TCU01005

器件型号:TCU01005
器件类别:热门应用    测试测量   
厂商名称:Red Lion Controls, Inc.
厂商官网:http://www.redlion.net/
标准:  
下载文档

器件描述

W/analog cooling & rs485 comm

参数

Datasheets:
TCU Model:
3D Model:
TCU.dwg:
Standard Package : 1
Category: Industrial Controls, Meters
Family: Controllers - Process, Temperature
Series: TCU
Type: Temperature Controller (RTD, Type B, E, J, K, N, R, S, T)
Input Range: -200°C ~ 1820°C, -5 ~ 56mV
Output Type: Analog (2), Option Cards Available
Control Method: On/Off, Proportional (PID)
Communications: RS-485
Number Of Characters Per Row: 4, 4
Display Type: LED - Dual Color Characters
Display Characters - Height: 0.401" (10.20mm), 0.299" (7.60mm)
Voltage - Supply: 115/230VAC
Panel Cutout Dimensions: Rectangular - 92.00mm x 45.00mm
Mounting Type: Panel Mount
Termination Style: Screw Terminal
Ingress Protection: -
Operating Temperature: 0°C ~ 50°C
Features: -
Weight: 1.3 lbs (589.7g)
Associated Product: RLY70000-ND - RELAY SSR SPST-NO DINRLY6A000-ND - RELAY SSR SPST-NO 40A DINRLY60000-ND - RELAY SSR SPST-NO 25A DINRLY50000-ND - RELAY SSR SPST-NO 45AOMD00003-ND - SSR DRIVE MODULEOMD00001-ND - TRIAC MODULEOMD00000-ND - RELAY MODULECT005001-ND - 50 0.1A FOR USE WITH TCU/PCUCT004001-ND - 40 0.1A FOR USE WITH TCU/PCU

TCU01005器件文档内容

                                                                                                                Bulletin No. TCU-H
                                                                                                                Drawing No. LP0314
                                                                                                                Released 08/13

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

MODEL TCU - TEMPERATURE CONTROL UNIT

C UR L US LISTED                                                                  SELF-DIAGNOSTICS
                            IND. CONT. EQ.
                                      51EB                                        FULL PID CONTROL WITH REDUCED OVERSHOOT

100 msec SAMPLING PERIOD WITH 0.15% ACCURACY                                     OPTIONAL RS485 SERIAL COMMUNICATIONS INTERFACE

ON DEMAND AUTO-TUNING OF PID CONTROL SETTINGS                                    OPTIONAL DUAL ALARM OUTPUTS (USES OUTPUT MODULES)

DUAL LED DISPLAYS FOR SIMULTANEOUS INDICATION OF                                 OPTIONAL COOLING OUTPUT (USES OUTPUT MODULE)
   TEMPERATURE AND SETPOINT, SECOND ANALOG INPUT OR
   HEATER CURRENT                                                                 OPTIONAL LINEAR 4 to 20 mA or 0 to 10 VDC OUTPUT FOR
                                                                                    CONTROL OR TEMPERATURE RE-TRANSMISSION
ACCEPTS 10 DIFFERENT TYPES OF SENSOR INPUTS
   (Thermocouple or RTD)                                                          OPTIONAL HEATER CURRENT MONITOR AND BREAK ALARM

                                                                                  OPTIONAL MOTORIZED VALVE POSITION CONTROL AND
                                                                                    VALVE FAIL ALARM

                                                                                  OPTIONAL SECOND ANALOG INPUT FOR REMOTE SETPOINT
                                                                                    AND CASCADE CONTROL

                                                                                  OPTIONAL TYPE 4X/IP65 SEALED FRONT BEZEL

                                                                                  STATUS INDICATORS FOR OUTPUTS AND CONTROL MODES

                                                                                  PROGRAMMABLE USER INPUT (DIGITAL) FOR ADDED
                                                                                    FLEXIBILITY

                                                                                  SENSOR ERROR COMPENSATION (Slope and Offset) AND
                                                                                    BREAK DETECTION

                                                                                  MANUAL/AUTOMATIC AND LOCAL/REMOTE SETPOINT
                                                                                    CONTROL MODES

                                                                                  SETPOINT RAMPING FOR PROCESS STARTUP

                                                                                  PARAMETER SECURITY VIA PROGRAMMABLE LOCKOUTS

                                                                                  FIELD REPLACEABLE AND INTERCHANGEABLE OUTPUT
                                                                                    MODULES (Relay, Logic/SSR Drive and Triac)

DESCRIPTION                                                                         Dual 4-digit displays allow viewing of the process temperature and setpoint
                                                                                 simultaneously. Front panel indicators inform the operator of the controller and
   The TCU Controller accepts signals from a variety of temperature sensors      output status. Replaceable and interchangeable output modules (relay, SSR
(thermocouple or RTD elements), precisely displays the process temperature,      drive, or triac) can be installed for the main control output, alarm output(s) and
and provides an accurate output control signal (time proportional or linear) to  cooling output.
maintain a process at the desired control point. A comprehensive set of easy to
use steps allows the controller to solve various application requirements.          Optional dual alarms can be configured to activate according to a variety of
                                                                                 actions (Absolute HI or LO, Deviation HI or LO, Band IN or OUT, Heater
   The controller can operate in the PID control mode for both heating and       Break and Valve Fail Detect) with adjustable hysteresis. A standby feature
cooling, with on-demand auto-tune, which will establish the tuning constants.    suppresses the output during power-up until the temperature stabilizes outside
The PID tuning constants may be fine-tuned by the operator at any time and then  the alarm region. An optional secondary output is available (for processes that
locked out from further modification. The controller employs a unique overshoot  require cooling) which provides increased control accuracy and response.
suppression feature, which allows the quickest response without excessive
overshoot. The unit can be transferred to operate in the manual mode, providing
the operator with direct control of the output. The controller may also be
programmed to operate in the ON/OFF control mode with adjustable hysteresis.

DIMENSIONS In inches (mm)                   Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 5.5" (140) H x 2.1" (53.4) W.

                                              5.41                                               PANELCUT-OUT
                                            (137.4)

                                                                                                 1.77  +.02
                                                                                                       -.00

                                                                                                 (45.0 +-..60)

                       %PW MAN AL1   3.80                                         3.60           3.62           +.03
                       DEV OP1 AL2  (96.5)                                       (91.4)                         -.00

                        DSP                                                                      (92.0 +-..80)

                        PAR

                        1.95          .40     5.29                                        1.75
                       (49.5)       (10.2)  (134.4)                                      (44.4)

                                                           11
DESCRIPTION (Cont'd)                                                                     "SLid" - Appears when loss of slidewire signal is detected.

OPTIONS                                                                                  "VALV" - Appears when valve actuator error is detected.
   A linear 4 to 20 mA or 0 to 10 VDC output signal is available to interface
                                                                                         2. POWER: Switch selectable for 115/230 VAC (+10%, -15%) no observable
with actuators, chart recorders, indicators, or other controllers. The output signal
can be digitally scaled and selected to transmit one of the following: % output          line variation effect, 48 to 62 Hz, 10 VA
power, process temperature value, process temperature value deviation or
setpoint value. For Linear DC control applications, the adjustable output                3. ANNUNCIATORS:
demand dampening, output deadband and output update time parameters
expand the versatility of the TCU with final control devices.                            LED Backlight Status Indicators (Model dependent):

   The optional Heater Current Monitor serves as a digital ammeter for heater            %PW - Lower auxiliary display shows power output in (%).
current monitoring. Current transformer accessory (CT005001), is required. An
alarm event output can be programmed to signal when the heater or heater                 DEV         - Lower auxiliary display shows deviation (error)
control devices have failed, before damage to process material occurs. The
Heater Break alarm triggers under two conditions:                                                    from temperature setpoint.
1) The main output (OP1) is "on" and the heater current is below the heater
                                                                                         OP1         - Main control output is active.
   current alarm value, indicating an aged or failed heater.
2) Output (OP1) is "off" and the heater current is more than 10% of the alarm            AL1         - Alarm #1 is active.

   value, indicating a shorted heater control device or other problem.                   AL2         - Alarm #2 is active (for Dual Alarm Option).

   The optional Motorized Valve Positioner directly controls the position of a           OP2         - Cooling output is active (for Cooling Option).
valve by the use of twin outputs (open and close) to control the direction of
motor rotation. The motor position defines the opening position of the valve.            OPN         - Valve positioner OPEN output is active
Two control modes are possible: position control, which makes use of the
slidewire feedback signal supplied with the positioner and velocity control, in                      (for Valve Positioner option).
which no slidewire feedback signal is used. Parameters are provided to adjust
the operation of the valve. These include:                                               CLS         - Valve positioner CLOSE output is active

             Valve activity hysteresis                                                               (for Valve Positioner option).
             Valve update time
             Variable control dampening                                                  CUR         - Lower auxiliary display shows heater current
             Slidewire signal fail action
             Adjustable valve position limits.                                                       (for Heater Current Monitor option).
   The valve positioner TCU achieves tight process control, yet minimizes
unnecessary valve activity. An alarm event output or display alarm can be                SEC         - Lower auxiliary display shows second analog input
programmed under loss of slidewire feedback or under valve fail detection.
   The optional Second Analog Input (0-20 mA DC) can be configured as a                              (For Second Analog Input option).
remote setpoint signal or as a secondary process signal. Configuration of the
second analog input as a remote setpoint signal allows ratio control, master             MAN         - Flashing: Controller is in manual mode.
setpoint/multiple slave operation, and the ability to cascade the TCU with
another controller (external cascade). Configuration of the second input as a            REM         - ON: controller is in remote setpoint mode
secondary process signal allows operation as a two-process cascade controller
within a single unit (internal cascade). In either control mode, parameters are                      (Second Analog Input option).
provided to scale, configure, communicate and monitor the activity of both
analog inputs. A square law linearizer function can be used to linearize signals                     - OFF: controller is in local setpoint mode
derived from flow transmitters.
   The optional RS485 multidrop serial communication interface provides two-                         (Second Analog Input option).
way communication between a TCU unit and other compatible equipment such
as a printer, a programmable controller, or a host computer. In multipoint                           - Flashing: controller is in Manual control mode
applications the address number of each unit on the line can be programmed from
0-99. Up to thirty-two units can be installed on a single pair of wires. The                         (Second Analog Input optional).
Setpoint value, % Output Power, Setpoint Ramp Rate, etc. can be interrogated or
changed by sending the proper command code via serial communications. Alarm              4. CONTROLS: Four front panel push buttons for modifying and setup of
output(s) may also be reset via the serial communications interface option.
   An optional Type 4X/IP65 rated bezel is available for wash down and/or dirty          controller functions and one external input for parameter lockout or other
environments, when properly installed. Modern surface-mount technology,
extensive testing, plus high immunity to noise interference makes the controller         functions.
extremely reliable in industrial environments.
                                                                                         5. MAIN SENSOR INPUT:

                                                                                         Sample Period: 100 msec

                                                                                         Response Time: 300 msec (to within 99% of final value w/step input;

                                                                                         typically, response is limited to response time of probe)

                                                                                         Failed Sensor Response:

                                                                                         Main Control Output(s): Programmable preset output

                                                                                         Display: "OPEN"

                                                                                         Alarms: Upscale drive

                                                                                         DC Linear: Programmable preset output

                                                                                         Normal Mode Rejection: 40 dB @ 50/60 Hz (improves with increased

                                                                                         digital filtering.

                                                                                         Common Mode Rejection: 100 dB, DC to 60 Hz

                                                                                         Protection: Input overload 120 VAC for 30 seconds.

                                                                                         6. THERMOCOUPLE:

                                                                                         Types: T, E, J, K, R, S, B, N, Linear mV

                                                                                         Input Impedance: 20 M  all types

                                                                                         Lead resistance effect: 20 V/350

                                                                                         Cold junction compensation: Less than 1C error over 0 - 50C ambient

                                                                                         temperature range. Disabled for Linear mV type.

                                                                                         Resolution: 1C/F all types, or 0.1C/F for T, E, J, K, and N only.

                                                                                         7. RTD: 2, 3 or 4 wire, 100  platinum, alpha = 0.00385 (DIN 43760),

                                                                                         alpha = 0.003916

                                                                                         Excitation: 0.175 mA

                                                                                         Resolution: 1 or 0.1 degree

                                                                                         Lead Resistance: 7  maximum

                                                                                         8. RANGE AND ACCURACY:

                                                                                         Errors include NIST conformity and A/D conversion errors at 23C after 20

                                                                                         min. warm-up. Thermocouple errors include cold junction effect. Errors are

SAFETY SUMMARY                                                                           expressed as percent of reading and 3/4 LSD unless otherwise noted.

   All safety related regulations, local codes and instructions that appear in the       TC TYPE             RANGE           ACCURACY                  WIRE COLOR
manual or on equipment must be observed to ensure personal safety and to                                                                                    (ANSI)
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection               T       -200 to +400C         0.20% + 1.5C               blue
provided by the equipment may be impaired.                                                            -328 to +752F         0.20% + 2.7F               violet
                                                                                              E                                                          white
   Do not use the TCU to directly command motors, valves, or other actuators                           -200 to 750C         0.20% + 1.5C              yellow
not equipped with safeguards. To do so, can be potentially harmful to persons                 J      -328 to +1382F         0.20% + 2.7F               black
or equipment in the event of a fault to the unit. An independent and redundant                        -200 to +760C         0.15% + 1.5C               black
temperature limit indicator with alarm outputs is strongly recommended. The                   K      -328 to +1400F         0.15% + 2.7F               grey
indicators should have input sensors and AC power feeds independent from                             -200 to +1250C         0.20% + 1.5C              orange
other equipment.                                                                              R      -328 to +2282F         0.20% + 2.7F
                                                                                                                             0.15% + 2.5C                  __
SPECIFICATIONS                                                                                S        0 to +1768C          0.15% + 4.5F                  __
1. DISPLAY: Dual 4-digit                                                                              +32 to +3214F         0.15% + 2.5C
                                                                                              B                              0.15% + 4.5F                  __
Upper Temperature Display: 0.4" (10.2 mm) high red LED                                                 0 to +1768C          0.15% + 2.5C                  __
                                                                                              N       +32 to +3214F         0.15% + 4.5F
Lower Auxiliary Display: 0.3" (7.6 mm) high green LED                                        mV      +200 to +1820C         0.20% + 1.5C
                                                                                            RTD      +300 to +3308F         0.20% + 2.5F
Display Messages (Model dependent):                                                         (385)    -200 to +1300C         0.15% + 1 LSD
                                                                                            RTD      -328 to +2372F
"OLOL" - Appears when measurement exceeds + sensor range.                                   (392)      -5.00 to 56.00        0.10% + 0.5C
                                                                                           OHMS                              0.10% + 0.9F
"ULUL" - Appears when measurement exceeds - sensor range.                                             -200 to +600C
                                                                                                     -328 to +1100F         0.10% + 0.5C
"OPEN" - Appears when open sensor is detected.                                                                               0.10% + 0.9F
                                                                                                      -160 to +600C
"SHrt" - Appears when shorted sensor is detected (RTD only)                                          -256 to +1100F         0.15% + 1 LSD

"...."  - Appears when display values exceed + display range.                                           1.0 to 320.0

"-..."  - Appears when display values exceed - display range.

                                                                                      2
9. OUTPUT MODULES [Optional] (For All Output Channels):                                Alarm mode: Dual acting; loss of slidewire feedback signal and valve fail
   Relay:                                                                                 detection
      Type: Form-C (Form-A with some models. See Ordering Information.)
      Rating: 5 Amps @ 120/240 VAC or 28 VDC (resistive load), 1/8 HP @             15. SECOND ANALOG INPUT:
         120 VAC (inductive load)                                                      Range: 0 to 20 mA (Isolated from main input)
      Life Expectancy: 100,000 cycles at max. load rating. (Decreasing load            Overload: 100 mA (steady state)
         and/or increasing cycle time, increases life expectancy).                     Input Resistance: 10
   Logic/SSR Drive: Can drive multiple SSR Power Units.                                Voltage Drop (@ 20 mA): 0.2 V
      Type: Non-isolated switched DC, 12 VDC typical                                   Accuracy: 0.15% of reading 10 A 1 LSD
      Drive: 45 mA max.                                                                Scale Range: -999 to 9999
   Triac:
      Type: Isolated, Zero Crossing Detection                                       16. SERIAL COMMUNICATION:
      Rating:                                                                          Type: RS485 Multi-point, Balanced Interface
         Voltage: 120/240 VAC                                                          Communication Format:
         Max. Load Current: 1 Amp @ 35C                                                  Baud Rate: Programmable from 300 to 9600
         0.75 Amp @ 50C                                                                  Parity: Programmable for odd, even, or no parity
         Min. Load Current: 10 mA max.                                                    Frame: 1 start bit, 7 data bits, 1 or no parity bit, 1 stop bit
         Offstate Leakage Current: 7mA max. @ 60 Hz                                       Unit Address: Programmable from 0 to 99, max. of 32 units per line
      Operating Frequency: 20 to 400 Hz                                                Transmit Delay: 100 msec min., 200 msec max.
      Protection: Internal Transient Snubber, Fused                                    RS485 Common: Isolated from signal input common
                                                                                       Auto Print Time: Off to 9999 seconds between print-outs
10. MAIN CONTROL OUTPUT (Heating or Cooling):
   Control: PID or ON/OFF                                                           17. USER INPUT (Optional): Internally pulled up to +5 VDC.
   Output: Time proportioning or linear DC                                             VIN MAX = 5.25 VDC, VIL = 0.85 VMAX; VIH = 3.0 VMIN,
   Hardware: Plug-in, replaceable output modules                                       Available on all second input (HCM, MVP & ANA) models, and on models
   Cycle time: Programmable                                                               with RS485.
   Auto-tune: When selected, sets proportional band, integral time, and                Response Time: 100 msec max.
      derivative time values.                                                          Functions: Program Lock
   Probe Break Action: Programmable                                                                  Integral Action Lock
                                                                                                     Auto/Manual Mode Select
11 . COOLING OUTPUT (Optional):                                                                      Setpoint Ramp Select
   Control: PID or ON/OFF                                                                            Reset Alarms
   Output: Time proportioning or linear DC                                                           Print Request
   Hardware: Plug-in, replaceable output modules                                                     Local/Remote Setpoint Select
   Cycle time: Programmable
   Proportional Gain Adjust: Programmable                                           18. ALARMS (Optional):
   Heat/Cool Deadband Overlap: Programmable                                            Hardware: Plug-in, replaceable output module
                                                                                       Modes: Absolute high acting
12. LINEAR DC OUTPUT (Optional): With digital scale and offset,                                  Absolute low acting
   programmable deadband and update time.                                                        Deviation high acting
   4 to 20 mA:                                                                                   Deviation low acting
      Resolution: 1 part in 3500 typ.                                                            Inside band acting
      Accuracy: (0.1% of reading + 25 A)                                                       Heater break
      Compliance: 10 V (500  max. loop impedance)                                                Valve fail
   0 to 10 VDC:                                                                                  Second Analog Input monitoring
      Resolution: 1 part in 3500 typ.                                                  Reset Action: Programmable; automatic or latched
      Accuracy: (0.1% of reading + 35 mV)                                             Standby Mode: Programmable; enable or disable
      Min. Load Resistance: 10 K (1 mA max.)                                           Hysteresis: Programmable
   Source: % output power, setpoint, deviation, or temperature                         Probe Break Action: Upscale
      (Available for heat or cool, but not both.)                                      Annunciator: LED backlight for "AL1", "AL2", (Alarm #2 not available
                                                                                          with cooling output or motorized valve position option.)
13. HEATER CURRENT MONITOR (Optional):
   Type: Single phase, full wave monitoring of load currents controlled by main     19. ENVIRONMENTAL CONDITIONS:
      output (OP1)                                                                     Operating Temperature Range: 0 to 50C
   Input: 100 mA AC output from current transformer RLC part number                    Storage Temperature Range: -40 to 80C
      CT005001 or any current transformer with 100 mA AC output                        Vibration to IEC 68-2-6: Operational 5-150 Hz, 1 g
   Display Scale Range: 1.0 to 999.9 amperes or 100.0%                                 Shock to IEC 68-2-27: Operational 5 g
   Input resistance: 5                                                                 Span Drift (maximum): 100 ppm/C, main input; 150 ppm/C, second input
   Accuracy: 1% of full scale 1 LSD (10 to 100% of range)                             Operating and Storage Humidity:
   Frequency: 50 to 400 Hz                                                                85% max. (non-condensing) from 0 to 50C
   Alarm mode: Dual acting; heater element fail detect and control device fail         Zero Drift (maximum): 1 V/C, main input;2 A/C, second input
      detect                                                                           Altitude: Up to 2000 meters
   Overload: 200 mA (steady state)
   Min. output "on" time for Heater break alarm detect: 400 msec                    20. ISOLATION BREAKDOWN RATINGS:
                                                                                       All inputs and outputs with respect to AC line: 2300 V
14. MOTORIZED VALVE POSITIONER (Optional):                                             Analog Outputs, Second Analog Input, Heater Current Input or
   Two Outputs: Valve open and valve close or Linear DC (optional)                        Slidewire Input with respect to main input: 500 V
   Hardware: Plug-in, replaceable output modules
   Three Inputs: Slidewire feedback, signal fail detect (Isolated from main         21. CERTIFICATIONS AND COMPLIANCES:
      input)                                                                           CE Approved
   Slidewire Resistance: 100 to 100 K                                                     EN 61326-1 Immunity to Industrial Locations
   Slidewire Exciting Voltage: 0.9 VDC                                                    Emission CISPR 11 Class A
   Slidewire Fail Action: programmable                                                    EN 61010-1
   Control Mode: Position mode (with slidewire) and velocity mode (w/o                    RoHS Compliant
      slidewire).                                                                      UL Recognized Component: File #E156876
   Control Deadband: 1% to 25.0% (position mode)                                       UL Listed: File #E137808
      0.1 to 25.0 seconds (velocity mode)                                              Type 2 Enclosure rating (Face only) for TCU0
   Update Time: 1 to 250 seconds                                                       Type 4X/IP65 Enclosure rating (Face only) for TCU1
   Motor Time (open, close): 1 to 9999 seconds                                         Refer to EMC Installation Guidelines section of the manual for additional
   Position Limits: Adjustable 0.0 to 100.0% of valve stroke                              information.
   Valve Fail Time: Off to 9999 seconds
                                                                                    22. CONNECTION: Jaw-type terminal block
                                                                                          Wire Range: 12-30 AWG copper wire
                                                                                          Torque: 5-7 inch-lbs (56-79 N-cm)

                                                                                 3
23. CONSTRUCTION:                                                                     SETPOINT FEATURES
   Front Panel: Flame and scratch resistant tinted plastic
   Case: High impact black plastic. (Mounting collar included)                           The controller setpoint can be protected from out of range values by
   Type 4X/IP65 model only: Sealed bezel utilizing two captive mounting               programming the setpoint range limit values. Additionally, safeguards from
      screws (panel gasket included). This unit is rated for Type 4X/IP65 indoor      inadvertent data entry can be programmed.
      use. Installation Category II, Pollution Degree 2
                                                                                         The setpoint ramp feature ramps the setpoint value at start-up or any time a
24. WEIGHT: 1.3 lbs (0.6 kgs)                                                         setpoint change is made, at a user programmable rate. This feature reduces
                                                                                      thermal shock to the process and helps to minimize temperature overshoot.The
ACCESSORIES:                                                                          setpoint may also be transmitted by the optional linear DC output for slave
   External SSR Power Unit:                                                           control loops.
      Switched Voltage Range: 50 to 280 VAC (Nominal: 240 VAC)
      Load Current: 45 Amps @ 25C ambient temperature                                   The second analog input may be configured as a remote setpoint. As such, the
         35 Amps @ 50C ambient temperature                                           controller is easily switched from local/remote setpoint operation via the front
      On State Input: 3 to 32 VDC @ 1500  impedance. (isolated)                       panel or user input. Ratio and bias parameters provide on-line scaling of the
         (Use Logic/SSR drive output module.)                                         remote setpoint. Absolute limit values and maximum rate of change of the
      Off State Input: 0.0 to 1.0 VDC                                                 remote setpoint further enhance controller flexibility.
      Size: 5.5" (14 cm) L x 4.75" (12 cm) W x 2.62" (6.6 cm) H
   Current Transformer:                                                               INPUT FEATURES
      Current Ratio: 50:0.1 (Amperes)
      Accuracy: 5.0%                                                                    A programmable input filter can be used to stabilize readings from a process
      Operating Frequency: 50 to 400 Hz                                               with varying or oscillating temperature characteristics, helping to provide better
      Insulation Class: 0.6 Kv BIL 10 Kv full wave                                    temperature control. A programmable temperature shift and slope function can
      Terminals: Brass studs No. 8-36, (flat washer, washer, nut)                     be used to compensate for probe errors or to have multiple TCU units indicate
      Weight: 8.0 oz (226 g)                                                          the same nominal temperature.
      Approvals: UL recognized component
                                                                                         The programmable User Input can be used to control a variety of functions,
BASIC OPERATION                                                                       such as auto/manual transfer of the controller, reset alarm output(s), etc.

   The TCU controls a process temperature by measuring the temperature via an            The second analog input has independent scaling parameters to match the
input probe, then calculating a control output power value by use of a modified       units of other processes or transmitters, or to match the controller's range.
PID control algorithm. The unit controls the system with the new output power
value to keep the process temperature at setpoint. The PID control algorithm          OUTPUT FEATURES
incorporates features which provide for high control accuracy and low
temperature overshoot from process disturbances.                                         Programmable output power limits provide protection for processes where
                                                                                      excessive power can cause damage. Automatic sensor probe break detection, for
FRONT PANEL FEATURES                                                                  fail-safe operation, causes the controller to default to a programmed output
                                                                                      power (upscale or downscale burnout). With adjustable time proportioning-
   In the normal operating mode, the unit will display the process temperature        cycle time, and programmable DC linear output, the controller can satisfy a
in the upper display. One of six other parameters can be viewed in the lower          wide variety of output requirements.
display:
                                                                                         Programmable dampening output hysteresis and output update time parameters
             - Setpoint                                                               can dramatically reduce actuator activity without degrading control accuracy.
             - % Power Output
             - Temperature Deviation                                                     The RS485 Communication option allows the user to access various
             - Heater Current                                                         controller parameters such as the setpoint, % output power, % proportional
             - Second Input Process Value                                             band, etc. The controller may be setup to transmit various parameters at a
             - Temperature Symbol (F or C)                                            programmable automatic print rate.

   The six parameters can be scrolled through by pressing the DSP button. If          AUTO-TUNE
enabled, the control setpoint or power output (manual mode only) can be
directly modified in this mode.                                                          The TCU has an auto-tune feature which, on demand, automatically
                                                                                      determines the PID control parameters for a particular thermal process. After
   In the normal operating mode, parameters are selected by use of the PAR            completion of auto-tune, the PID parameters are automatically optimized for
button and modified by use of the UP and DOWN buttons. Parameters are then            that process and loaded into nonvolatile memory. The operator may view and
entered by the PAR button, which advances the user to the next parameter.             modify the parameters as desired.
Pressing the DSP button immediately returns the controller to the normal
operating mode when making a parameter change. The controller's configuration            Auto-tune may be invoked either at start-up or at setpoint, depending on the
and parameter settings are stored in an internal E2PROM device.                       process requirements. An auto-tune programmable dampening factor produces
                                                                                      various levels of process control and response characteristics.

HARDWARE FEATURES

   The fast 100 msec input sampling rate provides quick controller response to a
process disturbance, thus providing excellent temperature control. Measurement
accuracy of 0.15% or better, provides closer process control conforming to the
desired control setpoint value. One model accepts a variety of both thermocouple
or RTD temperature probes. The AC input power is switch selectable, allowing
the unit to operate from either 115 VAC or 230 VAC. Since the controller is
serviceable from the front of the panel, the output modules may be easily changed
or replaced without disturbing the wiring behind the panel. No re-programming is
required when changing or replacing modules.

   The optional Type 4X/IP65 rated model utilizes two bezel securing screws
and a neoprene gasket to guarantee a water tight seal, when properly installed.
The standard model simply requires pressing a latch to remove the unit.

   Low-drift, highly stable circuitry ensures years of reliable and accurate
temperature control. The recommended two-year re-calibration interval is easily
accomplished via the programming menu.

                                                                                   4
OPTIONS                                                                                 INTERNAL CASCADE

HEATING AND COOLING CONTROL                                                                                                                                STEAM
                                                                                                                                                            FLOW
             MAIN OUTPUT    HEATING                                                                       LINEAR DC OUTPUT
                    (OP1)   CONTROL                                                                                                                        PROCESS
                                                   PROCESS

%PW MAN AL1  SECOND OUTPUT  COOLING                                                     %PW REM AL1       SECOND INPUT
DEV OP1 OP2          (OP2)  CONTROL                                                     SEC OP1 AL2
                                                                                                          STEAM PRESSURE
DSP         MAIN INPUT                                                                  DSP              (SECONDARY VARIABLE)
             TEMPERATURE
PAR                                                                                     PAR              MAIN INPUT

                                                                                                          TEMPERATURE
                                                                                                          (PRIMARY VARIABLE)

                                                                                        Cascade control allows the process to be divided into two control loops: the

The TCU has dual outputs for providing heating and cooling to those                     primary control loop and the secondary control loop. The secondary loop

processes that require them. Many extruder applications require both heating            receives it's setpoint from the primary loop to control an intermediate variable

and cooling to maintain accurate extruder barrel and die temperatures. The TCU          (steam pressure). The control level of the intermediate variable is the input to

is easily configured for these applications.                                            the primary process. The primary loop (temperature) controller maintains loop

Cooling Configuration Parameters                                                        regulation by manipulating the setpoint of the secondary controller. The

             "CYC2" - Enter cooling time proportioning cycle time                       setpoint of the secondary controller, in turn, changes the intermediate variable.

             "GAN2" - Enter cooling relative gain                                       The secondary loop can react faster to disturbances of the intermediate variable,

             "db-2" - Enter heat/cool deadband or overlap                               thereby minimizing the effects to the primary control loop. Control loops

HEATER CURRENT MONITOR                                                                  cascaded in such a manner provide greater control quality than would be

                                                                                        possible with single loop control. A single TCU can accomplish two-process

             AL1 OUTPUT                           HEATER BREAK                          cascade control.
                                                         ALARM
             MAIN                                                                       Internal Cascade Configuration Parameters
             OUTPUT         POWER
             (OP1)         CONTROL                                                                        "OPer" - Select cascade mode

             HEATER         DEVICE                                                                        "root"               - Select second input square root linearization
             CURRENT
                                        CURRENT TRANSFORMER                                               "dPt2" - Select second input decimal point

%PW MAN AL1                                                                                               "dSP1" - Enter scaling units of second input
CUR OP1 AL2
                                                                                                          "INP1" - Enter scaling units of second input

DSP                                       HEATING  PROCESS                                                "dSP2" - Enter scaling units of second input
PAR                                       ELEMENT
                                                                                                          "INP2" - Enter scaling units of second input
             MAIN INPUT
             TEMPERATURE                                                                                  "OPd2" - Output dampening of secondary

                                                                                        Internal Cascade Operational Parameters

                                                                                                          "SP-2" - View secondary setpoint value

The Heater Current Monitor serves as a heater element fail sentry, so                                     "Pb-2" - Enter secondary proportional band

operators can take corrective action before significant process errors occur in                           "It-2"               - Enter secondary integral time

the event of a failure. The actual heater current can be viewed in the secondary                          "dt-2"               - Enter secondary derivative time

display and/or a heater break alarm output can be programmed.                           EXTERNAL CASCADE

Heater Current Monitor Configuration Parameters                                                          PRIMARY                                                           SECONDARY
                                                                                                     CONTROLLER                                                            CONTROLLER
             "HCur" - Enter full scale current of current transformer

     ACt1", "ACt2" - Program alarm(s) as heater break alarm

MOTORIZED VALVE POSITIONER                                                                                   LINEAR DC                            SECOND INPUT
                                                                                                          (PRIMARY OUTPUT)                        REMOTE SETPOINT

                                                                                                                                           STEAM

             AL1 OUTPUT                            VALVE FAIL
                                                       ALARM

%PW MAN OPN  VALVE OPEN OUTPUT                     STEAM FLOW                           %PW MAN AL1                                                             LINEAR DC  %PW REM AL1
DEV AL1 CLS  VALVE CLOSE OUTPUT                      PROCESS                            DEV OP1 AL2                                                              OUTPUT    SEC OP1 AL2

DSP         SECOND INPUT                                                                DSP                                                                MAIN INPUT      DSP
             VALVE POSITION                                                                                                                           STEAM PRESSURE
PAR         MAIN INPUT                                                                  PAR                                                      (SECONDARY VARIABLE)      PAR

                                                                                        TCU                                                                                PCU

                                                                                                          MAIN INPUT                              PROCESS
                                                                                                          PROCESS TEMPERATURE
                                                                                                          (PRIMARY VARIABLE)

The motorized valve positioner controls the position of a valve directly, by use

of "open" and "close" control outputs. The slidewire feedback signals of the valve         Similar to internal cascade control, external cascade control differs by the
                                                                                        employment of two controllers, one of which is equipped with a second analog
may optionally be connected to the controller. Alternatively, the controller may be     input configured as a remote setpoint. A PCU controls the secondary loop, while
                                                                                        a TCU controls the primary loop.
configured for linear input valve control using the 4 to 20 mA DC output.

Motorized Valve Positioner Configuration Parameters

Position mode: "VPS1" - Enter or measure valve closed position                          External Cascade Configuration Parameters

             "VPS2" - Enter or measure valve open position                                                "OPEr" - Select ratio mode

             "VUdt" - Enter Valve update time                                                             "root"               - Select second input square root linearization

             "VPdb" - Enter valve control deadband                                                        "dPt2" - Select second input decimal point

             "VFAL" - Enter valve fail detect time                                                        "dSP1" - Enter scaling units of second input

             "Act1" - Program alarm as valve fail output                                                  "INP1" - Enter scaling units of second input

Velocity mode: "VUdt"      - Enter Valve update time                                                      "dSP2" - Enter scaling units of second input
                           - Enter valve open time
             "VOPt"        - Enter valve close time                                                       "INP2" - Enter scaling units of second input
                           - Enter valve control deadband
             "VCLt"                                                                                       "SPtr"               - Local/Remote select options
                             (minimum on time)
             "VONt"                                                                     External Cascade Operational Parameters

                                                                                                          "rtio"               - Remote setpoint ratio

                                                                                                          "bIAS" - Remote setpoint bias

                                                                                     5
                                                                                               LINEAR DC OUTPUT SETPOINT RE-TRANSMISSION

SETPOINT MASTER CONTROL

   Setpoint Master Control allows automatic setpoint changes to slave                  MASTER                      SECOND INPUT   SLAVE                SECOND INPUT          SLAVE
controller units (up to 50 units total) from a master TCU controller.                    UNIT                 REMOTE SETPOINT    UNIT #1               REMOTE SETPOINT     UNIT `N'
The linear DC output of the master is looped with the second analog                                                                                                     (UP TO 50)
input of the slave TCU controllers. Each slave unit can have unique
remote setpoint ratio and bias values.

Setpoint Slave Configuration Parameters

  "OPEr" - Select remote setpoint mode

  "root" - Select second input square root                                             %PW MAN AL1                               %PW REM AL1                            %PW REM AL1
                                                                                       DEV OP1 AL2                               SEC OP1 AL2                             SEC OP1 AL2
             Linearization                                                              DSP                                       DSP                                    DSP
                                                                                        PAR                                       PAR                                    PAR
  "dPt2" - Select second input decimal point
                                                                                                       MAIN                                     MAIN                                    MAIN
  "dSP1" - Enter scaling units of second input                                                         INPUT                                    INPUT                                   INPUT

  "INP1" - Enter scaling units of second input                                         PROCESS #1                                PROCESS #2                             PROCESS "N"

  "dSP2" - Enter scaling units of second input

  "INP2" - Enter scaling units of second input

  "SPLO"  -  Limit range of remote setpoint
  "SPHI"

  "SPrP" - Limit rate of change of remote

             setpoint

Setpoint Slave Operational Parameters

  "rtio" - Second input ratio

  "bIAS" - Second input bias

CONTROLLER PROGRAMMING                                                                         Configuration 1, Inputs
                                                                                                              "tYPE" - Select input probe type
   The TCU has been designed to reduce the operator interaction with the
controller while still maintaining a high degree of control accuracy and user                                 "SCAL" - Select temperature scale
flexibility. Front Panel Program Disable allows all of the controller's set-ups to be
locked-out from further operator intervention after the initial parameter set-up.                             "dCPt" - Select temperature resolution

             The programming of the controller is divided into four sections:                                 "FLtr" - Select level of input filtering
             Unprotected Parameter Mode
             Configuration Parameter Mode                                                                     "SPAN" - Enter input correction span (slope)
             Protected Parameter Mode
             Hidden Function Mode                                                                             "SHFt" - Enter input correction shift (offset)

   These four programming modes allow the controller to adapt to any required                                 "SPLO" - Enter setpoint lower limit
user-interface level.
                                                                                                              "SPHI" - Enter setpoint higher limit

                                                                                                              "SPrP" - Enter setpoint ramp rate

                                                                                                              "InPt" - Select user input function *
                                                                                                              "HCur" - Enter full scale heater current *

                                                                                               Configuration 2, Outputs
                                                                                                              "CYCt" - Enter time proportioning cycle time

                                                                                                              "OPAC" - Select control action

UNPROTECTED PARAMETER MODE *                                                                                  "OPLO" - Enter output power low limit

   The unprotected parameter mode is accessible when program disable is                                       "OPHI" - Enter output power high limit

inactive or when the proper access code number from the protected mode is                                     "OPFL" - Enter probe fail power preset

                                                                                                              "OPdP" - Enter output control dampening

entered.The configuration parameter modes can be accessed only from this mode.                                "CHYS" - Enter ON/OFF control hysteresis

  "SP" - Enter Setpoint                                                                                       "tcod" - Select auto-tuning dampening

  "OP" - Enter output power                                                                                   "ANAS" - Select linear DC output assignment *
                                                                                                              "ANLO" - Enter linear DC output low scaling value *
  "ProP" - Enter proportional band                                                                            "ANHI" - Enter linear DC output high scaling value *
                                                                                                              "ANdb" - Enter linear DC output control deadband *
  "Intt" - Enter integral time                                                                                "ANUt" - Enter linear DC output update time *

  "dErt" - Enter derivative time

  "rtio" - Enter Remote Setpoint ratio value

  "bIAS" - Enter Remote Setpoint bias value                                                    Configuration 3, Parameter lock-outs

  "SP-2" - View internal cascade secondary setpoint                                                           "SP" - Select degree of setpoint access

          demand                                                                                              "OP" - Select degree of power access

  "Pb-2" - Enter internal cascade, secondary                                                                  "dEv" - Enable deviation display *
                                                                                                              "IN-2" - Enable second input display *
          proportional band                                                                    
                                                                                                              "HCur" - Enable heater current display
  "It-2" - Enter internal cascade, secondary integral

          time                                                                                                "UdSP" - Enable temperature scale display

  "dt-2" - Enter internal cascade, secondary                                                                  "CodE" - Enter parameter access code

          derivative time                                                                                     "PId" - Select degree of PID access

  "AL-1" - Enter value for alarm #1                                                                           "PId2" - Select degree of secondary PID access *
                                                                                                              "rtbS" - Select degree of ratio/bias access *
  "AL-2" - Enter value for alarm #2                                                                           "AL" - Select degree of alarm access *
                                                                                                              "ALrS" - Enable alarm reset access *
  "CNFP" - Select basic configuration mode                                                                    "SPSL" - Enable local/remote setpoint selection *
                                                                                               
  "End" - Return to normal display mode                                                                       "trnF" - Enable auto/manual mode selection

* These parameters may not appear due to option configuration or other

   programming.

                                                                                                              "tUNE" - Enable auto-tune invocation

CONFIGURATION PARAMETER MODE                                                                   Configuration 4, Alarms *
   The configuration parameter mode allows the operator to set-up the basic                                   "Act1" - Select operation mode of alarm #1

requirements of the controller. It is divided into sections which group together                              "rSt1" - Select reset mode of alarm #1
related programming steps, such as inputs, outputs, alarms, etc. Upon
completion of each section, the program returns to the configuration selection                                "Stb1" - Enable activation delay of alarm #1
stage allowing the user to return to the normal display mode.
                                                                                                              "AL-1" - Enter value for alarm #1

                                                                                                              "Act2" - Select operation mode of alarm #2

                                                                                                              "rSt2" - Select reset mode of alarm #2

                                                                                                              "Stb2" - Enable activation delay of alarm #2

                                                                                                              "AL-2" - Enter value for alarm #2

                                                                                                              "AHYS" - Enter hysteresis value for both alarms

                                                                                               Configuration 5, Cooling *
                                                                                                              "CYC2" - Enter cooling time proportioning cycle time

                                                                                                              "GAN2" - Enter cooling relative gain

                                                                                                              "db-2" - Enter heat/cool deadband or overlap

                                                                                       6
Configuration 6, Serial Communications *                                       HIDDEN FUNCTION MODE *
  "bAUd" - Select baud rate
                                                                               The hidden function mode is accessible from the normal operating mode. The
  "PArb" - Select parity bit
                                                                               four functions in this mode may be locked-out individually in configuration 3
  "Addr" - Enter unit address number
                                                                               parameter lock-out section.
  "Abrv" - Select abbreviated or full mnemonic
                                                                                           "SPSL" - Select Local/Remote Setpoint
  transmissions
                                                                                           "trnF" - Transfer between automatic (PID) control
  "PrAt" - Enter automatic print rate
                                                                                                            and manual control
  "PoPt" - Select parameters to be included in print-out
                                                                                           "tUNE" - Invoke/cancel PID Auto-tune

Configuration 7, Second Input *                                                            "ALrS" - Reset latched alarms

  "OPEr" - Select remote setpoint or internal

  cascade mode                                                                 PROTECTED PARAMETERS MODE *

  "root" - Select second input square root linearization

  "dPt2" - Select second input decimal point                                   The protected parameters mode is enabled when program disable is active.

  "dSP1" - Enter scaling parameters of second input                            This mode prevents access to the configuration modes without the proper access

  "INP1" - Enter scaling parameters of second input                            code number. Only the parameters that are selected in the configuration 3

  "dSP2" - Enter scaling parameters of second input                            parameter lock-out section can be accessed.

  "INP2" - Enter scaling parameters of second input                                        "ProP" - Enter Proportional band

  "SPtr" - Enter local/remote select options                                               "Intt" - Enter integral time

  "OPd2" - Enter Secondary output control dampening                                        "dErt" - Enter derivative time

Configuration 8, Motorized Valve Positioner *                                              "rtio" - Enter remote setpoint ratio value

Position mode: "VPS1" - Enter or measure valve closed position                            "bIAS" - Enter remote setpoint bias value

  "VPS2" - Enter or measure valve open position                                            "SP-2" - Enter internal cascade, secondary setpoint

  "VUdt" - Enter valve update time                                                         "Pb-2" - Enter internal cascade, secondary

  "VPdb" - Enter valve control deadband                                                                     proportional band

  "VFAL" - Enter valve fail detect time                                                    "It-2" - Enter internal cascade, secondary

Velocity mode: "VUdt" - Enter valve update time                                                             integral time

  "VOPt" - Enter valve open time                                                           "dt-2" - Enter internal cascade, secondary

  "VCLt" - Enter valve close time                                                                           derivative time

  "VONt" - Enter valve control deadband                                                    "AL-1" - Enter value for alarm #1

  (minimum on time)                                                                        "AL-2" - Enter value for alarm #2

                                                                                           "CodE" - Enter access value to unprotected

                                                                                                            parameters & configuration parameters

                                                                               * These parameters may not appear due to option configuration or other

                                                                                  programming.

ACCESSORY - EXTERNAL RLY50000 SSR                                              ACCESSORY - CT005001 CURRENT
POWER UNIT SHOWN                                                               TRANSFORMER SHOWN

(External DIN Rail mount SSR power units available)                            (Lower current CT available)

   The external SSR Power Unit is used with the Logic/SSR Drive Module            The external Current Transformer is used when specifying TCUs
(OMD00003) to switch loads up to 240 VAC @ 45 amps, 25C ambient.              equipped with the Heater Current Monitor. The primary current rating is 50
The unit is operated by applying a low level DC control signal to the          amperes.
isolated input. The unit features zero cross detection circuits which reduces
radiated RFI when switching load currents. With no contacts to wear out,
the SSR Power Unit provides virtually limitless operational life. The unit is
supplied with an integral heat sink for immediate installation.

                                                                               1.60                                           .96 2.00
                                                                               (40.6)                                        (24.4) (50.8)

                                 2.62
                                 (66.5)

           4.75 (121)                     0.22 (TYP.)                                                        1.75                      4X .31
           4.56 (116)                      (5.5)                                                            (44.5)           4X .27 (7.9)
                                                                                                            1.10              (6.9)
CENTERS FOR #8 SCREWS                                                                                       (27.9)
                                                                                                                                 2X #8-32UNC TERMINAL
                                                                                                                         X1
                                                                                                                                            .44
                                                                                                                                          (11.2)

                                         5.50                                          H1                   1.13                       2.68
                                         (140)                                                              (28.7)                    (67.8)

                                 4.50                                                                                         1.25
                                 (114)                                                                                       (31.8)

                                          0.20 (TYP.)                                                        2.40
                                            (5.1)                                                           (61.0)

                                                                          7
OUTPUT MODULES                                                                             TRIAC MODULE         120VAC
                                                                                                         A
         RELAY      TYPICAL CONNECTIONS                                                ISOLATED          B              RELAY OR             POWER
        MODULE                                                                           1 AMP           C                 TRIAC
                           A                                                                AT                            DEVICE

                                                                                     120/240VAC                                        LOAD
                                                                                     DO NOT CONNECT

5 AMPS              B                   POWER
   AT
                    C                                                                   Drive: 45 mA maximum.
240VAC                      LOAD                                                     Triac:

Relay:                                                                                  Type: Isolated, Zero Crossing Detection
   Type: Form-C (Form-A with some models. See ordering information.)                    Rating:

Rating: 5 amps @ 120/240 VAC or 28 VDC (resistive load), 1/8 HP @ 120                      Voltage: 120/240 VAC
                                                                                           Max. Load Current: 1 ampere @ 35C
   VAC (inductive).                                                                        0.75 ampere @ 50C
Life Expectancy: 100,000 cycles at maximum load rating.                                    Min. Load Current: 10 mA
                                                                                        Off State Leakage Current: 7 mA max. @ 60 Hz
LOGIC/SSR DRIVE                                                                         Operating Frequency: 20 to 400 Hz
      MODULE                                                                            Protection: Internal Transient Snubber, Fused

+12VDC           -  A

UNREG.                        4 SSR 1

NOT                 B         POWER                      POWER

ISOLATED         +            3 UNIT 2

                    C

DO NOT CONNECT                               LOAD

      (Decreasing load and/or increasing cycle time, increases life expectancy).
Logic/SSR Drive: Can drive multiple SSR Power Units.

   Type: Non-isolated switched DC, 12 VDC typical

     EXTRUDER    COOLING              ALARM/COOLING                   120 VAC
                  WATER                      SUPPLY

                                                                                     AC POWER                           APPLICATION

                                                                                                                        Several TCU controllers are

                                                         1 AL1/OP2 COMM COOLING/ALARM COMMON                            employed to control the temperature of

                       240V HEATER                       2 OP2-A                     COOLING OUTPUT                     a plastics extruder. Each TCU controls
                          SUPPLY
                                        HB               3 AL1-A                     HEATER CURRENT FAIL OUTPUT         a heating element and a cooling water
                                      ALARM
                                                         4 OP1-A                                                        solenoid to maintain each extruder

                   CURRENT      SSR                       5 OP1-B                    MAIN CONTROL OUTPUT                zone at a desired temperature. The
                 TRANSFORMER  POWER                       6 OP1-C                                                       heater current monitor of the TCU is
                                                          7 USER INPUT               THERMOCOUPLE INPUT                 used for early detection of heater
                                UNIT                      8                          4 -20 mA LINEAR DC OUTPUT          element failure. The linear DC output
                                                          9 TC +                                                        is used to retransmit the process
                                                         10 COMM                                                        temperature to a control computer for
                                                         11 OUT +                                                       data logging purposes.

                                        DATA             12 OUT -                    TEMPERATURE RETRANSMISSION
                                      LOGGER
                                                         13 N/C

                                                         14 N/C

                                                         15 CT                       SECOND INPUT
                                                         16 CT                       (CURRENT TRANSFORMER)

                                                                                  8
ORDERING INFORMATION

MODELS WITHOUT SECOND INPUT OPTIONS

Type 4X/IP65  4 to 20 mA       0 to 10 VDC       ALARM      COOLING            RS485 COM            PART NUMBER
    BEZEL      ANALOG           ANALOG          OUTPUTS     OUTPUT                  NO                115/230 VAC
               OUTPUT            OUTPUT
     NO                                            NO          NO                                     TCU00000
                  NO                NO

NO                 NO                  NO       2                NO                             NO  TCU00001

NO                 NO                  NO       1                YES                            NO  TCU00002

NO                YES                  NO       2                NO                             NO  TCU01001

NO                YES                  NO       2                NO                         YES     TCU01004

NO                YES                  NO       1                YES                        YES     TCU01005

YES                NO                  NO       NO               NO                             NO  TCU10000

YES                NO                  NO       2                NO                             NO  TCU10001

YES                NO                  NO       1                YES                            NO  TCU10002

YES               YES                  NO       2                NO                             NO  TCU11001

YES               YES                  NO       1                YES                            NO  TCU11002

YES               YES                  NO       2                NO                         YES     TCU11004

YES               YES                  NO       1                YES                        YES     TCU11005

YES                NO                  YES      2                NO                             NO  TCU12001

YES                NO                  YES      2                NO                         YES     TCU12004

YES                NO                  YES      1                YES                        YES     TCU12005

These models have dual alarm outputs, or single alarm with cooling outputs, with shared common terminals (Form A
Type). As a result, these outputs should be fitted with the same type of output module. The main output (OP1) may be
fitted with any type of output module.

HEATER CURRENT MONITOR MODELS (HCM)

Type 4X/IP65  4 to 20 mA  0 to 10 VDC   ALARM   COOLING  RS485 COM PART NUMBER
    BEZEL      ANALOG      ANALOG      OUTPUTS  OUTPUT
               OUTPUT       OUTPUT

YES           NO          NO                2   NO          YES                TCU10204

YES           YES         NO                2   NO          NO                 TCU11208

These models have dual alarm outputs, or single alarm with cooling outputs, with shared
common terminals (Form A Type). As a result, these outputs should be fitted with the same type
of output module. The main output (OP1) may be fitted with any type of output module.

SECOND ANALOG INPUT MODELS (ANA)

Type 4X/IP65  4 to 20 mA  0 to 10 VDC   ALARM   COOLING  RS485 COM PART NUMBER
    BEZEL      ANALOG      ANALOG      OUTPUTS  OUTPUT
               OUTPUT       OUTPUT

YES           NO          NO                2   NO          YES                TCU10104

YES           YES         NO                2   NO          NO                 TCU11108

YES           NO          YES               2   NO          NO                 TCU12108

These models have dual alarm outputs, or single alarm with cooling outputs, with shared
common terminals (Form A Type). As a result, these outputs should be fitted with the same
type of output module. The main output (OP1) may be fitted with any type of output module.

MOTORIZED VALVE POSITIONER MODELS (MVP)

Type 4X/IP65  4 to 20 mA  0 to 10 VDC   ALARM   COOLING  RS485 COM PART NUMBER
    BEZEL      ANALOG      ANALOG      OUTPUTS  OUTPUT
               OUTPUT       OUTPUT                          YES                TCU10307
    YES                                     1      NO       NO                 TCU11306
    YES           NO           NO           1      NO       NO                 TCU12306
    YES                                     1      NO
                 YES           NO

                  NO          YES

ACCESSORIES

DESCRIPTION                                              PART NUMBER

Relay Module                                             OMD00000
Triac Module                                             OMD00001
Logic/SSR Drive Module                                   OMD00003
45 A Single Phase Panel Mount SSR                        RLY50000
25 A Single Phase DIN Rail Mount SSR                     RLY60000
40 A Single Phase DIN Rail Mount SSR                     RLY6A000
25 A Three Phase DIN Rail Mount SSR                      RLY70000
50:0.1 Ampere Current Transformer                        CT005001
40:0.1 Ampere Current Transformer                        CT004001

Note: Output Modules are NOT supplied with the controller. When specifying the controller, be
   sure to purchase the appropriate output module for the Main Control Output and if necessary,
   the alarm output(s), the cooling output, and valve positioner outputs. The controller can be
   fitted with any combination of output modules.

The Logic/SSR Drive Module is a switched DC source, intended to drive the DC input of an
SSR power unit. It should never be connected to line voltage.

All output modules are packaged separately and must be installed by the user.

                                                         9
                                                            LIMITED WARRANTY

                          The Company warrants the products it manufactures against defects in materials and workmanship for a
                          period limited to two years from the date of shipment, provided the products have been stored, handled,
                          installed, and used under proper conditions. The Company's liability under this limited warranty shall
                          extend only to the repair or replacement of a defective product, at The Company's option. The Company
                          disclaims all liability for any affirmation, promise or representation with respect to the products.

                          The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against
                          damages, claims, and expenses arising out of subsequent sales of RLC products or products containing
                          components manufactured by RLC and based upon personal injuries, deaths, property damage, lost profits,
                          and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable,
                          including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and
                          liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in
                          effect or as amended hereafter.

                          No warranties expressed or implied are created with respect to The Company's products except those
                          expressly contained herein. The Customer acknowledges the disclaimers and limitations contained herein
                          and relies on no other warranties or affirmations.

Red Lion Controls              Red Lion Controls            Red Lion Controls                                                                           Red Lion Controls
Headquarters                          Europe                         India                                                                                              China
20 Willow Springs Circle
York PA 17406                   Softwareweg 9       201-B, 2nd Floor, Park Centra                                                                  Unit 302, XinAn Plaza
Tel +1 (717) 767-6511     NL - 3821 BN Amersfoort   Opp 32 Mile Stone, Sector-30                                                   Building 13, No.99 Tianzhou Road
Fax +1 (717) 764-0839     Tel +31 (0) 334 723 225  Gurgaon-122002 Haryana, India
                          Fax +31 (0) 334 893 793                                                                                        ShangHai, P.R. China 200223
                                                         Tel +91 984 487 0503                                                                     Tel +86 21 6113 3688
                                                                                                                                                 Fax +86 21 6113 3683
This datasheet has been downloaded from:
            datasheet.eeworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company

小广播

该厂商的其它器件

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2017 EEWORLD.com.cn, Inc. All rights reserved