Safety Relays

Monitoring Safety Relays with Delayed Outputs

Minotaur MSR138DP

                                                                      Specifications

                                                                      Standards                         EN 954-1, ISO 13849-1, IEC/EN
                                                                                                        60204-1, IEC 60947-4-1, IEC
                                                                                                        60947-5-1, ANSI B11.19, AS4024.1

                                                                      Category Instantaneous/Delayed Cat. 4/Cat. 3 per EN 954-1

                                                                      Approvals                         C-Tick, CE marked for all
                                                                                                        applicable directives and cULus

                                                                      Power Supply                      24V AC/DC, 115V AC or 230V AC
                                                                                                        0.8 to 1.1 x rated voltage, 50/60Hz

                                                                      Power Consumption                 4W

                                                                      Safety Inputs                     1 N.C., 2 N.C. or light curtain

                                                                      Input Simultaneity                Infinite

                                                                      Max. Allowable Input Resistance 135 ohms

                                                                      Reset                             Monitored Manual or Auto./Manual

Description                                                           Outputs                           2 N.O. Safety; 3 N.O. Safety
                                                                                                        Delayed (MSR138DP); 2 N.O.
The MSR138DP is a versatile monitoring safety relay. It can be                                          Safety Delayed (MSR138.1DP); 1
connected in four different input wiring configurations: 1 N.C., 2                                      N.C. Aux. Delayed (MSR138.1DP)
N.C., or 2 PNP connections from a light curtain. When connected in
the 2 N.C. fashion, the MSR138DP checks for cross faults across the   Output Utilization per IEC        AC-1: 7A/250V AC
two inputs. When connected to light curtains, the light curtain must  60947-4-1 (Resistive)             DC-1: 7A/24V DC
perform the cross fault detection.
                                                                       Output Utilization per IEC       B300, AC-15
The MSR138DP has output monitoring that can accommodate               60947-5-1 (Inductive)                 6A/250V AC, 6A/125V AC
either automatic/manual reset or a monitored manual rest. When
configured with automatic/manual reset (jumpers on X1-X2 and                                            P300, DC-13; 3A/24V DC
X3-X4), the MSR138DP can have the reset terminals S33-S34                                                   6A/24V DC @ 6 ops/min
jumpered or can be converted to an unmonitored manual reset by
adding a normally open switch in the monitoring loop (S33-S34).       Thermal Current (non switching) Max 7A in one current path
When configured to monitored manual reset, the MSR138DP                 Units with 24V AC/DC supply: 5x3.5A or 3x4.5A
checks the output monitoring circuit through the manual application
of the reset switch.                                                   Units with 115/230V AC supply: 5x2.5A or 3x3.5A

The outputs of the MSR138DP include 2 normally open immediate         Fuses Output (external)           6A Slow Blow or 10A Quick Blow
safety outputs and 3 normally open delayed safety outputs. The
outputs of the MSR138.1DP include 2 normally open immediate           Min. Switched Current/Voltage 10ma/10V
safety rated outputs, 2 normally open delayed safety outputs and 1
normally closed delayed safety output. The safety outputs have        Contact Material                  AgSnO2 + 0.5mAu
independent and redundant internal contacts to help ensure the
safety function.                                                      Power On Delay                    1s

A N.C. timer reset switch can be added to force the delayed contacts  Response Time                     15ms
opened prior to the completion of the timing cycle. An electronic
protection circuit detects shorts across the input, when the          Recovery Time                     100ms
MSR138DP wired for cross fault detection.
                                                                      Indication LEDs                   Green= Power
Features                                                                                                Green= CH1 Output Active
                                                                                                        Green= CH2 Output Active
Category 4/3 per EN 954-1                                                                             Green=CHT1 Timed Output Act.
Stop category 0 and 1                                                                                 Green=CHT2 Timed Output Act.
Light curtain, E-Stop, Safety Gate inputs
2 immediate safety outputs                                          Impulse Withstand Voltage         2500V
Delayed outputs: 3 safety or 2 safety and 1 aux.
Cross fault monitoring                                              Pollution Degree                  2
Monitored or automatic reset
Removable terminals                                                 Operating Temperature             -5C to +55C (+23F to 131F)

                                                                      Enclosure Protection              IP40 (NEMA 1)

                                                                      Terminal Protection               IP20

                                                                      Conductor Size                    0.24mm2 (2412 AWG)

                                                                      Torque Settings--term. screws 0.40.5 Nm (3.544.43lbin)

                                                                      Case Material                     Polyamide PA 6.6

                                                                      Mounting                          35mm DIN rail

                                                                      Weight 24V DC                     350g (0.77lbs)
                                                                       110V AC or 230V AC               490g (1.08 lbs)

                                                                      Electrical Life (w/Surge Supp.)   100,000 operations
                                                                          250V AC/6A/1500VA cos=1       500,000 operations
                                                                         250V AC/2.5A/625VA cos=1       300,000 operations
                                                                                                        100,000 operations
                                                                      250V AC/1.5A/375VA cos=0.35       1,000,000 operations
                                                                        250V AC/5A/1250VA cos=0.6       2,000,000 operations
                                                                                         24V DC/2A/48W

                                                                                    10V DC/0.01A/0.1W

                                                                      Mechanical Life                   2,000,000 cycles

                                                                      Vibration                         10-55Hz, 0.35mm

                                                                      Shock                             10g, 16ms, 100 shocks

                                                                       See Output Ratings on page 1-29 for details. Consult factory for ratings not
                                                                          shown.

4-48
                                                                                                                              Safety Relays

                                                Monitoring Safety Relays with Delayed Outputs

                                                                                                                 Minotaur MSR138DP

Product Selection

       Inputs           Safety Outputs          Safety Delayed                                                          Time Delay             Power Supply                       Catalogue Number
                                                    Outputs                                                               1.0s fixed              115V AC                             440R-M23080
                                                                                                                          0.15 3s                                                   440R-M23143
                                                                                               3 N.O.                                            24V AC/DC                            440R-M23141
                                                                                            (MSR138DP)                    0.5 10s               115V AC                             440R-M23140
                                                                                                                                                  230V AC                             440R-M23147
1 N.C. or 2 N.C. or      2 N.O.                                                                                              1.5 30s                                                440R-M23145
    Light Curtain                                                                                                            0.15 3s           24V AC/DC                            440R-M23144
                                                                                                                             0.5 10s            115V AC                             440R-M23151
                                                    2 N.O.                                                                   1.5 30s            230V AC                             440R-M23149
                                                    1 N.C.                                                                                                                            440R-M23148
                                                (MSR138.1DP)                                                                                     24V AC/DC                            440R-M23084
                                                                                                                                                  115V AC                             440R-M23082
                                                                                                                                                  230V AC                             440R-M23081
                                                                                                                                                                                      440R-M23088
                                                                                                                                                 24V AC/DC                            440R-M23086
                                                                                                                                                  115V AC                             440R-M23085
                                                                                                                                                  230V AC                             440R-M23092
                                                                                                                                                                                      440R-M23090
                                                                                                                                                 24V AC/DC                            440R-M23089
                                                                                                                                                  115V AC
                                                                                                                                                  230V AC

                                                                                                                                                 24V AC/DC
                                                                                                                                                  115V AC
                                                                                                                                                  230V AC

Dimensions--mm (inches)                                                                     Block Diagram

        99 (3.89)              45 (1.77)        A1(+) A2(-) S11 (+) X1 X2 X3 X4 S12                                     S52   13 23 37 47 57 A1(+) A2(-) S11 (+) X1 X2 X3 X4 S12              S52        13 23 37 47 55

                                                Overvoltage                                 Start Logic       Logic                            Overvoltage        Start Logic                    Logic
                                                 protection                                                Channel 2                            protection                                    Channel 2

                                                AC                                                              Logic         CH1       CH T1  AC                                     Logic              CH1                    CH T1
                                                     24VDC                                                   Channel 1                  CH T2       24VDC                          Channel 1                                    CH T2
                                                                                                                        CHT2                                                                  CHT2
                                                          PWR                                            CH1 CHT1 CH2                                     PWR                  CH1 CHT1 CH2

114.5                                                                                                    CH1 CHT1 CH2 CHT2 CH2                                                 CH1 CHT1 CH2 CHT2 CH2
(4.5)                                                                                                     Time Reset                                                            Time Reset

                                                S21/PE S33 S34 Y1 Y2 Y39 Y40 S22                                              14 24 38 48 58   S21/PE S33 S34 Y1 Y2 Y39 Y40 S22                          14 24 38 48 56

                                                                                                         MSR138DP                                                 MSR138.1DP

                                                In applications with 24V DC supply: terminal S21 must not be connected to PE.

Typical Wiring Diagrams

+24V DC                                                                                                                       L1

                        Reset                                                                                                           Light Curtain    +        Reset
                                                                                                                                        Out2 Out 1
E-Stop                                                                                                                                                 24VDC
                                                                                            L1 L2 L3                                                           -

                                                                                                                                                                                                                                L1 L2 L3

A1 S52 S11 S12 S21 S22  S33 S34 13 23 37 47 57                                                                                          A1 S52 S11 S12 S21 S22    S33 S34 13 23 37 47 55

                                                                                        K1                                                                                                                                  K1

       MSR138DP                                                                                                                         MSR138.1DP

                                                                                       K2                                                                                                                                   K2

A2 X1 X2 X3 X4 Y39 Y40 Y2 Y1 14 24 38 48 58                                                                                             A2 X1 X2 X3 X4 Y39 Y40 Y2 Y1 14 24 38 48 56

                                                         M                                                                                                                     K1 K2 D1 D2 Indicator                            M

                               K1 K2 D1 D2 Indicator                                                                          N                                                D1, D2 = Delayed Output Load
                                        D1, D2 = Delayed Output Load
Ground          Timer
               Override

          24V DC Supply Dual Channel E-Stop,                                                                                            115/230V AC Supply, 24V DC Light Curtain,
       Monitored Manual Reset, Monitored Output                                                                                         Monitored Manual Reset, Monitored Output

                                                                                                                                                                                                                                4-49
This datasheet has been downloaded from:
             www.EEworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company

MSR138DP器件购买:

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2017 EEWORLD.com.cn, Inc. All rights reserved