  Three-phase Hybrid Soft Starter                                                                                                               CSM_G3JA-C_DS_E_6_1
  (Soft Start, Kick Start, Current Limit Start, Soft Stop)

G3JA-C

Built-in Bypass Relay and Smooth Motor Starts/Stops
Achieved in a Compact Starter

Advanced functions include soft start, kick start, and soft stop.
Phase control using a thyristor limits current when the motor starts, and a

bypass relay minimizes power loss while the motor is running.
Controls 3-phase, 3-wire motor or 3-phase, 6-wire motor.
Built-in electronic thermal overload relay.
Built-in fault diagnosis for overtemperature, phase reversal, phase loss/open

load, current imbalance, and shorted SCR.
cULus listed; complies with IEC standards.
Mounts with screws or to DIN track.
Built-in operation/fault indicator.
Built-in auxiliary contact for fault indication.
Built-in auxiliary contact to output operating status.
An Optional Auxiliary Contact Block can be added to output operating status.

          Refer to Safety Precautions on page 16.

Characteristics                                                                                              Model Number Structure

Item                                                                Type 3-phase, 3-lead  3-phase, 6-lead     Model Number Legend
                                                                                          motor (star-delta
Applicable                                                                   motor        wiring)
motors
            Rated operating voltage (motor)                                      200 to 480 VAC (10%)       Soft Starter
Functions                                                                            50/60 Hz (5%)

            Rated operating current (motor)                         3 to 37 A             3 to 64 A          G3JA-C@@@@

            Applicable motor capacity                               0.55 to 7.5 kW 0.55 to 18.5 kW           1 2 345
            IEC 60947-4-2, 230 VAC

            Voltage control start (See note.)                                                                1. Controller Type

            Kick start                                                                                       C: Soft start/stop

            Current limit start (See note.)                                                                  2. Rated Operating Voltage of Main Circuit

            Soft stop                                                                                        4: 200 to 480 VAC, 3 phase, 50/60 Hz

            Fault detection relay output (NO)                                                                3. Rated Operating Current of Main Circuit

            Auxiliary contact output (NO)                                                                    03: 3 A   19: 19 A 30: 30 A

            Optional Auxiliary Contact Block                                                                 09: 9 A   25: 25 A 37: 37 A
            output
                                                                                                             16: 16 A
            Fault detection LED indicator                                                
                                                                                                             4. Terminal Type
            Overload protection                                                           
                                                                                                             B: Screw terminals (screw clamps)
            Phase reversal detection                                                      
                                                                                                             5. Control Voltage
            Current imbalance detection                                                   
                                                                                                             AC100-240: 100 to 240 VAC 50/60 Hz

Note: Select either voltage control start or current limit start.                                            AC/DC24: 24 VAC 50/60 Hz, 24 VDC

Applicable Motors                                                                                            Accessories

Three-phase, 3-wire Motor                                           Three-phase, 6-wire Motor                G32J-@@
(Line)                                                              (Delta)
                                                                                                                          12
The G3JA-C can be                                                   A 3-phase, 6-                            1. Option
used for a 3-phase,
3-wire motor as                                                     wire motor                                   CA: Auxiliary Contact Block
shown in the                                                                                                 2. Number of Contacts
following diagram.                                                  (that supports
(Star-delta wiring for                                                                                           10: 1 NO 01: 1 NC
the motor is required                                               a star-delta                                 20: 2 NO 11: 1 NO/1 NC
if a 3-phase, 6-wire
motor is used.)                                                     operation                                G32J-@

                                                             Motor  start) can be                                         1
                                                                                                             1. Option
                                                                    used. The
                                                                                                                 CF64: Fan
                                                                    G3JA-C is                                    TA10: Round Terminal Block Adapter

                                                                    compact and

                                                                    includes

                                                                    functionality

                                                                    for devices             Motor

                                                                    that start

                                                                    operation with

                                                                    star-delta

                                                                    ( - ) wiring.

                                                                                                                                                                     1
                                                                                                                 G3JA-C

Ordering Information

List of Models

Soft Starters (Complies with IEC 60947-4-2, UL508)

Three-phase, 3-wire Motors

Applicable motor Rated Operating                        Applicable motor capacity (reference values)             Model

     wiring   Current of Main Circuit                   kW                                     HP

                 Current Adjustable 200 VAC 50/ 230 VAC           380/400/      200 VAC      230 VAC  460 VAC
              rating (A) range (A)            60 Hz               415 VAC         60 Hz        60 Hz    60 Hz
                                                        50 Hz
                                                                    50 Hz

              3             1 to 3     0.2 to 0.4 0.37         0.75         0.5           0.5         0.5 to 1   G3JA-C403B AC100-240

                                                                                                                 G3JA-C403B AC/DC-24

              9             3 to 9     0.55 to 1.5 1.5         3            0.75 to 1.5 0.75 to 2 1.5 to 3       G3JA-C409B AC100-240

                                                                                                                 G3JA-C409B AC/DC-24

              16            5.3 to 16 1.1 to 2.2 3             5.5          1.5 to 3      1.5 to 3    5 to 7.5   G3JA-C416B AC100-240

                                                                                                                 G3JA-C416B AC/DC-24

              19            6.3 to 19 1.5 to 3.7 4             5.5          1.5 to 3      2 to 3      5 to 10    G3JA-C419B AC100-240

                                                                                                                 G3JA-C419B AC/DC-24

              25            8.3 to 25 2.2 to 5.5 4             9.5          3 to 5        3 to 5      7.5 to 10 G3JA-C425B AC100-240

     Motor                                                                                                       G3JA-C425B AC/DC-24

              30            10 to 30 2.2 to 5.5 5.5            11           3 to 5        5 to 7.5    7.5 to 15  G3JA-C430B AC100-240
                                                                                                                 G3JA-C430B AC/DC-24
     (Line)

              37            12.3 to 37 3.7 to 7.5 7.5          15           5 to 7.5      5 to 10     10 to 20   G3JA-C437B AC100-240

                                                                                                                 G3JA-C437B AC/DC-24

Note: The applicable motor capacities given in the table are reference values. The motor FLA must fall within the current range of the device.
        It is not possible to use motors that are outside the adjustable range of the Soft Starter.

Three-phase, 6-wire Motors (Star-delta Wiring)

Applicable       Rated operating                       Applicable motor capacity (reference values)                             Model
motor wiring  current of main circuit
                                                        kW                                     HP                G3JA-C403B AC100-240
                                                                                                                 G3JA-C403B AC/DC-24
                 Current Adjustable 200 VAC 50/ 230 VAC           380/400/      200 VAC      230 VAC    460 VAC  G3JA-C409B AC100-240
              rating (A) range (A)            60 Hz               415 VAC         60 Hz        60 Hz      60 Hz  G3JA-C409B AC/DC-24
                                                        50 Hz                                                    G3JA-C416B AC100-240
                                                                    50 Hz                             0.5 to 2   G3JA-C416B AC/DC-24
                                                                                                      2 to 7.5   G3JA-C419B AC100-240
              3             1.7 to 5.1 ---           0.25 to 1.1 0.55 to 2.2 1            1           5 to 15    G3JA-C419B AC/DC-24
                                                                                                      5 to 15    G3JA-C425B AC100-240
              9             5.1 to 16 ---            1.1 to 4  2.2 to 7.5 1.5 to 3        1 to 5      7.5 to 20  G3JA-C425B AC/DC-24
                                                                                                      7.5 to 30  G3JA-C430B AC100-240
              16            9.1 to 27.6 ---          2.2 to 7.5 4 to 11     3 to 7.5      3 to 10     10 to 30   G3JA-C430B AC/DC-24
                                                                                                                 G3JA-C437B AC100-240
              19            10.9 to 32.8 ---         2.2 to 7.5 4 to 15     3 to 10       3 to 10                G3JA-C437B AC/DC-24

                        25  14.3 to 43 ---           4 to 11   5.5 to 22    3 to 10       3 to 15
                            17.3 to 52 ---                                  5 to 10       5 to 15
     Motor                  21 to 64 ---             4 to 15   7.5 to 22    7.5 to 20     7.5 to 20

                        30                           5.5 to 18.5 7.5 to 30

     (Delta)

                        37

Note: The applicable motor capacities given in the table are reference values. The motor FLA must fall within the current range of the device.
        It is not possible to use motors that are outside the adjustable range of the Soft Starter.

Upgraded Models

Production of a new version of the Soft Starter (version 2) with added functions was started in August 2008. The DIP switch settings of the new
version are different from the previous version. For details, refer to Upgrades for Version 2 on page 13.
When replacing G3JA-C (version 2) with G3JA-D, refer to "Three-phase, 6-wire Motors (Star-delta Wiring)" list above.

Accessories (Order Separately)

     Product name                      Model                            Remarks
                                                        Contact configuration: 1 NO
Auxiliary Contact Blocks    G32J-CA10                   Contact configuration: 2 NO
                                                        Contact configuration: 1 NC
                            G32J-CA20                   Contact configuration: 1 NO/1 NC

                            G32J-CA01                   Set of 2 Adapters

                            G32J-CA11

Fan                         G32J-CF64

Round Terminal Block Adapters G32J-TA10

Note: Refer to Safety Precautions on page 16.

                                                                                                                                                 2
                                                                                                                                                                                      G3JA-C

Specifications

Ratings and Characteristics

Ratings

Item                              Model G3JA-C403 G3JA-C409 G3JA-C416 G3JA-C419 G3JA-C425 G3JA-C430                                                                                   G3JA-C437
                                                                                                                                                                                      37 A
Rated operating current                    3A              9A                                                                       16 A        19 A              25 A         30 A   24 W

Heat dissipation, continuous               11 W            12 W                                                                     14 W        15 W              17 W         19 W   12.3 to 37 A

Rated operating voltage of main circuit 200 to 480 VAC (10%), 50/60 Hz (5%), 3-phase

Main circuit power Wire gauge              2.5 to 25 mm2 (14 to 4 AWG), Stripping length (recommended): 11 mm

supply terminals      Tightening torque 2.3 to 3.4 Nm
(L1, L2, and L3)

Main circuit load     Wire gauge           2.5 to 16 mm2 (14 to 6 AWG), Stripping length (recommended): 11 mm
power terminals
(T1, T2, and T3)      Tightening torque 2.3 to 3.4 Nm

Control terminals Wire gauge               0.2 to 2.5 mm2 (24 to 14 AWG), Stripping length (recommended): 9 mm

(A1, A2, IN1, IN2,    Tightening torque    0.5 to 0.9 Nm
97, 98, 13, and 14)

Overload current range                     1 to 3 A        3 to 9 A                                                                 5.3 to 16 A 6.3 to 19 A 8.3 to 25 A 10 to 30 A

Control voltage                            100 to 240 VAC or 24 VAC, 50/60 Hz, 24 VDC

Note: The load can be switched up to four times per hour. (Conditions: Rated current applied, Ambient temperature: 50C max., Limit current:
        300%, Start time: 15 s, ON time ratio: 70% max.) By using optional fans, however, it is possible to switch the load up to ten times per hour
        under the same conditions.

G3JA Switching Frequency                              G3JA-C (40C, Start time: 10 s, Current limit: 350%

G3JA-C (40C, Start time: 10 s, Current limit: 350%   with fan used)

without fan)

Operations/hour60                                                                                                        140              G3JA-C403/C409
                                                                                                        Operations/hour                   G3JA-C416/C419
50                    G3JA-C403/C409                                                                                     120

                      G3JA-C416/C419

40                    G3JA-C425/C430/C437                                                                                100              G3JA-C425/C430/C437

                                                                                                        80
30

                                                                                                        60

20                                                                                                                       40

10                                                                                                                       20

0     5 10 15 20 25 30 35 40                                                                                             0    5 10 15 20 25 30 35 40

                               Load current (A)                                                                                                 Load current (A)

Short Circuit Coordination (Maximum Fuse or Circuit Breaker Size) Type 1

Item                                             Model G3JA-C403 G3JA-C409 G3JA-C416 G3JA-C419 G3JA-C425 G3JA-C430 G3JA-C437

UL Class K5 and RK5 fuse                              Rated breaking current: 5 kA

UL-listed combination (600 V)                         12 A                                                                    30 A        60 A            70 A          100 A  110 A            125 A

UL-listed thermal electromagnetic circuit breaker Rated breaking current: 5 kA

UL-listed combination (600 V)                         12 A                                                                    30 A        60 A            70 A          100 A  110 A            125 A

Main Circuit

Item                     Classification                                                                                  cULus (UL 508)                                 IEC (EN/IEC 60947-4-2)

Rated operating voltage                    200 to 480 VAC                                                                                                 400 VAC
                                                                                                                                                          500 VAC
Isolation rated voltage                    600 VAC                                                                                                        2,500 VAC

Dielectric strength (between the           2,200 VAC
control and main circuits)

Repetitive peak voltage                    1,400 V

Operating frequency                        50/60 Hz (5%)

Utilization category                       Intermittent duty                                                                                              AC-53b

Single-phase/3-phase                       Equipment designed for 3-phase only

Rated impulse voltage                      6 kV

DV/DT protection                           1,000 V/s

Overvoltage category                       III

                                                                                                                                                                                                       3
                                                                                                                               G3JA-C

Control Circuits

Item                                         Classification                       cULus (UL 508)         IEC (EN/IEC 60947-4-2)

Rated operational voltage                                     100 to 240 VAC 50/60 Hz, 24 VAC 50/60 Hz, 24 VDC

Voltage range                                                 10% of control voltage

Overvoltage category                                          ---                                        III (See note.)

Input onstate voltage minimum during start (A1, A2) 90 VAC max. (100 to 240 VAC), 15.2 VAC/21.6 VDC max. (24 VAC/DC)

Input onstate current, during start with the G32J-            9.8 mA at 120 VAC; 19.6 mA at 240 VAC, 7.3 mA at 24 VAC/DC
CF64 Fan (IN1, IN2)

Input offstate voltage maximum (A1, A2)                       15 VAC min. (100 to 240 VAC), 3.6 VAC/5.1 VDC min. (24 VAC/VDC)

Offstate current consumption (IN1, IN2)                       10 mA max. (IN1), 12 mA max. (IN2)

Onstate current consumption, with Fan (A2)                    215 mA max. at 120 VAC/180 mA max. at 240 VAC, 660 mA max. at 24 VAC/800 mA
                                                              max. at 24 VDC

Onstate current consumption, without Fan (A2)                 205 mA max. at 120 VAC/145 mA max. at 240 VAC, 580 mA max. at 24 VAC/705 mA
                                                              max. at 24 VDC

Note: Overvoltage category II applies when control or auxiliary contacts are connected to an SELV or PELV circuit.

Auxiliary Contacts

Item                                Classification                                cULus (UL 508)                        IEC (EN/IEC 60947-4-2)

Rated operational voltage                            250 VAC/30 VDC                                      4 kV
                                                                                                         2,000 VAC
Rated impulse voltage                                ---                                                 III (See note.)

Dielectric strength                                  1,500 VAC                                           AC15

Overvoltage category                                 ---

Operating frequency                                  50/60 Hz

Utilization category                                 D300

TB-97, -98            Control circuit configuration Electromagnetic relay
(overload/fault)
                      Number of contacts             1

                      Contact                        NO contact

                      Current specifications         AC/DC

                      Rated operating current        0.6 A at 120 VAC, 0.3 A at 240 VAC

                      Contact switching capacity Open: 72 VA
                                                                   Close: 432 VA

TB-13, -14            Control circuit configuration  Electromagnetic relay
(normal/up-to-        Number of contacts             1
speed)                Contact                        NO contact

                      Current specifications         AC/DC

                      Rated operating current        0.6 A at 120 VAC, 0.3 A at 240 VAC

                      Contact switching capacity Open: 72 VA
                                                                   Close: 432 VA

Note: Overvoltage category II applies when control or auxiliary contacts are connected to an SELV or PELV circuit.

Standard Functions

Item                         Classification                   cULus (UL 508)                             IEC (EN/IEC 60947-4-2)
Start time
Soft start (initial torque)                  2 s, 5 s, 10 s, 15 s, 20 s, 25 s, or 30 s
Current limit
Soft stop time                               15%, 25%, 35%, or 65% of locked rotor torque
Weight
                                             150%, 250%, 350%, or 450% of full-load current

                                             0%, 100%, 200%, or 300% of the start time

                                             Approx. 860 g

Vibration and Shock Resistance

Item                         Classification                   cULus (UL 508)                             IEC (EN/IEC 60947-4-2)
Vibration resistance
                       Destruction           25-m/s2 peak, 10 to 55 to 10 Hz, 0.19-mm single amplitude
Shock resistance
                       Malfunction           10-m/s2 peak, 10 to 55 to 10 Hz, 0.075-mm single amplitude

                       Destruction           300 m/s2 (30 G)

                       Malfunction           150 m/s2 (15 G)

                                                                                                                                                4
Environmental Conditions                                                                                           G3JA-C

Item                  Classification                 cULus (UL 508)                                   IEC (EN/IEC 60947-4-2)

Ambient operating temperature          0 to 50C

Ambient storage temperature            -25 to 85C

Elevation                              2,000 m max.

Ambient operating humidity             5% to 85% (with no condensation)

Pollution degree                       2

Degree of protection                   IP20

Other Specifications

Item                           Classification        cULus (UL 508)                                          IEC (EN/IEC 60947-4-2)

EMI                   Noise terminal voltage ---                                             Class A
(emission test)                                                                              Class A
                      Radiation field          ---
EMS
(immunity test)       Electrostatic discharge 4 kV contact discharge and 8 kV air discharge

                      Radio frequency          ---                                           Conforms to IEC 60947-4-2

                      electromagnetic field                                                  Conforms to IEC 60947-4-2
                                                                                             Conforms to IEC 60947-4-2
                      Electrical fast transient ---

                      Surge immunity           ---

Applicable Standards

Safety standards                       UL 508 (Listing: File No. E64562), CSA 22.2 No. 14, EN/IEC 60947-4-2

                                                                                                                                     5
Connections                                                                                                                                      G3JA-C

Wiring                                                                                                      Three-wire Connections

Two-wire Connections                                                                                                                                            Fuse, NF breaker, etc.

                                                       Fuse, NF breaker, etc.

                                                H3 H2                                                                                                                                                 H3 H2

                                             H1 H4                                                                                                                                                    H1 H4
                                                                               Transformer *1
                                        -TC                                                                                                                                                      -TC                Transformer *1

                                             X2 X1                                                                                                                                                    X2 X1

               L1 L2 L3         GRD                                                                                         L1 L2 L3                                                             GRD

                         135                  -SB                                                                                    135                                                                -SB1
                                        E-STOP                                                                                                                                                        E-STOP
             -E1 G3JA *2                                                                                                 -E1 G3JA *2
Main circuit 2 4 6                                                                                           Main circuit 2 4 6
terminals                                                                                                    terminals

                      T1 T2 T3                                                                                                    T1 T2 T3

               -M Motor                 Start/Stop                                                                          -M Motor                                                                  -SB2
                                                                                                                                                                                                       Stop

                                                                                                                                                                                                      -SB3
                                                                                                                                                                                                      Start

                                A1 A2 IN1                                      IN2 97 98 13 14                                                                                                   A1 A2              IN1 IN2 97 98 13 14
                                (+) (-)                                                                                                                                                          (+) (-)

                                                              Overload/fault                   Auxiliary                                                                                                                     Overload/fault Auxiliary
                                                                                               contact
                                             Control terminals                                                                                                                                               Control terminals         contact

                                                           -E1                                                                                                                                                      -E1

Operation Chart: Two-wire Connections with Main Circuit                                                      Operation Chart: Three-wire Connections with Main Circuit

Fault Shutoff                                                                                                Fault Shutoff

                                                Soft stop                                                                                                                                                           Soft stop

               Motor speed                                                     Coast to stop                                                                                                                                 Coast to stop
                                                                                                                                                                     Motor speed

                                                                                               Time                                                                                                                                    Time

               Start           Stable                                          Stop                                                                                                   Start        Stable                    Stop
                             operation                                                                                                                                                           operation

Start/stop                                                                                     IN1 (IN2)-A2    Start                                                                                                                        IN1-A2
    E-stop                                                                                     A1-A2         E-stop                                                                                                                         A1-A2

      Normal                                                                                   13-14                  Stop                                                                                                                  IN2-A2
Up-to-speed                                                                                    13-14
                                                                                                                   Normal                                                                                                                   13-14
                                                                                                             Up-to-speed                                                                                                                    13-14

*1. This transformer is used to convert the load voltage into the control voltage of *1. This transformer is used to convert the load voltage into the control voltage of

the G3JA. A transformer is not required if the load voltage is within the rated                              the G3JA. A transformer is not required if the load voltage is within the rated

operational voltage range of the G3JA.                                                                       operational voltage range of the G3JA.

*2. The wiring in the following diagram is used for a 3-phase, 6-wire motor (Delta). *2. The wiring in the following diagram is used for a 3-phase, 6-wire motor (Delta).

                                                      1                              3               5                                                                                                                    1         3       5

                                                      2                              G3JA                                                                                                                                 2    G3JA
                                                 T1                                                                                                                                                                  T1
L3             L2        L1                     (U1)                                      4          6       L3                                                                   L2         L1                     (U1)            4        6

(U2) (W2) (V2)                                                                        T2        T3           (U2) (W2) (V2)                                                                                                     T2      T3
                                                                                     (V1)      (W1)                                                                                                                            (V1)    (W1)

                                         Motor                                                                                                                                                               Motor
                             -M                                                                                                                                                                  -M

                                                                                                                                                                                                                                                       6
Examples: Main Circuit Fault Shutoff                                                                                                        G3JA-C

                                       Fuse, NF breaker, etc.                                           Forward/Reverse Rotation

                                                                                                        Note: 1. Provide a time lag of at least 1.0 s between forward and re-
                                                                                                                    verse rotation.

                                                                                                                2. Disable phase reversal protection.

                                                                                                                                                                           Fuse, NF breaker, etc.

                        135                      H3 H2
                   -KM
                                                 H1 H4         Transformer *2
                        246
                                            -TC
                      L1 L2 L3
                                                 X2 X1

                       135                  GRD                                                                                                                                                     H3 H2

                   -E1 G3JA *3                                                                                                                                                                      H1 H4    Transformer *2
Main circuit 2 4 6
                                                                                                                                                                                               -TC

terminals                                                                                                                                                                                           X2 X1

                   T1 T2 T3                       -SB1                                                  -KM1                                                               -KM2  GRD
                                                 E-STOP

                   -M Motor                      -SB2                                                                       L1 L2 L3                                                                    -SB
                                                 Stop                                                                                                                                               E-STOP
                                   -KA                                                                                         135
                                -KM              -SB3                                                                                                                                                     OFF
                                                  Start                                                             -E1 G3JA *3                                                                      FORREV
                                                                                                        Main circuit 2 4 6
                                                                              -KA                       terminals                                                                                        123
                                                                                                                                                                                                    -SA
                                                                                                                            T1 T2 T3
                                                                                                                                                                                                        -KM2 -KM1 -KM2 -KM1

                                                                                                        -M Motor                                                                                    -KM1           -KM2

                                            A1 A2              IN1 IN2 97 98 13 14
                                            (+) (-)

                                                                        Overload/fault Auxiliary

                                                               Control terminals          contact

                                                                                            -E1                                                                                  A1 A2 IN1 IN2 97 98 13 14
                                                                                                                                                                                 (+) (-)
Operation Chart: Three-wire Connections with Main Circuit
Fault Shutoff

                                                                                                                                                                                                             Overload/fault Auxiliary
                                                                                                                                                                                                                                   contact
                                                                                                                                                                                                    Control terminals

                   Motor speed                                                                                                                                                                        -E1
                                                                                                                                                          Motor speed
                                                                                                        Operation Chart: Two-wire Connections with Forward/
                                                                                                        Reverse Rotation

                       Start Stable operation                  Stop     Time                                                                                                                                 Inertial stop
                                                                                                                                                                                                                        Soft stop

            Start                                                                  IN1-A2                                                                              Start Stable operation                Stop                  Time
            Stop                                                                   A1-A2                                                                                                                                           A1-A2
        E-STOP                                                                     IN2-A2
Overload/fault
   Main circuit                                                                    97/98 (See note 1.)

                                                                                                        Start

Normal                                                                             13-14                Normal                                                                                                                     13-14

Up-to-speed                                                                        13-14                Up-to-speed                                                                                                                13-14

*1. If an overload or other fault is detected, the main circuit will turn OFF, and the *1. This transformer is used to convert the load voltage into the control voltage of

alarm contact (97-98) built into the G3JA will operate. (Refer to Description of                        the G3JA. A transformer is not required if the load voltage is within the rated

Functions on page 9 for details.)                                                                       operational voltage range of the G3JA.

*2. This transformer is used to convert the load voltage into the control voltage of *2. The wiring in the following diagram is used for a 3-phase, 6-wire motor (Delta).

the G3JA. A transformer is not required if the load voltage is within the rated

operational voltage range of the G3JA.

*3. The wiring in the following diagram is used for a 3-phase, 6-wire motor (Delta).

                                                                                                                                                                                                          1        3     5

                                                                                                                                                                                                          2  G3JA
                                                                                                                                                                                                     T1
                                                                     1      3          5                                                                                                            (U1)          4            6

                                                                     2  G3JA                            L3                                                             L2  L1                                 T2          T3
                                                                T1                                                                                                                                           (V1)        (W1)
                                                               (U1)                                     (U2) (W2) (V2)

                                                                            4          6

                   L3  L2               L1                              T2         T3

                   (U2) (W2) (V2)                                       (V1) (W1)

                                                                                                                                                                                             Motor
                                                                                                                                                                                 -M

                                                        Motor
                                            -M

                                                                                                                                                                                                                                            7
                                                                                                                                                           G3JA-C

Operation                                                                                            Kick Start

Operating ModesPercentage of voltage                                                                A kick start, or boost, at the beginning of the start mode provides a
                                                                                                     current pulse of 450% of the full-load current. The kick start time can
Soft Start                                                                                           be set to OFF, 0.5 s, 1 s, or 1.5 s. This allows the motor to develop
                                                                                                     additional torque at start for loads which may need a boost to get
A soft start is used to reduce mechanical shock when starting the                                    started.
motor. The motor voltage is increased from the initial torque to full
voltage.                                                                                             Some loads that may not start well in soft start mode will start more
The initial torque can be set to 15%, 25%, 35%, or 65% of the locked                                 smoothly if the kick start is enabled to provide more rotational torque
rotor torque. The motor voltage is gradually increased during the                                    to the motor. Increase the kick start time one step at a time to
acceleration ramp time. The acceleration ramp time can be set to 2 s,                                gradually increase the initial torque.
5 s, 10 s, 15 s, 20 s, 25 s, or 30 s. The bypass relay turns ON after
the motor starts.                                                                                    The current will increase temporarily during the kick start, but the
                                                                                                     start mode that was selected will continue after the kick start has
                       100%                                                                          been completed.

                                       Starting                                                      When the current limit start function has been enabled, the kick start
                                       torque                                                        will be disabled.

                                                                                                     Percentage of voltage             Kick start
                                                                                                                                       (when selected) *2

                                                 Start t1      Stable                                                       100%
                                                             operation

                                                                          Time

Current Limit Start                                                                                                         Starting
                                                                                                                            torque *1
This start mode is used when the maximum starting current must be
limited. During the start time, the thyristor will reduce the motor                                                                            Start t1     Stable
terminal voltage to limit the current at startup. During stable                                                             Kick start t2                  operation
operation, the built-in bypass relay will be ON.
                                                                                                                                                                        Time
The current limit can be set to 150%, 250%, 350%, or 450% of the
full-load current. The start time can be set to 2 s, 5 s, 10 s, 15 s, 20 s,                          Note: Refer to DIP Switch Settings on page 11 for details.
25 s, or 30 s.                                                                                               *1. Initial Torque Setting for Soft Start
                                                                                                             *2. Kick Start

Percentage of motor full-load current  600%      Direct input                                        Soft Stop
                                       350%
                                                                    Current limit start              A soft stop is used with applications that require an extended coast
                                                                    (at 350% of full-load current )  to stop. When enabled, the voltage ramp down time can be set to
                                                                                                     one, two, or three times the start time. The motor will stop when the
                                                                                                     motor voltage drops to the point where the load torque is greater
                                                                                                     than the motor torque.

                                       100%

                                                 Start time   Stable                                 Motor speed
                                                             operation

                                                                         Time

                                                                                                                            Start t1     Stable          Coast
                                                                                                                                       operation         to stop
                                                                                                                                                          Soft-stop t3

                                                                                                                                                                            Time

                                                                                                     Start Time for a Soft Start or Current
                                                                                                     Limit Start

                                                                                                     A built-in current transformer (CT) is used to detect the motor
                                                                                                     current. The completion of motor startup is determined by detecting
                                                                                                     the convergence of the current as the speed of the motor increases.
                                                                                                     The Soft Starter operation is then changed to stable operation. The
                                                                                                     start time given here is a guideline for when the total load current set
                                                                                                     on the overload FLA setting dial and the actual load current are the
                                                                                                     same. If the motor load is smaller, the motor will start faster, so that
                                                                                                     actual start time will be shorter than the start time given here.

                                                                                                     Soft Stop Time

                                                                                                     The soft stop function gradually reduces the motor voltage to prevent
                                                                                                     the motor from stopping suddenly under a large load. A built-in CT is
                                                                                                     used to detect the motor current and size of the current is used to
                                                                                                     determine the size of the load and the rate at which the voltage is
                                                                                                     reduced. If the motor load is extremely small, the soft stop time will
                                                                                                     be very short.

                                                                                                                                                                                  8
Description of Functions                                                                                  G3JA-C

Overload Protection                                                      Phase Loss

The G3JA-C is equipped with overload protection. The overload            The G3JA-C monitors phase loss. If phase loss lasts for two power
class can be set to OFF, 10, 15, or 20. Either automatic or manual       supply frequency cycles, the G3JA-C turns OFF the output, indicates
mode can be used to reset an overload (trip). Set the trip current to    the phase loss with a flashing LED indicator and closes the alarm
the rated full-load current of the motor through the overload FLA        contact.
setting dial. When an overload fault occurs, the G3JA-C indicates the
overload with a flashing LED indicator and closes the alarm contact.     Current Imbalance

After an error is detected, the SCR will become hot, and an              The G3JA-C monitors the phase current imbalance. If the imbalance
overtemperature fault may also be detected. If it is, pushing the reset  exceeds the preset limit, the G3JA-C turns OFF the output, indicates
button will not reset the system. Resetting will be possible once the    the current imbalance with a flashing LED indicator and closes the
temperature of the SCR has decreased. Wait about two minutes to          alarm contact.
allow the SCR to cool (assuming the ambient temperature is normal)
                                                                         Shorted SCR
Overtemperature
                                                                         The G3JA-C always checks the SCR for a short circuit before the
The G3JA-C monitors the SCR temperature through an internal              starting sequence. If a short circuit is found, the G3JA-C stops the
thermistor. If the SCR gets too hot, the G3JA-C turns OFF the            starting sequence, indicates the short circuit with a flashing LED
output, indicates the overtemperature status with a flashing LED, and    indicator, and closes the alarm contact.
closes the alarm contact. Pushing the reset button will not reset the
system. Resetting will be possible once the temperature of the SCR
has decreased. Wait about two minutes to allow the SCR to cool
(assuming the ambient temperature is normal).

Phase Reversal Protection

When this function is enabled with a DIP switch setting, the G3JA-C
checks phase sequence prior to startup. If the G3JA-C detects a
phase reversal fault in the main circuit power supply, it stops the
starting sequence, indicates the phase reversal with a flashing LED
indicator, and closes the alarm contact.

                                                                                                                                               9
                                                                                                                                              G3JA-C

Nomenclature

Part Names and Functions

Upgraded Models                                                                                            DIP Switch Configuration
                                                                                                           Use the DIP switch to set the functions.
Production of a new version of the Soft Starter (version 2) with
added functions was started in August 2008. The DIP switch                                                 DIP switch           Function
settings of the new version are different from the previous version.                                       pin
For details, refer to Upgrades for Version 2 on page 13.
                                                                                                           1
                                                                                  Main Circuit Terminals,          Start time
                                                                                  Power Supply Side
                                                                                                           2

                                                                                                           3 Start mode (current limit start or soft start)

                                                                                                           4           Current limit start setting (when selected) or initial

                                                                                                           5           torque setting for a soft start (when selected)

                                                                                                           6
                                                                                                                   Soft stop

                                                                                                           7

                                                                                                           8 Long time setting for start time

                                                                                                           9
                                                                                                                    Kick start

                                                                                                           10

Reset Button                                                                                               11
All faults can be reset by pressing the Reset Button or turning                                                     Overload class selection
OFF the control power supply. Cooling time may be required
before overload and overtemperature status can be reset.                                                   12

Note: Test Mode for overload testing will be entered when the                                              13 Overload reset
       Reset Button is pressed for approximately seconds.
       Test Mode will be cancelled when the Reset Button is                                                14 Auxiliary/optional auxiliary contact (normal/up-to-speed)
       pressed again.
                                                                        G3JA-C Ver.2                       15 Motor wiring (Line or Delta)

                                                                        SOFT STARTER                       16 Phase reversal protection

                                                                                                           Overload FLA Setting Dial
                                                                                                           Use this dial to set the trip current to the rated full-load
                                                                                                           current of the motor. If the setting is not correct, it will not
                                                                                                           be possible to drive the motor properly.
                                                                                                           For a 3-phase, 6-wire motor, use the following formula
                                                                                                           to calculate the dial setting.

                                                                                                           Set value = Total motor load current/1.73
                                                                                                           For example, if the total motor load current is 20 A, the
                                                                                                           dial setting is 11.6 A (20 A/1.73).

Control Terminals                                                                                          RUN/FAULT Indicator
The G3JA-C has eight input terminals on the front. Each                                                    The G3JA-C monitors the status before startup and
terminal is described in the following table.                                                              during operation. One indicator indicates both normal
                                                                                                           operation (RUN) and faults (FAULT). If the G3JA-C
Terminal         Description                                                                               detects a fault, it turns OFF the motor and indicates
                                                                                                           the fault with a flashing LED indicator.
A1 Control power supply input                                                                              The G3JA-C monitors the following conditions.

A2 Control power supply common

IN1 START input                                                                                                         Flashing indicator status

IN2 STOP input                                                          Main Circuit Terminals,            Fault
                                                                        Load Side
97 NO auxiliary contact (auxiliary contact for fault detection output)                                     Overload

98 NO auxiliary contact (auxiliary contact for fault detection output)                                     Over-
                                                                                                           temperature
13 NO auxiliary contact (normal/up-to-speed)

14 NO auxiliary contact (normal/up-to-speed)                                                               Phase
                                                                                                           reversal

Auxiliary Contacts                                                                                         Phase loss
The G3JA-C is equipped with two auxiliary contacts as a
standard feature. One contact can be used for fault detection                                                        Current
output. The other one is used to output operating status and                                                         imbalance
can be set to either Normal or Up-to-speed using the DIP                                                             Shorted
switch setting at pin number 14.                                                                                     SCR
An optional Auxiliary Contact Block can be added, and DIP
switch pin number 14 can be used to set the operating status to                                            Note: The indicator will flash seven times in test mode (trip test).
output (either Normal or Set Speed).

                                                                                                                                                                                 10
                                                                                                                               G3JA-C

DIP Switch Settings

Start Time t1                               Initial Torque Setting for                                  Current Limit Start Setting
                                            Soft Start
      DIP switch pins         Time                                                                      DIP switch pins        FLA current
                           (seconds)                                                                                             limit (%)
1          2           3                    DIP switch pins                          LRT initial        4            5
                                 2                                                   torque (%)                                    150%
OFF   OFF             OFF        5          4               5                                           OFF          OFF           250%
                                10                                                       15%                                       350%
ON    OFF             OFF       15          OFF             OFF                          25%            ON           OFF           450%
                                20                                                       35%
OFF       ON          OFF       25          ON              OFF                          65%            OFF          ON
                                30
ON        ON          OFF                   OFF             ON                                          ON           ON

OFF   OFF              ON                   ON              ON

ON    OFF              ON

OFF       ON           ON

Start Mode (Current Limit
Start or Soft Start)

DIP switch pin pins3       Setting

      ON               Soft start

      OFF              Current limit start

Soft Stop t3                                Kick Start t2                                               Overload Class Selection

DIP switch pins             Setting         DIP switch pins                         Time (seconds)      DIP switch pins        Overload
                                                                                                                                 class
   6          7        Coast to stop                     9  10                              OFF         11              12
                       100% of the                                                           0.5                                  OFF
OFF           OFF      start time           OFF             OFF                              1.0        OFF          OFF           10
                       200% of the                                                           1.5                                   15
ON            OFF      start time           ON              OFF                                         ON           OFF           20
                       300% of the
                       start time           OFF             ON                                          OFF             ON

OFF           ON                            ON              ON                                          ON              ON

ON            ON                            * Set Kick Start to OFF if the G3JA is used with a
                                              Current Limit Start.

Overload Reset                              Auxiliary Contacts and                                      Motor Wiring
                                            Optional Auxiliary Contact
                                            Block                                                           DIP switch pin 15
                                                                                                                      ON
DIP switch pin 13            Reset          DIP switch      Auxiliary                Optional                         OFF        Motor wiring
          ON           Automatic               pin 14       contacts                 Auxiliary                                 Line
         OFF           Manual                               (13 to 14)                Contact                                  Delta
                                                 ON
                                                OFF                                    Block
                                                                                     (23 to 24)

                                                            Up-to-speed Normal

Phase Reversal Protection                                   Normal                   Up-to-speed                     G3JA              G3JA

DIP switch pin 16            Setting                                                 Soft stop
          ON           Disabled
         OFF           Enabled              Motor speed                              Coast to stop
                                                                                     during soft stop

                                                            Start Stable operation   Stop         Time        Motor            Motor

                                            Normal                                                           Line               Delta

                                            Up-to-speed

                                            Normal:         Power supplied to motor

                                            Up-to-speed: Bypass relay ON

                                                                                                                                               11
                                                                                                                                                                                                                                                       G3JA-C

Engineering Data                                 Trip Class 15                                                                                                                                     Trip Class 20

Trip Curves                                          1,000                                                                                                                                              1,000
                                                                                 Cold trip                                                                                                                                             Cold trip
Trip Class 10
                                                        100                                                                                                                                               100
  1,000
                                Cold trip                                                                                                                                                                            Hot trip
                                                                                                                                                                                                            10
     100
Time (s)
                                                                                            Time (s)
                                                                                                                                                                                            Time (s)

           Hot trip                                                Hot trip
10                                                      10

1                                                       1                                                                                                                                              1

100                                        1,000        100                                                1,000                                                                                       100                                             1,000
                                                                                                  Current (%)
                     Current (%)                                                                                                                                                                                                                       Current (%)
                                                                                            109
Dimensions                                                                                                                                                                                                                                            (Unit: mm)

                                                                                                                                                                                                            Panel Cutouts

                                                  44.8                                                                                                                                              3                         4.5 dia. or M4

                                                                                                                                                                                                      46.4

                                                               141.5                                                                                                                                                                              132

                                                                                                                                                                                                                          35

Note: All models are the same size regardless of the capacity.

Mounting Dimensions for the Auxiliary Contact Block and Round Terminal Block Adapter

                                                  44.8     10                               109                                                                                                     3

                                                               23

                                                                                                                                                                                                      46.4

                                                               141.5

                                                               23

                                                                                                               12
                                                                                                                            G3JA-C

Upgrades for Version 2                                                   Identifying Upgraded Models

Upgrades                                                               You can check whether the G3JA is an upgraded version by the
                                                                        markings on the G3JA or the label on the box. If the G3JA is not
1. Control of 3-phase, 6-wire motors (star-delta wiring) is supported.  marked "Ver. 2," it is the previous version.
2. The soft start time can be set to up to 30 s.

                                                                        Markings on Unit                  Label on Box

                                                                                                                                 Ver.2

Previous Version

The DIP switch settings are different for the upgraded version (version 2) and the previous version.
Refer to the following tables for compatibility.

Comparison of Functions                                                 Comparison of DIP Switch Settings

            Item     Previous version      New version                      DIP     Previous version            New version (version 2)
                                            (version 2)                 switch pin
1. 3-phase, 6-wire  Control not        Control possible.
motors (Delta)      possible.                                           1           Start time                  Start time
2. Soft start time  2, 5, 10, or 15 s  2, 5, 10, 15, 20, 25,
settings                               or 30 s                          2           Start mode (current limit Start mode (current limit

                                                                        3           start or soft start)        start or soft start)

                                                                        4           Current limit start setting Current limit start setting

                                                                        5           (when selected) or initial (when selected) or initial
                                                                                    torque setting for a soft torque setting for a soft

                                                                                    start (when selected)       start (when selected)

                                                                        6           Soft stop                   Soft stop

                                                                        7

                                                                        8 * Not used                            Long time setting for start
                                                                                                                time

                                                                        9           Kick start                  Kick start

                                                                        10

                                                                        11          Trip class selection        Trip class selection

                                                                        12

                                                                        13          Overload (trip) reset       Overload (trip) reset

                                                                        14 *        Auxiliary contact (normal/  Auxiliary contact or
                                                                                    up-to-speed)                Optional Auxiliary Contact
                                                                                                                Block (normal/up-to-
                                                                                                                speed)

                                                                        15 *        Optional Auxiliary Contact Motor wiring

                                                                                    Block (normal/up-to-        (Line or Delta)

                                                                                    speed)

                                                                        16          Phase reversal protection Phase reversal protection

                                                                        * These settings are different for the previous version and the new version.

                                                                                                                                                      13
                                                                                                                  G3JA-C

Comparison of DIP Switch Setting Differences

1. Start Time

                        Previous version                                            New version (version 2)

               DIP switch pins                     Time (unit: s)                   DIP switch pins               Time (unit: s)

1                       2              8                                1           2                 8                   2
                                                                                                                          5
OFF                     OFF            Not used            2            OFF         OFF               OFF                10
                                                                                                                         15
ON                      OFF                                5            ON          OFF               OFF                20
                                                                                                                         25
OFF                     ON                                 10           OFF         ON                OFF                30

ON                      ON                                 15           ON          ON                OFF

                                                                        OFF         OFF               ON

                                  ---                                   ON          OFF               ON

                                                                        OFF         ON                ON

2. Auxiliary Contact and Optional Auxiliary Contact Block               3. Motor Wiring Method (New Version)
(New Version)                                                           Optional Auxiliary Contact Block (Previous Version)
Auxiliary Contact (Previous Version)
                                                                             Previous version         New version (version 2)

Previous version                 New version (version 2)                DIP switch  Optional          DIP switch  Motor wiring

DIP switch  Auxiliary   DIP switch     Auxiliary       Optional         pin 15 Auxiliary Contact pin 15
   pin 14   contacts       pin 14      contacts       Auxiliary
            (13 to 14)                 (13 to 14)  Contact Block                    Block (23 to 24)
                                                      (23 to 24)
                                                                        ON          Up-to-speed       ON          3-phase, 3-wire

                                                                                                                  motor (Line)

ON          Up-to-           ON        Up-to-      Normal               OFF Normal                    OFF         3-phase, 6-wire
                                                                                                                  motor (Delta)
            speed                      speed

OFF Normal                   OFF       Normal Up-to-speed

Note: With the new version, it is not possible to individually set the
        auxiliary contacts (13 to 14) and Optional Auxiliary Contact
        Block (23 to 24).

                                                                                                                                   14
Accessories (Order Separately)                                                                                 G3JA-C

Auxiliary Contact Blocks                                                      Fan

G32J-CA10                                                                     G32J-CF64
G32J-CA20
G32J-CA01                                                                     It is possible to perform switching four times
G32J-CA11                                                                     per hour without a fan if the G3JA is used at
                                                                              the rated current in an ambient temperature
Mounting                                                                      of 50C max. with a sine current of 300%, a
                                                                              start time of 15 s, and an ON time ratio of
1. Insert the connector and hooks on the Auxiliary Contact Block              70% max. If a fan is used, switching can be
    (G32J-CA) into the mounting holes of the G3JA. When doing so,             performed ten times per hour under the
    be careful that the connector terminals do not bend.                      same conditions.

2. Press down on the Auxiliary Contact Block in the direction of              Mounting
    arrow 2 in the figure until you hear a click.
                                                                              1. Mount the fan so that the arrow on the surface of the Fan (G32J-
3. To wire the Auxiliary Contact Block, use sheathed wire (length of              CF64) is in the direction shown in the figure.
    stripped wire: 9 mm) with a core thickness of 0.5 to 2.5 mm2
    (AWG18 to AWG14). Use a tightening torque of 1.0 to 1.1 Nm.              2. Insert the fan connector into the G3JA connector until it clicks into
                                                                                  place.

                                                                              3. Mount the fan on the G3JA.

                                                                                         Fan

                                           Auxiliary Contact
                                           Blocks

Removing                                                                      Round Terminal Block Adaptor

1. Gradually pull out the connector on                                        G32J-TA10
    the top part of the Auxiliary Contact
    Block (G32J-CA) in the direction of                                       This is a terminal block adaptor for
    arrow 1 in the figure.                                                    wiring with round crimp terminals.

2. Pull the Auxiliary Contact Block in the                                    Mounting                                                                               10
    direction of arrow 2 in the figure.                                                                             13

3. Pull the Auxiliary Contact Block in the                                                                                     23
    direction of arrow 3 in the figure and
    remove it.                                                                Once the Terminal Block Adaptor for Round Terminals is wired,
                                                                              mount it to the main circuit terminals of the G3JA. If wiring is
     Contacts                              Contact form           Model       performed after mounting the Terminal Block Adaptor for Round
1NO                                                                           Terminals on the G3JA, tighten the screws again on the main
                 23                                           24  G32J-CA10   terminals of the G3JA and the Terminal Block Adaptor to the
                                                                              specified tightening torque once wiring is completed.
2NO              33                                           34 G32J-CA20
                                                                              Note: 1. The Round Terminal Block
                 23                                           24                          Adaptor (G32J-TA10) is
                                                                                          delivered with the cover
1NC                                                                G32J-CA01              removed.

                                       11                     12                      2. The mounting strength of the
                                                                                          cover on the Round Terminal
1NO/1NC                                                            G32J-CA11              Block Adaptor has been
                                                                                          increased to prevent it from
                                       11                     12                          becoming removed or falling
                                                                                          off.
                                       23                     24                          Remove the cover by inserting Three, M4
                                                                                          a flat-head screwdriver into the
Specifications                                                                            cover bump on the back of the Round Terminal Block
                                                                                          Adaptor and making a gap. Be careful not to become injured
     Item                                                     Specifications              when removing the cover.

Control circuit method Electromagnetic relay                                          3. Tighten the screws to the specified torque.
                                                                                          The tightening torque for mounting the Round Terminal
Current specifications AC/DC                                                              Block Adaptor to the G3JA is 2.3 to 3.4 Nm.
                                                                                          The tightening torque for wiring the Round Terminal Block
Rated operating                            2.5 A, 300 VAC                                 Adaptor is G3JA is 0.98 to 1.37 Nm.
current

                                                                                                                                                                         15
                                                                                                                           G3JA-C

Safety Precautions                                                       Installation and Use

Refer to Safety Precautions for All Solid State Relays.                   If two or more Units are used with close

                            !CAUTION                                     mounting, it is recommended to install

Installation and Environment                                             them with a gap of approximately 5 mm

Always turn OFF the power supply if there is a possibility               between Units. (No gap is required for
that the terminals may be touched. Not doing so may
occasionally result in minor electric shock.                             Auxiliary Contact Units.)

Firmly tighten the screws to the specified torque. If the                If close mounting is used, also take into
screws are not firmly tightened, minor fires may
occasionally occur. Refer to Specifications and                          account the increase in ambient
Accessories (Order Separately) for details.
                                                                         temperature due to heat dissipated by the
Maintenance
                                                                         Units themselves. In particular, use fans for                 5 mm
The charge of the electrolytic capacitor used in the
internal circuit may occasionally result in minor electric               sufficient ventilation with external air if the
shock. Before touching the terminals, turn OFF the power
supply and make sure that the voltage has been                           Units are mounted inside a panel.
eliminated due to discharge.
                                                                         Do not use the product with loads greater than the rated current.
Precautions for Safe Use                                                  Doing so will result in abnormal heat radiation.

Operation and Storage Locations                                           For protection against grounding accidents, always install a fuse,
                                                                           breaker, or other protective device on the power supply side.
Do not use or store the SSR in the following locations. Doing so
  may result in damage, malfunction, or deterioration of performance      Select a power supply that is in the rated frequencies. Not doing so
  characteristics.                                                         will result in malfunction, failure, or burning.
    Locations subject to excessive shock or vibration
    Locations subject to exposure to water, oil, or chemicals           Precautions for Correct Use
    Usage locations subject to ambient temperatures outside the
      range of 0C to 50C                                               Altitude Derating
    Storage locations subject to ambient temperatures outside the
      range of -25C to 85C                                             The rated current of the G3JA must be decreased at altitudes above
    Usage locations subject to humidity outside the range of 5% to     2,000 m because of decreased efficiency of the heat sink and fan
      85% or to condensation due to sudden temperature change            (G32J-CF64).
    Locations subject to corrosive or flammable gases
    Locations subject to excessive dust, salinity, or metal powder.    Warning Labels Included with Product

Installation                                                             If voltage is applied to the main circuit power supply side of the
                                                                         G3JA, there will be voltage in the terminals on the main circuit load
Do not drop the product or subject it to abnormal vibration or shock.  side even if the G3JA is OFF. Be sure to use the warning labels
  Doing so may result in failure or malfunction.                         included with the product to provide notification of this hazard on
                                                                         locations such as the motor terminal box, G3JA, and control panel.
Do not install the product if your hands are dirty with oil or metal
  dust. Doing so may result in failure.                                  Main Circuit Cutoff at Error

Installation and Handling                                                Safety is further improved by turning OFF the contacts and other
                                                                         lines on the main circuit power supply side of the G3JA as shown in
The product is heavy. Firmly mount it on a DIN Track. Also securely    the following figure. For a wiring example, refer to Examples: Main
  mount the DIN Track.                                                   Circuit Fault Shutoff.

Mount the product in the specified mounting direction. Abnormal        Standard Connection Diagram for Main Circuit Cutoff at Error
  heat radiation from the Unit will result in SCR failure or damage.
                                                                                                    KM      L1 1           2 T1        Motor
Installation and Wiring                                                                                     L2 3           4 T2
                                                                         Fuse, breaker,                     L3
Make sure that all lead wires are appropriate for the load current.    etc.                                                   T3
  Abnormal heat radiation from the wires may result in burning.                                                   5        6

Do not use wires with a damaged sheath. Doing so may result in                                                     G3JA
  electric shock or current leakage.
                                                                         Connecting Varistors
Do not wire power lines or high-tension lines along with the control
  circuit lines in the same conduit or duct. Doing so may result in      The G3JA will be damaged by overvoltage if
  damage or malfunction due to induction.
                                                                         high-energy surge voltage builds up in the AC
Use wires of an appropriate length. Wires of improper length may
  result in malfunction or burning due to induction.                     power supply that is used. If surge voltage is a

Connect to the primary side (i.e., power supply side) of the G3JA      problem, connect three varistors with one on
  output terminals if you use a power capacitor.
                                                                         each phase in the position shown in the following L1          L2     L3

                                                                         figure. The following varistor is recommended.             1  3      5

                                                                         Also, when you connect the varistor, always                2  4      6

                                                                         install a fuse, breaker, or other protective device T1        T2     T3

                                                                         on the power supply side of the varistor.                     Motor

                                                                         Varistor voltage: 910 V
                                                                         Energy resistance: 200 joules min. (10 1000 s)

                                                                         Limiting Resistor

                                                                         The G3JA cannot use a limiting resistor.

                                                                         Operation Start Signal

                                                                         Do not apply an operation start signal during a soft stop. Doing so
                                                                         will result in abnormal operation.

                                                                                                                                                  16
                                                                                                                G3JA-C

Connecting a Power Capacitor

If you use a power capacitor, connect it to the primary side (i.e.,
power supply side) of the G3JA output terminals.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                  In the interest of product improvement, specifications are subject to change without notice.

                                                                                                                17
                                                       Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.

                                                      Warranty and Limitations of Liability

WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.

In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

                                                            Application Considerations

SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.

At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:

       Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.

       Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
           safety equipment, and installations subject to separate industry or government regulations.

       Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.

                                                                       Disclaimers

CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.

DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.

ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.

OMRON Corporation                                                                                                                                        2011.5
                               In the interest of product improvement, specifications are subject to change without notice.
Industrial Automation Company
                                                                                   (c)Copyright OMRON Corporation 2011 All Right Reserved.
http://www.ia.omron.com/
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Omron:

  G3JA-C403B AC100-240 G3JA-C403B AC/DC24 G3JA-C409B AC100-240 G3JA-C409B AC/DC24 G3JA-C416B
AC100-240 G3JA-C416B AC/DC24 G3JA-C419B AC100-240 G3JA-C419B AC/DC24 G3JA-C425B AC100-240
G3JA-C425B AC/DC24 G3JA-C430B AC100-240 G3JA-C430B AC/DC24 G3JA-C437B AC100-240 G3JA-C437B
AC/DC24