timers analog solid state

参数

Manufacturer: Omron
Product Category: Timers
RoHS: Yes
Brand: Omron Automation and Safety
Series: H3CR
Factory Pack Quantity: 1
Part # Aliases: 24-48VAC/12-48VDC 3137960 H3CR-A H3CRA2448VAC1248VDC

H3CR-A-AC24-48/DC12-48器件文档内容

Solid-state Multi-functional Timers                               CSM_H3CR-A_DS_E_6_2

H3CR-A                                                                      LR

Multiple Operating Modes and Multiple Time
Ranges. DIN 48 x 48-mm Multifunctional
Timer with Wide AC/DC Power Supply Range
for Both High and Low Voltages.

A wide AC/DC power supply range greatly reduces the number
of timer models kept in stock.

A wide range of applications with multiple operating modes, six
modes for 11-pin models and four modes for 8-pin models.

Ecological design with reduced current consumption.
Easy sequence checking with instantaneous outputs for a zero

set value.
Length of 80 mm or less when panel-mounted with a P3GA-11

Socket (H3CR-A8E, 100 to 240 VAC, 100 to 125 VDC)
PNP input models available.
Standards: UL, CSA, NK, LR, EN 61812-1, and CE Marking.

Model Number Structure

Model Number Legend

Note: This model number legend includes combinations that are not available. Before ordering, please check the List of Models on page 2 for avail-
        ability.

H3CR-A@ @ @ - @ @

                  1 23 45

1. Number of Pins

None: 11-pin models

8: 8-pin models

2. Input Type for 11-pin Models

None: No-voltage input (NPN type)

P: Voltage input (PNP type)

3. Output

None: Relay output (DPDT)

S: Transistor output (NPN/PNP universal use)

E: Relay output (SPDT) with instantaneous relay output (SPDT)

4. Suffix

300: Dual mode models (signal ON/OFF-delay and one-shot)

301: Double time scale (range) models (0.1 s to 600 h)

5. Supply Voltage

100-240AC/100-125DC: 100 to 240 VAC/100 to 125 VDC

24-48AC/12-48DC: 24 to 48 VAC/12 to 48 VDC

24-48AC/DC:          24 to 48 VAC/VDC (Only for H3CR-A8E)

                                                                                                                                                    1
                                                                                                                   H3CR-A

Ordering Information

List of Models

Note: 1. Specify both the model number and supply voltage when ordering.
               Example: H3CR-A 100-240AC/100-125DC

                                       Supply voltage

2. The operating modes are as follows

         A: ON-delay                   D: Signal OFF-delay

         B: Flicker OFF start          E: Interval

         B2: Flicker ON start          G: Signal ON/OFF-delay

         C: Signal ON/OFF-delay        J: One-shot

11-pin Models

         Output                Supply voltage       Input type            Time range           Operating mode             Model
                                                                                                  (See note 2)       (See note 1.)
Contact          100 to 240 VAC (50/60 Hz)/         No-voltage input 0.05 s to 300 h
                 100 to 125 VDC                                                            Six multi-modes: A, B,  H3CR-A
Transistor                                                                                 B2, C, D, E
(Photocoupler)   24 to 48 VAC (50/60 Hz)/
                 12 to 48 VDC                                                              Dual-modes: G, J        H3CR-A-300

                 100 to 240 VAC (50/60 Hz)/         Voltage input                          Six multi-modes: A, B, H3CR-AP
                 100 to 125 VDC                                                            B2, C, D, E

                 24 to 48 VAC (50/60 Hz)/           No-voltage input 0.1 s to 600 h                                H3CR-A-301
                 12 to 48 VDC
                                                                          0.05 s to 300 h                          H3CR-AS
                 100 to 240 VAC (50/60 Hz)/
                 100 to 125 VDC

                 24 to 48 VAC (50/60 Hz)/
                 12 to 48 VDC

                 100 to 240 VAC (50/60 Hz)/
                 100 to 125 VDC

                 24 to 48 VAC (50/60 Hz)/
                 12 to 48 VDC

                 24 to 48 VAC (50/60 Hz)/
                 12 to 48 VDC

8-pin Models

         Output                Supply voltage       Input type            Time range           Operating mode             Model
                                                                                                  (See note 2)       (See note 1.)
Contact          100 to 240 VAC (50/60 Hz)/         No-input available 0.05 s to 300 h
                 100 to 125 VDC                                                            Four multi-modes: A,    H3CR-A8
                                                                                           B2, E, J
                 24 to 48 VAC (50/60 Hz)/                                                  (Power supply start)
                 12 to 48 VDC

                 100 to 240 VAC (50/60 Hz)/                               0.1 s to 600 h                           H3CR-A8-301
                 100 to 125 VDC

                 24 to 48 VAC (50/60 Hz)/
                 12 to 48 VDC

Transistor       24 to 48 VAC (50/60 Hz)/                                 0.05 s to 300 h                          H3CR-A8S
(Photocoupler)   12 to 48 VDC                                                                                      H3CR-A8E

Time-limit contact and 100 to 240 VAC (50/60 Hz)/
instantaneous contact 100 to 125 VDC

                 24 to 48 VAC/VDC (50/60 Hz)

                                                                                                                                    2
                                                                                               H3CR-A

Accessories (Order Separately)

Adapter, Protective Cover, Hold down Clip, Setting Ring and Panel Cover

                                Name/specifications                                    Models
Flush Mounting Adapter
                                                            Y92F-30
Protective Cover                 For PF085A Socket          Y92F-73
Hold-down Clip (Sold in sets of  For PL08 and PL11 Sockets  Y92F-74
two)                                                        Y92A-48B
                                 Light gray (5Y7/1)         Y92H-8
Setting Ring A                   Black (N1.5)               Y92H-7
Setting Ring B and C             Medium gray (5Y5/1)        Y92S-27
Panel Cover                                                 Y92S-28
                                                            Y92P-48GL
                                                            Y92P-48GB
                                                            Y92P-48GM

Sockets

         Timer                                  Connection              Round Sockets                    Models
          Pin                    Front Connecting                            Terminal  P2CF-11
                                 Back Connecting                                       P2CF-11-E
11-pin                                                      DIN track mounting
                                 Front Connecting           DIN track mounting         P3GA-11
8-pin                                                       (Finger-safe type)         PL11
                                 Back Connecting            Screw terminal             PL11-Q
                                                            Solder terminal            PLE11-0
                                                            Wrapping terminal          P2CF-08
                                                            PCB terminal               P2CF-08-E
                                                            DIN track mounting
                                                            DIN track mounting         PF085A
                                                            (Finger-safe type)         P3G-08
                                                            DIN track mounting         PL08
                                                            Screw terminal             PL08-Q
                                                            Solder terminal            PLE08-0
                                                            Wrapping terminal
                                                            PCB terminal

Note: 1. The P2CF-@@-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals.
        2. The P3GA-11 and P3G-08 Socket can be used together with the Y92A-48G Terminal Cover to implement finger protection.
        3. For details, refer to Socket and DIN Track Products.

Terminal Cover

                                       Application                             Model                      Remarks
For back connecting socket                                  Y92A-48G                           For P3G-08 and P3GA-11

Note: For details, refer to Socket and DIN Track Products.

                                                                                                                                3
                                                                                                                             H3CR-A

Specifications

General

            Item                H3CR-A/-AS     H3CR-AP                            H3CR-A8/-A8S                               H3CR-A8E

Operating mode          A: ON-delay                                   A: ON-delay (power supply start)
                        B: Flicker OFF start                          B2: Flicker ON start (power supply start)
                        B2: Flicker ON start                          E: Interval (power supply start)
                        C: Signal ON/OFF-delay                        J: One-shot (power supply start)
                        D: Signal OFF-delay
                        E: Interval
                        G: Signal ON/OFF-delay (Only for H3CR-A-300)
                        J: One-shot (Only for H3CR-A-300)

Pin type                11-pin                                        8-pin

Input type              No-voltage input       Voltage input          ---

Time-limit output type  H3CR-A/-A8/-AP: Relay output (DPDT)                                           Relay output (SPDT)
                        H3CR-AS/-A8S: Transistor output (NPN/PNP universal)*

Instantaneous output type ---                                                                         Relay output (SPDT)

Mounting method         DIN track mounting, surface mounting, and flush mounting

Approved standards      UL508, CSA C22.2 No.14, NK, Lloyds
                        Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
                        Output category according to EN60947-5-1 for Timers with Contact Outputs.
                        Output category according to EN60947-5-2 for Timers with Transistor Outputs.

*The internal circuits are optically isolated from the output. This enables universal application as NPN or PNP transistor.

Time Ranges

Note: When the time setting knob is turned below "0" until the point where the time setting knob stops, the output will operate instantaneously at
        all time range settings.

Standard (0.05-s to 300-h) Models

         Time unit                    s (sec)              min (min)              h (hrs)                      10 h (10 hrs)
                        0.05 to 1.2            0.12 to 1.2                                            1.2 to 12
Full scale 1.2          0.3 to 3                                                                      3 to 30
                        1.2 to 12                                                                     12 to 120
setting     3           3 to 30                                                                       30 to 300

            12

            30

Double (0.1-s to 600-h) Models

         Time unit                    s (sec)              min (min)              h (hrs)                      10 h (10 hrs)
                        0.1 to 2.4             0.24 to 2.4                                            2.4 to 24
Full scale 2.4          0.6 to 6                                                                      6 to 60
                        2.4 to 24                                                                     24 to 240
setting     6           6 to 60                                                                       60 to 600

            24

            60

                                                                                                                                                    4
                                                                                                                    H3CR-A

Ratings

Rated supply voltage (See notes 1, 2, and 5.) 100 to 240 VAC (50/60 Hz)/100 to 125 VDC, 24 to 48 VAC (50/60 Hz)/12 to 48 VDC (24 to 48 VAC/VDC for H3CR-
                                                                 A8E) (See note3.)

Operating voltage range  85% to 110% of rated supply voltage (90% to 110% at 12 VDC)

Power reset              Minimum power-opening time: 0.1 s

Input                    No-voltage Input

                         ON impedance:       1 k max.

                         ON residual voltage: 1 V max.

                         OFF impedance:      100 k min.

                         Voltage Input

                         Max. permissible capacitance between inputs lines (terminals 6 and 7): 1,200 pF

                         Load connectable in parallel with inputs (terminals 6 and 7).

                         100 to 240 VAC/100 to 125 VDC

                         High (logic) level: 85 to 264 VAC/85 to 137.5 VDC

                         Low (logic) level: 0 to 10 VAC/0 to 10 VDC

                         24 to 48 VAC/12 to 48 VDC

                         High (logic) level: 20.4 to 52.8 VAC/10.8 to 52.8 VDC

                         Low (logic) level: 0 to 2.4 VAC/0 to 1.2 VDC

Power consumption        H3CR-A/-A8

                         100 to 240 VAC/100 to 125 VDC                                   Relay OFF: approx. 1.3 VA (1.1 W)
                            (When at 240 VAC, 60 Hz)                                       Relay OFF: approx. 0.2 W
                                           Relay ON: approx. 2.0 VA (1.6 W)
                                                                                           Relay OFF: approx. 1.8 VA (1.7 W) (See note 4.)
                         24 to 48 VAC/12 to 48 VDC                                       Relay OFF: approx. 0.3 W (See note 4.)
                            (When at 24 VDC)
                                           Relay ON: approx. 0.8 W

                         H3CR-AP (See note 3)

                         100 to 240 VAC/100 to 125 VDC
                            (When at 240 VAC, 60 Hz)
                                           Relay ON: approx. 2.5 VA (2.2 W) (See note 4.)

                         24 to 48 VAC/12 to 48 VDC
                            (When at 24 VDC)
                                           Relay ON: approx. 0.9 W (See note 4.)

                         H3CR-A8E

                         100 to 240 VAC/100 to 125 VDC
                            (When at 240 VAC, 60 Hz)
                                           Relay ON/OFF: approx. 2 VA (0.9 W)

                         24 to 48 VAC/VDC
                            (When at 24 VDC)
                                           Relay ON/OFF: approx. 0.9 W

                         H3CR-AS/-A8S

                         24 to 48 VAC/12 to 48 VDC
                            (When at 24 VDC)
                                           Output ON: 0.3 W Output OFF: 0.2 W

Control outputs          Time limit contacts: 5 A at 250 VAC/30 VDC, 0.15 A at 125 VDC, resistive load (cos = 1)

                         Transistor output:  Open collector (NPN/PNP), 100 mA max. at 30 VDC max.,

                                             residual voltage: 2 V max.

                         Instantaneous contact: 5 A at 250 VAC/30 VDC, 0.15 A at 125 VDC, resistive load (cos = 1)

Note: 1. DC ripple rate: 20% max. (A single-phase, full-wave-rectification power supply can be used).

        2. Do not use an inverter output as the power supply. Refer to Safety Precautions for All Timers for details.

        3. Models with 24-to-48-VAC or 12-to-48-VDC power supply have inrush current. Caution is thus required when turning ON and OFF power
            to the Timer with a non-contact output from a device such as a sensor. (Models with an inrush current of approximately 50 mA and a 24-
            VDC power supply are available (the H3CR-A-302 and H3CR-A8-302).)

        4. The values are for when the terminals 2 and 7 and terminals 10 and 6 are short-circuited, and include the consumption current of the
            input circuit.

        5. Refer to Safety Precautions for All Timers when using the Timer together with a 2-wire AC proximity sensor.

                                                                                                                                                          5
                                                                                                                                          H3CR-A

Characteristics

Accuracy of operating 0.2% FS max. (0.2%10 ms max. in a range of 1.2 s or 3 s)
time

Setting error                         5% FS 50 ms (See note 1)

Reset time                            Min. power-opening time: 0.1 s max.

                                      Min. pulse width:                        0.05 s (H3CR-A/-AS)

Reset voltage                         10% max. of rated supply voltage

Influence of voltage                  0.2% FS max. (0.2%10 ms max. in a range of 1.2 s or 3 s)

Influence of temperature 1% FS max. (1%10 ms max. in a range of 1.2 s or 3 s)

Insulation resistance 100 M min. (at 500 VDC)

Dielectric strength                   2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-
                                      current-carrying metal parts)
                                      2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between control output terminals and operating circuit)
                                      2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)

                                      1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)

                                      2,000 VAC, 50/60 Hz for 1 min (between input and control output terminals and operation circuit) for H3CR-AP

Impulse withstand                     3 kV (between power terminals) for 100 to 240 VAC/100 to 125 VDC, 1 kV for 24 to 48 VAC/12 to 48 VDC
voltage                               4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC/100 to
                                      125 VDC, 1.5 kV for 24 to 48 VAC/12 to 48 VDC and 24 to 48 VAC/VDC

Noise immunity                        1.5 kV (between power terminals) and 600 V (between no-voltage input terminals), square-wave noise by noise
                                      simulator (pulse width: 100 ns/1 s, 1-ns rise)

Static immunity                       Malfunction: 8 kV
                                      Destruction: 15 kV

Vibration resistance                  Destruction: 10 to 55 Hz with 0.75-mm single amplitude each in 3 directions for 2 hours each
                                      Malfunction: 10 to 55 Hz with 0.5-mm single amplitude each in 3 directions for 10 minutes each

Shock resistance                      Destruction: 1,000 m/s2 3 times each in 6 directions
                                      Malfunction: 100 m/s2 3 times each in 6 directions

Ambient temperature                   Operating: -10C to 55C (with no icing)
                                      Storage: -25C to 65C (with no icing)

Ambient humidity                      Operating: 35% to 85%

Life expectancy                       Mechanical: 20,000,000 operations min. (under no load at 1,800 operations/h)
                                      Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note 2)

EMC                                   (EMI)                                    EN61812-1

                                      Emission Enclosure:                      EN55011 Group 1 class A

                                      Emission AC Mains:                       EN55011 Group 1 class A

                                      (EMS)                                    EN61812-1

                                      Immunity ESD:                            IEC61000-4-2:            6 kV contact discharge (level 3)

                                                                                                        8 kV air discharge (level 3)

                                      Immunity RF-interference from AM Radio Waves:                     IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)

                                      Immunity RF-interference from Pulse-modulated Radio Waves:IEC61000-4-3: 10 V/m (9005 MHz) (level 3)

                                      Immunity Conducted Disturbance: IEC61000-4-6:                     10 V (0.15 to 80 MHz) (level 3)

                                      Immunity Burst:                          IEC61000-4-4:            2 kV power-line (level 3)

                                                                                                        2 kV I/O signal-line (level 4)

                                      Immunity Surge:                          IEC61000-4-5:            1 kV line to line (level 3)

                                                                                                        2 kV line to ground (level 3)

Case color                            Light gray (Munsell 5Y7/1)

Degree of protection IP40 (panel surface)

Weight                                Approx. 90 g

Note: 1. The value is 5% FS +100 ms to -0 ms max. when the C, D, or G mode signal of the H3CR-AP is OFF.
        2. Refer to the Life-test Curve.
        3. Relay output only.

Life-test Curve

Switching operations (x 103)  10,000
                               5,000

                              1,000            30 VDC L/R = 7 ms               Reference:  A maximum current of 0.15 A can be switched at 125 VDC (cos = 1)
                                500                            250 VAC/30 VDC              and a maximum current of 0.1 A can be switched if L/R is 7 ms. In
                                                               (cos = 1)                   both cases, a life of 100,000 operations can be expected.
                                100                                                        The minimum applicable load is 10 mA at 5 VDC (failure level: P).
                                      250 VAC (cos = 0.4)

                                            Load current (A)

                                                                                                                                                              6
                                                                                                       H3CR-A

Connections                                         Zero setting  Time range/     Operating
                                                    detection     unit selectors  mode selector
Block Diagrams                                     circuit

H3CR-A/AS
                                     AC (DC) input

         Power supply                               Oscillation   Counting        Output circuit
         circuit                                    circuit       circuit

         Reset input, start input, and gate input                 Input circuit   Indicator
                                                                                  circuit

                                                                                  Power-ON Output-ON
                                                                                  indicator indicator

H3CR-AP

         AC (DC) input                              Zero setting  Time range/     Operating
                                                    detection     unit selectors  mode selector
                                                    circuit

         Power supply                               Oscillation   Counting        Output circuit
         circuit                                    circuit       circuit

         Start                                                    Input circuit   Indicator
                                                                                  circuit

                                                                                  Power-ON Output-ON
                                                                                  indicator indicator

                                                                                                               7
                                                                                                 H3CR-A

H3CR-A8/A8S

                       AC (DC) input          Zero setting  Time range/     Operating
                                              detection     unit selectors  mode selector
                                              circuit

                          Power supply        Oscillation   Counting        Output circuit
                          circuit             circuit       circuit

                                                                            Indicator
                                                                            circuit

                                                                            Power-ON Output-ON
                                                                            indicator indicator

H3CR-A8E

                       AC (DC) input          Zero setting  Time range/     Operating
                                              detection     unit selectors  mode selector
                                              circuit

                          Power supply        Oscillation   Counting        Output circuit
                          circuit             circuit       circuit

                                                                            Indicator
                                                                            circuit

                                                                            Power-ON Output-ON
                                                                            indicator indicator

                                                                                Instantaneous
                                                                                output circuit

I/O Functions

Inputs (for -A/ Start     Starts time-measurement.
-AS models) Reset         Interrupts time-measurement and resets time-measurement value. No time-measurement is made and
                          control output is OFF while the reset input is ON.
Outputs   Gate            Prohibits time-measurement.
          Control output  Outputs are turned ON according to designated output mode when preset value is reached.

Note: H3CR-AP incorporates start input only.

                                                                                                                          8
                                                                                                                   H3CR-A

Terminal Arrangement

Note: The delayed contact of conventional Timers was indicated as

The contact symbol of the H3CR-A is indicated as      because its operating mode is six multi-modes (four multi-modes for the H3CR-A8).

11-pin Models                                                           8-pin Models

H3CR-A/-A-300/-A-301 (Contact Output)                                   H3CR-A8/-A8-301 (Contact Output)

Reset input
       Start input
              Gate input

                                        Power supply                                                 Power supply
H3CR-AS (Transistor Output)                                             H3CR-A8S (Transistor Output)

Reset input                                                                                          Power supply
       Start input
              Gate input                                                Note: Terminals 1, 3, 4, and 5 are empty. Terminals 2 and 7 are the
                                                                                same as for the H3CR-A8.

                                                                        H3CR-A8E (Contact Output)

                                        Power supply

Note: Terminals 1, 3, 4, and 8 are empty. Terminals 2, 5, 6, 7, and 10
        are the same as for the H3CR-A.

H3CR-AP (Contact Output)

Start input                                                                           Power supply

                                      Power supply

Note: 1. Terminal 5 is empty.
        2. Separate power supplies can be used for the Timer and in-
            puts.

                                                                                                                                             9
                                                                                                                   H3CR-A

Input Connections

H3CR-A/-AS

The inputs of the H3CR-A/-AS are no-voltage (short-circuit or open) inputs.

No-voltage Inputs                     Contact Input                          No-contact Input

No-contact Input                                                Timer

(Connection to NPN open                                                      (Connection to a voltage
collector output sensor.)                                                    output sensor.)

12 to 24 VDC                                                                 12 to 24 VDC           + DC power
(sensor power supply)                                                        (sensor power supply)  - supply

                       + DC power
                       - supply

                       Timer                                                                        Timer

Sensor

                                                                             Sensor

                        5 Gate                5 Gate                                                5 Gate
                        6 Start               6 Start                                               6 Start
                        7 Reset               7 Reset                                               7 Reset

                       2 Input (0 V)         2 Input (0 V)                                          2 Input (0 V)

Operates with transistor ON           Operates with relay ON                 Operates with transistor ON

No-voltage Input Signal Levels

No-contact  1. Short-circuit level
input       Transistor ON
            Residual voltage: 1 V max.
            Impedance when ON: 1 k max.

            2. Open level
            Transistor OFF
            Impedance when OFF: 100 k min.

Contact     Use contacts which can
input       adequately switch 0.1 mA at 5 V

                                                                                                                           10
                                                                                                                                                H3CR-A

H3CR-AP

The start input of the H3CR-AP is voltage input. (Voltage imposition or open)

Voltage Inputs                                      No-contact Input                                Contact Input
                                                    (Connection to NPN open
  No-contact Input                                  collector output sensor)

  (Connection to PNP open
  collector output sensor)

12 to 24 VDC           + DC power                         12 to 24 VDC           + DC power
(sensor power supply)  - supply                           (sensor power supply)  - supply

Sensor                    Timer                     Sensor                          Timer

                                                                                                    AC power supply                      Timer
                                                                                                                     DC power supply
                                   10 Power                                      10 Power                                             10  Power   (+)
                                        supply (+)                                   supply (+)                                           supply

                                   6 Start                                       6 Start                                              6 Start

                                   7 Input 0V                                    7 Input 0V                                           7 Input 0V

                                   2 Power                                       2  Power                                             2   Power
                                        supply                                      supply (-)                                            supply (-)
                                        (-)
                                                    Operates with NPN transistor ON                 Operates with relay ON
Operates with PNP transistor ON

                                                      Note: The input circuit is isolated from the  Note: Refer to the signal levels in the
                                                                power supply circuit. Thus, an NPN            following table and be aware of the
                                                                transistor can be connected.                  minimum applicable load of the relay.

Note: Before making connections, refer to Safety Precautions (H3CR-@).

Voltage Input Signal Levels

No-contact 1. Transistor ON

input    Residual voltage: 1 V max.

         The voltage between terminals 6 and 7 must be 10.8 VDC min.

         2. Transistor OFF
         Leakage current: 0.01 mA max.
         The voltage between terminals 6 and 7 must be 1.2 VDC max.

Contact  Use contacts that can adequately switch 0.1 mA at each
input    operating voltage.
         The voltage between terminals 6 and 7 with contacts ON or
         OFF must satisfy the specified value.

         Contacts ON
         100-to-240-VAC and 100-to-125-VDC models: 85 to 264 VAC
         or 85 to 137.5 VDC
         24-to-48-VAC and 12-to-48-VDC models: 20.4 to 52.8 VAC or
         10.8 to 52.8 VDC

         Contacts OFF
         100-to-240-VAC and 100-to-125-VDC models: 0 to 10 VAC or
         0 to 10 VDC
         24-to-48-VAC and 12-to-48-VDC models: 0 to 2.4 VAC or 0 to
         1.2 VDC

                                                                                                                                                       11
                                                                                                                                            H3CR-A

Operation

Timing Chart

Note: 1. The minimum power-opening time ("Rt") is 0.1 s.
        2. The minimum input pulse width (for start, reset) is 0.05 s.
        3. The letter "t" in the timing charts stands for the set time and "ta" means that the period is less than the time set.
        4. Power supply start in mode J is also possible for H3CR-A8/-A8E/-A8S/-A8-301 models.
        5. Refer to page 17 for application examples.

H3CR-A/-AS/-AP*

*H3CR-AP model incorporates start input only.

  Operating                                       Timing chart
     mode
                                    t          t                Basic operation
A: ON-delay  Power

             Start                                              Power

                            Reset                               Start
             Output relay (NC)
                                                                (See note)                t

                                                                Output

             Output relay (NO)                                  Note: Start input is invalid while the
             (Output indicator)                                           Timer is in operation.

B:              Power indicator                                 Basic operation
Flicker OFF
start                       Power                                  Power
                              Start
                                                                       Start     t           t     t                               t
                            Reset                               (See note)
             Output relay (NC)
             Output relay (NO)                                  Output
             (Output indicator)
                                                                   Note: Start input is invalid while
                Power indicator                                              the Timer is in operation.

B2:                                                             Basic operation
Flicker ON
start        Power

                                                                Power

                              Start                                    Start     t              t     t                                  t
                                                                (See note)
                            Reset
             Output relay (NC)                                       Output

             Output relay (NO)                                  Note: Start input is invalid while the
             (Output indicator)                                           Timer is in operation.

C:             Power indicator                                                Basic operation
Signal ON/
OFF-delay                   Power                                               Power
                              Start

                            Reset                                             Start          t     t                                  t     t

             Output relay (NC)                                                (See note)

             Output relay (NO)                                                Output
             (Output indicator)
                                                                              Note: Start input is valid and
                Power indicator                                                         retriggerable while the Timer
                                                                                        is in operation.

                                                                                                                                                    12
                                                                                                                         H3CR-A

  Operating                                                  Timing chart
     mode
                                                                                                  Basic operation
D:
Signal OFF-        Power
delay               Start

                                                                                                  Power

                              Reset                                                               Start
               Output relay (NC)
                                                                                          (See note)                  t
               Output relay (NO)
               (Output indicator)                                                                 Output

                 Power indicator                                                          Note: Start input is valid and
                                                                                                    retriggerable while the
                                                                                                    Timer is in operation.

E:                                                                                       Basic operation
Interval

                              Power                                                       Power
                                Start
                                                                                          Start           t
                              Reset
               Output relay (NC)                                                  (See note)

               Output relay (NO)                                                          Output
               (Output indicator)
                                                                                          Note: Start input is valid and
                  Power indicator                                                                   retriggerable while the
                                                                                                    Timer is in operation.

G:                                                                         Basic operation
Signal ON/
OFF-delay                     Power

                                Start                                      Power

                              Reset                                        Start
               Output relay (NC)
                                                                      (See note)  t         tt               t
               Output relay (NO)
               (Output indicator)                                          Output

                  Power indicator                                            Note: Start input is valid and
                                                                                       retriggerable while the Timer
                                                                                       is in operation.

J:                                                                                Basic operation
One-shot
output                        Power
                                Start
                                                                                  Power
                              Reset
                                                                                  Start
               Output relay (NC)
                                                                           (See note)             t          10.6 s
               Output relay (NO)
               (Output indicator)      10.6 s               10.6 s              Output                     (Fixed)
                                       (Fixed)               (Fixed)
                 Power indicator
                                                                                  Note: Start input is valid and
                                                                                            retriggerable while the
                                                                                            Timer is in operation.
                                                                                            (Previous start input will
                                                                                            be cancelled.)

Gate Signal Input

               t1                      t2

Power     ON
          OFF

Start ON
        OFF

Gate ON
        OFF

Reset ON
          OFF

Output ON
relay OFF

  Note: 1. This timing chart indicates the gate input in
                 operating mode A (ON-delay operation).

            2. The set time is the sum of t1 and t2.
            3. H3CR-AP model incorporates start input only.

                                                                                                                             13
H3CR-A8/-A8S                                                                                                                       H3CR-A

  Operating                           Timing chart                                                                                     t
     mode
             Power                                                                                                                                              v
A:
ON-delay                                                                                                                           10.6 s
                                                                                                                                   (Fixed)
             Output relay                             Basic operation
             (NC)
             Output relay                           Power
             (NO) (output                                                   t
             indicator)
                                                    Output
                  Power
B2:               indicator                         Basic operation
Flicker ON
start                Power                          Power

E:           Output relay                                   t        t          t
Interval     (NC)
                                                    Output
             Output relay
             (NO) (output
             indicator)

                  Power
                  indicator

                      Power

             Output relay                            Basic operation
             (NC)
                                                    Power
             Output relay                                                    t
             (NO) (output
             indicator)                             Output

J:                Power
One-shot          indicator
output
                     Power
                             10.6 s  10.6 s        Basic operation
             Output relay    (Fixed)  (Fixed)
             (NC)                                   Power
                                                                            t
             Output relay
             (NO) (output                           Output
             indicator)

                  Power
                  indicator

Note: 1. The minimum power-opening time ("Rt") is 0.1 s.
        2. The letter "t" in the timing charts stands for the set time and "ta" means that the period is less than the time set.

                                                                                                                                                                   14
H3CR-A8E                                                                                                                           H3CR-A

  Operating                                                    Timing chart                                                         t
     mode                                                                                                                           10.6 s
                                                                                                                                    (Fixed)
A:
ON-delay

             Power

             Output relay (NC)

             Output relay (NO)                                                       Basic operation
             (output indicator)
             Instantaneous                                                          Power
             output relay (NC)                                                                               t
             Instantaneous
             output relay (NO)                                                      Output

B2:            Power indicator
Flicker ON
start                       Power
             Output relay (NC)

                                                                             Basic operation

             Output relay (NO)                                               Power
             (output indicator)
             Instantaneous                                                           t                                      t  t
             output relay (NC)
             Instantaneous                                                   Output
             output relay (NO)
E:
Interval       Power indicator

                           Power

             Output relay (NC)

             Output relay (NO)                                                        Basic operation
             (output indicator)
             Instantaneous                                                           Power
             output relay (NC)                                                                               t
             Instantaneous
             output relay (NO)                                                       Output
             Power indicator
J:
One-shot                    Power
output
             Output relay (NC)

             Output relay (NO)       (Fixed)                   (Fixed)                  Basic operation
             (output indicator)
                                                                                     Power
             Instantaneous                                                                                     t
             output relay (NC)
             Instantaneous                                                           Output
             output relay (NO)

               Power indicator

Note: 1. The minimum power-opening time ("Rt") is 0.1 s.
        2. The letter "t" in the timing charts stands for the set time and "ta" means that the period is less than the time set.

Nomenclature

                                 Power indicator (green) (Flashes when Timer
                                 operates; lit when Timer stops operating)

                                                                                             Operating mode display window

          Output indicator (orange)                            Operating mode selector
          (Lit when output)                                    Select a mode from:
                                                               A, B, B2, C, D, and E (H3CR-A, -AP, and -AS) A,

                                                                    B2, E and J (H3CR-A8, -A8S, and -A8E) G
                                                                    and J (H3CR-A-300)

                                                               Scale range display windows

Time range selector (select one               Time setting     Time unit display window
from 1.2, 3, 12, and 30 at full               knob (set time)
scale; with the H3CR-A@-301,                                   Time unit selector (select one
select from 2.4, 6, 24, or 60 at                               from sec, min, hrs, and 10h)
full scale.)

                                                                                                                                   15
                                                                                                                                                               H3CR-A

Dimensions                                                                                                           15      66.6

Note: All units are in millimeters unless otherwise indicated.                                                       6       52.3

H3CR-A                                                                                                                             0.7
H3CR-AP
H3CR-AS                                                                                                     39 dia.                         44.8 44.8
                                                                                                                                        11 pins
                                                                                                    48

                                                                                48

H3CR-A8                                                                                                              15      66.6
H3CR-A8S
H3CR-A8E                                                                                                                 6   52.3

Dimensions with Set Ring                         48                                                                                0.7
                              48
                                                                                                            39 dia.                        44.8 44.8
                                                 50                                                                    16.5             8 pins
                              50
                                                                                                            42 dia.

Dimensions with Front Connecting Socket                                                                   Time Setting Panel cover
P2CF-08-@/P2CF-11-@                                                                                       Ring

                                                                                                        Dimensions with Back Connecting Socket
                                                                                                        P3G-08/P3GA-11

                                                                                                        15           81.5               15               81.5
                                                                                                                     80
                                                                                                                                                         75

        H3CR-A                H3CR-A8@

100.8*  H3CR-AS  98.5  89.9*             87.6                                                                     H3CR-A                    H3CR-A8@
        H3CR-AP                                                                                                   H3CR-AS                   + Adapter
                                                                                                                  H3CR-AP
                                                                                                                  +                         Y92F-30          P3G-08
                                                                                                                  Adapter
         P2CF-11 2.3*         P2CF-08    2.3*                                                                                                                 (When
        P2CF-11-E                                                                                                      P3GA-11                                Y92A-48G
                              P2CF-08-E                                                                     Y92F-30 (When                                     mounted)

                                                                                                                           Y92A-48G

                                                                                                                           mounted)

*These dimensions vary with the kind of DIN track (reference value).

                                                                                                                                                                        16
                                                                                                                                 H3CR-A

Application Examples (H3CR-A)

A Mode: ON-delay

ON-delay operation (A mode) is a basic mode.

1. Power-ON Start/Power-OFF Reset                                          3. Control of Integrated Time with Gate
                                                                             Signal
The Power-ON start/Power-OFF reset operation is a standard
operating method.                                                          With a gate signal, the Power-ON start operation and Signal start
                                                                           operation can be controlled (the operation can be interrupted).
                                                 t
Power (2 and 10)                                                                                                 t1          t2  t1 + t2: set time

Start (2 and 6)                                                            Power (2 and 10)

Reset (2 and 7)                                                            Start (2 and 6)

Control output: NC (8 and 11)                                                                   Gate (2 and 5)
                      NC (1 and 4)
                                                                           Control output: NC (8 and 11)
Control output: NO (9 and 11)                                                                    NC (1 and 4)
                      NO (1 and 3)

Power indicator                                                            Control output: NO (9 and 11)
                                                                                                 NO (1 and 3)
                                         Flashing
                                                    Lit
                                                                           Power indicator

Externally short-circuited                                                                                           Flashing    Lit

                                                                           Gate signal (The operation is interrupted with the
                                                                           gate signal if the Timer detects an abnormal signal.)

                                                                           Externally
                                                                           short-circuited

                                                                   Power                                                                      Power
                                                                   supply                                                                     supply

2. Signal Start/Signal Reset                                               B/B2 Mode: Flicker

The Signal start/Signal reset operation is useful for remote control of    The flicker operation in the B and B2 modes can be effectively
the Timer.                                                                 applied to lamp or buzzer (ON and OFF) alarms or the monitoring of
                                                                           an intermittent operation with a display.
Power (2 and 10)
   Start (2 and 6)                                                         1. Power-ON Start/Power-OFF Reset (in B
                                                                             Mode)
Reset (2 and 7)

Control output: NC (8 and 11)                                                               Power (2 and 10)
                      NC (1 and 4)
                                                                                                Start (2 and 6)
Control output: NO (9 and 11)                                              Control output: NC (8 and 11)
                      NO (1 and 3)
                                                                                                 NC (1 and 4)
Power indicator                                                            Control output: NO (9 and 11)

                                    Lit  Flashing        Lit                                     NO (1 and 3)

                 Start signal (remote control possible)                                        Power indicator
                 Reset signal
                 (remote control possible)

                                                                                                                     Flashing

                                                                           Externally short-circuited

                                                         Power
                                                         supply

                                         (Power continuously supplied)

                                                                                                                     Power
                                                                                                                     supply

                                                                                                                                                    17
2. Signal Start/Signal Reset (in B Mode)                                                                           H3CR-A

If there is an abnormal signal, flashing starts. When the abnormal               2. Signal-ON-OFF Start/Instantaneous
condition is restored, a reset signal stops the display flashing.                  Operation/Time-limit Reset

                                                             tt                                    Power (2 and 10)
                                                                                                       Start (2 and 6)
Power (2 and 10)
   Start (2 and 6)                                                               Control output: NC (8 and 11)
                                                                                                       NC (1 and 4)
                    Reset (2 and 7)
                                                                                 Control output: NO (9 and 11)
Control output: NC (8 and 11)                                                                          NO (1 and 3)
                      NC (1 and 4)
                                                                                                      Power indicator
Control output: NO (9 and 11)
                      NO (1 and 3)                                                                                           Start signal
                                                                                                                             (The operation starts with the signal ON or OFF)
                    Power indicator                                                                                     Lit
                                                                                                                               Flashing
                                          Lit
                                                                                                                                      Lit
                                                                                                                                              Flashing

                                                                                                                                                    Lit
                                                                                                                                                             Flashing

                                                                                                                                                                        Lit

                                                  Flashing                Lit

Start signal
Reset signal

                                                                    Power                                                                                   Power
                                                                    supply                                                                                  supply
                                                  (Power continuously supplied)                                                           (Power continuously supplied)

C Mode: Signal ON/OFF-delay                                                      D Mode: Signal OFF-delay

The Signal ON-/OFF-delay operation (C mode) is useful for the                    Signal OFF-delay operation (D mode) can be effectively used to keep
control of distribution of products on a production line into boxes by           a load operating for a certain period. For example, this function
the specified number or time.                                                    enables the cooling fan for a lamp or heater to operate for a certain
                                                                                 period after the lamp or heater is switched OFF.
1. Power-ON Start/Instantaneous Operation/
  Time-limit Reset                                                               1. Power-ON Start/Instantaneous Operation/
                                                                                   Time-limit Reset
A set of these functions is useful for the operation of a machine for a
specified period when power is ON.                                                                 Power (2 and 10)

                                               t          t                                            Start (2 and 6)

Power (2 and 10)                                                                 Control output: NC (8 and 11)
                                                                                                       NC (1 and 4)
                     Start (2 and 6)
                                                                                 Control output: NO (9 and 11)
Control output: NC (8 and 11)                                                                          NO (1 and 3)
                      NC (1 and 4)
                                                                                                     Power indicator
Control output: NO (9 and 11)
                      NO (1 and 3)                                                                                      Lit  Flashing            Lit

Power indicator                                                                                                         Start signal (NC to NO)

                                               Flashing Lit Flashing Lit

Externally short-circuited

                                                                                                                             Power
                                                                                                                             supply

                                                  Power
                                                  supply

                                                                                                                                                                               18
                                                                                                                                  H3CR-A

2. Signal Start/Instantaneous Operation/                                              2. Signal Start/Instantaneous Operation/
  Time-limit Reset                                                                      Time-limit Reset

                 Power (2 and 10)                                                     This function is useful for the repetitive control such as the filling of
                                                                                      liquid for a specified period after each Signal start input.
                     Start (2 and 6)
                                                                                                                            t  t
Control output: NC (8 and 11)
                      NC (1 and 4)                                                    Power (2 and 10)

Control output: NO (9 and 11)                                       Flashing     Lit                       Start (2 and 6)
                      NO (1 and 3)
                                                                                      Control output: NC (8 and 11)
                    Power indicator                                                                         NC (1 and 4)
                                                       Lit
                                                                                      Control output: NO (9 and 11)
                                                                                                            NO (1 and 3)

Start signal (NO to NC to NO)                                                         Power indicator                       Flashing Lit Flashing Lit
                                                                                       Start signal

                                                                    Power                                                                   Power
                                                                    supply                                                                  supply
                                                  (Power continuously supplied)
                                                                                                                            (Power continuously supplied)
E Mode: Interval

1. Power-ON Start/Instantaneous Operation/
  Time-limit Reset

This function is useful for the operation of a machine for a specified
period after power is ON.

                                      t                             t

Power (2 and 10)

                     Start (2 and 6)

Control output: NC (8 and 11)
                      NC (1 and 4)

Control output: NO (9 and 11)
                      NO (1 and 3)

Power indicator
                              Flashing Lit Flashing Lit

  Externally short-circuited

                                                            Power
                                                            supply

                                                                                                                                                                 19
                                                                                                               H3CR-A

Safety Precautions (H3CR-A)                                              Input/Output

Refer to Safety Precautions for All Timers.                             Relationship between Input and Power
Note: The following precautions apply to all H3CR-A models.             Supply Circuits (except for H3CR-A8E)

Power Supplies                                                         The H3CR-A (except for H3CR-A8E) uses transformerless power
                                                                        supply. When connecting a relay or transistor as an external signal
For the power supply of an input device of the H3CR-A@/-A@S/-AP,        input device, pay attention to the following points to prevent short-
use an isolating transformer with the primary and secondary             circuiting due to a sneak current to the transformerless power supply.
windings mutually isolated and the secondary winding not grounded.      If a relay or transistor is connected to two or more Timers, the input
                                                                        terminals of those Timers must be wired properly so that they will not
   Correct                                                              differ in phase, otherwise the terminals will be short-circuited to one
                                                                        another.
           G, S, R    H3CR-A               Power supply
           5, 6, 7
                                       10
                   2  Input
                      terminal 2

                                                                        Incorrect                    H3CR-A    Short-circuit current
                                                                                                                             Power supply
                                                                         Contact or transistor for   Input
                                                                         external input signal       terminal

           Input device    Isolation transformer is required.

Incorrect

           G, S, R    H3CR-A               Power                                                     Input
           5, 6, 7                    10   supply                                                    terminal

                   2    Input
                      terminal 2

                                                                                            Correct  Input     Power supply
                                                                                                     terminal
                                           Input device Isolation
                                                               transformer                           Input
                                                                                                     terminal
The H3CR-A@/-A@S/AP's power supply terminal 2 is a common ter-
minal for input signals to the Timer. Do not disconnect the wires on
terminal 2, otherwise the internal circuitry of the Timer will be dam-
aged.

              5, 6, 7           10                                      It is impossible to provide two independent power switches as shown
              G, S, R                                                   below regardless of whether or not the Timers are different in phase.
                           H3CR-A
           Input terminal

                                                                                                     Input     Power supply
                                                                                                     terminal
                                                      2

Make sure that the voltage is applied within the specified range, oth-
erwise the internal elements of the Timer may be damaged.

                                                                                                     Input
                                                                                                     terminal

                                                                                                                                                 20
                                                                                                                                                        H3CR-A

Relationship between Input and Power                                                       If a relay or transistor is connected to two or more Timers, the input
Supply Circuits (H3CR-A@/-A@S)                                                             terminals of those Timers must be wired properly so that they will not
                                                                                           be different in phase or the terminals will be short-circuited to one
An appropriate input is applied to the input signal terminals of the                       another (refer to the figures below).
H3CR-A@/-A@S when one of the input terminals is short-circuited
with the common terminal (terminal 2) for the input signals. Never                         Incorrect Contact or transistor for                          Power supply
use terminal 10 as the common terminal for this purpose, otherwise
the internal circuit of the Timer will be damaged.                                                              external input signal

Incorrect                                                                                                                                           10
                                                                                                                                     6
                                                                                       10
                                                                                                                                            H3CR-AP
                                                                                                                                     7

                                                                                           2

AC or DC                           5, 6, 7     H3CR-A                                                    10
power supply                       G, S, R            2                                    6

                               Input terminal                                                    H3CR-AP
                                                                                           7
                                                                                                                                                        Short-circuit current
                                                                                                         2
Correct
                                   5, 6, 7           10                                    Correct Contact or transistor for
                 AC or DC          G, S, R     H3CR-A
                 power supply                                                                               external input signal
                               Input terminal                                                                                                   10

                                                            2                                                                    6                              Power supply
                                                                                                                                 7 H3CR-AP              Short-circuit current
Do not connect a relay or any other load between input terminals,
otherwise the internal circuit of the Timer will be damaged due to the                                                                         2
high-tension voltage applied to the input terminals.
                                                                                                                                                10
                                                                          10                                                     6
                               Ry                                                                                                7 H3CR-AP

AC or DC                           5, 6, 7     H3CR-A                                                                                          2
power supply                       G, S, R           2

             Input             Input terminal
             contact
                                                                                           Common to All H3CR-A Models
Relationship between Input and Power
Supply Circuits (H3CR-AP)                                                                  With the H3CR-AP, input wires must be as short as possible. If the
                                                                                           floating capacity of wires exceeds 1,200 pF (approx. 10 m for cables
                                                                                           with 120 pF/m), the operation will be affected. Pay particular
                                                                                           attention when using shielded cables.

                                                                                           The H3CR-A@S transistor output is isolated from the internal
                                                                                           circuitry by a photocoupler. Therefore, either NPN or PNP output is
                                                                                           possible.

H3CR-AP

AC/DC                          Input circuit  Power supply
power                                         circuit
supply

Since the input circuit and the power supply circuit are configured
independently, the input circuit can be turned ON or OFF irrespective
of the ON/OFF state of the power supply.
It must be noted that a voltage equivalent to the power supply voltage
is applied to the input circuit.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                  In the interest of product improvement, specifications are subject to change without notice.

                                                                                                                                                                               21
                                                       Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.

                                                      Warranty and Limitations of Liability

WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.

In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

                                                            Application Considerations

SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.

At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:

       Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.

       Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
           safety equipment, and installations subject to separate industry or government regulations.

       Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.

                                                                       Disclaimers

CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.

DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.

ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.

OMRON Corporation                                                                                                                                      2010.12
                               In the interest of product improvement, specifications are subject to change without notice.
Industrial Automation Company
                                                                                   (c)Copyright OMRON Corporation 2010 All Right Reserved.
http://www.ia.omron.com/
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Omron:

  H3CR-A-AC100-240/DC100-125 H3CR-A8E AC100-240/DC100-125 H3CR-A8E AC/DC24-48 H3CR-A-300 AC24-
48/DC12-48 H3CR-A8-301 AC100-240/DC100125 H3CR-A8S AC24-48/DC12-48 H3CR-AS AC24-48/DC12-48
H3CR-A-301 AC100-240/DC100-125 H3CR-A8E-AC100-240/DC100-12 H3CR-A8-302 DC24 H3CR-A8 AC24-
48/DC12-48 H3CR-AP AC24-48/DC12-48 H3CR-A-301 AC24-48/DC12-48 H3CR-A8-301 AC24-48/DC12-48 H3CR-
AP AC100-240/DC100-125 H3CR-A-AC24-48/DC12-48 H3CR-A-300-AC100-240/DC100-125 H3CR-A8-AC100-
240/DC100-125

小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2017 EEWORLD.com.cn, Inc. All rights reserved