Solid-state Twin Timers

H3CR-F

DIN 48 48-mm Twin Timers

Wide power supply ranges of 100 to 240 VAC and 48 to
125 VDC respectively.

ON- and OFF-times can be set independently and so
combinations of long ON- or OFF-time and short OFF- or ON-
time settings are possible.

Fourteen time ranges from 0.05 s to 30 h or from 1.2 s to 300 h
depending on the model to be used.

Models with a flicker ON start or flicker OFF start are available.
Easy sequence checks through instantaneous outputs for a

zero set value at any time range.
Length, when panel-mounted with a Socket, of 80 mm or less.
11-pin and 8-pin models are available.

Model Number Structure

Model Number Legend

H3CR - F @ @ - @ @               3. Twin Timer Mode                         5. Supply Voltage
                                 None: Flicker OFF start
                  12 3 4 5       N: Flicker ON start                        100-240AC: 100 to 240 VAC

1. Classification                4. Time Range                              24AC/DC: 24 VAC/VDC
F: Twin timers                   None: 0.05 s to 30 h models
2. Configuration                 300: 1.2 s to 300 h models                 12DC:  12 VDC
None: 11-pin socket
8: 8-pin socket                                                             48-125DC: 48 to 125 VDC

Ordering Information

List of Models

Operating    Supply                              0.05 s to 30 h models                         1.2 s to 300 h models
  modes      voltage
                                 11-pin models                8-pin models         11-pin models       8-pin models

Flicker OFF  100 to 240 VAC      H3CR-F 100-240AC   H3CR-F8 100-240AC       H3CR-F-300 100-240AC       H3CR-F8-300 100-240AC
start        24 VAC/DC
                                 H3CR-F 24AC/DC     H3CR-F8 24AC/DC         H3CR-F-300 24AC/DC         H3CR-F8-300 24AC/DC

             12 VDC              H3CR-F 12DC        H3CR-F8 12DC            H3CR-F-300 12DC            H3CR-F8-300 12DC

             48 to 125 VDC       H3CR-F 48-125DC    H3CR-F8 48-125DC        H3CR-F-300 48-125DC        H3CR-F8-300 48-125DC

Flicker ON start 100 to 240 VAC  H3CR-FN 100-240AC  H3CR-F8N 100-240AC      H3CR-FN-300 100-240AC H3CR-F8N-300 100-240AC

             24 VAC/DC           H3CR-FN 24AC/DC    H3CR-F8N 24AC/DC        H3CR-FN-300 24AC/DC        H3CR-F8N-300 24AC/DC

             12 VDC              H3CR-FN 12DC       H3CR-F8N 12DC           H3CR-FN-300 12DC           H3CR-F8N-300 12DC

             48 to 125 VDC       H3CR-FN 48-125DC   H3CR-F8N 48-125DC       H3CR-FN-300 48-125DC       H3CR-F8N-300 48-125DC

Note: Specify both the model number and supply voltage when ordering.
        Example: H3CR-F 100-240AC

                                 Supply voltage

             http://www.ia.omron.com/                                       (c)Copyright OMRON Corporation 2007 All Rights Reserved.  1
                                                                                                                           H3CR-F

Accessories (Order Separately)

                             Name/specifications                                                                   Models
                                                                                  Y92F-30
Flush Mounting Adapter                                                            Y92F-73
                                                                                  Y92F-74
Mounting Track                       50 cm (l) 7.3 mm (t)                       PFP-50N
                                     1 m (l) 7.3 mm (t)                         PFP-100N
End Plate                            1 m (l) 16 mm (t)                          PFP-100N2
Spacer                                                                            PFP-M
Protective Cover                     8-pin                                        PFP-S
Track Mounting/                      8-pin, finger safe type                      Y92A-48B
Front Connecting Socket              11-pin                                       P2CF-08
                                     11-pin, finger safe type                     P2CF-08-E
Back Connecting Socket               8-pin                                        P2CF-11
                                     8-pin, finger safe type                      P2CF-11-E
Hold-down Clip (See note 2)          11-pin                                       P3G-08
                                     11-pin, finger safe type                     P3G-08 with Y92A-48G (See note 1)
                                     For PL08 and PL11 Sockets                    P3GA-11
                                     For PF085A Socket                            P3GA-11 with Y92A-48G (See note 1)
                                                                                  Y92H-7
                                                                                  Y92H-8

Note: 1. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 or P3GA-11 Socket.
        2. Hold-down Clips are sold in sets of two.

Specifications

General

                 Item                H3CR-F              H3CR-F8                          H3CR-FN                       H3CR-F8N
Operating mode                                                                                               8-pin
Pin type                     Flicker OFF start                                    Flicker ON start
Operating/Reset method                                                                                                    h (hrs)
Output type                  11-pin               8-pin                           11-pin
Mounting method                                                                                                      10 h (10 hrs)
Approved standards           Time-limit operation/Time-limit reset or self-reset                            1.2 to 12
                                                                                                            3 to 30
                             Relay output (DPDT)                                                            12 to 120
                                                                                                            30 to 300
                             DIN track mounting, surface mounting, and flush mounting

                             UL508, CSA C22.2 No.14, NK, Lloyds
                             Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
                             Output category according to EN60947-5-1.

Time Ranges

0.05 s to 30 h Models

         Time unit                    s (sec)              10 s (10 sec)                     min (min)
                        0.05 to 1.2               1.2 to 12                       0.12 to 1.2
Setting  1.2            0.3 to 3                  3 to 30                         0.3 to 3
                        1.2 to 12                 12 to 120                       1.2 to 12
         3              3 to 30                   30 to 300                       3 to 30

         12

         30

Note: Instantaneous output is available at any time range. To obtain instantaneous output, set to below 0.

1.2 s to 300 h Models

         Time unit               10 s (10 sec)          10 min (10 min)                       h (hrs)
                        1.2 to 12                 1.2 to 12                       0.12 to 1.2
Setting  1.2            3 to 30                   3 to 30                         0.3 to 3
                        12 to 120                 12 to 120                       1.2 to 12
         3              30 to 300                 30 to 300                       3 to 30

         12

         30

Note: Instantaneous output is available at any time range. To obtain instantaneous output, set to below 0.

                    http://www.ia.omron.com/                                      (c)Copyright OMRON Corporation 2007 All Rights Reserved.  2
                                                                                                                     H3CR-F

Ratings

Rated supply voltage (See notes 1, 2, and 3.) 100 to 240 VAC (50/60 Hz),12 VDC, 24 VAC/DC (50/60 Hz), 48 to 125 VDC

Operating voltage range                       85% to 110% of rated supply voltage; 90% to 110% with 12-VDC models

Power reset                                   Minimum power-opening time: 0.1 s

Power consumption                             100 to 240 VAC: approx. 10 VA (2.1 W) at 240 VAC

                                              24 VAC/VDC: approx. 2 VA (1.7 W) at 24 VAC

                                                       approx. 1 W at 24 VDC

                                              48 to 125 VDC: approx. 1.5 W at 125 VDC

                                              12 VDC:  approx. 1 W at 12 VDC

Control outputs                               Contact output: 5 A at 250 VAC/30 VDC, resistive load (cos = 1)

Note: 1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
        2. Do not use an inverter output as the power supply. Refer to Safety Precautions for All Timers for details.
        3. Refer to Safety Precautions for All Timers when using the Timer together with a 2-wire AC proximity sensor.

Characteristics

Accuracy of operating 0.2% FS max. (0.2% FS 10 ms max. in ranges of 1.2 and 3 s)
time

Setting error            5% FS 50 ms max.

Reset time               0.1 s max.

Reset voltage            10% max. of rated voltage

Influence of voltage     0.2% FS max. (0.2% FS 10 ms max. in ranges of 1.2 and 3 s)

Influence of temperature 1% FS max. (1% FS 10 ms max. in ranges of 1.2 and 3s)

Insulation resistance 100 M min. (at 500 VDC)

Dielectric strength      2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)
                         2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
                         2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
                         1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)

Impulse withstand        3 kV (between power terminals) for 100 to 240 VAC, 48 to 125 VDC
voltage                  1 kV for 12 VDC, 24 VAC/DC
                         4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC, 48 to
                         125 VDC
                         1.5 kV for 12 VDC, 24 VAC/DC

Noise immunity           1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 s, 1-ns rise)
                         400 V for 12 VDC

Static immunity          Malfunction: 8 kV
                         Destruction: 15 kV

Vibration resistance     Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
                         Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions

Shock resistance         Destruction: 980 m/s2 three times each in six directions
                         Malfunction: 98 m/s2 three times each in six directions

Ambient temperature      Operating: -10C to 55C (with no icing)
                         Storage: -25C to 65C (with no icing)

Ambient humidity         Operating: 35% to 85%

Life expectancy          Mechanical: 20 million operations min. (under no load at 1,800 operations/h)
                         Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note)

EMC                      (EMI)                         EN61812-1

                         Emission Enclosure:           EN55011 Group 1 class A

                         Emission AC Mains:            EN55011 Group 1 class A

                         (EMS)                         EN61812-1

                         Immunity ESD:                 IEC61000-4-2:               6 kV contact discharge (level 3)

                                                                                   8 kV air discharge (level 3)

                         Immunity RF-interference from AM Radio Waves:             IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)

                         Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (9005 MHz) (level 3)

                         Immunity Conducted Disturbance: IEC61000-4-6:             10 V (0.15 to 80 MHz) (level 3)

                         Immunity Burst:               IEC61000-4-4:               2 kV power-line (level 3)

                                                                                   2 kV I/O signal-line (level 4)

                         Immunity Surge:               IEC61000-4-5:               1 kV line to line (level 3)

                                                                                   2 kV line to ground (level 3)

Case color               Light Gray (Munsell 5Y7/1)

Degree of protection IP40 (panel surface)

Weight                   Approx. 100 g

Note: Refer to the Life-test Curve.

                 http://www.ia.omron.com/                               (c)Copyright OMRON Corporation 2007 All Rights Reserved.            3
                                                                                                                                                 H3CR-F

Life-test CurveSwitching operations (x 103)

       10,000
         5,000

                              1,000          30 VDC L/R = 7 ms                 Reference: A maximum current of 0.15 A can be switched at 125 VDC (cos = 1)
                                500                            250 VAC/30 VDC                  and a maximum current of 0.1 A can be switched if L/R is 7 ms. In
                                                               (cos = 1)                       both cases, a life of 100,000 operations can be expected.
                                100                                                            The minimum applicable load is 10 mA at 5 VDC (failure level: P).
                                     250 VAC (cos = 0.4)

                                           Load current (A)

Connections

Block Diagrams

                                                                  ON indicator OFF indicator   Zero setting
                                                                                               detection
                                                                                               circuit

                                                                               Indicator
                                                                               circuit

                                                                                          ROM  RAM  Clock

                                                                                                                                       Output
                                                                                                                                       circuit

                                     AC (DC) input  Power supply                              One-chip microcomputer  Time range/unit
                                                    circuit                                                           selectors

I/O Functions

Inputs                               Control output               ---
Outputs                                                           Outputs are turned ON/OFF according to the time set by the ON- and OFF-time setting knob.

Terminal Arrangement

                                     H3CR-F8                                                   H3CR-F
                                     H3CR-F8                                                   H3CR-FN
                                     NH3CR-F8-300                                              H3CR-F-300
                                     H3CR-F8N-300                                              H3CR-FN-300

                                                    Power supply                                                                         (+)(~)

                                                                                                                 Power supply
                                                                                               Note: Leave terminals 5, 6, and 7 open.

                                                                                                         Do not use them as relay terminals.

                                     http://www.ia.omron.com/                                       (c)Copyright OMRON Corporation 2007 All Rights Reserved.      4
                                                                                                                           H3CR-F

Operation

Timing Chart                                                       Timing chart

    tON: ON set time                                                                                0.1 s min.
    tOFF: OFF set time                                                                              tOFF

  Operating mode
Flicker OFF start

                        Power ON
                                                   OFF
                                                        tOFF  tON   tOFF  tON     tOFF

                        ON                         Lit

                        indicator Not lit

                        OFF                        Lit

                        indicator Not lit

                        Output ON

                        NO                         OFF

                        Output ON

                        NC                         OFF

Flicker ON start                                                                        0.1 s min.

                        Power                      ON
                                                   OFF
                                                        tON   tOFF  tON   tOFF          tON         tOFF

                        ON                         Lit

                        indicator Not lit

                        OFF                        Lit

                        indicator Not lit

                        Output ON

                        NO                         OFF

                        Output ON

                        NC                         OFF

Note: 1. The reset time requires a minimum of 0.1 s.

        2. When power is supplied in flicker ON start mode, the OFF indicator lights momentarily. This, however, has no effect on the performance
            of the Timer.

Nomenclature

                  OFF indicator (green)                                   OFF-time unit display window
                  Lit when the output is OFF.                             OFF-time unit selector (select one from sec.
                  ON indicator (orange)                                   10 s, min., and hrs, or from 10 s, 10 min, hrs,
                  Lit when the output is ON.                              and 10 h)

                  Scale range display                                     ON-time setting knob (with orange pointer)
                  windows                                                 For ON-time setting

                  Time range selector (select one                         OFF-time setting knob (with green pointer)
                  from 1.2, 3, 12, and 30 at full                         For OFF-time setting
                  scale)
                  For both ON-time and OFF-time.                          ON-time unit display window

                                                                          ON-time unit selector (select one
                                                                          from sec, 10 s, min, and hrs, or from
                                                                          10 s, 10 min, hrs, and 10 h)

                  http://www.ia.omron.com/                          (c)Copyright OMRON Corporation 2007 All Rights Reserved.                       5
                                                                                                                                           H3CR-F

Dimensions

Note: All units are in millimeters unless otherwise indicated.

H3CR-F                                                                                        17.4               66.6
                                                                                                5.7
H3CR-FN                                                               48                            6            52.3    0.7

H3CR-F-300                                                                      37 dia.
                                                                                       14 dia.
H3CR-FN-300

                                             48                                                                               44.8 44.8

H3CR-F8                                                        48                                     R1.3         66.6           11 pins
H3CR-F8N                                     48                                                                  52.3    0.7
H3CR-F8-300                                                                                              17.4
H3CR-F8N-300                                                                                              5.7
                                                                                                              6

                                                                                37 dia.                                       44.8 44.8
                                                                                      14 dia.

                                                                                                      R1.3

                                                                                                                              8 pins

Dimensions with Front Connecting Socket                                   Dimensions with Back Connecting Socket
P2CF-08-@/P2CF-11-@                                                       P3G-08/P3GA-11

                                                                          17.4  81.5                                                         81.5
                                                                                                                       17.4
                                                                                80
                                                                                                                                             75
         H3CR-F                 H3CR-F8
         H3CR-FN                H3CR-F8N                                                                                              H3CR-F8
                                                                                                                                     H3CR-F8N
103.2*             100.9 92.3*                                  90.0
                                                                                                                             Y92F-30 P3G-08
                                                                                              H3CR-F                                        (When
                                                                                             H3CR-FN                                        Y92A-48G
                                                                                                                                            mounted)
         P2CF-11   2.3*         P2CF-08                         2.3*                        P3GA-11
                                                                                Y92F-30
        P2CF-11-E               P2CF-08-E
                                                                                               (When
                                                                                               Y92A-48G
                                                                                               mounted)

*These dimensions vary with the kind of DIN track (reference value).

              ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
              To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                                In the interest of product improvement, specifications are subject to change without notice.

                   http://www.ia.omron.com/                                         (c)Copyright OMRON Corporation 2007 All Rights Reserved.          6
Solid-state Star-delta Timers

H3CR-G

DIN 48 48-mm Star-delta Timer

A wide star-time range (up to 120 seconds) and star-delta
transfer time range (up to 0.5 seconds).

Model Number Structure

Model Number Legend

H3CR - G 8 @ L @                              3. Outputs                          5. Supply Voltage
                                                                                  100-120AC: 100 to 120 VAC
                  123 4 5                     None: Star-delta operation contact  200-240AC: 200 to 240 VAC
                                              E: Star-delta operation contact
1. Classification
G: Star-delta timer                                    and instantaneous contact
2. Configuration                              4. Dimensions
8: 8-pin socket
                                              L: Long-body model

Ordering Information

List of Models

                             Outputs               Supply voltage                                         8-pin models
Time-limit contact                            100 to 120 VAC            H3CR-G8L 100-120AC
                                              200 to 240 VAC            H3CR-G8L 200-240AC
Time-limit contact and instantaneous contact  100 to 120 VAC            H3CR-G8EL 100-120AC
                                              200 to 240 VAC            H3CR-G8EL 200-240AC

Note: Specify both the model number and supply voltage when ordering.
        Example: H3CR-G8L 100-120AC

                                                        Supply voltage

http://www.ia.omron.com/                                                (c)Copyright OMRON Corporation 2007 All Rights Reserved.  7
                                                                                                                            H3CR-G

Accessories (Order Separately)

                                  Name/specifications                                                               Models
                                                                                   Y92F-30
Flush Mounting Adapter                                                             Y92F-70
                                                                                   Y92F-71
Mounting Track                           50 cm (l) 7.3 mm (t)                    PFP-50N
                                         1 m (l) 7.3 mm (t)                      PFP-100N
End Plate                                1 m (l) 16 mm (t)                       PFP-100N2
Spacer                                                                             PFP-M
Protective Cover                         8-pin                                     PFP-S
Track Mounting/                          8-pin, finger safe type                   Y92A-48B
Front Connecting Socket                  8-pin                                     P2CF-08
Back Connecting Socket                   8-pin, finger safe type                   P2CF-08-E
                                         Setting a specific time                   P3G-08
Time Setting Ring                        Limiting the setting range                P3G-08 with Y92A-48G (See note 1)
                                         Light gray (5Y7/1)                        Y92S-27
Panel Cover (See note 2)                 Black (N1.5)                              Y92S-28
                                         Medium gray (5Y5/1)                       Y92P-48GL
Hold-down Clip (See note 3)              For PL08 and PL11 Sockets                 Y92P-48GB
                                         For PF085A Socket                         Y92P-48GM
                                                                                   Y92H-1
                                                                                   Y92H-2

Note: 1. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 Socket.
        2. The Time Setting Ring and Panel Cover are sold together.
        3. Hold-down Clips are sold in sets of two.

Specifications

General                                               H3CR-G8L                             H3CR-G8EL

                  Item            Star-delta timer                                 Star-delta timer with instantaneous output
Functions
Pin type                          8-pin
Operating/Reset method
Output type                       Time-limit operation/Self-reset

Mounting method                   Time-limit: SPST-NO (star operation circuit)     Time-limit: SPST-NO (star operation circuit)
Approved standards                              SPST-NO (delta operation circuit)                       SPST-NO (delta operation circuit)

                                                                                   Instantaneous: SPST-NO

                                  DIN track mounting, surface mounting, and flush mounting

                                  UL508, CSA C22.2 No.14, NK, Lloyds
                                  Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
                                  Output category according to EN60947-5-1.

Time Ranges

            Time unit                           Star operation time ranges
Full scale setting 6              0.5 to 6 s
                                  1 to 12 s
                             12   5 to 60 s
                             60   10 to 120 s
                             120

Star-delta transfer time Programmable at 0.05 s, 0.1 s, 0.25 s or 0.5 s

http://www.ia.omron.com/                                                           (c)Copyright OMRON Corporation 2007 All Rights Reserved.  8
                                                                                                                        H3CR-G

Ratings

Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz)

Operating voltage range                    85% to 110% of rated supply voltage

Power reset                                Minimum power-opening time: 0.5 s

Power consumption                          100 to 120 VAC: approx. 6 VA (2.6 W) at 120 VAC
                                           200 to 240 VAC: approx. 12 VA (3.0 W) at 240 VAC

Control outputs                            Contact output: 5 A at 250 VAC/30 VDC, resistive load (cos = 1)

Note: 1. Do not use an inverter output as the power supply. Refer to Safety Precautions for All Timers for details.
        2. Refer to Safety Precautions for All Timers when using the Timer together with a 2-wire AC proximity sensor.

Characteristics

Accuracy of operating     0.2% FS max.
time
Setting error             5% FS 50 ms max.
Accuracy of Star-delta    25% FS + 5 ms max.
transfer time
Reset voltage             10% max. of rated voltage
Influence of voltage
Influence of temperature  0.2% FS max.
Insulation resistance
Dielectric strength       1% FS max.

Impulse withstand         100 M min. (at 500 VDC)
voltage
Noise immunity            2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)
Static immunity           2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
Vibration resistance      2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
Shock resistance          1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
Ambient temperature
Ambient humidity          3 kV (between power terminals)
Life expectancy           4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
EMC
                          1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 s, 1-ns rise)
Case color
Degree of protection      Malfunction: 8 kV
Weight                    Destruction: 15 kV

                          Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
                          Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions

                          Destruction: 980 m/s2 three times each in six directions
                          Malfunction: 294 m/s2 three times each in six directions

                          Operating: -10C to 55C (with no icing)
                          Storage: -25C to 65C (with no icing)

                          Operating: 35% to 85%

                          Mechanical: 20 million operations min. (under no load at 1,800 operations/h)
                          Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note)

                          (EMI)                       EN61812-1

                          Emission Enclosure:         EN55011 Group 1 class A

                          Emission AC Mains:          EN55011 Group 1 class A

                          (EMS)                       EN61812-1

                          Immunity ESD:               IEC61000-4-2:                 6 kV contact discharge (level 3)

                                                                                    8 kV air discharge (level 3)

                          Immunity RF-interference from AM Radio Waves:             IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)

                          Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (9005 MHz) (level 3)

                          Immunity Conducted Disturbance: IEC61000-4-6:             10 V (0.15 to 80 MHz) (level 3)

                          Immunity Burst:             IEC61000-4-4:                 2 kV power-line (level 3)

                                                                                    2 kV I/O signal-line (level 4)

                          Immunity Surge:             IEC61000-4-5:                 1 kV line to line (level 3)

                                                                                    2 kV line to ground (level 3)

                          Light Gray (Munsell 5Y7/1)

                          IP40 (panel surface)

                          H3CR-G8L: approx. 110 g; H3CR-G8EL: approx. 130 g

Note: Refer to the Life-test Curve.

                 http://www.ia.omron.com/                                (c)Copyright OMRON Corporation 2007 All Rights Reserved.            9
                                                                                                                                               H3CR-G

Life-test CurveSwitching operations ( 103)

       10,000
         5,000

                              1,000               30 VDC L/R = 7 ms               Reference:     A maximum current of 0.15 A can be switched at 125 VDC (cos = 1)
                                500                               250 VAC/30 VDC                 and a maximum current of 0.1 A can be switched if L/R is 7 ms. In
                                                                  (cos = 1)                      both cases, a life of 100,000 operations can be expected.
                                100                                                              The minimum applicable load is 10 mA at 5 VDC (failure level: P).
                                        250 VAC (cos = 0.4)

                                              Load current (A)

Connections

Block Diagrams

H3CR-G8L

                                                                                  Star           Star-delta
                                                                                  operation      transfer time
                                                                                  time range     selector
                                                                                  selector

                              AC input  Power    Star operation                   Star           Star-delta     Star-delta     Output          Star operation
                                        supply   time                             operation      transfer time  transfer time  circuit         Delta operation
                                        circuit  oscillation                      time counting  oscillation    counting
                                                 circuit                          circuit        circuit        circuit

                                                                                                                               Indicator       Star
                                                                                                                               circuit         operation
                                                                                                                                               indicator

                                                                                                                                               Delta
                                                                                                                                               operation
                                                                                                                                               indicator

H3CR-G8EL

                                                                                  Star           Star-delta
                                                                                  operation      transfer time
                                                                                  time range     selector
                                                                                  selector

                              AC input  Power    Star operation                   Star           Star-delta     Star-delta     Output          Star operation
                                        supply   time                             operation      transfer time  transfer time  circuit         Delta operation
                                        circuit  oscillation                      time counting  oscillation    counting
                                                 circuit                          circuit        circuit        circuit

                                                                                                                               Indicator       Star
                                                                                                                               circuit         operation
                                                                                                                                               indicator

                                                                                                                                               Delta
                                                                                                                                               operation
                                                                                                                                               indicator

                                                                                                                               Instantaneous
                                                                                                                               output circuit

                                        http://www.ia.omron.com/                                                (c)Copyright OMRON Corporation 2007 All Rights Reserved.  10
I/O Functions                                                                               H3CR-G

Inputs    Control output             ---
Outputs                              If the time reaches the value set with the time setting knob, the star operation output will be turned OFF
                                     and there will be delta operation output after the set star-delta transfer time has elapsed.

Terminal Arrangement

H3CR-G8L                                                       H3CR-G8EL

          Delta                      Star             Instantaneous contact                                    Delta      Star
          operation                  operation                                                                 operation  operation
          contact                    contact                                                                   contact    contact

Note: Leave terminals 1, 3, and 4 open.                                             Note: Leave terminal 4 open. Do not use
          Do not use them as relay terminals.                                                 them as relay terminals.

Operation                                                                           Timing chart                                                 0.5 s min.

Timing Chart                                                                           t1
                                                                                                           t2
    t1: Star operation time setting
    t2: Star-delta transfer time

                   Model
         H3CR-G8L/-G8EL

                                     Power (2 - 7)             ON
                                                               OFF

                                     Instantaneous output      ON
                                     (1 - 3) (-E models)       OFF

                                     Star operation            ON
                                     output (8 - 5)            OFF

                                     Delta operation           ON
                                     output (8 - 6)            OFF

                                     Star operation indicator  Lit
                                                               Not lit

                                     Delta operation indicator Lit
                                                                           Not lit

Nomenclature

          Star operation                                                                                      Time unit display
          indicator (green)                                                                                   (sec is fixed)
          Delta operation
          indicator (orange)                                                                                  Time setting knob (for setting
                                                                                                              star operation time)
          Scale range display
          windows                                                                                             Star-delta transfer time selector
                                                                                                              (select one from 0.05 s, 0.1 s,
          Star operation time range selector                                                                  0.25 s, and 0.5 s)
          (select one from 6, 12, 60, and 120
          at full scale)                              Star-delta transfer time display window

          http://www.ia.omron.com/                                                  (c)Copyright OMRON Corporation 2007 All Rights Reserved.                 11
                                                                                                                                                                 H3CR-G

Dimensions                                                                                                           15          (78.0)
                                                                                                                        6
Note: All units are in millimeters unless otherwise indicated.                                                                   63.7        0.7
                                                                                                        39 dia.
                                                                                                   48                                             44.8 44.8
                                                                                                                                                         8 pins
                                                                                   48
                                                                                                                           16.5
Dimensions with Set Ring

                                                                                                    50

                   50                                                                                   42 dia.

Dimensions with Front Connecting Socket                                                                  Time setting ring Panel cover
P2CF-08-@
                                                                                                        Dimensions with Back Connecting Socket
                                                                                                        P3G-08

                                                                                                                           15          92.9

                                                                                                                                       86.4

101.3*  H3CR-G8@L  99

        P2CF-08    2.3*                                                                                                                  H3CR-
                                                                                                                                         G8@L
        P2CF-08-E
                                                                                                                                             P3G-08
                                                                                                                                 Y92F-30

                                                                                                                                               (When
                                                                                                                                               Y92A-48G
                                                                                                                                               mounted)

*These dimensions vary with the kind of DIN track (reference value).

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                  In the interest of product improvement, specifications are subject to change without notice.

http://www.ia.omron.com/                                                                                                       (c)Copyright OMRON Corporation 2007 All Rights Reserved.  12
Solid-state Power OFF-delay Timers

H3CR-H

DIN 48 48-mm Power OFF-delay Timer

Long power OFF-delay times;
S-series: up to 12 seconds,
M-series: up to 12 minutes.

Models with forced-reset input are available.
11-pin and 8-pin models are available.

Model Number Structure

Model Number Legend

Note: This model number legend includes combinations that are not available. Before ordering, please check the List of Models on page 1 for
        availability.

H3CR - H @ @ L @ @               3. Input                   5. Supply Voltage                            6. Time Range
                                 None: Without reset input                                               S: 0.05 to 12 s
                  1 2 34 5 6     R: With reset input        100-120AC: 100 to 120 VAC                    M: 0.05 to 12 min

1. Classification                4. Dimensions              200-240AC: 200 to 240 VAC
H: Power OFF-delay timer         L: Long-body model
2. Configuration                                            48DC:                       48 VDC
None: 11-pin socket
8: 8-pin socket                                             100-125DC: 100 to 125 VDC

List of Models

Input Output Supply voltage                     S-series                                                 M-series

                                 11-pin models              8-pin models                11-pin models              8-pin models

Without DPDT 100 to 120 VAC ---                 H3CR-H8L 100-120AC S ---                                      H3CR-H8L 100-120AC M
                                                H3CR-H8L 200-240AC S                                          H3CR-H8L 200-240AC M
reset  200 to 240 VAC                           H3CR-H8L 24AC/DC S                                            H3CR-H8L 24AC/DC M
input  24 VAC/DC

       48 VDC                                   H3CR-H8L 48DC S                                               H3CR-H8L 48DC M

       100 to 125 VDC                           H3CR-H8L 100-125DC S                                          H3CR-H8L 100-125DC M

With   100 to 120 VAC H3CR-HRL 100-120AC S ---                                          H3CR-HRL 100-120AC M ---
reset  200 to 240 VAC H3CR-HRL 200-240AC S                                              H3CR-HRL 200-240AC M
input  24 VAC/DC H3CR-HRL 24AC/DC S                                                     H3CR-HRL 24AC/DC M

       48 VDC                 H3CR-HRL 48DC S                                           H3CR-HRL 48DC M

       100 to 125 VDC H3CR-HRL 100-125DC S                                              H3CR-HRL 100-125DC M

       SPDT 100 to 120 VAC ---                  H3CR-H8RL 100-120AC S ---                                     H3CR-H8RL 100-120AC M

       200 to 240 VAC                           H3CR-H8RL 200-240AC S                                         H3CR-H8RL 200-240AC M

       24 VAC/DC                                H3CR-H8RL 24AC/DC S                                           H3CR-H8RL 24AC/DC M

       48 VDC                                   H3CR-H8RL 48DC S                                              H3CR-H8RL 48DC M

       100 to 125 VDC                           H3CR-H8RL 100-125DC S                                         H3CR-H8RL 100-125DC M

Note: Specify the model number, supply voltage, and time range (S or M) when ordering.
        Example: H3CR-H8L 100-120AC S

                                                             Time range
                                                             Supply voltage

       http://www.ia.omron.com/                             (c)Copyright OMRON Corporation 2007 All Rights Reserved.                         13
                                                                                                                            H3CR-H

Accessories (Order Separately)

                             Name/specifications                                                Models
                                                               Y92F-30
Flush Mounting Adapter                                         Y92F-70
                                                               Y92F-71
Mounting Track                      50 cm (l) 7.3 mm (t)     PFP-50N
                                    1 m (l) 7.3 mm (t)       PFP-100N
End Plate                           1 m (l) 16 mm (t)        PFP-100N2
Spacer                                                         PFP-M
Protective Cover                    8-pin                      PFP-S
Track Mounting/                     8-pin, finger safe type    Y92A-48B
Front Connecting Socket             11-pin                     P2CF-08
                                    11-pin, finger safe type   P2CF-08-E
Back Connecting Socket              8-pin                      P2CF-11
                                    8-pin, finger safe type    P2CF-11-E
Hold-down Clip (See note 2)         11-pin                     P3G-08
                                    11-pin, finger safe type   P3G-08 with Y92A-48G (See note 1)
                                    For PL08 and PL11 Sockets  P3GA-11
                                    For PF085A Socket          P3GA-11 with Y92A-48G (See note 1)
                                                               Y92H-1
                                                               Y92H-2

Note: 1. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 or P3GA-11 Socket.
        2. Hold-down Clips are sold in sets of two.

Specifications

General                            H3CR-H8L                   H3CR-H8RL                                      H3CR-HRL

                  Item       Instantaneous operation/Time-limit Instantaneous operation/Time-limit reset/Forced reset
Operating/Reset method       reset

Pin type                     8-pin                                                                    11-pin
Input type
Output type                  ---                  No-voltage
Mounting method
Approved standards           Relay output (DPDT)  Relay output (SPDT)                                 Relay output (DPDT)

                             DIN track mounting, surface mounting, and flush mounting

                             UL508, CSA C22.2 No.14, NK, Lloyds
                             Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
                             Output category according to EN60947-5-1.

Time Ranges

Time unit                                         S-series                                                       M-series
                                                   s (sec)                                                       min (min)

Setting                      0.6    0.05 to 0.6                                        2 s min.
                                    0.12 to 1.2
                             1.2    0.6 to 6
                                    1.2 to 12
                             6      0.1 s min.
                                    3 s min.
                             12     3 s min.

Min. power ON time

Time-up operation repeat period

Forced-reset repeat period

Note: 1. If the above minimum power ON time is not secured, the H3CR may not operate. Be sure to secure the above minimum power ON time.

        2. Do not use the Timer with a repeat period of less than 3 s. Doing so may result in abnormal heating or burning. Refer to Safety Precautions
            (H3CR-H) on page 8 for details.

                    http://www.ia.omron.com/                   (c)Copyright OMRON Corporation 2007 All Rights Reserved.                                 14
                                                                                                                       H3CR-H

Ratings

Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz), 24 VAC/VDC (50/60 Hz), 48 VDC,
                                                             100 to 125 VDC

Operating voltage range                    85% to 110% of rated supply voltage

No-voltage input (See note 3.)             ON-impedance: 1 k max.
                                           ON residual voltage: 1 V max.
                                           OFF impedance: 500 k min.

Power consumption                          100 to 120 VAC: approx. 0.23 VA (0.22 W) at 120 VAC

                                           200 to 240 VAC: approx. 0.35 VA (0.3 W) at 240 VAC

                                           24 VAC/DC:  approx. 0.17 VA (0.15 W) at 24 VAC

                                                       approx. 0.1 W at 24 VDC

                                           48 VDC:     approx. 0.18 W at 48 VDC

                                           100 to 125 VDC: approx. 0.5 W at 125 VDC

Control outputs                            Contact output: 5 A at 250 VAC/30 VDC, resistive load (cos = 1)

Note: 1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
        2. Do not use an inverter output as the power supply. Refer to Safety Precautions for All Timers for details.
        3. For contact input, use contacts which can adequately switch 1 mA at 5 V.

Characteristics

Accuracy of operating    0.2% FS max. (0.2% FS 10 ms max. in ranges of 0.6 and 1.2 s)
time

Setting error            5% FS 50 ms max.

Operation start voltage 30% max. of rated voltage

Influence of voltage     0.2% FS max. (0.2% FS 10 ms max. in ranges of 0.6 and 1.2 s)

Influence of temperature 1% FS max. (1% FS 10 ms max. in ranges of 0.6 and 1.2 s)

Insulation resistance    100 M min. (at 500 VDC)

Dielectric strength      2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)
                         2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
                         2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
                         1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)

Impulse withstand        3 kV (between power terminals) for 100 to 120 VAC, 200 to 240 VAC, 100 to 125 VDC;
voltage                  1 kV for 24 VAC/DC, 48 VDC
                         4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 120 VAC, 200 to
                         240 VAC, 100 to 125 VDC;
                         1.5 kV for 24 VAC/DC, 48 VDC

Noise immunity           1.5 kV (between power terminals) and 600 V (between input terminals), square-wave noise by noise simulator
                         (pulse width: 100 ns/1 s, 1-ns rise); 1 kV (between power terminals) for 48 VDC

Static immunity          Malfunction: 8 kV, Destruction:15 kV

Vibration resistance     Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
                         Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions

Shock resistance         Destruction: 980 m/s2 three times each in six directions
                         Malfunction: 98 m/s2 three times each in six directions

Ambient temperature      Operating: -10C to 55C (with no icing),
                         Storage: -25C to 65C (with no icing)

Ambient humidity         Operating: 35% to 85%

Life expectancy          Mechanical: 10 million operations min. (under no load at 1,200 operations/h)
                         Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h) (See note)

EMC                      (EMI)                         EN61812-1

                         Emission Enclosure:           EN55011 Group 1 class A

                         Emission AC Mains:            EN55011 Group 1 class A

                         (EMS)                         EN61812-1

                         Immunity ESD:                 IEC61000-4-2:                 6 kV contact discharge (level 3)

                                                                                     8 kV air discharge (level 3)

                         Immunity RF-interference from AM Radio Waves:               IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)

                         Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (9005 MHz) (level 3)

                         Immunity Conducted Disturbance: IEC61000-4-6:               10 V (0.15 to 80 MHz) (level 3)

                         Immunity Burst:               IEC61000-4-4:                 2 kV power-line (level 3)

                                                                                     2 kV I/O signal-line (level 4)

                         Immunity Surge:               IEC61000-4-5:                 1 kV line to line (level 3)

                                                                                     2 kV line to ground (level 3)

Case color               Light Gray (Munsell 5Y7/1)

Degree of protection     IP40 (panel surface)

Weight                   Approx. 120 g

Note: Refer to the Life-test Curve.

                 http://www.ia.omron.com/                                 (c)Copyright OMRON Corporation 2007 All Rights Reserved.           15
                                                                                                                                       H3CR-H

Life-test CurveSwitching operations ( 103)

       10,000
         5,000

                              1,000            30 VDC L/R = 7 ms                Reference:   A maximum current of 0.15 A can be switched at 125 VDC (cos = 1)
                                500                           250 VAC/30 VDC                 and a maximum current of 0.1 A can be switched if L/R is 7 ms. In
                                                              (cos = 1)                      both cases, a life of 100,000 operations can be expected.
                               100                                                           The minimum applicable load is 10 mA at 5 VDC for H3CR-H8L/-HRL
                                     250 VAC (cos = 0.4)                                     and 100 mA at 5 VDC for H3CR-H8RL (failure level: P).

                                           Load current (A)

Connections

Block Diagrams

Without Reset Input (H3CR-H8L)

                                                                                             Time range/
                                                                                             unit selector

                                     AC (DC) input  Power supply                Oscillation  Counting       Output
                                                    circuit                     circuit      circuit        circuit

                                                             Power failure                                  Indicator  LCD  Output
                                                             detection circuit                              circuit         indicator

With Reset Input (H3CR-H8RL/-HRL)

                                                                                             Time range/
                                                                                             unit selector

                                     AC (DC) input  Power supply                Oscillation  Counting       Output
                                                    circuit                     circuit      circuit        circuit

                                                Power failure                                               Indicator  LCD  Output
                                                detection circuit                                           circuit         indicator

                                     Reset input                                             Input circuit

I/O Functions

Inputs                               Reset           Turns off the control output and resets the elapsed time.
Outputs                              Control output
                                                     Operates instantaneously when the power is turned on and time-limit resets when the set time is up
                                                     after the power is turned off.

                                     http://www.ia.omron.com/                                               (c)Copyright OMRON Corporation 2007 All Rights Reserved.  16
                                                                                               H3CR-H

Terminal Arrangement

Note: DC models, including 24 VAC/DC models, have polarity.

8-pin Models                                          With Reset Input (H3CR-H8RL)
Without Reset Input (H3CR-H8L)

                                                             Reset
                                                             input

                            Power supply                                Power supply

11-pin Model                                          Note: Leave terminal 3 open. Do not use
With Reset Input (H3CR-HRL)                                     them as relay terminals.

                                         Reset input

                     Power supply

Note: Leave terminal 6 open. Do not use
          them as relay terminals.

http://www.ia.omron.com/                                            (c)Copyright OMRON Corporation 2007 All Rights Reserved.  17
                                                                                                                            H3CR-H

Operation

Timing Chart

t: Set time
Rt: Minimum power ON time (S-series: 0.1 s min.; M-series: 2 s min.)

      If the power ON time is less than this value, the Timer may not operate (i.e., output may not turn ON).

            Model                                                 Timing chart            Rt
H3CR-H8L                                                                                              t
                                                               Rt
                                                 ON                                    t

                   Power

                   (See note) OFF

                   Output (1 - 3)

                   Output (1 - 4)
                   Output (8 - 6)

                   Output (8 - 5)

                   Output                        Lit
                   indicator                     Not lit

H3CR-H8RL                                                        Rt                       Rt
                                                                               t                      t
                   Power                              ON
                   (See note)                         OFF      0.05 s min.

                                                                                                               0.05 s min.

                   Reset input ON (Short-circuited)
                                   OFF (Open)

                   Output (8 - 6)

                   Output (8 - 5)

                   Output                             Lit
                   indicator                          Not lit

H3CR-HRL                                                         Rt                       Rt
                                                                                  t                   t
                   Power                     ON
                                                               0.05 s
                   (See note) OFF                              min.

                                                                                                               0.05 s min.

                   Reset input

                   Output (1 - 3)

                   Output (1 - 4)
                   Output (11 - 9)

                   Output (11 - 8)

                   Output                    Lit
                   indicator                 Not lit

Note: If the power is turned ON until the set time is up, the timer will be retriggered.

                   http://www.ia.omron.com/                                               (c)Copyright OMRON Corporation 2007 All Rights Reserved.  18
                                                                                                                                                                                             H3CR-H

Nomenclature

                                         Output indicator (red)
                                                                 Scale range display windows

                                               Time range selector (select                                                                             Time setting knob (for setting
                                               one from 0.6, 1.2, 6, and 12 at                                                                         power OFF-delay time)
                                               full scale)
                                                                                                            Time unit display
Dimensions                                                                                                  S-series: sec
                                                                                                            M-series: min
Note: All units are in millimeters unless otherwise indicated.
                                                                                                                     15                        78.0
H3CR-H8L
H3CR-H8RL                                                                                                            6   63.7                        0.7

                                                                                                 48

                                    48                                                                      39 dia.                                       44.8 44.8
                                                                                                                                                                       8 pins

H3CR-HRL

                                              48                                                                     15                        78.0

                                                                                                                     6   63.7                        0.7

                                    48                                                                      39 dia.                                       44.8 44.8
                                                                                                                                                                        11 pins

Dimensions with Front Connecting Socket                                                                              Dimensions with Back Connecting Socket
P2CF-08-@/P2CF-11-@                                                                                                  P3G-08/P3GA-11

                                                                                                                                         92.9             15                           92.9
                                                                                                                     15
                                                                                                                                                                                       91.4
                                                                                                                                        86.4
        H3CR-H8@L                   H3CR-HRL
                                                                                                                                    H3CR-
101.3*             99    112.2*                                                                      109.9                          H8@L

        P2CF-08    2.3*             P2CF-11                                                          2.3*                            P3G-08                         H3CR-HRL
                                                                                                                         Y92F-30
        P2CF-08-E                P2CF-11-E                                                                                                                               P3GA-11
                                                                                                                                        (When                 Y92F-30
                                                                                                                                        Y92A-48G
                                                                                                                                        mounted)                             (When
                                                                                                                                                                             Y92A-48G
                                                                                                                                                                             mounted)

*These dimensions vary with the kind of DIN track (reference value).

          http://www.ia.omron.com/                                                                                       (c)Copyright OMRON Corporation 2007 All Rights Reserved.            19
                                                                                                                           H3CR-H

Safety Precautions (H3CR-H)

Note: The undermentioned is common for all H3CR-H models.

Power Supplies                                                              Wiring

The H3CR-H has a large inrush current; provide sufficient power             The H3CR-H has a high impedance circuit. Therefore, the H3CR-H
supply capacity. If the power supply capacity is too small, there may       may not be reset if the H3CR-H is influenced by inductive voltage. In
be delays in turning ON the output.                                         order to eliminate any influence of inductive voltage, the wires
                                                                            connected to the H3CR-H must be as short as possible and should
With the H3CR-H@RL, for the power supply of an input device, use            not be installed alongside power lines. If the H3CR-H is influenced by
an isolating transformer, of which the primary and secondary                inductive voltage that is 30% or more of the rated voltage, connect a
windings are mutually isolated and the secondary winding is not             CR filter with a capacitance of approximately 0.1 F and a resistance
grounded.                                                                   of approximately 120  or a bleeder resistor between the power
                                                                            supply terminals. If there is any residual voltage due to current
Correct                                                                     leakage, connect a bleeder resistor between the power supply
                                                                            terminals.
                    H3CR-H@RL
           4*, 7 Input terminal 10, 7*

                                    2, 2*            Power supply            Operation

           1*, 5

                                                  *:H3CR-H8RL               An interval of 3 s minimum is required to turn on the H3CR-H after
                                                                            the H3CR-H is turned off. If the H3CR-H is turned on and off
                                        Isolation transformer is required.  repeatedly with an interval of shorter than 3 s, abnormal heating or
                                                                            burning may occur in internal elements.

                                                                                     3 s min.

                  Input device                                              Power

Incorrect

                            H3CR-H@RL                                                      Output
                                                                                           state 1
                     4*, 7              10, 7*
                                                                                           Output
                     1*, 5       Input               Power                                 state 2
                                terminal 2, 2*       supply
                                                                            After the forced reset function of the H3CR-H is activated, an interval
                                                     *:H3CR-H8RL            of 3 s minimum is required to activate the forced reset function again.
                                                                            If the forced reset function is activated repeatedly with an interval of
                                                                            shorter than 3 s, the internal parts of the H3CR-H may deteriorate
                                                                            and the H3CR-H may malfunction.

                     Input device Isolation                                 Power
                                        transformer
                                                                            Reset
Input/Output (H3CR-H@RL)                                                   input       3 s min.  3 s min.

An appropriate input is applied to the input signal terminal of the                            Output
Timer when the input terminal for the input signal is short-circuited.
Do not attempt to connect any input terminal to any terminal other          If it is required that the output be turned on repeatedly with an
than the input terminal or to apply voltage across other than the           interval of shorter than 3 s, consider use of the H3CR-A in mode D
specified input terminals or the internal circuits of the Timer may be      (signal OFF-delay).
damaged.
                                                                             Others
The H3CR-H@RL uses transformerless power supply. When
connecting a relay or transistor as an external signal input device,        If the H3CR-H is dropped or experiences some other kind of shock,
pay attention to the following points to prevent short-circuiting due to    because a latching relay is used for output, contacts may be reversed
a sneak current to the transformerless power supply.                        or go into a neutral state. If the H3CR-H is dropped, reconfirm correct
                                                                            operation.
If input is made simultaneously from one input contact or a transistor
to the H3CR-H and a Timer whose common input terminals are used
as power terminals, such as the H3CR-A, a short-circuit current will
be generated. Either input through isolated contacts, or isolate the
power supply for one of the Timers.

                  H3CR-H@RL

           4*, 7                10, 7*

           1*, 5                2, 2*

                                                     Short-circuit current

           G. S. R.             10

           5 67

                     H3CR-A 2

                                                       *: H3CR-H8RL

           ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
           To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                             In the interest of product improvement, specifications are subject to change without notice.

                     http://www.ia.omron.com/                               (c)Copyright OMRON Corporation 2007 All Rights Reserved.                  20
Safety Precautions for All Timers

Refer to the Safety Precautions for individual Timers for precautions specific to each Timer.

                           !WARNING                                        Normal operation may not be possible in locations subject to
                                                                             sulfidizing gas, such as in sewer systems or waste incinerators.
The following Timers contain lithium batteries that are                      OMRON does not market any Timers or other control devices for
not explosion proof.                                                         operation in atmospheres containing sulfidizing gas. Seal the Timer
                                                                             so that sulfidizing gas will not enter it. If sealing is not possible,
1. Timers with Built-in Batteries: H5L                                       OMRON does provide special Timers with improved resistance to
    The Timer contains a lithium battery, which may occasionally             sulfidizing gas. Ask your OMRON representative for details.
    ignite or rupture. Do not disassemble, deform under pressure,
    heat to 100C or higher, or incinerate the Timer.                      Power Supply

2. Timers with Replaceable Batteries: Y92S-20 (for H5CN-M)                  Be sure that the voltage applied is within the specified range,
    The battery may occasionally rupture, ignite, or leak fluid. Do          otherwise the internal elements of the Timer may be damaged.
    not short the positive and negative terminals. Do not charge,
    disassemble, deform under pressure, or throw the battery into a         Install a switch or circuit breaker that allows the operator to
    fire. If a non-specified battery is used, the battery may leak fluid     immediately turn OFF the power, and label it to clearly indicate its
    or rupture, occasionally resulting in equipment failure or minor         function.
    injury. Use only the specified battery.
                                                                            Maintain voltage fluctuations    Allowable
                                                                             in the power supply within     Voltage Range
                                                                             the specified range.

!CAUTION

The following Timers contain lithium batteries that are                     Use a commercial power supply for the power supply voltage input
explosion proof.                                                             to models with AC inputs.
                                                                             Inverters with an output frequency of 50/60 Hz are available, but
     Timers with Built-in Batteries: H5BR, H5AN-4DM, H5S, H5F, and           the rise in the internal temperature of the Timer may result in
                                            H4KV                             ignition or burning. Do not use an inverter output for the power
                                                                             supply of the Timer.
     The Timer contains a lithium battery, which may occasionally
     ignite or rupture. Do not disassemble, deform under pressure,          The Timers listed below cannot be directly turned ON and OFF by
     heat to 100C or higher, or incinerate the Timer.                       using an AC 2-wire proximity sensor to turn the Timer's power
                                                                             supply ON and OFF.
Precautions for Safe Use                                                    Use the following countermeasure when using an AC 2-wire
                                                                             proximity sensor with the Timer. (The power supply circuit in the
Operating Environment                                                        Timer uses half-wave rectification. Only a half AC wave is supplied
                                                                             to the proximity sensor, which may cause operation to be unstable.)
Use the Timer within the ratings specified for ambient operating
  temperature and ambient operating humidity for each model.                Applicable Models

Store the Timer with the specified temperature range for each              H3Y, H3YN, H3RN, H3CA-8, RD2P, and H3CR(-A, -A8, -AP, -F, and
  model. If the Timer has been stored at a temperature of less than          -G)
  -10C, allow the Timer to stand at room temperature for at least 3
  hours before using it.                                                    Countermeasure

Use the Timer within the performance specified for water and oil           Wire through a relay and use the relay contacts to turn the power
  exposure for each model.                                                   supply ON and OFF.

Do not use the Timer in locations subject to shock and vibration.          Confirm the stability of operation after making the connections.
  Long-term usage in such locations may damage the Timer due to
  stress.                                                                   Install protective measures (such as earth leakage breakers, wiring
  Magnetic contactors generate a shock of 1,000 to 2,000 m/s2 when           breakers, or fuses) on the power supply side according to any
  switching a load. When mounting to DIN Track, separate magnetic            applicable laws or regulations.
  contactors from the Timer so that the Timer is not subjected to
  vibration and shock. Use anti-vibration rubber.

Do not use the Timer in locations subject to excessive dust,
  corrosive gases, or direct sunlight.

Do not use organic solvents (such as paint thinner or benzine),
  strong alkalis, or strong acids because they will damage the
  external finish of the Timer.

Separate the input devices, input wiring, and Timer as far as
  possible from sources of noise and power lines carrying noise.

When using the Timer in environments subject to large amounts of
  static electricity (e.g., pipes carrying molding materials, powders, or
  fluid materials), separate the Timer as far as possible from the
  sources of static electricity.

Do not remove the external case from the Timer.
Do not use the Timer in locations where condensation may occur

  due to high humidity or sudden temperature changes.
  Condensation inside the Timer may result in malfunction or
  damage to Timer elements.
The life of internal parts may be reduced if Timers are mounted in
  close proximity to each other.
Resin and rubber parts (e.g., rubber packing) may deteriorate,
  shrink, or harden depending on the operating environment (e.g.,
  subjected to corrosive gases, ultraviolet light, or high
  temperatures). We recommend periodic inspection and
  replacement.

http://www.ia.omron.com/                                                   (c)Copyright OMRON Corporation 2007 All Rights Reserved.           C-1
Correctly Handling Input Signals                                          Other Precautions

Malfunction due to noise may occur if input wiring is placed in the       Confirm that you have the correct model before using it.
same duct or conduit as power lines or high-voltage lines. Separate
input wiring from power lines and wire them in a separate system.          Be sure that all terminals are wired correctly.
Also, use shielded cables, use metal conduits, and keep wiring
distances as short as possible.                                           Always test the output status with a tester before using a Timer with
                                                                            a built-in keep relay (e.g., the H3CR-H and H3DE-H). Shock
Timers with Relays                                                          resulting from dropping the Timer during transport or handling may
                                                                            cause the output contacts to reverse or to be in a neutral status.
Do not connect a load that exceeds contact ratings, such as the
  switching capacity (contact voltage or contact current). Insulation      Leaving the Timer with outputs ON at a high temperature for a long
  faults, contact welding, contact faults, and other failures to achieve    time may hasten the degradation of internal parts (such as
  specified performance may occur and the relay may be damaged or           electrolytic capacitors). Use the Timer in combination with relays
  may burn.                                                                 and avoid leaving the Timer with the output turned ON for an
                                                                            extended period of time (e.g., for more than a month).
Continued use with deteriorated performance may ultimately result         Reference Example (Use the Timer as shown below.)
  in insulation breakdown between circuits or relay burning. The life
  of the built-in relay is greatly affected by switching conditions.         X2/b  T/a  X1/a  X1/a
  Before using the Timer, test operation under actual application
  conditions and confirm that the switching frequency presents no         T        X1         X2    X Auxiliary relay
  problems in performance.
                                                                                                                               (e.g., MY Relays)
Electrical life depends on the type of load, switching frequency, and
  ambient environment. Observe the following precautions when             Be sure that only a qualified worker (e.g., an electrical engineer)
  using the Timer. When switching a DC load, contact transfer may           performs electrical work for the Timer.
  cause the contacts to stick or may cause contact failure. Confirm
  applicability and consider using a surge absorbing element. When
  switching at high frequencies, heat generated by arcing may cause
  contacts to melt or may cause metal corrosion. Consider
  connecting an arc absorbing element, reducing the switching
  frequency, or lowering the humidity.

The surge current depends on the type of load, which also affects
  contact switching frequency and the number of operations. Check
  the rated current and the surge current, and design the circuits with
  sufficient margin.

Resistive load Solenoid load Motor load           Incandescent
                                                    lamp load
Rated current  10 to 20 times    5 to 10 times
               the rated         the rated       10 to 20 times
               current           current         the rated
                                                 current

Sodium light   Capacitor          Transformer     Mercury light
     loads        loads                loads           loads

1 to 3 times the 20 to 40 times  5 to 15 times   1 to 3 times the
                                 the rated load  rated load
rated load     the rated load

Arcing when switching and relay heating may result in ignition or
  explosion. Do not use the Timer in atmospheres subject to
  inflammable or explosive gases.

Contact faults may occur. Do not use the Timer in atmospheres
  subject to sulfidizing gas, chloride gas, or silicon gas.

The switching capacity for DC voltage loads is lower than that for
  AC voltage loads.

Timers with Non-contact Outputs

Short faults or open faults may occur due to destruction of the
  output element. Do not use the Timer for a load that exceeds the
  rated output current.

Short faults or open faults may occur due to destruction of the
  output element from reverse electromotive force. When using the
  Timer for a DC inductive load, always connect a diode as a
  countermeasure against reverse electromotive force.

               ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
               To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                                 In the interest of product improvement, specifications are subject to change without notice.

               http://www.ia.omron.com/                                   (c)Copyright OMRON Corporation 2007 All Rights Reserved.                 C-2
                                                                 Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.

                                                      Warranty and Limitations of Liability
WARRANTY

OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if
specified) from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL
LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR
STRICT LIABILITY.

In no event shall responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

                                                             Application Considerations
SUITABILITY FOR USE

OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the product.

At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:

Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.

Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety
   equipment, and installations subject to separate industry or government regulations.

Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

                                                                        Disclaimers
CHANGE IN SPECIFICATIONS

Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the product may be changed without any notice. When in doubt, special model numbers may be assigned to fix
or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased product.

DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

ERRORS AND OMISSIONS
The information in this catalog has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.

PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent
the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.

PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.

COPYRIGHT AND COPY PERMISSION
This catalog shall not be copied for sales or promotions without permission.

This catalog is protected by copyright and is intended solely for use in conjunction with the product. Please notify us before copying or reproducing this
catalog in any manner, for any other purpose. If copying or transmitting this catalog to another, please copy or transmit it in its entirety.

OMRON Corporation                                                                                                                                      2007. 3
                               In the interest of product improvement, specifications are subject to change without notice.
Industrial Automation Company
                                                      (c)Copyright OMRON Corporation 2007 All Rights Reserved.
http://www.ia.omron.com/
This datasheet has been downloaded from:
            datasheet.eeworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn