Cable Limiters

600 Volts AC

                                                                  SPECIFICATIONS
                                                                  Voltage Rating: 600 volts AC
                                                                  Interrupting Rating: 200,000 Amperes
                                                                  Cable Size Range: 4/0 750MCM Copper or Aluminum
                                                                  Minimum Operating Temperature: 80C

                                                                  ORDERING INFORMATION

                                                                        LFCL - 500 - C - 1

                                                                     Littelfuse
                                                                         Cable Limiter
                                                                                          Conductor Size
                                                                                                     Terminal Material
                                                                                                        (Aluminum or Copper)
                                                                                                                   Type of Termination

                                                                     DESCRIPTION               CATALOG NUMBER

                                                                  Type Termination Cable Size  Cable Type

                                                                                               COPPER ALUMINUM

Cable limiters are fusible devices that provide very fast                4/0                   LFCL4/0C1 LFCL4/0A1
short-circuit protection, primarily to faulted cables, but also
to other conductors such as busway. Cable limiters do not                250MCM LFCL250C1 LFCL250A1
have an ampere rating, and cannot be used to provide over-
load protection. Cable limiters are selected by cable size;       1      350MCM LFCL350C1 LFCL350A1
for example, a 500 kcmil cable requires a 500 kcmil cable
limiter. Their main use is to isolate faulted cables in circuits     Cable to 500MCM LFCL500C1 LFCL500A1
containing three or more parallel conductors per phase.
They may be installed on the line side of the main service           Cable 750MCM LFCL750C1 LFCL750A1
to provide short-circuit protection to the service conductors.
This is especially important when service conductors are                 4/0                   LFCL4/0C3 LFCL4/0A3
tapped from large low-voltage networks or from large low
impedance transformers.                                                  250MCM LFCL250C3 LFCL250A3

Cable limiters have terminals which permit them to be             3      350MCM LFCL350C3 LFCL350A3
installed in a variety of equipment. The most common
configuration is the offset blade on one end and the crimp           Cable to 500MCM LFCL500C3 LFCL500A3
terminal on the other end. This permits the limiter to replace
a cable terminal (lug).                                              Offset Bus 750MCM LFCL750C3 LFCL750A3

APPLICATIONS                                                             4/0                   LFCL4/0C5

Service entrance conductors                                              250MCM LFCL250C5

Between transformer or network bus and busway                     5 Straight Bus 350MCM LFCL350C5
terminal boxes
                                                                     to  500MCM LFCL500C5
Large feeders with three or more conductors per phase
                                                                     Offset Bus 750MCM LFCL750C5
FEATURES
                                                                         4/0                   LFCL4/0C6 LFCL4/0A6
I Current-limiting characteristics provide protection to
   conductor insulation and reduce damage when faults occur.             250MCM LFCL250C6 LFCL250A6

I Properly applied cable limiters may permit the use of           6      350MCM LFCL350C6 LFCL350A6
   equipment with reduced withstand ratings
                                                                     Mole to 500MCM LFCL500C6 LFCL500A6
I Wide variety of terminations and cable ratings permit use
   in almost every situation.                                        Cable 750MCM LFCL750C6 LFCL750A6

                                                                         4/0                   LFCL4/0C8

                                                                         250MCM LFCL250C8

                                                                  8      350MCM LFCL350C8

                                                                     Mole to 500MCM LFCL500C8

                                                                     Offset Bus 750MCM LFCL750C8

106
This datasheet has been downloaded from:
             www.EEworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2017 EEWORLD.com.cn, Inc. All rights reserved