Multifunction Digital Timer                                                                                      H5AN

Quartz Timer Offers Eight Time

Ranges, Seven Output Operations

s  Field-selectable time ranges from 0.01

   second to 9999 hours

s  Selectable elapsed time (UP) and

   time remaining (DOWN) display

s  Contact and solid-state outputs available

   simultaneously

s  ON-delay with sustained and adjustable

   one-shot outputs, with and without

   continued timing

s  Built-in DC power supply for input devices

s  Easy-to-read 8 mm-high LED display

s  10-year battery memory back-up available

s  Draw-out construction allows setting,

   servicing without disconnecting wiring

s  Panel mounting hardware included

Ordering Information

s  TIMERS

Add the supply voltage to the part number when you order.  For example,  H5AN-4DM-AC100-240.

   Timing functions     ON-delay and ON-delay with one-shot

   Contact type         SPDT relay and open collector transistor         outputs, both available simultaneously

   Terminal form        14  terminal screws on rear of case

   DC power supply for  Provided                                         Provided

   external components

   Memory back-up       Not provided                                     Provided, 10-year built-in battery

   Part number          H5AN-4D                                          H5AN-4DM

Supply   AC             100 to 240 V; 50/60 Hz                           100 to 240 V; 50/60 Hz

voltage  DC             12 to 24 V, 48 V or 100 V                        12 to 24 V

s  REPLACEMENT PARTS

   Description                                                                                Part number

   Plastic front cover                                                                        H5AN COVER         0377762-0

   Mounting bracket (one pair supplied with each timer); order two                            Y92H-5
H5AN                                                                                                                        H5AN

Specifications

Part number                           H5AN-4D                                           H5AN-4DM

Supply                 AC             100 to 240 V; 50/60 Hz                            100 to 240 V; 50/60 Hz

voltage                DC             12 to 24 V, 48 V or 100 V                         12 to 24 V

                                      (permissible ripple factor:  20% max.)            (permissible ripple factor:     20% max.)

Operating voltage                     85 to 100% of rated voltage

Power                  AC             10 VA at 240 VAC, 50 Hz

consumption            DC             5 W at 24 VDC

Internal power supply                 12 VDC ±10%, 80 mA

for external components               (permissible ripple factor:  5% max.)

Timing functions                      ON-delay and ON-delay with one-slot

Reset and Gate inputs                 No-voltage

Control     Type       Time limit     SPDT relay and open collector solid-state output

output                 Instantaneous  –

            Max. load                 3 A, 250 VAC (p.f. = 1) for relay; 100 mA max., 30 VDC for open collector output

            Min. load                 10 mA, 5 VDC

Repeat accuracy                       ±0.01% ±0.05 sec max. (power-OFF start); ±0.005% ±0.03 sec max. (reset start)

Setting error                         See "Repeat Accuracy"

Resetting system                      Power-OFF, manual or external                     Manual or external

Resetting time                        Power-OFF:    0.5 sec min.; External:   0.02 sec signal minimum

Indicators                            Time Up (red LED), Reset Input (red LED); 8 mm LED numeric display

Materials                             Plastic

Mounting                              Panel; two mounting brackets included

Connections                           Back-mounted screw terminals

Weight                                360 g (12.7 oz.)

Approvals                             UL/CSA/SEV

Operating ambient temperature         -10° to 55°C (14° to 131°F)

Humidity                              35 to 85% RH

Vibration   Mechanical durability     10 to 55 Hz; 0.75 mm (0.03 in) double amplitude

            Malfunction durability    10 to 55 Hz; 0.5 mm (0.02 in) double amplitude

Shock       Mechanical durability     30 G

            Malfunction durability    10 G

Variation due to voltage change       See "Repeat Accuracy"

Variation due to temperature change   See "Repeat Accuracy"

Insulation resistance                 100 MΩ min. at 500 VDC

Dielectric strength                   2,000 VAC, 50/60 Hz for 1 minute between current-carrying terminals and non-current-

                                      carrying metal parts

                                      750 VAC, 50/60 Hz for 1 minute between non-continuous contacts

Service life           Mechanical     10 million operations minimum

                       Electrical     100,000 operations minimum at maximum rating

                                                                   2
H5AN                                                                                                                                      H5AN

Engineering Data

s      ELECTRICAL SERVICE LIFE

Timing Charts

s      ELAPSED TIME (UP) DISPLAY

Power                    1-2       ON

                                   OFF

Reset                    8-9       ON

input                              OFF

                                   ON                      Interruption

Gate                   8 - 10

input                              OFF

Time setting

Digital display

                                                                                                      (See       note)

Control  Relay   4 - 5,  4-6       ON

output   Solid-state     12-13-14  OFF

                                                                                                      (See       note)

                                   ON

Time up indicator                  OFF

                                   ON

Reset input indicator              OFF

                                   NOTE:  After the   set time has elapsed,     operation  continues  according  to the  mode  selected.

s      TIME      REMAINING (DOWN)                     DISPLAY

Power                    1-2       ON

                                   OFF

Reset                    8-9       ON

input                              OFF

Gate                   8 - 10      ON                      Interruption

input                              OFF

Time setting

Digital display

                                   ON                                                                 (See note)

Control  Relay   4 - 5,  4-6

output   Solid-state     12-13-14  OFF

                                   ON                                                                 (See note)

Time up indicator                  OFF

                                   ON

Reset input indicator              OFF

                                   NOTE:  After  the  set  time  has  elapsed,  operation  continues  according to the   mode  selected.

                                                                                           3
H5AN                                                                                                                               H5AN

s  OPERATION  MODES

   Mode                            Elapsed time (UP) display                       Time remaining (DOWN) display

   N          Reset                                                                    Reset

   Sustained

   output     Set value                                                                Set value

              Digital display                                                          Digital display

              Control output                                                           Control output

              The display increments from zero to the preset.  When         The display decrements from the preset to zero.        When

              the preset is reached, the output is energized.  The          zero is reached, the output is energized.  Zeros are

              preset is display until the timer is reset.                   displayed until the timer is reset.

   F          Reset                                                                    Reset

   Sustained

   Output     Set value                                                                Set value

              Digital display                                                          Digital display

              Control output                                                           Control output

              The display increments from zero to the preset.  When         The display decrements from the preset to zero.          When

              the preset is reached, the output is energized.  The          zero is reached, the output is energized.  The display

              display will continue to increment until the timer is reset.  will continue to decrement until the timer is reset.

   C          Reset                                                                    Reset

   One-shot

   Output     Set value                                                                Set value

              Digital display                                                          Digital display

              Control output                                                           Control output

              The display increments from zero to the preset.  When         The display decrements from the preset to zero.        When

              the preset is reached, the timer restarts its timing from     zero is reached, the timer restarts its timing from the

              zero and energizes a one-shot output.        The cycle is     preset and energizes a one-shot output.    The cycle is

              repeated until the timer is reset.                            repeated until the timer is reset.

   R          Reset                                                                    Reset

   One-shot

   Output     Set value                                                                Set value

              Digital display                                                          Digital display

              Control output                                                           Control output

              The display increments from zero to the preset.  When         The display decrements from the preset to zero.        When

              the preset is reached, the output is energized for the        zero is reached, the output is energized for the one-shot

              one-shot time.   Timing from zero is restarted at the         time.  Timing from the preset is restarted at the trailing

              trailing edge of the output.  The cycle is repeated until     edge of the output.         The cycle is repeated until the timer

              the timer is reset.                                           is reset.

   K          Reset                                                                    Reset

   One-shot

   Output     Set value                                                                Set value

              Digital display                                                          Digital display

              Control output                                                           Control output

              The display increments from zero to the preset.  When         The display decrements from the preset to zero.        When

              the preset is reached, the output is energized for the        zero is reached, the output is energized for the one-shot

              one-shot time.   The display continues to increment until     time.  The display continues to decrement until the timer

              the timer is reset.                                           is reset.

NOTE:  In modes F and K, when the 99 min 59 s or 99 h 59 min ranges are     selected in DOWN display, the overflow values will be

       shown as 9959, 9958, 9957, etc.

       In C mode, the set time should be longer than the one-shot time.

                                                               4
H5AN                                                                                                                            H5AN

OPERATION         MODES (continued)

Mode                               Elapsed time  (UP)  display                             Time remaining (DOWN) display

P                 Reset                                                                    Reset

One-shot

output            Set value                                                                Set value

                  Digital display                                                          Digital display

                  Control output                                                           Control output

                  The display increments from zero to the preset.        When  The display decrements from the preset to zero.  When

                  the preset is reached, the output is energized for the       zero is reached, the output is energized for the one-shot

                  one-shot time.   The timer restarts its timing, but the      time.       The timer restarts its timing, but the display is not

                  display is not updated until the one-shot time is up.        updated until the one-shot time is up.         The cycle is

                  The cycle is repeated.                                       repeated.

Q                 Reset                                                                    Reset

One-shot

Output            Set value                                                                Set value

                  Digital display                                                          Digital display

                  Control output                                                           Control output

                  The display increments from zero to the preset.        When  The display decrements from the preset to zero.              When

                  the preset is reached, the output is energized for the       zero is reached, the output is energized for the one-shot

                  one-shot time.   The display continues incrementing          time.       The display continues decrementing during the

                  during the one-shot, but restarts from zero when the         one-shot, but restarts from the preset when the one-shot

                  one-shot time is up.     The cycle is repeated.              time is up.            The cycle is repeated.

NOTE:   In mode Q, when the 99 min 59 s or 99 h 59 min ranges are selected in DOWN display, the overflow values will be shown as

        9959, 9958, 9957, etc.

        In P mode, the set time should be longer than the one-shot time.

Dimensions

Unit:  mm (inch)

                                                                                           Two mounting

                                                                                           brackets

                                                                                                            M3.5 terminal

                                                                                                            screws

                                   72                                                                       67.6

                                   (2.83)                                                                   (2.66)

                                                 72                            115 (4.53)

                                           (2.83)

                                                                               130 (5.12)

Panel cutout                                           Panel cutout for side-by-side

                                                       mounting for two units

                                                       NOTE:       Recommended panel thickness is 1 to   5  mm.

                                                                   Panel cutout conforms to DIN 43700.

                                                                         5
H5AN                                                                                                                             H5AN

Connections

Input terminal number (no-voltage only)

COM               Reset     Gate                                           0  VDC

                                                                              –

   8              9            10

Power supply terminal numbers

AC (common), DC-         AC (hot), DC+      Ground

          1                        2             3                                 –      +

Output terminal numbers

                                                                        Power supply for externally  connected  equipment

Contact

COM                      NO                   NC                           Voltage supply            DC-           DC+

   4                     5                    6                            12 VDC, 80 mA                  8        11

Solid-state

COM                      Load           Surge absorber

   12                    13             14

s     POWER SUPPLY CONNECTION

                                                        AC power supply                              DC power supply

Connect the required supply voltage to terminals

1 and 2.  In environments with external noise,

connect ground terminal 3 at a resistance of less

than 100Ω.

                                                                                                             12 to 24 VAC,

                                                        24 VAC or                                            (48 VDC or 100 VDC

                                                        100 to 240 VAC,       50/60   Hz                     for H5AN-4DM only)

s     LOAD CONNECTION

Terminals 4, 5 and 6 are for contact output.            Contact output                       Solid-state  output

Terminals 12 and 13 are for solid-state output.

Terminal 14 is a surge absorber for use when

an inductive load is connected.

Load Operation

                  Start        Time up

Timing operation                                                        –

        Load 1                                                          +

                                                                                             High and low output levels

        Load 2                                                                               are selected by internal switch.

                                                                                             See "Operations" section for

        H→L                                                                                  setting information.

        setting

Load 3  L→H

        setting

                                                        6
H5AN                                                                                                                        H5AN

s  RESET AND GATE INPUTS

Reset input                                   Gate input

Use a no-voltage contact or open              Use a no-voltage contact or open

collector type transistor between             collector type transistor between

terminals 8 and 9.  The timer resets          terminals 8 and 10.     The timer stops

when contact is made or when the              when the contact     makes or when

transistor is ON.                             the transistor is ON.   When the gate

                                              signal opens, timing resumes at the

                                              point of interruption.  Use a contact

                                              with minimum contact bounce (chatter),

                                              otherwise the bounce time will cause

                                              an error in the timer's operating time.

Input signal requirements

Contact input

Resistance                1 kΩ max.

Residual voltage          1 V max. when the contact makes

Contact material          Gold-plated contacts recommended

Solid-state input

Input type                                    Open collector transistor

Voltage when collector is OFF                 20 V min.

Saturated voltage when transistor is ON       3 V max.

Collector current                             50 mA min.

Input current between collector and base      0.5 µA max.

Solid-state inputs (NPN)

When connecting a solid-state circuit not of  current that flows from either terminal 9 or

the open collector type to the gate or reset  10 is approximately 10 mA).         Moreover, it is

inputs as shown in the figure below, the      essential that the circuit be ON for gate or

voltage of the solid-state circuit (+ V)      reset input, and OFF when there is no input.

should be 13 to 30 V, and the VCE(S) of the

transistor should be less than 3 V (the

s  POWER SUPPLY FOR EXTERNALLY-CONNECTED COMPONENTS

The H5AN has a built-in power supply for                   Gate or Reset input                     Solid-state output load

externally connected components such as

sensors for gate or reset input, or loads

connected to the solid-state control output

(12 VDC, 80 mA).

Power can be applied to the sensors and

loads simultaneously.

                                                                      7
H5AN                                                                                                                           H5AN

s  SIMULTANEOUS INPUT TO SEVERAL                          H5AN         TIMERS

A single contact or open collector type transistor

can be used to apply the gate or reset input to

two or more H5AN timers.  Caution is required

because a large current flows into the transistor.

The current that flows from H5AN is approximately

10 mA per unit.

Operation

s  NOMENCLATURE                                     7-segment LED display

                                                                                           Time-up indicator

                                                                                      Reset input indicator

                 Front cover                                                               Pushbutton switch for manual reset

                                                                                           Maintenance access screw

                                                                                      One-Shot time adjustment screw

                                                                                      (0.1 to 1 sec range)

                                                    Time  range decal

s  ACCESS TO SELECTOR         SWITCHES

                                                          Open the front cover.

                                                          Use a Phillips screwdriver

                                                          to gain access to internal

                                                          parts.       As the maintenance

                                                          access screw is turned, the

                                                          internal mechanism draws

                                                          out.  Pull out the timer from

                                                          its case to set internal

                                                          switches to desired settings.

                                                                           8
H5AN                                                                                                                                                      H5AN

s  PROGRAMMING H5AN SPECIFICATIONS

Internal selector switches are used for programming

elapsed time (UP) or time remaining (DOWN) display,

time range, operation mode and solid-state output level.

                                                                                                                        Operation mode selector

Manual reset (front  panel)

enable switch                                                        Solid-state output                                 Switch    Operation

                                                                     level selector switch                              position  Mode          Display mode

                                                                     Changed "low" to "high" when time is up            0         N

                                                                     Changed "high" to "low" when time is up            1         F

                                                                     Time range selector settings                       2         C             Time remaining

                                                                                                                        3         R             (DOWN) display

                                                                     Switch                                             4         K

                                                                     position               Time range                  5         P

                                                                     0                      0.01 to 99.99 s             6         Q

                                                                     1                      0.1 to 999.9 s              7         (same as 0)

                                                                     2                      1 to 9999 s                 8         N

                                                                     3                      1 s to 99 min 59 s          9         F

                                                                     4                      0.1 to 999.9 min            A         C             Elapsed time

                                                                     5                      1 min to 99 h 59 min        B         R             (UP) display

                     Time range                     Operation mode   6                      0.1 to 999.9 h              C         K

                     selection switch               selector switch  7                      1 to 9999 h                 D         P

                                                                     8                      same as "0"                 E         Q

                                                                     9                      same as "1"                 F         (same as 8)

s  SETTING TIME PRESET

Use the four pushwheel switches on the front                         Undesirable setting                                Warning

panel to set the desired time.         The H5AN timer                                                                   Do not set all four digits to

does not display the decimal point in ranges for                                                                        zero.   This causes a momentary

99.99 sec, 999.9 sec, 999.9 min or 999.9 hr.                                                                            output to occur that may lead to

Firmly push the switches to avoid having two                                                                  5 min     accidental injury or damage.

numbers appear in the display window.               This                                                     30 second

causes the operating time to drift widely.

In the 99 hr 59 min and 99 min 59 sec                                                    59 second                                                     00 h 00 min

ranges, the second digit from the right                                                  99 min                                                        (Momentary

cannot be more than 5.           Even if the digit                                                                                                     output)

is set to 6, 7, 8 or 9, the setting will be

interpreted as 5.

                                                                                                                                        59 min

                                                                                                                                        99 h

        9      9     7         9

                     ↑

               Any digit higher

               than 5 will be

               interpreted as 5.

s  SETTING ONE-SHOT TIME

Output modes C, R, K, P and Q provide a one-

shot output.   Be sure to set the one-shot value,

between 0.1 and 1 second, using the poten-

tiometer in the lower right corner of the front

panel.

                                                                                         9
H5AN                                                                                                                                    H5AN

s  PROGRAMMING CONSIDERATIONS FOR TIMERS WITH MEMORY PROTECTION

For units with memory protection,   it is         in accordance with the previous data.  Also

necessary to reset (either externally or          reset the timer after any changes are made

manually) the timer at the time the power is      to the internal switches.

applied.  If the timer is not reset, it operates

s  RECOVERY FROM A POWER FAILURE

H5AN-4D                                                                                        H5AN-4DM

The duration of the power failure determines how the                                           This timer has a battery backed memory to

timer acts when power is restored.                                                             protect settings against power failure.

                                                                                               When a power failure occurs, the timing

With a power failure of less than 0.01 second duration,                                        operation is interrupted.  When power

the timer resumes timing from the point of interruption                                        returns, the timer continues from the point

upon recovering power.                                                                         of interruption.

Length of power failure            Action when power is restored                               The back-up battery will retain data for up

                                                                                               to 10 years.  However, the battery may not

0.01 sec or less                   Timer resumes timing and does not reset                     be replaced.

0.01 sec to 0.5 sec                Timer either resets or resumes timing

0.5 sec or more                    Timer resets

          NOTE: DIMENSIONS ARE             SHOWN  IN MILLIMETERS. To convert millimeters to                  inches divide by 25.4.

OMRON ELECTRONICS LLC                                    OMRON ON-LINE                                           OMRON CANADA, INC.

One East Commerce Drive                                  Global - http://www.omron.com                           885 Milner Avenue

Schaumburg, IL 60173                                     USA - http://www.omron.com/oei                          Scarborough, Ontario M1B 5V8

1-800-55-OMRON                                           Canada - http://www.omron.com/oci                       416-286-6465

Cat. No. GC TMCN1        3/02                            Specifications subject to change without notice.                 Printed in the U.S.A.

                                                                  10
This datasheet has been downloaded from:

datasheet.eeworld.com.cn

Free Download

Daily Updated Database

100% Free Datasheet Search Site

100% Free IC Replacement Search Site

Convenient Electronic Dictionary

Fast Search System

www.EEworld.com.cn

All Datasheets Cannot Be Modified Without Permission

               Copyright © Each Manufacturing Company
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2020 EEWORLD.com.cn, Inc. All rights reserved