H3CA-8-AC200/220/240

器件型号:H3CA-8-AC200/220/240
器件类别:热门应用    机电_工控_自动化   
文件大小:20544.78KB,共10页
厂商名称:OMRON
厂商官网:https://www.omron.com
标准:  
下载文档

器件描述

timers solid state timer

参数

Manufacturer: Omron
Product Category: Timers
RoHS: No
Product: Digital Timer
Type: Solid State Timer
Supply Voltage: 200 VAC, 220 VAC, 240 VAC
Timing Range: 0.1 s to 9990 hr
Display Type: LCD Display
Brand: Omron Automation and Safety
Accuracy: +/- 0.3 %
Operating Temperature Range: - 10 C to + 55 C
Series: H3CA
Factory Pack Quantity: 1
Termination Style: Plug, Octal Style

H3CA-8-AC200/220/240器件文档内容

Solid-state Timer                                                                                                        CSM_H3CA_DS_E_3_1

H3CA

DIN-sized (48 x 48, 45 x 75 mm) Timer with
Digital Setting and LCD Display

Dual power supplies for free AC/DC.
Eight operation modes selectable with one unit.
Any desired time can be set digitally within a range from 0.1

seconds to 9,990 hrs.
Four external signal inputs.
ON/OFF indicator for control output and bar indicator for

remaining time.
Conforms to UL, CSA, and CE marking.

Ordering Information

Operation/resetting Operation mode                    Terminal   Time-limit             Instantaneous                     Mounting
        system                                                    contact                    contact
                                                                                                             Surface      Flush mounting
                                                                                       ---                 mounting/
                                                                                                        track mounting

Time-limit operation/self- 8 operation modes 11-pin round socket SPDT                                   H3CA-A            H3CA-A

resetting/external        (selectable)         Front screw                                              H3CA-FA           ---
resetting (see note 2)    (see note 3)

Time-limit operation/     ON-delay operation 8-pin round socket DPDT                   ---              H3CA-8            H3CA-8
self-resetting                                                                   SPDT  SPDT             H3CA-8H           H3CA-8H

Note: 1. Specify both the model number and supply voltage when ordering for the H3CA-8H and H3CA-8.
        2. The operation/resetting system depends on the selected operation mode. For details, see "Timing Chart".

3. The 8 operation modes are as follows:

            A: ON-delay operation                                                            E: Interval operation
            B: Repeat cycle operation                                                        F: One-shot and flicker operation
            C: Signal ON/OFF-delay operation (1)                                             G: Signal ON/OFF-delay operation (2)
            D: Signal OFF-delay operation (1)                                                H: Signal OFF-delay operation (2)

Accessories (Order Separately)

                   Timer         Track mounted socket                                         Back connecting socket
                                         (See note.)
H3CA-A                                                                                 Solder terminal                    Screw terminal
H3CA-8H/H3CA-8            P2CF-11
                          P2CF-08                                     PL11                                       P3GA-11
                                                                      PL08
                                                                                                                 P3G-08

Note: Track mounted socket can be used as a front connecting socket.

Specifications

Time Ranges

A desired time can be set within a range of 0.1 s to 9,990 hrs by combining the three thumbwheel switch modules for time setting and one module
for time unit selection.

Time unit                                      0.1 s  1s              0.1 min          1 min            0.1 hrs     1 hr            10 hrs

Time range                1 to 999 (3 digits)

                                                                                                                                                 1
                                                                                                                             H3CA

Ratings

                 Item    H3CA-A/H3CA-FA                                    H3CA-8                                   H3CA-8H
Rated supply voltage
(See note 2.)            24 to 240 VAC (50/60 Hz),          100/110/120, 200/220/240 VAC, (50/60 Hz),

Operating voltage range  12 to 240 VDC (permissible ripple: 24 VDC, 110 VDC (permissible ripple: 20% max.) (See note 1.)
Power consumption
                         20% max.)
Control outputs
                         90% to 110% of rated supply voltage 85% to 110% of rated supply voltage

                         AC: approx. 4 VA                   AC: approx. 10 VA/1 W                 AC: approx. 10 VA/1.5 W
                         DC: approx. 2 W                    DC: approx. 1 W                       DC: approx. 2 W

                         3 A at 250 VAC, resistive load (cos = 1)

                         Minimum applicable load            H3CA-8, H3CA-A and H3CA-FA: 10 mA at 5 VDC (failure level: Preference value)

                                                            H3CA-8H:               100mA at 5 VDC (failure level: Preference value)

Note: 1. Single-phase, full-wave rectified power sources may be used for 24 to 240 VDC.
        2. Refer to Safety Precautions for All Times when combining the Timer with an AC 2-wire proximity sensor.

Characteristics

Accuracy of operating    0.3% 0.05 s
time
Influence of voltage     0.5% 0.05 s max.
Influence of
temperature              H3CA-A/-FA: 0.5 s max.
Setting error            H3CA-8H/-8: 0.1 s max.
Reset time
Insulation resistance    100 M min. (at 500 VDC)
Dielectric strength
                         2,000 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying parts and between contact and
Impulse withstand        control circuit)
voltage                  1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance
Shock resistance         3 kV
Ambient temperature
Ambient humidity         Destruction: 10 to 55 Hz with 0.75-mm double amplitude for 1 h each in three directions
Life expectancy          Malfunction: 10 to 55 Hz with 0.5-mm double amplitude for 10 min each in three directions

Approved standards       Destruction: 980 m/s2
EMC                      Malfunction: 98 m/s2

Weight                   Operating: 10C to 55C

                         Operating: 35% to 85%

                         Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h)
                         Electrical: 100,000 operations min. (3 A at 250 VAC, cos = 1 at 1,800 operations/h)

                                           See Lift-test Curve for more details.

                         UL508, CSA C22.2 No. 14, LR, NK
                         Conforms to EN61010-1.

                         (EMI)                              EN61326
                         Emission Enclosure:                EN55011 Group 1 class A
                         Emission AC mains:                 EN55011 Group 1 class A
                         (EMS)                              EN61326
                         Immunity ESD:                      EN61000-4-2: 4 kV contact discharge (level 2)

                         Immunity RF-interference:                                    8 kV air discharge (level 3)
                                                            EN61000-4-3: 10 V/m (Amplitude-modulated, 80 MHz to 1 GHz) (level 3);
                         Immunity Conducted
                         Disturbance:                                                 10 V/m (Pulse-modulated, 900 MHz 5 MHz) (level 3)
                         Immunity Burst:
                                                            EN61000-4-6:   10 V (0.15 to 80 MHz) (according to EN61000-6-2)
                         Immunity Surge:                    EN61000-4-4:   2 kV power-line (level 3);
                                                                           1 kV I/O signal-line (level 4)
                         Immunity Voltage Dip/Interruption  EN61000-4-5:   1 kV line to lines (power and output lines) (level 3);
                                                                           2 kV line to ground (power and output lines) (level 3)
                                                            EN61000-4-11:  0.5 cycle, 100% (rated voltage)

                         H3CA-A: approx. 110 g
                         H3CA-FA: approx. 190 g

                                                                                                                                          2
                                                                                                                                          H3CA

Engineering Data

Life-test Curve

Switching operations (103)                              Reference: A maximum current of 0.15 A can be switched at 125 VDC (cos = 1).
                                                                         Maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a
                                                                         life of 100,000 operations can be expected.

                                                            Note: 1. The H3CA Series has been tested for the following: impulse voltages, noise
                                                                        (via noise simulator, for L loads, and for relay oscillation), and resistance to
                                                                        static electricity.

                                                                    2. Minimum applicable load (P reference values):
                                                                        H3CA-A(FA), H3CA-8H: 100 mA at 5 VDC
                                                                        H3CA-8: 10 mA at 5 VDC

                         Load current (A)

Nomenclature

H3CA-A/H3CA-8H                                                                  H3CA-FA

                                     Time Unit Selector                                                  LCD Display

LCD Display                                Set Time Indicators (3 Digits)                                             Time Unit Selector
Control output ON/OFF indication
Remaining time elapses, the
remaining time is indicated by a
pattern of bars in tenth of 1/10 of
the set time.

                             Operation Mode Selector (Fixed to "A" in H3CA-8H)  Operation Mode Selector  Set Time Indicators (3 Digits)

                             A: ON-delay operation
                             B: Flicker operation
                             C: Signal ON/OFF-delay operation (1)
                             D: Signal OFF-delay operation (1)
                             E: Interval operation
                             F: One-shot and flicker operation
                             G: Signal ON/OFF-delay operation (2)
                             H: Signal OFF-delay operation (2)

                                                                                                                                                          3
Operation                                                                                                                                H3CA

Timing Chart                                                                                   Power-ON Start/Power-OFF Reset

H3CA-A (FA)

ON-delay Operation (A Mode)

Signal Start

                                                    t: Set time; t-a: Time within the set time                               t: Set time; R: Resetting time; t-a: Time within the set time

                  Note: The minimum signal input time is 0.05 s.                                Power-ON Start/Power-OFF Reset

Flicker Operation (B Mode)

Signal Start

                                                                                                t: Set time

                          t: Set time; t-a: Time within the set time

Note: The minimum signal input time is 0.05 s.

                                                                                                                                                                                            4
                                                                                                                                                             H3CA

Signal ON/OFF-delay Operation 1 (C Mode)                                                         Signal OFF-delay Operation 1 (D Mode)

t: Set time; t-a: Time within the set time                                                       t: Set time; t-a: Time within the set time

Note: 1. The minimum signal input time is 0.05 s.
          2. Operation 1 refers to the version in which the output relay operates when the Start signal is ON.

Interval Operation (E Mode)

Signal Start

                                                     t: Set time; t-a: Time within the set time                                                 t: Set time

                    Note: The minimum signal input time is 0.05 s.                               Power-ON Start/Power-OFF Reset

One-shot and Flicker Operation (F Mode)

Signal Start

                                                     t: Set time; t-a: Time within the set time                                                      t: Set time; t-a: Time within the set time

                    Note: The minimum signal input time is 0.05 s.                                                 Note: The minimum signal input time is 0.05 s.

Signal ON/OFF-delay Operation 2 (G Mode)                                                         Signal ON/OFF-delay Operation 2 (H Mode)

                                                                                                                                                                       t-a

t: Set time; t-a: Time within the set time                                                       t: Set time; t-a: Time within the set time

Note: 1. The minimum signal input time is 0.05 s.
          2. Operation 2 refers to the version in which the output relay does not operate when the Start signal is ON.

                                                                                                                                                                                                 5
How to Use Gate Signal Input                                             H3CA

                              How to Use Check Signal Input

                              If a check signal is input to the timer during the lapse of a set time,
                              the remaining set time will become 0 and the timer will enter the
                              next control state. Also, while a check signal is being input, the
                              elapsed time measurement of the set time is not performed.
                              ON-delay Operation

Note: 1. This timing chart indicates the gate input in operation
              mode A (ON-delay operation).

          2. The set time is the sum of t1 and t2.

                                                                                                                                                                t: Set time; t-a: Time within the set time

                                                                                       Repeat Cycle Operation

                              t: Set time; t-a: Time within the set time

H3CA-8H

                                                                                                                                                                                                            6
                                                                                                                                         H3CA

Dimensions                                                      H3CA-FA

Note: All units are in millimeters unless otherwise indicated.

Timers

H3CA-A/-8H

Panel Cutouts      Horizontally connecting n units              Mounting Holes
When mounting      No front cover:
a single unit      N = (48n - 2.5)+1/-0                                                             Two,M4 or 4.5 dia. holes
t = 1 to 3.2 mm    With front cover:
                   N = {48n - 2.5 + (n - 1) x 3}+1/-0                                              Note: When mounting two or more
                                                                                                            timers in line, dimension L
                                            45+-00.6 (N)                                                    between two adjacent timers
                                             (N)                                                            should be 10 mm min.

Accessories (Order Separately)

Track Mounted Front Connecting Socket

P2CF-11

Eleven, M3.5 7.5                             Terminal Arrangement      Mounting Holes           Mounting Height of
sems                                           (Top View)                                         Timer with Socket
                                                                            Two, 4.5 dia.
                                     Two,                                   mounting holes        108.1
                                     4.5 dia.
                                     holes                                                        Mounting Height of
                                                                                                  Timer with Socket
                                                                     Note: P2CF-11 can be
                                                                              used as a front       97.2
                                                                              connecting socket.

P2CF-08                                        Terminal Arrangement      Mounting Holes
                                               (Top View)
Eight, M3.5 7.5                                                            Two, 4.5 dia. or
sems                                                                         Two, M4

                   Two,
                   4.5 dia.
                   holes

                                                                     Note: P2CF-08 can be
                                                                              used as a front
                                                                              connecting socket.

                                                                                                                                               7
                                                                                                            H3CA

Back Connecting Socket                       Terminal Arrangement
                                             (Bottom View)
P3GA-11

                   27 dia.

P3G-08                                                             Terminal Arrangement         Mounting Height of
                                                                   (Bottom View)                Timer with Socket

                                                                                                10.9  86.3

                                             M3.5

                                                                                                            P3G-08

PL11                                         Terminal Arrangement  Mounting Holes               Mounting Height of
                                             (Bottom View)                                      Timer with Socket
                 35 max.
                          Two, 2 dia. holes                        Two, 3.5 dia. or 3M socket
PL08                                                               mounting holes
                                                                                                            Hold-down

                                                                                                79.6        clip
                                                                                                            Y92H-1

                          Approx. 20.5

                                             Terminal Arrangement  Mounting Holes                  Mounting Height of
                                             (Bottom View)                                         Timer with Socket
                                                                    Two, 3.5 dia. or 3M socket
                          Two, 2 dia.                               mounting holes              79.6
                          holes

                                                                                                                       8
                                                                                                                                  H3CA

Mounting Track (Meets DIN EN50022)                                PFP-100N2

PFP-100N/PFP-50N                                                                      Twelve, 25 4.5 elliptic holes (see note)

                           (see note)                             Note: A total of 12-25 4.5 elliptic holes are provided with 6 holes
                                                                           cut from each rail end at a pitch of 10 mm between holes.
Note: This dimension applied to PFP-50N.
                                                                  PFP-S
End Plate

PFP-M

Adapter for Flush Mounting

Y92F-30

Note: Pay attention to the orientation of the adapter when mounting
         two or more timers in a vertical or horizontal line.

Protective Cover

Y92A-48B/Y92A-48D

The protective cover protects the front panel, particularly the

time setting section, against dust, dirt and water drip, as well

as prevents the set value from being altered due to accidental

contact with the time setting knob.  Y92A-48D                     Note: The Y92A-48B Protective Cover is made of a hard plastic and
                                     Soft PVC Cover                        therefore, must be removed to change the timer set value. However,
           Y92A-48B                                                        since the Y92A-48D Protective Cover is made of PVC, the set value
           Hard Plastic Cover                                              can be altered by pressing on the surface of the cover.
                                                                           It may be, however, difficult to make setting changes of the Timer
                                                                           with the Y92A-48B Protective Cover attached, which must be taken
                                                                           into consideration before using the Y92A-48B Protective Cover.
                                                                           When attaching the Y92A-48A to the Timer to be panel-mounted,
                                                                           use the Y92F-30 Mounting Adapter along with the Timer.
                                                                           The Protective Cover cannot be, however, used for the H3CA-FA
                                                                           Series.

                                                                                                                                               9
                                                                                                                        H3CA

Installation                                                          H3CA-FA

Terminal Arrangement

H3CA-A

        ** * *                                                                 (+) or (-)* * * *

                                 (See                                                                         (See
                                 note                                                                         note
                                 2)                                                                           2)

(+) or                   (+) or                                                                   (+) or (-)
(-)                      (-)

Note: 1. *C: Check: 3-4

*G: Gate: 3-5                                                         Note: 1. *C: Check: X-E1

*S: Start: 3-6                                                                 *G: Gate: X-D1

*R: Reset: 3-7                                                            *S: Start: X-C1
                                                                          *R: Reset: X-B1
2. Conventional time-limit contacts are symbolized as .
     However, the contacts of H3CA-A are symbolized as                2. Conventional time-limit contacts are symbolized as .
     because timer has 8 operation modes.                                  However, the contacts of H3CA-FA are symbolized

                                                                               as because timer has 8 operation modes.

Input Connections                                                    Solid-state Signal Inputs

Signal Inputs                                                         Connect the start input transistor between terminals C and F, the
                                                                      reset input transistor between terminals C and G, the gate input
Connect the start input contact between terminals C and F, the        transistor between terminals C and E, and the check input
reset input contact between terminals C and G, the gate input         transistor between terminals C and D.
contact between terminals C and E, and the check input contact
between terminals C and D.

For each signal input contact, use a gold-plated contacts with high   For signal input, use an open collector type transistor with
reliability. Be sure that these input signals satisfy the following
requirements: a resistance of 1 k (max.) and a residual voltage of 1  characteristics: VCEO = 20 V min., VCE(S) = 1 V max., IC = 50 mA min.
V (max.) when the contact is made.                                    and ICBO = 0.5 A max. In addition, be sure that the input signals
                                                                      satisfy the following requirements: a resistance of 1 k (max.) and a
                                                                      residual voltage of 1 V (max.) when the transistor is ON, and a
                                                                      resistance of 200 k (min.) when the transistor is OFF.

                                                                                                                                             10
                                                                                             H3CA

From a solid-state circuit (proximity sensor, photoelectric sensor, or
the like) with rated power supply voltage ranging from 6 to 30 VDC,
input signals can also be applied by other than an open collector type
transistor as shown in the following diagram. The input signal from a
solid-state circuit is applied when output transistor Tr turns ON. In
terms of signal voltage, the signal is input when it goes from a high to
low level. Again, the residual voltage should be 1 V (max.) when the
transistor is ON. As the current output from the timer to Tr is
approximately 0.1 mA, this connection is possible provided the
residual voltage is kept to a maximum of 1 V.

                    Solid-state circuit (proximity sensor,
                    photoelectric sensor, etc.)

Note: Except for the power supply circuitry, avoid the laying of input
        signal wires in parallel or in the same conduit with high-tension
        or power lines. It is recommended to use shielded wires or
        wiring with independent metal conduits for the shortest
        possible distance.

H3CA-8H                                                                    H3CA-8

         (-)  (+)                                                                  (-)  (+)

                                                                                             11
                                                                                        H3CA

Application Examples

Standard type H3CA is used for the following application examples. In the schematic diagrams, each thick the indicates the wiring necessary for
selecting the desired operation mode.

ON-delay Operation (A Mode)                                          Signal Start/Signal Reset
Power-ON Start/Power-OFF Reset

(+) or (-)  (+)
            or (-)

                                                                     (+) or (-)                 (+)
                                                                                                or (-)

Flicker Operation (B Mode)                                           Signal Start/Signal Reset
Power-ON Start/Power-OFF Reset

(+) or (-)  (+)
            or (-)

                                                                     (+) or (-)                  (+)
                                                                                                or (-)

Signal ON/OFF-delay Operation 1 (C Mode)                             Signal OFF-delay Operation 1 (D Mode)
                                                                     Signal Start/Instantaneous Operation/Time-limit Reset
Signal ON/OFF-start/Instantaneous Operation/
Time-limit Reset

                                                        t-a

                                (+) or (-)                     (+)                                      (+) or (-)            (+)
                                                             or (-)                                                         or (-)

t: Set time, t-a: Time within the set time

                                                                                                                                                 12
                                                                                                       H3CA

Signal ON/OFF-delay Operation 2 (G Mode)              Signal Start/Signal Reset

Signal ON/OFF-start/Instantaneous Operation/
Time-limit Reset

                                (+) or (-)                                               (+) or (-)    (+)
                                                                                                       or (-)

                                              (+) or (-)

Interval Operation (E Mode)                           Signal Start/Signal Reset

Power-ON Start/Power-OFF Reset

                                (+) or (-)    (+)
                                              or (-)

                                                          (+) or (-)               (+)
                                                                                 or (-)

One-shot and Flicker Operation (F Mode)               Signal OFF-delay Operation 2 (H Mode)

Power-ON Start/Power-OFF Reset                        Signal/Instantaneous Operation/Time-limit Reset

                                (+) or (-)    (+)                                        (+) or (-)
                                              or (-)
                                                                                                        (+)
                                                                                                       or (-)

                                                                                                               13
                                                                                                                                H3CA

Safety Precautions                                                                               Connecting the Operating Power

How to Change Operation Mode                                                                     Supply

Operate the pushbuttons of the thumbwheel switch, located at the                                 The H3CA-8@ contains a capacitor-drop power circuit. Use a
leftmost position on the front panel to set the operation mode. Eight                            sinusoidal power supply with a commercial frequency. Do not use
operation modes (A, B, C, D, E, F, G, and H) are selectable and the                              power supplies with a high frequency component (such as inverter
selected operation mode is displayed in the operation mode display                               power supplies) for Timers with 100 to 240-VAC specifications. Using
window.                                                                                          these power supplies can damage internal circuits.

       Note: The operation mode is fixed to "A" for H3CA-8H.                                     The power supply connections to the H3CA-A and H3CA-FA can be
                The characters are yellow.                                                       made without regard to polarity for both AC and DC power supplies;
                                                                                                 just connect to the specified terminals (2 and 10, or A1 and A2).
How to Change Time Unit and Rated                                                                When connecting a DC power supply to the H3CA-8 or H3CA-8H,
Time                                                                                             however, the polarity must be connected as indicated.

Operate the pushbuttons of the rightmost thumbwheel switch to                                    Although there is a wide range of power connectable to the H3CA-A
select the desired time unit. Seven time units (0.1 s, s, 0.1 m, m,                              and H3CA-FA, be sure that there is no inductive voltage or residual
0.1 h, h, or 10 h) are selectable and the selected time unit is                                  voltage applied to the timer power supply terminals (2 and 10, or A1
displayed in the time unit display window. The desired rated time is                             and A2) when the power switch is turned OFF. (Inductive voltage can
specified by operating the three thumbwheel switches in the middle                               be generated in the power supply line if it is placed in parallel with
of the front panel. The range of rated time is 001 to 999 for each unit.                         high-voltage or power lines.)

                                                               Remaining time display            A DC power supply can be connected if its ripple factor is 20% or
                                                                The remaining time is displayed  less and the mean voltage is within the rated operating voltage range
                                                                as a decreasing percentage       of the Timer.
                                                                between 0% and 100%.
                                                                                                 Connect the power supply voltage through a relay or switch in such a
                                                                  Time unit                      way that the voltage reaches a fixed value at once or the Timer may
                                                                  selector                       not be reset or a timer error could result.

                                                                                                 H3CA-8 and H3CA-8H Timers with AC specifications are equivalent
                                                                                                 to capacitor loads. When switching the Timer power supply with an
                                                                                                 SSR, use an SSR with a withstand voltage of twice the power supply
                                                                                                 voltage.

                                                                                                 Since the H3CA-8 and H3CA-8H Timers of AC specifications
                                                                                                 externally discharges a part of internal energy when the power is
                                                                                                 turned OFF, it may malfunction if an extremely sensitive relay is used
                                                                                                 with the following sequence circuit.
                                                                                                 If such a malfunction occurs, change the circuit configuration as
                                                                                                 shown below on the right side.

                                                                                                      X/a                       X/a

                                                                                                 T/b       If malfunction  T/b  X/a

                                                                                                           is expected.

Rated time display  Rated time  Time unit display
window              selector    window
001 to 999                      0.1 s, s, 0.1 m
                                0.1 h, h, 10 h

Note: The characters are yellow.

Time Unit and Rated Time

        Time unit                    Rated time
0.1 s               0.1 to 99.9 s
s                   1 to 999 s
0.1 m               0.1 to 99.9 m
m                   1 to 999 m
0.1 h               0.1 to 99.9 h
h                   1 to 999 h
10 h                10 to 9,990 h

                            !CAUTION

1. Do not change the time unit, rated time, or operation mode while
    the timer is in operation. Otherwise, the timer may malfunction or
    be damaged. Be sure to turn off the power supply to the timer
    before changing the timer unit, rated time or operation mode.

2. Note that output will be generated in C, D, E, G, or H mode even if
    the rated time is set to 000. No output will be generated in A, B, or
    F mode.

                                                                                                                                                                         14
Input/Output                                                                                                                          H3CA

The operation of the output contacts varies with the operation                                   How to Mount the Timer on Mounting
specifications. Before making connections, check the operation                                   Track
specifications and operating conditions using the application
examples provided.                                                                               When mounting a H3CA-FA Timer on a socket mounting track,
                                                                                                 observe the following procedures:
The H3CA-A and H3CA-FA do not use transformers. Simultaneous
inputting power from two or more power supplies to separate timers                               Mounting
or counters from a single input contact or transistor is not possible.
                                                                                                 First hook portion A of the timer to an edge of the track and then
For the power supply of an input device, use an isolating transformer,                           depress the timer in direction B.
of which the primary and secondary windings are mutually isolated
and the secondary winding is not grounded.                                                                      B

                                       H3CA-A/-FA

Input              Power supply
terminal

Rectifier circuit                                                                                A  C

                            Circuit                                                              Dismounting

                                                             Isolation transformer is required.  Pull out portion C with a round-blade screwdriver and remove the
                                                                                                 timer from the mounting track.
A transformer is not used in the power supplies for the H3CA-A and
H3CA-FA. You can therefore receive an electrical shock by touching
the input terminals when the power supply voltage is being applied.
Take adequate precautions to protect against electrical shock.

Inputs to input signal terminals are made by shorting the individual
input terminals to the common terminal (terminal 3 for the H3CA-A or
terminal (X) for the H3CA-FA). Internal circuits may be damaged if
connections are made to any other terminals or if voltages are
applied.
If contacts are used to short the terminals, they will be switching a
low voltage (approximately 5 VDC) and current (approximately
100 A). You must therefore use high-reliability contacts with a
contact resistance of 1 k or less when shorted and residual voltage
of 1 V maximum when shorted.

The reset input will take priority if both the set and reset inputs are
turned ON simultaneously.

Others

Holding relays are used for outputs on the H3CA-A Series. Dropping
the Unit or otherwise subjecting it to shock can cause the relay to
reverse or to move to the center position.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                  In the interest of product improvement, specifications are subject to change without notice.

                                                                                                                                                                   15
                                                       Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.

                                                      Warranty and Limitations of Liability

WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.

In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

                                                            Application Considerations

SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.

At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:

       Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.

       Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
           safety equipment, and installations subject to separate industry or government regulations.

       Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.

                                                                       Disclaimers

CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.

DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.

ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.

OMRON Corporation                                                                                                                                      2010.10
                               In the interest of product improvement, specifications are subject to change without notice.
Industrial Automation Company
                                                                                   (c)Copyright OMRON Corporation 2010 All Right Reserved.
http://www.ia.omron.com/
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Omron:

  H3CA-A H3CA-8-AC100/110/120 H3CA-8H-AC100/110/120 H3CA-8-AC200/220/240 H3CA-FA H3CA8HDC110