器件描述

lan/电信/电缆测试 AC loop impedance tester

参数
制造商: Megger
RoHS: 不可用
电流额定值: 15 mA
显示器类型: 3 digit LCD
频率: 60 Hz
测量元件: Loop Resistances
电阻: 200 Ohms
安全额定值: IEC 1010-1 (1992), EN 61010 (1993) at 230 V

LT7器件文档内容

                                                                                  LT7
                                                              Digital Loop Testers

LT7
Digital Loop Testers

                                                              s Tests Phase-Earth and Phase-Neutral
                                                                 supply loops

                                                              s Low current loop test does not trip RCDs

                                                              s Direct readout of Prospective Short Circuit
                                                                 Current and Prospective Earth Fault
                                                                 Current

                                                              s Makes measurements on supplies from
                                                                 50 V to 263 V

DESCRIPTION                                                   The LT7 Digital Loop Tester is powered by four internal
                                                              dry cells although the test current uses the mains supply
The Megger LT7 Digital Loop Tester is a small hand held      voltage. It is therefore able to make measurements of
instrument designed to accurately, reliably and easily        phase-earth loop resistance via a standard mains plug, or
measure loop resistances and prospective fault currents at    of phase-earth or phase-neutral loop resistance using the
socket outlets, distribution boards and light sockets. The    two wire lead set. The two wire set may also be used to
LT7 may also be used for testing earth bonding.               test bonded metalwork.

Two loop tests are available; the traditional high current    APPLICATIONS
test for circuits protected by fuses, and a low current test
for taking measurements on circuits which are protected       The tests carried out by the LT7 Digital Loop Tester
by residual current devices (RCDs).                           comply with International requirements for the testing of
                                                              fixed wiring installations in industrial, commercial and
Measurements of phase-earth loop resistance and               domestic premises.
prospective earth fault current (PEFC) are made at socket
outlets using the standard lead supplied. The included two    The resistance of the phase-neutral loop is needed to
wire lead set allows these measurements, also phase-          ensure that adequate over-current protection has been
neutral loop resistance and prospective short circuit         provided in the case of a short circuit developing between
current (PSCC), to be taken at locations such as              the two live conductors.
distribution boards or lighting fittings where there is no
socket outlet available.                                      The phase-earth loop resistance is also needed to ensure
                                                              adequate over-current protection, but also to ensure that,
For all prospective fault current measurements simply         in the case of an earth fault, an adequately large current
select the dedicated switch position. The nominal 23A test    will flow to activate any protective devices. These may be
current is applied and the results are displayed directly on  in the form of fuses or residual current devices.
the liquid crystal display.
                                                              Generally, circuits protected by fuses need to have very
Two liquid crystal "neons" monitor the voltage between        low loop resistances. A 0-20  range is provided, with a
phase and earth and between neutral and earth, and will       resolution of 0.01 , to test these circuits. Tests on this
"light up" if a voltage is detected. The LT7 will check that  range are carried out with a nominal 23 A test current.
the mains supply voltage is within limits and will inhibit
testing if the earth contact voltage would rise above 50 V
if the test were continued.
                                                                                                                               LT7
                                                                                                           Digital Loop Testers

Circuits protected by residual current devices may be of       SPECIFICATION
much higher resistance. Since RCDs and low current rated
MCBs are sensitive to a high test current, the LT7 is          Measurement Ranges                0,01 - 19,9
provided with a 15 mA test range which measures to                          20                   0,1 - 1,99 k
2000 .                                                                      200 / 2k             0,01 - 0,99 kA
                                                                                                 1,0 - 19,9 kA
At these levels the 0.01  resolution is not necessary for                   PSCC
safety and so the resolution is limited to 0.1 .
                                                               Accuracy
Residual current devices with ratings of 30 mA or greater
should not trip when using this range.                         Voltage
                                                               2% 2 digits (when the L-PE neon illuminates.)
FEATURES AND BENEFITS                                          20 Range
                                                               2% 3 digits (on 230V supply)
s Low current loop test means that circuits protected by       5% 6 digits (on 110V supply)
  RCDs may be tested without tripping the rcd.                 200/2k
                                                               2% 3 digits (on 230V supply)
s Tests phase-earth and phase-neutral supply loops on          5% 6 digits (on 110V supply)
  230 V and 110 V supplies.                                    PSCC
                                                               Calculated from 20 range.
s Ensures that adequately low loop resistances are present
  to operate protective devices                                Note: The calibration of the instrument includes the test leads
                                                               and plug as supplied.
s Direct readout of prospective short circuit current
  (PSCC) and of prospective earth fault current (PEFC).        Operational Supply

s No tedious calculations to determine the required rating     50 V - 263 V  50/60Hz
  of overcurrent devices.
                                                               Battery Supply
s The instrument carries the CE mark to show compliance        4 x 1,5 V Alkaline cells type IEC LR6, or
  with both the Low Voltage and EMC Directives
                                                               4 x 1,2 V NiCd or NiMH rechargeable cells.
s The instruments are designed to meet the requirements
  of IEC 1010-1, Installation Category III for Phase to Earth
  Voltages up to 300 V. Expensive fused test leads are not
  required.

s "Neon" indication of supply voltages.
s Fuse and thermal protection.

                                                               Battery Life
                                                               Typically 1200 one minute tests.

                                                               Auto shut off
                                                               After 5 minutes of instrument inactivity.

                                                               Low Battery Indicator
                                                               A display indicator illuminates when alkaline battery cells are
                                                               almost exhausted.

                                                               Display
                                                               3 digit L.C.D. with low battery and excessive noise indication.

                                                               Thermal Protection
                                                               A thermal cut out will operate to inhibit testing if the instrument
                                                               becomes over heated through repetitive testing.

                                                               Fuses
                                                               Internal 10 A (F) 440 V 10 kA 32 mm ceramic HBC.

                                                               Test leads terminated with a 3 pin BS1363/A plug should have a
                                                               10 A fuse to BS1362 fitted in the plug.
                                                                                                                                 LT7
                                                                                                             Digital Loop Testers

Safety
The instrument meets the requirements for double insulation to
IEC 1010-1 (1992), EN61010 (1993) at 230 V Installation Category
III. Installation Category III relates to the transient overvoltages
likely to be found in fixed installation wiring.

EMC
In accordance with IEC61326 including Amendment No.1.

Environmental Protection
IP40

Temperature Range
Operating:
-5C to 40C
Storage:
-25C to 65C

Humidity Range
Operating:
0 - 90% RH non condensing
Storage:
0 - 95% RH non condensing at 40C

Weight
1200 gm (including leads, case & battery)
(2,6 lb approx.)

Dimensions
220 x 92 x 55 mm.
(8,6 x 3,6 x 2 ins. approx.)

                                        ORDERING INFORMATION

Item (Qty)                              Order No.                     Item (Qty)                             Order No.
UK Digital Loop Tester                             LT7                Optional Accessories                      6231-586
Continental Digital Loop Tester                                       Earth Bond Lead Set                       6231-593
Included Accessories                      LT7/EURO                    Option for LT7/Euro
User Guide                                                            Power Cord Test Lead with CEE7/7 Plug     6231-601
2-Wire Lead Set                            6172-087                   Option for LT7
Test & Carry Case                          6231-591                   Power Cord Test Lead with 3 pin plug
Power Cord Test Lead with 3 pin plug       6420-092                   to BS1363/A
to BS1363/A (with LT7)
Power Cord Test Lead with CEE 7/7 plug     6231-601
(with LT7/Euro)
                                        6231-593

UK                     UNITED STATES                                  OTHER TECHNICAL SALES OFFICES    Registered to ISO 9001:2000 Reg no. Q 09290
Archcliffe Road Dover  4271 Bronze Way                                Norristown USA, Toronto CANADA,  Registered to ISO 14001 Reg no. EMS 61597
CT17 9EN England       Dallas TX 75237-1088 USA                       Mumbai INDIA, Trappes FRANCE,    LT7_DS_en_V10
T +44 (0) 1304 502101  T 800 723 2861 (USA only)                      Sydney AUSTRALIA, Madrid SPAIN
F +44 (0) 1304 207342  T +1 214 333 3201                              and the Kingdom of BAHRAIN.      www.megger.com
                       F +1 214 331 7399                                                               Megger is a registered trademark
This datasheet has been downloaded from:
            datasheet.eeworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2020 EEWORLD.com.cn, Inc. All rights reserved