电子工程世界电子工程世界电子工程世界

产品描述

搜索
 

H7GP-T

器件型号:H7GP-T
器件类别:热门应用    机电/工控/自动化   
厂商名称:OMRON
厂商官网:https://www.omron.com
下载文档 在线购买

H7GP-T在线购买

供应商 器件名称 价格 最低购买 库存  
H7GP-T - 1 点击查看 点击购买

器件描述

Controllers 6-Dig Time totalizer Lt gray 100-240VAC

参数
产品属性属性值
Product AttributeAttribute Value
制造商:
Manufacturer:
Omron
产品种类:
Product Category:
Controllers
RoHS:YES
封装:
Packaging:
Bulk
系列:
Series:
H7GP
商标:
Brand:
Omron Automation and Safety
工厂包装数量:
Factory Pack Quantity:
1
零件号别名:
Part # Aliases:
H7GPT
单位重量:
Unit Weight:
2.645547 oz

H7GP-T器件文档内容

    Total Counter/Time Counter (DIN                                   48         x   24)

    H7GP

                                                                                                                   CSM_H7GP_DS_E_4_5

DIN 48 x 24-mm Total Counter/Time Counter

with Easy-to-read Displays and Water and

Oil Resistance Equivalent to IP66

• High-visibility, negative transmissive LCD display with 8.5-mm-

high characters and built-in red LED backlight at low power

consumption.

• IP66 with oil resistance and NEMA 4 protection achieved by

unifying the front with the case and by using oil-resistant parts

and materials.

• Compact (80 mm) body.                                                              For the most recent information on models that have been certified for

                                                                                     safety standards, refer to your OMRON website.

• Just change a switch setting for either an NPN or PNP input.

• Supports both external resetting and manual resetting.

• Finger-protection terminal block cover prevents electrical shock

and conforms to VDE0106, Part 100.

• Certified for UL and CSA safety standards.

• Complies with EMC standards (EN 61326) and CE Marking.

Model Number Structure

■ Model Number            Legend

H7GP-@@@

        1     2     3

1.  Classification                                                           3.  Case Color of Front Section

    C:  Total counter                                                            None: Light gray (Munsell 5Y7/1)

    T:  Time counter                                                             B:  Black

2.  Supply Voltage

    None: 100 to 240 VAC

    D:  12 to 24 VDC

Ordering Information

■ List of Models

Total counter

        Supply voltage                        6-digit  total counter

                                  Light  gray                         Black

100 to 240 VAC            H7GP-C                       H7GP-CB

12 to 24 VDC              H7GP-CD                      H7GP-CDB

Time counter

        Supply voltage                        6-digit  time counter

                                  Light  gray                         Black

100 to 240 VAC            H7GP-T                       H7GP-TB

12 to 24 VDC              H7GP-TD                      H7GP-TDB

                                                                                                                                                             1
                                                                                                                                       H7GP

Specifications

■ Ratings

            Item                               6-digit total counter                                    6-digit time counter

                                           H7GP-C                    H7GP-CD                    H7GP-T                 H7GP-TD

Rated supply voltage        100 to 240 VAC (50/60 Hz)    12 to 24 VDC (see note 1)     100 to 240 VAC (50/60 Hz)  12 to 24 VDC (see    note               1)

External power supply       50 mA at 12 VDC              ---                           50 mA at 12 VDC            ---

Operating voltage range     85% to 110% of rated supply voltage

Power consumption           100 to 240 VAC:        6.5 VA max.

                            12 to 24 VDC:          0.6 W max.

Dimensions                  48 x 24 x 80 mm (W x H x D)

Mounting method             Flush mounting

External connections        Screw terminals

Degree of protection        Panel surface: IP66 with oil resistance and NEMA Type 4 (indoors).

Display                     7-segment, negative transmissive LCD (with red backlight)

Digits                      6 digits (8.5-mm-high characters)

Input mode                  Up (increment)                                             Accumulative

Max. counting speeds        30 Hz or 5 kHz (selected via DIP switch)                   ---

Counting range              0 to 999999                                                ---

Time specification          ---                                                        0.1 to 99999.9 h/1 s to 99 h 59 min 59 s

                                                                                       (selected via DIP switch)

Timing accuracy             ---                                                        ±100 ppm (–10°C to 55°C)

Memory backup               EEP-ROM (overwrites: 200,000 times min.) that can store data for 20 years min.

Input       Input signals   Count, reset, and key protection (see note 2)              Start, reset, and key protection (see note 2)

            Input method    No-voltage input (NPN transistor input) or voltage input (PNP transistor input) (selected via DIP switch)

            Count, reset,   No-voltage input (NPN transistor input)

            start                Short-circuit (ON) impedance:       1 kΩ max.

                                 Short-circuit (ON) residual voltage:2 VDC max.

                                 Open (OFF) impedance:               100 kΩ min.

                            Voltage input (PNP transistor input)

                                 Short-circuit (ON) impedance:       1 kΩ max.

                                 ON voltage:                         9 to 24 VDC

                                 OFF voltage:                        5 VDC max.

                                 Open (OFF) impedance:               100 kΩ min.

            Key protection  No-voltage input (NPN transistor input)

                                 Short-circuit (ON) impedance:       1 kΩ max.

                                 Short-circuit (ON) residual voltage:0.5 VDC max.

                                 Open (OFF) impedance:               100 kΩ min.

Input re-   Reset           20 or 1 ms (automatically switched according to counting   20 ms

sponse                      speed)

speed       Start           ---                                                        20 ms

            Key protection  Approx. 1 s                                                Approx. 1 s

Reset system                External and manual resets

Note: 1.   Contains 20% ripple (p-p) max.

       2.  Only a non-voltage input (NPN transistor) is possible for the key protection input. The key protection input will be a non-voltage input even

           if the NPN/PNP input mode is set to PNP. Key protection is used to prohibit operating the Reset Key. The reset input terminals will still be

           functional.

                                                                                                                                                              2
                                                                                                                                        H7GP

■ Characteristics

Insulation resistance      100 MΩ min. (at 500 VDC)

Dielectric strength        2,000 VAC, 50/60 Hz for 1 min between current-carrying terminal and exposed non-current-carrying metal parts

                           (AC model)

                           1,000 VAC, 50/60 Hz for 1 min between current-carrying terminal and exposed non-current-carrying metal parts

                           (DC model)

                           2,000 VAC, 50/60 Hz for 1 min between power terminals and control input terminals (AC model)

Impulse withstand voltage  3 kV (between power terminals) (1 kV for 12-to-24-VDC models)

                           4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) (1.5 kV for 12-to-24-VDC

                           models)

Noise immunity             ±1.5 kV (between AC power terminals), ±480 V (between DC power terminals),

                           ±480 V (between input terminals);

                           square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)

Static immunity            Display:         Malfunction:8 kV

                                            Destruction:15 kV

                           DIP switch: Malfunction:4 kV

                                            Destruction:8 kV

Vibration resistance       Destruction: 10 to 55 Hz with 0.75-mm single amplitude, 2 hours each in three directions

                           Malfunction: 10 to 55 Hz with 0.5-mm single amplitude, 10 minutes each in three directions

Shock resistance           Destruction: 294 m/s2 each in three directions

                           Malfunction: 196 m/s2 each in three directions

Ambient temperature        Operating: –10°C to 55°C (with no icing)

                           Storage:    –25°C to 65°C (with no icing)

Ambient humidity           Operating: 35% to 85%

EMC                        (EMI)                                  EN61326-1 (note 1.)

                           Emission  Enclosure:                   EN55011 Group 1 class A

                           Emission  AC Mains:                    EN55011 Group 1 class A

                           (EMS)                                  EN61326-1 (note 1.)

                           Immunity  ESD:                         EN61000-4-2:  4 kV contact discharge (level 2)

                                                                                8 kV air discharge (level 3)

                           Immunity  RF-interference:             EN61000-4-3:  10 V/m (Amplitude-modulated, 80 MHz to 1 GHz) (level 3);

                                                                                10 V/m (Pulse-modulated, 900 MHz ±5 MHz) (level 3)

                           Immunity  Conducted Disturbance:       EN61000-4-6:  10 V (0.15 to 80 MHz) (according to EN61000-6-2)

                           Immunity  Burst:                       EN61000-4-4:  2 kV power-line (level 3);

                                                                                2 kV I/O signal-line (level 4)

                           Immunity  Surge:                       EN61000-4-5:  1 kV line to lines (power and output lines) (level 2);

                                                                                2 kV line to ground (power and output lines) (level 3)

                           Immunity  Voltage Dip/Interruption:    EN61000-4-11: 0.5 cycle, 100% (rated voltage)

Approved standards         UL508 (note 2), CSA C22.2 No.14 (note 2), conforms to EN61010-1, VDE0106/P100

Case color                 Rear section: Gray smoke; Front section: 5Y7/1 (light gray) or N1.5 (black)

Weight                     Approx. 75 g

Note: 1.  Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)

     2.   UL508 and CAN/CSA-C22.2 No.14 certification conditions

          • Power supply 100 to 240VAC types

            Ambient temperature 30°C Single mounting

          • Power supply 12 to 24VDC types

            Ambient temperature 40°C Single mounting

                                                                                                                                              3
                                                                                                                  H7GP

Connections

■ Terminal Arrangement

Note: Non-contact input is also available.

AC Models

H7GP-C                                                H7GP-T

                             External power supply                                         External power supply

         100 to 240 VAC      12 VDC 50 mA max.                        100 to 240 VAC       12 VDC 50 mA max.

        Power   Power     0V                12 VDC             Power            Power   0V      12 VDC

        supply  supply                                         supply           supply

        5       6         7                 8                         5         6       7       8

        1       2         3                 4                         1         2       3       4

Key protection  Reset     Count             Unused             Key protection   Reset   Count   Unused

input           input     input                                input            input   input

                                            NPN mode                                            NPN mode

                                            PNP mode                                            PNP mode

DC Models

H7GP-CD                                               H7GP-TD

            12 to 24 VDC                                                 12 to  24 VDC

        0V      Power     Unused            Unused             0V               Power   Unused  Unused

                supply                                                          supply

        5       6         7                 8                         5         6       7       8

        1       2         3                 4                         1         2       3       4

Key protection  Reset     Count             Unused             Key protection   Reset   Start   Unused

input           input     input                                input            input   input

NPN mode                                    PNP mode           NPN mode                         PNP mode

                                                                                                                        4
                                                                                                                                               H7GP

Operation

■ DIP Switch Settings

Set all DIP switches before mounting the Counter to a control panel.      H7GP-T/-TD

All switches are set toward the display panel before shipping.

                                                                                           Switch               Item           Function

H7GP-C/-CD                                                                         3 (On right side     Input mode      Display side        NPN

         Switch         Item             Function                                  from front)          (note 1)        Terminal side       PNP

3 (On right side    Input mode (note     Display side           NPN                4 (On left side      Time range      Display side        99999.9h

from front)         1)                   Terminal side          PNP                from front)          (note 1)                            (note 2)

4 (On left side     Counting speed       Display side           30 Hz                                                   Terminal side       99 h 59 min

from front)         (note 1)                                                                                                                59 s

                                         Terminal side          5 kHz

                                                                          Note: 1.             When the setting has been changed, turned power off and

                                                                                               on to continue. The display will show “0” when the power is

                                                                                               turned back on.

                                                                                           2.  The decimal point will flash every second when “99999.9 h”

                                                                                               is set.

■ Operating Modes

Total Counters                                                            Time Counters

Reset input                                                               Reset input

Count input                                                               Start input

999999                                                                    99999.9 h

                                                                          (see note)

Display                                                                   Display

         0                                                                         0.0h

Note: The count value will return to "0" when "999999" is                 Note: Display values are shown for full scale set to 99999.9 h.

         exceeded.                                                                 The count value will return to "0" when "99999.9" is

         The display and output are turned OFF when the power                      exceeded.

         supply turns OFF, but the count value is stored internally.               The display and output are turned OFF when the power

                                                                                   supply turns OFF, but the count value is stored internally.

Nomenclature

         4

                                                                                       1.  Reset Key

                                                                                           Resets the count value, but will not operate while

                                                                                           the keys are protected.

                                                                                       2.  Key Protection Indicator

         2                                                                                 Lit while the keys are protected. (Reset Key is

                                                                       3                   disabled.).

                                                                                       3.  NPN/PNP DIP Switch

                                                                                           (Count or start with reset)

                                                                                           When the setting has been changed, turned power

                                                                                           off and on to continue. The display will show "0"

                                                                                           when the power is turned back on. See below for

                                                                                           details.

                                      1                                                4.  Counting Speed DIP Switch (H7GP-C)

                                                                                           Time Range DIP Switch (H7GP-T)

                                                                                           When the setting has been changed, turned power

                                                                                           off and on to continue. The display will show "0"

                                                                                           when the power is turned back on. Refer to DIP

                                                                                           Switch Setting for details.

                                                                                                                                                            5
                                                                                                                                                 H7GP

Dimensions

Note: All units are in millimeters unless  otherwise  indicated.

H7GP-C

H7GP-T

                                                                                                    Panel Cutouts

                                                      M3.5 terminal screw                           Panel cutouts are as shown below

                                                                                                    (according to DIN43700).

                                                                                                                      50 min.

                                                                                                                      5.0 min.

                                                                                                            45  +0.6            45  +0.6

                                                                                                                0                   0

                                                                                                22.2  +0.3                                         22.2  +0.3

                                                                                                      0                                                  0

                                                                  Terminal  cover (provided)

                                                                                                    Note: 1. The mounting panel thickness should

                                                                                                            be 1 to 6 mm.

                                                                                                            2. Water resistance will be lost if

                                                                                                            Counters are mounted side-by-side.

                                                                                                            3. The terminal screws are M3.5.

                                                                                                            (Theeffective thread length is 6 mm.)

                                                                                                            4. When horizontally mounting Counters

                                                                                                            side-by-side, leave at least 50 mm

With Flush Mounting Bracket                                                                                 between any two Counters.

                                           Y92S-32 rubber         Panel     Y92F-32 flush mounting

                                           packing (provided)               adaptor (provided)

        ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

        To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

            In the interest of product improvement, specifications are subject to change without notice.

                                                                                                                                                               6
                                                     Terms and Conditions Agreement

Read and understand this catalog.

Please read and understand this catalog before purchasing the products.                 Please consult your OMRON representative if you

have any questions or comments.

Warranties.

(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship

for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron

disclaims all other warranties, express or implied.

(b)  Limitations.      OMRON    MAKES           NO   WARRANTY          OR   REPRESENTATION,         EXPRESS             OR   IMPLIED,      ABOUT

NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER

ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE

PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.

Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the

Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at

Omron’s     election,  to  (i)  replace    (in  the  form  originally  shipped    with  Buyer  responsible  for  labor  charges  for  removal            or

replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount

equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,

repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products

were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate

modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall

not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or

electronic   components,        circuits,  system    assemblies  or    any  other  materials   or   substances   or  environments.    Any  advice,

recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above

warranty.

See http://www.omron.com/global/           or contact your Omron representative for published information.

Limitation on Liability; Etc.

OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,

LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,

WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.

Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.

Suitability of Use.

Omron     Companies    shall    not  be    responsible     for  conformity  with  any   standards,  codes   or  regulations  which  apply  to            the

combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable

third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself

is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,

system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product

with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.

NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE

QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,

AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE

OVERALL EQUIPMENT OR SYSTEM.

Programmable Products.

Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence

thereof.

Performance Data.

Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining

suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate

it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.

Change in Specifications.

Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our

practice to change part numbers when published ratings or features are changed, or when significant construction changes are

made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers

may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at

any time to confirm actual specifications of purchased Product.

Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.

                                                                                                                                           2016.7

                                                           In the interest of product improvement, specifications are subject to change without notice.

OMRON Corporation

Industrial Automation Company

http://www.ia.omron.com/                                                                       (c)Copyright OMRON Corporation 2016 All Right Reserved.
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle      Information:

Omron:

H7GP-CDB  H7GP-TDB      H7GP-TB  H7GP-CB  H7GP-CD  H7GP-TD  H7GP-T  H7GP-C
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

器件索引   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
搜索索引   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号 Copyright © 2005-2021 EEWORLD.com.cn, Inc. All rights reserved