Digital Heater Element Burnout Detector

K8AC-H

A high-precision Heater Element

Burnout Detector compatible with a

wide-range of heater control methods.

• Push-in terminals reduce the workload. *1

• Scaling *1

• NPN or PNP equivalent output. *1

• Lineup includes models compatible with many heater control methods,

including ON/OFF control, phase control, and cyclic control.

• High-precision heater burnout alarm with digital measurement.

• Contributes to preventative maintenance.

• If the gate function is disabled, the gate input can be used as an

undercurrent/overcurrent relay or for motor or lamp loads.

• Undercurrent detection values can be set separately for CT1 and

CT2.      *2

• CE marking and cUL certified (K8AC-H2@@@).

*1. K8AC-H2@@@ Series only.
*2. The overvoltage detection value is the same for the CT1 and CT2. Also, there
is one undercurrent output.                                                       Wide Current Input Range: 0.200 to 200.0 A AC.

Note: 1.  Consult with your OMRON representative before using the K8AC with

          phase control or cyclic control under the following conditions.         For the most recent information on models that have been certified for

          • Using multiple heaters with different heater capacities               safety standards, refer to your OMRON website.

          • Using heaters with varying heater resistance (e.g., halogen heaters)

2.        The K8AC-H is designed to monitor for element burnouts on heaters

          controlled with power regulators that used a three-alarm method.

          Normal monitoring is not possible for circuits that use a power regulator with a six-alarm method.

Features

High-precision Heater Burnout Alarms with                                         Push-in Terminals for Reduced Wiring Work

High-resolution Digital Measurement                                               (K8AC-H2@@@ Series Only)

Burnout Alarm Possible for One of Multiple                                        Push-in terminals have no screws to come loose, which eliminates

Heater Elements                                                                   the need to control screw tightening torque and retighten screws and

                                                                                  helps to reduce your workload.

Heater burnout is detected by digitally processing minor current

fluctuations.

               RST                  E5@@

                                    Digital

                                    Temperature

                    G3PE            Controller

                    Three-phase

                    SSR                                                           Easily connect terminals using ferrules with insulation sleeves.

                                                                                  Easy Scaling Using the External CT Ratio

                                                                                  and Number of CT Passes

                                                                                  (K8AC-H2@@@ Series Only)

                              Current Transformer                                 Easily set the scaling just by inputting (1) the CT ratio and (2) the

                                    K8AC-H@                                       number of CT passes.

                                    Digital Heater                                External

                                    Element Burnout                               CT

                                    Detector

                    Electric                                                      @A/1A

                    oven                                                          (1) CT ratio                    K8AC-CT@

Three-phase                                                                                                       Current Transformer

delta-connected heater

                                                                                                                  (2) Number of CT passes

                                                                                  Heater

                                                                                                                                                          1
   K8AC-H

   Compatible with Various Heater Control                                                           The transistor output from the K8AC-H2@@N

   Methods                                                                                          can be used as either an NPN open-collector

   Models with heater burnout alarms for ON/OFF control, phase                                      output or a PNP equivalent output.

   control, and cyclic control have been added to the lineup.                                       The transistor output of the K8AC-H2@@N uses a photocoupler for

   Check the current input range, connected CT, and relay output type                               isolation with the internal circuits, and so either an NPN open-

   before selecting the model from the product specifications.                                      collector output or a PNP equivalent output can be used.

   Note: Both single-phase and three-phase heaters are supported.

                                                                                                    NPN Output               PNP Equivalent Output

   Overcurrent and SSR Failure Detection from

   Heater Layer Short Circuits.

   •  Overcurrent can be detected from layer short circuits in addition to

      providing heater burnout alarms with overcurrent detection

      settings.                                                                                                        Load  Load

   •  SSR short circuit failures and SSR open circuit failures are

      detected by monitoring the heater current and the control outputs                             Load power supply        Load power supply

      from the temperature controller.

   •  Detecting SSR failures enables promptly discovering that                                      Preventive Maintenance

      temperature control has failed.                                                               The run time can be measured by the K8AC-H.

   Heater Burnout Alarms for Cyclic Control or                                                      Managing the run time history until burnouts occur is useful for

   Phase Control Heaters                                                                            diagnosis and preventative maintenance for equipment.

   (K8AC-H@@P@)                                                                                     Count the Total Number of Alarms Output

   The burnout detection value is shifted according to the                                          Set the upper and lower limits to count the total number of alarms that

   control output value from the temperature controller.                                            have been output.

   • Analog control is performed on the output power according to the

      temperature controller's current output (4 to 20 mA) when phase

      control or cyclic control is used.

   • Heater burnout alarms are stable with the K8AC-H because the

      heater burnout alarm values are linked with the control output

      value from the temperature controller.

      Heater current  Heater current

                                                      Heater Burnout Alarm Value

                                                      The heater burnout alarm value shifts

                                                      according to the control input (4 to

                                      Heater burnout  20 mA) from the temperature controller.

                                      alarm value

                      4 mA  7 mA                      20 mA

                      Control output from temperature controller

   Compatible with Gradient Settings of Power Controllers

   When using gradient settings with a power controller, set a gate

   current level that is suitable for the gradient settings.

                      Output current

                      100%                  Measurement range               Gradient setting: 100%

                                                                            Gradient setting: 50%

                            0%                                              Control signal

                                      4 mA            14 mA                 20 mA

                                      Not detected                Detected

                                                                  Operation gate current level

   Note: Set the heater burnout alarm value based on the current at the

                      heater's rated input.

2
                                                                                                                                                     K8AC-H

Model Number Structure

Model Number Legend

K8AC-H@@@@ -FLK                          100-240VAC

        1  2        3   4   5  6                     7

1.  Basic Model                                                                        5.  Output Type

    K8AC-H: Digital Heater Element Burnout           Detector                              C: Contact output (one SPDT relay contact output)

2.  Product Type                                                                           T: Transistor output (two NPN open collector outputs) *1

    1: Screw terminals                                                                     N: Transistor outputs (Two outputs: either NPN open-collector

    2: Push-in terminals (Power Input: Screw         Terminals.)                           output or PNP equivalent output can be used.) *2

3.  Current Input Range                                                                    *1. K8AC-H1@@T only.
                                                                                           *2. K8AC-H2@@N only.
    1: 0.200 to 2.200 A                                                                6.  Communications Specifications

    2: 2.00 to 22.00 A                                                                     FLK: RS-485

    3: 20.0 to 200.0 A                                                                 7.  Power Supply Voltage

4.  Heater Control Type                                                                    100-240VAC: 100 to 240 VAC

    C:ON/OFF control (SSR or contactor)

    P: Phase control or cyclic control

Ordering Information

Digital Heater Element Burnout Detectors

Models with Push-in Terminals (Power Input: Screw Terminals)

Power                          Input                               Com-                                 Current input range

supply     Heater control      specifica-   Output specifi-    munica-

voltage             method     tions             cations           tions  0.200 to 2.200 A          2.00 to 22.00 A                    20.0 to 200.0 A

                                                               output

           ON/OFF control      Two          One relay output              K8AC-H21CC-FLK           K8AC-H22CC-FLK          K8AC-H23CC-FLK

           SSR control         current      Two transistor

                               inputs       outputs                       K8AC-H21CN-FLK           K8AC-H22CN-FLK          K8AC-H23CN-FLK

100 to                         (for either                     RS-485

240 VAC                        single-      One relay output              K8AC-H21PC-FLK           K8AC-H22PC-FLK          K8AC-H23PC-FLK

           Phase control       phase or     Two transistor

           Cyclic control      three-       outputs                       K8AC-H21PN-FLK           K8AC-H22PN-FLK          K8AC-H23PN-FLK

                               phase)

                                                                                                                           K8AC-CT200 or                 Current

                    Applicable Current Transformer                        K8AC-CT20S or K8AC-CT20L                         K8AC-CT200L               Transformers

                                                                                                                                              (sold separately)

Note: Consult with an OMRON representative if multiple heaters with different capacities are to be connected in parallel or if the heater resistance

        will vary.

Models with Screw Terminals                 Production To Be Discontinued at the End of March 2009

Power                          Input                               Com-                                 Current input range

supply     Heater control      specifica-   Output specifi-    munica-

voltage             method     tions             cations           tions  0.200 to 2.200 A          2.00 to 22.00 A                    20.0 to 200.0 A

                                                               output

           ON/OFF control      Two          One relay output              K8AC-H11CC-FLK           K8AC-H12CC-FLK          K8AC-H13CC-FLK

           SSR control         current      Two transistor

                               inputs       outputs                       K8AC-H11CT-FLK           K8AC-H12CT-FLK          K8AC-H13CT-FLK

100 to                         (for either                     RS-485

240 VAC                        single-      One relay output              K8AC-H11PC-FLK           K8AC-H12PC-FLK          K8AC-H13PC-FLK

           Phase control       phase or     Two transistor

           Cyclic control      three-       outputs                       K8AC-H11PT-FLK           K8AC-H12PT-FLK          K8AC-H13PT-FLK

                               phase)

                                                                                                                           K8AC-CT200 or                 Current

                    Applicable Current Transformer                        K8AC-CT20S or K8AC-CT20L                         K8AC-CT200L               Transformers

                                                                                                                                              (sold separately)

Note: Consult with an OMRON representative if multiple heaters with different capacities are to be connected in parallel or if the heater resistance

        will vary.

Optional Products (Sold Separately)

Current Transformers

Through-hole diameter          Rated current                Installation method             Model

           5.8-mm dia.                               Surface-mounted with screws       K8AC-CT20S

                               0.200 to 22.00 A      Rear-surface mounted with screws  K8AC-CT20L

           12-mm dia.                                Binding band

                               20.0 to 200.0 A       Rear-surface mounted with screws  K8AC-CT200

                                                     Binding band

           30-mm dia.          20.0 to 200.0 A       Surface-mounted with screws       K8AC-CT200L

Note: When selecting a Current Transformer, make sure that the rated current of the heater              does  not  exceed  the  rated  upper  limit  or  the  rated

        current of the Current Transformer.

                                                                                                                                                                     3
   K8AC-H

   Specifications

   Ratings

                   Heater control method   Models for ON/OFF control (e.g., SSRs or contactors)                    Models for phase control and cyclic control

   Item                            Model                       K8AC-H@@C@-FLK                                                    K8AC-H@@P@-FLK

   Power supply voltage                    100 to 240 VAC (50/60 Hz) *2

   Operating voltage range                 85% to 110% min. of the rated power supply voltage (85 to 264 V)

   Power consumption                       35 VA max.

   (at max. load)

   Applicable circuits                     Single-phase or three-phase (with same model)

                                           ON/OFF control (e.g., temperature controller with relay output)

   Applicable control methods              SSR control (e.g., temperature controller with voltage output)

                                           Cyclic control and phase control (e.g., temperature controller with current output)

                                           Current measurement via two special Current Transformers (Burnout alarm set value can be set separately for each Current

   Input signal and applicable Current     Transformer.)

   Transformer                             Refer to Current Measurement Ranges by Model on page 6 for information on the current measurement range and

                                           applicable Current Transformer.

   Measurement method                      Average value calculation

                   ON/OFF control          Voltage = 12/24 VDC (continuous input possible to 30 VDC)          ---

                                           Input impedance = 4 kΩ min.

                                           ON voltage: 9.6 VDC max., OFF voltage: 1 VDC min.

   Gate input      SSR control             Minimum voltage pulse ON time for burnout detection:               ---

   signal *1                               200 ms min.

                                           Input impedance = 4 kΩ min.

                   Cyclic and phase con-                                                                      4 to 20 mA DC (Burnout detection is possible for an input of

                   trol                    ---                                                                7 mA or greater.)

                                                                                                              Input impedance = 50 Ω max.

                                           One SPDT relay contact output

                   Relay contact outputs:  Same output used for heater burnout, SSR short circuit, SSR open circuit, and heater layer short circuit alarms.

                   K8AC-H@@@C-FLK          0.3 A at 125 VAC (resistive load), 1 A at 30 VDC (resistive load)

                                           Maximum switching capacity: 37.5 VA, 30 W

                                           Mechanical durability: 50 million operations min., electrical durability: 100,000 operations min.

                                           Two transistor outputs (NPN open-collector)

                   Transistor outputs      One ALM output: Outputs heater burnout alarm or heater layer short circuit alarm.

   Outputs         (NPN open-collector):   One SSR error output: Outputs SSR short circuit alarm or SSR open circuit alarm.

                   K8AC-H1@@T-FLK          12 to 24 VDC, 50 mA max.

                                           OFF leakage current: 100 μA max., ON residual voltage: 1.5 V max.

                                           Two transistor outputs: Can be used either NPN open-collector outputs or PNP equivalent outputs.

                   Transistor outputs:     One ALM output: Outputs heater burnout alarm or heater layer short circuit alarm.

                   K8AC-H2@@N-FLK          One SSR error output: Outputs SSR short circuit or SSR open circuit detection.

                                           12 to 24 VDC, 50 mA

                                           OFF leakage current: 100 μA max., ON residual voltage: 1.5 V max.

   Communications                          RS-485  1200, 2400, 4800, 9600, 19200 bps (CompoWay/F)

   Indication method                       7-segment digital display: No. of display digits: 4 (red)

                                           LED status indicators: RUN (green), ADJ (orange), SET (orange), GATE (orange), SSR (orange) and ALM (orange)

                                           Heater burnout alarm, heater layer short circuit alarm, SSR short circuit detection, SSR open circuit detection, voltage

   Main functions                          fluctuation compensation, output ON-delay timer, energy-saving mode, key protection, and power supply voltage

                                           measurement

   Ambient         Operating               −10 to 55°C (with no icing or condensation)

   temperature     Storage                 −25 to 65°C (with no icing or condensation)

   Ambient         Operating               25% to 85% (with no condensation)

   humidity        Storage                 25% to 85% (with no condensation)

   Altitude                                2,000 m max.

   Accessories                             Instruction sheet

   Case material                           PC (Polycarbonate)

   Case color                              N1.5 (clear black)

   Mounting method                         Mounting to a DIN Track

   *1. The gate input enables correct measurement by syncing to heater control.

   When using it with ON/OFF control, receive the relay contact output from the temperature controller or other controller with a 24-VDC auxiliary

   relay and then use this signal as the gate input signal to the K8AC.

   The gate function can also be disabled. If it is disabled, the gate input can be used as a normal undercurrent/overcurrent relay.

   *2. When using the K8AC-H for a 380 to 480-V AC power supply circuit, use a step-down transformer. Contact your OMRON representative for

   information on transformers.

   *3. Order the Current Transformers separately.

4
                                                                                                                                                         K8AC-H

Characteristics

                     Heater control method  Models for ON/OFF control (e.g., SSRs or contactors)          Models for phase control and cycle control

Item                               Model                       K8AC-H@@@C@-FLK                                             K8AC-H@@P@-FLK

Heater current    Input range               K8AC-H@1@@: 0.200 to 2.200 A (Current Transformer: K8AC-CT20S (5.8 dia.), K8AC-CT20L (12 dia.) *1)
                                            K8AC-H@2@@: 2.00 to 22.00 A (Current Transformer: K8AC-CT20S (5.8 dia.), K8AC-CT20L (12 dia.) *1)
input                                       K8AC-H@3@@: 20.0 to 200.0 A (Current Transformer: K8AC-CT200 (12 dia.), K8AC-CT200L (30 dia.) *1)

(at 10 to 30°C)

category II       Measurement accuracy      ±3% rdg ±10 digits max. *2                                    ±6% rdg ±10 digits max. (at control level of 100%) *2

Voltage           Input range               85 to 264 VAC

fluctuation

compensation      Measurement accuracy      ±3% rdg ±10 digits max.

category II

Gate input        Input range               0 to12 VDC or 0 to 24 VDC                                     4 to 20 mA DC

                                            ON: 9.6 VDC max., OFF: 1 VDC min.

Display cycle                               Selectable: Immediate, 0.2 s, 0.5 s, 1.0 s

Output ON-delay time                        0.0 to 99.9 s (operating time)

Soft start time                             0.0 to 99.9 s (used when using the soft start function of a Power Controller)

Output reset method                         Automatic reset

Alarm hysteresis                            1 to 999 digits

Output response time                        500 ms max.                                                   3.5 s max.

                                            20 MΩ min.

                                            Between terminals and case

Insulation resistance                       Between power supply terminals/CT primary terminals and gate input terminals/communications terminals

                                            Between power supply terminals/CT primary terminals and output terminals

                                            Between gate input terminal/communications terminals and output terminals

                                            2,000 V for 1 min

Dielectric strength                         Between terminals and case

                                            Between power supply terminals/CT primary terminals and gate input terminals/communications terminals
                                            Between power supply terminals/CT primary terminals and output terminals

                                            Between gate input terminal/communications terminals and output terminals

Noise immunity                              Power supply terminals normal/common mode: ±1,500 V (startup 1-ns square-wave noise, pulse width: 1 μs/100 ns)

Vibration resistance                        Vibration: 10 to 55 Hz, Acceleration: 50 m/s2 for 5 min with 10 sweeps each in X, Y, and Z directions

Shock resistance                            150 m/s2 (100 m/s2 for relay contacts) 3 times in 6 directions in X, Y, and Z directions

                  Current Transformer       K8AC-H@1@@: 4 A: 30 s, 12 A: 1 s
                                            K8AC-H@2@@: 40 A: 30 s, 120 A: 1 s
                  primary current           K8AC-H@3@@: 400 A: 30 s, 1,200 A: 1 s
Maximum

allowable input   Gate signal: 4 to 20 mA   40 mA DC continuous

                  Voltage pulse gate in-    30 VDC continuous

                  put

Input imped-      Gate signal: 4 to 20 m    50 Ω max.

ance              Voltage pulse gate in-    4 kΩ min.

                  put

Weight                                      Approx. 200 g

Memory protection                           Non-volatile memory (number of writes: 100,000 operations)

Installation environment                    Installation Category 2, Pollution Class 2

Approved standards                          UL61010-1 and CAN/CSA C22.2 No.61010-1

                                            EN 61010-1 (IEC 61010-1)

                                            EMI:                                                          EN61326-1 Industrial electromagnetic environment

                                            Radiated Interference Electromagnetic       Field  Strength:  EN55011 Group 1, class A

                                            Noise Terminal Voltage:                                       EN55011 Group 1, class A

                                            EMS:                                                          EN61326-1 Industrial electromagnetic environment

                                            ESD Immunity:                                                 EN61000-4-2:  4 kV (contact discharge)

                                                                                                                        8 kV (air discharge)

EMC                                         Electromagnetic Immunity:                                     EN61000-4-3:  10 V/m 1 kHz sine wave amplitude modulation

                                                                                                                        (80 MHz to 1 GHz)

                                            Fast Transient Burst Immunity:                                EN61000-4-4:  2 kV (power line)

                                                                                                                        1 kV (I/O signal line)

                                            Surge immunity:                                               EN61000-4-5:  1 kV (line to line, power line)

                                                                                                                        2 kV (line to ground, power line)

                                            Conducted Noise Immunity                                      EN61000-4-6:  3 V (0.15 to 80 MHz)

                                            Voltage Dip/Interrupting Immunity                             EN61000-4-11: 0.5 cycle, 0.180°,100% (rated voltage)

Note: For phase control, the accuracy is the value when the control value of the power regulator is 100% (when the waveform of the heater current

       is a sine wave). “rdg” is the error in the reading of the input current.

*1. The Current Transformers are sold separately.
*2. The values for measurement current apply when the K8AC-H is used in combination with a Current Transformer.

                                                                                                                                                                     5
   K8AC-H

   Current Measurement Ranges by Model                                           I/O Ratings

                                                                                 Relay Contact Output

   Item  Model  K8AC-H@1@@-FLK       K8AC-H@2@@-FLK          K8AC-H@3@@-FLK      Item                  Load            Resistive load (cosφ = 1)

   Current

   measure-     0.200 to 2.200 A AC      2.00 to 22.00 A AC  20.0 to 200.0 A AC  Rated load                     125 VAC, 0.3 A, 30 VDC, 1 A

   ment                                                                          Maximum contact voltage        125 VAC, 60 VDC

   range

         200 A                                               200.0 A             Maximum contact current        1A

                                                                                 Maximum switching capaci-      37.5 VA, 30 W

                                                                                 ty

                                                                                 Minimum applicable load

         100 A                                                                   (failure rate P value, refer-  5 VDC, 10 mA

                                                                                 ence value)

         20 A                            22.00 A                                 Mechanical life expectancy     50,000,000 operations min. (at a switching

                2.200 A                                      20.0 A                                             frequency of 18,000 times/h)

          2A                                                                     Electrical life expectancy

                0.200 A                  2.00 A                                  (Ambient temperature con-      100,000 operations min. (at rated load and

                                                             K8AC-CT200:         dition: 20°C)                  switching frequency of 1,800 times/h)

   Current      K8AC-CT20S: 5.8-mm through-hole diameter     12-mm through-hole

   Trans-                            or                      diameter            Transistor Output

                                                                       or

   former       K8AC-CT20L: 12-mm through-hole diameter      K8AC-CT200L:

                                                             30-mm through-hole  Maximum load voltage           12 to 24 VDC (+10%, −15%)

                                                             diameter

                                                                                 Maximum load current           50 mA

                                                                                 OFF leakage current            100 μA max.

                                                                                 ON residual voltage            1.5 V max.

                                                                                 Communications Specifications

                                                                                 Item        Communications                      RS-485

                                                                                 Transmission method            Two-wire, half-duplex

                                                                                 Synchronization method         Start-stop synchronization

                                                                                 Baud rate                      1,200, 2,400, 4,800, 9,600, or  19,200  bps

                                                                                 Transmission code              ASCII

6
                                                                                                                                                                                         K8AC-H

Connections

Terminal Arrangement

K8AC-H2@@@-FLK                                                                                            K8AC-H1@@@-FLK

         Current inputs                          Gate input                     Communications               Current inputs                          Gate    input                 Communications

                                  K8AC-H2@C@             K8AC-H2@P@                                                                       K8AC-H1@C@         K8AC-H1@P@

   CT1                CT2         Voltage pulse          Linear current                                      CT1               CT2        Voltage pulse      Linear current

                                  12 VDC or              4 to 20 mA DC              RS-485                                                12 VDC or          4 to 20 mA DC               RS-485

                                  24 VDC                                                                                                  24 VDC

                                                                                   A(−)     B(+)                                                                                        A(−)     B(+)

7           8  9           10        11          12         11    12                13      14            7        8        9     10         11     12       11        12                13      14

                           7      8           9      10  11       12     13     14                                                  7     8      9       10  11     12       13      14

                               1                 2          3     4        5    6                                                      1             2       3         4     5       6

Power supply voltage                                              Outputs                                 Power supply voltage                                            Outputs

                                                 K8AC-H2@@N                     K8AC-H2@@C                                                               K8AC-H1@@T                  K8AC-H1@@C

                                                                              COM                                                                    COM                         COM

         1              2                                                       4        5        6          1                 2                         4   5         6             4        5        6

                                     3               4      5         6            125 VAC,                                                              12 to 24 VDC,                  125 VAC,

        100 to 240 VAC               12 to 24 VDC,       12 to 24 VDC,             0.3 A AC                  100 to 240 VAC                              50 mA DC                       0.3 A AC

                                     50 mA DC            50 mA DC                  30 VDC,                                                                                              30 VDC,

                                                                                   1 A DC                                                                                               1 A DC

Terminals                  Name                                                     Description                                   Applicable models

1 to 2         Power supply voltage              Connect to the operating power supply.                               All models                                    Note:        1.  Terminals 4 to 6:

3 to 4,                                                                                                               K8AC-H2@@N                                                     Alarm output

                                                                                                                                                                                     terminals. Depend

5 to 6                                           Outputs SSR open or short circuit detection results.                 (transistor output)                                            on the output type

5 to 4,        Outputs                           Outputs heater burnout or layer short circuit detection results.     K8AC-H1@@T                                                     (relay contact

6 to 4                                                                                                                (NPN open-collector output)                                    output or transistor

                                                                                                                                                                                     output).

5, 6 to 4                                        Outputs an OR of the status of all alarms.                           K8AC-H@@@C (relay output)                                  2.  Terminals 11 and

7 to 8                                           Connect to CT1. Current input from CT1 secondary-side output.                                                                       12: Gate input

               Current inputs                                                                                         All models                                                     terminals. Depend

9 to 10                                          Connect to CT2. Current input from CT2 secondary-side output.                                                                       on the heater

                                                 Connect to gate signal (voltage pulse).                              K8AC-H@@C@                                                     control type (ON-

11 to 12       Gate input                                                                                                                                                            OFF/SSR control

                                                 Connect to a 4 to 20-mA gate signal.                                 K8AC-H@@P@                                                     or cyclic/phase

13 to 14       Communications                    Connect to host device for RS-485 communications.                    All models                                                     control).

Current Input Circuits                                                                                    Output Circuits

CT Inputs (Heater Current)                                                                                Contact Outputs

                                                                                                                                          +12 V                              COM

               7                           −                          A/D                                                                                                 4

                                           +                      conversion

CT1                                                                                                                Relay

               8                                                                                                   drive                                                  5  N.C. contact

                                                                                                                   circuit

               9                           −                          A/D                                                                                                 6  N.O. contact

                                           +                      conversion

CT2                                                                                                       Note: For contact outputs, the same outputs are used for SSR error

               10                                                                                            and for heater burnouts and heater layer short circuit alarm

                                                                                                             outputs.

Transistor Output

K8AC-H2@@N-FLK                                                                                            K8AC-H1@@T-FLK

            Transistor                                   4

               drive                                           SSR alarm output                                                                                     4     COM

            circuit                                      3

            Transistor                                   6     Heater burnout,

               drive                                           heater layer short circuit,                                                                          5     SSR alarm output

            circuit                                      5     overcurrent alarm output                      Transistor

                                                                                                             drive circuit

The transistor output of the K8AC-H2@@N uses a photocoupler                                          for

isolation with the internal circuits, and so either an NPN open-                                             Transistor                                             6     Heater burnout, heater layer short

collector output or a PNP equivalent output can be used.                                                     drive circuit                                                circuit, overcurrent alarm output

               NPN Output                                PNP Equivalent Output

                                     Load                   Load

                        Load power supply                   Load power supply

                                                                                                                                                                                                              7
   K8AC-H

   External Connection Example

   Wiring Method When Using the K8AC-H with SSR Control Heaters

   Power supply                                                                  Operation Description

                                                                                 •  If the heater current detected at either CT1 or CT2 falls below the

                                                   RS-485                           burnout alarm set value, an alarm is output. The burnout alarm set

                                                                                    value can be set separately for CT1 and CT2.

                                                           Transistor Output        No burnout alarm is output, however, when the temperature con-

                        1  2     13  14                    K8AC-H2@@N-FLK           troller control output is OFF.

                                                                              3     Burnouts are detected only while the temperature controller control

                                                3                                   output is being input to the gate input terminals (11 and 12).

                                                                              4     Faulty outputs do not occur because heater burnout detection is

                                                4                                   linked with the temperature controller.

                                                5                                •  The minimum burnout detection time is 200 ms. Shorter burnouts

                                                                                    are not detected.

                                                6                             5  •  Turn ON the voltage fluctuation compensation function (default: OFF)

                                                                              6     to detect power supply voltage fluctuations and automatically compen-

                                                                                    sate the burnout alarm value. Also, turn ON the voltage fluctuation

                        7  8  9  10  11     12                                      compensation function to detect minor current fluctuations.

                                                                                 Correct Usage

                                                        Temperature              •  Always take the power supply voltage from the primary side of the SSR.

        SSR                                             Controller

                                                   (DC voltage output)           •  Use temperature controllers with a 12 or 24-VDC voltage output

                                                                                    (30 VDC max.).

                                                                                 •  CT1 and CT2 are special products. Use the K8AC-CT@@.

   CT1                                                                           •  The CTs do not have polarity.

                   CT2                                                           •  Connect only one CT for single-phase heaters.

                                                                                 •  Connect two CTs for three-phase heaters.

                                                                                 •  For three-phase heaters, always set the burnout alarm set values

                                                                                    for both CT1 and CT2.

        Heater

   Wiring Method When Using the K8AC-H with ON/OFF Control Heaters

   Power supply                                                                  Operation Description

                                                   RS-485                        •  If the heater current detected at either CT1 or CT2 falls below the

                                                                                    burnout alarm set value, an alarm is output. The burnout alarm set

                                                          Transistor Output         value can be set separately for CT1 and CT2.

                        1  2     13  14                   K8AC-H2@@N-FLK            No burnout alarm is output, however, when the temperature con-

                                                                                    troller control output is OFF.

                                                3                             3     Burnouts are detected only while the temperature controller control

                                                                                    output is being input to the gate input terminals (11 and 12).

                                                4                             4     Faulty outputs do not occur because heater burnout detection is

                                                                                    linked with the temperature controller.

                                                5                                •  The minimum burnout detection time is 200 ms. Shorter burnouts

                                                                              5     are not detected.

                                                6                             6  •  Turn ON the voltage fluctuation compensation function (default: OFF)

                                                                                    to detect power supply voltage fluctuations and automatically compen-

                        7  8  9  10  11     12                                      sate the burnout alarm value. Also, turn ON the voltage fluctuation

                                                                                    compensation function to detect minor current fluctuations.

                                                24-VDC                           Correct Usage

                                            power supply   Temperature

        Contactor                        X                 Controller            •  Always take the power supply voltage from the primary side of the SSR.

                                                           (relay output)        •  Use a temperature controller with relay output.

                                                                                 •  The input to the gate input terminals (11 and 12) must be a DC volt-

   CT1                                                                              age input, so wire the 24-VDC power supply as shown in the dia-

                                                                                    gram to the left.

                   CT2                                                           •  CT1 and CT2 are special products. Use K8AC-CT@@.

                                                                                 •  The CTs do not have polarity.

                                                                                 •  Connect only one CT for single-phase heaters.

                                                                                 •  Connect two CTs for three-phase heaters.

        Heater                                                                   •  For three-phase heaters, always set the burnout alarm set values

                                                                                    for both CT1 and CT2.

8
                                                                                                                                                                      K8AC-H

Wiring Method When                  Using     the  K8AC-H with Cyclic Control Heaters

     Power supply                                                                                                   Operation Description

                                                                                     RS-485                         •  If the heater current detected at either CT1 or CT2 falls below the

                                                                                                                       burnout alarm set value, an alarm is output. The burnout alarm set

                                                                                              Transistor Output        value can be set separately for CT1 and CT2.

                                 1  2                13      14                               K8AC-H2@@N-FLK           No burnout alarm is output, however, when the temperature con-

                                                                                                                       troller control output is OFF.

                                                                                  3                              3     Burnouts are detected only while the temperature controller control output

                                                                                                                 4     is being input to the gate input terminals (11 and 12). Burnout is detected

                                                                                  4                                    with no errors because the automatic adjustment of burnout alarm level is

                                                                                                                       linked to the temperature controller control output (4 to 20 mA).

                                                                                  5                                 •  Burnout is detected when control outputs from the temperature con-

                                                                                                                 5     troller are 7 mA min.

                                                                                  6                              6  Correct Usage

                                 7  8         9      10      12               11                                    •  Always take the power supply voltage from the primary side of the SSR.

                                                                                                                    •  Use a temperature controller with a 4 to 20-mA current output.

                                                                                                                    •  When you adjust the set value for the burnout alarm, make sure

SSR         SSR    G32A-EA                                                           Temperature                       that you make the setting with the temperature controller's control
                   Cyclic
                   Control Unit                      4 to 20 mA current output            Controller                   output at a 100% output.

                                                                                                                       The burnout detection value is the detection value at 100% output.

                                                                                                                       Therefore, correct operation will not be possible if the setting is

CT1                                                                                                                    made based on a measurement value when the output is not 100%.

                                                                                                                    •  CT1 and CT2 are special products. Use K8AC-CT@@.

                CT2                                                                                                 •  The CTs do not have polarity.

                                                                                                                    •  Connect only one CT for single-phase heaters.

                                                                                                                    •  Connect two CTs for three-phase heaters.

                   *  Consult with your OMRON representative if multiple heaters are connected                      •  For three-phase heaters, always set the burnout alarm set values

     Heater *         in parallel different heater capacities, or if a heater with varying heater                      for both CT1 and CT2.

                      resistance is used.

Wiring Method         When          Using     the K8AC-H with Phase Control Heaters

Power supply                                                                                                        Operation Description

                                                                                  RS-485                            •  If the heater current detected at either CT1 or CT2 falls below the

                                                                                                                       burnout alarm set value, an alarm is output. The burnout alarm set

                                                                                          Transistor Output            value can be set separately for CT1 and CT2.

                           1     2               13  14                                   K8AC-H2@@N-FLK               No burnout alarm is output, however, when the temperature con-

                                                                                                                       troller control output is OFF.

                                                                              3                              3         Burnouts are detected only while the temperature controller control

                                                                                                             4         output is being input to the gate input terminals (11 and 12).

                                                                              4                                        Burnout is detected with no errors because the automatic adjust-

                                                                                                                       ment of burnout alarm level is linked to the temperature controller

                                                                              5                                        control output (4 to 20 mA).

                                                                                                             5      •  Burnout is detected when control outputs from the temperature con-

                                                                              6                              6         troller are 7 mA min.

                           7     8         9  10         12  11                                                     Correct Usage

                                                                                                                    •  Always take the power supply voltage from the primary side of the

                                                                                                                       contactor.

     Power                                                                        Temperature                       •  Use a temperature controller with a 4 to 20-mA current output.

     Regulator                                     4 to 20 mA current output      Controller                        •  When you adjust the set value for the burnout alarm, make sure

                                                                                                                       that you make the setting with the temperature controller's control

                                                                                                                       output at a 100% output (20 mA).

CT1                                                                                                                    The burnout detection value is the detection value at a 100% out-

                                                                                                                       put. Therefore, correct operation will not be possible if the setting is

                                                                                                                       made based on a measurement value when the output is not 100%.

                CT2                                                                                                 •  Adjust the burnout alarm set value at a 100% output for gradient

                                                                                                                       settings as well.

                                                                                                                    •  If using the soft startup function with a power regulator, set the soft

                   *  Consult with your OMRON representative if multiple heaters are connected                         startup function on the K8AC-H as well, to prevent malfunctions.

     Heater *         in parallel different heater capacities, or if a heater with varying heater                   •  CT1 and CT2 are special products. Use K8AC-CT@@.

                      resistance is used.                                                                           •  The CTs do not have polarity.

                                                                                                                    •  Connect only one CT for single-phase heaters.

                                                                                                                    •  Connect two CTs for three-phase heaters.

                                                                                                                    •  For three-phase heaters, always set the burnout alarm set values

                                                                                                                       for both CT1 and CT2.

                                                                                                                    •  When using the power regulator's gradient settings, change the

                                                                                                                       operation gate current level so that the heater current value is

                                                                                                                       within the measurement range. (The initial value is 7 mA.)

                                                                                                                       For details on operating methods, refer to pages 16 to 18.

                                                                                                                                                                                                    9
K8AC-H

Heater Connection Methods and Current

Depending on the heater connection method, the current when an error occurs will be as shown in the following table. Refer to this table when

determining burnout alarm set values.

                                                  Normal condition                                                   Abnormal condition

                                                  5A                                                                        0A

    Single-phase                         200 V                       1 kW                                            200 V

                                                                     5A                                                           0A

                                                       8.7 A                                      7.5 A                                      5A

                                                200 V  8.7 A         1 kW                         7.5 A                                  8.7 A

                Delta                    200 V                             1 kW

                connection                      200 V

                                                       8.7 A         1 kW                                                                    5A

                                                       (5 A ×  3  )                           (5 A ×     3×    3  )                   (5 A ×        3×    1)

                                                                                                               2                                          3

                                                       2.9 A                                      2.5 A                                      2.5 A

                                                200 V  2.9 A         1kW                          2.5 A                                      2.5 A

    Three-      Star                     200 V                 1 kW

    phase       connection                      200 V

                                                       2.9 A         1 kW

                                                       (5 A ×  1  )                           (5  A×  1  ×     3  )                      (5  A×     1  ×  3   )

                                                               3                                      3        2                                    3     2

                                                       5A                                         2.5 A                                      5A

                                                200 V  8.7 A         1 kW                                                                    5A

                V                        200 V

                connection                      200 V

                                                       5A            1 kW                         2.5 A

                                                  (5 A ×       3 = 8.7 A)                     (5 A ×  1  )                               (5 A × 1)

                                                                                                      2

Note: This is the current for when a 200-V, 1-kW heater is used for single-phase or three-phase operation.

Rate of Change for Currents with Parallel Heaters

The following table shows the current change ratios when multiple heaters of the same capacity are connected in parallel and                                  one   of the heater

elements burns out. Use this table for reference when making corrections.

If five single-phase heaters are connected in parallel, the current change when burnout occurs is 20% per heater.

For example, if the current for a single heater is low and the change ratio is very slight, it may not be detected. Therefore take                            into  account the

detection accuracy for the total current when selecting the number of heaters to be connected in parallel.

                             Connection                                          n=1                     n=2                n=3              n=4                    n=5

    Single-            I                                                   With one heater

    phase                    n heaters                                           burned out,             0.5                0.67             0.75                   0.8

                                                                                 I is 0.

                          I          Number of    Current in burned-       With one heater

                                     heaters per  out phase                      burned out,             0.6                0.75             0.82                   0.86

    Star                             phase = n                                   I is 0.

    connection

                                                  Current in other               0.87                    0.92               0.95             0.96                   0.97

                                                  phases

                          I                       Current in lines

                                                  near burned-out                0.58                    0.77               0.84             0.88                   0.91

                                                  phase (Same as 2-

    Delta                                         phase.)

    connection

                                                  Current in other               1                          1               1                    1                  1

                      Number of heaters           phases

                      per phase = n

Note: 1.       The figures in the above table show the current change ratios when burnout occurs for one heater connected in parallel.

           2.  The numbers represent the current ratio after one heater burns out, with the current prior to the burnout (i.e., the normal current) taken

               as 1.

           3.  In actual operation there may be effects from factors such as load (heater) imbalances, so conduct an actual test for confirmation before

               making adjustments if the current change ratio between normal and abnormal operation is slight.

           4.  Consult with your OMRON representative if multiple heaters are used with different heater capacities.

10
                                                                                                                                                                         K8AC-H

Operation

Main K8AC-H Functions

The K8AC-H is a digital heater burnout detector that detects heater                burnout  by measuring the heater current from various power supply systems.

The K8AC-H provides the following functions.

Applicable Heater Control Methods                                                           Error Detection

The following heater control methods can be used.                                           The following errors are detected according to status.

ON/OFF Control (Contactor/SSR)                                                              Heater Layer Short Circuit Detection (overcurrent

                                                                                            detection).

                                                                                            Layer short circuits can be detected in the heater.

                                                                                            The preset overcurrent detection set value is compared with the

           ON                                                                               heater current and an alarm is output accordingly.

                     OFF

           1 to 99 s

Cyclic Control                                                                              Set value

                                                                                            Current

                ON          OFF

                0.2 to 3.0 s

Phase Control (Applicable to 4 to 20 mA Current-output                                               Alarm

Temperature Controllers)                                                                             Transistor output models: ALM indicator lit, ALM transistor output

                                                                                                     Relay output models: ALM indicator lit, OR of all detection status output

                                                                                            SSR Short Circuit Detection

                                                                                            If current is measured when there is no gate input, an SSR                          short

                      ON                                                                    circuit error is detected and an alarm is output.

                OFF

                Half cycle                                                                  Gate input

Heater Burnout Alarm

The preset burnout detection value is compared     with the                heater

current and an alarm is output accordingly.

                                                                                            Current

Current                                                                                     measurement

Set value

                500 ms                             100 ms                                            Alarm

                                                                                            Transistor output models: SSR indicator lit, SSR transistor output

                                                                                            Relay output models: SSR indicator lit, OR of all detection status output

                                                                                            SSR Open Circuit Detection

Alarm                                                                                       If current is not measured during gate input, an SSR open circuit                   error

                                                                                            is detected and an alarm is output.

Transistor output models: ALM indicator lit, ALM transistor output

Relay output models: ALM indicator lit, OR of all detection status output

                                                                                            Gate input

                                                                                            Current

                                                                                            measurement

                                                                                                     Alarm

                                                                                            Transistor output models: SSR indicator lit, SSR transistor output

                                                                                            Relay output models: SSR indicator lit, OR of all detection status output

                                                                                                                                                                                       11
K8AC-H

Voltage Fluctuation Compensation                                                Using the Power Regulator's Gradient Settings

The voltage fluctuation compensation function automatically adjusts             The power regulator's gradient settings can be used to prevent

the burnout alarm value of the K8AC-H according to voltage                      malfunction by setting the operation gate current level. The

fluctuations in the heater circuit.                                             relationship between the gradient settings and output current

The operating value for burnout detection when multiple heaters are             depends on the power regulator manufacturer and model, so be sure

connected is set very close to the normal value. Thus, a false burnout          to check the characteristics of the power regulator being used before

alarm output will occur if there is a voltage drop in the heater circuit.       setting.

The voltage fluctuation compensation function prevents this type of             Setting Example

false output.                                                                   Initial setting: 7 mA

Example: Voltage Drop from 100 V to 95 V in the Heater Circuit

     Conditions:                                                                          Output current                                              Gradient

     Voltage fluctuation compensation standard value = 100 V                                       100%                                               setting 100%

     Burnout alarm set value = 10.0 A                                                                               Measurement range

     If the power supply voltage drops from 100% to 95%, the

     operating value will also reduced from 100% to 95%.

     Burnout alarm operating value = 10.0 A × 95% = 9.5 A

Gate Input                                                                                         0%                                                 Control signal

The gate input provides a sync signal used to link burnout detection

to the control output of the temperature controller.                                                                4 mA  7 mA                        20 mA

For SSR control, the voltage output pulse from the temperature                                                      Not detected       Detected

controller is input.                                                            When the power regulator's gradient settings are changed, the

For ON/OFF control, 24 VDC linked to a relay contact of the                     operation gate current level is set so that the output current is within

temperature controller is input.                                                the measurement range. (In the following diagram, 14 mA is set.)

For cyclic or phase control, a 4 to 20-mA control signal is input.                        Output current                                              Gradient

If there is no gate input for a Heater Element Burnout Detector, a                                 100%             Measurement range                 setting 100%

heater burnout alarm would be falsely output when the voltage output

pulse from the temperature controller turns OFF, and there would be                                                                                   Gradient

no way to tell whether it was a false output.                                                                                                         setting 50%

Note: The gate input function can be disabled. If it is disabled, Heater

     Element Burnout Detector operation will not be linked to the                                  0%                                                 Control signal

     temperature controller control signal. (The gate input can be

     used as a simple undercurrent relay.)                                                                          4 mA          14 mA               20 mA

Power-saving Operation                                                                                              Not detected            Detected

If there are no key operations performed within a preset time period,           Using Halogen or Other Heaters with Varying

the display automatically turns OFF.                                            Resistance during Phase and Cyclic Control

                                  Power Save Mode                               When phase control is used with halogen heaters or other pure metal

                                  Standby Time                                  heaters, the heater resistance fluctuates according to the control

                                                                                level. As a result, high-precision detection of heater burnout is not

                                                                                possible. The effect on the heater and setting methods depends on

Output Operation Time Charts                                                    the heater being used. Therefore, consult with your OMRON

Heater Burnout and Heater Layer Short Circuit                                   representative before using a heater with varying resistance values.

(Overcurrent) Alarms                                                            Halogen Heater Resistance Fluctuation Example

                                                Alarm hysteresis                In the following example, burnout of one element in a six-element

     Heater layer short circuits                                                heater can be detected at a control level of 20 mA, but detection is not

     Overcurrent set value                                                      possible due to the effect of fluctuating resistance if the control level

               Heater current                                                   is any lower.

     Heater burnout set value                                                   Heater resistance

                                                                                8Ω                                                                              Three elements

                                                                                                                          Detectable range                      burned out

               Alarm output                                                     6Ω

                                  ALM indicator lights.  ALM indicator lights.                                                                                  One element

SSR  Short/Open Circuit Alarm                                                                                                                                   burned out

                                                                                4Ω                 Threshold

     SSR short-circuit

     SSR open-circuit                                                           2Ω                                                                    Normal

                                                                                                                                                      (six elements in parallel)

               Alarm output

                                  SSR indicator lights.  SSR indicator lights.  0Ω                                                                            Control signal

                                                                                                              4 mA  7 mA                              20 mA

12
                                                                                                                                            K8AC-H

Nomenclature

Nomenclature and Operations

K8AC-H2@@@-FLK                             K8AC-H1@@@-FLK                                   Name                                 Operation

                                                                                  Main display             Displays processing values, parameter characters,

                                                                                                           and set values.

                                                                                             RUN (Mea-     Lights when the power is turned ON and the

                                                                                             surement      measurement operation is in progress.

                                Operation                                                    operation)    OFF at all other times.

                                indicators                                                   ADJ           Lights while in Adjust Mode.

                               Main display                                                  (Adjust)      Flashes while in Test Mode.

                               area                                                                        OFF at all other times.

                                                                                             SET (Set)     Lights while in Set Mode.

                                Shift key                                         Oper-                    OFF at all other times.

                                                                                  ation                    Lights or turns OFF according to gate input status.

                                Up key                                            indi-                    Gate pulse:

                                                                                  cators     GATE                Lights for high voltage pulse; OFF for low

                                Mode key                                                     (Gate)              voltage pulse.

                                Down key                                                                   Gate signal (4 to 20 mA):

                                                                                                                 Lights for 4 mA or over; OFF for less than 4 mA.

                                Level key                                                    SSR           Lights when an SSR error occurs (open or short

                                                                                             (SSR error)   circuit).

                                                                                             *             OFF when SSR is normal.

                                                                                             ALM           Lights for heater burnout or overcurrent.

                                                                                             (Alarm) *     OFF at all other times.

                                                                                  Up key                   Increments a set value when the set value is in

                                                                                                           change status.

                                                                                  Down key                 Decrements a set value when the set value is in

                                                                                                           change status.

                                                                                                           Used to check set values while parameters are

                                                                                  Shift key                displayed, and to put set values in change status.

                                                                                                           Used to shift the set value digit when the set value is

                                                                                                           in change status.

                                                                                  Mode key                 Used to switch the displayed parameter.

                                                                                  Level key                Used to change the level.

                                                                                  * Check the specific status using the alarm display parameters on the
                                                                                  main display.

Alarm Indicator                                                                   Processing Value Display Ranges and Functions

                                                                               s

Order                          7-segment     LED                                  Processing           Display        Display    Unit       Function

of        Alarm                 display      indicator      Alarm contents        value name         characters       range

priority                       characters                                                                                              This is the CT1 heater

1         Heater burnout 1      hbt1         ALM            CT1 heater                                                0100 to          current processing value.

                                             indicator lit  burnout detected.     Heater 1             ct  1          2300       A     Alarm operations such as

2         Heater burnout 2                   ALM            CT2 heater            current                             *1               the heater burnout alarm

                                hbt2         indicator lit  burnout detected.                                         *2               are determined based on

                                                            SSR open circuit                                                           this processing value.

                                                            detected (when                                                             This is the CT2 heater

                                                            heater current                                            0100 to          current processing value.

3         SSR open circuit                   SSR            cannot be             Heater 2             ct  2          2300       A     Alarm operations such as

                                ssro         indicator lit  detected with         current                             *1               the heater burnout alarm

                                                            temperature                                               *2               are determined based on

                                                            control gate                                                               this processing value.

                                                            output ON).           *1. The decimal point position depends on the input type.

                                                            SSR short circuit     K8AC-H@1@@: 0.100 to 2.300
                                                                                  K8AC-H@2@@: 1.00 to 23.00
                                                            detected (when        K8AC-H@3@@: 10.0 to 210.0

                                             SSR            heater current is     *2. If the display is below 0100, the bar display “----” will be shown.

4         SSR short circuit     ssrs         indicator lit  detected with

                                                            temperature

                                                            control gate

                                                            output OFF).

5         Heater layer          hrs1         ALM            CT1 overcurrent

          short circuit 1                    indicator lit  detected.

6         Heater layer          hrs2         ALM            CT2 overcurrent

          short circuit 2                    indicator lit  detected.

Note: 1.  As soon as the cause of an alarm is removed, the alarm is

          reset automatically.

    2.    If multiple alarms occur simultaneously, the one with the

          highest priority is displayed.

    3.    If the mode is changed to Adjust or Set Mode while an alarm

          is in effect, the alarm output is reset and the ALM and SSR

          indicators turn OFF.

    4.    If an SSR operation gate current level is set for a model with

          phase control or cycle control, alarms will not be output for

          SSR short circuits.

                                                                                                                                                                    13
K8AC-H

Settings Method

Settings Methods for SSR and ON/OFF Control Heaters

Settings Conditions                                                                        K8AC-H Parameter Setting Procedure

Detecting burnouts in just one heater when ten 300-W rated heaters                             (Only the minimum settings are shown here. Refer to pages 16 to

are connected in parallel to a single-phase 200-V power supply.                                18 for information on how to set parameters.)

The heater is SSR controlled.                                                              1.  Turn ON the power to the K8AC-H. The initial status when power

Normal Heater Current and Heater Current with One                                              is turned ON is called Run Mode.

Heater Element Burnout                                                                     2.  Press the L Key for at least 3 s to change from Run Mode to

    Normal current = (300 W × 10 (heaters))/200 V = 15.0 A                                     Adjust Mode (the mode for adjusting burnout alarm set values.)

    Current with one burnout = (300 W × 9)/200 V = 13.5 A                                  3.  Set the burnout alarm set values. (AL-1 = CT1 burnout alarm set

    Heater burnout alarm set value =                                                           value and AL-2 = CT2 burnout alarm set value.)

                                                                                               Set “14.3” to AL-1.

    (Normal    current  +   current  at  malfunction)        15.0  + 13.5                      Set the AL-2 burnout alarm set value to “----” so that it will not

                               2                          =        2       = 14.3 A            detect heater burnout, because this is a single-phase heater.

                                                                                           4.  Change to Run Mode.

Selecting Heater Element Burnout Detector Models                                               Press the  L Key while in Adjust Mode for at least 1 s to change

For the above example, K8AC-H12C@-FLK would be selected.                                       to Run Mode.

                                                                                           5.  Check operation.

The burnout alarm set value is 14.3 A, so the current input range 2.00                         Test heater burnout detection by burning out one heater.

to 22.00 A should be selected.                                                                 Also check that there are no malfunctions during temperature

SSR control is used, so type C should be selected. (Type C is also                             control.

selected for ON/OFF control.)                                                              Note: The default setting for functions including the voltage

Select the appropriate relay or transistor output specifications,                              fluctuation compensation function, alarm hysteresis, output

depending on the application.                                                                  ON-delay time, and SSR error detection function is OFF. Turn

                                                                                               ON any of these functions as required.

Settings Method for Cyclic and Phase Control Heaters

Settings Conditions                                                                            ON-delay time, and SSR error detection function is OFF. Turn

Detecting burnouts in one heater when five 1,000 W-rated heaters are                           ON any of these functions as required.

connected to each phase of a three-phase delta-connected 200-V                             Burnout Alarm Set Value Setting Method

power supply.                                                                              Setting Method

A power regulator (phase control) performs heater control.                                 • Wire the K8AC-H, temperature controller (4 to 20 mA current

Normal Heater Current and Heater Current With One                                              output type), and power regulator (phase control).

Heater Element Burnout                                                                     • Press the L Key on the K8AC-H for at least 3 s to change from

    Example: When One of Five Single-phase Heaters (R-S) Burns                                 Run Mode to Adjust Mode.

    Out                                                                                    • AL-1 (CT1 burnout alarm set value) will be displayed when the

    Normal current =      3    (1,000 W × 5 (heaters))/200 V = 43.3 A                          mode is changed to Adjust Mode. Press the S key once when AL-

    Current with one burnout = 43.3 A × 0.91 = 39.4 A                                          1 is displayed. Next, press the U Key once. The present heater

    (Refer to Rate of Change for Currents with Parallel Heaters on                             current value will be displayed on the main display, so note this as

    page 10.)                                                                                  the normal current value. Always have the temperature controller

    Heater burnout alarm set value =                                                           output at 20.0 mA at this time (See note 1.)

         Normal  current    +  current   at  malfunction     =  43.3  +  39.4  =  41.4  A  • Next, disconnect one heater and note the heater current in this

                                  2                                   2                        burnout state. Alternatively, use the current when one heater is

                                                                                               burned out (calculated earlier) as the current during malfunction. It

Selecting Heater Element Burnout Detector Models                                               is recommended that the current at an actual burnout is confirmed.

For the above example, K8AC-H13P@-FLK would be selected.                                   • Set the K8AC-H burnout alarm set value based on the results. The

The burnout alarm set value is 41.4 A, so the current input range 20.0                         burnout alarm set value is set at the mid-point between the normal

to 200.0 A should be selected.                                                                 current and the current at malfunction, taking errors and variations

Phase control is used, so type P should be selected. (Type P is also                           in heater capacity into consideration.

selected for cyclic control.)                                                              • In this setting example, the set value for AL-2 (CT2 burnout alarm

Select the appropriate relay or transistor output specifications,                              setting) is the same as the set value for AL-1. (See note 2.)

depending on the application.                                                              Note: 1.  The K8AC-H automatically adjusts burnout alarm levels to

                                                                                                     compensate based on the temperature controller current

K8AC-H Parameter Settings Procedure                                                                  output. The burnout alarm value must be set when the

    (Only the minimum settings are shown here. Refer to pages 16 to                                  temperature controller output is at 100% (20 mA), so be

    18 for information on how to set parameters.)                                                    sure to have the temperature controller at 20 mA output.

1.                                                                                             2.    If the heater capacity is unbalanced, the burnout alarm

    Turn ON the power to the K8AC-H. The initial status when power                                   values for CT1 and CT2 may not be the same.

    is turned ON is called Run Mode.

2.  Press the L Key for at least 3 s to change from Run Mode to

    Adjust Mode (the mode for adjusting burnout alarm set values.)

3.  Change from Adjust Mode to Set Mode (the default settings mode

    for all functions). The password “0169” is required to move to Set

    Mode.

4.  Set the heater control method parameter to PH-3 (three-phase

    control).

    The default setting is PH-1 (single-phase control).

    Note: Set the parameter to CYCL (cyclic control) when using

           cyclic control.

5.  Press the L Key for at least 1 s to change from Set Mode to Adjust

    Mode. Press the L Key again for at least 1 s to change from

    Adjust Mode to Run Mode.

Note: The default setting for functions including the voltage

         fluctuation compensation function, alarm hysteresis, output

14
                                                                                                                                                 K8AC-H

Measurement Monitor Value Display Ranges and Functions

Other than measuring the heater current, the K8AC-H can measure the power supply voltage, maximum/minimum current, maximum/minimum

voltage, and other values. The measurement data can be monitored from a host using RS-485 communications. The measurement monitor value

names, display ranges, and functions are given in the following table.

   Measurement monitor           Display char-  Display range       Unit                                             Function

         value name              acters

                                                                           This is the measurement value of the K8AC-H power supply voltage. When the voltage

Power supply voltage             sce               0085 to 0264     V      fluctuation compensation function is enabled, the heater burnout determination based on

                                                                           this voltage is automatically compensated.

Heater 1 maximum current         max1              0100 to 2300     A

*

Heater 1 minimum current         min1              0100 to 2300     A

*                                                                          These hold the maximum and minimum values for each processing value.

Heater 2 maximum current         max2              0100 to 2300     A      • The maximum and minimum heater currents after the power is turned ON or after a

*                                                                          maximum or minimum reset are displayed.

Heater 2 minimum current                                                   • The values are not saved when power is interrupted.

*                                min2              0100 to 2300     A      • The current values are not refreshed when startup lock is in effect and when the gate

                                                                           input is enabled but the gate input is OFF.

Maximum power supply             maxs              0085 to 0264     V      • Measurement values for power supply voltages are always refreshed.

voltage *

Minimum power supply             mins              0085 to 0264     V

voltage *

                                                                           This value counts the total number of alarms output for heater burnout, SSR open and

                                                                           short circuits, and heater layer shorts.

                                                                           • The count is refreshed each time an alarm is output, and it is saved in non-volatile

Number of alarm outputs          acnt              0000 to 9999  Outputs   memory.

                                                                           • The value is saved when power is interrupted.

                                                                           • The number of outputs is not counted for the test function.

                                                                           • After counting to 9999, the value is held at 9999 and any further alarms are not

                                                                           counted. To return the count to 0, perform a reset.

                                                                           This holds the CT1 or CT2 processing value when a heater burnout alarm is output.

Processing value for alarm       memo              0100 to 2300     A      • This is the most recent processing value, and it is refreshed each time a heater

output                                                                     burnout alarm occurs.

                                                                           • The value is not saved when power is interrupted.

                                                                           This is the total run time value from when power is turned ON or the processing value is

                                                                           reset until an alarm occurs.

                                                                           • The total time is recorded in non-volatile memory approximately once per hour. If

Run time                         otim              0000 to 9999  × 10h     power is interrupted within the hour, however, the data since the beginning of the hour

                                                                           is lost and the total starts over from when the time was last saved.

                                                                           • The total is stopped during heater burnout alarm output. When the alarm is cleared,

                                                                           the total resumes from the time just before the alarm occurred.

Heater 1 input shift display                                               This is the shift value for displaying the CT1 heater current measurement set in

current                          isc1              −999 to 999      digit  measurement parameter CT1.

                                                                           • The value is saved when power is interrupted.

Heater 2 input shift display                                               This is the shift value for displaying the CT2 heater current measurement set in

current                          isc2              −999 to 999      digit  measurement parameter CT2.

                                                                           • The value is saved when power is interrupted.

* Each measurement value can be individually reset. Refer to the K8AC-H Digital Heater Element Burnout Detector User’s Manual (Cat. No. N132)
for operating procedures.

Modes

Groups of setting items are called “modes.” The K8AC-H has five modes.

         Mode                                                              Function                                                              Alarm operation

Run Mode                 This is the normal operating mode, used for receiving inputs, executing heater burnout outputs, etc.                    Executed

                         Operation goes into Run Mode immediately after power is turned ON.

Adjust Mode              This mode is used to change comparatively frequently set parameters, such as alarm value settings.                      Stopped

                         This also the mode for entering the password to move to the Set Mode.

Set Mode                 This mode is used to make the initial settings for the various functions.                                               Stopped

Protection Settings      This mode is used to make settings to prevent unintended key operations. The protected modes are not displayed,         Stopped

Mode                     preventing changes to set values.

Test Mode                This mode is used to simulate inputs with key operations to test alarm outputs.                                         Executed

Gate Mode                This mode sets the gate current value that stops an alarm or detection.                                                 Executed

Note: If more than five minutes elapses with no operations performed in the Protection Settings Mode, Adjust Mode, or Set Mode, the status will

        return automatically to the processing value display. If this occurs while settings are in progress, it may cause unintended operations in the

        processing value display. Be careful not to allow this to happen.

Settings Data Notation

The letters of the alphabet in settings data are displayed as shown below.

a        b   c       d        e  f  g           h  i        j    k     l   m  n      o              p     q  r       s         t  u       V  w   x           y       z

A        B   C       D        E  F  G           H  I        J    K     L   M  N      O              P     Q  R       S         T  U       V  W   X           Y       Z

                                                                                                                                                                        15
K8AC-H

Operating Procedures

Moving between Modes

                                                   Press the D                                   To Gate Mode

                                                   key for at least 1 s.  Gate Mode              When the D key is pressed for at least one second in Run Mode, the

                                                   Power ON               Press the D            mode will be switched to Gate Mode. To return to Run Mode from

                         Press the                                        key for at least 1 s.  Gate Mode, press the D key for at least one second.

                         L and M                                Press the S
                                                                key for at least 1 s.
                         keys.                                                                   To Test Mode

          1234                                     Run Mode                  Test Mode           When the S key is pressed for at least one second in Run Mode, the

                         When the                               Press the S                      mode will be switched to Test Mode. To return to Run Mode from Test
                                                                key for at least 1 s.
                         key is                                                                  Mode, press the S key for at least one second.

    Press the L          released                                            Press the L key

    and M keys for                                  When the key             for at least 1 s.   To Set Mode (Password Input)

    5 s.                                            is released

          Protection                                                                             A special operation is required to move to the Set Mode.

          Settings Mode  Press the    Press the                           1234                   Use the following procedure.

                         L and M      L key for                                                  Procedure

                         keys for at  at least 1s.

                         least 1 s.                             Hold down for at

                                                   Adjust Mode  least another 2 s.                      amoV                        A.  Move to the Adjust Mode and use the M key to

                                                                                                                                        display the parameter for moving to the Set Mode.

                         Press the L key            Password: 0169                                                                      · The parameter characters are "amoV".
                         for         at least 1s.

                                                   Set Mode                                                                0        B.  Press the S key to display the set value

                                                                                                                                        (password).

To Adjust Mode

When the L key is pressed for one second in Run Mode, the 7-                                            0000                        C. Press the S key again to enable changing

segment display will begin to flash. If the key is held down for another                                                                the password.

two seconds, the mode will be switched to Adjust Mode.

To return to Run Mode from Adjust Mode, press the L key for at least                                    0169                        D. Use U, D, and S keys to set the password.

one second.                                                                                                                             The password is 0169.

To Protection Settings Mode                                                                                                         · Press the M key.

When the L and M keys are pressed for one second in Run Mode,                                                                       · If the password is correct, the mode will change to

the 7-segment display will begin to flash. If the keys are held down for                                                            the Set Mode.

                                                                                                                                    · If the password is incorrect, the next parameter will

another five seconds, the mode will be switched to Protection Settings                                                              be displayed while still in Adjust Mode.

Mode. To return to Run Mode from Protection Settings Mode, press                                            amoV                S         0         S   0000         S    0169

L and M keys for at least one second.                                                                       M                       M                                     M

                                                                                                                                                        M

                                                                                                                                                       When password          When password

                                                                                                        Next parameter                                 is incorrect           is correct

                                                                                                        in Adjust Mode                                      Set Mode      init

Setting the Parameter

The value set for each parameter is called the “set value.” Set values                           Procedure

include both numbers and characters.                                                                                                A.  Press the S key while a parameter is displayed to

The status when a set value is displayed is called “monitor status,”                                                                    go into monitor status. The set value for that

and when it can be changed it is called “change status.”                                                                                parameter will be displayed.

Use the following procedure to display and change set values.                                                                       B.  If the set value is not to be changed, press the M

                                                                                                 Note:                                  key while in monitor status to switch to the next

                                                                                                 If a set value is out of               parameter.

                                                                                                 range, either too high or too      C.  Press the S key again while in monitor status to

                                                                                                 low, the maximum or                    enable the changing set value.

                                                                                                 minimum value will                 · The place where the set value can be changed will

                                                                                                 automatically be set. For          begin to flash.

                                                                                                 models with a current input

                                                                                                 of 0.200 to 2.200 A, for           D.  Use the S, U, and D keys to change the set

                                                                                                 example, the maximum                   value.

                                                                                                 value is 2.200 and the             E.  Press the M key to save the changed set value in

                                                                                                 minimum value is 0.200.                internal memory and switch to the next parameter.

                                                                                                                                        · Changed set values will not be saved in memory if

                                                                                                                                        the     mode    is  changed   by  another  key  operation

                                                                                                                                        without first pressing the M key.

                                                                                                                                    M                Monitor status   Change status

                                                                                                                                    al-1        S      2000 S             2000

                                                                                                                                    M                   M                 M   Use the S, U, and

                                                                                                                                                                              D keys to change

                                                                                                                                                                              the set value.

                                                                                                                                To  next parameter

16
                                                                                                                                                                 K8AC-H

Parameter List

The setting items in each mode are called “parameters.”

Parameters can be switched by using the M key.

            Protection Mode          *3                                                Adjust Mode      *3                      Set Mode        *3

                  aspt                                                                 al-1                                     init

                           Setting change protection                                              Burnout alarm                 All initialization

                                                                                                  setting value 1                                             dsmd

                  wtpt                                                                 al-2                                     sini                                  Display mode

                           Setting change protection                                              Burnout alarm                 Set value initialization

                                                                                                  setting value 2                                             dsrf

ON                                                                                     VfcV                         1  s  min.  pini                                    Display

                                                                                                                                                                        refresh time

Powe r                                                                                 Voltage fluctuation                                Processing value

                                                                                       compensation standard value                        initialization      u  no

        5s  min.           1 s min.                                                                 *1                          hys1

                                                                                       amoV                                                                             Unit number

            Run Mode                                                                   Password for                             Alarm hysteresis 1               bps

                                                                             1 s min.  moving to Set

                                             1234                                      Mode: 0169                               hys2

                                                                                                                                                                      Baud rate

                                                       (Processing value                                                        Alarm hysteresis 2               len

                                                       display status)       3 s min.

                                                                                                                                gate                                Data length

                                             ct        1                                                                        Gate input function           sbit

                                                       Heater 1 current                                                         comp

                                                                                                                                                                    Stop bits

                                             ct        2                                                                        Voltage fluctuation

                                                                                       Test Mode                                compensation standard value   prty

                                                       Heater 2 current                                                         stim                                    Parity bit

            i     s  c  2                    s   c  e                        1 s min.  test

                                                                                                                                          Startup lock time   goht      *4

                           Heater 2 input shift        Power supply voltage            An alarm is output if

                           display current             measurement value               the test value falls                     odly                             Gate OFF

                                                                                       below the burnout                                                         output hold time

                                                                             1 s min.  alarm value 1 setting.

            i     s  c  1                    m   a  x  1                                                                        Output ON-delay time

                           Heater 1 input shift        Heater 1                                                                                               nct1

                           display current             maximum current                                                          soft                             Number of

            o     t  i  m                    m   i  n  1                                                                                                         CT passes 1

                                                                                                                                          Soft startup time

                           RUN time                       Heater 1                                                                                            ctr1

                                                          minimum current              Gate Mode        *2                      ssht

                                                                                                                                                                 CT ratio 1

            memo                             max2                                                                                         SSR short circuit

                                                                                                                                          detection function  ndp1

                           Processing value               Heater 2           1 s min.  g-lV

                           for alarm output               maximum current                                                       sopn                             Setting 1 for number of

                                                                                       Alarm or detection is                                                     effective digits to be displayed

            acnt                             min2                                      stopped if the gate                                SSR open circuit       after the decimal point

                                                                                       current value falls                                detection function

                           Number of                      Heater 2           1 s min.  below the set value.                                                   nct2

                           alarm outputs                  minimum current                                                       hrst

                                                                                                                                                                 Number of

            min5                             maxs                                                                               Heater layer short circuit       CT passes 2

                           Minimum power                  Maximum power                                                         detection function            ctr2

                           supply voltage                 supply voltage

                                                                                                                                hral                             CT ratio 2

                  Measurement                                                                                                   Heater layer short circuit    ndp2

                     parameters          *3                                                                                     alarm set value

                                                                                                                                                                 Setting 2 for number of

                                                                                                                                msmd                             effective digits to be displayed

                                                                                                                                          *2                     after the decimal point

                                                                                                                                      Heater control             Note:

                                                                                                                                      method                     Displayed only for

                                                                                                                                dsel                             the K8AC-H2@@@.

                                                                                                                                          Switchable          sdly

                        Parameter Display                                                                                                 display

                                     : Displayed for all models and settings.                                                   psmd                             SSR ON delay

                                     : May not be displayed depending on the model or settings.                                           Power save          sglV

                                                                                                                                          mode

                                                                                                                                pstm                             SSR operation

                                                                                                                                          Power save             gate current level

                                                                                                                                          mode standby

                                                                                                                                          time                cyct

                                                                                                                                                                 Cycle time

*1.     Displayed when the Selectable Protection Level parameter is set to 0.

*2.     Displayed by the K8AC-H@@P@-FLK.

*3.     If more than five minutes elapses with no operations performed in Protection Settings Mode, Adjust Mode, Set Mode, or                                 for a measurement

        parameter, the status will return automatically to the processing value display.

        If this occurs while settings are in progress, it may cause unintended operations to be performed in Run Mode (i.e., with                             measurement values

        displayed). Be careful not to allow this to happen.

*4.     Displayed by the K8AC-H@@C@-FLK.

                                                                                                                                                                                                   17
K8AC-H

Parameter Defaults and                              Descriptions                Note:                  Shaded parameters must always   be set regardless of the

                                                                                              measurement method.

          Item           Parameter name                                         Description                                    Param-        Setting range        Default

    Mode                                                                                                                       eter

                                                    Restricts access to Adjust Mode or Set Mode from Run Mode.

    Protec-     Setting Change Protection           0: Access enabled to both Adjust Mode and Set Mode.                        aspt    0 to 2                     0

    tion                                            1: Access enabled to Adjust Mode and disabled to Set Mode.

    Mode                                            2: Access disabled to both Adjust Mode and Set Mode.

                Setting Value Change                Prohibits changes to set values.                                           wtpt    ON/OFF                     OFF

                Prohibition

                Burnout Alarm             K8AC-H@1  Sets the output operation value for the burnout alarm.                             0.200 to 2.200 A           1.000 A

                Value 1                   K8AC-H@2  The burnout alarm function can be disabled by setting the set value to     al-1    2.00 to 22.00 A            10.00 A

                                          K8AC-H@3  “−”.                                                                               20.0 to 200.0 A            100.0 A

    Adjust      Burnout Alarm             K8AC-H@1  Sets the output operation value for the burnout alarm.                             0.200 to 2.200 A           1.000 A

    Mode        Value 2                   K8AC-H@2  The burnout alarm function can be disabled by setting the set value to     al-2    2.00 to 22.00 A            10.00A

                                          K8AC-H@3  “−”.                                                                               20.0 to 200.0 A            100.0 A

                Voltage Fluctuation                 Sets the standard voltage used by the voltage fluctuation

                Compensation Standard Value         compensation function. The fluctuation compensation function               vfcv    100 to 240 VAC             100 V

                                                    operates in respect to this set value.

                All Initialization                  Returns all set values and measurement values to their default             init    ON/OFF                     OFF

                                                    settings.

                Set Value Initialization            Returns all set values to their default settings.                          sini    ON/OFF                     OFF

                Processing Value Initialization     Returns all measurement values to their default settings.                  pini    ON/OFF                     OFF

                Alarm Hysteresis 1                  Sets hysteresis for the alarm output value for burnout detection           hys1    1 to 999                   10

                                                    (undercurrent) and heater layer short circuits (overcurrent) for CT1.

                Alarm Hysteresis 2                  Sets hysteresis for the alarm output value for burnout detection           hys2    1 to 999                   10

                                                    (undercurrent) and heater layer short circuits (overcurrent) for CT2.

                Gate Input Function                 Turns the gate input function ON and OFF. If the gate input is turned      gate    ON/OFF                     ON

                                                    OFF, application as a simple ammeter is possible.

                Voltage Fluctuation                 Turns the voltage fluctuation compensation function ON and OFF.            comp    ON/OFF                     OFF

                Compensation Reference Value

                Startup Lock Time                   Sets the lock time for the startup lock.                                   stim    0 (OFF) to 255 s           0 (OFF)

                Output ON-Delay                     Sets the output delay time. Set this parameter to set the operating time.  odly    0.0 (OFF) to 99.9 s        0.0 (OFF)

                Soft Startup Time                   Sets the soft startup time. Set this parameter only when using a soft      soft    0.0 (OFF) to 99.9 s        0.0 (OFF)

                                                    start function with the power regulator.

                SSR Short Circuit Detection         Turns the SSR short circuit detection function ON and OFF.                 ssht    ON/OFF                     OFF

                SSR Open Circuit Detection          Turns the SSR open circuit detection function ON and OFF.                  sopn    ON/OFF                     OFF

                Heater Layer Short Circuit          Turns the heater layer short circuit (overcurrent) detection function ON

                Detection (Overcurrent              and OFF.                                                                   hrst    ON/OFF                     OFF

                Detection)

                Heater Layer Short        K8AC-H@1  Sets the operating level for heater layer short circuit (overcurrent)              0.200 to 2.200 A           2.000 A

                Circuit Alarm Level       K8AC-H@2  alarms.                                                                    hral    2.00 to 22.00 A            20.00 A

                (Overcurrent Alarm        K8AC-H@3  The heater layer short circuit alarm level is the same for both CT1 and            20.0 to 200.0 A            200.0 A

                Set Value)                          CT2.

                Heater Control Method *1            Sets the control method of the cyclic/phase control heater.                msmd    PH1, PH3, CYCL             PH1

    Set Mode    Switchable Display                  Sets the CT for which to normally display the current.                     dsel    CT1, CT2                   CT1

                Power Save Mode                     Turns entering the power save mode ON and OFF.                             psmd    ON/OFF                     OFF

                Power Save Mode Standby Time        Sets the time to enter power save mode.                                    pstm    10 to 300 s                60 s

                Display Mode                        Sets a 7-segment (NORM). full-span comparison (CMP), or bar (BAR)          dsmd    NORM, CMP, BAR             NORM

                                                    display.

                Display Refresh Time                Sets the refresh time for the display.                                     dsrf    0.2 s, 0.5 s, 1.0 s, FAST  0.5 s

                Unit Number                         Sets the unit number for RS-485 communications.                            u  no   0 to 64                    0

                Baud Rate                           Sets the baud rate for RS-485 communications.                                 dps  1200, 2400, 4800, 9600,    9600

                                                                                                                                       19200

                Data Length                         Sets the data length for RS-485 communications.                               len  7, 8                       7

                Stop Bits                           Sets the number of stop bits for RS-485 communications.                    sbit    1, 2                       2

                Parity Bit                          Sets the parity for RS-485 communications.                                 prty    EVEN, ODD, NONE            EVEN

                Gate OFF output hold time *2        Sets the time from when the gate signal goes OFF until the burnout         goht    0 to 999 s                 2s

                                                    alarm output turns OFF.

                Number of CT passes 1               Sets the number of times the conductor for CT1 is passed through the       nct1    1 to 99 times              1 time

                                                    current transformer.

                CT Ratio 1                          Sets the CT ratio for CT1.                                                 ctr1    1 to 999                   1

                Setting 1 for number of effective   Sets the number of effective digits to be displayed after the decimal                                         Depends

                digits to be displayed after the    point for the CT1 current display.                                         ndp1    0 to 3 places              on the

                decimal point                                                                                                                                     model.

                Number of CT passes 2               Sets the number of times the conductor for CT2 is passed through the       nct2    1 to 99 times              1 time

                                                    current transformer.

                CT Ratio 2                          Sets the CT ratio for CT2.                                                 ctr2    1 to 999                   1

                Setting 2 for number of effective   Sets the number of effective digits to be displayed after the decimal                                         Depends

                digits to be displayed after the    point for the CT2 current display.                                         ndp2    0 to 3 places              on the

                decimal point.                                                                                                                                    model.

18
                                                                                                                                                          K8AC-H

      Item     Parameter name                                                  Description                                  Param-       Setting range    Default

Mode                                                                                                                        eter

            SSR ON delay                      Sets the SSR ON-delay time.                                                   sdly    0.0  (OFF) to 99.9 s  0.2 s

                                              Sets the gate current level for SSR operation.

            SSR operation gate current level  (This setting is valid only when cyclic or phase control is selected as       sglv    4.0  to 20 mA         7.0 mA

Set Mode                                      the heater control method.)

                                              Sets the cycle time.

            Cycle time *3                     (This setting is valid only when cyclic control is selected as the heater     cyct    0.2  to 3.0 s         0.2 s

                                              control method.)

Gate        Gate Current Level *1             Sets the gate current value that stops an alarm, detection, or output.        g-lv    7.0  to 20.0 mA       7.0 mA

Mode

*1. Displayed by the K8AC-H@@P@-FLK.
*2. Displayed by the K8AC-H@@C@-FLK.
*3. You must restart the K8AC after you change the setting of the cycle time.

Dimensions                                                                                                                                                (Unit: mm)

Digital Heater Element Burnout Detectors

K8AC-H2@@@-FLK

                                              35                2.1            100

                                                                                                                            To remove a wire, insert the recom-

                                                                                                                            mended flat-blade screwdriver straight

                                                                                                                            into the hole under the push-in terminal

                                                                                                                            of the wire to enable easily remove it.

                                                                                                              90

                                                                1.7                                                    4.5

                                                                                              6

K8AC-H1@@@-FLK

                                              35                               100

                                                                                                              90

Recommended Tools                                                              Recommended Crimp Terminals

Recommended Flat-blade Screwdriver                                                                                                                        Recom-

Manufacturer: Phoenix Contact                                                  Terminals                      Recommended crimp terminals                 mended

Model number: SZF0.4 × 2.5                                                                                                                                wire gauge

                                                                                              M3 crimp terminals (Width: 5.8 mm max.)

Crimper for Bar Terminals (Crimping Tool)                                                                                           5.8 mm max.           AWG16 to

Manufacturer:  Phoenix Contact                                                 1 and 2                                                                    AWG18

Model number: CRIMPF0X UD6

Recommended power line diameters: AWG10 to AWG24                                                                                    5.8 mm max.

                                                                                              M2 bar terminals: Al 0.34-8TQ (Phoenix Contact)             AWG22

                                                                               3 to 14        M2 bar terminals: Al 0.5-8WH (Phoenix Contact)              AWG20

                                                                                              M2 bar terminals: Al 0.75-8GY (Phoenix Contact)             AWG18

                                                                               Note: Securely tighten the terminal screws to the following torque:

                                                                                              Power supply terminals: 0.5 N·m

                                                                                              I/O terminals:                0.23 N·m

                                                                                                                                                                      19
K8AC-H

Optional Parts (Sold Separately)

Current Transformer                                                 15                            1.2 dia.  2.8

K8AC-CT20S                                                              0.5

                                                                                                  5.5                  7

                                            5.8 dia.

                                                                                                                 25

                                                                                           10.5

                                                                    21             2.5

                                                                                  Two, 3.5 dia.

                                                                                   10

                                                                    30

                                                                    40

Current Transformer                                                                    Accessories               with     K8AC-CT20L:    Connection Example

K8AC-CT20L                         30                                   2.36 dia.      Contact

                                                     9                                                                                   Contact

                                                                                                                                   Plug

                                                                                        Approx. 3 dia.                                            Lead

                                            40

                                                                                                                 18

                       12 dia.

                                   40                           15                     Plug

                                            Two, M3

                                            Depth: 4       max.                             Approx. 6 dia.

                                            15                                                                   (22)

                                5  30

Current Transformer                                             30

K8AC-CT200 (Pre-wired  Leads)                                                          5

                                                                                   100

                                                                                   40

                                            12 dia.

                                                                40                                15

                                                                                  Two, M3

                                                                                  Depth: 4  max.

                                                                                   15

                                                        5       30

Current Transformer                                        9.3          9.3

K8AC-CT200L                                                1.7               1.7

                                                                    11       4.7

                                                                63                                          20

                                                                54                Four, M4 × 6 screws

                                                           50                                               17

                                                                                       8.5                                               Mounting Hole Dimensions

                                                                                            13.5

                                                                                                                                         Two, M5 screw holes

                                                                                            34.5                                         or two, 5.5-dia. holes

                                                                                                  81.5

                                                                                            33.5                                                  76

                                                                                        6

                                            14.5           57           14.5                                              30 dia.

                                                           86

                                                                                   5.2

                                   10                                                       20

                                   10

                                                     1.8                                                               Note: Wire only the K and L terminals to the K8AC-H.

                                       4.1                 76                      5.9                                             Leave the Kt and Lt terminals open.

20
                                                                                                                                             K8AC-H

Safety Precautions

                Precautions for Safe Use                                   Mounting the K8AC-H

                                                                           • Pull down the hook on the bottom of the K8AC-H, and then catch

The following precautions are essential to ensure safety. Always heed          the hook on the top of the K8AC-H onto the DIN Track and press

these precautions.                                                             the K8AC-H onto the DIN Track until it locks into place.

1.  Do not use or store the Product in the following locations.

    • Outdoors or in locations subject to direct sunlight, wind, or rain

    • Locations subject to dust, metal powder, or corrosive gases (in

    particular, sulfuric or ammonia gas)

    • Locations subject to static electricity or noise

    • Locations subject to flooding or exposure to oil

2.  Use DIN Track for installation and mount the Product in the correct

    direction.

3.  Do not touch the terminals when power is being supplied. Electric      Removing the K8AC-H

    shock may occasionally occur.

4.  Be sure you understand the contents of the Instruction Sheet and       • Pull down on the hook with a flat-blade screwdriver and lift up on

    User’s Manual and handle the Product according to the                      the K8AC-H.

    instructions provided.

5.  Check all terminal numbers and polarity when wiring and wire all

    connections correctly.

6.  Tighten terminal screws to the following torque.

    Power supply terminals: 0.5 N·m

7.  Use the Product within the specified temperature and humidity

    ranges.

8.  Do not use the product in locations subject to flammable or

    explosive gases. Explosions may occasionally occur if the product

    is used in such locations.

9.  Do not install the Product in any way that would place a load on it.   Noise Countermeasures

10.Use the Current Transformer specified by OMRON.                         1.  Do not install the product near devices generating strong high

11.Install an external switch or circuit breaker that complies with            frequency waves or surges.

    applicable IEC60947-1 and IEC60947-3 requirements and label it         2.  When using a noise filter, check the voltage and current and install

    clearly so that the operator can quickly turn OFF the power.               it as close to the product as possible.

12.The product must be handled by personnel who have knowledge             3.  In order to prevent inductive noise, wire the lines connected to the

    of electrical systems.                                                     product separately from power lines carrying high voltages or

                Precautions for Correct Use                                    currents. Do not wire in parallel with or on the same cable as power

                                                                               lines.

The following precautions are essential to ensure correct use. Always          Other measures for reducing noise include running lines along

heed these precautions.                                                        separate ducts and using shield lines.

1.  Do not use the product in the following locations.                     Wiring

    • Places subject to radiant heat from heat generating devices.         • Do not touch terminals or perform wiring while power is supplied to

    • Places subject to vibrations or physical shocks.                         the product. Doing so may result in injury or malfunction.

2.  Make sure to use setting values appropriate for the controlled         • Wire to the correct terminal number. Incorrect wiring may result in

    object. Failure to do so can cause unintended operation, and may           damage to or burning of components.

    result in accident or corruption of the product.

3.  Do not use thinner or similar solvent for cleaning. Use commercial     Wiring the Push-in Terminals

    alcohol.                                                               • Directly insert the ferrule in the hole of the terminal to be wired.

4.  When discarding, properly dispose of the product as industrial

    waste.

5.  To measure correct values, perform aging for approximately 15

    minutes.

6.  Only use this product within a board whose structure allows no                                            7     8     9  10 11 12 13 14

    possibility for fire to escape.                                                                           RUN ADJ SET GATE SSR ALM

Installation                                                                                               8. 8. 8. 8.

1.  When wiring, use only recommended crimp terminals.

2.  Do not block areas around the product for proper dissipation of

    heat. (If you do not secure space for heat dissipation, life cycle of

    the product will be compromised.)                                      Removing Wires from the Push-in Terminals

                                                                           • Insert the recommended flat-blade screwdriver straight          into  the

                                                                               hole to pull out the wire.

                                                                                                           7     8     9  10 11 12 13 14

                                                                                                           RUN ADJ SET GATE SSR ALM

                                                                                            8. 8. 8. 8.

                                                                                                                 U

                                                                                                                                                        21
K8AC-H

                                             Q&A

    Q               Why does the current measured by the K8AC-H decrease

                    during cyclic or phase control?

                    To enable measuring the current accurately for the heater

                    control value, the K8AC-H@@P@-FLK uses the current input

                    waveform from a gate input and the Current Transformer to

                    compensate the measured current value and burnout alarm

                    value. The compensated current value is displayed, so it

                    appears as if the measured current is lower during cyclic or

                    phase control, but the K8AC-H@@P@-FLK is operating

                    correctly.

    Q               How do I set the burnout detection alarm of the K8AC-

                    H@@P@-FLK when phase control is used?

                    Set the burnout alarm value of the K8AC-H@@P@-FLK based

                    on the current measurement value with the heater output at

                    100%. (This is because the burnout detection alarm of the

                    K8AC-H@@P@-FLK depends on the control input.)

                    When you set the burnout alarm value, make sure that you

                    make the setting based on the current measurement value

                    when the control of the power regulator is 100% or the rated

                    voltage is applied to the heater.

    Heater current  Heater current

                                                Heater Burnout Alarm Value

                                                The heater burnout alarm value shifts

                                                according to the control input (4 to

                                Heater burnout  20 mA) from the temperature controller.

                                alarm value

                    4 mA  7 mA                  20 mA

                    Control output from temperature controller

22
Warranty and Application Considerations

                          Warranty and Limitations of Liability

WARRANTY

OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or

other period if specified) from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,

MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER

ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET

THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR

IMPLIED.

LIMITATIONS OF LIABILITY

OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS,

OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON

CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.

In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE

PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,

INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE

MODIFICATION OR REPAIR.

                          Application Considerations

SUITABILITY FOR USE

OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of

products in the customer's application or use of the products.

Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will

be used.

Know and observe all prohibitions of use applicable to this product.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT

ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON

PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR

SYSTEM.

                                                        Disclaimers

CHANGE IN SPECIFICATIONS

Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with

your OMRON representative at any time to confirm actual specifications of purchased product.

DIMENSIONS AND WEIGHTS

Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
Related Products

                                                                         Heater Element Burnout Detector

                                                                         K2CU

                                                                         Enables detection of single-phase/three-phase burnouts.

                                                                         For heaters with ON/OFF control only, provides voltage

                                                                         fluctuation compensation.

                                                                         Rated current: 0.25 to 80 A AC

                                                                         Current Sensor

                                                                         SAO

                                                                         Enables detection of single-phase/three-phase overcurrents.

                                                                         Inverse operation models and instantaneous operation models

                                                                         (with startup lock) are available.

                                                                         Rated current: 1 to 160 A AC

For details, refer to the Measuring      &  Motor  Protective  Relays  Group Catalog (Cat. No. X070).

• The application examples provided in this catalog are for reference only. Check functions and safety of the equipment before use.

• Never use the products for any application requiring special safety requirements, such as nuclear energy control systems, railroad systems, aviation systems, medical equipment,

amusement machines, vehicles, safety equipment, or other application involving serious risk to life or property, without ensuring that the system as a whole has been designed to address

the risks, and that the OMRON products are properly rated and installed for the intended use within the overall equipment or system.

                  ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

                  To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

OMRON Corporation                    Industrial Automation Company                                Authorized Distributor:

Tokyo, JAPAN

                  Contact:    www.ia.omron.com

Regional Headquarters

OMRON EUROPE B.V.                                  OMRON ELECTRONICS LLC

Wegalaan 67-69-2132 JD Hoofddorp                   One Commerce Drive Schaumburg,

The Netherlands                                    IL 60173-5302 U.S.A.

Tel: (31)2356-81-300/Fax: (31)2356-81-388          Tel: (1) 847-843-7900/Fax: (1) 847-843-7787

OMRON ASIA PACIFIC PTE. LTD.                       OMRON (CHINA) CO., LTD.                        © OMRON Corporation 2009            All Rights Reserved.

No. 438A Alexandra Road # 05-05/08 (Lobby 2),      Room 2211, Bank of China Tower,                In the interest of product improvement,

Alexandra Technopark,                              200 Yin Cheng Zhong Road,                      specifications are subject to change without notice.

Singapore 119967                                   PuDong New Area, Shanghai, 200120, China       CSM_9_3_0618                             Printed in                                      Japan

Tel: (65) 6835-3011/Fax: (65) 6835-2711            Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200  Cat. No. N137-E1-03                                                                      0508
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory,  Delivery  &  Lifecycle  Information:

Omron:

K8AC-H22PN-FLK
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

器件索引   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
搜索索引   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2020 EEWORLD.com.cn, Inc. All rights reserved