Three-phase Hybrid Soft Starter

(Soft Start, Kick Start, Current Limit Start, Soft Stop)

G3JA-C

                                                                                                                                   CSM_G3JA-C_DS_E_6_1

Built-in Bypass Relay and Smooth Motor Starts/Stops

Achieved in a Compact Starter

• Advanced functions include soft start, kick start, and soft stop.

• Phase control using a thyristor limits current when the motor starts, and a

bypass relay minimizes power loss while the motor is running.

• Controls 3-phase, 3-wire motor or 3-phase, 6-wire motor.

• Built-in electronic thermal overload relay.

• Built-in fault diagnosis for overtemperature, phase reversal, phase loss/open

load, current imbalance, and shorted SCR.

• cULus listed; complies with IEC standards.

• Mounts with screws or to DIN track.

• Built-in operation/fault indicator.

• Built-in auxiliary contact for fault indication.

• Built-in auxiliary contact to output operating status.

• An Optional Auxiliary Contact Block can be added to output operating status.

        Refer to Safety Precautions on page 16.

Characteristics                                                                            Model Number Structure

                                                 Type  3-phase, 3-lead  3-phase, 6-lead    ■ Model Number Legend

Item                                                   motor            motor (star-delta

                                                                        wiring)

              Rated operating voltage (motor)                      200 to 480 VAC (±10%)   Soft Starter

Applicable                                                         50/60 Hz (±5%)

motors        Rated operating current (motor)          3 to 37 A        3 to 64 A          G3JA-C@@@@

              Applicable motor capacity                0.55 to 7.5 kW   0.55 to 18.5 kW

              IEC 60947-4-2, 230 VAC                                                                    1  2  3  4  5

              Voltage control start (See note.)                         ❍                  1.  Controller Type

              Kick start                                                ❍                      C: Soft start/stop

              Current limit start (See note.)                           ❍                  2.  Rated Operating Voltage of Main Circuit

              Soft stop                                                 ❍                      4:   200 to 480 VAC, 3 phase, 50/60 Hz

              Fault detection relay output (NO)                         ❍                  3.  Rated Operating Current of Main Circuit

Functions     Auxiliary contact output (NO)                             ❍                      03: 3 A        19: 19 A  30: 30 A

              Optional Auxiliary Contact Block                          ❍                      09: 9 A        25: 25 A  37: 37 A

              output                                                                           16: 16 A

              Fault detection LED indicator                             ❍                  4.  Terminal Type

              Overload protection                                       ❍                      B: Screw terminals (screw clamps)

              Phase reversal detection                                  ❍                  5.  Control Voltage

              Current imbalance detection                               ❍                      AC100-240:     100 to 240 VAC 50/60 Hz

Note: Select either voltage control start or current limit start.                              AC/DC24:       24 VAC 50/60 Hz, 24 VDC

Applicable Motors                                                                          Accessories

Three-phase, 3-wire       Motor                  Three-phase,      6-wire Motor

(Line)                                           (Delta)                                   G32J-@@

The G3JA-C can be                                A 3-phase, 6-                                         1   2

used for a 3-phase,                              wire motor                                1.  Option

3-wire motor as                                  (that supports                                CA: Auxiliary Contact Block

shown in the                                     a star-delta                              2.  Number of Contacts

following diagram.                               operation                                     10:  1 NO      01: 1 NC

(Star-delta wiring for                           start) can be                                 20:  2 NO      11: 1 NO/1 NC

the motor is required                            used. The

if a 3-phase, 6-wire                             G3JA-C is                                 G32J-@

motor is used.)                                  compact and

                                                 includes                                              1

                                                 functionality                             1.  Option

                          Motor                  for devices               Motor

                                                 that start                                    CF64: Fan

                                                 operation with                                TA10: Round Terminal Block Adapter

                                                 star-delta

                                                 (  −  ) wiring.

                                                                                                                                                        1
                                                                                                                              G3JA-C

Ordering Information

■ List of Models

Soft Starters (Complies with IEC 60947-4-2, UL508)

Three-phase, 3-wire Motors

Applicable motor      Rated Operating                          Applicable motor capacity (reference values)                   Model

     wiring       Current of Main Circuit                      kW                                          HP

                     Current  Adjustable    200 VAC 50/     230 VAC      380/400/        200 VAC         230 VAC  460 VAC

                  rating (A)  range (A)          60 Hz        50 Hz      415 VAC           60 Hz           60 Hz  60 Hz

                                                                           50 Hz

                  3           1 to 3        0.2 to 0.4   0.37         0.75            0.5             0.5         0.5 to 1    G3JA-C403B        AC100-240

                                                                                                                              G3JA-C403B        AC/DC-24

                  9           3 to 9        0.55 to 1.5  1.5          3               0.75 to 1.5     0.75 to 2   1.5 to 3    G3JA-C409B        AC100-240

                                                                                                                              G3JA-C409B        AC/DC-24

                  16          5.3 to 16     1.1 to 2.2   3            5.5             1.5 to 3        1.5 to 3    5 to 7.5    G3JA-C416B        AC100-240

                                                                                                                              G3JA-C416B        AC/DC-24

                  19          6.3 to 19     1.5 to 3.7   4            5.5             1.5 to 3        2 to 3      5 to 10     G3JA-C419B        AC100-240

                                                                                                                              G3JA-C419B        AC/DC-24

                  25          8.3 to 25     2.2 to 5.5   4            9.5             3 to 5          3 to 5      7.5 to 10   G3JA-C425B        AC100-240

     Motor                                                                                                                    G3JA-C425B        AC/DC-24

                  30          10 to 30      2.2 to 5.5   5.5          11              3 to 5          5 to 7.5    7.5 to 15   G3JA-C430B        AC100-240

     (Line)                                                                                                                   G3JA-C430B        AC/DC-24

                  37          12.3 to 37    3.7 to 7.5   7.5          15              5 to 7.5        5 to 10     10 to 20    G3JA-C437B        AC100-240

                                                                                                                              G3JA-C437B        AC/DC-24

Note: The applicable motor capacities given in the table are reference values. The motor FLA must fall            within the  current range of  the device.

     It is not possible to use motors that are outside the adjustable range of the Soft Starter.

Three-phase, 6-wire Motors (Star-delta Wiring)

Applicable            Rated operating                          Applicable motor capacity (reference values)                   Model

motor wiring      current of main circuit                      kW                                          HP

                     Current  Adjustable    200 VAC 50/     230 VAC      380/400/        200 VAC         230 VAC  460 VAC

                  rating (A)  range (A)          60 Hz        50 Hz      415 VAC           60 Hz           60 Hz  60 Hz

                                                                           50 Hz

                  3           1.7 to 5.1    ---          0.25 to 1.1  0.55 to 2.2     1               1           0.5 to 2    G3JA-C403B        AC100-240

                                                                                                                              G3JA-C403B        AC/DC-24

                  9           5.1 to 16     ---          1.1 to 4     2.2 to 7.5      1.5 to 3        1 to 5      2 to 7.5    G3JA-C409B        AC100-240

                                                                                                                              G3JA-C409B        AC/DC-24

                  16          9.1 to 27.6   ---          2.2 to 7.5   4 to 11         3 to 7.5        3 to 10     5 to 15     G3JA-C416B        AC100-240

                                                                                                                              G3JA-C416B        AC/DC-24

                  19          10.9 to 32.8  ---          2.2 to 7.5   4 to 15         3 to 10         3 to 10     5 to 15     G3JA-C419B        AC100-240

                                                                                                                              G3JA-C419B        AC/DC-24

                  25          14.3 to 43    ---          4 to 11      5.5 to 22       3 to 10         3 to 15     7.5 to 20   G3JA-C425B        AC100-240

     Motor                                                                                                                    G3JA-C425B        AC/DC-24

                  30          17.3 to 52    ---          4 to 15      7.5 to 22       5 to 10         5 to 15     7.5 to 30   G3JA-C430B        AC100-240

     (Delta)                                                                                                                  G3JA-C430B        AC/DC-24

                  37          21 to 64      ---          5.5 to 18.5  7.5 to 30       7.5 to 20       7.5 to 20   10 to 30    G3JA-C437B        AC100-240

                                                                                                                              G3JA-C437B        AC/DC-24

Note: The applicable motor capacities given in the table are reference values. The motor FLA must fall            within the  current range of  the device.

     It is not possible to use motors that are outside the adjustable range of the Soft Starter.

Upgraded Models

Production of a new version of the Soft Starter (version 2) with added functions was started in August 2008. The DIP switch settings of the new

version are different from the previous version. For details, refer to Upgrades for Version 2 on page 13.

When replacing G3JA-C (version 2) with G3JA-D, refer to “Three-phase, 6-wire Motors (Star-delta Wiring)” list above.

■ Accessories (Order Separately)

            Product name                    Model                          Remarks

Auxiliary Contact Blocks       G32J-CA10                      Contact configuration:  1  NO

                               G32J-CA20                      Contact configuration:  2  NO

                               G32J-CA01                      Contact configuration:  1  NC

                               G32J-CA11                      Contact configuration:  1  NO/1     NC

Fan                            G32J-CF64

Round Terminal Block Adapters  G32J-TA10                      Set of 2 Adapters

Note: Refer to Safety Precautions on page 16.

                                                                                                                                                             2
                                                                                                                                                                        G3JA-C

Specifications

■ Ratings and Characteristics

Ratings

Item                                                 Model  G3JA-C403                        G3JA-C409      G3JA-C416        G3JA-C419         G3JA-C425    G3JA-C430        G3JA-C437

Rated operating current                                     3A              9A                              16 A             19 A              25 A         30 A             37 A

Heat dissipation, continuous                                11 W            12 W                            14 W             15 W              17 W         19 W             24 W

Rated operating voltage of main circuit                     200 to 480 VAC (±10%), 50/60 Hz (±5%), 3-phase

Main circuit power              Wire gauge                  2.5 to 25 mm2 (14 to 4 AWG), Stripping length (recommended): 11 mm

supply terminals                Tightening torque           2.3 to 3.4 N·m

(L1, L2, and L3)

Main circuit load               Wire gauge                  2.5 to 16 mm2 (14 to 6 AWG), Stripping length (recommended): 11 mm

power terminals                 Tightening torque           2.3 to 3.4 N·m

(T1, T2, and T3)

Control terminals               Wire gauge                  0.2 to 2.5 mm2 (24 to 14 AWG), Stripping length (recommended): 9 mm

(A1, A2, IN1, IN2,              Tightening torque           0.5 to 0.9 N·m

97, 98, 13, and 14)

Overload current range                                      1 to 3 A        3 to 9 A                        5.3 to 16 A      6.3 to 19 A       8.3 to 25 A  10 to 30 A       12.3 to 37 A

Control voltage                                             100 to 240 VAC or 24 VAC, 50/60 Hz, 24 VDC

Note: The load can be switched up to four times per hour. (Conditions: Rated current applied, Ambient temperature: 50°C max., Limit current:

                     300%, Start time: 15 s, ON time ratio: 70% max.) By using optional fans, however, it is possible to switch the load up to ten times per hour

                     under the same conditions.

G3JA Switching Frequency

G3JA-C (40°C, Start time: 10 s, Current limit: 350%                         G3JA-C (40°C, Start time: 10 s, Current limit: 350%

without fan)                                                                with fan used)

Operations/hour  60             G3JA-C403/C409                              Operations/hour  140                  G3JA-C403/C409

                 50             G3JA-C416/C419                                               120                  G3JA-C416/C419

                 40             G3JA-C425/C430/C437                                          100                  G3JA-C425/C430/C437

                 30                                                                          80

                                                                                             60

                 20                                                                          40

                 10                                                                          20

                 0   5  10  15  20       25      30  35     40                               0    5     10  15    20     25  30    35     40

                                                 Load current (A)                                                            Load current (A)

Short Circuit Coordination (Maximum Fuse or Circuit Breaker Size) Type 1

Item                                                               Model    G3JA-C403 G3JA-C409                   G3JA-C416        G3JA-C419         G3JA-C425  G3JA-C430    G3JA-C437

UL Class                K5 and RK5 fuse                                     Rated breaking current: 5             kA

UL-listed               combination (600 V)                                 12 A                     30 A         60 A             70 A              100 A      110 A        125 A

UL-listed               thermal electromagnetic      circuit       breaker  Rated breaking current: 5             kA

UL-listed               combination (600 V)                                 12 A                     30 A         60 A             70 A              100 A      110 A        125 A

Main Circuit

Item                                Classification                                           cULus (UL 508)                                          IEC (EN/IEC 60947-4-2)

Rated operating voltage                                     200 to 480 VAC                                                         400 VAC

Isolation rated voltage                                     600 VAC                                                                500 VAC

Dielectric strength (between the                            2,200 VAC                                                              2,500 VAC

control and main circuits)

Repetitive peak voltage                                     1,400 V

Operating frequency                                         50/60 Hz (±5%)

Utilization category                                        Intermittent duty                                                      AC-53b

Single-phase/3-phase                                        Equipment designed for 3-phase only

Rated impulse voltage                                       6 kV

DV/DT protection                                            1,000 V/μs

Overvoltage category                                        III

                                                                                                                                                                                           3
                                                                                                                                  G3JA-C

Control Circuits

Item                                         Classification            cULus (UL 508)                                IEC (EN/IEC 60947-4-2)

Rated operational voltage                                     100 to 240 VAC 50/60 Hz, 24 VAC 50/60 Hz, 24 VDC

Voltage range                                                 ±10% of control voltage

Overvoltage category                                          ---                                        III (See note.)

Input onstate voltage minimum during start (A1, A2)           90 VAC max. (100 to 240 VAC), 15.2 VAC/21.6 VDC max. (24 VAC/DC)

Input onstate current, during start with the G32J-            9.8 mA at 120 VAC; 19.6 mA at 240 VAC, 7.3 mA at 24 VAC/DC

CF64 Fan (IN1, IN2)

Input offstate voltage maximum (A1, A2)                       15 VAC min. (100 to 240 VAC), 3.6 VAC/5.1 VDC min. (24 VAC/VDC)

Offstate current consumption (IN1, IN2)                       10 mA max. (IN1), 12 mA max. (IN2)

Onstate current consumption, with Fan (A2)                    215 mA max. at 120 VAC/180 mA max. at 240 VAC, 660 mA max. at 24 VAC/800        mA

                                                              max. at 24 VDC

Onstate current consumption, without Fan (A2)                 205 mA max. at 120 VAC/145 mA max. at 240 VAC, 580 mA max. at 24 VAC/705        mA

                                                              max. at 24 VDC

Note:  Overvoltage category II applies when control or auxiliary contacts are connected to an SELV or PELV circuit.

Auxiliary Contacts

Item                                Classification                    cULus (UL 508)                                 IEC (EN/IEC  60947-4-2)

Rated operational voltage                              250 VAC/30 VDC

Rated impulse voltage                                  ---                                               4 kV

Dielectric strength                                    1,500 VAC                                         2,000 VAC

Overvoltage category                                   ---                                               III (See note.)

Operating frequency                                    50/60 Hz

Utilization category                                   D300                                              AC15

TB-97, -98             Control circuit configuration   Electromagnetic relay

(overload/fault)       Number of contacts              1

                       Contact                         NO contact

                       Current specifications          AC/DC

                       Rated operating current         0.6 A at 120 VAC, 0.3 A at 240 VAC

                       Contact switching capacity      Open: 72 VA

                                                       Close: 432 VA

TB-13, -14             Control circuit configuration   Electromagnetic relay

(normal/up-to-         Number of contacts              1

speed)

                       Contact                         NO contact

                       Current specifications          AC/DC

                       Rated operating current         0.6 A at 120 VAC, 0.3 A at 240 VAC

                       Contact switching capacity      Open: 72 VA

                                                       Close: 432 VA

Note: Overvoltage category II applies when control or  auxiliary contacts are connected to   an   SELV   or PELV circuit.

Standard Functions

Item                         Classification                   cULus (UL 508)                                   IEC (EN/IEC 60947-4-2)

Start time                                   2 s, 5 s, 10 s, 15 s, 20 s, 25 s, or 30 s

Soft start (initial torque)                  15%, 25%, 35%, or 65% of locked rotor torque

Current limit                                150%, 250%, 350%, or 450% of full-load current

Soft stop time                               0%, 100%, 200%, or 300% of the start time

Weight                                       Approx. 860 g

Vibration and Shock Resistance

Item                         Classification                   cULus (UL 508)                                   IEC (EN/IEC 60947-4-2)

Vibration resistance   Destruction           25-m/s2 peak, 10 to 55 to 10 Hz, 0.19-mm single amplitude

                       Malfunction           10-m/s2 peak, 10 to 55 to 10 Hz, 0.075-mm single amplitude

Shock resistance       Destruction           300 m/s2 (30 G)

                       Malfunction           150 m/s2 (15 G)

                                                                                                                                                  4
                                                                                                                               G3JA-C

Environmental Conditions

Item                  Classification                  cULus (UL 508)                                         IEC (EN/IEC 60947-4-2)

Ambient operating temperature          0 to 50°C

Ambient storage temperature            −25 to 85°C

Elevation                              2,000 m max.

Ambient operating humidity             5% to 85% (with no condensation)

Pollution degree                       2

Degree of protection                   IP20

Other Specifications

Item                           Classification         cULus (UL 508)                                         IEC (EN/IEC 60947-4-2)

EMI                   Noise terminal voltage     ---                                             Class A

(emission test)       Radiation field            ---                                             Class A

EMS                   Electrostatic discharge    4 kV contact discharge and 8 kV air  discharge

(immunity test)       Radio frequency            ---                                             Conforms    to IEC 60947-4-2

                      electromagnetic field

                      Electrical fast transient  ---                                             Conforms    to IEC 60947-4-2

                      Surge immunity             ---                                             Conforms    to IEC 60947-4-2

■ Applicable Standards

Safety standards                       UL 508 (Listing: File No. E64562), CSA 22.2 No. 14, EN/IEC 60947-4-2

                                                                                                                                       5
                                                                                                                                                                                                                              G3JA-C

Connections

■ Wiring

Two-wire Connections                                                                                                    Three-wire Connections

                                                         Fuse, NF breaker, etc.                                                                                               Fuse, NF breaker, etc.

                                                                           H3 H2                                                                                                          H3 H2

                                                                         H1       H4                 *1                                                                                   H1     H4
                                                                                  Transformer
                                                                    -TC                                                                                                           -TC                Transformer    *1

                                                                         X2       X1                                                                                                      X2     X1

                               L1      L2     L3         GRD                                                                                 L1             L2     L3             GRD

                  -E1              1       3      5                                                                                                     1       3      5

                                       G3JA          *2                                                                                 -E1                 G3JA          *2

     Main circuit                  2       4      6                          -SB                                             Main circuit               2       4      6                  -SB1

     terminals                                                           E-STOP                                              terminals                                                    E-STOP

                               T1      T2     T3                                                                                             T1             T2     T3

                                                                    Start/Stop                                                                                                            -SB2

                               -M      Motor                                                                                               -M              Motor                          Stop

                                                                                                                                                                                          -SB3

                                                                                                                                                                                          Start

                                                             A1     A2   IN1          IN2   97    98      13       14                                                             A1      A2         IN1   IN2  97      98    13         14

                                                             (+)    (−)                                                                                                           (+)     (−)

                                                                                         Overload/fault   Auxiliary                                                                                           Overload/fault  Auxiliary

                                                                         Control terminals                contact                                                                                Control terminals            contact

                                                                                      -E1                                                                                                                  -E1

Operation Chart:                      Two-wire Connections with Main Circuit                                            Operation Chart:                    Three-wire                 Connections with Main                                 Circuit

Fault Shutoff                                                                                                           Fault Shutoff

                                                                             Soft stop                                                                                                               Soft stop

                  Motor speed                                                              Coast to stop                                   Motor speed                                                          Coast to stop

                                                                                                         Time                                                                                                                 Time

                                      Start              Stable                       Stop                                                                                        Stable

                                                         operation                                                                                              Start         operation                       Stop

     Start/stop                                                                                           IN1 (IN2)-A2       Start

                                                                                                                                                                                                                                  IN1-A2

     E-stop                                                                                               A1-A2                                                                                                                   A1-A2

                                                                                                                             E-stop

     Normal                                                                                               13-14              Stop                                                                                                 IN2-A2

     Up-to-speed                                                                                          13-14

                                                                                                                             Normal                                                                                               13-14

                                                                                                                             Up-to-speed                                                                                          13-14

*1.  This transformer is used to convert the load voltage into the control voltage of                                   *1.  This transformer is used to convert the load voltage into the control voltage of

     the G3JA. A transformer is not required if the load voltage is within the rated                                         the G3JA. A transformer is not required if the load voltage is within the rated

     operational voltage range of the G3JA.                                                                                  operational voltage range of the G3JA.

*2.  The wiring in the following diagram is used for a 3-phase, 6-wire motor (Delta).                                   *2.  The wiring in the following diagram is used for a 3-phase, 6-wire motor (Delta).

                                                                                      1           3            5                                                                                           1            3           5

                                                                                            G3JA                                                                                                                    G3JA

                                                                                      2           4            6                                                                                           2            4           6

     L3                            L2                L1                       T1            T2            T3                 L3                         L2                L1                         T1             T2        T3

     (U2)                      (W2)               (V2)                        (U1)          (V1)         (W1)                (U2)            (W2)                      (V2)                          (U1)       (V1)          (W1)

                                                                    Motor                                                                                                                 Motor

                                                         -M                                                                                                                   -M

                                                                                                                                                                                                                                                      6
                                                                                                                                                                                                                     G3JA-C

Examples: Main Circuit Fault Shutoff                                                                                    Forward/Reverse Rotation

                                                                                                                        Note: 1.  Provide a time lag of at least 1.0 s between forward and re-

                                                  Fuse, NF breaker, etc.                                                          verse rotation.

                                                                                                                             2.   Disable phase reversal protection.

                                                                                                                                                                       Fuse, NF breaker, etc.

                                 1  3       5

                -KM                                              H3   H2

                                 2  4       6                    H1     H4  Transformer *2

                                                            -TC

                             L1     L2     L3                    X2     X1

                                 1      3      5        GRD                                                                                                                                   H3 H2

                -E1                 G3JA          *3                                                                                                                                          H1       H4

Main circuit                     2      4      6                                                                                                                                         -TC                Transformer *2

terminals                                                                                                                                                                                     X2       X1

                             T1     T2     T3                    -SB1                                                              -KM1                                -KM2

                                                                 E-STOP                                                                                                               GRD

                             -M     Motor

                                                                 -SB2                                                                                                                             -SB

                                                                 Stop                                                                   L1               L2     L3                            E-STOP

                                                                                                                                   -E1      1                3      5

                                            -KA                  -SB3                                                                                    G3JA          *3                           OFF
                                                                                                                                                                                              FORREV
                                                                                                                        Main circuit        2                4      6                               123

                                                                 Start                                                  terminals                                                             -SA

                                        -KM                                                                                             T1               T2     T3

                                                                                          -KA                                                                                                      -KM2          -KM1      -KM2     -KM1

                                                                                                                                   -M          Motor                                          -KM1            -KM2

                                                        A1       A2         IN1      IN2   97   98       13         14

                                                        (+)      (−)

                                                                                     Overload/fault      Auxiliary

                                                                        Control terminals                contact

                                                                                     -E1

Operation Chart: Three-wire Connections with Main Circuit                                                                                                                        A1   A2      IN1      IN2       97    98       13         14

Fault Shutoff                                                                                                                                                                    (+)  (−)

                                                                                                                                                                                                           Overload/fault       Auxiliary

                                                                                                                                                                                             Control terminals                  contact

                Motor speed                                                                                                                                                                              -E1

                                                                                                                        Operation Chart: Two-wire                                Connections with Forward/

                                                                                                                        Reverse Rotation

                                                                                                                                            Motor speed                                                Inertial stop

                                    Start      Stable operation         Stop              Time                                                                                                                       Soft stop

     Start                                                                                      IN1-A2

     Stop                                                                                       A1-A2

     E-STOP                                                                                     IN2-A2                                                          Start  Stable operation                Stop                     Time

Overload/fault                                                                                  97/98 (See note 1.)

Main circuit                                                                                                                       Start                                                                                        A1-A2

     Normal                                                                                     13-14                             Normal                                                                                        13-14

Up-to-speed                                                                                     13-14                        Up-to-speed                                                                                        13-14

*1. If an overload or other fault is detected, the main circuit will turn OFF, and the                                  *1.  This transformer is used to convert the load voltage into the control voltage of

     alarm contact (97-98) built into the G3JA will operate. (Refer to Description of                                        the G3JA. A transformer is not required if the load voltage is within the rated

     Functions on page 9 for details.)                                                                                       operational voltage range of the G3JA.

*2.  This transformer is used to convert the load voltage into the control voltage of                                   *2.  The wiring in the following diagram is used for a 3-phase, 6-wire motor (Delta).

     the G3JA. A transformer is not required if the load voltage is within the rated

     operational voltage range of the G3JA.

*3. The wiring in the following diagram is used for a 3-phase, 6-wire motor (Delta).

                                                                                                                                                                                                    1            3         5

                                                                                                                                                                                                            G3JA

                                                                                  1        3          5                                                                                             2            4         6

                                                                                     G3JA                                               L3                      L2     L1                     T1            T2         T3

                                                                                                                                      (U2)                   (W2)      (V2)                   (U1)         (V1)      (W1)

                                                                                  2        4          6

                             L3         L2        L1                        T1       T2         T3

                (U2)                (W2)          (V2)                      (U1)     (V1)       (W1)

                                                                                                                                                                                      Motor

                                                                                                                                                                             -M

                                                                 Motor

                                                        -M

                                                                                                                                                                                                                                               7
                                                                                                                                                                    G3JA-C

Operation

■ Operating Modes

Soft Start                                                                                Kick Start

A soft start is used to reduce mechanical shock when starting the                         A kick start, or boost, at the beginning of the start mode provides a

motor. The motor voltage is increased from the initial torque to full                     current pulse of 450% of the full-load current. The kick start time can

voltage.                                                                                  be set to OFF, 0.5 s, 1 s, or 1.5 s. This allows the motor to develop

The initial torque can be set to 15%, 25%, 35%, or 65% of the locked                      additional torque at start for loads which may need a boost to get

rotor torque. The motor voltage is gradually increased during the                         started.

acceleration ramp time. The acceleration ramp time can be set to 2 s,                     Some loads that may not start well in soft start mode will start more

5 s, 10 s, 15 s, 20 s, 25 s, or 30 s. The bypass relay turns ON after                     smoothly if the kick start is enabled to provide more rotational torque

the motor starts.                                                                         to the motor. Increase the kick start time one step at a time to

                                                                                          gradually increase the initial torque.

          Percentage of voltage  100%                                                     The current will increase temporarily during the kick start, but the

                                                                                          start mode that was selected will continue after the kick start has

                                                                                          been completed.

                                                                                          When the current limit start function has been enabled, the kick start

                                 Starting                                                 will be disabled.

                                 torque

                                                                                                                                          Kick start

                                                                                                    Percentage of voltage                 (when selected) *2

                                           Start t1      Stable                                                            100%

                                                         operation

                                                                              Time

Current Limit Start                                                                                                        Starting

This start mode is used when the maximum starting current must be                                                          torque *1

limited. During the start time, the thyristor will reduce the motor

terminal voltage to limit the current at startup. During stable                                                                           Start t1                  Stable

operation, the built-in bypass relay will be ON.                                                                                                               operation

                                                                                                                           Kick start t2                                    Time

The current limit can be set to 150%, 250%, 350%, or 450% of the                          Note: Refer to DIP Switch Settings on page 11 for details.

full-load current. The start time can be set to 2 s, 5 s, 10 s, 15 s, 20 s,               *1. Initial Torque Setting for Soft Start

25 s, or 30 s.                                                                            *2. Kick Start

current                          600%      Direct input                                   Soft Stop

full-load                                                Current limit start              A soft stop is used with applications that require an extended coast

                                                         (at 350% of full-load current )  to stop. When enabled, the voltage ramp down time can be set to

                                 350%                                                     one, two, or three times the start time. The motor will stop when the

motor                                                                                     motor voltage drops to the point where the load torque is greater

of                                                                                        than the motor torque.

Percentage                       100%

                                           Start time    Stable                                     Motor speed

                                                         operation
                                                                    Time

                                                                                                                                                      Coast

                                                                                                                           Start t1       Stable      to stop

                                                                                                                                      operation       Soft-stop t3

                                                                                                                                                                    Time

                                                                                          Start Time for a Soft Start or Current

                                                                                          Limit Start

                                                                                          A built-in current transformer (CT) is used to detect the motor

                                                                                          current. The completion of motor startup is determined by detecting

                                                                                          the convergence of the current as the speed of the motor increases.

                                                                                          The Soft Starter operation is then changed to stable operation. The

                                                                                          start time given here is a guideline for when the total load current set

                                                                                          on the overload FLA setting dial and the actual load current are the

                                                                                          same. If the motor load is smaller, the motor will start faster, so that

                                                                                          actual start time will be shorter than the start time given here.

                                                                                          Soft Stop Time

                                                                                          The soft stop function gradually reduces the motor voltage to prevent

                                                                                          the motor from stopping suddenly under a large load. A built-in CT is

                                                                                          used to detect the motor current and size of the current is used to

                                                                                          determine the size of the load and the rate at which the voltage is

                                                                                          reduced. If the motor load is extremely small, the soft stop time will

                                                                                          be very short.

                                                                                                                                                                                  8
                                                                                                                   G3JA-C

■ Description of Functions

Overload Protection                                                      Phase Loss

The G3JA-C is equipped with overload protection. The overload            The G3JA-C monitors phase loss. If phase loss lasts for two power

class can be set to OFF, 10, 15, or 20. Either automatic or manual       supply frequency cycles, the G3JA-C turns OFF the output, indicates

mode can be used to reset an overload (trip). Set the trip current to    the phase loss with a flashing LED indicator and closes the alarm

the rated full-load current of the motor through the overload FLA        contact.

setting dial. When an overload fault occurs, the G3JA-C indicates the

overload with a flashing LED indicator and closes the alarm contact.     Current Imbalance

After an error is detected, the SCR will become hot, and an

overtemperature fault may also be detected. If it is, pushing the reset  The G3JA-C monitors the phase current imbalance. If the imbalance

button will not reset the system. Resetting will be possible once the    exceeds the preset limit, the G3JA-C turns OFF the output, indicates

temperature of the SCR has decreased. Wait about two minutes to          the current imbalance with a flashing LED indicator and closes the

allow the SCR to cool (assuming the ambient temperature is normal)       alarm contact.

Overtemperature                                                          Shorted SCR

The G3JA-C monitors the SCR temperature through an internal              The G3JA-C always checks the SCR for a short circuit before the

thermistor. If the SCR gets too hot, the G3JA-C turns OFF the            starting sequence. If a short circuit is found, the G3JA-C stops the

output, indicates the overtemperature status with a flashing LED, and    starting sequence, indicates the short circuit with a flashing LED

closes the alarm contact. Pushing the reset button will not reset the    indicator, and closes the alarm contact.

system. Resetting will be possible once the temperature of the SCR

has decreased. Wait about two minutes to allow the SCR to cool

(assuming the ambient temperature is normal).

Phase Reversal Protection

When this function is enabled with a DIP switch setting, the G3JA-C

checks phase sequence prior to startup. If the G3JA-C detects a

phase reversal fault in the main circuit power supply, it stops the

starting sequence, indicates the phase reversal with a flashing LED

indicator, and closes the alarm contact.

                                                                                                                                               9
                                                                                                                                                          G3JA-C

Nomenclature

■ Part Names and Functions

Upgraded Models                                                                                                DIP Switch Configuration

Production of a new version of the Soft Starter (version 2) with                                               Use the DIP switch to set the functions.

added functions was started in August 2008. The DIP switch                                                     DIP switch                      Function

settings of the new version are different from the previous version.                                           pin

For details, refer to Upgrades for Version 2 on page 13.                                                            1

                                                                                                                    2      Start time

                                                                                                                    3      Start mode (current limit start or soft start)

                                                                               Main Circuit Terminals,              4      Current limit start setting (when selected) or initial

                                                                               Power Supply Side                    5      torque setting for a soft start (when selected)

                                                                                                                    6      Soft stop

                                                                                                                    7

                                                                                                                    8      Long time setting for start time

                                                                                                                    9      Kick start

                                                                                                                    10

                                                                                                                    11

                                                                                                                    12     Overload class selection

Reset Button                                                                                                        13     Overload reset

All faults can be reset by pressing the Reset Button or turning

OFF the control power supply. Cooling time may be required                                                          14     Auxiliary/optional auxiliary contact (normal/up-to-speed)

before overload and overtemperature status can be reset.                                                            15     Motor wiring (Line or Delta)

Note: Test Mode for overload testing will be entered when the                  G3JA-C        Ver.2

Reset Button is pressed for approximately seconds.                             SOFT STARTER                         16     Phase reversal protection

Test Mode will be cancelled when the Reset Button is

pressed again.

                                                                                                               Overload FLA Setting Dial

                                                                                                               Use this dial to set the trip current to the rated full-load

                                                                                                               current of the motor. If the setting is not correct, it will not

                                                                                                               be possible to drive the motor properly.

                                                                                                               For a 3-phase, 6-wire motor, use the following formula

                                                                                                               to calculate the dial setting.

                                                                                                               Set value = Total motor load current/1.73

                                                                                                               For example, if the total motor load current is 20 A, the

                                                                                                               dial setting is 11.6 A (20 A/1.73).

Control Terminals                                                                                              RUN/FAULT Indicator

The G3JA-C has eight input terminals on the front. Each

terminal is described in the following table.                                                                  The G3JA-C monitors the status before startup and

                                                                                                               during operation. One indicator indicates both normal

Terminal                          Description                                                                  operation (RUN) and faults (FAULT). If the G3JA-C

A1        Control power supply input                                                                           detects a fault, it turns OFF the motor and indicates

A2        Control power supply common                                                                          the fault with a flashing LED indicator.

                                                                                                               The G3JA-C monitors the following conditions.

IN1       START input                                                                                                                 Flashing indicator status

IN2       STOP input                                                           Main Circuit Terminals,              Fault

97        NO auxiliary contact (auxiliary contact for fault detection output)  Load Side                       Overload

98        NO auxiliary contact (auxiliary contact for fault detection output)                                  Over-

13        NO auxiliary contact (normal/up-to-speed)                                                            temperature

14        NO auxiliary contact (normal/up-to-speed)                                                            Phase

                                                                                                               reversal

Auxiliary Contacts

The G3JA-C is equipped with two auxiliary contacts as a                                                        Phase loss

standard feature. One contact can be used for fault detection                                                  Current

output. The other one is used to output operating status and                                                   imbalance

can be set to either Normal or Up-to-speed using the DIP                                                       Shorted

switch setting at pin number 14.                                                                               SCR

An optional Auxiliary Contact Block can be added, and DIP

switch pin number 14 can be used to set the operating status to                                         Note:  The indicator will flash seven times in test mode (trip test).

output (either Normal or Set Speed).

                                                                                                                                                                                      10
                                                                                                                                             G3JA-C

■ DIP Switch Settings

Start Time t1                                 Initial Torque                         Setting for                   Current Limit             Start Setting

      DIP  switch  pins              Time     Soft Start                                                           DIP switch pins           FLA current

1              2         3    (seconds)       DIP switch pins                                LRT initial           4               5         limit (%)

OFF        OFF           OFF           2               4                   5                 torque (%)            OFF             OFF       150%

ON         OFF           OFF           5      OFF                          OFF               15%                   ON              OFF       250%

OFF        ON            OFF           10     ON                           OFF               25%                   OFF             ON        350%

ON         ON            OFF           15     OFF                          ON                35%                   ON              ON        450%

OFF        OFF           ON            20     ON                           ON                65%

ON         OFF           ON            25

OFF        ON            ON            30

Start Mode (Current Limit

Start or Soft Start)

DIP switch pin pins3          Setting

      ON                 Soft start

      OFF                Current limit start

Soft Stop t3                                  Kick Start t2                                                        Overload Class            Selection

DIP switch pins               Setting         DIP switch pins                                Time (seconds)        DIP switch pins                  Overload

   6               7                                       9               10                                      11                    12         class

OFF               OFF    Coast to stop        OFF                          OFF               OFF                   OFF             OFF              OFF

ON                OFF    100% of the          ON                           OFF                          0.5        ON              OFF              10

                         start time           OFF                          ON                           1.0        OFF                ON            15

OFF               ON     200% of the          ON                           ON                           1.5        ON                 ON            20

                         start time

ON                ON     300% of the          * Set Kick Start to OFF if             the     G3JA is used with a

                         start time           Current Limit Start.

                                              Auxiliary Contacts and

                                              Optional Auxiliary Contact

Overload Reset                                Block                                                                Motor Wiring

DIP switch pin 13             Reset           DIP switch                                     Optional              DIP switch pin 15         Motor  wiring

           ON               Automatic         pin 14                       Auxiliary         Auxiliary                         ON            Line

      OFF                   Manual                                         contacts          Contact                    OFF                  Delta

                                                                           (13 to 14)                   Block

                                                                                             (23 to 24)

                                                           ON              Up-to-speed       Normal

Phase Reversal           Protection                        OFF             Normal            Up-to-speed                           G3JA                    G3JA

DIP switch pin 16             Setting                                                        Soft stop

           ON            Disabled                      Motor speed

      OFF                Enabled                                                             Coast to stop

                                                                                             during soft stop

                                                                                                                        Motor                Motor

                                                                    Start  Stable operation  Stop            Time

                                              Normal                                                                    Line                 Delta

                                              Up-to-speed

                                              Normal:               Power supplied to motor

                                              Up-to-speed:          Bypass relay ON

                                                                                                                                                                 11
                                                                                                                                                                 G3JA-C

■ Engineering                       Data

Trip Curves

Trip Class 10                                    Trip Class                     15                            Trip Class                     20

Time (s)1,000                                    Time (s)  1,000                                              Time (s)  1,000

                         Cold trip                                              Cold  trip                                                       Cold trip

          100                                              100                                                          100

                                                                                                                                   Hot trip

               Hot trip                                               Hot trip

          10                                               10                                                           10

          1                                                1                                                                  1

          100                             1,000            100                                   1,000                        100                                    1,000

                                    Current (%)                                                  Current (%)                                                         Current (%)

■ Dimensions                                                                                                                                                         (Unit: mm)

                                                                                                                                   Panel     Cutouts

                                                 44.8                                       109               3                                  4.5 dia. or     M4

                                                                                                                        46.4

                                                                      141.5                                                                                 132

                                                                                                                                             35

Note: All models are the same size regardless    of the capacity.

Mounting Dimensions for the Auxiliary            Contact Block and Round                    Terminal Block    Adapter

                                                 44.8             10                        109               3

                                                                      23

                                                                                                                        46.4

                                                                      141.5

                                                                      23

                                                                                                                                                                                  12
                                                                                                                                    G3JA-C

Upgrades for Version 2

■ Upgrades                                                                ■ Identifying Upgraded Models

1.  Control of 3-phase, 6-wire motors (star-delta wiring) is supported.   You can check whether the G3JA is an upgraded version by the

2.  The soft start time can be set to up to 30 s.                         markings on the G3JA or the label on the box. If the G3JA is not

                                                                          marked “Ver. 2,” it is the previous version.

                                                                          Markings on Unit                  Label on Box

                                                                                                                                         Ver.2

■ Previous Version

The DIP switch settings are different for the      upgraded version (version 2) and the previous version.

Refer to the following tables for compatibility.

Comparison of Functions                                                   Comparison of DIP Switch Settings

          Item      Previous version               New version            DIP         Previous version                  New version (version 2)

                                                   (version 2)            switch pin

1. 3-phase, 6-wire  Control not                    Control possible.      1           Start time                        Start time

motors (Delta)      possible.                                             2           Start mode (current limit         Start mode (current limit

2. Soft start time  2, 5, 10, or 15 s              2, 5, 10, 15, 20, 25,  3           start or soft start)              start or soft start)

settings                                           or 30 s                4           Current limit start setting       Current limit start setting

                                                                          5           (when selected) or initial        (when selected) or initial

                                                                                      torque setting for a soft         torque setting for a soft

                                                                                      start (when selected)             start (when selected)

                                                                          6           Soft stop                         Soft stop

                                                                          7

                                                                          8*          Not used                          Long time setting for start

                                                                                                                        time

                                                                          9           Kick start                        Kick start

                                                                          10

                                                                          11          Trip class selection              Trip class selection

                                                                          12

                                                                          13          Overload (trip) reset             Overload (trip) reset

                                                                          14 *        Auxiliary contact (normal/        Auxiliary contact or

                                                                                      up-to-speed)                      Optional Auxiliary Contact

                                                                                                                        Block (normal/up-to-

                                                                                                                        speed)

                                                                          15 *        Optional Auxiliary Contact        Motor wiring

                                                                                      Block (normal/up-to-              (Line or Delta)

                                                                                      speed)

                                                                          16          Phase reversal protection         Phase reversal protection

                                                                          * These settings are different for the previous version and the new version.

                                                                                                                                                        13
                                                                                                                    G3JA-C

Comparison of DIP Switch Setting Differences

1. Start Time

                           Previous version                                              New version   (version 2)

               DIP switch pins                        Time (unit: s)                DIP  switch pins                Time (unit: s)

    1                      2                 8                          1                   2          8

OFF                        OFF            Not used            2         OFF              OFF           OFF          2

ON                         OFF                                5         ON               OFF           OFF          5

OFF                        ON                                 10        OFF                 ON         OFF          10

ON                         ON                                 15        ON                  ON         OFF          15

                                                                        OFF              OFF           ON           20

                                     ---                                ON               OFF           ON           25

                                                                        OFF                 ON         ON           30

2. Auxiliary Contact and Optional Auxiliary Contact Block               3. Motor Wiring Method (New Version)

(New Version)                                                           Optional Auxiliary Contact Block (Previous Version)

Auxiliary Contact (Previous Version)                                         Previous version          New version (version 2)

Previous version                     New version (version 2)            DIP switch       Optional      DIP switch   Motor wiring

DIP switch     Auxiliary   DIP switch     Auxiliary   Optional          pin 15      Auxiliary Contact  pin 15

pin 14                          pin 14    contacts    Auxiliary                     Block (23 to 24)

               contacts                   (13 to 14)  Contact Block     ON          Up-to-speed        ON           3-phase, 3-wire

               (13 to 14)                             (23 to 24)                                                    motor (Line)

ON          Up-to-              ON        Up-to-      Normal            OFF         Normal             OFF          3-phase, 6-wire

            speed                         speed                                                                     motor (Delta)

OFF         Normal              OFF       Normal      Up-to-speed

Note: With the new version, it is not possible to individually set the

auxiliary contacts (13 to 14) and Optional Auxiliary Contact

Block (23 to 24).

                                                                                                                                     14
                                                                                                                                    G3JA-C

■ Accessories (Order Separately)

Auxiliary Contact Blocks                                               Fan

G32J-CA10                                                              G32J-CF64

G32J-CA20

G32J-CA01                                                              It is possible to perform switching four times

G32J-CA11                                                              per hour without a fan if the G3JA is used at

                                                                       the rated current in an ambient temperature

                                                                       of 50°C max. with a sine current of 300%, a

                                                                       start time of 15 s, and an ON time ratio of

                                                                       70% max. If a fan is used, switching can be

Mounting                                                               performed ten times per hour under the

                                                                       same conditions.

1.  Insert the connector and hooks on the Auxiliary Contact Block      Mounting

    (G32J-CA) into the mounting holes of the G3JA. When doing so,

    be careful that the connector terminals do not bend.               1.  Mount the fan so that the arrow on the surface of the Fan (G32J-

2.  Press down on the Auxiliary Contact Block in the direction of          CF64) is in the direction shown in the figure.

    arrow 2 in the figure until you hear a click.                      2.  Insert the fan connector into the G3JA connector until it clicks into

3.  To wire the Auxiliary Contact Block, use sheathed wire (length of      place.

    stripped wire: 9 mm) with a core thickness of 0.5 to 2.5 mm2       3.  Mount the fan on the G3JA.

    (AWG18 to AWG14). Use a tightening torque of 1.0 to 1.1 N·m.

                                                                                             Fan

                            Auxiliary Contact

                            Blocks

Removing                                                               Round Terminal Block Adaptor

1.  Gradually pull out the connector on

    the top part of the Auxiliary Contact                              G32J-TA10

    Block (G32J-CA) in the direction of

    arrow 1 in the figure.                                             This is a terminal block adaptor for

2.  Pull the Auxiliary Contact Block in the                            wiring with round crimp terminals.

    direction of arrow 2 in the figure.                                                                                                           10

3.  Pull the Auxiliary Contact Block in the                                                                          13

    direction of arrow 3 in the figure and                             Mounting                                            23

    remove it.                                                         Once the Terminal Block Adaptor for Round Terminals is wired,

                                                                       mount it to the main circuit terminals of the G3JA. If wiring is

    Contacts                Contact form                  Model        performed after mounting the Terminal Block Adaptor for Round

1NO                                                G32J-CA10           Terminals on the G3JA, tighten the screws again on the main

                 23                            24                      terminals of the G3JA and the Terminal Block Adaptor to the

                                                                       specified tightening torque once wiring is completed.

2NO              33                            34  G32J-CA20           Note: 1.    The Round Terminal Block

                                                                                   Adaptor (G32J-TA10) is

                 23                            24                                  delivered with the cover

                                                                                   removed.

1NC                                                G32J-CA01                2.     The mounting strength of the

                                                                                   cover on the Round Terminal

                 11                            12                                  Block Adaptor has been

1NO/1NC                                            G32J-CA11                       increased to prevent it from

                 11                            12                                  becoming removed or falling

                                                                                   off.

                 23                            24                                  Remove the cover by inserting         Three, M4

                                                                                   a flat-head screwdriver into the

Specifications                                                                     cover bump on the back of the Round Terminal Block

                                                                                   Adaptor and making a gap. Be careful not to become injured

         Item                                  Specifications                      when removing the cover.

Control circuit method      Electromagnetic relay                           3.     Tighten the screws to the specified torque.

Current specifications      AC/DC                                                  The tightening torque for mounting the Round Terminal

                                                                                   Block Adaptor to the G3JA is 2.3 to 3.4 N·m.

Rated operating             2.5 A, 300 VAC                                         The tightening torque for wiring the Round Terminal Block

current                                                                            Adaptor is G3JA is 0.98 to 1.37 N·m.

                                                                                                                                                      15
                                                                                                                                         G3JA-C

Safety Precautions

Refer to Safety Precautions for All Solid State Relays.                  Installation and Use

                         !CAUTION                                        •  If two or more Units are used with close

                                                                            mounting, it is recommended to install

                                                                            them with a gap of approximately 5 mm

Installation and Environment                                                between Units. (No gap is required for

                                                                            Auxiliary Contact Units.)

Always turn OFF the power supply if there is a possibility                  If close mounting is used, also take into

that the terminals may be touched. Not doing so may                         account the increase in ambient

occasionally result in minor electric shock.                                temperature due to heat dissipated by the

                                                                            Units themselves. In particular, use fans for

Firmly tighten the screws to the specified torque. If the                   sufficient ventilation with external air if the                     5 mm

screws are not firmly tightened, minor fires may                            Units are mounted inside a panel.

occasionally occur. Refer to Specifications and                          •  Do not use the product with loads greater than the rated current.

Accessories (Order Separately) for details.                                 Doing so will result in abnormal heat radiation.

Maintenance                                                              •  For protection against grounding accidents, always install a fuse,

                                                                            breaker, or other protective device on the power supply side.

The charge of the electrolytic capacitor used in the                     •  Select a power supply that is in the rated frequencies. Not doing so

internal circuit may occasionally result in minor electric                  will result in malfunction, failure, or burning.

shock. Before touching the terminals, turn OFF the power                 ■ Precautions for Correct Use

supply and make sure that the voltage has been

eliminated due to discharge.

■ Precautions for Safe Use                                               Altitude Derating

                                                                         The rated current of the G3JA must be decreased at altitudes above

                                                                         2,000 m because of decreased efficiency of the heat sink and fan

Operation and Storage Locations                                          (G32J-CF64).

•  Do not use or store the SSR in the following locations. Doing so      Warning Labels Included with Product

   may result in damage, malfunction, or deterioration of performance

   characteristics.                                                      If voltage is applied to the main circuit power supply side of the

   • Locations subject to excessive shock or vibration                   G3JA, there will be voltage in the terminals on the main circuit load

   • Locations subject to exposure to water, oil, or chemicals           side even if the G3JA is OFF. Be sure to use the warning labels

                                                                         included with the product to provide notification of this hazard on

   • Usage locations subject to ambient temperatures outside the         locations such as the motor terminal box, G3JA, and control panel.

   range of 0°C to 50°C                                                  Main Circuit Cutoff at Error

   • Storage locations subject to ambient temperatures outside the

   range of −25°C to 85°C                                                Safety is further improved by turning OFF the contacts and other

   • Usage locations subject to humidity outside the range of 5% to      lines on the main circuit power supply side of the G3JA as shown in

   85% or to condensation due to sudden temperature change               the following figure. For a wiring example, refer to Examples: Main

   • Locations subject to corrosive or flammable gases                   Circuit Fault Shutoff.

   • Locations subject to excessive dust, salinity, or metal powder.     Standard Connection Diagram for Main Circuit Cutoff at Error

Installation                                                                                     KM                 L1                   T1

                                                                                                                             1        2

                                                                                                                    L2       3        4  T2     Motor

• Do not drop the product or subject it to abnormal vibration or shock.                                             L3                   T3

   Doing so may result in failure or malfunction.                                                                            5        6

• Do not install the product if your hands are dirty with oil or metal      Fuse, breaker,                                      G3JA

   dust. Doing so may result in failure.                                    etc.

Installation and Handling                                                Connecting              Varistors

• The product is heavy. Firmly mount it on a DIN Track. Also securely    The G3JA will be damaged by overvoltage if

   mount the DIN Track.                                                  high-energy surge voltage builds up in the AC

• Mount the product in the specified mounting direction. Abnormal        power supply that is used. If surge voltage is a

   heat radiation from the Unit will result in SCR failure or damage.    problem, connect three varistors with one on

                                                                         each phase in the position shown in the following               L1     L2     L3

                                                                         figure. The following varistor is recommended.                      1      3      5

Installation and Wiring                                                  Also, when you connect the varistor, always                         2      4      6

•  Make sure that all lead wires are appropriate for the load current.   install a fuse, breaker, or other protective device             T1     T2     T3

   Abnormal heat radiation from the wires may result in burning.         on the power supply side of the varistor.                              Motor

•  Do not use wires with a damaged sheath. Doing so may result in           Varistor voltage: 910 V

   electric shock or current leakage.                                       Energy resistance: 200 joules min. (10 × 1000                µs)

•  Do not wire power lines or high-tension lines along with the control  Limiting Resistor

   circuit lines in the same conduit or duct. Doing so may result in

   damage or malfunction due to induction.

•  Use wires of an appropriate length. Wires of improper length may      The G3JA cannot use a limiting resistor.

   result in malfunction or burning due to induction.                    Operation Start Signal

•  Connect to the primary side (i.e., power supply side) of the G3JA

   output terminals if you use a power capacitor.                        Do not apply an operation start signal during a soft stop. Doing so

                                                                         will result in abnormal operation.

                                                                                                                                                              16
                                                                                                             G3JA-C

Connecting a Power Capacitor

If you use a power capacitor, connect it to the primary side (i.e.,

power supply side) of the G3JA output terminals.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

In the interest of product improvement, specifications are subject to change without notice.

                                                                                                                     17
                                                      Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or

comments.

                                                      Warranty and Limitations of Liability

WARRANTY

OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)

from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR

FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS.                     ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS

DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.                                OMRON DISCLAIMS ALL OTHER

WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY

OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS

IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT

LIABILITY.

In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS

OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT

SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

                                                      Application Considerations

SUITABILITY FOR USE

OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's

application or use of the products.

At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the

products.   This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,

machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given.             This is not intended to be an exhaustive list of all possible

uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:

•  Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.

•  Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,

   safety equipment, and installations subject to separate industry or government regulations.

•  Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE

SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND

INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

PROGRAMMABLE PRODUCTS

OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.

                                                                    Disclaimers

CHANGE IN SPECIFICATIONS

Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.

However, some specifications of the products may be changed without any notice.     When in doubt, special model numbers may be assigned to fix or

establish key specifications for your application on your request.  Please consult with your OMRON representative at any time to confirm actual

specifications of purchased products.

DIMENSIONS AND WEIGHTS

Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

PERFORMANCE DATA

Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent               the

result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON

Warranty and Limitations of Liability.

ERRORS AND OMISSIONS

The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,

typographical, or proofreading errors, or omissions.

                                                                                                                                                                         2011.5

                                                      In the interest of product improvement, specifications are subject to change without notice.

OMRON Corporation

Industrial Automation Company

http://www.ia.omron.com/

                                                                                                          (c)Copyright OMRON Corporation 2011 All Right Reserved.
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Omron:

G3JA-C403B AC100-240    G3JA-C403B AC/DC24    G3JA-C409B AC100-240  G3JA-C409B AC/DC24  G3JA-C416B

AC100-240  G3JA-C416B AC/DC24  G3JA-C419B AC100-240  G3JA-C419B AC/DC24  G3JA-C425B AC100-240

G3JA-C425B AC/DC24      G3JA-C430B AC100-240  G3JA-C430B AC/DC24  G3JA-C437B AC100-240  G3JA-C437B

AC/DC24
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2020 EEWORLD.com.cn, Inc. All rights reserved