                                                                                                                              Bulletin No. TLA-B
                                                                                                                              Drawing No. LP0553
                                                                                                                              Released 06/13

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

MODEL TLA - TEMPERATURE LIMIT ALARM

     FM                                                                               FM APPROVED, UL RECOGNIZED
                                                                                      2-LINE BY 4-DIGIT DISPLAY
      APPROVED                                                                        EXCEED, OUTPUT, AND ALARM ANNUNCIATORS
                                                                                      FOUR BUTTON SILICONE RUBBER KEYPAD
  PROCESS CONTROL EQUIPMENT                                                           THERMOCOUPLE OR RTD SENSOR INPUT
                                                                                      REMOTE RESET INPUT
GENERAL DESCRIPTION                                                                   MAIN LIMIT OUTPUT: 5A RELAY. SELECTABLE FOR HIGH OR

   The TLA is a Factory Mutual approved temperature limit alarm, intended to            LOW TRIP ACTIVATION
provide an independent shutdown for thermal processes. The TLA accepts                OPTIONAL ALARMS: 5A RELAY(S)
signals from a variety of temperature sensors (thermocouple or RTD elements),         OPTIONAL NEMA 4X/IP65 SEALED FRONT BEZEL
and its comprehensive programming allows it to meet a wide variety of                 PARAMETER SECURITY VIA PROGRAMMABLE LOCKOUTS
application requirements.
                                                                                                                                   UL Recognized Component,
   Dual 4-digit displays allow viewing of the process temperature and limit                                                        File # E156876
setpoint simultaneously. Front panel indicators inform the operator of the
process and output status. The main limit output and alarm outputs are field         SAFETY SUMMARY
replaceable.
                                                                                        All safety related regulations, local codes and instructions that appear in the
   The limit output is selectable for high or low trip activation. If the process    manual or on equipment must be observed to ensure personal safety and to
temperature goes above the limit setpoint for a high trip, or below the limit        prevent damage to either the instrument or equipment connected to it. If
setpoint for a low trip, the limit relay will de-energize to initiate a process      equipment is used in a manner not specified by the manufacturer, the protection
shutdown. The limit output cannot be reset until the process temperature returns     provided by the equipment may be impaired.
to the proper operating range; manual reset is required (local or remote). Sensor
failure will initiate a process shutdown.                                               Do not use the TLA to directly command motors, valves, or other actuators
                                                                                     not equipped with safeguards. To do so can be potentially harmful to persons or
   Relay alarm(s) can be configured to activate according to a variety of actions    equipment in the event of a fault to the unit.
(Absolute HI or LO, Deviation HI or LO, and Band IN or OUT) with adjustable
hysteresis. A standby feature suppresses the alarm during power-up until the                CAUTION: Risk of Danger.          CAUTION: Risk of electric shock.
process stabilizes outside the alarm region.                                         Read complete instructions prior to

   The unit is constructed of a lightweight, high impact plastic case with a tinted  installation and operation of the unit.
front panel. The front panel meets NEMA 4X/IP65 specifications when properly
installed. Multiple units can be stacked horizontally or vertically. Modern
surface-mount technology, extensive testing, plus high immunity to noise
interference makes the TLA extremely reliable in industrial environments.

DIMENSIONS In inches (mm)

                                                                                                                              PANEL CUT-OUT

                1.95                                                                                                          1.772  +0.024
                (49.5)                                                                                                               -0.000

  EX OUT A1 A2       0.37                                                                                                     (45 +-00..60)
RP                   (9.4)
                            4.17 (105.9)                                                                                      1.772  +0.024
1.95 (49.5)                                                                                                                          -0.000
                               1
                                                                                                                              (45 +-00..06)
GENERAL SPECIFICATIONS                                                         6. ISOLATION BREAKDOWN RATINGS:

1. DISPLAY: 2 line by 4-digit LED                                              AC line with respect to all inputs and outputs: 2300 V for 1 minute (250
   Upper (Main) Display: 0.4" (10.2 mm) high red LED
   Lower (Secondary) Display: 0.3" (7.6 mm) high green LED                     V working)
   Display Messages:
      "OLOL" - Appears when measurement exceeds + sensor range.                Relay contacts to all other inputs and outputs: 2300 VAC
      "ULUL" - Appears when measurement exceeds - sensor range.
      "OPEN" - Appears when open sensor is detected.                           DC Power with respect to sensor input: 50 V working (500 V for 1 minute)
      "SHrt" - Appears when shorted sensor is detected (RTD only)
      "..." - Appears when display values exceed + display range.              7. CERTIFICATIONS AND COMPLIANCES:
      "-.." - Appears when display values exceed - display range.
                                                                               CE Approved
LED Status Annunciators:
      EX - Temperature exceeds limit setpoint                                  EN 61326-1 Immunity to Industrial Locations
      OUT - Limit output is de-energized
      A1 - Alarm #1 is active                                                  Emission CISPR 11 Class A
      A2 - Alarm #2 is active
                                                                               IEC/EN 61010-1
2. POWER:
   Line Voltage Models: 85 to 250 VAC, 50/60 Hz, 8 VA.                         RoHS Compliant
   Low Voltage Models:
      DC Power: 18 to 36 VDC, 7 W.                                             Factory Mutual (FM) Listed: File #3014646
      AC Power: 24 VAC +/-10%, 50/60 Hz, 9 VA
                                                                               UL Recognized Component: File #E156876
3. CONTROLS: Four rubber push buttons: R, P, Up, Down
4. MEMORY: Nonvolatile E2PROM retains all programmable parameters and          Type 4X Enclosure rating (Face only)

   values.                                                                     IP65 Enclosure rating (Face only)
5. ENVIRONMENTAL CONDITIONS:
                                                                               IP20 Enclosure rating (Rear of unit)
   Operating Range: FM rated @ 0 to 65C, UL rated @ 0 to 55C
   Storage Range: -40 to 80C                                                  Refer to EMC Installation Guidelines section of the bulletin for additional
   Operating and Storage Humidity: 85% max. relative humidity (non-
                                                                               information.
      condensing) from 0C to 65C.
   Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g.                      8. CONNECTION: Wire clamping screw terminals
   Shock to IEC 68-2-27: Operational 20 g (10 g relay).
   Altitude: Up to 2000 meters                                                 Wire Gage Capacity: Two 14 AWG (2.55 mm), four 18 AWG (1.02 mm), or

                                                                               four 20 AWG (0.61 mm).

                                                                               Terminal Torque: 1.0Nm (8.9 in-lbs.).

                                                                                               1.4Nm (12.4 in-lbs.) max.

                                                                               9. CONSTRUCTION: Black plastic alloy case and collar style panel latch.

                                                                               Panel latch can be installed for vertical or horizontal instrument stacking.

                                                                               One piece tinted plastic bezel. Bezel assembly with circuit boards can be

                                                                               removed from the case to change the output board without removing the case

                                                                               from the panel or disconnecting wiring. Unit meets NEMA 4X/IP65

                                                                               requirements for indoor use, when properly installed. Flame resistant.

                                                                               Installation Category II, Pollution Degree 2.

                                                                               10. WEIGHT: 0.38 lbs (0.17 kgs)

INPUT SPECIFICATIONS                                                           5. THERMOCOUPLE INPUT:
                                                                                  Types: T, E, J, K, R, S, B, N, Linear mV, software selectable
1. SENSOR INPUT:                                                                  Input Impedance: 20 M all types
   Sample Period: 100 msec                                                        Lead resistance effect: 0.25 V/
   Step Response Time: Less than 300 msec typ., 400 msec max. (to within          Cold junction compensation: Less than 1C typ., (1.5C max), error over
      99% of final value)                                                            0 to 65C max. ambient temperature range. Defeated for Linear mV
   Normal Mode Rejection: Greater than 40 dB @ 50/60 Hz                              indication mode.
   Common Mode Rejection: Greater than 120 dB, DC to 60 Hz                        Resolution: 1 for all types, or 0.1 for T, E, J, K, and N onlY.
   Overvoltage Protection: Input overload 120 VAC for 15 seconds max.
                                                                               TC TYPE               RANGE                    WIRE COLOR
2. Failed Sensor Response:                                                         T
   Main Output: Sensor failure will initiate a process shutdown                    E          -200 to +400C          ANSI        BS 1843
   Display: "OPEN"                                                                 J          -328 to +752F
   Alarms: Upscale                                                                 K          -200 to +750C          blue (+)    white (+)
                                                                                   R         -328 to +1382F           red (-)     blue (-)
3. INDICATION ACCURACY: (0.3% of Span +1C) at 23C ambient after                 S          -200 to +760C
   20 minute warm-up. (Includes NIST conformity, cold junction effect, A/D         B          -328 to 1400F          violet (+)  brown (+)
   conversion errors and linearization conformity.                                 N         -200 to +1250C           red (-)     blue (-)
   Span Drift (maximum): 130 PPM/C                                                          -328 to +2282F
                                                                                  mV                                  white (+)   yellow (+)
4. RTD INPUT: 2 or 3 wire, 100  platinum, alpha = 0.00385 (DIN 43760),                          0 to 1768C            red (-)     blue (-)
   alpha = 0.0039162                                                                          +32 to +3214F
   Excitation: 150 A typical                                                                                        yellow (+)   brown (+)
   Resolution: 1 or 0.1 degree                                                                  0 to 1768C            red (-)     blue (-)
   Lead Resistance: 15  max. per input lead                                                   +32 to 3214F
                                                                                             +149 to +1820C          black (+)   white (+)
                                                                                             +300 to +3308F           red (-)     blue (-)
                                                                                             -200 to +1300C
                                                                                             -328 to +2372F          black (+)   white (+)
                                                                                                                       red (-)     blue (-)
                                                                                              -5.00 to +56.00
RTD TYPE         RANGE                                                                                                grey (+)    no standard
   385                                                                                                                 red (-)
   392    -200 to +600C
          -328 to +1100F                                                                                            orange (+) orange (+)
OHMS
          -200 to +600C                                                                                              red (-)     blue (-)
          -328 to +1100F
                                                                                                                     no standard no standard
            2.0 to 320.0
                                                                               6. REMOTE RESET INPUT: Internally pulled up to +5 VDC (1M).
                                                                                  VIL: 0.85 V max., VIH: 3.65 V min., VIN MAX: 5.25 VDC, IOFF: 1A max.

                                                                            2
OUTPUT SPECIFICATIONS                                                                   3. ALARM OUTPUTS (Optional): One or two Form-A relays.

1. LIMIT AND ALARM OUTPUT RELAYS:                                                       Modes:
   Contact Rating: 5 A @ 250 VAC or 30 VDC (resistive load).
   Life Expectancy: 100,000 cycles at max. load rating. (Decreasing load                Absolute High Acting Absolute Low Acting
      increases life expectancy.)
                                                                                        Deviation High Acting Deviation Low Acting
2. LIMIT OUTPUT: TLA21000: Form-C relay; TLA11100: Form-A relay.
   Selectable for high or low trip activation. If the process temperature goes          Inside Band Acting          Outside Band Acting
   above the limit setpoint for a high trip, or below the limit setpoint for a low
   trip, the limit relay will de-energize to initiate a process shutdown. The limit     Reset Action: Programmable; automatic or latched. Latched alarms can be
   output cannot be reset until the process temperature returns to the proper
   operating range; manual reset is required (local or remote).                         reset regardless of limit exceed condition.
   Annunciators:
      "EX" - Lit when the process temperature exceeds the limit setpoint.               Standby Mode: Programmable; enable or disable.
      "OUT" - Lit when the limit output is de-energized.
                                                                                        Hysteresis: Programmable.

                                                                                        Annunciator: "A1" and "A2" programmable for normal or reverse acting.

ORDERING INFORMATION

85 to 250 VAC

LIMIT OUTPUT          ALARM 1 OUTPUT  ALARM 2 OUTPUT                                    REPLACEMENT   PART NUMBERS
                                        Form-A Relay                                    OUTPUT BOARD
Form-C Relay            Form-A Relay                                                                     TLA21000
Form-A Relay            Form-A Relay                                                      RBDLA210       TLA11100
                                                                                           RBD48111

18 to 36 VDC / 24 VAC

LIMIT OUTPUT          ALARM 1 OUTPUT  ALARM 2 OUTPUT                                    REPLACEMENT   PART NUMBERS
                                        Form-A Relay                                    OUTPUT BOARD
Form-C Relay            Form-A Relay                                                                     TLA21010
Form-A Relay            Form-A Relay                                                      RBDLA210       TLA11110
                                                                                           RBD48111

EMC INSTALLATION GUIDELINES

   Although Red Lion Controls Products are designed with a high degree of               effective. The following EMI suppression devices (or equivalent) are
immunity to Electromagnetic Interference (EMI), proper installation and wiring          recommended:
methods must be followed to ensure compatibility in each application. The type
of the electrical noise, source or coupling method into a unit may be different            Fair-Rite part number 0443167251 (RLC part number FCOR0000)
for various installations. Cable length, routing, and shield termination are very          Line Filters for input power cables:
important and can mean the difference between a successful or troublesome
installation. Listed are some EMI guidelines for a successful installation in an        Schaffner # FN2010-1/07 (Red Lion Controls # LFIL0000)
industrial environment.
                                                                                        6. To protect relay contacts that control inductive loads and to minimize radiated
1. A unit should be mounted in a metal enclosure, which is properly connected
   to protective earth.                                                                 and conducted noise (EMI), some type of contact protection network is
                                                                                        normally installed across the load, the contacts or both. The most effective
2. Use shielded cables for all Signal and Control inputs. The shield connection         location is across the load.
   should be made as short as possible. The connection point for the shield             a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide
   depends somewhat upon the application. Listed below are the recommended
   methods of connecting the shield, in order of their effectiveness.                      varistor (MOV) across an AC inductive load is very effective at reducing
   a. Connect the shield to earth ground (protective earth) at one end where the           EMI and increasing relay contact life.
      unit is mounted.                                                                  b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor
   b. Connect the shield to earth ground at both ends of the cable, usually when           switch, care must be taken not to exceed the breakdown voltage of the
      the noise source frequency is over 1 MHz.
                                                                                        transistor when the load is switched. One of the most effective ways is to
3. Never run Signal or Control cables in the same conduit or raceway with AC            place a diode across the inductive load. Most RLC products with solid
   power lines, conductors, feeding motors, solenoids, SCR controls, and                state outputs have internal zener diode protection. However external diode
   heaters, etc. The cables should be run through metal conduit that is properly        protection at the load is always a good design practice to limit EMI.
   grounded. This is especially useful in applications where cable runs are long
   and portable two-way radios are used in close proximity or if the installation       Although the use of a snubber or varistor could be used.
   is near a commercial radio transmitter. Also, Signal or Control cables within
   an enclosure should be routed as far away as possible from contactors,               RLC part numbers: Snubber: SNUB0000
   control relays, transformers, and other noisy components.
                                                                                                            Varistor: ILS11500 or ILS23000
4. Long cable runs are more susceptible to EMI pickup than short cable runs.
                                                                                        7. Care should be taken when connecting input and output devices to the
5. In extremely high EMI environments, the use of external EMI suppression                 instrument. When a separate input and output common is provided, they
   devices such as Ferrite Suppression Cores for signal and control cables is              should not be mixed. Therefore a sensor common should NOT be connected
                                                                                           to an output common. This would cause EMI on the sensitive input common,
                                                                                           which could affect the instrument's operation.

                                                                                           Visit RLC's web site at http://www.redlion.net/Support/InstallationConsiderations.
                                                                                        html for more information on EMI guidelines, Safety and CE issues as they
                                                                                        relate to Red Lion Controls products.

                                                                                     3
1.0 INSTALLING THE TLA

   The TLA meets NEMA 4X/IP65 requirements for indoor use to provide a                        2.39 (60.7)                            1.96 (49.8)
watertight seal in steel panels with a minimum thickness of 0.09 inch, or                         MAX.                                   MAX.
aluminum panels with a minimum thickness of 0.12 inch. The units are intended
to be mounted into an enclosed panel. It is designed so that the units can be                 13 14                                  13 14
stacked horizontally or vertically. The bezel assembly MUST be in place during
installation of the unit.                                                                  1               6          1                                   6

                                                                                           2               7          2                                   7

Instructions:                                                                              3               8          1.96 (49.8) 3                       8 2.39 (60.7)
                                                                                                                          MAX.                                       MAX.

1. Prepare the panel cutout to the dimensions.                                             4               9          4                                   9

2. Remove the panel latch from the unit. Discard the cardboard sleeve.                     5               10         5                                   10

3. Carefully remove the center section of the panel gasket and discard. Slide                 11 12                                  11 12

the panel gasket over the unit from the rear, seating it against the lip at the            PANEL LATCH INSTALLED FOR
                                                                                              VERTICAL UNIT STACKING
front of the case.                                                                                                    PANEL LATCH INSTALLED FOR
                                                                                                                      HORIZONTAL UNIT STACKING
4. Insert the unit into the panel cutout. While holding the unit in place, push the

panel latch over the rear of the unit, engaging the tabs of the panel latch in

the farthest forward slot possible.

5. To achieve a proper seal, tighten the

panel latch screws evenly until the                                                                                                               PANEL GASKET
                                                                                                                                                        BEZEL
unit is snug in the panel, torquing             1.772  +0.024
the screws to approximately 7 in-lbs                   -0.000
(79 N-cm). Over tightening can

result in distortion of the panel, and          (45    +0.6    )                                           PANEL
reduce the effectiveness of the seal.                  -0.0

Note: The installation location of the

TLA is important. Be sure to keep it

away from heat sources (ovens,

furnaces, etc.), and away from                  1.772  +0.024                                  PANEL                                                LATCHING
direct contact with caustic vapors,                    -0.000                              MOUNTING                                                 SLOTS
oils, steam, or any other process                                                                                     PANEL LATCH
byproducts in which exposure may                (45    ) +0.6                                  SCREW
affect proper operation.
                                                       -0.0                                   LATCHING
                                                                                                   TABS

Multiple Unit Stacking                                                                                                                              PANEL
   The TLA is designed for close spacing of multiple units. Units can be stacked
                                                                                                                                          CASE
either horizontally or vertically. For vertical stacking, install the panel latch with                                                    LIP
the screws to the sides of the unit. For horizontal stacking, the panel latch
screws should be at the top and bottom of the unit. The minimum spacing from                                      EB0783
center line to center line of units is 1.96" (49.8 mm). This spacing is the same
for vertical or horizontal stacking.

                                                                  1.96 (49.8)
                                                                       MIN.

STANDARD                                                                                                                                             PRY
   PANEL                                                                                                                                            SLOT

CUT-OUT                                                                                       R
                                                                                                   P

                            IF NEMA 4 IS NOT REQUIRED,                                                     BEZEL
                    THIS PANEL MATERIAL MAY BE REMOVED.

   Note: When stacking units, provide adequate panel ventilation to ensure that            slot on either side of the unit. Twist the screwdriver handle until the unit is
      the maximum operating temperature range is not exceeded.                             ejected enough to allow removal.
                                                                                           Caution: The bezel assembly contains electronic circuits that can be damaged
              Caution: Disconnect power to the unit and to the output control
              circuits to eliminate the potential shock hazard when removing the              by static electricity. Before removing the assembly, discharge static charge on
              bezel assembly.                                                                 your body by touching an earth ground point. It is also important that the
                                                                                              bezel assembly be handled only by the bezel itself. Additionally, if it is
Unit Removal Procedure                                                                        necessary to handle a circuit board, be certain that hands are free from dirt,
   To remove a unit from the panel, first loosen the panel latch screws. Insert               oil, etc., to avoid circuit contamination that may lead to malfunction. If it
                                                                                              becomes necessary to ship the unit for repairs, place the unit in its case
flat blade screwdrivers between the latch and the case on either side of the unit,            before shipping.
so that the latches disengage from the grooves in the case. Push the unit through
the panel from the rear.                                                                   Installing Bezel Assembly
                                                                                              To install the bezel assembly, insert the assembly into the case until the bezel
Removing Bezel Assembly
   The bezel assembly must be removed from the case to replace the output                  is fully seated against the lip of the case. Properly installing the bezel assembly
                                                                                           is necessary for watertight sealing.
board. To remove the bezel assembly, insert a flat blade screwdriver into the pry

                                                                                        4
2.0 WIRING THE TLA                                                                     RTD
                                                                                          When connecting the RTD, be certain that the connections are clean and
   After the unit has been mechanically mounted, it is ready to be wired. All
wiring connections are made to the rear screw terminals. When wiring the unit,         tight. RTD sensors have a higher degree of accuracy and stability than
use the numbers on the label and those embossed on the back of the case, to            thermocouple sensors. Most RTD sensors available are the three wire type. The
identify the position number with the proper function.                                 third wire is a sense lead for canceling the effects of lead resistance of the probe.
                                                                                       Four wire RTD elements may be used by leaving one of the sense leads
   All conductors should meet voltage and current ratings for each terminal.           disconnected. Two wire RTD sensors may be used in either of two ways:
Also cabling should conform to appropriate standards of good installation, local       A) Attach the RTD to terminals #8 and #10. Install a copper sense wire of the
codes and regulations. It is recommended that power supplied to the unit (AC
or DC) be protected by a fuse or circuit breaker. Strip the wire, leaving                 same wire gauge as the RTD leads. Attach one end of the wire at the probe
approximately 1/4" (6 mm) bare wire exposed (stranded wires should be tinned              and the other end to terminal #9. Complete lead wire compensation is
with solder). Insert the wire under the clamping washer and tighten the screw             obtained. This is the preferred method.
until the wire is clamped tightly.                                                     B) Attach the RTD to terminals #8 and #10. Install a shorting wire between
Caution: Unused terminals are NOT to be used as tie points. Damage to the TLA             terminals #9 and #10. A temperature offset error of 2.5C/ohm of lead
                                                                                          resistance exists. The error may be compensated by programming a
   may result if these terminals are used.                                                temperature offset.

POWER WIRING                                                                           Note: With extended cable runs, be sure the lead resistance is less than 15 ohms/
AC Power                                                                                  lead.

   Primary AC power is connected to terminals #11 and #12, labeled AC. To                                                                               USER INPUT
reduce the chance of noise spikes entering the AC line and affecting the TLA,
an AC feed separate from that of the load should be used to power the TLA. Be                                        COMM.            RTD
certain that the AC power to the TLA is relatively "clean" and within the                                                             PROBE
variation limit. Connecting power from heavily loaded circuits or circuits that
also power loads that cycle on and off (contacts, relays, motors, etc.), should be                                               RTD
avoided.
                                                                                                POWER
DC Power
   DCPower (18 to 36 VDC) is connected to terminals #11 and #12 labeled                                   RTD Connection

DC+ and DC- respectively.                                                              RELAY CONNECTIONS
                                                                                          To prolong contact life and suppress electrical noise interference due to the
              CAUTION:Observe proper polarity when connecting DCvoltages.
              Damage to the unit may occur if polarity is reversed.                    switching of inductive loads, it is good installation practice to install a snubber
                                                                                       across the contactor. Follow the manufacturer's instructions for installation.
SIGNAL WIRING
Thermocouple                                                                           5 AMPS   N.C.  *
                                                                                           AT
   When connecting the thermocouple, be certain that the connections are clean                  N.O.  *
and tight. If the thermocouple probe cannot be connected directly to the TLA,          250 VAC
thermocouple wire or thermocouple extension-grade wire must be used to
extend the connection points (copper wire does not work). Always refer to the                                     *                   LOAD  FUSE
thermocouple manufacturer's recommendations for mounting, temperature                  CONTROLLER
range, shielding, etc. For multi-probe temperature averaging applications, two
or more thermocouple probes may be connected to the TLA (always use the
same type). Paralleling a single thermocouple to more than one TLA is not
recommended. Generally, the red wire from the thermocouple is negative and
connected to the TLA's common.

                                                                       USER INPUT

            -                                                                                                                                                                  AC/DC
COMM.                                                                                                                                                                          POWER

TC                       +                                                             Note: Snubber leakage current can cause some electromechanical devices to be
                                                                                          held ON.
NO
CONNECTION                                                                             *Terminal numbers are model dependent. See Terminal Configurations for
                                                                                          description.
POWER
                                                                                       REMOTE RESET WIRING
Thermocouple Connection                                                                   The use of shielded cable is recommended. Follow the EMC installation

                                                                                       guidelines for shield connection.
                                                                                          Terminal #6 is the Remote Reset. Any form of mechanical switch may be

                                                                                       connected to terminal #6 (REMOTE RESET) and terminal #8 (COMM.).
                                                                                       Sinking open collector logic with less than 0.7 V saturation and off-state leakage
                                                                                       current of less than 1 A may also be used.

                                                                                    5
3.0 FRONT PANEL DESCRIPTION                                                               MAIN DISPLAY-

                      SECONDARY DISPLAY-                                                  DISPLAYS THE PROCESS TEMPERATURE.
                                                                                          ALSO DISPLAYS MNEMONIC OF SELECTED
                                 DISPLAYS THE LIMIT SETPOINT.                             PARAMETER IN A CONFIGURATION MODULE.
                                 ALSO DISPLAYS MNEMONIC OR
                                                                                          ILLUMINATES WHEN ALARM 2 IS ON.
                                             NUMERIC VALUE WHEN
                                        MODIFYING A PARAMETER.

                                          EX OUT A1 A2

          ILLUMINATES WHEN THE            RP                                                                         ILLUMINATES WHEN ALARM 1 IS ON.

         PROCESS TEMPERATURE                                                              ILLUMINATES WHEN THE LIMIT OUTPUT IS DE-ENERGIZED.

                 EXCEEDS THE LIMIT                                                        checks for correct internal operation and displays an error message (E-xx) if an
                               SETPOINT.                                                  internal fault is detected. (See the Troubleshooting section for further
                                                                                          information.)
   The front panel bezel material is flame and scratch resistant, tinted plastic that
meets NEMA 4X/IP65 requirements, when properly installed. Continuous                         Upon completion of this sequence, the TLA begins displaying the input value
exposure to direct sunlight may accelerate the aging process of the bezel. The            and setpoint, and updates the outputs based upon this condition.
bezel should be cleaned only with a soft cloth and neutral soap product. Do NOT
use solvents. There are two 4-digit LED displays, a red upper Main Display and            TLACONFIGURATIONOVERVIEW
a lower green Secondary Display.                                                             The TLA is programmed with certain parameter settings from the factory.

   There are up to four panel annunciators, with red backlighting, that illuminate        Factory settings are listed in parentheses in the various Configuration of
to inform the operator of the TLA and output status. See the front panel diagram          Parameters tables. In many cases, these settings must be changed to the
for a description of the annunciators. Four front panel buttons are used to access        particulars of the application before proper operation can be started.
different modes and parameters. The following is a description of each button.
                                                                                             The TLA is typically in the Normal Display Mode. In this mode, the process
   Do NOT use tools of any kind (screwdrivers, pens, pencils, etc) to operate the         temperature is displayed in the main (top) display, and the limit setpoint is
keypad of this unit.                                                                      displayed in the secondary (bottom) display. When changes to the parameter
                                                                                          configurations are needed, the P button is pressed, and the TLA will enter into
Button Functions                                                                          the Parameter Mode.

R - The Reset (R)button is used to reset the limit and alarm relays. The limit output     PARAMETERCONFIGURATIONBASICSTARTUP
   cannot be reset until the process temperature returns to the proper operating             For basic start-up, it is important to verify or change Input Parameter Module
   range. Latched alarms can be reset regardless of limit exceed condition.
                                                                                          (1-IN) parameters tYPE and SCAL, and Output Parameter Module (2-OP)
P - The Parameter (P) button is used to access programming, enter the change,             parameter LiAC (Limit Trip Action). For alarm set-up, it is important to verify
   and scroll through the available parameters in any mode.                               or change Alarms Parameter Module (4-AL) parameters ACt1, AL-1, ACt2, and
                                                                                          AL-2.
UP, DN - The Up/Down buttons are used to modify parameters.
                                                                                             If the above Input parameters or the input wiring connections are not correct,
TLA POWER-UP                                                                              then the main (top) display may display an error message or incorrect value.
   Upon applying power, the TLA delays input indication and control action for            Verify the input programming and wiring. (If incorrect display continues, refer
                                                                                          to the Troubleshooting section.)All other parameter configurations are important
five seconds to perform several self-diagnostic tests and to display basic TLA            but will not prevent the TLA from showing a correct display.
information. Initially, the TLA illuminates both displays and all annunciators to
verify that all display elements are functioning. The TLA then displays the
programmed input sensor type in the main (top) display and the revision number
of the TLA's operating system in the secondary (bottom) display. The TLA

4.0 PARAMETER MODE

   The Parameter Mode is accessed by pressing the PButton from the                        immediately, but the change is not committed to non-volatile memory until the
NormalDisplay Mode. While in the ParameterMode, the temperature is                        TLA is returned to the Normal Display Mode. If power loss occurs before
displayed in the main (top) display, and the parameter is displayed in the                returning to the normal display mode, the new values must be re-entered.
secondary (bottom) display. The correct password must be entered before any
parameters can be accessed. To modify values, use the UP or DOWN button                      To gain access to the Configuration Parameter Modules continue to CNFP
while the parameter is displayed. Use the P button to accept the new value, and           and press the UPbutton. These modules allow access to the fundamental set-up
to scroll through the parameters. The TLA will automatically return to the normal         parameters of the TLA. If the setpoint or alarm values are modified, the CNFP
display mode if no action is taken. The TLA responds to the new values                    step will be skipped.

Parameter Mode Reference Table

DISPLAY                    PARAMETER                  RANGE                                                                          DESCRIPTION
         Password to access parameters             0 to 250
PASS                                                                                      If an incorrect value is entered, the TLA will display "End"
                                                -999 to 9999                              momentarily, and then return to the normal display mode. The
  SP     Limit setpoint                         -999 to 9999                              default password is 10. The wildcard password is 222 (in case the
         Alarm #1                               -999 to 9999                              password is forgotten).
AL-1 *   Alarm #2                            "Up" button: enter
AL-2 *   Configuration parameter modules  configuration modules.                          Range limited by SPLO & SPHI.
CNFP
                                                                                          The Alarm parameters can be independently locked out from
End      End of Parameter Mode                                                            appearing. See Configuration Module 3, Parameter Lock-outs.

                                                                                          These modules allow access to the fundamental set-up parameters
                                                                                          of the TLA. The modules are grouped into related
                                                                                          programming steps, such as inputs, outputs, alarms, etc. Upon
                                                                                          completion of each module, the program returns to "CNFP".

                                                                                          When the parameter list has been scrolled through, the TLA
                                                                                          will display "End" momentarily, and then return to the normal
                                                                                          display mode.

*Model Number Dependent.

                                                                                       6
CONFIGURATION PARAMETER MODULES                                                       Pbutton is pressed, however, the change is not committed to permanent memory
   The Configuration Parameter modules are accessed by pressing the UP button         until the TLA is returned to the Normal Display Mode. If power loss occurs before
                                                                                      returning to the Normal Display Mode, the new values must be entered again. At
from CNFP in the Parameter Mode. The UP or DOWN buttons can be pressed to             the end of each module, the TLA will go back to CNFP. Other Parameter Modules
move to the desired Parameter Module. The P button is then pressed to enter into      can be accessed by pressing the UP or DOWN buttons, or pressing P will return
that module. The main (top) display will be the parameter, and the secondary          to the Normal Display Mode.
(bottom) display will be the parameter value. The UP or DOWN buttons are used
to modify the desired parameter value, and the P button enters the new value, and        Parameters that are model number, or program dependent will only be
moves to the next parameter. The TLA responds to the new values after the             displayed when the appropriate options are installed or programmed.

Configure Module 1 - Input Parameters (1-IN)

DISPLAY             PARAMETER                    RANGE                                                                 DESCRIPTION/ COMMENTS
         Input Type                    (FACTORY SETTING)                              Select from the list of various thermocouple and RTD sensors.
tYPE
         Temperature Scale               tc-t - Type T TC                             Select either degrees Fahrenheit (F) or degrees Celsius (C). If
SCAL     Temperature Resolution          tc-E - Type E TC                             changed, be sure to check all parameters.
dCPt     Digital Input Filtering and     tc-J - Type J TC
FLtr     Display Update                  tc-K - Type K TC
                                        tc-r - Type R TC
SHFt     Input Signal Shift             tc-S - Type S TC
SPLO     (correction offset)            tc-b - Type B TC
SPHI     Limit Setpoint Lower Limit     tc-N - Type N TC
         Limit Setpoint Upper Limit      LIN - Linear mV
                                      r385 - 385 curve RTD
                                      r392 - 392 curve RTD
                                       rLIN - Linear ohms

                                                 (tc-J)

                                               F or C
                                                  (F)

                                      0 or 0.0                                        Select either 1 or 0.1 degree resolution. If changed, be sure to
                                         (0)                                          check all parameters.

                                      0 to 4                                          Select the relative degree of input signal filtering and display update

                                      0 - least input filtering                       rate. The filter is an adaptive digital filter that discriminates between

                                      3 - most input filtering                        measurement noise and actual process changes. Therefore, the

                                      4 - most input filtering and slower 500 influence on step response time is minimal. If the signal is varying

                                      msec display update rate (outputs still too greatly due to measurement noise, increase the filter value.

                                      update at 100 msec rate)                        Conversely, if the fastest TLA response is desired, decrease the

                                      (1)                                             filter value.

                                       -999 to 9999                                   If the TLA temperature disagrees with a reference temperature
                                      1 or 0.1 degree                                 instrument or if the temperature sensor has a known calibration, the
                                                                                      TLA temperature can be compensated by a correction offset. The
                                              (0)                                     following equation expresses the relationship: Desired Display
                                                                                      Temp = (TLA Temp) + SHFt. Normally set to 0.

                                        -999 to 9999                                  The TLA has programmable high and low setpoint limit values to
                                      1 or 0.1 degree                                 restrict the setting range of the limit setpoint. Set the limit values so
                                                                                      that the temperature setpoint value cannot be set outside the safe
                                               (0)                                    operating area of the process. SPHI must be above SPLO.

                                       -999 to 9999
                                      1 or 0.1 degree

                                            (9999)

Configure Module 2 - Output Parameters (2-OP)

DISPLAY              PARAMETER                 RANGE                                                                   DESCRIPTION/ COMMENTS
         Limit Output Trip Action     (FACTORY SETTING)
LiAc                                                                                  The limit output is selectable for high or low trip activation. If the
                                        LO - Low Acting                               process temperature goes above the limit setpoint for a high trip, or
                                         HI - High Acting                             below the limit setpoint for a low trip, the limit relay will de-energize
                                                                                      to initiate a process shutdown. See the Limit Output Action section
                                                 (HI)                                 for details.

                                                                                   7
Configure Module 3 - Lockout Parameters (3-LC)

DISPLAY              PARAMETER                               RANGE                                                DESCRIPTION/ COMMENTS
         Password                                  (FACTORY SETTING)
PASS                                                                        The password is required to access all parameters. The password can be
         Alarms #1 and #2 access                         0 to 250           set to any value between 0 and 250. A wildcard password, 222, can be
AL *    level                                              (10)            used as an alternative to the programmed password.
                                                                            The alarm(s) parameter in the Parameter Mode can be configured to be
FPrS     Front panel reset         LOC - lockout, prevents the alarms from  completely locked out, read only, or fully accessible.
                                                       appearing
                                                                            The front panel R button can be enabled or disabled. The Remote Reset
                                      rEd - read only, alarms appear, but   input is not affected by this setting.
                                                 cannot be modified

                                    Ent - enter, alarms appear, and can be
                                                        modified
                                                          (Ent)

                                                    NO - disabled
                                                     YES - active

                                                          (YES)

*Model Number Dependent.

Configure Module 4 - Alarms Parameters (4-AL)

DISPLAY              PARAMETER              RANGE                                                      DESCRIPTION/ COMMENTS
         Alarm 1 action mode       (FACTORY SETTING)
Act1                               A-HI - absolute high      When deviation low-acting with positive alarm value (d-LO), deviation high-
                                   A-LO - absolute low       acting with negative value (d-HI), or band inside-acting (b-IN) is selected for
rSt1     Alarm 1 reset mode        d-HI - deviation high     the alarm action, the indicator is OFF when the alarm output is ON. See the
                                   d-LO - deviation low      Alarms section for complete details of each action. If changed, check alarm
Stb1     Alarm 1 standby function                            values.
         (delay)                    b-IN - band inside
                                   b-Ot - band outside       Automatic reset alarms are reset by the TLA when the alarm condition clears.
AL-1 Alarm 1 value                                           Latched alarms require operator action to reset the alarm condition. The front
                                            (A-HI)           panel R button, if enabled, can be used to reset a latched alarm (see FPrS in
Act2 *   Alarm 2 action mode         Auto - automatic        Configure Module 3). A latched alarm condition may also be reset via the
                                   LATC - manual reset       Remote Reset input. See the Reset Action diagram in the Alarms section.
rSt2 * Alarm 2 reset mode
                                            (Auto)           The alarm(s) may be independently configured to exhibit a power-on, standby
Stb2 *   Alarm 2 standby function                            delay which suppresses the alarm output from turning ON until the temperature
AL-2 *   (delay)                         NO or YES           first stabilizes outside the alarm region. After this condition is satisfied, the alarm
AHYS     Alarm 2 value                       (NO)            standby delay is canceled and the alarm triggers normally, until the next TLA
                                                             power-on. This feature also works for deviation and band alarms when the
         Alarm hysteresis value         -999 to 9999         setpoint is changed via keypad. This action suppresses "nuisance" alarms. See
                                               (0)           the Alarm Standby diagram in the Alarms section.
                                                             The alarm values are either absolute values, or relative to the limit setpoint value
                                   A-HI - absolute high      (deviation and band alarms). An absolute alarm value is the value that is entered
                                   A-LO - absolute low       for the alarm. A relative alarm value is the mathematical sum of the temperature
                                   d-HI - deviation high     limit setpoint value and the alarm value (positive or negative), thus a relative
                                   d-LO - deviation low      alarm tracks the limit setpoint value as it is changed. If the alarm action is set as
                                    b-IN - band inside       a Band Alarm, then only a positive alarm value can be entered.
                                   b-Ot - band outside
                                                             The Alarm 2 parameters are programmed independently of alarm 1. See the
                                            (A-HI)           corresponding Alarm 1 parameter for description.
                                     Auto - automatic
                                   LATC - manual reset       The alarm value(s) have a programmable hysteresis band to prevent alarm
                                                             output chatter near the alarm trigger point. The hysteresis value should be set
                                            (Auto)           to eliminate this effect. A value of 2 to 5 is usually sufficient for most
                                                             applications. A single alarm hysteresis value applies to both alarms. See the
                                         NO or YES           Alarm Action Figures, in the Alarms section, for the effect of hysteresis on the
                                             (NO)            various alarm types.

                                        -999 to 9999
                                               (0)

                                           1 to 250
                                               (1)

*Model Number Dependent.

                                                          8
Configure Module 9 - Factory Service Operations (9-FS)

      DISPLAY              PARAMETER                              RANGE                                          DESCRIPTION/ COMMENTS

CodE           Factory service function    48 - Calibrate instrument            TLA calibration. Refer to the Calibration section for details.
               code
                                           66 - Reset parameters to factory     Entering code 66 restores all parameters to factory settings. The
                                           settings                             unit indicates the operation after the P button is pressed, by
                                                                                displaying "rSEt" in the lower display momentarily.
                                           77 (twice in succession) -
                                           Reset TLA calibration to nominal     Caution: this operation erases the TLA calibration values and
                                           values                               defaults the values to nominal settings. Reading errors of 10%
                                                                                may result. Do not perform this operation unless the TLA has lost
                                                                                calibration. Loss of calibration is signaled by an "E-CL" error
                                                                                flag at power-up. To clear this flag, perform calibration procedure
                                                                                as noted in the Calibration section. Alternatively, "stepping" through
                                                                                one of the calibration procedures clears the error flag, but does
                                                                                NOT validate the calibration accuracy in any manner.

USER PARAMETER VALUE CHART

TLA Number _____________

MNEMONIC       PARAMETER                   USER SETTING                          Lockout Parameters
                                           USER SETTING
               Password                                                         MNEMONIC  PARAMETER                USER SETTING
               Limit Setpoint
               Alarm 1 Value                                                              Password
               Alarm 2 Value                                                              Alarm(s) Access Level
                                                                                          Front Panel Reset

Input Parameters                                                                Configure Alarm Parameters

MNEMONIC       PARAMETER                                                        MNEMONIC  PARAMETER                USER SETTING

               Input Sensor Type                                                          Alarm 1 Action Mode
               Temperature Scale Units                                                    Alarm 1 Reset Mode
               Temperature Resolution                                                     Alarm 1 Standby Enabled
               Digital Filtering                                                          Alarm 1 Value
               Input Offset                                                               Alarm 2 Action Mode
               Limit Setpoint Lower Limit                                                 Alarm 2 Reset Mode
               Limit Setpoint Upper Limit                                                 Alarm 2 Standby Enabled
                                                                                          Alarm 2 Value
                                                                                          Alarm Hysteresis Value

Output Parameters

MNEMONIC       PARAMETER                   USER SETTING

               Limit Output Trip Action

                                                                             9
LIMITOUTPUTACTION                                                                                                                  High Trip Action
   The limit output is selectable for high or low trip activation. If the process
                                                                                                                                           Setpoint
temperature goes above the limit setpoint for a high trip, or below the limit                                                      Process Temp
setpoint for a low trip, the limit relay will de-energize to initiate a process
shutdown. The limit output cannot be reset until the process temperature returns                                                   Reset             OFF             ON                                        ON
to the proper operating range; manual reset is required. The following action                                                                                               OFF               OFF
figures describe the status of the limit output and the front panel indicators for
various over/under setpoint, and reset conditions. Reset is either by the front                                                           EXceed     OFF  ON                                                   OFF
panel R button, if enabled, or by the Remote Reset input, terminal #6. Refer to                                                    Annunciator                                                                 Energized
Configure Module 2 - Output Parameters for details of configuring the limit
output. Refer to Configure Module 3 - Lockout Parameters for details of                                                                   OUT                        ON                                        ON
configuring the front panel Reset button.                                                                                          Annunciator        OFF                                     OFF
                                                                                                                                                     Energized
                                                                                                                                          Limit                                                                OFF
                                                                                                                                          Output                     De-energized                              Energized

                                                                                                                                   Low Trip Action

                                                                                                                                   Process Temp

                                                                                                                                            Setpoint

                                                                                                                                   Reset             OFF             ON
                                                                                                                                                                            OFF

                                                                                                                                          EXceed     OFF  ON
                                                                                                                                   Annunciator

                                                                                                                                          OUT                        ON
                                                                                                                                   Annunciator        OFF
                                                                                                                                                     Energized
                                                                                                                                          Limit
                                                                                                                                          Output                     De-energized

5.0 Alarms (Optional)                                                                                                              might be OFF while the output is ON. Refer to Configure Module 4 - Alarm
                                                                                                                                   Parameters for details of configuring the alarms.
   The alarm action figures describe the status of the alarm output and the front
panel indicator for various over/under temperature conditions. The alarm output
wave form is shown with the output in the automatic reset mode. Select the
alarm action with care -- in some configurations, the front panel indicator (LED)

            ABSOLUTE HIGH-ACTING ALARM (A-HI)                                                                                                                ABSOLUTE LOW-ACTING ALARM (A-LO)

TEMP                                                                                                                                             TEMP

AL

                                                                                                           HYS

                                                                                                                                              AL                                               HYS

OUTPUT OFF      OUTPUT ON  OUTPUT OFF  OUTPUT ON                                                                                   OUTPUT OFF             OUTPUT ON                OUTPUT OFF  OUTPUT ON
   LED OFF         LED ON     LED OFF     LED ON                                                                                      LED OFF                LED ON                   LED OFF     LED ON

DEVIATION HIGH-ACTING WITH POSITIVE ALARM VALUE (d-HI)                                                                             DEVIATION HIGH-ACTING WITH NEGATIVE ALARM VALUE (d-HI)
     INPUT                                                                                                                              INPUT

SP + AL                                                                                                                              SP

                                                                                                                          HYS

                                                                                                                                   SP + (-AL)

                                                                                                                                                                                                                                                                     HYS

            SP  OUTPUT ON  OUTPUT OFF  OUTPUT ON                                                                                   OUTPUT ON         OUTPUT OFF                    OUTPUT ON   OUTPUT OFF
                   LED ON     LED OFF     LED ON                                                                                     LED OFF            LED ON                       LED OFF      LED ON
OUTPUT OFF
   LED OFF

                                                                                                                               10
           DEVIATION LOW-ACTING WITH POSITIVE ALARM VALUE (d-LO)                                                                                                                                      DEVIATION LOW-ACTING WITH NEGATIVE ALARM VALUE (d-LO)
                  INPUT                                                                                                                                                                                          INPUT
                                                                                                                                                                                                                SP
                                                                                                                               HYS
                                                                                                                                                                                                                                                                                                                              HYS
           SP + AL
                  SP                                                                                                                                                                                  SP + (-AL)

OUTPUT ON                     OUTPUT OFF  OUTPUT ON                                                                                                                    OUTPUT OFF                     OUTPUT OFF             OUTPUT ON                    OUTPUT OFF       OUTPUT ON
  LED OFF                        LED ON     LED OFF                                                                                                                       LED ON                        LED OFF                LED ON                       LED OFF          LED ON

          INPUT               BAND INSIDE ACTING (b-IN)                                                                                                                                                INPUT                 BAND OUTSIDE ACTING (b-Ot)
SP + AL                                                                                                                                                                                      SP + AL
                                                           HYS                                                                                                                                                                             HYS
       SP
                                                                                                                                                                                             SP

SP - AL                                                                                                                                                                                      SP - AL                                                                  HYS
                                                                                                                                                                  HYS

OUTPUT ON        OUTPUT OFF   OUTPUT ON   OUTPUT OFF            OUTPUT ON                                                                                              OUTPUT OFF            OUTPUT OFF       OUTPUT ON      OUTPUT OFF  OUTPUT ON        OUTPUT OFF            OUTPUT ON
  LED OFF             LED ON    LED OFF        LED ON             LED OFF                                                                                                   LED ON             LED OFF          LED ON         LED OFF     LED ON           LED OFF               LED ON

Alarm Reset Sequence                                                                                                                                                                         Alarm Standby Delay Sequence

                 INPUT                                                                                                                                                                                        INPUT                   ALARM MODE
                                                                                                                                                                                                                             (ABSOLUTE LOW ACTING
                                              ALARM MODE                                                                                                                                                                     W/AUTO-RESET SHOWN)
                              (ABSOLUTE LOW ACTING SHOWN)

ALARM VALUE

                                                                                                                                                                                             ALARM VALUE

                                                                                                                                                                                   TIME

                                                                                                                                                                                                  UNIT                                                                                                                             TIME
                                                                                                                                                                                             POWER-ON
AUTOMATIC               OFF   ON          OFF                   ON                                                                                                     OFF
   RESET                                                                                                                                                                                           STANDBY
                                                                                                                                                                                                   ENABLED
                                                                                                                                                                                                                                         OFF              ON               OFF  ON
                                                                                                                                                                                                                                                     OFF
MANUAL                  OFF   ON          OFF                              ON
RESET
                                                                MANUAL RESET
                                                                PERFORMED BY OPERATOR                                                                                                        STANDBY                     ON                                           ON OFF    ON

                                                                                                                                                                                             DISABLED

CALIBRATION CHECKS                                                                                                                                                                           RTD Ohms Reading Check

   The instrument has been fully calibrated at the factory for all input types. If                                                                                                           1. Connect RTD simulator (with an accuracy of 0.1 ohm or better) capable of
the unit appears to be indicating or controlling incorrectly, see the Troubleshooting                                                                                                           operating with less than 150 A to terminals #8, #9, & #10.
section before attempting this procedure.
                                                                                                                                                                                             2. Configure Input Parameters Module 1 for linear ohms (rLin) input, under tYPE.
   If the TLA is suspected of reading incorrectly, the instrument may be checked                                                                                                             3. Compare the TLA read-out with the RTD simulator at various points over the
for indication accuracy without disturbing the factory calibration. The following
procedures may be used for this purpose.                                                                                                                                                        range 2.0 to 300.0 ohms. The tolerance is (0.3% of span + 1 LSD).
                                                                                                                                                                                             4. Calibrate the TLA RTD ohms if out of tolerance.
   Note: Allow hour warm-up before checking these parameters.
                                                                                                                                                                                             Error Flag E-CL
mV Reading Check
                                                                                                                                                                                                If error flag "E-CL" appears at power-up, a loss of calibration parameters due
1. Connect a DC mV source with an accuracy of 0.03% or better to terminal #8                                                                                                                 to noise spikes has occurred. Entering code 77 twice in Factory Service
   (-) & #9 (+).                                                                                                                                                                             Operations Module (9-FS) erases the TLA calibration values and defaults the
                                                                                                                                                                                             values to nominal settings. Reading errors of 10% may result. It is recommended
2. Configure Input Parameters Module 1 for linear mV (Lin) input, under tYPE.                                                                                                                that the TLA be fully recalibrated. If using thermocouple only, the RTD
3. Compare the TLA read-out to the standard at various points over the range                                                                                                                 calibration need not be performed.

   (-5.00 mV to 56.00 mV). The tolerance is (0.15% of reading + 1 LSD).                                                                                                                        Note: the "E-CL" flag may be cleared by "stepping" through cold junction
4. Calibrate the TLA if the readings are out of tolerance.                                                                                                                                   calibration procedure without the need to change any calibration values. A
                                                                                                                                                                                             10% reading error will still exist.
Thermocouple Cold Junction Temperature Check
1. Connect a thermocouple probe of known accuracy (Types T, E, J, K, N only)

   to TLA. Select the probe used in Configure Module 1.
2. Connect a reference temperature probe to measuring end of thermocouple to

   monitor temperature. Allow sufficient time for temperatures to equalize.
3. Compare TLA display with reference temperature probe. The TLA display

   should equal the calibrated probe temperature. (Tolerance is 1C.)
4. Calibrate the cold junction temperature if out of tolerance.

                                                                                                                                                                                         11
6.0 Calibration                                                                            This procedure may be aborted by disconnecting power to the TLA before
                                                                                        exiting the configuration mode. The existing calibration settings remain in
   When re-calibration is required (generally every two years), this procedure          affect.
should be performed by qualified technicians using appropriate equipment.               Note: After completing any of the calibration sequences, the TLA defaults the
Equipment source accuracy of 0.03% or better is required.
                                                                                           input sensor type to thermocouple type "J" (tc-J). Be sure to set input sensor
   The procedure consists of: applying accurate mV signals, setting the                    for proper type.
thermocouple cold junction temperature, and applying precision resistance,              Note: The TLA must be restored to normal display mode before any data is
among others. Allow a 30 minute warm-up period before starting this procedure.             stored.
Do not use thermocouple wire for the millivolt or RTD ohms calibration.
                                                                                                                                    DESCRIPTION/ COMMENTS
Factory Service Operations - Calibration (9-FS)
                                                                                          Calibrate instrument.
DISPLAY                   PARAMETER              RANGE                                    Calibration required for both RTD and TC input.If this procedure is performed,
                                                                                          the cold junction temp or RTD ohms calibration procedures in turn must be
CodE     Enter function code                        48                                    completed.
CAL      Millivolt calibration                    yes/no                                  Not required if only using RTD input. This procedure can only be performed
                                                                                          AFTER an accurate mV calibration.
CJC      Thermocouple cold junction              yes/no                                   Not required if only using TC input. This procedure can only be performed
rtd      temperature calibration                 yes/no                                   AFTER an accurate mV calibration.

         RTD resistance calibration

Millivolt Calibration (CAL)                                                             RTD Ohms Calibration (RTD)
                                                                                           This procedure must be performed AFTER an accurate mV calibration.
   Connect precision millivolt source with an accuracy of 0.03% to terminals #8
                                                                                        Connect one leg of precision resistance (accuracy of 0.1 ohm) to terminals #9
(-) & #9 (+). Cold Junction or RTD ohms calibration MUST be performed after             and #10 together, and the other leg to #8.

millivolt calibration.

DISPLAY                 ACTION       DESCRIPTION/ COMMENTS                              DISPLAY            ACTION   DESCRIPTION/ COMMENTS
                                                                                                                    Wait 10 seconds, press P.
StP1     Apply 0.0 mV                Wait 10 seconds, press P.                          rtd1      Connect 0.0 ohm   Wait 10 seconds, press P.
                                                                                        rtd2         (jumper wire)
StP2     Apply 14.0 mV               Wait 10 seconds, press P.
                                                                                                 Connect 277.0 ohm
StP3     Apply 28.0 mV               Wait 10 seconds, press P.

StP4     Apply 42.0 mV               Wait 10 seconds, press P.

StP5     Apply 56.0 mV               Wait 10 seconds, press P.

Thermocouple Cold Junction Calibration (CJC)

This procedure must be performed AFTER an accurate mV calibration.
1. Exit Factory Service Operations (continually press P until "End"), and return

   to Normal Display Mode.
2. Connect a thermocouple probe of known accuracy to the TLA (Types T, E, J,

   K, and N only). Select the probe type used in Configure Module 1.
3. Connect a reference temperature probe to the measuring end of the TLA

   thermocouple probe. The two probes should be shielded from air movement
   and allowed sufficient time to equalize in temperature. (As an alternative, the
   TLA thermocouple probe may be placed in a calibration bath of known
   temperature.)
4. Compare TLA display with reference temperature probe (or calibration bath).
   If the displayed TLA temperature does not equal the reference probe
   temperature, calculate the CJ error as follows:

      CJ Error = reference probe temperature - displayed TLA temperature
5. Enter Factory Service Operations Module (9-FS).

DISPLAY    PARAMETER                   DESCRIPTION/ COMMENTS

CJC     Cold Junction  Observe the indicated cold junction
         Temperature    temperature. Add the calculated CJ Error to
                        the displayed value. Enter the sum as the new
                        value for CJC. Exit 9-FS and repeat step 4.

                        Note: If the initial value for CJC is not within
                        the range of 15C to 40C, enter 25.0 for
                        CJC and repeat the Cold Junction Calibration
                        procedure.

                                                                                    12
7.0 Troubleshooting                                                                      For further technical assistance, contact technical support at the appropriate
                                                                                      company numbers listed.
   The majority of problems can be traced to improper connections or incorrect
set-up parameters. Be sure all connections are clean and tight, that the correct
output board is fitted, and that the set-up parameters are correct.

                      PROBLEMS                             POSSIBLE CAUSE                                                              REMEDIES
NO DISPLAY
                                1. Power off.                                          1. Check power.
TLA NOT WORKING                 2. Brown-out condition.                                2. Verify power reading.
"E-FP" IN DISPLAY               3. Loose connection or improperly wired.               3. Check connections.
"E-UP" IN DISPLAY               4. Bezel assembly not fully seated into rear of TLA.   4. Check installation.
"E-E2" IN DISPLAY
"E-CL" IN DISPLAY               1. Incorrect parameter set-up.                         1. Check set-up parameters.
"..." or "-.." IN DISPLAY
                                1. Defective front panel button.                       1. Press R to escape, then check all buttons for proper operation.
"OPEN" IN DISPLAY                                                                      2. Replace unit.
                                1. Internal problem with TLA.
"OLOL" IN UPPER DISPLAY                                                                1. Replace unit.
                                1. Loss of setup parameters due to noise spike or
"ULUL" IN UPPER DISPLAY            other EMI event.                                    1. Press R to escape, then check all set-up parameters.
                                                                                          a. Check sensor input and AC line for excessive noise.
"OLOL" OR "ULUL" IN LOWER       1. Loss of calibration parameters due to noise            b. If fault persists, replace TLA.
DISPLAY                            spike or other EMI event.
                                                                                       1. Press R to escape, then check TLA accuracy.
                                1. Display value exceeds display range.                   a. Recalibrate TLA. (See Factory Service Module code 77.)
                                2. Defective or mis-calibrated cold junction circuit.     b. Reset parameters to factory default settings.
                                3. Loss of set-up parameters.
                                4. Internal malfunction.                               1. Change resolution to display whole number and verify reading.
                                                                                       2. Perform cold junction calibration.
                                1. Probe disconnected.                                 3. Check set-up parameters.
                                2. Broken or burned-out probe.                         4. Perform Input calibration.
                                3. Corroded or broken terminations.
                                4. Excessive process temperature.                      1. Connect probe.
                                                                                       2. Replace probe.
                                1. Check input parameters.                             3. Check connections.
                                2. Change to input sensor with a higher                4. Check process parameters.

                                   temperature range.                                  1. Input exceeds range of TLA.
                                3. Replace transmitter or probe.                       2. Temperature exceeds range of input probe.
                                4. Reduce temperature.
                                5. Perform input calibration.                          3. Defective or incorrect transmitter or probe.
                                                                                       4. Excessive high temperature for probe.
                                1. Input is below range of TLA.                        5. Loss of setup parameters.
                                2. Temperature below range of input probe.
                                3. Defective or incorrect transmitter or probe.        1. Check input parameters.
                                4. Excessive low temperature for probe.                2. Change to input sensor with a lower temperature range.
                                5. Loss of setup parameters.                           3. Replace transmitter or probe.
                                                                                       4. Raise temperature.
                                1. Signal input exceeds allowable range by 5%.         5. Perform input calibration.

                                                                                       1. Check remote signal source.

                                                                                  13
8.0 Installing an Output Board                                                                   AL1

   The TLA is supplied with an output board installed.                                                               Form-C Relay

Replacing Output Board                                                                           LIMIT           Output Board

1. Remove the bezel assembly.                                                                                    #RBDLA210
2. Lift up on the top bezel board latch while gently pulling out on the bezel/
                                                                                                 AL2             Form-A Relay
   display board assembly. Do NOT remove the display board from the bezel.
3. Remove the output board by pulling it away from the other boards. Replace                     AL1             Output Board

   the output board by aligning the board to board connector. Be certain the
   connector is fully mated.
4. Connect the bezel/ display board assembly by guiding the board ends into the
   bezel latches. Slide the assembly on evenly until the display board connector
   is completely engaged and bezel latches are fully seated onto the boards.

                                                                                                                 #RBD48111

                                                                                                 LIMIT

   DISPLAY                                                                        CPU BOARD

    BOARD                                                                                                                                                                                                                        EB0784
CONNECTOR

                                                                                                         MD1797

                                                                                  EX  OUTA1                                    OUTPUT BOARD
                                                                                      P
                      BEZEL BOARD                                                            A2          OUTPUT BOARD
                        LATCH                                                                            CONNECTOR
                                                                                                 POWER
          BEZEL/DISPLAY                                                                          SUPPLY
          BOARD ASSEMBLY                                                                         BOARD

9.0 Terminal Configurations

                  ACModels                                                                       DCModels

Form-A Limit Relay with 2 Alarms                                                  Form-A Limit Relay with 2 Alarms

          A2 N.O. 1     13 14      6   REMOTE                                                    A2 N.O. 1                                                                                                                               13 14  6  REMOTE
           COMM. 2                     RESET                                                      COMM. 2                                                                                                                                          RESET
ALARM                                                                                 ALARM                                                                                                                                                     7
RELAYS    A1 N.O. 3                7                                                  RELAYS     A1 N.O. 3                                                                                                                                      8 COMM. -
                                   8 COMM. -
  LIMIT                                                                                 LIMIT       N.O. 4                                                                                                                                      9  TC +
RELAY         N.O. 4              9   TC +                                            RELAY     COMM. 5
            COMM. 5                                                                                                                                                                                                                      11 12  10 RTD
                        11 12      10
                                       RTD                                                               POWER (+) (-)
                        ~AC ~AC
            85-250 VAC                                                                                   DC 18-36V 7W
            50/60 HZ 8VA                                                                                  AC 24V 10%

                                                                                                         50/60 HZ 9VA

Form-C Limit Relay with 1 Alarm                                                   Form-C Limit Relay with 1 Alarm

ALARM 1     N.O. 1 13 14           6   REMOTE                                         ALARM 1        N.O. 1                                                                                                                              13 14  6  REMOTE
RELAY                                 RESET                                           RELAY     COMM. 2                                                                                                                                           RESET
                                                                                                                                                                                                                                                7
   LIMIT    COMM. 2                7                                                      LIMIT     N.O. 3                                                                                                                                      8 COMM. -
   RELAY       N.O. 3                  COMM.                                             RELAY
                                   8              -                                                      N.C. 4                                                                                                                                 9  TC +

                N.C. 4             9   TC +                                                      COMM. 5 11 12 10 RTD
            COMM. 5
                        11 12      10  RTD                                                               POWER(+) (-)

                        ~AC ~AC                                                                          DC 18-36V 7W
            85-250 VAC                                                                                    AC 24V 10%
            50/60 HZ 8VA
                                                                                                         50/60 HZ 9VA

                                                     14
This page intentionally left blank

                             15
                                                        LIMITED WARRANTY

                          The Company warrants the products it manufactures against defects in materials and workmanship
                          for a period limited to two years from the date of shipment, provided the products have been stored,
                          handled, installed, and used under proper conditions. The Company's liability under this limited
                          warranty shall extend only to the repair or replacement of a defective product, at The Company's
                          option. The Company disclaims all liability for any affirmation, promise or representation with
                          respect to the products.

                          The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against
                          damages, claims, and expenses arising out of subsequent sales of RLC products or products
                          containing components manufactured by RLC and based upon personal injuries, deaths, property
                          damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be
                          to any extent liable, including without limitation penalties imposed by the Consumer Product Safety
                          Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty
                          Act (P.L. 93-637), as now in effect or as amended hereafter.

                          No warranties expressed or implied are created with respect to The Company's products except those
                          expressly contained herein. The Customer acknowledges the disclaimers and limitations contained
                          herein and relies on no other warranties or affirmations.

Red Lion Controls              Red Lion Controls            Red Lion Controls                                                                        Red Lion Controls
Headquarters                          Europe                         India                                                                                           China
20 Willow Springs Circle
York PA 17406                   Softwareweg 9       201-B, 2nd Floor, Park Centra                                                               Unit 302, XinAn Plaza
Tel +1 (717) 767-6511     NL - 3821 BN Amersfoort   Opp 32 Mile Stone, Sector-30                                                Building 13, No.99 Tianzhou Road
Fax +1 (717) 764-0839     Tel +31 (0) 334 723 225  Gurgaon-122002 Haryana, India
                          Fax +31 (0) 334 893 793                                                                                     ShangHai, P.R. China 200223
                                                         Tel +91 984 487 0503                                                                  Tel +86 21 6113 3688
                                                                                                                                              Fax +86 21 6113 3683
This datasheet has been downloaded from:
            datasheet.eeworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company

小广播

该厂商的其它器件

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2017 EEWORLD.com.cn, Inc. All rights reserved