Voltage Transducer LV 25-P                                                                                 IPN = 10 mA
                                                                                                           V = 10 .. 500 V
For the electronic measurement of voltages : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high voltage)                                          PN
and the secondary circuit (electronic circuit).

         Electrical data

I  PN    Primary nominal r.m.s. current                                    10                          mA  Features

IP       Primary current, measuring range                                  0 .. 14                   mA  Closed loop (compensated) voltage
                                                                                                             transducer using the Hall effect
R     M  Measuring resistance                                              R                R
                                                                               M min            M max      Insulated plastic case recognized
                                                                                                             according to UL 94-V0.
                    with 12 V       @ 10 mA                            30               190
                    with 15 V                                  max                                       Principle of use
                                                                           30               100
                                      @ 14 mA max                                                        For voltage measurements, a current
                                      @ 10 mA                            100 350                           proportional to the measured voltage
                                                                                                             must be passed through an external
                                                                 max       100 190                           resistor R 1 which is selected by the
                                                                                                             user and installed in series with the
                                      @ 14 mA max                                                          primary circuit of the transducer.

ISN      Secondary nominal r.m.s. current                                  25                          mA

K N Conversion ratio                                                       2500 : 1000

VC Supply voltage ( 5 %)                                                   12 .. 15                  V

IC       Current consumption                                               10 (@ 15 V)+ IS mA

V     d  R.m.s. voltage for AC isolation test 1), 50 Hz, 1 mn              2.5                         kV

         Accuracy - Dynamic performance data

X G Overall Accuracy @ IPN , TA = 25C @ 12 .. 15 V                      0.9                       %   Advantages

L                                                 @ 15 V ( 5 %)          0.8                       %   Excellent accuracy
                                                                                                           Very good linearity
         Linearity                                                         < 0.2                       %   Low thermal drift
                                                                                                           Low response time
IO       Offset current @ IP = 0, TA = 25C                                 Typ Max                        High bandwidth
                                                                                     0.15 mA             High immunity to external
I  OT    Thermal drift of I   O                       0C .. + 25C
                                                                            0.06 0.25 mA                  interference
                                                      + 25C .. + 70C      0.10 0.35 mA                Low disturbance in common mode.

t  r     Response time 2) @ 90 % of V          P max                       40                          s  Applications

         General data                                                                                      AC variable speed drives and servo
                                                                                                             motor drives
TA       Ambient operating temperature                                     0 .. + 70                   C
                                                                                                           Static converters for DC motor drives
T     S  Ambient storage temperature                                       - 25 .. + 85                C  Battery supplied applications
                                                                                                           Uninterruptible Power Supplies
R P Primary coil resistance @ TA = 70C                                    250                        
                                                                                                             (UPS)
R     S  Secondary coil resistance @ T = 70C                              110                             Power supplies for welding
                                               A
                                                                                                             applications.
m        Mass                                                              22                          g

         Standards 3)                                                      EN 50178

Notes : 1) Between primary and secondary

         2)  R      =  25  k  (L/R  constant,  produced  by           the  resistance  and  inductance
                 1

             of the primary circuit)

         3) A list of corresponding tests is available                                                     981125/14

LEM Components                                                                                             w w w .lem.com
Dimensions LV 25-P (in mm. 1 mm = 0.0394 inch)

Bottom view                                  Right view                                      Top view

                                                                                              swiss
                                                                                              made

                                                                                Standard 00  Year Week
                                                                                or N SP..

                                                               Secondary terminals

                                                               Terminal + : supply voltage + 12 .. 15 V
                                                               Terminal M : measure
                                                               Terminal - : supply voltage - 12 .. 15 V

                                                               Connection

Back view

Mechanical characteristics                                     Remarks

General tolerance                            0.2 mm          IS is positive when VP is applied on terminal +HT.
Fastening & connection of primary           2 pins            This is a standard model. For different versions (supply
                                             0.635 x 0.635 mm
Fastening & connection of secondary         3 pins  1 mm        voltages, turns ratios, unidirectional measurements...),
Recommended PCB hole                        1.2 mm              please contact us.

Instructions for use of the voltage transducer model LV 25-P

Primary resistor R 1 : the transducer's optimum accuracy is obtained at the nominal primary current. As far as possible, R 1 should be
calculated so that the nominal voltage to be measured corresponds to a primary current of 10 mA.

Example: Voltage to be measured VPN = 250 V  a) R 1 = 25 k / 2.5 W, IP = 10 mA  Accuracy = 0.8 % of VPN (@ TA = + 25C)
                                             b) R 1 = 50 k / 1.25 W, IP = 5 mA  Accuracy = 1.6 % of VPN (@ TA = + 25C)

Operating range (recommended) : taking into account the resistance of the primary windings (which must remain low compared to R 1, in order
to keep thermal deviation as low as possible) and the isolation, this transducer is suitable for measuring nominal voltages from 10 to 500 V.

LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
This datasheet has been downloaded from:
             www.EEworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company

LV25-P器件购买:

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2017 EEWORLD.com.cn, Inc. All rights reserved