ITMA3035器件文档内容

                                                                                                                                                                                                       Bulletin No. ITMA3-D
                                                                                                                                                                                                       Drawing No. LP0405
                                                                                                                                                                                                       Released 06/13

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

MODEL ITMA DC - INTELLIGENT THERMOCOUPLE MODULE WITH ANALOG OUTPUT

                                                                                                         USER PROGRAMMABLE INPUT
                                                                                                            (Thermocouple types J, K, T, & E, or millivolt)

                                                                                                         MICROPROCESSOR CONTROLLED
                                                                                                         SIMPLE ADJUSTABLE RANGE SETTING (Using Input Signal)
                                                                                                         THERMOCOUPLE BREAK DETECTION
                                                                                                         MOUNTS ON "T" AND "G" STYLE DIN RAILS
                                                                                                         3-WAY ELECTRICAL ISOLATION (POWER/INPUT/OUTPUT)
                                                                                                         MULTIPLE ANALOG OUTPUTS (0 to 20 mA, 4 to 20 mA, and 0 to

                                                                                                            10 VDC)
                                                                                                         WIDE OPERATING TEMPERATURE RANGE (-25C to 75C)
                                                                                                         POWER & MEMORY ERROR INDICATION
                                                                                                         9 to 32 VDC POWERED

DESCRIPTION                                                                                                                                                                                            SAFETY SUMMARY

   The ITMA accepts a thermocouple or millivolt input and converts it into a                                                                                                                              All safety related regulations, local codes and instructions that appear in the
voltage or current output. The voltage or current output is linearly proportional                                                                                                                      manual or on equipment must be observed to ensure personal safety and to
to the temperature or millivolt input. This output is ideal for interfacing to                                                                                                                         prevent damage to either the instrument or equipment connected to it. If
indicators, chart recorders, controllers, or other instrumentation equipment.                                                                                                                          equipment is used in a manner not specified by the manufacturer, the protection
                                                                                                                                                                                                       provided by the equipment may be impaired.
   The ITMA is DC powered. The DC power input is isolated from the signal
input and analog output. The unit scales the analog output proportionally to the                                                                                                                                                 CAUTION: Read complete instructions prior
thermocouple or millivolt input signal. The analog output may be configured for                                                                                                                                                      to installation and operation of the unit.
one of the following: 0 to 20 mA, 4 to 20 mA, or 0 to 10 VDC. Making the
signal conversion with the ITMA to a current output signal, makes the signal                                                                                                                           SPECIFICATIONS
less susceptible to noise interference and allows accurate transmission over long
distances. The 3-Way isolation allows the use of grounded thermocouples which                                                                                                                          1. POWER: 9 to 32 VDC; 1.75 W The power supply must have 300 mA for 200
can provide additional noise reduction benefits.                                                                                                                                                          msec. surge capacity.

   The ITMA uses a ten position DIP switch to accomplish the input sensor                                                                                                                              2. INPUT: J, K, T, E, mV [selectable via DIP switch]
configuration, range selection, and unit calibration. A simple range setting                                                                                                                           3. OUTPUT: Self-powered (active); All output signals scaled linearly using
technique (Field Calibration) is used so the actual input signal adjusts the output
for scaling. This technique eliminates the need for potentiometers which are                                                                                                                              temperature or mV input. Unit is shipped set for 4 to 20 mA output. 4 to 20
vulnerable to changes due to vibration.                                                                                                                                                                   mA or 0 to 20 mA selected via internal jumper.
                                                                                                                                                                                                          Voltage Output Compliance:
   The unit is equipped with a universal mounting foot for attachment to
standard DIN style mounting rails, including top hat rail (T) according to EN 50                                                                                                                             0 to 10 VDC across min 1 K load (10 mA)
022 - 35 7.5 and 35 15, and (G) profile according to EN 50 035 - G 32.                                                                                                                                   20 mV peak to peak max. ripple (for frequencies up to 120 Hz)
                                                                                                                                                                                                          Current Output Compliance:
DIMENSIONS In inches (mm)                                                                                                                                                             1.08                   0 to 20 mA through max. 600 load (12 VDC)
                                                                                                                                                                                     (27.5)                  4 to 20 mA through max. 600 load (12 VDC)
                       3.12                                                                                                                                                                                  15 mV peak to peak max. ripple across 600 load (for freq. up to 120 Hz)
                      (79.2)                                                                                                                                                                           4. TC BREAK DETECTION: Nominal values shown in the following order:
                                                                                                                                                                                                          (0 to 20 mA, 4 to 20 mA, and 0 to 10 VDC).
                               9-32 VDC               VDC+ 10 11 12 VDC-         ERROR  POWER  V+ 4 5 6 V-  I+ 1 2 3 I-                                                                                   Upscale: 22.9 mA, 22.5 mA, and 11.5 VDC
                                                                          TC+ 7 8 9                                                                                                                       Downscale: -0.5 mA, 3.5 mA, and -0.4 VDC
                                                                                                                                                                                                       5. RESPONSE TIME: 400 msec (to within 99% of final value w/step input;
MC2220X                                                                            5                                                           RED LION CONTROLS                                          typically, response is limited to response time of probe.)
                                                                              TC- 4                                                           YORK, PA. MADE IN U.S.A.                                 6. TEMPERATURE EFFECTS:
                                                      1  2                              6  7   8            9  10                                                                                         Temperature Coefficient: 0.025% of input range per C
                                                                          3                                                              MODEL ITMA                                                       Ice Point Compensation: 0.75C for a 50C change in temperature
                                                                                                                                                                                                       7. DIELECTRIC WITHSTAND VOLTAGE: 1500 VAC for 1 minute
ON = 1   DIP SWITCH SETTINGS:                                                                                                                                                                             Working Voltage: 50 VAC
                                                                                                                                                                                                          Power input to Signal input, Power input to Signal output, & Signal input to
OFF = 0                                                                                       RANGE                                                                     4.20 REF             POWER        Signal output.
                                                                                          RANGE                                                                             (106.7)                    8. RANGE & ACCURACY: (12 Bit resolution)
                                                                                     TC TYPE                                                                                                 ITMA         Accuracy: ( 0.075% Range + 0.25C [Conformity] + 0.50C [Ice Point])
                                                                                 TC TYPE                                                                                                     ERROR           at 23C after 20 min. warm-up, conforming to ITS-90.
                                                                            TC TYPE                                                                                                                       Note: TCConformity and Ice Point do not apply to mV input
                                                                        OPEN SEN UP/DN
                                                                   ICE PT DIS/EN
                                                               BASIC CAL
                                                          FIELD CAL
                                                      OUTPUT CAL

                                               RANGE                         TC TYPE                        UP           DOWN  OPEN SEN           ICE POINT

                                         0                             J                                                                    ENABLED
                                      1                            K                                                                     DISABLED
                                  2                             T
                               3                            E
                                                         MV

                                               9 10                          678                            1            0     5                      SWITCH
                                                                                                                                                  4
                                         00                            000
                                      01                           00 1                                                                     0
                                  10                            0 10                                                                     1
                               11                           0 11
                                                         111

                                                                                                                                                                                                    1
   Relative Humidity: Less than 85% RH (non-condensing)                              Ice Point Compensation
   Span: The input span can be set to a min. of 1/8 of the full scale range,            The Ice Point Compensation for the thermocouple sensors can be enabled (DIP

      anywhere within that range.                                                    Switch OFF) or disabled (DIP Switch ON). The mV sensor input is not affected
                                                                                     by this setting. Generally, the Ice Point Compensation is always enabled.
Thermocouple Accuracy for each type and the corresponding ranges:
                                                                                     Unit Malfunction
   TC    RANGE  DIP SWITCH   TEMPERATURE         RANGE    WIRE COLOR                    If the unit has scaling problems (output remains at -0.5 mA, 3.5 mA, or -0.5
(INPUT)                       & mV RANGE      ACCURACY   ANSI BS1843
                TYPE RANGE                                                           VDC nominal), check the ERROR LED on the front of the unit. An E2PROM
                6 7 8 9 10                                                           problem is indicated when the ERROR LED is on. If the ERROR LED is on,
                                                                                     perform a Basic Calibration followed by a Field Calibration. Turn the power off
         0 0 0 0 0 0 -136 to 111C 0.19C                                          for 5 seconds. Turn power on and check if the ERROR LED is on. If the LED
                                                                                     is on, contact the factory.
J        1 0 0 0 0 1 69 to 575C 0.38C White (+) Yellow (+)
         2 0 0 0 1 0 338 to 800C 0.35C Red (-) Blue (-)

         3 0 0 0 1 1 -149 to 862C 0.76C

         0 0 0 1 0 0 -200 to 541C 0.56C                                          EMC INSTALLATION GUIDELINES

K        1 0 0 1 0 1 427 to 1132C 0.53C Yellow (+) Brown (+)                     Although Red Lion Controls Products are designed with a high degree of
         2 0 0 1 1 0 648 to 1372C 0.54C Red (-) Blue (-)

         3 0 0 1 1 1 -192 to 1372C 1.17C                                         immunity to Electromagnetic Interference (EMI), proper installation and wiring

         0 0 1 0 0 0 -225 to 149C 0.28C                                          methods must be followed to ensure compatibility in each application. The type

         1 0 1 0 0 1 74 to 326C               0.19C   Blue (+) White (+)          of the electrical noise, source or coupling method into a unit may be different
         2 0 1 0 1 0 68 to 400C               0.25C   Red (-) Blue (-)
T                                                                                    for various installations. Cable length, routing, and shield termination are very

         3 0 1 0 1 1 -200 to 400C 0.45C                                          important and can mean the difference between a successful or troublesome

         0 0 1 1 0 0 -111 to 311C 0.32C                                          installation. Listed are some EMI guidelines for a successful installation in an

         1 0 1 1 0 1 276 to 609C 0.25C Violet (+) Brown (+)                      industrial environment.
         2 0 1 1 1 0 377 to 1000C 0.47C Red (-) Blue (-)
E                                                                                    1. A unit should be mounted in a metal enclosure, which is properly connected

         3 0 1 1 1 1 -114 to 1000C 0.84C                                         to protective earth.

         0 1 1 1 0 0 -9 to 6 mV 0.0113 mV                                          2. Use shielded cables for all Signal and Control inputs. The shield connection

         1      1 1 1 0 1 -9 to 22 mV 0.0233 mV                                    should be made as short as possible. The connection point for the shield
         2      1 1 1 1 0 -9 to 63 mV 0.0540 mV
mV                                                        N/A   N/A                  depends somewhat upon the application. Listed below are the recommended

         3 1 1 1 1 1 -9 to 77 mV 0.0645 mV                                         methods of connecting the shield, in order of their effectiveness.

                                                                                     a. Connect the shield to earth ground (protective earth) at one end where the

                Note: DIP switch settings ON = 1 OFF = 0                             unit is mounted.

Accuracy Example:            Range      Conformity  Ice Point   Total Error          b. Connect the shield to earth ground at both ends of the cable, usually when
Type "J" Range "0"                                              0.94C
                                                                                     the noise source frequency is over 1 MHz.
  -136C to 111C
                             ( 0.19C + 0.25C + 0.50C ) =                       3. Never run Signal or Control cables in the same conduit or raceway with AC

9. ENVIRONMENTAL CONDITIONS:                                                         power lines, conductors, feeding motors, solenoids, SCR controls, and
   Operating Temperature Range: -25C to 75C (-13F to 167F)
   Storage Temperature Range: -40 to 85C (-40F to 185F)                           heaters, etc. The cables should be run through metal conduit that is properly
   Operating and Storage Humidity: 85% max. relative humidity (non-
      condensing) from -25C to 75C.                                                grounded. This is especially useful in applications where cable runs are long
   Vibration to IEC 68-2-6: Operational 5-150 Hz, 2 g
   Shock to IEC 68-2-27: Operational 30 g                                            and portable two-way radios are used in close proximity or if the installation
   Altitude: Up to 2000 meters
                                                                                     is near a commercial radio transmitter. Also, Signal or Control cables within
10. MOUNTING: Universal mounting foot for attachment to standard DIN
   style mounting rails, including top hat (T) profile rail according to EN50022     an enclosure should be routed as far away as possible from contactors,
  -35 7.5 and -35 15, and G profile rail according to EN50035 - G32.
                                                                                     control relays, transformers, and other noisy components.
11. CONNECTION: Compression type terminal block
12. CONSTRUCTION: High impact black plastic case                                     4. Long cable runs are more susceptible to EMI pickup than short cable runs.
13. CERTIFICATIONS AND COMPLIANCES:
                                                                                     5. In extremely high EMI environments, the use of external EMI suppression
   CE Approved
      EN 61326-1 Immunity to Industrial Locations                                    devices such as Ferrite Suppression Cores for signal and control cables is
      Emission CISPR 11 Class B
      IEC/EN 61010-1                                                                 effective. The following EMI suppression devices (or equivalent) are
      RoHS Compliant
                                                                                     recommended:
   Refer to the EMC Installation Guidelines section of this bulletin for
      additional information.                                                        Fair-Rite part number 0443167251 (RLC part number FCOR0000)

14. WEIGHT: 4.02 oz. (114.0 g)                                                       Line Filters for input power cables:

                                                                                     Schaffner # FN2010-1/07 (Red Lion Controls # LFIL0000)

                                                                                     6. To protect relay contacts that control inductive loads and to minimize radiated

                                                                                     and conducted noise (EMI), some type of contact protection network is

                                                                                     normally installed across the load, the contacts or both. The most effective

                                                                                     location is across the load.

                                                                                     a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide

                                                                                     varistor (MOV) across an AC inductive load is very effective at reducing

                                                                                     EMI and increasing relay contact life.

                                                                                     b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor

                                BLOCK DIAGRAM                                        switch, care must be taken not to exceed the breakdown voltage of the

                3V                                                                   transistor when the load is switched. One of the most effective ways is to

                                                                                     place a diode across the inductive load. Most RLC products with solid

                22M                                                                  state outputs have internal zener diode protection. However external diode

            7           A/D                        PWM                               protection at the load is always a good design practice to limit EMI.
    +             CONVERTER                   CONTROL
TC                           PROCESS          CIRCUITRY                              Although the use of a snubber or varistor could be used.
    -            1.7V        CIRCUITRY
                                                                                     RLC part numbers: Snubber: SNUB0000
            8                 POWER
                             SUPPLY     22V              1 + CURRENT                                          Varistor: ILS11500 or ILS23000
   DC 10                                4V               3 - OUTPUT
POWER                                   3V     ANALOG                                7. Care should be taken when connecting input and output devices to the
                                        1.7V   OUTPUT    4 + VOLTAGE
            12                                CIRCUITRY  6 - OUTPUT                  instrument. When a separate input and output common is provided, they

                                                                                     should not be mixed. Therefore a sensor common should NOT be connected

                                                                                     to an output common. This would cause EMI on the sensitive input common,

                                                                                     which could affect the instrument's operation.

FUNCTION DESCRIPTIONS                                                                   Visit RLC's web site at http://www.redlion.net/Support/InstallationConsiderations.
                                                                                     html for more information on EMI guidelines, Safety and CE issues as they
Open Sensor Detection                                                                relate to Red Lion Controls products.
   The output can be set to go Upscale or Downscale for the detection of an

open sensor. The nominal values for each output range are listed under TC
Break Detection in the Specifications section. This setting is always active, so
changes to the setting are effective immediately.

                                                                                  2
WIRING CONNECTIONS                       MONITORING INSTRUMENT                      OUTPUT
                                                                                       Connect the output signal wires to the desired output terminals. For voltage
   All conductors should meet                    VOLTAGE METER
voltage and current ratings for each                        OR                      output, use terminals #4 and #6; for current output, use terminals #1 and #3
terminal. Also, cabling should                                                      observing proper polarity. Only one output may be used at a time. The unit is
conform to appropriate standards of             CURRENT METER                       factory set for a 4 to 20 mA output. The voltage output will track the current
good installation, local codes and                                                  output nominally within a 2.5% deviation range.
regulations. It is recommended that      I+ 1 2 3 I-
power supplied to the unit be                                                          To select 0 to 20 mA, output you must open the case and cut the wire jumper.
protected by a fuse or circuit                                                      The jumper is located to the left side of the board as shown in the drawing.
breaker. When wiring the unit, use
the numbers on the label to identify     V+ 4 5 6 V-
the position number with the proper
function. Strip the wire, leaving              POWER                                POWER
approximately 1/4" (6 mm) of bare                                                      Connect DC power to terminals #10 and #12 observing proper polarity. Be
wire exposed (stranded wire should    +  TC-   ERROR
be tinned with solder). Insert the    -   TC+  789                                  certain DC power is within the 9 to 32 VDC specifications.
wire into the terminal, and tighten
the screw until the wire is clamped      VDC+ 10 11 12 VDC-                         POWER LED
tightly.                                                                               The ITMA has a green LED located on the front to indicate that power is

                                                                                    applied to the unit.

                                                                                    DIP SWITCH SETTING DESCRIPTIONS

                                               POWER SUPPLY                         SWITCH    LABEL           DESCRIPTION
                                                9 to 32 VDC

                                                                                    1               OUTPUT CAL Output Calibration

INPUT, OUTPUT, AND POWER CONNECTIONS                                                2               FIELD CAL Field Calibration

INPUT                                                                               3               BASIC CAL Basic Calibration
   Ensure thermocouple wire ends are stripped and clean. Connect positive
                                                                                    4         ICE PT DIS/EN   Ice Point Compensation -
thermocouple lead to terminal #7 (TC+). Connect negative thermocouple lead                                    Disabled (ON) / Enabled (OFF)
to terminal #8 (TC-). If the thermocouple probe cannot be connected directly to
the module, thermocouple wire or thermocouple extension-grade wire must be          5         OPEN SEN UP/DN  Open Sensor Detection -
used to extend the connection (copper wire does not work). Always refer to the                                Upscale (ON) / Downscale (OFF)
thermocouple manufacturer's recommendations for: mounting, temperature
range, shielding, etc.                                                              6                         Thermocouple Type - 3 switch
                                                                                                              combination setting
            Remove this                                                             7               TC TYPE
            side of the
            unit case.                                                              8

                                                                                    9                RANGE    Sensor Range - 2 switch
                                                                                    10                        combination setting

                                                                                    TCType and Range switch settings (ON = 1 OFF = 0)

                                                                                         TC    DIP SWITCH     RANGE              DIP SWITCH
                                                                                        TYPE  678                                  9 10
                                                                                              000                0                 00
                                                                                          J   001                1                 01
                                                                                          K   010                2                 10
                                                                                          T   011                3                 11
                                                                                          E   111
                                                                                         mV

                                                                                    FACTORY SETTINGS
                                                                                       The unit is shipped from the factory calibrated for a 4 to 20 mA output using

                                                                                    a type J thermocouple in range 3. The ITMAshould be Field calibrated by the
                                                                                    operator for the application environment it will be used in. If the unit is not
                                                                                    recalibrated by the operator, the following table lists the temperature ranges for
                                                                                    the given thermocouple types.

                                                                                              NOMINAL FACTORY FIELD CALIBRATION

                                                                                              TYPE   RANGE    TEMPERATURE RANGE

                                                                                                J       3         -50C to 500C
                                                                                                K       3         -85C to 790C
                                                                                                T       3        -195C to 162C
                                                                                                E       3          3C to 602C

WIRE JUMPER                                                                         TROUBLESHOOTING

                                                                                       For further technical assistance, contact technical support at the appropriate

                                                                                    company numbers listed.

                                                                                 3
                                                              CALIBRATION PROCEDURES

1.0 Field Calibration

                                              VOLTAGE METER   Note: The nominal output value for the various output ranges are designated in the following order: (0 to 20 mA, 4
                                                          OR     to 20 mA, 0 to 10 VDC)
                                                                 Allow a 30 minute warm-up period before starting Field Calibration. Field Calibration scales the voltage or current
                                              CURRENT METER
                                                              output to a temperature or mV input. This procedure assigns an input value to analog output low and an input value
                                              I+ 1 2 3 I-     to analog output high. The microprocessor handles configuring the output so it is linear to the temperature or mV input.
                                                              The Field Calibration procedure is described below.

                                      V+ 4 5 6 V-             1 2 3 4 5 6 7 8 9 10      Note: The unit needs to have the Field Calibration completed by the operator before

                                              POWER                Step 1.3 & 1.4   ON  normal operation. To abort this calibration and reset to the previous settings, set

                 +                    TC-     ERROR           1 2 3 4 5 6 7 8 9 10      the FIELD CAL switch(#2) OFF prior to the final OFF setting of the OUTPUT
                 -                     TC+    789
THERMOCOUPLE                                                                            CAL switch (Step 1.13) and turn off power. Wait 5 seconds and then turn on power
   CALIBRATOR         +
                       -                                                                and the previous settings will be loaded.

                                      VDC+ 10 11 12 VDC-                            ON Field Calibration with a Thermocouple Calibrator

                                                                       Step 1.5         1.1 Enable the Ice Point Compensation on the Thermocouple Calibrator and set it to

                                           POWER SUPPLY       1 2 3 4 5 6 7 8 9 10         the Thermocouple type being used in your application.
                                             9 to 32 VDC
                                                                       Step 1.7         1.2 Connect the thermocouple wire as selected in step 1 to the TC input terminals of
                 Field Calibration Wiring
                                                              1 2 3 4 5 6 7 8 9 10              the ITMA and the thermocouple calibrator.
                                                                                    ON 1.3 Set the ICE PT EN/DIS switch (#4) OFF to enable Ice Point Compensation.
                                                                       Step 1.9
                                                                                        1.4 Set the Type and Range for the thermocouple or mV used in your application
                                                              1 2 3 4 5 6 7 8 9 10
                                                                                           (DIPswitches #6 through #10). (TC type "J", Range 0 shown)
                                                                       Step 1.11
                                                                                        1.5 Set the FIELD CAL switch (#2) ON. [Output goes to -0.8 mA, 3.5 mA, or -0.4 V
                                                              1 2 3 4 5 6 7 8 9 10
                                                                                    ON     nominal]
                                                                       Step 1.13
                                                                                        1.6 Apply the input signal for the analog output low value.
                                                              1 2 3 4 5 6 7 8 9 10
                                      MODEL ITMA                                        1.7 Set the OUTPUT CAL switch (#1) ON. [Output stays at -0.8 mA, 3.5 mA, or -0.4
                                                                       Step 1.14
                                                                                           V nominal]

I+ 1 2 3 I-                 10                RANGE                                        1.8 Adjust the input signal up until the output equals desired low value.
                                              RANGE                                 ON 1.9 Set the OUTPUT CAL switch (#1) OFF. [Output increases to 22.9 mA, 22.5 mA,
                               9
                                                    TYPE
V+ 4 5 6 V-                    8              TC
                                              TC TYPE
POWER                          7              OPEN SEN DN                                  or 11.5 V nominal]
                                              ICE PT DIS/EN
                               6              BASIC CAL
                                              FIELD CAL
          ERROR                    5          OUTPUT CAL                                1.10 Apply the input signal for the analog output high value.
TC+ 7 8 9               TC- 4
                                                                                        1.11 Set the OUTPUT CAL switch (#1) ON. [Output decreases to 21.1 mA, 20.7 mA,
                                   3

VDC+ 10 11 12 VDC-             2

                               1                                                    ON     or 10.6 V nominal]

9-32 VDC

                                                                                        1.12 Adjust the input signal down until the output equals desired high value.

                                      DIP SWITCH SETTINGS:                              1.13 Set the OUTPUT CAL switch (#1) OFF.

                                      ON = 1  OFF = 0                                   1.14 Set the FIELD CAL switch (#2) OFF.

                                                                                    ON 1.15 Disconnect the thermocouple calibrator from the ITMA and connect the actual
                                                                                                 sensor to be used in the application.

2.0 Field Calibration With an Accurate Adjustable Millivolt Source: (Alternate Method)

                                      VOLTAGE METER           1 2 3 4 5 6 7 8 9 10      Note: The nominal output value for the various output ranges are designated in the
                                                  OR
                                                                   Step 2.2 & 2.3       following order: (0 to 20 mA, 4 to 20 mA, 0 to 10 VDC)
                                      CURRENT METER
                                                                                    ON  This calibration procedure can be used to assign the high and low input values if a

                                                                                        thermocouple calibrator is not available.

                                      I+ 1 2 3 I-             1 2 3 4 5 6 7 8 9 10      Note: To abort this calibration and reset to the previous settings, set the FIELD CAL

                                      V+ 4 5 6 V-                      Step 2.4     ON  switch(#2) OFF prior to the final OFF setting of the OUTPUT CAL switch (Step

                                              POWER           1 2 3 4 5 6 7 8 9 10      2.12) and turn off power. Wait 5 seconds and then turn on power and the previous

                                                                       Step 2.6         settings will be loaded.

ADJUSTABLE                     TC-            ERROR           1 2 3 4 5 6 7 8 9 10         2.1 Connect the accurate Adjustable Millivolt Source to the TC input terminals.
  MILLIVOLT                     TC+           789                                   ON 2.2 Set the ICE PT EN/DIS switch (#4) ON to disable Ice Point Compensation.
   SOURCE                                                              Step 2.8
                                                                                           2.3 Set the Type and Range for the thermocouple or mV used in your application
                        VDC+ 10 11 12 VDC-                    1 2 3 4 5 6 7 8 9 10              (DIPswitches #6 through #10).(TC type "J", Range 0 shown)

                               POWER SUPPLY                           Step 2.10            2.4 Set the FIELD CAL switch (#2) ON.[Output goes to -0.8 mA, 3.5 mA, or -0.4 V
                                 9 to 32 VDC                                                    nominal]
                                                              1 2 3 4 5 6 7 8 9 10
          Field Calibration Wiring                                                  ON 2.5 Apply the input signal (mV equivalent for the thermocouple temperature) for the
                                                                      Step 2.12                 analog output low value.

                                                              1 2 3 4 5 6 7 8 9 10         2.6 Set the OUTPUT CAL switch (#1) ON. [Output stays at -0.8 mA, 3.5 mA, or -0.4
                                                                                                V nominal]
                                                                      Step 2.13
                                                                                    ON 2.7 Adjust the input signal up until the output equals desired low value.
                                                              1 2 3 4 5 6 7 8 9 10
                                                                                        2.8 Set the OUTPUT CAL switch (#1) OFF. [Output increases to 22.9 mA, 22.5 mA,
                                                                      Step 2.14
                                      MODEL ITMA                                           or 11.5 V nominal]

                                                                                    ON  2.9 Apply the input signal (millivolt equivalent for the thermocouple temperature) for

                        10                    RANGE                                        the analog output high value.
                                              RANGE
I+ 1 2 3 I-             9
                                                    TYPE
V+ 4 5 6 V-             8                     TC                                           2.10 Set the OUTPUT CAL switch (#1) ON. [Output decreases to 21.1 mA, 20.7 mA,
                                              TC TYPE                                           or 10.6 V nominal]
POWER                   7                     OPEN SEN DN
                                              ICE PT DIS/EN                         ON 2.11 Adjust the input signal down until the output equals desired high value.
                        6                     BASIC CAL
                                              FIELD CAL
          ERROR             5                 OUTPUT CAL
TC+ 7 8 9        TC- 4

                            3

VDC+ 10 11 12 VDC-      2

                        1

9-32 VDC                                                                                   2.12 Set the OUTPUT CAL switch (#1) OFF.
                                                                                           2.13 Set the FIELD CAL switch (#2) OFF.
                               DIP SWITCH SETTINGS:                                        2.14 Set the ICE PT EN/DIS switch (#4) OFF to enable Ice Point Compensation.
                                                                                    ON 2.15 Disconnect millivolt source from the ITMA and connect the actual sensor to be
                                      ON = 1  OFF = 0
                                                                                                 used in the application.

                                                                                        4
3.0 Ice Point Calibration

                                   VOLTAGE METER                                                     Note: The nominal output value for the various output ranges are designated in the
                                               OR                                                       following order: (0 to 20 mA, 4 to 20 mA, 0 to 10 VDC)
                                                                                                        The Ice Point Calibration should only be performed with an ambient temperature
                                   CURRENT METER
                                                                                                     between 21C and 29C. This Calibration was performed on the unit at the factory
                                   I+ 1 2 3 I-                          1 2 3 4 5 6 7 8 9 10         during the Basic Calibration and generally does not need to be done again. The Ice
                                                                                                     Point Compensation can be adjusted through this calibration. The Ice Point Calibration
                                   V+ 4 5 6 V-                                   Step 3.1     ON procedure is described below.

                                           POWER             PRECISION  1 2 3 4 5 6 7 8 9 10      Note: Calibration can be aborted by setting the BASIC CAL switch(#3) OFF prior to
                                           ERROR          THERMOMETER
ADJUSTABLE       +   TC-                   789                                                    the setting of the OUTPUT CAL switch OFF. (Step 3.6)
  MILLIVOLT      -    TC+
   SOURCE                                                                                         3.1 Connect a precision mV source with an accuracy of 0.02% to Terminal #7 TC+
                 +
                  -  VDC+ 10 11 12 VDC-                                                              Input and Terminal #8 TC- Input. Set the OUTPUT CAL switch (#1) and ICE PT

                                                                                                     EN/DIS switch (#4) OFF. Set the BASIC CAL (#3) and FIELD CAL (#2)

                                                                                                     switches ON. The positions of switches #5 thru #10 are not relevant for this

                      POWER SUPPLY                                                            ON     calibration procedure.
                        9 to 32 VDC
                                                                                 Step 3.5         3.2 Connect a precision thermometer (accuracy of 0.1C) to the unused terminal (#9)
Ice Point Calibration Wiring
                                                                        1 2 3 4 5 6 7 8 9 10         beside the TC Input terminals.

                                                                                                  3.3 Apply power and allow a 30 minute warm-up period. [Output goes to -0.9 mA,

                                                                                                          3.4 mA, or -0.5V nominal]
                                                                                              ON 3.4 Using the temperature indicated by the precision thermometer, input an equivalent

                                                                        Step 3.5                     1 mV/C signal to the TC Input terminals and wait 5 seconds.

                                                                        1 2 3 4 5 6 7 8 9 10         3.5 Set the OUTPUT CAL switch (#1) ON and then OFF.

                                                                                 Step 3.6     ON

                                                                                                     3.6 Set the BASIC CAL switch (#3) and FIELD CAL switch (#2) OFF. [Output
                                                                                                          increases to -0.8 mA, 3.5 mA, or -0.38 V nominal, or more]

4.0 Basic Calibration

                                   VOLTAGE METER                                                  Note: The nominal output value for the various output ranges are designated in the
                                               OR                                                    following order: (0 to 20 mA, 4 to 20 mA, 0 to 10 VDC)
                                                                                                     The Basic Calibration should only be performed with an ambient temperature
                                   CURRENT METER
                                                                                                  between 21C and 29C. The Basic Calibration was performed on the unit at the
                                   I+ 1 2 3 I-                                                    factory and generally does not need to be done again. This procedure initializes the
                                                                                                  unit by calibrating the input, and the Ice Point Compensation. The Basic Calibration
                                   V+ 4 5 6 V-                                                    should be performed only if a condition exists as described in the "Unit Malfunction"
                                                                                                  section. After completion of this calibration, the unit needs to be scaled in Field
                                                                                                  Calibration. The Basic Calibration procedure is described below.

                                           POWER             PRECISION  1 2 3 4 5 6 7 8 9 10      Note: To abort this calibration and reset to the previous settings, set the BASIC CAL
                                           ERROR          THERMOMETER
ADJUSTABLE           TC-                   789                                   Step 4.1     ON  switch(#3) OFF prior to the final setting of the OUTPUT CAL switch (Step 4.17)
  MILLIVOLT           TC+
   SOURCE                                                                                         and turn off power for 5 seconds. Then turn on power and the previous settings will

                                                                                                  be loaded.

                     VDC+ 10 11 12 VDC-                                                           4.1 Connect a precision mV source with an accuracy of 0.02% to Terminal #7 (TC+

                                                                                                     Input) and Terminal #8 (TC- Input). Set the ICE PT EN/DIS switch (#4),

                                                                                                     RANGE (#9 ), TYPE (#6, #7, and #8), OUTPUT CAL (#1), and FIELD

                             POWER SUPPLY                                                            CAL (#2) switches OFF. Set the BASIC CAL switch (#3) ON.
                               9 to 32 VDC
                                                                                                  4.2 Apply power and allow a 30 minute warm-up period. [Output goes to -0.9 mA,
          Basic Calibration Wiring
                                                                        1 2 3 4 5 6 7 8 9 10         3.4 mA, or -0.5 V nominal]
                                                                        1 2 3 4 5 6 7 8 9 10
                                                                                              ON 4.3 Set the OUTPUT CAL switch (#1) ON and then OFF.
                                                                           Steps 4.3 to 4.15         4.4 Input -9 mV and wait 5 seconds.
                                                                                                     4.5 Set the OUTPUT CAL switch (#1) ON and then OFF.
                                                                        1 2 3 4 5 6 7 8 9 10
                                                                                              ON 4.6 Input 6 mV and wait 5 seconds.
                                                                                Step 4.16            4.7 Set the OUTPUT CAL switch (#1) ON and then OFF.
                                                                                                     4.8 Input 22 mV and wait 5 seconds.
                                                                        1 2 3 4 5 6 7 8 9 10         4.9 Set the OUTPUT CAL switch (#1) ON and then OFF.
                                                                        1 2 3 4 5 6 7 8 9 10         4.10 Input 41mV and wait 5 seconds.
                                                                                                     4.11 Set the OUTPUT CAL switch (#1) ON and then OFF.
                                                                                Step 4.17
                                                                                              ON 4.12 Input 63 mV and wait 5 seconds.
                                                                        1 2 3 4 5 6 7 8 9 10         4.13 Set the OUTPUT CAL switch (#1) ON and then OFF.
                                                                                                     4.14 Input 77 mV and wait 5 seconds.
                                                                                Step 4.18            4.15 Set the OUTPUT CAL switch (#1) ON and then OFF.

                                   MODEL ITMA                                                     4.16 Ice Point Calibration.

                                                                                              ON     a. If ice point calibration is not desired, go to step 4.17.

I+ 1 2 3 I-          10                    RANGE                                                     b. To Enable ice point calibration, set the FIELD CAL switch (#2) ON.
                                           RANGE
                     9                                                                               1. Connect a precision thermometer (accuracy of 0.1C) to the unused
                                                 TYPE
V+ 4 5 6 V-          8                     TC
                                           TC TYPE
POWER                7                     OPEN SEN DN                                        ON
                                           ICE PT DIS/EN
                     6                     BASIC CAL                                                 terminal beside the TC Input terminals.
                                           FIELD CAL
          ERROR                 5          OUTPUT CAL                                                2. Allow 5 minutes for the temperature to equalize.
TC+ 7 8 9            TC- 4

                                3

VDC+ 10 11 12 VDC-   2                                                                               3. Using the temperature indicated by the precision thermometer, input an

                     1

9-32 VDC                                                                                             equivalent 1 mV/C signal to the TC Input terminals.

                                   DIP SWITCH SETTINGS:                                       ON 4.17 Set the OUTPUT CAL switch (#1) ON and then OFF.
                                                                                                     4.18 Set the BASIC CAL switch (#3) and FIELD CAL switch (#2) OFF. [Output
                                   ON = 1  OFF = 0                                                         increases to -0.8 mA, 3.5 mA, or -0.4 V nominal, or more]
                                                                                                     4.19 Perform a Field Calibration. (See Section 1.0)

                                                                                                  5
                                                   INSTALLATION

                The unit is equipped with a universal mounting foot for attachment to standard DIN style mounting rails,
             including G profile rail according to EN50035 - G32 , and top hat (T) profile rail according to EN50022 - 35 x 7.5
             and 35 x 15. The unit should be installed in a location that does not exceed the maximum operating temperature
             and provides good air circulation. Placing the unit near devices that generate excessive heat should be avoided.

                      G Rail Installation                                                           T Rail Installation

   To install the ITMA on                                                       To install the ITMA on a
a "G" style DIN rail,                                                        "T" style rail, angle the
angle the module so that                                                     module so that the top groove
the upper groove of the                                                      of the "foot" is located over
"foot" catches under the                                                     the lip of the top rail. Push
lip of the top rail. Push                                                    the module toward the rail
the module toward the                                                        until it snaps into place. To
rail until it snaps into                                                     remove a module from the
place. To remove a                                                           rail, insert a screwdriver into
module from the rail,                                                        the slot on the bottom of the
push up on the bottom of                                                     "foot", and pry upwards on
the module while pulling                                                     the module until it releases
out away from the rail.                                                      from the rail.

APPLICATION                                                                                   I+ 1 2 3 I-

The temperature of certain industrial plastics is critical for melt flow of                   V+ 4 5 6 V-

an injection molding process. Different plastic grades and the complexity

of the mold determine required temperatures for efficient material flow.                            POWER
The master control room monitors the temperature of the melt flow of
each injection mold machine. They will determine whether the operator        MELT FLOW              ERROR
                                                                             MONITORED
                                                                                                                                                                                 -TC-
                                                                                                                                                                                +
may start the process on his machine or override the injection molding                        TC+ 7 8 9
process. The injection molding machines are located throughout the plant,    +
                                                                             -
posing a thermocouple signal loss problem from long cable runs. The                           VDC+  10 11 12  VDC-
ITMADCpowered unit is mounted at the machine and uses the local 24
VDC for power. The signal loss problem is solved using the 4 to 20 mA            MACHINE'S                                                                                           MASTER
                                                                             POWER SUPPLY                                                                                           CONTROL

analog output for the long cable run to the master control room.                24VDC                                                                                                  ROOM

                                                                                        COMM

             ORDERING INFORMATION

             MODEL NO.                                    DESCRIPTION                         PART NUMBER
                ITMA                       Intelligent Thermocouple Module                      ITMA3035

                                                                             6
This page intentionally left blank

                              7
                                                        LIMITED WARRANTY

                          The Company warrants the products it manufactures against defects in materials and workmanship
                          for a period limited to two years from the date of shipment, provided the products have been stored,
                          handled, installed, and used under proper conditions. The Company's liability under this limited
                          warranty shall extend only to the repair or replacement of a defective product, at The Company's
                          option. The Company disclaims all liability for any affirmation, promise or representation with
                          respect to the products.

                          The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against
                          damages, claims, and expenses arising out of subsequent sales of RLC products or products
                          containing components manufactured by RLC and based upon personal injuries, deaths, property
                          damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be
                          to any extent liable, including without limitation penalties imposed by the Consumer Product Safety
                          Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty
                          Act (P.L. 93-637), as now in effect or as amended hereafter.

                          No warranties expressed or implied are created with respect to The Company's products except those
                          expressly contained herein. The Customer acknowledges the disclaimers and limitations contained
                          herein and relies on no other warranties or affirmations.

Red Lion Controls              Red Lion Controls            Red Lion Controls                                                                        Red Lion Controls
Headquarters                          Europe                         India                                                                                           China
20 Willow Springs Circle
York PA 17406                   Softwareweg 9       201-B, 2nd Floor, Park Centra                                                               Unit 302, XinAn Plaza
Tel +1 (717) 767-6511     NL - 3821 BN Amersfoort   Opp 32 Mile Stone, Sector-30                                                Building 13, No.99 Tianzhou Road
Fax +1 (717) 764-0839     Tel +31 (0) 334 723 225  Gurgaon-122002 Haryana, India
                          Fax +31 (0) 334 893 793                                                                                     ShangHai, P.R. China 200223
                                                         Tel +91 984 487 0503                                                                  Tel +86 21 6113 3688
                                                                                                                                              Fax +86 21 6113 3683
This datasheet has been downloaded from:
            datasheet.eeworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company