电子工程世界电子工程世界电子工程世界

产品描述

搜索
 

H3RN-2 AC24

器件型号:H3RN-2 AC24
器件类别:热门应用    机电/工控/自动化   
文件大小:4772.71KB,共10页
厂商名称:OMRON
厂商官网:https://www.omron.com
标准:
下载文档

器件描述

控制器 timer slim-multi

参数
制造商: Omron
产品种类: 控制器
RoHS:

H3RN-2 AC24器件文档内容

Solid-state timer

H3RN

Ultra-slim Timer for G2R Relay Socket

Pin configuration compatible with G2R Relay and mounts to the
P2R/P2RF Socket.

Standard multiple time ranges and multiple operating modes.
Conforms to EN61812-1 and IEC60664-1 4 kV/2 for Low Volt-

age, and EMC Directives.

Model Number Structure                                           2. Time Range
                                                                     None: Short-time range (0.1 s to 10 min)
Model Number Legend                                                 1: Long-time range (0.1 min to 10 hrs)

H3RN-@@

               12
1. Output

    1: SPDT
    2: DPST-NO

Ordering Information

List of Models

Supply voltage     Time-limit contact                                  Short-time range model         Long-time range model
                                                                             (0.1 s to 10 min)             (0.1 min to 10 h)
24 VAC;            SPDT
12, 24 VDC         DPST-NO                                       H3RN-1                         H3RN-11

                                                                 H3RN-2                         H3RN-21

Note: Specify both the model number and supply voltage when ordering.
               Example: H3RN-1 24 VAC

                                                     Supply voltage

Accessories (Order Separately)

Connecting Socket

            Timer                       Track mounting/Front connecting socket                Back connecting socket
                                      P2RF-05-E                                 P2R-057P
H3RN-1/-11                            P2RF-08-E                                 P2R-087P
H3RN-2/-21

            http://www.ia.omron.com/                                   (c)Copyright OMRON Corporation 2007 All Rights Reserved.  1
                                                                                                                          H3RN

Specifications

Ratings

                 Item                             H3RN-1/H3RN-2                                     H3RN-11/H3RN-21

Time ranges                         0.1 s to 10 min (1 s, 10 s, 1 min, or 10 min max. 0.1 min to 10 h (1 min, 10 min, 1 h, or 10 hrs max.

                                    selectable)                                   selectable)

Rated supply voltage (See note 2.)  24 VAC (50/60 Hz); 12, 24 VDC
Pin type
Operating mode                      Plug-in
Operating voltage range
                                    ON-delay, interval, flicker OFF-start, or flicker-ON start selectable by DIP switch

                                    85% to 110% of rated supply voltage (12 VDC: 90% to 110% of rated supply voltage)
                                    (See note 1.)

Reset voltage                       10% max. of rated supply voltage
Power consumption
                                    24 VAC: Relay ON: approx. 0.8 VA (0.6 W) at 24 VAC, 60 Hz
                                                Relay OFF: approx. 0.6 VA (0.4 W) at 24 VAC, 60 Hz

                                    12 VDC: Relay ON: approx. 0.5 W at 12 VDC
                                                Relay OFF: approx. 0.2 W at 12 VDC

                                    24 VDC: Relay ON: approx. 0.6 W at 24 VDC
                                                Relay OFF: approx. 0.3 W at 24 VDC

Control outputs                     3 A at 250 VAC, resistive load (cos = 1) (G6B-2@14P-FD-US used)
                                    The minimum applicable load is 10 mA at 5 VDC (P reference value).

Note: 1. When using the H3RN in any place where the ambient temperature is more than 50C, supply 90% to 110% of the rated voltages
            (12 VDC: 95% to 110% of the rated voltage).

        2. Refer to Safety Precautions for All Times when combining the Timer with an AC 2-wire proximity sensor.

Characteristics

                        Item                      H3RN-1/H3RN-2                                     H3RN-11/H3RN-21
Accuracy of operating time
Setting error                       1% FS max. (1 s range: 1%10 ms max.)
Reset time
Influence of voltage                15%50 ms FS max.
Influence of temperature
Insulation resistance               Min. power-opening time: 12, 24 VDC: 0.1 s max. (including halfway reset)
Dielectric strength                                                   24 VAC: 0.5 s max. (including halfway reset)

Vibration resistance                2% FS max.
Shock resistance
Ambient temperature                 2% FS max.
Ambient humidity
Life expectancy                     100 M min. (at 500 VDC)
Impulse withstand voltage
Noise immunity                      2,000 VAC, 50/60 Hz for 1 min (between operating circuit and control output, or contacts of different
Static immunity                     poles)
Degree of protection                1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Weight
EMC                                 Destruction: 10 to 55 Hz, 0.75-mm single amplitude for 1 h each in 3 directions
                                    Malfunction: 10 to 55 Hz, 0.5-mm single amplitude for 10 min each in 3 directions
Approved standards
                                    Destruction: 300 m/s2
                                    Malfunction: 100 m/s2

                                    Operating: -10C to 55C (with no icing)
                                    Storage: -25C to 65C (with no icing)

                                    Operating: 35% to 85%

                                    Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h)
                                    Electrical: 100,000 operations min. (3 A at 250 VAC, resistive load at 1,800 operations/h)

                                    Between power terminals: 1 kV

                                    1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 s, 1-ns rise)

                                    Destruction: 8 kV
                                    Malfunction: 4 kV

                                    IP40 (Terminal screw sections are excluded.)

                                    Approx. 18 g

                                    (EMI)                             EN61812-1
                                    Emission Enclosure:               EN55011 Group 1 class A
                                    Emission AC Mains:                EN55011 Group 1 class A
                                    (EMS)                             EN61812-1
                                    Immunity ESD:                     EN61000-4-2: 6 kV contact discharge (level 3)

                                                                                          8 kV air discharge (level 3)

                                    Immunity RF-interference from AM Radio Waves: IEC61000-4-3:10 V/m (80 MHz to 1 GHz) (level 3)

                                    Immunity Burst:                   EN61000-4-4: 2 kV power-line (level 3)
                                    Immunity Surge:                                       2 kV I/O signal-line (level 4)

                                                                      IEC51000-4-5: 1 kV line to line (level 3)
                                                                                          2 kV line to ground (level 3)

                                    UL508, CSA C22.2 No. 14
                                    Conforms to EN61812-1, IEC60664-1 4 kV/2.
                                    Output category according to IEC60947-5-1.

                   http://www.ia.omron.com/                           (c)Copyright OMRON Corporation 2007 All Rights Reserved.             2
                                                                                                                                    H3RN

Connections                                                             H3RN-2/H3RN-21

Connection                                                                                                         DIN Indication

H3RN-1/H3RN-11

                                           DIN Indication

Timer                                                                                    Timer
circuit                                                                                  circuit

  OUT PW                                                                                 OUT PW

Bottom View                                                                              Bottom View

Pulse Operation

A pulse output for a certain period can be obtained with a random external input signal.
Use the H3RN in interval mode as shown in the following timing charts.

H3RN-2/H3RN-21

                                                           Power (3-8)

                                                           External short circuit (1-4)           50 ms
                                                           External input (1-3)                   min.

                               Timer                       Time limit contact
                               circuit                     NO (6-5)

                                 External input            Run/Power indicator (PW)
                                                           Output indicator (OUT)
  !Caution
                                                                                         Note: t: Set time
Be careful when connecting wires.                                                        Rt: Reset time

                 Mode                                                                                    Terminals

Pulse operation                                  Power supply between 3 and 8
                                                 Short-circuit between 4 and 1
                                                 Input signal between 3 and 1

Operating mode; interval and all other Power supply between 1 and 8
modes

                 http://www.ia.omron.com/                                                (c)Copyright OMRON Corporation 2007 All Rights Reserved.  3
                                                                                                 H3RN

Operation

Timing Chart                                                Timing chart

         Operating mode

                                             H3RN-1/H3RN-11                      H3RN-2/H3RN-21

ON-delay                 Power (1-5)                         Power (1-8)

Power                   Time limit contact                  Time limit contact
Output                  NC (4-2)                            NO (4-3, 5-6)
                         Time limit contact
Interval                 NO (4-3)                            Run/Power
                         Run/Power                           indicator (PW)
Power                   indicator (PW)
Output                  Output indicator                    Output indicator
                         (OUT)                               (OUT)
Flicker OFF-start
                         Power (1-5)                         Power (1-8)
Power
Output                  Time limit contact                  Time limit contact
                         NC (4-2)                            NO (4-3, 5-6)
Flicker ON-start                                             Run/Power
                         Time limit contact                  indicator (PW)
Power                   NO (4-3)                            Output indicator
Output                  Run/Power                           (OUT)
                         indicator (PW)
Note: t: Set time        Output indicator                    Power (1-8)
        Rt: Reset time   (OUT)
                                                             Time limit contact
                         Power (1-5)                         NO (4-3, 5-6)
                                                             Run/Power
                         Time limit contact                  indicator (PW)
                         NC (4-2)                            Output indicator
                         Time limit contact                  (OUT)
                         NO (4-3)
                         Run/Power                           Power (1-8)
                         indicator (PW)                      Time limit contact
                         Output indicator                    NO (4-3, 5-6)
                         (OUT)                               Run/Power
                                                             indicator (PW)
                         Power (1-5)                         Output indicator
                                                             (OUT)
                         Time limit contact
                         NC (4-2)

                         Time limit contact
                         NO (4-3)

                         Run/Power
                         indicator (PW)
                         Output indicator
                         (OUT)

                        http://www.ia.omron.com/             (c)Copyright OMRON Corporation 2007 All Rights Reserved.  4
                                                                                                                     H3RN

DIP Switch Settings

The 1-s range and ON-delay mode for H3RN-1/-2, 1-min range and ON-delay mode for H3RN-11/-21 are factory-set before shipping.

Time Ranges

     Model           Time range     Time setting     Setting              Factory-set
                  1s                     range                          Yes
H3RN-1,
H3RN-2                           0.1 to 1 s

                  10 s           1 to 10 s                              No

                  1 min          0.1 to 1 min                           No

                  10 min         1 to 10 min                            No

H3RN-11,          1 min          0.1 to 1 min                           Yes

H3RN-21

                  10 min         1 to 10 min                            No

                  1h             0.1 to 1 h                             No

                  10 h           1 to 10 h                              No

Note: The left two DIP switch pins are used to select the time ranges.

Operating Modes

                   Operating mode                    Setting              Factory-set
                                                                        Yes
ON-delay

Interval                                                                No

Flicker OFF-start                                                       No

Flicker ON-start                                                        No

Note: The right two DIP switch pins are used to select the operating modes.

Nomenclature

                        Run/Power Indicator (Green)                          Main Dial
                        (Lit: Power ON)
                                                                             Set the desired time according to time
                        Output Indicator (Orange)                            range selectable by DIP switch.
                        (Lit: Output ON)

                   http://www.ia.omron.com/                                  (c)Copyright OMRON Corporation 2007 All Rights Reserved.  5
                                                                                                     H3RN

Dimensions

Note: All units are in millimeters unless otherwise indicated.

Timers

H3RN-1/H3RN-11 Front Mounting

H3RN-2/H3RN-21 Front Mounting

Mounting Height

Use the P2RF-@-E or P2R-@7P to mount the H3RN. When ordering any one of these sockets,
replace "@" with "05" for SPDT or "08" for DPST-NO.
The P2RF-@ cannot be used because the hook is a different shape.

P2RF-@-E                                                        P2R-@7P

          H3RN Series                                                                   H3RN Series
                                                                                        P2R-@7P
P2RF-@-E                                  80.9 (see note 1)                             Socket
Socket                                    (84.9) (see note 2)

                                    79.5 (see note 1)
                                    (83.5) (see note 2)

Note:  1. The value shown indicates the dimension for the
           P2RF-05-E with the PFP-@N Mounting Rail.
           The value is 71.5 mm when using the PFP-N@2.

       2. The value shown in parentheses indicates the
           dimension for the P2RF-08-E with the PFP-@N
           Mounting Rail.
           The value is 75.5 mm when using the PFP-N@2.

          http://www.ia.omron.com/                              (c)Copyright OMRON Corporation 2007 All Rights Reserved.  6
                                                                                                                             H3RN

Safety Precautions                                                                            Do not use the SPDT contact in a circuit which may cause short-cir-
                                                                                              cuiting at three points (otherwise, short-circuiting of the power supply
Correct Use                                                                                  may occur) because the SPDT contact of H3RN-1/-11 is composed
                                                                                              of an SPST-NC contact.
When using the H3RN in any place where the ambient temperature
is more than 50C, supply 90% to 110% of the rated voltages (at                                                                                      3
12 VDC: 95% to 110%).
                                                                                                                                         Short-circuit current 4
Do not leave the H3RN in time-up condition for a long period of time                                                      Power supply
(for example, more than one month in any place where the ambient                                                          for load
temperature is high), otherwise the internal parts may become dam-
aged. Therefore, the use of the H3RN with a relay as shown in the                                                                                      2
following circuit diagram is recommended.

                                                                                                                 1  5

   X2/b          T/a  X1/a      X1/a

T            X1             X2                                                                Do not set to the minimum setting in the flicker modes, otherwise the
                                                                                              contact may be damaged.
                                                       X : Auxiliary relay such as G2R Relay
                                                                                              Do not use the H3RN in places where there is excessive dust, corro-
The H3RN must be disconnected from the socket when setting the                                sive gas, or direct sunlight.
DIP switch, otherwise the user may touch a terminal imposed with a
high voltage and get an electric shock.                                                       Make sure that there is a space of 3 mm or more between any H3RN
                                                                                              Models next to each other. (When using the P2RF-@-E Socket, a
Do not connect the H3RN as shown in the following circuit diagram                             space of 3 mm or more will be secured.) If a space of 3 mm or more
on the right hand side, otherwise the H3RN's internal contacts differ-                        is not secured, the ambient temperature must be less than 50C.
ent from each other in polarity may become short-circuited.
                                                                                              The internal parts may become damaged if a supply voltage other
                                                                                              than the rated ones is imposed on the H3RN.

Correct                         Incorrect                                                      Precautions for EN61812-1
                                                                                                Conformance
                                           L2

         L1      L2                   L1                                                      The H3RN as a built-in timer conforms to EN61812-1 provided that
                                                                                              the following conditions are satisfied.

Use the following safety circuit when building a self-holding circuit                         Handling
with the H3RN and an auxiliary relay, such as a G2R Relay, in combi-
nation.                                                                                       Do not touch the DIP switch while power is supplied to the H3RN.

                                                                                              Before dismounting the H3RN from the socket, make sure that no
                                                                                              voltage is imposed on any terminal of the H3RN.

                                                                                              Wiring

                                                                                              Basic insulation is ensured between the H3RN's operating circuit and
                                                                                              control output.

                                                                              G2R Relay       Basic insulation:  Overvoltage category III,
                                                                                                                 pollution degree 2
In the case of the above circuit, the H3RN will be in pulse operation.                                           (with a clearance of 3.0 mm and a creepage
Therefore, if the circuit shown on page 3 is used, no auxiliary relay                                            distance of 3.0 mm at 240 VAC)
will be required.
                                                                                              The clearance from the edge of the P2R-087P Socket to internal,
                                                                                              current-carrying metal parts is 1.3 mm. Position the H3RN to provide
                                                                                              the necessary clearance for the voltage used.
                                                                                              When using the P2RF-@-E or P2R-057P Socket, basic insulation is
                                                                                              ensured in the mounted condition for a voltage of 250 VAC max.

             ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
             To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                               In the interest of product improvement, specifications are subject to change without notice.

         http://www.ia.omron.com/                                                             (c)Copyright OMRON Corporation 2007 All Rights Reserved.                  7
Safety Precautions for All Timers

Refer to the Safety Precautions for individual Timers for precautions specific to each Timer.

                           !WARNING                                        Normal operation may not be possible in locations subject to
                                                                             sulfidizing gas, such as in sewer systems or waste incinerators.
The following Timers contain lithium batteries that are                      OMRON does not market any Timers or other control devices for
not explosion proof.                                                         operation in atmospheres containing sulfidizing gas. Seal the Timer
                                                                             so that sulfidizing gas will not enter it. If sealing is not possible,
1. Timers with Built-in Batteries: H5L                                       OMRON does provide special Timers with improved resistance to
    The Timer contains a lithium battery, which may occasionally             sulfidizing gas. Ask your OMRON representative for details.
    ignite or rupture. Do not disassemble, deform under pressure,
    heat to 100C or higher, or incinerate the Timer.                      Power Supply

2. Timers with Replaceable Batteries: Y92S-20 (for H5CN-M)                  Be sure that the voltage applied is within the specified range,
    The battery may occasionally rupture, ignite, or leak fluid. Do          otherwise the internal elements of the Timer may be damaged.
    not short the positive and negative terminals. Do not charge,
    disassemble, deform under pressure, or throw the battery into a         Install a switch or circuit breaker that allows the operator to
    fire. If a non-specified battery is used, the battery may leak fluid     immediately turn OFF the power, and label it to clearly indicate its
    or rupture, occasionally resulting in equipment failure or minor         function.
    injury. Use only the specified battery.
                                                                            Maintain voltage fluctuations    Allowable
                                                                             in the power supply within     Voltage Range
                                                                             the specified range.

!CAUTION

The following Timers contain lithium batteries that are                     Use a commercial power supply for the power supply voltage input
explosion proof.                                                             to models with AC inputs.
                                                                             Inverters with an output frequency of 50/60 Hz are available, but
     Timers with Built-in Batteries: H5BR, H5AN-4DM, H5S, H5F, and           the rise in the internal temperature of the Timer may result in
                                            H4KV                             ignition or burning. Do not use an inverter output for the power
                                                                             supply of the Timer.
     The Timer contains a lithium battery, which may occasionally
     ignite or rupture. Do not disassemble, deform under pressure,          The Timers listed below cannot be directly turned ON and OFF by
     heat to 100C or higher, or incinerate the Timer.                       using an AC 2-wire proximity sensor to turn the Timer's power
                                                                             supply ON and OFF.
Precautions for Safe Use                                                    Use the following countermeasure when using an AC 2-wire
                                                                             proximity sensor with the Timer. (The power supply circuit in the
Operating Environment                                                        Timer uses half-wave rectification. Only a half AC wave is supplied
                                                                             to the proximity sensor, which may cause operation to be unstable.)
Use the Timer within the ratings specified for ambient operating
  temperature and ambient operating humidity for each model.                Applicable Models

Store the Timer with the specified temperature range for each              H3Y, H3YN, H3RN, H3CA-8, RD2P, and H3CR(-A, -A8, -AP, -F, and
  model. If the Timer has been stored at a temperature of less than          -G)
  -10C, allow the Timer to stand at room temperature for at least 3
  hours before using it.                                                    Countermeasure

Use the Timer within the performance specified for water and oil           Wire through a relay and use the relay contacts to turn the power
  exposure for each model.                                                   supply ON and OFF.

Do not use the Timer in locations subject to shock and vibration.          Confirm the stability of operation after making the connections.
  Long-term usage in such locations may damage the Timer due to
  stress.                                                                   Install protective measures (such as earth leakage breakers, wiring
  Magnetic contactors generate a shock of 1,000 to 2,000 m/s2 when           breakers, or fuses) on the power supply side according to any
  switching a load. When mounting to DIN Track, separate magnetic            applicable laws or regulations.
  contactors from the Timer so that the Timer is not subjected to
  vibration and shock. Use anti-vibration rubber.

Do not use the Timer in locations subject to excessive dust,
  corrosive gases, or direct sunlight.

Do not use organic solvents (such as paint thinner or benzine),
  strong alkalis, or strong acids because they will damage the
  external finish of the Timer.

Separate the input devices, input wiring, and Timer as far as
  possible from sources of noise and power lines carrying noise.

When using the Timer in environments subject to large amounts of
  static electricity (e.g., pipes carrying molding materials, powders, or
  fluid materials), separate the Timer as far as possible from the
  sources of static electricity.

Do not remove the external case from the Timer.
Do not use the Timer in locations where condensation may occur

  due to high humidity or sudden temperature changes.
  Condensation inside the Timer may result in malfunction or
  damage to Timer elements.
The life of internal parts may be reduced if Timers are mounted in
  close proximity to each other.
Resin and rubber parts (e.g., rubber packing) may deteriorate,
  shrink, or harden depending on the operating environment (e.g.,
  subjected to corrosive gases, ultraviolet light, or high
  temperatures). We recommend periodic inspection and
  replacement.

http://www.ia.omron.com/                                                   (c)Copyright OMRON Corporation 2007 All Rights Reserved.           C-1
Correctly Handling Input Signals                                          Other Precautions

Malfunction due to noise may occur if input wiring is placed in the       Confirm that you have the correct model before using it.
same duct or conduit as power lines or high-voltage lines. Separate
input wiring from power lines and wire them in a separate system.          Be sure that all terminals are wired correctly.
Also, use shielded cables, use metal conduits, and keep wiring
distances as short as possible.                                           Always test the output status with a tester before using a Timer with
                                                                            a built-in keep relay (e.g., the H3CR-H and H3DE-H). Shock
Timers with Relays                                                          resulting from dropping the Timer during transport or handling may
                                                                            cause the output contacts to reverse or to be in a neutral status.
Do not connect a load that exceeds contact ratings, such as the
  switching capacity (contact voltage or contact current). Insulation      Leaving the Timer with outputs ON at a high temperature for a long
  faults, contact welding, contact faults, and other failures to achieve    time may hasten the degradation of internal parts (such as
  specified performance may occur and the relay may be damaged or           electrolytic capacitors). Use the Timer in combination with relays
  may burn.                                                                 and avoid leaving the Timer with the output turned ON for an
                                                                            extended period of time (e.g., for more than a month).
Continued use with deteriorated performance may ultimately result         Reference Example (Use the Timer as shown below.)
  in insulation breakdown between circuits or relay burning. The life
  of the built-in relay is greatly affected by switching conditions.         X2/b  T/a  X1/a  X1/a
  Before using the Timer, test operation under actual application
  conditions and confirm that the switching frequency presents no         T        X1         X2    X Auxiliary relay
  problems in performance.
                                                                                                                               (e.g., MY Relays)
Electrical life depends on the type of load, switching frequency, and
  ambient environment. Observe the following precautions when             Be sure that only a qualified worker (e.g., an electrical engineer)
  using the Timer. When switching a DC load, contact transfer may           performs electrical work for the Timer.
  cause the contacts to stick or may cause contact failure. Confirm
  applicability and consider using a surge absorbing element. When
  switching at high frequencies, heat generated by arcing may cause
  contacts to melt or may cause metal corrosion. Consider
  connecting an arc absorbing element, reducing the switching
  frequency, or lowering the humidity.

The surge current depends on the type of load, which also affects
  contact switching frequency and the number of operations. Check
  the rated current and the surge current, and design the circuits with
  sufficient margin.

Resistive load Solenoid load Motor load           Incandescent
                                                    lamp load
Rated current  10 to 20 times    5 to 10 times
               the rated         the rated       10 to 20 times
               current           current         the rated
                                                 current

Sodium light   Capacitor          Transformer     Mercury light
     loads        loads                loads           loads

1 to 3 times the 20 to 40 times  5 to 15 times   1 to 3 times the
                                 the rated load  rated load
rated load     the rated load

Arcing when switching and relay heating may result in ignition or
  explosion. Do not use the Timer in atmospheres subject to
  inflammable or explosive gases.

Contact faults may occur. Do not use the Timer in atmospheres
  subject to sulfidizing gas, chloride gas, or silicon gas.

The switching capacity for DC voltage loads is lower than that for
  AC voltage loads.

Timers with Non-contact Outputs

Short faults or open faults may occur due to destruction of the
  output element. Do not use the Timer for a load that exceeds the
  rated output current.

Short faults or open faults may occur due to destruction of the
  output element from reverse electromotive force. When using the
  Timer for a DC inductive load, always connect a diode as a
  countermeasure against reverse electromotive force.

               ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
               To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                                 In the interest of product improvement, specifications are subject to change without notice.

               http://www.ia.omron.com/                                   (c)Copyright OMRON Corporation 2007 All Rights Reserved.                 C-2
                                                                 Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.

                                                      Warranty and Limitations of Liability
WARRANTY

OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if
specified) from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL
LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR
STRICT LIABILITY.

In no event shall responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

                                                             Application Considerations
SUITABILITY FOR USE

OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the product.

At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:

Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.

Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety
   equipment, and installations subject to separate industry or government regulations.

Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

                                                                        Disclaimers
CHANGE IN SPECIFICATIONS

Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the product may be changed without any notice. When in doubt, special model numbers may be assigned to fix
or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased product.

DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

ERRORS AND OMISSIONS
The information in this catalog has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.

PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent
the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.

PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.

COPYRIGHT AND COPY PERMISSION
This catalog shall not be copied for sales or promotions without permission.

This catalog is protected by copyright and is intended solely for use in conjunction with the product. Please notify us before copying or reproducing this
catalog in any manner, for any other purpose. If copying or transmitting this catalog to another, please copy or transmit it in its entirety.

OMRON Corporation                                                                                                                                      2007. 3
                               In the interest of product improvement, specifications are subject to change without notice.
Industrial Automation Company
                                                      (c)Copyright OMRON Corporation 2007 All Rights Reserved.
http://www.ia.omron.com/
This datasheet has been downloaded from:
            datasheet.eeworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

器件索引   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2020 EEWORLD.com.cn, Inc. All rights reserved