   Fluke 1623 and 1625

            GEO Earth Ground Testers

                                                                             Technical Data

The new Fluke 1623 and 1625

GEO Earth Ground Testers offer

an innovative solution, called

Stakeless testing, to make your

earth ground loop resistance

testing quicker and easier. No

need for a separate earth

ground clamp.

•  3- and 4-pole Fall of Potential,

   earth resistance loop testing

•  4-pole Soil Resistivity testing

•  Selective earth ground rod

   testing using 1 clamp

•  Stakeless earth ground rod

   testing using 2 clamps

•  IP56 rated for outdoor use

•  Rugged carrying case

In addition, the Fluke 1625 offers

these advanced features:

•  Automatic Frequency Control

   (AFC) - identifies existing

   interference and chooses a

   measurement frequency to          Stakeless testing                       the building or structure under test, but

   minimize its effect, providing    The Fluke 1623 and 1625 earth           most are. If there is only one path to

   more accurate earth ground        ground testers are able to measure      ground, like at many residential appli-

   value                             earth ground loop resistances using     cations, the Stakeless method will not

•  R* measurement - calculates       only clamps. With this test method,     provide an acceptable value and the Fall

   earth ground impedance at         two clamps are placed around the        of Potential test method must be used.

                                     earth ground rod and each are con-      With Stakeless testing, the earth

   55 Hz to more accurately          nected to the tester. No earth ground   ground rod does not need to be dis-

   reflect the earth ground          stakes are used at all. A known, fixed  connected—leaving the bonded earth

   resistance that a fault-to-       voltage is induced by one clamp and     ground system intact during test. Gone

   earth ground would see            the current is measured using the       are the days of spending time placing

•  Adjustable limits - for quicker   second clamp. Then the tester auto-     and connecting stakes for each earth

   testing                           matically determines the resistance     ground rod on your system—a major

                                     of the earth ground rod.                time saver. You can also perform earth

                                     This test method only works if a        ground tests in places you’ve not

                                     bonded earth ground system exists for   considered before: inside buildings,

                                                                             power pylons, or anywhere you don’t

                                                                             have access to soil.
The most complete testers                                               The testers are also easy to use. For each test,

The Fluke 1623 and 1625 are distinctive earth                           the testers inform you which stakes or clamps need

ground testers that can perform all four types of                       to be connected and the large rotary switch can be

earth ground measurement:                                               used even with a gloved hand.

• 3- and 4-Pole Fall of Potential (using stakes)                        The complete model kit comes with the 1623

• 4-Pole Soil Resistivity testing (using stakes)                        or 1625 tester, test leads, 4 earth ground stakes,

• Selective testing (using 1 clamp and stakes)                          3 cable reels with wire, 2 clamps, batteries, and

• Stakeless testing (using 2 clamps only)                               manual—all inside a rugged Fluke carrying case.

1623 Specifications

General

   Display:1999 digit LCD                     Display with special symbols, digit height 25 mm, fluorescent backlight

   User interface                             Instant measurement through TURN and START one button concept. The only operating elements                        are

                                              rotary switch and START button

   Robust and waterproof                      Instrument is designed for tough environmental conditions (rubber protective cover, IP56)

Temperature ranges

   Working temperature                        -10 °C to 50 °C (14 °F    to 22 °F)

   Operating temperature                      0 °C   to 35 °C (32 °F    to 95 °F)

   Storage temperature                        -20 °C  to 60 °C (-4 °F   to 140 °F)

   Reference temperature                      23 °C   to ± 2 °C (73 °F  to ± 4 °F)

The chart of four temperature ranges for the  instrument exist to satisfy European Standards requirements; the instrument can be used over  the  full  working

temperature range by using the temperature    coefficient to calculate accuracy at the ambient temperature of use.

   Temperature coefficient                    ± 0.1 % of reading/K

   Intrinsic error                            Refers to the reference temperature range and is guaranteed for 1 year

   Operating error                            Refers to the operating temperature range and is guaranteed for 1 year

   Climatic class                             C1 (IEC 654-1), -5 °C to +45 °C (23° to +115° F), 5 % to 95 % RH

   Protective type                            IP56 for case, IP40 for battery door according to EN60529

   Safety                                     Protection by double and/or reinforced insulation. max. 50 V to earth

   EMC (Emission Immunity)                    IEC 61326-1:1997 Class A

   Quality system                             Developed, designed and manufactured according to DIN ISO 9001

   External voltage                           V ext, max = 24 V (dc, ac < 400 Hz), measurement inhibited for higher values

   V ext rejection                            > 120 dB (162⁄3, 50, 60, 400 Hz)

   Measuring time                             Typical 6 sec.

   Max. overload                              250 V rms (pertains to misuse)

   Auxiliary power                            6 x 1.5 V mignon cells alkali-manganese (type AA LR6)

   Battery life span                          Typical > 3,000 measurements

   Dimensions (WxHxD)                         250 mm x 133 mm x 187 mm (9.75 in x 5.25 in x 7.35 in)

   Weight                                     1.1 kg (2.43 lb) including batteries

  Fluke Corporation  1623 and 1625 GEO Earth Ground Testers
RA 3-pole ground resistance measurement (IEC 1557-5)

   Switch position             Resolution                     Measuring range                       Intrinsic error                   Operating   error

   RA 3-pole                   0.001 Ω to 10 Ω                0.001 Ω to 19.99 kΩ                   ± (2 % rdg + 3 d)                 ± (5 % rdg  + 3 d)

For 2-pole measurements connect terminals H and S with the supplied connector cable.

Measuring principle: Current and voltage measurement

   Measuring voltage                                                                                Vm = 48 V ac

   Short-circuit current                                                                            > 50 mA

   Measure frequency                                                                                128 Hz (125 Hz on request)

   Probe resistance (RS)                                                                            Max 100 kΩ

   Auxiliary earth electrode resistance (RH)                                                        Max. 100 kΩ

   Additional error from RH and RS                                                                  RH[kΩ]• • •RS[kΩ]/RA[Ω] • • •0.2  %

   Monitoring of RS and RH with error indicator

   Automatic range selection

   Measurement is not performed if the current    through     the  current  clamp     is  too  low

RA 4-pole ground resistance measurement (IEC 1557-5)

   Switch position             Resolution                     Measuring range                       Intrinsic error                   Operating error

   RA 4-pole                   0.001 Ω to 10 Ω                0.001 Ω to 19.99 kΩ                   ± (2 % rdg + 3 d)                 ± (5 % rdg + 3 d)

Measuring principle: Current/voltage measurement

   Measuring voltage                                                                                Vm = 48 V ac

   Short-circuit current                                                                            > 50 mA

   Measuring frequency                                                                              128 Hz (125 Hz on request)

   Probe resistance (RS+ RES)                                                                       Max. 100 kΩ

   Auxiliary earth electrode resistance (RH)                                                        Max. 100 kΩ

   Additional error from RH and RS                                                                  RH[kΩ]• • •RS[kΩ/RA[Ω]• • •0.2 %

   Monitoring of RS, and RH with error indicator

   Automatic range selection

RA 3-pole selective ground resistance measurement with current clamp                                                     (RA          )

   Switch position             Resolution                     Measuring range                       Intrinsic error                   Operating error

   RA 3-pole                   0.001 Ω to 10 Ω                0.001 Ω to 19.99 kΩ                   ± (7 % rdg + 3 d)                 ± (10 % rdg + 5 d)

Measuring principle: Current/voltage measurement (with external current clamp)

   Measuring voltage                                                                                Vm = 48 V ac

   Short-circuit current                                                                            > 50 mA

   Measuring frequency                                                                              128 Hz (125 Hz   on  request)

   Probe resistance (RS)                                                                            Max. 100 kΩ

   Auxiliary earth electrode resistance (RH)                                                        Max. 100 kΩ

   Monitoring of RS, and RH with error indicator

   Automatic range selection

   Measurement is not performed if the current    through     the  current  clamp     is  too  low

  Fluke Corporation  1623 and 1625 GEO Earth Ground Testers
RA 4-pole selective ground resistance measurement with current clamp                                                     (RA       )

   Switch position            Resolution                         Measuring range                    Intrinsic error                Operating error

   RA 4-pole                  0.001 Ω to 10 Ω                    0.001 Ω to 19.99 kΩ                ± (7 % rdg + 3 d)              ± (10 % rdg + 5 d)

Measuring principle: Current/voltage measurement (with external current clamp)

   Measuring voltage                                                                                Vm = 48 V ac

   Short-circuit current                                                                            > 50 mA

   Measuring frequency                                                                              128 Hz (125 Hz   on  request)

   Probe resistance (RS)                                                                            Max. 100 kΩ

   Auxiliary earth electrode resistance (RH)                                                        Max. 100 kΩ

   Monitoring of RS, and RH with error indicator

   Automatic range selection

   Measurement is not performed if the current    through        the  current  clamp  is  too  low

Stakeless ground loop measurement (                              )

   Switch position            Resolution                         Measuring range                    Intrinsic error                Operating error

   RA 4-pole                  0.001 Ω to 0.1 Ω                   0.001 Ω to 199.9 Ω                 ± (7 % rdg + 3 d)              ± (10 % rdg + 5 d)

Measuring principle: Stakeless measurement of resistance in closed loops using two current transformers

   Measuring voltage                                                                  Vm = 48 V ac (primary)

   Measuring frequency                                                                128 Hz (125 Hz on request)

   Noise current (IEXT)                                                               Max. IEXT = 10 A (ac) (RA < 20 Ω)

                                                                                      Max. IEXT = 2 A (ac) (RA > 20 Ω)

Automatic range selection

The information regarding stakeless ground loop measurements is only valid when used in conjunction with the recommended current clamps at the minimum

distance specified.

  Fluke Corporation     1623 and 1625 GEO Earth Ground Testers
1625 Specifications

General

   Description                Microprocessor controlled, fully automated earth measuring instrument with additional functions

   Measuring function         Interference voltage and frequency, earthing resistance 3- and 4-pole with/without clip-on current transformer,

                              resistance 2-pole with ac, 2- and 4-pole with dc

   Display                    4 digit (2999 Digit) - 7 segment liquid crystal display, digit size 18 mm (0.71 in) with supplementary signs and

                              active illumination

   Operation                  Central rotary switch and function keys

Temperature ranges

   Working temperature range                       -10 °C to 50 °C (14° F to 122° F)

   Operating temperature range                     0 °C to 35 °C (32° F to 95° F)

   Nominal temperature range                       18 °C to 28 °C (64° F to 82° F)

   Storage temperature range                       -30 °C to 60 °C (-22° F to 140° F)

Note: The chart of four temperature ranges for the instrument exist to satisfy European Standards requirements; the instrument can be used over the full Working

temperature range by using the temperature coefficient to calculate accuracy at the ambient temperature of use.

   Temperature coefficient                         ± 0.1 % of range/Kelvin

   Operating errors                                Refer to operating temperature range and RH < 20 RE, RS < 100 RE

The maximum percentage operating error within the measurement range does not exceed ± 30 % with the measured value as fiducial value, as determined in

accordance with Table 1 in the 1625 Users Manual.

The operating error applies under the rated operating conditions given in IEC1557-1 and the following:

•  injection of series interference voltages with system frequencies of 400 Hz, 60 Hz, 50 Hz, 162/3 Hz or with dc voltage respectively across the terminals E (ES)

   and S. The rms value of the series interference voltage shall be 3 V;

•  resistance of the auxiliary earth electrode and of the probes: 0 to 100 x RA but ≤ 50 kΩ;

•  system voltages between 85 % and 110 % of the nominal voltage and between 99 % and 101 % of the nominal system frequency for measuring equipment

   with a mains supply and/or measuring equipment deriving its output voltage directly from the distribution system.

  Fluke Corporation  1623 and 1625 GEO Earth Ground Testers
   Limits of error                    Refer to nominal temperature range

   Climate class                      C1 (IEC 654-1), -5 °C to 45 °C, 5 % to 95 % RH

   Type of protection                 IP56 for case, IP40 for battery door according to EN60529

   Max voltage                        !  socket                 to socket

                                      Urms =  0V

                                      Sockets ”                 “      to each other in any combination, max.   Urms = 250  V  (pertains  to  misuse)

   EMC (Emission Immunity)            IEC 61326-1:1997 Class A

   Quality standard                   Developed, designed and manufactured to comply with DIN ISO 9001

   External field influence           Complies with DIN 43780 (8/76)

   Auxiliary power                    6 x 1.5 V alkali-manganese-batteries (IEC LR6 or type AA )

   Battery life span                  With IEC LR6/type AA: typ. 3,000 measurements (RE+RH ≤ 1 kΩ)

                                      With IEC LR6/type AA : typ. 6,000 measurements (RE + RH > 10 kΩ)

   Dimensions (WxHxD)                 250 mm x 133 mm x 187 mm (9.75 in x 5.25 in x 7.35 in)

   Weight                             ≤ 1.1 kg (2.43 lb) without accessories

                                      ≤ 5.5 kg (12.13 lb) incl. accessories and batteries in carrying case

   Case material                      NORYL, shock -and scratch proof thermoplast

Measurement of interference voltage dc + ac (UST)

   Measuring Limits of error: method                               Fullwave rectification

   Measuring Range           Display Range                      Resolution                  Frequency Range                    Limits of Error

   1 V to 50 V               0.0 V to 50 V                      0.1 V                       dc/ac 45 Hz to 400  Hz  sine       ± (5 % of rdg + 5 digit)

   Measuring sequence        approx. 4 measurements/s

   Internal resistance       approx. 1.5 MΩ

   Max. overload             Urms = 250 V

Measurement of interference frequency (F )

   Measuring method          Measurement of oscillation period of the interference voltage

   Measuring Range           Display Range                                  Resolution        Range                            Limits of Error

   6.0 Hz to 400 Hz          16.0 Hz to 299.9 Hz to 999 Hz                  0.1 Hz to 1 Hz    1 V to 50 V                      ± (1 % of rdg + 2 digit)

Earthing resistance          (RE)

   Measuring method                   Current and voltage measurement with probe as IEC61557-5

   Open circuit voltage               20/48 V, ac

   Short circuit current              250 mA     ac

   Measuring frequency                94, 105, 111, 128 Hz         selected manually or automatic. (AFC) 55 Hz      in function R*

   Noise rejection                    120 dB (162/3, 50 , 60, 400 Hz)

   Max. overload                      Urms = 250 V

  Fluke Corporation    1623 and 1625 GEO Earth Ground Testers
Electrical measurement           specifications

                                                                                                                    Requirements or test in

   Intrinsic error or influence  Reference conditions or specified                      Designation                 accordance with the relevant                  Type

   quantity                      operating range                                                code                parts of IEC 1557                             of test

   Intrinsic error               Reference conditions                                           A                   Part 5, 6.1                                      R

   Position                      Reference position ± 90°                                       E1                  Part 1, 4.2                                      R

   Supply voltage                At the limits stated by the                                    E2                  Part 1, 4.2, 4.3                                 R

                                 manufacturer

   Temperature                   0 °C and 35 °C                                                 E3                  Part 1, 4.2                                      T

   Series interference voltage   See 4.2 and 4.3                                                E4                  Part 5, 4.2, 4.3                                 T

   Resistance of the probes and  0 to 100 x RA but ≤ 50 kΩ                                      E5                  Part 5, 4.3                                      T

   auxiliary earth electrodes

   System frequency              99 % to 101 % of the                                           E7                  Part 5, 4.3                                      T

                                 nominal frequency

   System voltage                85 % to 110 % of the nominal voltage                           E8                  Part 5, 4.3                                      T

   Operating error                                                                                                  Part 5, 4.3                                      R

   A   =       intrinsic error

   En  =       variations

   R   =       routine test

   T   =       type test

   Measuring

   Range                        Display Range                 Resolution                Instrinsic Error                              Max. Operating Error

   0.020 Ω to              0.001 Ω to 2.999 Ω                     0.001 Ω               ± ( 2 % of rdg + 2 digit )                    ± ( 5 % of rdg + 5 digit )

   300 kΩ                    3.00 Ω to 29.99 Ω                       0.01 Ω

                             30.0 Ω to 299.9 Ω                       0.1 Ω

                           0.300 kΩ to 2.999 kΩ                      1Ω

                           3.00 kΩ to 29.99 kΩ                       10 Ω

                           30.0 kΩ to 299.9 kΩ                       100 Ω

   Measuring time                                                                       typ. 8 sec. with a fixed frequency

                                                                                        30 sec. max. with AFC and complete cycle of all measuring frequencies

   Additional error because of probe-and         auxiliary earth

   electrode resistance

   Measuring error of RH and RS                                                         typ. 10 % of RE + RS + RH

   Max. probe resistance                                                                ≤ 1 MΩ

   Max. auxiliary earth electrode resistance                                            ≤ 1 MΩ

Automatic check if error is kept within the limits required by IEC61557-5.

If after a measurement of probe-, auxiliary earth electrode- and earthing resistance, a measurement error of higher than 30 % is assumed because of the influencing

conditions (see diagram), the display shows a warning symbol      !  and a notice that  RS or RH are too high.

  Fluke Corporation      1623 and 1625 GEO Earth Ground Testers
Automatic switchover of measuring resolution in

dependence to auxiliary earth electrode resistance RH

   RH with   Umeas = 48 V     RH with Umeas = 20 V        Resolution

   < 300 Ω                       < 250 Ω                         1 mΩ

   < 6 kΩ                        < 2.5 kΩ                        10 mΩ

   < 60 kΩ                       < 25 kΩ                         100 mΩ

   < 600 kΩ                      < 250 kΩ                        1Ω

Selective measurement of the earthing

resistance (RE             )

   Measuring method           Current and voltage measurement with

                              probe as per EN61557-5 and current

                              measurement in the individual branch

                              with additional current transformer

                              (patent applied for).

   Open circuit voltage       20/48 V ac

   Short circuit current      250 mA ac

   Measuring frequency        94, 105, 111, 128 Hz selected manually

                              or automatically (AFC), 55 Hz (R*)

   Noise rejection            120 dB (162/3, 50, 60, 400 Hz)

   Max. overload              Max. Urms = 250 V (measurement will

                              not be started)

   Measuring Range                                Display range              Resolution                     Intrinsic error*     Operating error*

   0.020 Ω to 30 kΩ                       0.001 to 2.999 Ω                       0.001 Ω            ± (7 % of rdg + 2 digit)     ± (10 % of rdg + 5 digit)

                                          3.00 to 29.99 Ω                        0.01 Ω

                                          30.0 to 299.9 Ω                        0.1 Ω

                                          0.300 to 2.999 kΩ                      1Ω

                                          3.00 to 29.99 kΩ                       10 Ω

*  With recommended current clamps/transformers.

   Additonal error because of probe- and auxiliary earth

   typ. electrode resistance

   Measuring error of RH and RS                                          Typ. of 10 % of RETOTAL + RS + RH

   Measuring time                                                        Typ. 8 sec. with a fixed frequency 30 sec. max. with AFC and complete cycle of

                                                                         all measuring frequencies

   Minimal current in single branch to be measured                       0.5 mA                     With transformer (1000:1)

                                                                         0.1 mA                     With transformer (200:1)

   Max. interference current through transformer                         3A                         With a transformer (1000:1)

  Fluke Corporation  1623 and 1625 GEO Earth Ground Testers
Resistance measurement (R~)

   Measuring method                 Current and voltage measurement

   Measuring voltage                20 V ac, square pulse

   Short circuit current            > 250 mA ac

   Measuring frequency              94, 105, 111, 128 Hz selected manually or automatically (AFC)

   Measuring range              Display range                 Resolution                                     Intrinsic    error                Operating errors

   0.020 Ω to 300 kΩ            0.001 Ω to 2.999 Ω                         0.001 Ω                        ±  (2 % of rdg  + 2 digit)     ± (5 % of rdg + 5 digit)

                                3.0 Ω to 29.99 Ω                           0.01 Ω

                                30 Ω to 299.9 Ω                            0.1 Ω

                                300 Ω to 2999 Ω                            1Ω

                                3.0 kΩ to 29.99 kΩ                         10 Ω

                              30.0 kΩ to 299.9 kΩ                          100 Ω

   Measuring time                   typ. 6 sec.

   Max. interference voltage        24 V, with higher voltages measurement          will      not            be started

   Max overload                     Urms       max. = 250 V

Resistance measurement          (R  )

   Measuring method                 current- voltage measurement as per IEC61557-4 possible

   Open circuit voltage             20 V dc

   Short circuit current            200 mA dc

   Formation of measured value      with 4-pole measurement wires on H, S, ES can be extended                             without  additional  error.

                                    Resistances > 1 Ω in wire E can cause additional error of 5m                          Ω/Ω.

   Measuring range              Display range                 Resolution                                     Intrinsic error                   Operating error

   0.020 Ω to 3 kΩ            0.001 Ω to 2.999 Ω                           0.001 Ω            ± (2 % of rdg + 2 digit)                   ± (5 % of rdg + 5 digit)

                                3.0 Ω to 29.99 Ω                           0.01 Ω

                              30.0 Ω to 299.9 Ω                            0.1 Ω

                                300 Ω to 2999 Ω                            1Ω

   Measuring sequence               Approx. 2 measurements/s

   Measuring time                   Typ. 4 sec. incl. reversal of polarity (2-pole or 4-pole)

   Max. interference voltage        ≤ 3 V ac or dc, with higher voltages measurement will not be started

   Max inductivity                  2 Henry

   Max. overload                    Urms = 250 V

Compensation of lead resistance (RK)

   Compensation of lead resistance (RK) can be switched on in functions RE 3-pole, RE 4-pole                 , R~ , and R        2-pole

   Formation of measured value      R = R - R * display
                                                    measured  compensated

* Value of setpoint entry RK = 0.000 Ω, variable from 0.000 to 29.99 Ω by means of measuring adjustment.

  Fluke Corporation  1623 and 1625 GEO Earth Ground Testers
Selection   guide by user

                       Field Service            Industrial             Power Utilities

                       Technician               Maintenance            and Telecom

                                                Technician

Fluke 1623                •                        •

Fluke 1625                                         •                   •

Standard    earth ground test methods

                          Fall of Potential                 Selective  Stakeless

                       3-pole         4-pole/soil            1 clamp   2 clamps

Fluke 1623             •                     •                 •          •

Fluke 1625             •                     •                 •          •

Ordering information

Fluke-1623 Kit                 Basic GEO Earth Ground Tester Kit

Fluke-1623                     Basic GEO Earth Ground Tester

EI-1623                        Selective/Stakeless Clamp Set for 1623

Fluke-1625 Kit                 Advanced GEO Earth Ground Tester Kit

Fluke-1625                     Advanced GEO Earth Ground Tester

EI-1625                        Selective/Stakeless Clamp Set for 1625

Optional accessories

ES-162P3                       Stake Set for 3-Pole Measurement

ES-162P4                       Stake Set for 4-Pole Measurement

Earth Stake                    Ground/Earth Stake

Cable-Reel 25 m                Ground/Earth Cable Reel 25 m (81.25 ft)

Cable-Reel 50 m                Ground/Earth Cable Reel 50 m (162.5 ft)

EI-162BN                       320 mm (12.6 in) Split Core Transformer

                                                                                        Fluke. Keeping your world

                                                                                        up and running.

                                                                                        Fluke Corporation

                                                                                        PO Box 9090, Everett, WA USA 98206

                                                                                        Fluke Europe B.V.

                                                                                        PO Box 1186, 5602 BD

                                                                                        Eindhoven, The Netherlands

                                                                                        For more information call:

                                                                                        In the U.S.A. (800) 443-5853 or

                                                                                        Fax (425) 446-5116

                                                                                        In Europe/M-East/Africa +31 (0) 40 2675 200    or

                                                                                        Fax +31 (0) 40 2675 222

                                                                                        In Canada (800) 36-FLUKE or

                                                                                        Fax (905) 890-6866

                                                                                        From other countries +1 (425) 446-5500 or

                                                                                        Fax +1 (425) 446-5116

                                                                                        Web access: http://www.fluke.com

                                                                                        ©2006 Fluke Corporation. All rights reserved.

                                                                                        Printed in U.S.A. 5/2006 2634980 D-EN-N Rev A

10  Fluke Corporation  1623 and 1625 GEO Earth Ground Testers
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle  Information:

Fluke:

FLUKE-1623  FLUKE-1623-KIT  FLUKE-1625  FLUKE-1625-KIT
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2020 EEWORLD.com.cn, Inc. All rights reserved