器件描述

Controllers PANEL METERAC INPUTS

参数

产品属性属性值
产品种类:
Product Category:
Controllers
制造商:
Manufacturer:
Omron
RoHS:YES
商标:
Brand:
Omron Automation and Safety
工厂包装数量:
Factory Pack Quantity:
1

K3TF-A914器件文档内容

Digital Panel Meter

K3TF

                                                                                                                    CSM_K3TF_DS_E_4_1

Easy-to-use, Low-cost Digital Panel Meter

that Accepts AC Input

• Compact DIN-size (96 x 48 (W x H)) body.

• Mounting thickness of only 3.5 mm required.

• Highly visible display with 14.2-mm-high LEDs.

• Detects and displays root-mean-square value of half-wave rec-

tified current.

• Confirms to EMC standards EN61010-1 (IEC61010-1).

                                                                                 For the most recent information on models that have been

                                                                                 certified for safety standards, refer to your OMRON website.

                                                                 Note:  This Panel Meter does not support scaling.

Model Number Structure

I Model Number                     Legend

K3TF -

            1     2  3  4

1, 2. Input Code                                     3. Series No.

V5:     0 to 199.9 mV                                        1:  Current series

V6:     0 to 1.999 V                                 4. Supply Voltage

V7:     0 to 19.99 V                                         4:  100 to 120 VAC

V8:     0 to 199.9 V                                         5:  200 to 240 VAC

V9:     0 to 400 V

A6:     0 to 1.999 mA

A7:     0 to 19.99 mA

A8:     0 to 199.9 mA

A9:     0 to 1.999 A

Ordering Information

I List of Models

Models with Line Monitor

Range                   Measuring ranges                         Supply voltage

                                                     100 to 120 VAC              200 to 240 VAC

AC voltage           0 to 199.9 V                 K3TF-V814                      K3TF-V815

                     0 to 400 V                   K3TF-V914                      K3TF-V915

                                                                                                                                               1
                                                                                                                   K3TF

Models with Signal Monitor

Range                     Measuring  ranges                                     Supply     voltage

                                             100 to     120              VAC               200 to       240   VAC

AC voltage        0   to  199.9 mV           K3TF-V514                                     K3TF-V515

                  0   to  1.999 V            K3TF-V614                                     K3TF-V615

                  0   to  19.99 V            K3TF-V714                                     K3TF-V715

AC current        0   to  1.999 mA           K3TF-A614                                     K3TF-A615

                  0   to  19.99 mA           K3TF-A714                                     K3TF-A715

                  0   to  199.9 mA           K3TF-A814                                     K3TF-A815

                  0   to  1.999 A            K3TF-A914                                     K3TF-A915

Note: The K3TF-V8@@ and K3TF-V9@@ do not conform to CE marking standards.

I Accessories (Order Separately)

                Name                         Appearance                                                 Model

Water-resistive Soft Front Cover                                                                    K32-L49SC

Terminal Cover                                                                                      K32-L49TC

Watertight Cover                                                                                    Y92A-49N

Note: 1.  Use the Mounting Bracket included with the K3TF for mounting.

2.        The Terminal Cover is used for finger protection. It has no relation  to  water  resistance.

                                                                                                                         2
                                                                                                                                      K3TF

Specifications

■ Ratings

Supply voltage                     100 to 120 VAC (50/60 Hz); 200 to 240 VAC (50/60 Hz)

Operating voltage range            −15% to +10% of supply voltage

Power consumption                  4 VA (at max. load)

Insulation resistance              10 MΩ min. (at 500 VDC) between external terminal and case

Dielectric strength                2,000 VAC min. for 1 min between input terminal and power supply

                                   2,000 VAC min. for 1 min between external terminal and case

Noise immunity                     ±1,500 V on power supply terminals in normal or common mode

Vibration resistance               Malfunction: 10 to 55 Hz, 0.5-mm single amplitude for 10 min each in X, Y, and Z directions

                                   Destruction: 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions

Shock resistance                   Malfunction: 98 m/s2 for 3 times each in 6 directions

                                   Destruction: 294 m/s2 for 3 times each in 6 directions

Ambient temperature                Operating: −10° to 55°C (with no icing)

                                   Storage:     −20° to 65°C (with no icing)

Ambient humidity                   Operating: 35% to 85% (with no condensation)

Ambient operating atmosphere       No corrosive gas

EMC                                (EMI)                                      EN61326+A1         Industry

                                   Emission     Enclosure:                    CISPR 11 Group  1  class A: CISRP16-1/-2

                                   Emission     AC Mains:                     CISPR 11 Group  1  class A: CISRP16-1/-2

                                   (EMS)                                      EN61326+A1         Industry

                                   Immunity     ESD:                          EN61000-4-2:       4 kV contact discharge (level 2)

                                                                                                 8 kV air discharge (level 3)

                                   Immunity     RF-interference:              EN61000-4-3:       10 V/m (amplitude-modulated,

                                                                                                 80 MHz to 1 GHz) (level 3)

                                   Immunity     Fast Transient Noise:         EN61000-4-4:       2 kV (power line) (level 3)

                                   Immunity     Burst Noise:                                     1 kV line to line (I/O signal line)

                                   Immunity     Surge:                        EN61000-4-5:       1 kV line to line

                                                                                                 2 kV line to ground (power line)

                                   Immunity     Conducted Disturbance         EN61000-4-6:       3 V (0.15 to 80 MHz) (level 2)

                                   Immunity     Voltage Dip/Interrupting      EN61000-4-11:      0.5 cycles, 0, 180°, 100% (rated     voltage)

Approved standard                  Conforms to EN61326+A1, EN61010-1 (IEC61010-1)

                                   Conforms to VDE0106/P100 (finger protection) when the terminal cover is mounted.

Note: The K3TF-V8@@ and K3TF-V9@@  do not conform to CE marking standards.

■ Characteristics

Input signal                       AC voltage/current

A/D conversion method              Double integral method

Root-mean-square value indication  Root-mean-square value of half-wave rectified current detected

Sampling period                    2.5 times/s

Display refresh period             2.5 times/s

Max. displayed digits              3 1/2 digits (1999)

Display                            7-segment red LED

Decimal point display position     Selected with slide switch (see note 1)

Overflow display                   Overflow: 1@@@

Zero suppression                   Not supported.

External control                   Process value hold (terminals on rear panel short-circuited)

Degree of protection               Front panel: IEC IP51 (see note 2)

                                   Case:        IEC IP20

                                   Terminals:   IEC IP00

Note: 1.  Only for models with signal monitor.

     2.   IP51 is maintained when the water-resistive soft cover and bracket  are used.  IP50 will be, however, maintained without these water-re-

          sistive accessories.

                                                                                                                                                    3
                                                                                                                                             K3TF

■ Measuring Ranges

Monitor       Input range  Measuring range            Max. resolution          Input impedance                     Accuracy          Max. permissible

                                                                                                                                             load

Line monitor  AC voltage   0  to  199.9  V            100 mV                10 MΩ                      ±0.3%rdg           ±1  digit  500 V

                                                                                                       (see note          1)

                           0  to  400 V               1V                    10 MΩ                      ±0.3%rdg           ±1  digit  500 V

Signal        AC voltage   0  to  199.9  mV           100 μV                10 MΩ                      ±0.3%rdg           ±1  digit  250 V

monitor                    0  to  1.999  V            1 mV                  10 MΩ                      ±0.3%rdg           ±1  digit  250 V

                           0  to  19.99  V            10 mV                 1 MΩ                       ±0.3%rdg           ±1  digit  250 V

              AC current   0  to  1.999  mA           1 μA                  100 Ω                      ±0.5%rdg           ±1  digit  50 mA

                           0  to  19.99  mA           10 μA                 10 Ω                       ±0.5%rdg           ±1  digit  150 mA

                           0  to  199.9  mA           100 μA                1Ω                         ±0.5%rdg           ±1  digit  500 mA

                           0  to  1.999  A            1 mA                  0.1 Ω                      ±0.5%rdg           ±1  digit  3A

Note: 1.  With 100% input. ±0.3% FS±1 digit when the input is less than 35% FS.

2.        The above accuracy is at an input frequency range of 40 Hz to 1 kHz and an ambient temperature of 23±5°C.

3.        A large error will result if a signal that is not a sine wave is used (e.g., a signal from thyristor control).

Connections

■ External Connections

                                  1          2          3     4             5      6                7  8                  9

                                  AC signal input     GND     HOLD               Unused                AC power supply

                           Note: Terminals 2 and 3 of the models are not internally insulated. Connect a relay with high

                                  contact reliability and insulation (with a minimum load current of 0.3 mA) or a

                                  photocoupler with high insulation (with a residual voltage of 1 V max. and a current

                                  leakage of 0.1 mA max.) to these terminals for external control.

Nomenclature

                                                                                                                   103

                                                                                                                   102

                                                                                                                   101

              Display                        Unit name                                                 No decimal point

                              Select the decimal position with the slide

                              switch under the cover on the front panel

                              (signal monitor only).

                              Remove the front panel by using a flat-blade

                              screwdriver or your fingernail in the two

                              notches at the bottom.

                              Note: The decimal position cannot be

                                  changed for the K3TF-V81@ or

                                  K3TF-V91@.

                                                                                                                                                       4
                                                                                                                                          K3TF

Dimensions

Note: All units are in millimeters unless otherwise indicated.

                                                                                                    Panel Cutouts

                                                                                                                       92+−00.8

                    98                                                                    45+−00.6

                    92

                                                                                                                                          75 min.

                                                                                                        120 min.

                                                                                              Note: The values above are recommended

                                                                                                    values. Do not group-mount the meters

                                                                                                    at intervals less than the

                                                                                                    recommended ones.

                                                                48                        43        LED Indicator Size

                                                                                                                14.2 mm

                    96                                              3.5  66

                                                                    The K3TF uses  M3.5 terminals.

                                                                                                        7.8 mm

Application Examples

High AC Voltage Measurement                                                        Large AC Current Measurement

When voltage exceeding the maximum voltage in the standard                         When AC current exceeding 2 A is measured, a

range is measured (for example: more than 400 V), a divider or                     current transformer (CT) is connected externally.

potential transformer (PT) is connected externally.

       Hi       Hi                                                                        Hi                    Hi

                             Digital                                                                                             Digital

Input                        panel                                                 Input                                         panel

                             meter                                                                                               meter

       Lo       Lo                                                                        Lo                    Lo

            PT                                                                                      CT

                                                                                                                                                   5
                                                                                                                                      K3TF

Safety Precautions

Refer to Safety Precautions for All Digital Panel Meters.

Precautions for Safe Use                                                 Calibration

The front panel cover is removed when setting the decimal point          Calibrate the Digital Panel Meter regularly so that the Digital Panel

position or performing calibration. Do not, however, touch any parts     Meter can maintain processing accuracy.

other than the slide switches or adjustment knob or come close to        Use a standard signal generator with an accuracy of 99.99% min. for

any metal parts.                                                         calibration.

                                                                         For the precise calibration methods, refer to the Instruction Sheet for

                                                                         the Digital Panel Meter.

                                                                         After the front panel cover is removed to calibrate the K3TF or set the

                                                                         decimal  position,   do   not  touch  components      other  than  the  slide

                                                                         switch and calibration adjustor. Keep metal objects off the K3TF after

                                                                         the cover is removed, especially when power is turned on.

Precautions for Correct Use                                              Accessories (Order Separately)

Mounting                                                                 Water-resistive Soft Front Cover

Recommended panel thickness is 1 to 3.2 mm.                              Before mounting the Digital Panel Meter to a panel, attach the water-

                                                                         resistive soft front cover and mounting bracket to the Digital Panel

Mount the Digital Panel Meter by attaching the mounting bracket sup-     Meter properly so that the Digital Panel Meter will maintain IP51

plied as an accessory from the rear of the Digital Panel Meter, hook     water-resistive standards. Before you calibrate Digital Panel Meters,

the mounting bracket to the Digital Panel Meter securely, and tighten    remove the water-resistive soft front cover. Refer to the operation

the mounting screws by turning them clockwise with a tightening          manual included with the Digital Panel Meter for the calibration pro-

torque of 5 kgf·cm (0.49 N·m). For dismounting, loosen the screws        cedure.

and widen the hooks.

Always attach the Mounting Bracket before wiring the terminals. Also,

always remove the wiring before removing the Mounting Bracket.                                                     Mounting

Mount the Digital Panel Meter as horizontally as possible.                                                         Bracket

Never use the Digital Panel Meter in locations where corrosive gas

(particularly sulfide or ammonia gas) is generated.

As much as possible avoid use of the Digital Panel Meter in a loca-

tion subject to severe shock or vibration, excessive dust, or exces-              Soft Cover

sive moisture.

Select a mounting location where the Digital Panel Meter can be          Note: Be sure to use the Water-resistive Soft Front Cover and

used at an ambient operating temperature −10° to 55°C.                                 mounting bracket together.

No product is shipped with the unit label attached. Select a unit label

from the sheet provided, and attach it to the Digital Panel Meter.

                  ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

                  To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                      In the interest of product improvement, specifications are subject to change without notice.

                                                                                                                                                        6
                                                     Terms and Conditions Agreement

Read and understand this catalog.

Please read and understand this catalog before purchasing the products.                 Please consult your OMRON representative if you

have any questions or comments.

Warranties.

(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship

for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron

disclaims all other warranties, express or implied.

(b)  Limitations.      OMRON    MAKES           NO   WARRANTY          OR   REPRESENTATION,         EXPRESS             OR   IMPLIED,      ABOUT

NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER

ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE

PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.

Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the

Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at

Omron’s     election,  to  (i)  replace    (in  the  form  originally  shipped    with  Buyer  responsible  for  labor  charges  for  removal            or

replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount

equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,

repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products

were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate

modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall

not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or

electronic   components,        circuits,  system    assemblies  or    any  other  materials   or   substances   or  environments.    Any  advice,

recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above

warranty.

See http://www.omron.com/global/           or contact your Omron representative for published information.

Limitation on Liability; Etc.

OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,

LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,

WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.

Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.

Suitability of Use.

Omron     Companies    shall    not  be    responsible     for  conformity  with  any   standards,  codes   or  regulations  which  apply  to            the

combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable

third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself

is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,

system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product

with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.

NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE

QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,

AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE

OVERALL EQUIPMENT OR SYSTEM.

Programmable Products.

Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence

thereof.

Performance Data.

Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining

suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate

it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.

Change in Specifications.

Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our

practice to change part numbers when published ratings or features are changed, or when significant construction changes are

made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers

may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at

any time to confirm actual specifications of purchased Product.

Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.

                                                                                                                                           2014.2

                                                           In the interest of product improvement, specifications are subject to change without notice.

OMRON Corporation

Industrial Automation Company

http://www.ia.omron.com/                                                                       (c)Copyright OMRON Corporation 2014 All Right Reserved.
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Omron:

K32 -L49TC  K3TF-A914   K32-L49TC  K3TF-V914  K3TF-V814  K3TF-V514

小广播

K3TF-A914器件购买:

该厂商的其它器件

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2017 EEWORLD.com.cn, Inc. All rights reserved