.1 W/cu-in
• Intelligent fan
(speed control/fault status)
• Downloadable GUI from website
• uP controlled PFC input with active
inrush protection
• Optional conformal coating
• Industrial temp range (-40 ºC
to 70
ºC)
• No preload required
• Industrial shock/vibration (> 50G’s)
• Low cost
• IEC or terminal block input
• Low profile 1U size
Electrical Specifications
Input
Input range:
Frequency:
Inrush current:
Efficiency:
Power Factor:
Turn-on time:
EMI filter:
Leakage current:
Radiated EMI:
Holdover storage:
AC OK:
Harmonic distortion:
Isolation:
Input fuse (internal):
Warranty:
47 - 440 Hz
40 A peak max. (soft start)
Up to 91% @ full case load
µMP4C shown
85 - 264 Vac, 120 - 350 Vdc (limited to 250 Vac/300 Vdc in medical apps)
0.99 typ. meets EN61000-3-2 (n/a @ 440 Hz)
AC on 2 sec for uMP1 and 1.5 sec for uMP4, inhibit/enable 250 ms typical
CISPR 22/EN55022 Level “B”
300 µA Max. @ 240 VAC
CISPR 22/EN55022 Level “B”
16.7 ms minimum (independent of input Vac, 0 °C to 50 °C))
Signal goes low indicating loss of AC input.
Hold up = Full cycle ride thru (50 Hz)
Meets EN61000-3-2
Meets EN60950 and EN60601
uMP1: 16 A/250 V TLAG, uMP4: 10 A / 250 V. (both lines fused)
2 years
Global Inhibit/Enable: TTL, Logic “1” and Logic “0”; fan off when unit is inhibited
Environmental Specifications
Safety
UL
CSA
VDE
BABT
UL60950/UL60601-1
CSA22.2 No. 234 Level 5
EN60950/EN60601-1
Compliance to
EN60950/EN60601 BS7002
Certificate and report
Mark to LVD
Approved
-40 ° to 70 °C ambient. Derate each output 2.5% per degree from 50 °C to 70 °C.
( -20 °C start up). Meets full spec after 1/2 load. 10 min warm-up
Storage temperature:
-40 °C to 85 °C
Electromagnetic susceptibility:
Designed to meet EN61000-4; -3, -5, -6, -11 Level 3, Level 4 for -2, -4
Humidity:
Operating; non-condensing 10% to 95% RH
Vibration:
MIL-STD-810E
MTBF demonstrated:
> 350,000 hours at full load, one uMP4 case + two modules, Telcordia SR-332
calculated MTBF
Altitude:
Up to 10k feet; derate linear to 50% from 10k-30k feet
Operating temperature:
CB
CE
CCC
Embedded Power for
Business-Critical Continuity
Output
Factory set point accuracy: ± 1%
Margining:
Overall regulation:
Ripple:
± 3 - 7% nominal analog (single output module only)
0.4% or 30 mV which ever is greater.
Rev. 12.12.2013
µMP
Series
2 of 6
RMS: 0.1% or 10 mV, whichever is greater
Pk-Pk: 1.0% or 50 mV, whichever is greater. Bandwidth limited to 20 MHz
Dynamic response:
< ± 5% or 250 mV, with 50% step load
Recovery time:
To within 1% in < 300 µsec
Reverse voltage protection: 100% of rated output current
Thermal protection:
(OTP)
Remote sense:
Single wire parallel:
DC OK:
Minimum load:
Housekeeping standby:
Module inhibit:
Output/Output isolation:
Vout
3V3 Module
0.9
3.3
3.6
40
40
40
36
36
30
25
20
16
13
10
8
7
5
4
2.00 V
5.96 V
6.31 V
5.76 V
9.00 V
10.80 V
10.80 V
15.60 V
19.50 V
15.60 V
31.20 V
39.00 V
36.40 V
62.40 V
78.00 V
130%
130%
130%
130%
130%
130%
130%
130%
130%
130%
130%
130%
130%
130%
130%
160%
160%
160%
160%
160%
160%
160%
160%
160%
160%
160%
160%
200%
160%
200%
150
250
250
250
250
300
300
600
750
600
1200
1500
1400
2400
3000
± 250
± 250
± 250
± 250
± 250
± 300
± 300
± 600
± 750
± 600
± 1200
± 1500
± 1400
± 2400
± 3000
All outputs disabled when internal temp exceeds safe operating range.
Up to 0.5 V total drop (not available on triple output module)
Current share to within 5% of total rated current
± 5% of nominal.
Not required
5 Vdc @ 1.0 A max. present whenever AC input is applied
Logic - output on with low or open. Different logic options available
> 1 Megohm, 500 V
Full load
(A)
OVP trip max
(V)
OCP trip typ (I-
out%)
SCP trip max (I-
out%)
Overshoot (max
mV)
Peak Deviation
(max mV)
5 V Module
3.2
5
6
12 V Module
6
12
15
24 V Module
12
24
30
48 V Module
28
48
60
Case Line-Up
Case
µMP4 - 4 Slot
µMP1 - 6 Slot
Max Output
400 W - 600 W
1000 W - 1200 W
Dimensions
256.9
±0.8 x
88.9
±0.5 x
40.0
±0.7
(10.11” x 3.5” x 1.57”)
256.9
±0.8 x
127
±0.5 x
40.0
±0.5
(10.11” x 5” x 1.57”)
Connections
IEC/Terminal Block
IEC/Terminal Block
Max Current Amps
9.91
13.87
Output Module Line-Up
Output Range
(Vdc)
0.9 - 3.6
3.2 - 6.0
6.0 - 15.0
12.0 - 30.0
28.0 - 54.0
5.0 - 28.0
5.0 - 28.0
Max Current
(Amps)
40
36
25
13
7
4
4
Max Power
(Watts)
144
180
240
240
240
96
96
Module Codes
Standard Outputs
A, B, C, D - 2, 2.2, 3, 3.3
E, F, G, H - 5, 5, 2, 5.5, 6
I, J, K, L, M, N - 8, 10, 11, 12, 14, 15
O, P, Q, R, S - 18, 20, 24, 28, 30
T, U, V, W, X, Y - 28, 30, 33, 36, 42, 48, 54, 60
Dual Output Module. Each output is rated to 96W (192
Watts total). Wide range is adjustable.
Embedded Power for
Business-Critical Continuity
Ordering Info
Case Size
Module/Voltage/Option Codes
Case Option Codes
Software Code
Rev. 12.12.2013
µMP
Series
3 of 6
Hardware Code
µMPXY
Case Size
Single - Phase Input where
X
=
4 = 1.57” x 3.5” x 10”; 400 W - 600 W, 4 Slots
1 = 1.57” x 5” x 10”; 1000 W - 1200 W, 6 Slots
Input Type where
Y
=
T = Terminal Block
C = IEC Connector, C14
B = IEC Connector, C16
-
S2E
-
DER
-
DLL
-
00
Case Option Codes
First digit
0 - F = Parallel Code
Second digit
0 = No Options
1 = Reverse Air
3 = Global Enable
5 = Opt 1 + Opt 3
-
A
Factory assigned
for modified
standards
-
###
Factory assigned
for modified
standards
Module Codes
S2 = 200 W Single O/P (1 slot)
D = 96 W/96 W Dual O/P Common
Ground (1 slot)
I = 96 W/96 W Dual O/P Isolated
Ground (1 slot)
Voltage Codes:
See Voltage Code Table
Parallel Codes
Code
1
2
3
4
5
Slots in Parallel
1&2
2&3
3&4
4&5
5&6
Code
6
7
8
9
A
Slots in Parallel
1,2&3
1,2,3&4
1,2,3,4&5
1,2,3,4,5&6
1&2; 3&4
Code
B
C
D
E
F
Slots in Parallel
1,2&3; 4&5
1,2,3&4; 5&6
1&2; 3&4; 5&6
1,2&3; 4,5&6
2&3; 4&5
Code
0
Slots in Parallel
no module in
parallel
Application Notes
(Only for Output Voltages 14.0V-24.0V)
1. Units should not be operated in parallel
2. In a single unit, parallel modules should
not be
individually inhibited
3.Total load capacitance should not exceed
2000uF
Voltage Codes
Standard Output Ratings
Module Output
Voltage Code
Module Identification
Single Output ONE SLOT
240 Watts Max
S2
Derating Curves - µMP1
Dual Output ONE SLOT
192 Watts Max
D = Dual Common Ground
I = Dual Isolated Ground
Output Module Line-Up
Code
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
* For “I” codes only
Volts
2.0 V
2.2 V
3.0 V
3.3 V
5.0 V
5.2 V
5.5 V
6.0 V
8.0 V
10.0 V
11.0 V
12.0 V
14.0 V
15.0 V
18.0 V
20.0 V
24.0 V
28.0 V
30.0 V
33.0 V
36.0 V
42.0 V
48.0 V
54.0 V
60.0 V
Output Current
V1
40.0
40.0
40.0
40.0
36.0
34.0
32.0
30.0
25.0
24.0
22.0
20.0
17.0
16.0
13.0
12.0
10.0
8.6
8.0
7
6.7
5.7
5.0
4.4
4.0
Output Current
V1
V2
N/A
N/A
N/A
4.0*
4.0*
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
3.4
3.4
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Embedded Power for
Business-Critical Continuity
µMP4
(AC input on opposite side)
S
L
O
T
S
L
O
T
S
L
O
T
S
L
O
T
J2
S2 Module
Rev. 12.12.2013
µMP
Series
4 of 6
DC Output Control & Signals
(Single output)
Pin
1
2
3
4
5
6
7
8
9
10
Function
No connection
No connection
Current share
Module inhibit return
Module ISO inhibit
SCOM
-RMT sense
Margin
Remote margin / V prog.
+RMT sense
29.8±0.2
37.5±0.3
32.5±0.3
36.5±0.3
CAPS HEIGHT
12.5 MAX
3.0 MAX
0.8 - 1.5
1.6±0.16
4
3
2
1
J1
Input
µMP4 =4 available slots
400 W max.
85-264 Vac
600 W max.
200-264 Vac
240 W
µMP1
(AC input on opposite side)
S
L
O
T
6
S
L
O
T
5
S
L
O
T
4
S
L
O
T
3
S
L
O
T
2
S
L
O
T
1
J2
5.3±0.5
1.0±0.25
V ADJ
J1
V+
V-
36.5±0.3
Input
4.5±0.3
µMP1 = 6 available slots
1000 W max.
85-264 Vac
1200 W max.
200-264 Vac
Pin Connectors
Figure 1.
AC Input
AC Input
Pin
1
2
3
J1
130.0±1.5
1
2
9
10
IEC Connector
Terminal Block
PE N L
Function
AC neutral
AC line (hot)
Chassis (earth) ground
Function
Input AC OK - “emitter”
Input AC OK - “collector”
Global DC OK - “emitter”
Global DC OK - “collector”
Spare
Global inhibit/optional enable logic “1”
Global inhibit/optional enable logic “0”
Global inhibit/optional enable return
+5 VSB housekeeping
Dual Module
DC Output Control & Signals
(Dual output)
Pin
1
2
3
4
5
6
7
8
9
10
Function
-RMT sense V2
+RMT sense V2
No connection
Module inhibit rtn
Module ISO inhibit
SCOM
-RMT sense V1
No connection
No connection
+RMT sense V1
PFC Input Connector (control & signals)
Pin
1
2
3
4
5
6
7
8
9
Figure 2.
Connector J1 & J2
10
+5 VSB housekeeping return
J2
I
2
C Bus Output Connector
Pin
1
2
3
4
5
6
7
8
9
10
Function
5 Vcc bus
Serial data signal (SDA)
Secondary return (COM)
Serial clock signal (SCL)
Address bit 2 (A2)
No connection
Address bit 1 (A1)
No connection
Address bit 0 (A0)
No connection
1
2
9
10
Mates with
Landwin 2050S1000 Housing
2053T011V Pin
or
JST PHDR-10VS Housing
JST SPHD-002T-P0.5 (28-24)
JST SPHD-001T-P0.5 (26-22)
Connector Kit Part No.:
70-841-023
Embedded Power for
Business-Critical Continuity
µMP
Series
µMP4
(400/600 Watts Max)
Case Size: µMP4: 10.11” x 3.5” x 1.57” (256.9mm x 88.9mm x 40.0mm)
Weight: µMP4 Case: 1.96 lbs • Single O/P: 0.22 lb. • Dual O/P: 0.16 lb.
• Blank: 0.06 lb.
Rev. 12.12.2013
µMP
Series
5 of 6
Forward Airflow
Notes:
1. Input: IEC 60320 C13 (for IEC connector)
Barrier Type DECA Switchlab MT300-50003 (for terminal block connector); Max Torque: 4.0 lb-in (0.4-0.5 Nm); Wire: 12-16 AWG;
Wire Strip Length: 0.354" (9.0 mm)
2. Control Connectors (J1 and J2): 10-position housing, brass, matte tin-plated contacts.
Mates with housing 2050S1000 (Landwin) with 2053T011P (Landwin) pins or housing PHDR-IOVS (JST) and SPHD-002T-PO.5 (JST) pins.
3. Output Module Connectors: All single O/P modules are M4 x 10mm screws; Max. Torque: 6.94 to 8.68 lb-in (0.785 to 0.981 N-m).
Dual O/P module is PUSH IN conductor connector; Wire Strip Length: 0.315" (8.0 mm); Control signal connector: Refer to Item 2.
4. Chassis Material: Steel with chemical film coating (conductive).
5. Customer Mounting: Screw M4-type mounting holes; Max. Penetration is 0.138" (3.5 mm); Max. Torque: 8.85 lb-in (1.0 N-m)
6. All dimensions are in millimeters and inches, and are typical.
Forward Airflow

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

器件索引   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
搜索索引   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京B2-20211791 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号 Copyright © 2005-2021 EEWORLD.com.cn, Inc. All rights reserved