                                                      Fluke 1750

                         Three-Phase Power Recorder

                                                                                       Technical             Data

Never miss capturing a

disturbance—with the exclusive

threshold-free measurement

system, it’s automatic.

   Capture every measurement, every event,

   on every cycle, all the time with the Fluke

   1750 Power Recorder. Outstanding accuracy

   and resolution provide complete visibility into

   your installation or distribution system.

•  Power quality that meets the standard:             •  Intuitive PC software: Easily analyze data and

   All measurements comply with IEC61000-4-30            generate reports. Automated EN50160 reporting

   standards for correct evaluation of all measured   •  and compliance.

   values including voltage, current, power, har-        Plug and play: Set up in minutes with self-

•  monics, flicker etc.                                   identifying current probes and single-lead voltage

   Quick and reliable configuration: PDA wire-         •  connections.

   less “front panel interface” provides the ability     No need to reconnect wires: Swap channels

   to verify setup without a laptop along with a         internally with the wireless PDA or PC when

   window into what the instrument is recording,      •  connections are not correct.

•  even in awkward test locations.                       Measure every parameter: voltage and current

   Threshold-free setup: Apply thresholds after       •  on three phases, neutral, and ground.

   data is collected with Fluke Power Analyze            5 MHz, 8000 Vpk waveform capture: Get a

   Software so there is no need to worry about        •  detailed picture of even the shortest events.

•  missed information due to incorrect set-up.           Quickly retrieve data: With included SD memory

   Captures everything: Cross-channel and current        card or via the 100BaseT high-speed Ethernet

   triggering capture every measurement, on every        connection.

   channel, every time.
                                                                Applications

                                                                Long-term analysis: Uncover hard-to-find or

                                                                intermittent issues; monitor critical equipment,

                                                                capturing power quality events to correlate with

                                                                equipment malfunction

                                                                Power quality surveys: Quantify power quality

                                                                throughout a facility, documenting results with

                                                                professional reports

                                                                Quality of service compliance: Validate incoming

                                                                power quality at the service entrance

                                                                Equipment Installation/Commissioning: Bench-

                                                                mark power system prior to install to insure quality

                                                                of service

                                                                Easy to use

                                                                The recorder automatically detects, scales, and

                                                                powers current probes without needing batteries.

                                                                Requiring only single-lead voltage connections

                                                                enables safe and quick setups. Once power is

                                                                applied the instrument automatically begins record-

                                                                ing and LEDs give you assurance that the recorder

                                                                is powered up and signals are within range – no

                                                                more uncertainty that data is being recorded. The

                                                                Fluke 1750 has an exclusive capture algorithm

                                                                which makes certain all events are captured with-

                                                                out the tedious setups and blind spots associated

                                                                with threshold driven equipment.

                                                                The PDA wirelessly interfaces with the recorder,

                                                                allowing quick setup and verification with wave-

                                                                form displays, meter screens, and phasor diagrams.

                                                                The built-in wireless technology allows you to

                                                                control multiple instruments from a distance easily,

                                                                without the need for a laptop computer (laptops can

                                                                also be used when desired).

View measurements real-time       with                Configurations are simple with wiring  No need to reconnect wires—swap      channels

wireless PDA interface.                               diagrams to guide you.                 internally using the PDA interface.

2  Fluke Corporation  Fluke 1750  Three-Phase  Power  Recorder
Comprehensive power system data                                 event data on all input channels simultaneously,

Every cycle on every channel is simultaneously                  no matter which channel triggered the event. When

sampled providing complete analysis of power                    periodic analysis of the waveform may be needed,

quality, harmonics, power and energy. Cross-                    the Snapshot mode captures waveforms at user-

channel current and voltage triggering captures                 defined intervals. Even dc signals can be recorded!

Events can be displayed against a variety of tolerance curves.  Full FFT on each channel to the 50th harmonic.

Display multiple parameters simultaneously on one graph.        Full-featured power meter display for each channel and totals.

Thresholds for the EN50160 report are easily customized.        EN50160 report delivers an easy to read pass or fail chart

                                                                along with drill down data.

Powerful data management                                        card without using your laptop, or transfer directly

Data is automatically stored on the internal flash               to your computer via Ethernet, using TCP/IP protocol.

memory that can store records for over a month                  Voice, data, and picture annotations can be made

without compression or overwriting. Data is                     via the PDA to flag important points in the data

retrieved via one of two quick and easy options:                stream. Imagine being able to flag in your recorded

download the data onto the included SD memory                   data when a transfer switch was operated, or load

                                                                changes were made.

3  Fluke Corporation  Fluke 1750 Three-Phase Power Recorder
View data the way you want

The new Fluke Power Analyze software revolu-

tionizes your ability to analyze data. No need to

worry about thresholds—with Fluke Power Ana-

lyze, thresholds can be modified after the data is

recorded! And the easy-to-use user interface will

display voltage as a phase-to-phase or phase-to-

neutral reading.

Apply thresholds to data after collection using a variety of

standard or customized templates.

                                                              All the latest power quality

                                                              standards are built-in

                                                              IEC 61000-4-30 compliant measurement systems pro-

                                                              vide the confidence that all parameters are measured

                                                              and calculated consistently with international standards.

                                                              Automated EN50160 compliance reporting for rapid Pass/

                                                              Fail testing.

                                                              600 V CAT IV and

Simplified report writer feature included in Fluke Power      1000 V CAT III safety rating

Analyze.

                                                              Designed to help protect you and your equipment,

                                                              the Fluke 1750 Three-Phase Power Recorder and accesso-

                                                              ries are all certified to meet the stringent safety standards

                                                              for use in 600 V CAT IV and 1000 V CAT III environ-

                                                              ments. They are the first tools of their kind to carry the

                                                              CAT IV rating and, therefore, can be used for most power

                                                              connections and for all outlets in a low-voltage power

                                                              distribution system.

4  Fluke Corporation  Fluke 1750 Three-Phase Power Recorder
                                    Optional                 Accessories

Fluke power quality current

transformers and flexible current

probes are specially designed

to work seamlessly with Fluke

power monitors (1750 and 1650).

All clamp-on and flexi-CT’s are

matched to take full advantage

of your instrument’s ability to

set scale factors for accurate

readings.

                                                                                                             Frequency

Cases                                Model No.               CT Type   Current Range    Accuracy             Response   Jaw Opening

1750/CASE Transit Case               3005-PR                 Clamp-On  0.01 A to 5 A    1 % RDG ± 0.5 % FS   5 kHz      2 cm (.78 in) dia.

• Rugged water tight transit case    3014-PR                 Clamp-On  0.1 A to 40 A    1 % RDG ± 0.1 % FS   5 kHz      2 cm (.78 in) dia.

   with rollers                      3140R                   Clamp-On  2 A to 400 A     2 % RDG ± 0.04 A     20 kHz     3.2 cm (1.25 in) dia.

Miscellaneous

1750/MC
• Additional SD Memory Card

   for Fluke 1750

1750/SEAT-L
• Fluke Power Analyze –

   Additional SEAT LICENSE
• One additional license for

   installation on one additional

   PC

1750/SITE-L                                                                                                  Frequency
• Fluke Power Analyze -
                                     Model No.               CT Type   Current Range    Accuracy             Response   Probe Length
   Additional SITE LICENSE
• Site license for installation on   3110-PR                 Flexi-CT  2 A to 100 A     1 % rdg ± 0.5 % FS   7 kHz      60 cm (24 in)

   unlimited PCs                     3210-PR                 Flexi-CT  20 A to 1000 A   1 % rdg ± 0.15 % FS  7 kHz      60 cm (24 in)

                                     3310-PR                 Flexi-CT  100 A to 5000 A  1 % rdg ± 0.15 % FS  7 kHz      60 cm (24 in)

4006 Security Cable                  3312-PR                 Flexi-CT  100 A to 5000 A  1 % rdg ± 0.15 % FS  7 kHz      120 cm (48 in)

• 1.8 m (6 ft) looped lockable

   steel cable for securing monitor

5  Fluke Corporation  Fluke 1750 Three-Phase Power Recorder
                      Specifications for the System:

   Recorder and Power Analyze Software

General

   Power quality measurement standards

   Conformance                          IEC 61999-1-4 Class 1, IEC 61000-4-30, IEEE519, IEEE1159, IEEE1459 and EN50160

   Clock/calendar                       Leap years, 24-hour clock

   Real-time clock accuracy             Not more than ± 1 s/day

   Internal memory capacity for data    At least 2 GB

   Maximum recording period             At least 31 days

   Measurement time control             Automatic

   Maximum number of events             Limited only by the size of the internal memory

   Power requirements                   100 to 240 V rms ± 10 %, 47-63 Hz, 40 W

   Operating time during interruptions  5 minutes per interruption, 60 minutes total operating time without recharging

   (internal UPS operation)

   Dimensions                           215 mm x 310 mm x 35 mm (8.5 in x 12.2 in x 3.5 in)

   Mass (weight)                        6.3 kg (14 lb)

Input

   Measurement types                    One Phase Plus Neutral, One Phase IT No Neutral, One Phase Split Phase, Three Phase Wye,

                                        Three Phase Delta, Three Phase IT, Three Phase High Leg, Three Phase Open Leg, 2 Element Delta,

                                        21/2 Element Wye

   Input channels                       Voltage: 4 channels, ac/dc

                                        Current: 5 channels

   Voltage channels                     Input resistance: 2 MΩ

                                        Input capacitance: < 20 pF

   Current input characteristics        2 V rms = full scale, 1 MΩ Input Impedance for ferro CTs, low impedance for Flexi-CTs

   Measuring method                     Simultaneous digital sampling of voltage and current. Digital PLL synchronized sampling, internal

                                        frequency reference used during voltage drops.

Synchronization and sampling

   PLL-synchronization source           The PLL synchronizes to the A-N voltage for wye power types, and to the A-B voltage for delta

                                        power types. All listed power types can be characterized as either wye or delta.

   PLL lock range                       42.5 to 69 Hz

   Sampling frequency                   Voltage and current: 256 samples/cycle

                                        Inter-harmonics per IEC 61000-4-7: 2560 points/10 cycles (50 Hz),

                                        3072 points/12 cycles (60 Hz)

                                        Transient Voltage: 5 MHz

   A/D resolution                       Voltage and current: 24 bits

                                        Transient voltage: 14 bits

Voltage and current measurements

   Voltage measurement range            AC voltage: 1000 V rms ± 10 % over range

                                        DC voltage: ± 1000 V + 10 % over range

   Voltage crest factor                 3 or less

   Current measurement range            Depends on current probe used

   Current crest factor                 4 or less

Voltage and current measurement accuracy

   RMS voltage

   Measurement type                     True rms calculated continuously: every cycle, every 1/2 cycle, and

                                        every 10 or 12 cycles at 50 or 60 Hz respectively, as required by IEC 61000-4-30.

   Measurement uncertainty              AC: ± 0.2 % reading ± 0.1 % full scale, above 50 V rms

                                        DC: ± 0.5 % reading ± 0.2 % full scale, above 50 V dc

   RMS current

   Measurement type                     True rms calculated continuously: every cycle, every 1/2 cycle, and

                                        every 10 or 12 cycles at 50 or 60 Hz respectively, as required by standards

   Measurement uncertainty              Ferromagnetic Clamps: ± (0.1 % full scale + 0.2 % reading + current sensor accuracy),

                                        valid for 5 % to 100 % of current sensor range

                                        Flexible Current Probes: ± (0.1 % full scale + 0.5 % reading + current sensor accuracy),

                                        valid for 5 % to 100 % of current sensor range

6  Fluke Corporation  Fluke 1750 Three-Phase Power Recorder
Transient voltage (impulse)

   Measurement type                      Waveshape sampling

   Full scale                            8000 V pk

   Sample resolution                     200 nS

   Measurement uncertainty               ± 5 % reading ± 20 V (test parameters: 1000 V dc, 1000    V rms,   100 kHz)

Dip (Sag) and Swell Measurements

   Voltage swell (rms swell)

   Measurement type                      True rms (one cycle calculation by overlapping each half  cycle -  voltage between  lines    is  measured

                                         for 3P3W lines and phase voltage is measured for 3P4W     lines)

   Displayed data                        Amplitude and duration of swell

   Measurement uncertainty               Same as rms voltage

   Voltage dip (rms sag)

   Measurement type                      True rms (one cycle calculation by overlapping each half  cycle -  voltage between  lines    is  measured

                                         for 3P3W lines and phase voltage is measured for 3P4W     lines)

   Displayed data                        Amplitude and duration of dip or interruption

   Measurement uncertainty               Same as rms voltage

   Voltage dropout (interruption)

   Measurement type                      Same as voltage dip

Power Measurements

   Calculated per IEEE1459 for best performance when distortion is present

   Measurement type                      True rms calculated continuously: every cycle, and every 10 or 12 cycles at 50 or 60 Hz respec-

                                         tively, as required by standards

   Measurement accuracy                  +/- (voltage uncertainty + current uncertainty + current probe uncertainty)

   Frequency

   Measurement range                     42.5 to 69 Hz

   Measurement source                    Same as PLL synchronization source

   Measurement accuracy                  ± 10 mHz (10 to 110 % of range, with sine wave)

   Power factor

   Measurement range                     0.000 to 1.000

   Measurement accuracy                  ± 1 digit from the calculation of each measured value (±3 digits for total)

   Displacement power factor

   Measurement method                    Calculated from the phase difference between voltage fundamental and current fundamental

   Measurement range                     - 1.000 (leading) to + 1.000 (lagging)

   Measurement accuracy                  ± 0.5 % reading ± 2 % full scale ± 1 digit

   Voltage unbalance and phase sequence

   Measurement method                    Positive sequence voltage divided by negative sequence voltage, per IEC 61000-4-30

   Harmonic voltage and current

   Analysis window                       rectangular

   Analysis order                        1st to 50th order

   Measurement accuracy                  Voltage / Current: 1st to 20th orders: ± 0.5 % reading ± 0.2 % full scale, 21st to 50th orders: ±  1  %

                                         reading ± 0.3 % full scale (current sensor accuracy must be included for current and power)

   Measurement method                    IEC 61000-4-7

   Inter-harmonic voltage and current (intermediate harmonics)

   Analysis window                       rectangular

   Analysis orders                       1.5 to 49.5th order

   Measurement method                    IEC 61000-4-7

   Voltage flicker

   Measurement method                    as per EN 61000-4-15:2003: 10 min (Pst), 2 h (Plt)

7  Fluke Corporation  Fluke 1750 Three-Phase Power Recorder
External Interface Specifications

   LAN interface

   Connector                            RJ-45

   Speed and type                       10/100 Base-T, auto MDIX

   Communications protocol              TCP/IP over Ethernet

   Wireless controller interface

   Connection                           wireless (2.4 GHz radio)

   Speed                                up to 700 kbit/second

   Communications protocol              Bluetooth SPP

Environmental and safety specifications

   Operating environment                Indoors or in covered area outdoors, up to 2000 m altitude (for compliance to IEC61010 standard)

   Storage temperature and humidity     -20 °C to 50 °C, 80 % RH max, non-condensing

   Operating temperature and humidity   0 °C to 40 °C, 80 % RH max, non-condensing

   Maximum rated working voltage

   Voltage terminals                    1100 V rms

   Voltage durability                   5550 V rms ac for 1 minute, between voltage input terminals, voltage input terminals and current

                                        probes, and voltage input terminals and case (50/60 Hz, 1 mA sense current)

   Enclosure protection                 IP30 (per EN 60529)

   Standards conformance

   EMC                                  EN 61326-1:1997+A1:1998 Class A

                                        EN 61000-3-2:1995+A1:1998+A2:1998

                                        EN 61000-3-3:1995

   Safety                               EN 61010-1 2nd Edition; 2000

                                        Voltage input unit: Contamination Level 2, Overvoltage Category 1000 V CAT III, 600 V CAT IV

                                        (anticipated overvoltage: 8000 V)

Ordering information                    •       SD memory card

Fluke 1750 Three-Phase Power            •       Fluke Power View and Fluke Power

Recorder                                •       Analyze software

                                        •       Power cord with international plug set

Includes:                                       Ethernet cable
• 1750 acquisition unit
• PDA wireless “front panel interface”  •       Color localization set
                                        •
                                        •       Printed Getting Started manual

   and charger power plug adapters              Product CD with software and users
• 4 - 400 A current probes (3140R)
• 5 test leads and clips                •       manual PDF

                                                Soft carrying case

Fluke 1750/B Three-Phase Basic Power Recorder

Includes items above with the exception of the

4 - 400 A current probes (3140R)                                                                          Fluke.  Keeping your world

                                                                                                                  up and running.®

                                                              Fluke offers a full suite of power qual-    Fluke Corporation

                                                              ity test tools to locate, predict, prevent  PO Box 9090, Everett, WA 98206 U.S.A.

                                                              and troubleshoot power problems.            Fluke Europe B.V.
                                                              • Handheld troubleshooters for in-
                                                                                                          PO Box 1186, 5602 BD

                                                              stant analysis                              Eindhoven, The Netherlands

                                                              • Ready-to-use power loggers                For more information call:

                                                              • Comprehensive power quality re-           In the U.S.A. (800) 443-5853 or

                                                              corders                                     Fax (425) 446-5116

                                                                                                          In Europe/M-East/Africa +31 (0) 40 2675          200  or

                                                              • Power calibrators and standards           Fax +31 (0) 40 2675 222

                                                              backed by Fluke metrology                   In Canada (800)-36-FLUKE or

                                                              expertise                                   Fax (905) 890-6866

                                                                                                          From other countries +1 (425) 446-5500           or

                                                              The Fluke power quality set of              Fax +1 (425) 446-5116

                                                                                                          Web access: http://www.fluke.com

                                                              products offers the highest level of        ©2006-2009 Fluke Corporation. Windows® is a

                                                              performance and maintains the Fluke         registered trademark of Microsoft Corporation.

                                                              promise of rugged and reliable test         Specifications subject to change without notice.

                                                                                                          Printed in U.S.A. 10/2009 2428201F D-EN-N

                                                              tools.                                      Modification of this document is not permitted

                                                                                                          without written permission from Fluke Corporation.

8  Fluke Corporation   Fluke 1750 Three-Phase Power Recorder

                                                                                                                                            Pub-ID 11578-eng
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Fluke:

FLUKE-1750  FLUKE-1750/CASE  FLUKE-1750/SITE-L  FLUKE-1750/B  FLUKE-1750/MC2GB