器件描述

Controllers End Unit M3 Screws

参数

产品属性属性值
产品种类:
Product Category:
Controllers
制造商:
Manufacturer:
Omron
RoHS:YES
类型:
Type:
Temperature Controllers
工作电源电压:
Operating Supply Voltage:
24 VDC
Mounting:DIN Rail
大小:
Size:
79.7 mm x 95.4 mm x 15.7 mm
商标:
Brand:
Omron Automation and Safety
Features:Standard control model, end unit
封装:
Packaging:
Bulk
系列:
Series:
EJ1
工厂包装数量:
Factory Pack Quantity:
1
单位重量:
Unit Weight:
6.349313 oz

EJ1C-EDUA-NFLK器件文档内容

Modular Temperature Controller

EJ1

In-panel Temperature Controller with Flexible Modular

Design and Wide Integration with Host Devices

• The compact modular structure enables construction of temperature

systems optimally suited to the application.

• Connection can be made to a Programmable Controller without any

programming required, reducing the number of steps required in ladder

programming design.

• One fully universal-input Unit includes a thermocouple, platinum-resistance

thermometer, and analog input for easy selection and reduced inventory

requirements.

• Connect directly to the G3ZA Multi-channel Power Controller using optimum

cycle control for high-accuracy regulation with minimal noise.

• Autotuning (AT) can be used for independent heating/cooling PID control,

and self-tuning (ST) can be used to calculate the PID constants with the step

response method.

• Up to 16 Temperature Controllers can be connected to a single DeviceNet                                              Supports DeviceNet Communications.

Communications Unit.

                                                                                                                                     Refer to the Safety Precautions on page 21.

Ordering Information

■ Temperature Controller

Standard Control Models

       Name          Power      No. of   Control               Control       Auxiliary                  Functions      Communications       Input type       Terminal          Model

                     supply     control  outputs               outputs       output                  Heater    Event   functions

                     voltage    points   1 and 2               3 and 4                               burnout   inputs

                                                                                                        alarm

Basic Unit           24 VDC     2        Voltage output:  Transistor         None                    2         2       G3ZA connection      Thermocouple,    M3 terminal       EJ1N-TC2A-QNHB

(temperature         supplied            2 points         output: 2 points                           (See              port: RS-485         platinum         Screw-less clamp  EJ1N-TC2B-QNHB

control)             from the            (for SSR drive)  (sinking)                                  note 3.)          From End Unit:       resistance

(See note 1.)        End Unit   4        (See note 2.)    Voltage output: 2                          None      None    Port A or port B:    thermometer,     M3 terminal       EJ1N-TC4A-QQ

               V1.2                                       points (for SSR                                              RS-485               analog voltage,

                                                          drive) (See note                                                                  and analog       Screw-less clamp  EJ1N-TC4B-QQ

                                                          2.)                                                                               current

                                                                                                                                            selectable for

                                2        Current output:  Transistor                                           2                            each channel.    M3 terminal       EJ1N-TC2A-CNB

                                         2 points         output: 2 points                                                                                   Screw-less clamp  EJ1N-TC2B-CNB

                                                          (sinking)

HFU with                        None     None             None               Transistor output:                4       Port C: RS-485 or    No input         M3 terminal       EJ1N-HFUA-NFLK

Programless                                                                  4 points (sinking)                        RS-232C                               Screw-less clamp

Communications                                                                                                         selectable.

(See note 1.)                                                                                                                                                                  EJ1N-HFUB-NFLK

               V1.2                                                                                                    From End Unit:

                                                                                                                       Port A: RS-485

                                                                                                                       Port C: RS-422                        M3 terminal       EJ1N-HFUA-NFL2

                                                                                                                       From End Unit:                        Screw-less clamp  EJ1N-HFUB-NFL2

                                                                                                                       Port A: RS-485

HFU with DeviceNet                                                           None                              None    DeviceNet                             Screw-less clamp

Communications                                                                                                         communications                                          EJ1N-HFUB-DRT

(See note 1.)

End Unit             24 VDC                                                  Transistor output:                None    Port A or B: RS-485                   M3 terminal       EJ1C-EDUA-NFLK

(See note 1.)                                                                2 points (sinking)                        Connector: Port A                     Detachable

                                                                                                                                                             connector         EJ1C-EDUC-NFLK

Note:     1.  An End Unit is always required for connection to a Basic Unit or an HFU. An HFU cannot operate without a Basic Unit. External communications cannot be performed when using a

              Basic Unit only.

          2.  For heating/cooling control applications, control outputs 3 and 4 on the 2-point models are used for the cooling or heating control outputs.

              On the 4-point models, heating/cooling control is performed for the two input points.

          3.  When using the heater burnout alarm, purchase a Current Transformer (E54-CT1 or E54-CT3) separately.

Functional Upgrades

Refer to page 18 for details.

Upgrade functions are supported by the indicated version ("V1.1" or "V1.2") or a higher version of the software.

       Refer to the following manual for precautionary information and other information necessary to use the EJ1:

       EJ1 Modular Temperature Controller User’s Manual (Cat. No. H142)

                                                                                                                  Modular Temperature Controller EJ1                                          1
■ Accessories (Order Separately)

Current Transformer (CT)                                           CX-Thermo Support Software Ver. 4.1

      Diameter                  Model                                                        Model

5.8 dia.              E54-CT1                                      EST2-2C-MV4

12.0 dia.             E54-CT3

                                                                   USB-Serial Conversion Cable

G3ZA Connecting Cable                                                                        Model

    Cable length                Model                              E58-CIFQ1

5m                    EJ1C-CBLA050

Rail Mounting Equipment

          Name                  Model

Mounting Rail         PFP-100N

                      PFP-50N

Specifications

                   Basic Unit/EJ1N-TC

■ Ratings

Item                     Type                      EJ1N-TC4                                                      EJ1N-TC2

Power supply voltage           24 VDC

Operating voltage range        85% to 110% of rated voltage

Power consumption              5 W max. (at maximum load)                              4 W max. (at maximum load)

Input (See note.)              Thermocouple:                       K, J, T, E, L, U, N, R, S, B, W, PLII

                               ES1B Infrared Thermosensor:         10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C

                               Analog input:                       4 to 20 mA, 0 to 20 mA, 1 to 5 V, 0 to 5 V, 0 to 10 V

                               Platinum resistance thermometer: Pt100, JPt100

Input impedance                Current input: 150 Ω max., voltage input: 1 MΩ min.

Control    Voltage output      Output voltage: 12 VDC ±15%, max. load current: 21 mA (PNP models with short-circuit protection circuit)

outputs    Transistor output   ---                                                     Max. operating voltage: 30 V, max. load current: 100 mA

           Current output      ---                                                     Current output range: 4 to 20 mA or 0 to 20 mA DC

                                                                                       Load: 500 Ω max. (including transfer output)

                                                                                       (Resolution: Approx. 2,800 for 4 to 20 mA DC, approx.

                                                                                       3,500 for 0 to 20 mA DC)

Event      Input points        ---                                                     2

inputs     Contact input       ---                                                     ON: 1 kΩ max., OFF: 100 kΩ min.

           Non-contact         ---                                                     ON: Residual voltage: 1.5 V max.,

           input                                                                       OFF: Leakage current: 0.1 mA max.

                               ---                                                     Outflow current: Approx. 4 mA per point

Number of input and control    Input points: 4, Control points: 4                      Input points: 2, Control points: 2

points

Setting method                 Via communications

Control method                 ON/OFF control or 2-PID (with autotuning, self-tuning)  V1.2

Other functions                Two-point input shift, digital input filter, remote SP, SP ramp, manual manipulated variable, manipulated variable

                               limiter, interference overshoot adjustment, loop burnout alarm, RUN/STOP, banks, I/O allocations, etc.

Ambient temperature range      Operating: −10°C to 55°C, Storage: −25°C to 65°C (with no icing or condensation)

Ambient humidity range         Operating: 25% to 85% (with no condensation)

Note: Inputs are fully universal. Therefore, platinum resistance thermometer, thermocouple, infrared thermosensor, and analog input can be

       selected.

2               Modular Temperature Controller EJ1
■ Characteristics

Indication accuracy                  Thermocouple input/platinum resistance thermometer input:

                                                    (±0.5% of indication value (PV) or ±1°C, whichever is greater) ±1 digit max. (See  note           1.)

                                     Analog input: ±0.5% FS ±1 digit max.

                                     CT input:      ±5% FS ±1 digit max.

Hysteresis                           0.1 to 999.9 EU (in units of 0.1 EU) (See note 2.)

Proportional band (P)                0.1 to 999.9 EU (in units of 0.1 EU) (See note 2.)

Integral time (I)                    0 to 3,999 s (in units of 1 s)

Derivative time (D)                  0.0 to 999.9 s (in units of 0.1 s)

Control period                       0.5 s, 1 to 99 s (in units of 1 s)

Manual reset value                   0.0% to 100.0% (in units of 0.1%)

Alarm setting range                  −1,999 to 9,999 (decimal point position depends on input type)

Sampling period                      250 ms

Influence of signal source           Thermocouple:                        0.1°C (0.2°F)/Ω max. (100 Ω max per line) (See note 3.)

resistance                           Platinum resistance thermometer: 0.4°C (0.8°F)/Ω max. (10 Ω max per line)

Insulation resistance                20 MΩ min. (at 500 VDC)

Dielectric strength                  600 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity

Vibration resistance                 10 to 55 Hz, 20 m/s2 for 2 hours each in X, Y, and Z directions

Shock resistance                     150 m/s2, 3 times each in 6 directions

Weight                               180 g

Degree of protection                 Rear case: IP20, Terminal section: IP00

Memory protection                    EEPROM (non-volatile memory) (number of writes: 100,000)

Standards   Approved standards       UL61010C-1, CSA C22.2 No.1010-1

            Conformed standards      EN61010-1 (IEC61010-1): Pollution level 2, overvoltage category II

EMC Directive                        EMI:                                             EN61326

                                     EMI Radiated:                                    EN55011 Group1 class A

                                     EMI Conducted:                                   EN55011 Group1 class A

                                     EMS:                                             EN61326

                                     ESD Immunity:                                    EN61000-4-2

                                     Electromagnetic Field Immunity:                  EN61000-4-3

                                     Burst immunity/Noise Immunity:                   EN61000-4-4

                                     Conducted Disturbance Immunity:                  EN61000-4-6

                                     Surge Immunity:                                  EN61000-4-5

                                     Power Frequency Magnetic Field Immunity:         EN61000-4-8

Note: 1.  The indication of K thermocouples in the −200 to 1,300°C range, T and N thermocouples at a temperature of −100°C or less, and U and

          L thermocouples at any temperature is ±2°C ±1 digit maximum. The indication of B thermocouples at a temperature of 400°C or less is

          unrestricted. The indication of R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit max.

          W = (±0.5% of indication value (PV) or ±3°C, whichever is greater) ±1 digit max. PLII = (±0.5% of indication value (PV) or ±2°C, whichever

          is greater) ±1 digit max.

          The indication accuracy for K thermocouples in the −199.9 to 999.9°C range     V1.2  is (±0.5% of indication value (PV) or ±1°C, whichever

          is greater) ±10 digit maximum. However, at a temperature of -100°C or less, it is ±2°C ±10 digit maximum.

2.        “EU” stands for Engineering Unit. The location of the decimal point depends on the type of sensor that is selected.

          If the decimal point locations is set to 0 (****), however, it will be treated as if it were set to 1 (***.*).

3.        B, R, S, and W sensors: 0.2°C/Ω max. (100 Ω max.)

                                                                                      Modular Temperature Controller EJ1                                   3
■ Communications Specifications

          Item                        Port B                     Port A Terminal/ Port A Connector               G3ZA Connection       Port

                                 (See note 1.)                              (See note 1.)                        (See note 2.)

Transmission path   RS-485 (multipoint)

connection

Communications      RS-485 (two-wire, half duplex)

method

Synchronization     Start-stop synchronization

method

Communications      CompoWay/F, Modbus (See note 4.)            CompoWay/F

protocol                                                  V1.1

Baud rate           9.6, 19.2, 38.4, 57.6, or 115.2 kbps        38.4 kbps fixed                         57.6  kbps fixed

Transmission code   CompoWay/F: ASCII, Modbus: RTU              CompoWay/F: ASCII

Data bit length     7 or 8 bits                                 7 bits

Stop bit length     1 or 2 bits                                 2 bits

Error detection     Vertical parity (none, even, or odd)        Vertical parity (even)

                    Block check character (BCC): with CompoWay/F, CRC-16: (with Modbus)

Flow control        None

Interface           RS-485

Retry function      None

Communications      0 to 99 ms (default: 5 ms)  V1.1            1 to 99 ms (default: 1 ms)              ---

response wait time

Number of Units     64 Units (model numbers with TC4: 256       64 Units (model numbers with TC4: 256   8 Units (Communications connection

that can be         channels, model numbers with TC2: 128       channels, model numbers with TC2: 128   via G3ZA port on the Basic Unit)

connected in        channels)                                   channels)

parallel            Communications connection via port B        Communications connection via port A

(See note 3.)       on the End Unit                             on the End Unit

Note: 1.   Connection from the EJ1C-EDU. When using an HFU, port B on the End Unit can be used for distributed placement only.

   2.      A special cable (EJ1C-CBLA050) must be purchased separately for the G3ZA connection.

   3.      For the number of Units that can be connected, refer to Connection Precautions on page 11.

   4.      The Modbus protocol can be used with Basic Unit with version 1.1 or higher.

■ Current Transformer (CT)                                                 ■ Characteristics of the Heater

   Rating                                                                        Burnout Alarm, SSR Failure

Dielectric       1,000 VAC for 1 min                                             Alarm, and Heater Overcurrent

strength                                                                         Alarm (TC2@-QNHB Model Only)

Vibration        50 Hz, 98 m/s2

resistance                                                                 Maximum          100 VAC

Weight           E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g            heater current

Accessories      Armatures (2), plugs (2)                                  Input current    ±5%FS ±1 digit max.

(E54-CT3 only)                                                             indication

                                                                           accuracy

                                                                           Heater           0.1 to 99.9 A (in units of 0.1 A)

                                                                           burnout alarm    0.0 A: Heater burnout alarm output turns OFF.

                                                                           setting range    100.0 A: Heater burnout alarm output turns ON.

                                                                                            Min. detection ON time: 100 ms (See note 1.)

                                                                           SSR failure      0.1 to 99.9 A (in units of 0.1 A)

                                                                           alarm setting    0.0 A: SSR failure alarm output turns ON.

                                                                           range            100.0 A: SSR alarm output turns OFF.

                                                                                            Min. detection OFF time: 100 ms (See note 2.)

                                                                           Heater           0.1 to 99.9 A (in units of 0.1 A)

                                                                           overcurrent      0.0 A: Heater overcurrent alarm output turns ON.

                                                                           alarm setting    100.0 A: Heater overcurrent alarm output turns OFF.

                                                                           range            Min. detection ON time: 100 ms (See note 1.)

                                                                           Note: 1.         When the control output ON time is less than 100 ms, heater

                                                                                            burnout detection, heater overcurrent detection, and heater

                                                                                            current measurement are not performed.

                                                                                        2.  When the control output OFF time is less than 100 ms, SSR

                                                                                            failure alarm and leakage current measurement are not

                                                                                            performed.

4               Modular Temperature Controller EJ1
■ Input Ranges

Sensor inputs are fully universal. Therefore, platinum resistance                         thermometer,      thermocouple,      infrared    thermosensor,    and   analog    input   can  be

selected.

Inputs can be set for each channel using universal inputs.

    Input type        Platinum resistance

                            thermometer

      Name               Pt100              JPt100

Tem-        2300

pera-       1800

ture

range       1700

(°C)        1600

            1500

            1400

            1300

            1200

            1100

            1000

            900    850

            800

            700

            600

            500             500.0           500.0

            400

            300

            200

            100                    100.0            100.0

                0

         −100.0                    0.0              0.0

         −200.0    −200  −199.9             −199.9

Setting number     0        1      2        3          4

    Input type                                                       Thermocouple                                                 ES1B Infrared             Analog input            Thermo-

                                                                                                                               Thermosensor                                         couple

      Name               K               J               T        E    L           U      N     R     S     B     W     PL     10     60   115  140   4 to  0 to  1 to  0 to  0 to       K

                                                                                                                           II  to     to   to    to   20    20    5V    5V    10 V

                                                                                                                               70     120  165  260   mA    mA

                                                                                                                               °C     °C   °C    °C

Tem-        2300                                                                                                  2300

pera-       1800                                                                                            1800

ture                                                                                            1700  1700

range       1700

(°C)        1600

            1500

            1400

            1300   1300                                                                   1300                          1300

            1200

            1100                                                                                                                                      Any of the following

            1000                                                                                                                                      ranges, by scaling:

            900                    850                                 850                                                                            −1999 to 9999                 −199.9

            800                                                                                                                                       −199.9 to 999.9               to 999.9

            700                                                                                                                                       −19.99 to 99.99

            600                                                   600                                                                                 −1.999 to 9.999

            500          500.0

            400                           400.0     400   400.0              400   400.0

            300                                                                                                                                  260

            200                                                                                                                       120  165

            100                                                                                                                90

                0                                                                                           100

           −100.0                                                 0                             0     0           0        0   0      0    0     0

           −200.0        −20.0     −100   −20.0                        −100

                   −200                            −200   −199.9             −200  −199.9 −200

Setting  number    5        6      7        8       9       10    11   12    13       14  15    16    17    18    19    20     21     22   23    24   25    26    27    28    29    30   V1.2

Applicable standards by input type are as follows:                     W:          W5Re/W26Re, ASTM E988-1990                                        Shaded ranges indicate   default settings.

K, J, T, E, N, R, S, B: JIS C1602-1995, IEC584-1                       PL II:      According to Platinel II Electromotive      Force

L:                       Fe-CuNi, DIN 43710-1985                                   Table by Engelhard Corp.

U:                       Cu-CuNi, DIN 43710-1985                       JPt100:     JIS C 1604-1989, JIS C 1606-1989

                                                                       Pt100:      JIS C 1604-1997 IEC 751

                                                                                                                  Modular Temperature Controller EJ1                                           5
              HFU Unit/EJ1N-HFU@-NFL@

■ Ratings

Power supply voltage                                     24 VDC

Operating voltage range                                  85% to 110% of rated voltage

Power consumption                                        2 W max. (at maximum load)

Auxiliary outputs       Outputs                          4

(See note.)             Transistor outputs               Max. operating voltage: 30 VDC, Max. load current: 50 mA

Event inputs            Inputs                           4

                        Contact inputs                   ON: 1 kΩ max., OFF: 100 kΩ min.

                        Transistor inputs                ON: residual voltage of 1.5 max., OFF: leakage current of 0.1    mA  max.

                                                         Outflow current: Approx. 4 mA (per contact)

Programless             Downloading                      Number of parameters that can be set: 1200    V1.2

connection              (EJ1 reads data from a PLC)

                        Uploading                        Number of parameters that can be set: 1200    V1.2

                        (EJ1 writes data to a PLC)

                        Applicable PLCs                  OMRON: SYSMAC CS/CJ/CP Series

                                                         Mitsubishi Electric: MELSEC-An/AnS/FX3UC Series     V1.1

                                                         Mitsubishi Electric: MELSEC-Q/QnA/QnAS Series

Ambient temperature range                                Operating:  −10°C to 55°C

                                                         Storage:    −25°C to 65°C (with no icing or condensation)

Ambient humidity range                                   Operating: 25% to 85% (with no condensation)

Note:  Auxiliary outputs can be allocated using digital  output allocations.

■ Characteristics

Insulation resistance                                    20 MΩ min. (at 500 VDC)

Dielectric strength                                      600 VAC, 50/60 Hz for 1 min between current-carrying terminals of different  polarity

Vibration resistance                                     10 to 55 Hz, 20 m/s2 for 2 hours each in X, Y, and Z directions

Shock resistance                                         150 m/s2, 3 times each in 6 directions

Weight                                                   160 g

Degree of protection                                     Rear case: IP20, Terminal section: IP00

Memory protection                                        EEPROM (non-volatile memory) (number of writes: 100,000)

Standards               Approved standards               UL61010C-1, CSA C22.2 No.1010-1

                        Conformed standards              EN61010-1 (IEC61010-1): Pollution level 2, overvoltage category II

EMC Directive                                            Refer to page 3.

■ Communications Characteristics: Port C

Transmission path connection                             RS-485/RS-422: Multi-point, RS-232C: Point-to-point (See note 1.)

Communications method                                    RS-485/RS-422 (two-wire, half duplex), RS-232C

Synchronization method                                   Start-stop synchronization

Communications protocol                                  •  OMRON PLC protocol (Connectable PLCs: SYSMAC CS/CJ/CP Series)

                                                         •  AnA/AnU CPU common commands (Connectable PLCs: MELSEC-An/AnS/FX3UC Series)          V1.1

                                                         •  MC protocol (form 5) (Connectable PLCs: MELSEC-Q/QnA/QnAS Series)

Baud rate                                                9.6, 19.2, 38.4, 57.6, or 115.2 kbps

Transmission code                                        Binary

Data bit length                                          8 bits

Stop bit length                                          1 bit

Error detection                                          Depends on protocol selected for the programless communications protocol.

Flow control                                             None

Interface                                                RS-485, RS-422, RS-232C (See note 1.)

Retry function                                           Available

Communications response wait time                        0 to 99 ms (default: 5 ms) V1.1

Number of Basic Units that can be connected         in   32 Units (model numbers with TC4:128 channels max., model numbers with TC2:64 channels max.)

parallel (See note 2.)

Number of HFUs that can be connected        V1.1         • SYSMAC CS/CJ/CP-series PLCs: 8 (EJ1-HFU@-NFLK)

                                                         • MELEC Q/QnA/QnAS-series PLCs: 8 (EJ1-HFU@-NFL2)

Note:  1.  The communications method can be switched between RS-485 and RS-232C. A separate model must be used for RS-422 communications.

       2.  For the number of Units that can be connected, refer to Connection Precautions on page 11.

6                Modular Temperature Controller EJ1
                HFU Unit/EJ1N-HFUB-DRT

■ Ratings

Power supply voltage     DeviceNet power supply  24 VDC (for internal circuits)

                         EDU power supply        24 VDC (for RS-485 communications circuits and Temperature Controllers)

Operating voltage range  DeviceNet power supply  11 to 25 VDC

                         EDU power supply        20.4 to 26.4 VDC

Power consumption                                1 W max. (at maximum load)

Main functions                                   Remote I/O communications, explicit message communications, CompoWay/F        command  feed-through

                                                 function, parameter backup function, and configuration registration

Ambient temperature range                        Operating: −10°C to 55°C

                                                 Storage:   −25°C to 65°C (with no icing or condensation)

Ambient humidity range                           Operating: 25% to 85% (with no condensation)

■ Characteristics

Insulation resistance                            20 MΩ min. (at 500 VDC)

Dielectric strength                              600 VAC, 50/60 Hz for 1 min

Vibration resistance                             10 to 55 Hz, 10 m/s2 for 2 hours each in X, Y, and Z directions

Shock resistance                                 150m/s2 max. 3 times each in 3 axes, 6 directions

Weight                                           70 g max.

Degree of protection                             IP20

Memory protection                                EEPROM, 100,000 write operations (backup data)

Standards              Approved standards        UL61010-1, CSA C22.2 No.1010-1

                       Conformed standards       EN61010-1 (IEC61010-1): Pollution level 2, overvoltage category          II

EMC Directive                                    Refer to page 3.

■ Communications Characteristics

Communications protocol                          Conforms to DeviceNet.

Communications           Remote I/O              Master-slave connections (polling, COS, or cyclic)

functions                communications          Conforms to DeviceNet specifications.

                         I/O allocation          Input and output data can be allocated freely by user with the Configurator.

                                                 Allocations can be made to DeviceNet parameters or Temperature Controller parameters.

                                                 Two blocks for IN Area, up to 100 words

                                                 One block for OUT Area, up to 100 words (The first word is always allocated to the OUT Enable Bit.)

                         Message communications  Explicit message communications

                                                 CompoWay/F communications commands can be sent (commands are sent in explicit message format).

Connection format                                Combination of multidrop and T-branch connections (for trunk and drop lines)

Baud rate                                        DeviceNet: 500, 250, or 125 kbps, or automatic detection of master baud rate

Communications media                             Special 5-wire cable (2 signal lines, 2 power lines, and 1 shield line)

Communications distance

                                                       Baud rate                 Network length      Drop line length          Total drop line length

                                                       500 kbps           100 m max. (100 m max.)            6 m max.          39 m max.

                                                       250 kbps           250 m max. (100 m max.)            6 m max.          78 m max.

                                                       125 kbps           500 m max. (100 m max.)            6 m max.          156 m max.

                                                 The values in parentheses apply when Thin Cables are used.

Communications power supply                      11 to 25 VDC

Maximum number of nodes that can be connected    64 (includes Configurator when used.)

Maximum number of slaves that can be connected   63

Error control                                    CRC error detection

DeviceNet power supply                           Power supplied from DeviceNet communications connector

Applicable Temperature Controllers               EJ1 Series (excluding the EJ1G)

                                                 TC4: EJ1N-TC4A-QQ and EJ1N-TC4B-QQ

                                                 TC2: EJ1N-TC2A-QNHB, EJ1N-TC2B-QNHB, EJ1N-TC2A-CNB, and EJ1N-TC2B-CNB

Maximum number of Temperature Controllers that   16 Units (model numbers with TC4: 64 channels max., model numbers with TC2: 32 channels max.)

can be connected (See note.)

Note: For the number of Units that can be connected, refer to Connection Precautions on page 11.

                                                                                  Modular Temperature Controller EJ1                                   7
                  End Unit/EJ1C-EDU

■ Ratings

Power supply voltage                                24 VDC

Operating voltage range                             85% to 110% of rated voltage

Auxiliary output  Outputs                           2

(See note.)       Transistor outputs                Max. operating voltage: 30 VDC, Max. load current: 50 mA

Ambient temperature range                           Operating: −10°C to 55°C

                                                    Storage:   −25°C to 65°C (with no icing or condensation)

Ambient humidity range                              Operating: 25% to 85% (with no condensation)

Note: Auxiliary output can be allocated using  the  bus output allocation for each Basic Unit.

■ Characteristics

Insulation resistance                               20 MΩ min. (at 500 VDC)

Dielectric strength                                 600 VAC, 50/60 Hz for 1 min between current-carrying terminals of   different  polarity

Vibration resistance                                10 to 55 Hz, 20 m/s2 for 2 hours each in X, Y, and Z directions

Shock resistance                                    150 m/s2, 3 times each in 6 directions

Weight                                              70 g

Degree of protection                                End Unit case: IP20, Terminal section: IP00

Standards         Approved standards                UL61010C-1, CSA C22.2 No.1010-1

                  Conformed standards               EN61010-1 (IEC61010-1): Pollution level 2, overvoltage category II

EMC Directive                                       Same as for the Basic Unit. Refer to page 3.

■ Communications

Port B (See note 1.)                                Basic Unit Communications (Refer to Communications Specifications on page 4.)

Port A                                              Basic Unit Communications (Refer to Communications Specifications on page 4.)

Port A connector (See note 2.)                      E58-CIFQ1

Note: 1.  Port B communications for the End Unit cannot be used when port C communications for the HFU is used.

   2.     Port A connector communications and port A terminal communications cannot be used at the same time.

8            Modular Temperature Controller EJ1
Unit Configuration Example

■ Minimal Configuration

Small Systems with 2 Channels or 4 Channels                                                                                                                                                                                                                                                               Communicating          with   the   Host

Device via RS-485 (CompoWay/F Protocol)

• Alarms can be allocated to the auxiliary output for the End Unit.

• G3ZA/G3PW outputs can be used.

EJ1N-TC4

                    or

EJ1N-TC2                                                         EJ1C-EDU

PWR                          COM1              Port A (connector): USB connection can be made                                                                                                                                                                         CX-Thermo for setting

RUN                 EJ1-TC4  COM2

ERR                          COM3

ALM

     BCDE    F 012                             with the E58-CIFQ1 (sold separately).
     789A
         3456
SW1

     ON

     1

     2

     34

     5                                                                                                                                                                                                                                                         PC

     6                                         Port B: RS-485 (CompoWay/F)

     7

     8

SW2                                                                                                                                                                                                                                                            Host devices

                                                                                                                                                                                                                                                          PLC         PT             PC

■ Multiple Units without an EJ1N-HFU

Building Systems Communicating with the Host Device, such                                                                                                                                                                                                                                                                        as  a  PLC,  PT, or

Computer, via RS-485 (CompoWay/F Protocol)

• The 2 auxiliary alarm outputs provided on the End Unit can be used for integrated alarm systems.

• G3ZA/G3PW outputs can be used.

• Distributed placement is possible by using multiple EJ1C-EDU End Units.

                                                                                            EJ1N-TC4

                                                                                            or

                                                                                            EJ1N-TC2                                                                                                                      EJ1C-EDU

                                                                      PWR                                  COM1  PWR                                           COM1      PWR                                  COM1                       Port A (connector): USB connection can be                        CX-Thermo for setting

                                                                      RUN                   EJ1-TC4        COM2  RUN                               EJ1-TC4     COM2      RUN                   EJ1-TC4        COM2

                                                                      ERR                                  COM3  ERR                                           COM3      ERR                                  COM3

                                                                      ALM                                        ALM                                                     ALM

                                                                           89ABCDEF                                     89ABCDEF                                              89ABCDEF                                                   made with the E58-CIFQ1 (sold separately).

                                                                                34567  012                                   34567  012                                            34567  012

                                                                      SW1                                        SW1                                                     SW1

                                                                           ON                                             ON                                                      ON

                                                                           1                                            1                                                     1

                                                                           2                                            2                                                     2

                                                                           3                                            3                                                     3

                                                                           4                                            4                                                     4

                                                                           5                                            5                                                     5                                                                                                                   PC

                                                                           6                                            6                                                     6                                                          Port B: RS-485 (CompoWay/F)

                                                                           7                                            7                                                     7

                                                                           8                                            8                                                     8

                                                                      SW2                                        SW2                                                     SW2

                                                                                                                                                                                                                                                                                         Host devices

G3ZA                                                                                                                                                                                                                                     G3ZA

connection                                                                                                                                    G3ZA                                                                                       connection

port                                                                                                                                          connection                                                                                 port
                                                                                                                                              port

                                   READY                                                                         READY                                                                                             READY                                                  PLC                         PT  PC

                                   SD/RD                                                                         SD/RD                                                                                             SD/RD

                                          SW1                                                                                            SW1                                                                                 SW1

                                   OCC    SW2                                                                    OCC                     SW2                                                                       OCC       SW2

                                   ERROR                                                                         ERROR                                                                                             ERROR

                                   G3ZA                                                                          G3ZA                                                                                              G3ZA

■ Multiple Units with an EJ1N-HFU

Using the EJ1N-HFU@-NFL@ to Build a System Communicating                                                                                                                                                                                                                                                                         1:1    with  a PLC

Using Programless Communications

• The 2 auxiliary outputs provided on the End Unit can be used.

• The 4 event inputs and 4 auxiliary outputs of the HFU can also be used.

• G3ZA/G3PW outputs can be used.

• Distributed placement is possible by using multiple EJ1C-EDU End Units

                                                                           RS-232C/RS-485

                                                                                                                 EJ1N-TC4                                                                                                                              PLC

                                                                                                                                                     or

                                   EJ1N-HFU                                                                      EJ1N-TC2                                                                                                 EJ1C-EDU

                                          PWR                                               PWR                                               PWR                                              PWR                                            Port A (connector): USB connection can be made              CX-Thermo for setting

                                                                                  COM1                                         COM1                                                   COM1                                   COM1

                                          RUN                    EJ1-HFU          COM2      RUN                  EJ1-TC4       COM2           RUN                        EJ1-TC4      COM2     RUN                  EJ1-TC4  COM2             with the E58-CIFQ1 (sold separately).

                                          ERR                                     COM3      ERR                                COM3           ERR                                     COM3     ERR                           COM3

                                          ALM                                               ALM                                               ALM                                              ALM

                                                    BCDE  F 012                                  BCDE    F 012                                       BCDE    F 012                                  BCDE    F 012
                                               789A                                              789A                                                789A                                           789A
                                                      3456                                           3456                                                3456                                           3456
                                          SW1                                               SW1                                               SW1                                              SW1

                                                    ON                                           ON                                                  ON                                             ON

                                               1                                                 1                                                   1                                              1

                                               2                                                 2                                                   2                                              2

                                               3                                                 3                                                   3                                              3

                                               4                                                 4                                                   4                                              4

                                               5                                                 5                                                   5                                              5                                                                                                 PC

                                               6                                                 6                                                   6                                              6                                          Port B

                                               7                                                 7                                                   7                                              7

                                               8                                                 8                                                   8                                              8                                                  Port B is used for distributed placement.

                                          SW2                                               SW2                                               SW2                                              SW2

                    Port C

G3ZA                                                                                                                                                                     G3ZA                                                                 G3ZA

connection                                                                                                                                                               connecti-                                                            connection

port                                                                                                                                                                     on port                                                              port

                                               READY                                                                                          READY                                                                               READY

                                               SD/RD                                                                                          SD/RD                                                                               SD/RD

                                                                 SW1                                                                                                SW1                                                                  SW1

                                               OCC               SW2                                                                          OCC                   SW2                                                           OCC    SW2

                                               ERROR                                                                                          ERROR                                                                               ERROR

                                          G3ZA                                                                                                G3ZA                                                                                       G3ZA

                                                                                                                                                                                                                                                                                                          Modular Temperature Controller EJ1          9
■ Multiple Units with an EJ1N-HFU

Using the EJ1N-HFU@-NFL@ to Build Systems                                                                                                                                                                                                            Communicating                    1:1  with              a    PLC

Using Programless Communications V1.1

• Up to eight HFUs can be connected to one port on a PLC.

• G3ZA/G3PW outputs can be used.

• Distributed placement is possible by using multiple EJ1C-EDU End Units.

• To connect more than one HFU, specific PLC and EJ1 models must be used.

Refer to Connecting EJ1 Controllers 1:N to a PLC on page 13.

    SYSMAC (OMRON PLC) RS-485

    MELSEC (Mitsubishi Electric PLC) RS-422

                                                                                  EJ1N-TC4                                                                                                                                    PLC

             EJ1N-HFU                                                             or                                                                                                                                                                                                  CX-Thermo for setting

                                                                                  EJ1N-TC2                                                                                        EJ1C-EDU

             PWR                           COM1       PWR                                 COM1     PWR                                     COM1      PWR                                     COM1

             RUN                  EJ1-HFU  COM2       RUN                    EJ1-TC4      COM2     RUN                     EJ1-TC4         COM2      RUN                     EJ1-TC4         COM2

             ERR                           COM3       ERR                                 COM3     ERR                                     COM3      ERR                                     COM3                     Port A (connector): USB connection can be made with the

             ALM                                      ALM                                          ALM                                               ALM

                  89AB  CDE                                89AB  CDE                                    89AB  CDE                                         89AB  CDE
                        F 012                                         F 012                                   F 012                                             F 012
                  34567                                    34567                                        34567                                             34567                                                       E58-CIFQ1 (sold separately).
             SW1                                      SW1                                          SW1                                               SW1

                  ON                                       ON                                           ON                                                ON

                  1                                        1                                            1                                                 1

                  2                                        2                                            2                                                 2

                  3                                        3                                            3                                                 3

                  4                                        4                                            4                                                 4

                  5                                        5                                            5                                                 5                                                                                                                           PC

                  6                                        6                                            6                                                 6

                  7                                        7                                            7                                                 7

                  8                                        8                                            8                                                 8                                                           Port B

             SW2                                      SW2                                          SW2                                               SW2

                                                                                                                                                                                                                                    Port B is used for distributed placement.

    Port  C

                                                                                                                     Up to eight HFUs can be                                                                          connected.

                                                                                  EJ1N-TC4

             EJ1N-HFU                                                             or                                                                                                  EJ1C-EDU

                                                                                  EJ1N-TC2

             PWR                           COM1       PWR                                 COM1     PWR                                     COM1      PWR                                     COM1

             RUN                  EJ1-HFU  COM2       RUN                    EJ1-TC4      COM2     RUN                     EJ1-TC4         COM2      RUN                     EJ1-TC4         COM2

             ERR                           COM3       ERR                                 COM3     ERR                                     COM3      ERR                                     COM3

             ALM                                      ALM                                          ALM                                               ALM

                  89AB  CDE                                89AB  CDE                                    89AB  CDE                                         89AB  CDE
                        F 012                                         F 012                                   F 012                                             F 012
                  34567                                    34567                                        34567                                             34567
             SW1                                      SW1                                          SW1                                               SW1

                  ON                                       ON                                           ON                                                ON

                  1                                        1                                            1                                                 1

                  2                                        2                                            2                                                 2

                  3                                        3                                            3                                                 3

                  4                                        4                                            4                                                 4

                  5                                        5                                            5                                                 5

                  6                                        6                                            6                                                 6

                  7                                        7                                            7                                                 7

                  8                                        8                                            8                                                 8

             SW2                                      SW2                                          SW2                                               SW2

    Port  C

    Note: Set the EJ1N-TC to a communications unit number that is not being used by the EJ1N-HFU.

■ Multiple Units with an EJ1N-HFU

Using the EJ1N-HFUB-DRT to Build a System Communicating with                                                                                                                                                                                                                               a                 PLC

• Up to 63 DeviceNet slaves can be connected to the DeviceNet Masters in one PLC.

• G3ZA/G3PW outputs can be used.

• Distributed placement is possible by using multiple EJ1C-EDU End Units.

                                                                                                                                                                                                                                                         DeviceNet Configurator

             DeviceNet                                                                                                                                                                                                        Serial communications      or CX-Integrator

                                                                                                                                              PLC

                                                                                                                   EJ1N-TC4                                                                                                                          PC

                                  EJ1N-HFU                                                                         or

                                                                                                                   EJ1N-TC2                                                                                     EJ1C-EDU

                                                                      EJ1N   PWR                                     COM1  PWR                                         COM1  PWR                                COM1

                                                 10                          RUN                   EJ1-TC4           COM2  RUN                            EJ1-TC4      COM2  RUN                       EJ1-TC4  COM2

                                                                      DRT    ERR                                     COM3  ERR                                         COM3  ERR                                COM3

                                           NODE                              ALM                                           ALM                                               ALM

                                                 ADR                                   DEF                                               DEF                                               DEF

                                                 1                    MS          89ABC       012                                   89ABC       012                                   89ABC       012

                                                                      NS     SW1       34567                               SW1           34567                               SW1           34567

                                           MAX                        TS
                                           No.

                                                           1 23 45 6  COPY

                                                                      EDS

                                                                      UP/DN           ON                                            ON                                                ON

                                                                      TC2/4       1                                                 1                                                 1

                                                                      MODE        2                                                 2                                                 2

                                                           NO                     3                                                 3                                                 3                                       Port  B

                                                                                  4                                                 4                                                 4

                                                                                  5                                                 5                                                 5

                                                                                  6                                                 6                                                 6                                                    Port B is used for distributed placement.

                                                                                  7                                                 7                                                 7

                                                                                  8                                                 8                                                 8

                                                                             SW2                                           SW2                                               SW2

             Port C

                                                                                                                                                                Up           to                    63 nodes (including              other  slaves)

                                                                                                                   EJ1N-TC4

                                  EJ1N-HFU                                                                         or

                                                                                                                   EJ1N-TC2                                                                                     EJ1C-EDU

                                                                      EJ1N   PWR                                     COM1  PWR                                         COM1  PWR                                COM1

                                                 10                          RUN                   EJ1-TC4           COM2  RUN                            EJ1-TC4      COM2  RUN                       EJ1-TC4  COM2

                                                                      DRT    ERR                                     COM3  ERR                                         COM3  ERR                                COM3

                                           NODE                              ALM                                           ALM                                               ALM

                                                 ADR                                   DEF                                               DEF                                               DEF

                                                 1                    MS          89ABC       012                                   89ABC       012                                   89ABC       012

                                                                      NS     SW1       34567                               SW1           34567                               SW1           34567

                                           MAX                        TS
                                           No.

                                                           1 23 45 6  COPY

                                                                      EDS

                                                                      UP/DN           ON                                            ON                                                ON

                                                                      TC2/4       1                                                 1                                                 1

                                                                      MODE        2                                                 2                                                 2

                                                           NO                     3                                                 3                                                 3

                                                                                  4                                                 4                                                 4

                                                                                  5                                                 5                                                 5

                                                                                  6                                                 6                                                 6

                                                                                  7                                                 7                                                 7

                                                                                  8                                                 8                                                 8

                                                                             SW2                                           SW2                                               SW2

10  Modular Temperature Controller EJ1
■ Connection Precautions

Communications Unit Number Setting                                                                                                                                                                                                                     Restrictions for Basic Units

• Communications unit numbers 0 to 63 can be assigned to Basic                                                                                                                                                                                         • When the system is configured of only Basic Units (EJ1N-TC4/

Units and HFUs.                                                                                                                                                                                                                                             TC2), up to 64 Units can be connected.

                                                                                                                                                                                                                                                       • Distributed placement is possible by using End Units (EJ1C-EDU).

Restrictions on the Number of Units                                                                                                                                                                                                                    • Up to 16 Units can be connected side by side. The End Unit is not

                                                                                                                                                                                                                                                            included in the 16 Units.

That Can Be Connected                                                                                                                                                                                                                                                                                                                                                                                                                                                                                    To the host device

                                                                                                                                                                                                                                                       PWR                              COM1  PWR                           COM1  PWR                             COM1                        PWR                            COM1  PWR                          COM1  PWR                          COM1

                                                                                                                                                                                                                                                       RUN                     EJ1-TC4  COM2  RUN                  EJ1-TC4  COM2  RUN                 EJ1-TC4     COM2                        RUN                   EJ1-TC4  COM2  RUN                 EJ1-TC4  COM2  RUN                 EJ1-TC4  COM2

                                                                                                                                                                                                                                                       ERR                              COM3  ERR                           COM3  ERR                             COM3                        ERR                            COM3  ERR                          COM3  ERR                          COM3

Restrictions for HFUs                                                                                                                                                                                                                                  ALM                                    ALM                                 ALM                                                         ALM                                  ALM                                ALM

                                                                                                                                                                                                                                                            BCDE    F 012                          BCDE    F 012                       BCDE    F 012                                                 BCDE    F 012                      BCDE    F 012                      BCDE    F 012
                                                                                                                                                                                                                                                            789A                                   789A                                789A                                                          789A                               789A                               789A
                                                                                                                                                                                                                                                                3456                                   3456                                3456                                                          3456                               3456                               3456
                                                                                                                                                                                                                                                       SW1                                    SW1                                 SW1                                                         SW1                                  SW1                                SW1

• One EJ1N-HFU can manage up to 32 Basic Units (EJ1N-TC4/                                                                                                                                                                                                   ON                                     ON                                  ON                                                            ON                                 ON                                 ON                            Port B

                                                                                                                                                                                                                                                            1                                      1                                   1                                                             1                                  1                                  1

                                                                                                                                                                                                                                                            2                                      2                                   2                                                             2                                  2                                  2

TC2).                                                                                                                                                                                                                                                       3                                      3                                   3                                                             3                                  3                                  3

                                                                                                                                                                                                                                                            4                                      4                                   4                                                             4                                  4                                  4

                                                                                                                                                                                                                                                            5                                      5                                   5                                                             5                                  5                                  5

                                                                                                                                                                                                                                                            6                                      6                                   6                                                             6                                  6                                  6

                                                                                                                                                                                                                                                            7                                      7                                   7                                                             7                                  7                                  7

                                                                                                                                                                                                                                                            8                                      8                                   8                                                             8                                  8                                  8

• Up to 16 Units can be connected side by side including the EJ1N-                                                                                                                                                                                     SW2                                    SW2                                 SW2                                                         SW2                                  SW2                                SW2

HFU. The End Unit is not included in the 16 Units.

                                                                                       One HFU can manage up to 16 Basic Units

                                                                                       (when using the EJ1N-TC4: 4 channels × 16                                                                                  Units               =  64 channels)

To  the  host  device                                                                                                                                                                                                                                                                                                                            EJ1N-TC4                            or    EJ1N-TC2                                                                   EJ1C-EDU

                                     PWR                          COM1  PWR                          COM1  PWR                          COM1               PWR                          COM1  PWR                          COM1

                                     RUN                 EJ1-HFU  COM2  RUN                 EJ1-TC4  COM2  RUN                 EJ1-TC4  COM2               RUN                 EJ1-TC4  COM2  RUN                 EJ1-TC4  COM2

                                     ERR                          COM3  ERR                          COM3  ERR                          COM3               ERR                          COM3  ERR                          COM3

                                     ALM                                ALM                                ALM                                             ALM                                ALM

                                          BCDE    F 012                      BCDE    F 012                      BCDE    F 012                                   BCDE    F 012                      BCDE    F 012
                                          789A                               789A                               789A                                            789A                               789A
                                              3456                               3456                               3456                                            3456                               3456
                                     SW1                                SW1                                SW1                                             SW1                                SW1

                                                                                                                                                                                                                                                       PWR                              COM1  PWR                           COM1  PWR                             COM1                        PWR                            COM1  PWR                          COM1  PWR                          COM1

                                                                                                                                                                                                                                                       RUN                     EJ1-TC4  COM2  RUN                  EJ1-TC4  COM2  RUN                 EJ1-TC4     COM2                        RUN                   EJ1-TC4  COM2  RUN                 EJ1-TC4  COM2  RUN                 EJ1-TC4  COM2

                                                                                                                                                                                                                                                       ERR                              COM3  ERR                           COM3  ERR                             COM3                        ERR                            COM3  ERR                          COM3  ERR                          COM3

                                                                                                                                                                                                                                                       ALM                                    ALM                                 ALM                                                         ALM                                  ALM                                ALM

                                          ON                                 ON                                 ON                                              ON                                 ON                                    Port B             BCDE    F 012                          BCDE    F 012                       BCDE    F 012                                                 BCDE    F 012                      BCDE    F 012                      BCDE    F 012
                                                                                                                                                                                                                                                            789A                                   789A                                789A                                                          789A                               789A                               789A
                                          1                                  1                                  1                                               1                                  1                                                            3456                                   3456                                3456                                                          3456                               3456                               3456

                                          2                                  2                                  2                                               2                                  2                                                   SW1                                    SW1                                 SW1                                                         SW1                                  SW1                                SW1

                                          3                                  3                                  3                                               3                                  3

                                          4                                  4                                  4                                               4                                  4

    Port C                                5                                  5                                  5                                               5                                  5

                                          6                                  6                                  6                                               6                                  6

                                          7                                  7                                  7                                               7                                  7

                                          8                                  8                                  8                                               8                                  8                                                                                                                                                                                                                                                                                                     Port B

                                     SW2                                SW2                                SW2                                             SW2                                SW2                                                           ON                                     ON                                  ON                                                            ON                                 ON                                 ON

                                                                                                                                                                                                                                                            1                                      1                                   1                                                             1                                  1                                  1

                                                                                                                                                                                                                                                            2                                      2                                   2                                                             2                                  2                                  2

                                                                                                                                                                                                                                                            3                                      3                                   3                                                             3                                  3                                  3

                                                                                                                                                                                                                                                            4                                      4                                   4                                                             4                                  4                                  4

                                                                                                                                                                                                                                                            5                                      5                                   5                                                             5                                  5                                  5

                                                                                                                                                                                                                                                            6                                      6                                   6                                                             6                                  6                                  6

                                                                                                                                                                                                                                                            7                                      7                                   7                                                             7                                  7                                  7

                                                                                                                                                                                                                                                            8                                      8                                   8                                                             8                                  8                                  8

                                                                                                                                                                                                                                                       SW2                                    SW2                                 SW2                                                         SW2                                  SW2                                SW2

                                                                                                                                              EJ1N-TC4

                                          EJ1N-HFU                                                                                                   or                        EJ1C-EDU

                                                                                                                                              EJ1N-TC2

                                          Up to 16 Units can be connected side by side.                                                                                                                                                                                                                                                          EJ1N-TC4 or EJ1N-TC2                                                                                                 EJ1C-EDU

                                          Note: End Units are not included in the number

                                                                  of Units that can be connected.                                                                                                                                                                          Up to 64 Basic Units can be connected using distributed placement.

                                                                                                                                                                                              PWR                          COM1

                                                                                                                                                                                              RUN                 EJ1-TC4  COM2                                            Using EJ1@-TC4 models: 4 channels × 64 Units = 256 channels

                                                                                                                                                                                              ERR                          COM3

                                                                                                                                                                                              ALM

                                                                                                                                                                                                   BCDE    F 012                                                           Using EJ1@-TC2 models: 2 channels × 64 Units = 128 channels
                                                                                                                                                                                                   789A
                                                                                                                                                                                                       3456
                                                                                                                                                                                              SW1

                                                                                                                                                                                                                                                                           Note: End Units are not included in the number of Units that can be connected.

                                                                                                                                                                                                   ON                                    Port B

                                                                                                                                                                                                   1

                                                                                                                                                                                                   2

                                                                                                                                                                                                   3                                                   Wiring for Distributed Placement

                                                                                                                                                                                                   4

                                                                                                                                                                                                   5

                                                                                                                                                                                                   6

                                                                                                                                                                                                   7

                                                                                                                                                                                                   8

                                                                                                                                                                                              SW2

                                                                                                                                                                                                                                                                                                                            Group A

                                                                                                                                                                                                                                                            PWR                                              COM1                                     PWR                            COM1

                                                                                                                                                                                                                                                            RUN                         EJ1-TC4              COM2                                     RUN                   EJ1-TC4  COM2

                                                                                                                                                                                                                                                            ERR                                              COM3                                     ERR                            COM3                                                                                                                        Host

                                                                                                                                                                                                                                                            ALM                                                                                       ALM

                                                                                                                                                                                                                                                                           DEF                                                                                 DEF                                             Port A                                                                                            devices
                                                                                                                                                                                                                                                                      89ABC                                                                                89ABC
                                                                                                                                                                EJ1N-TC4 or                                                                                                34567  012                                                                           34567  012

                                                                                                                                                                                                                                      EJ1C-EDU              SW1                                                                                       SW1                                  1

                                                                                                                                                                          EJ1N-TC2                                                                                                                                                                                                         2                                                                                                             FG

Restrictions When Connecting with                                                                                                                                                                                                the                                                                                                                                                       3

                                                                                                                                                                                                                                                                           ON                                                                                  ON                          4

                                                                                                                                                                                                                                                                           1                                                                                   1

                                                                                                                                                                                                                                                                           2                                                                                   2

                                                                                                                                                                                                                                                                           3                                                                                   3

G3ZA                                                                                                                                                                                                                                                                       4                                                                                   4                           5

                                                                                                                                                                                                                                                                           5                                                                                   5                                               Port B

                                                                                                                                                                                                                                                                           6                                                                                   6

                                                                                                                                                                                                                                                                           7                                                                                   7                           6

                                                                                                                                                                                                                                                                           8                                                                                   8

• Up to 8 G3ZA Multi-channel Power Controllers can be                                                                                                                                                                            connected       to         SW2                                                                                       SW2                                  7

one Basic Unit (EJ1N-TC4/TC2).                                                                                                                                                                                                                                                                                                                                                             8  24 VDC

                                                                                                                                                                                                                                                                                                                                                                                           9

                                                               EJ1N-TC4 or EJ1N-TC2

                                                                        EJ1C-EDU

               PWR                                       COM1

               RUN                        EJ1-TC4        COM2

               ERR                                       COM3

               ALM

                      BCDE    F 012
                      789A
                          3456
               SW1                                                                                                                                                                                                                                                                                                          Group                              B

                      ON                                                                                                                                                                                                                                    PWR                                              COM1                                     PWR                            COM1

                      1

                      2                                                                                                                                                                                                                                     RUN                         EJ1-TC4              COM2                                     RUN                   EJ1-TC4  COM2

                      3                                                                                                                                                                                                                                     ERR                                              COM3                                     ERR                            COM3

                      4                                                                                                                                                                                                                                     ALM                                                                                       ALM

                      5

                      6                                                                                                                                                                                                                                                    DEF                                                                                 DEF                                             Port A

                      7                                                                                                                                                                                                                                               89ABC       012                                                                      89ABC       012

                      8                                                                                                                                                                                                                                                    34567                                                                                34567                      1

               SW2                                                                                                                                                                                                                                          SW1                                                                                       SW1

                                                                                                                                                                                                                                                                                                                                                                                           2

                                                                                                                                                                                                                                                                                                                                                                                           3                                            RS-485

                                                                                                                                                                                                                                                                           ON                                                                                  ON                          4

                                                                                                                                                                                                                                                                           1                                                                                   1

                                                                                                                                                                                                                                                                           2                                                                                   2

                                                                                                                                                                                                                                                                           3                                                                                   3

                                                                                                                                                                                                                                                                           4                                                                                   4                           5

                                                                                                                                                                                                                                                                           5                                                                                   5                                               Port B

                                                    G3ZA connection port                                                                                                                                                                                                   6                                                                                   6

                                                                                                                                                                                                                                                                           7                                                                                   7                           6

                                                                                                                                                                                                                                                                           8                                                                                   8

                                                                                                                                                                                                                                                            SW2                                                                                       SW2                                  7

                                                                                                                                                                                                                                                                                                                                                                                           8                                                                    RS-485

                                                                                                                                                                                                                                                                                                                                                                                           9  24 VDC

               READY                                                                        READY                                             READY                                                               READY

               SD/RD                                                                        SD/RD                                             SD/RD                                                               SD/RD

                                SW1                                                                  SW1                                             SW1                                                                         SW1

               OCC              SW2                                                         OCC      SW2                                      OCC    SW2                                                          OCC            SW2

               ERROR                                                                        ERROR                                             ERROR                                                               ERROR                                Note: Wire the dotted line when settings for all distributed Units are

                                                                                                                                                                                                                                                                                              being made from one port A connector.

                                                                                                                                                                                                                                                                                              If the dotted lines are not wired, make the settings for group A

                                                                                                                                                                                                                                                                                              using the port A connector for group A and make the settings

                                                                                                                                                     G3ZA                                                                                                                                     for group B using the port A connector for group B.

               Up to 8 G3ZA Power Controllers can be connected to one Basic Unit.

                                                                                                                                                                                                                                                                                        Modular Temperature Controller EJ1                                                                                                                                                                                                11
Restrictions on Unit Placement

Always connect the HFU on the left side of the Basic Unit.                                                                            Do not connect the End    Unit  directly to the HFU.

                                                                                                                                      Always connect a Basic    Unit  to the End Unit.

                               PWR                          COM1  PWR                          COM1

                               RUN                 EJ1-TC4  COM2  RUN                 EJ1-HFU  COM2

                               ERR                          COM3  ERR                          COM3

                               ALM                                ALM

                                    BCDE    F 012                      BCDE    F 012                                                                                  PWR                          COM1
                                    789A                               789A
                                        3456                               3456                                                                                       RUN                 EJ1-HFU  COM2

                               SW1                                SW1                                                                                                 ERR                          COM3

                                                                                                                                                                      ALM

                                                                                                                                                                           BCDE    F 012
                                                                                                                                                                           789A
                                                                                                                                                                               3456
                                                                                                                                                                      SW1

                                    ON                                 ON

                                    1                                  1

                                    2                                  2

                                    3                                  3

                                    4                                  4

                                    5                                  5                                                                                                   ON

                                                                                                                                                                           1

                                    6                                  6                                                                                                   2

                                    7                                  7                                                                                                   3

                                    8                                  8                                                                                                   4

                               SW2                                SW2                                                                                                      5

                                                                                                                                                                           6

                                                                                                                                                                           7

                                                                                                                                                                           8

                                                                                                                                                                      SW2

                          EJ1N-TC4 or                             EJ1N-HFU

                          EJ1N-TC2                                                                                                                              EJ1N-HFU                                 EJ1C-EDU

■ Insulation Blocks

Each EJ1 Unit is electrically insulated for each function block as shown in the following figures.

Functional insulation is applied between the power supply, input, output, and communications terminal sections.

If reinforced double insulation is required, use power supplies that comply with IEC60664 for reinforced double insulation for the EJ1's external

power supply and for power supplies connected to the EJ1.

EJ1N-TC2                                                                                             EJ1N-TC4                                                   EJ1N-HFU@-NFL@

             Input 1                                                                                                Input 1                                                                              Event inputs 1 to 4

             Input 2                                                                                                Input 2                                                      Power                   Transistor outputs 1 to 4

                                                                                                                                                                               supply

    Power    Event inputs 1 and 2, CT1 and 2 (See note.)                                             Power          Input 3                                                                              Communications (Port B, port C)

    supply   Communications (Port A, port B, G3ZA)                                                   supply         Input 4                                                               Functional isolation

             Transistor outputs 3 and 4                                                                             Voltage outputs 1 to 4                      EJ1C-EDU

             Voltage outputs 1 and 2/Current outputs 1 and 2                                                        Communications (Port A, Port B, G3ZA)                                                Transistor outputs 1 and 2

                                                                                                                                                                               Power

    Functional isolation                                                                                        Functional isolation                                       supply                        Communications (Port A, port B)

Note: Not provided on models with current outputs.

                                                                                                                                                                                          Functional isolation

■ Programless Communications

Communications with PLCs from OMRON (SYSMAC CS/CJ/CP Series) and Mitsubishi Electric (MELSEC-Q/QnA/QnAS/An/Ans/FX3UC Series) can

be performed without creating ladder programming.

Using programless communications enables monitoring and changing settings for the EJ1 by simply reading and writing to PLC memory.

The EJ1 automatically performs communications with the PLC, which reduces work hours spent programming for communications from the PLC

to the EJ1.

                                                   PLC                                                                                    EJ1N-HFU                                                                  EJ1N-TC4/TC2

                          Monitor                                      PV                            The read monitor value is                PV                The EJ1N-HFU reads the monitor                                PV

                                                                                                     written to the PLC memory.                                 value for the EJ1N-TC4/TC2.

Monitoring can be                                  Manipulated variable                                                                   Manipulated variable                                                      Manipulated variable

performed for the                                           Status                                                                            Status                                                                          Status

EJ1 and the settings                                                                                 The EJ1N-HFU automatically

can be changed by                                                                                    performs communications

simply reading and        Setting                                      SP                            with the PLC.                            SP                                                                              SP

writing to memory.                                 Alarm value 1                                                                          Alarm value 1                                                             Alarm value 1

                                                   Alarm value 2                                     The EJ1N-HFU reads the value         Alarm value 2         The read setting is written to the                  Alarm value 2

                                                                                                     written to the PLC memory.                                 setting for the EJ1N-TC4/TC2.

Connectable Devices

Connecting an EJ1 Controller 1:1 to a PLC

SYSMAC CS/CJ/CP Series

             Name                                                                                    Model No.                                                  Communications ports

                                                                                                                                              Port 1                                                     Port 2

Serial Communications  Units                       CJ1W-SCU21-V1                                                                 RS-232C                              RS-232C

                                                   CJ1W-SCU31-V1                                                                 RS-422A/485                          RS-422A/485

                                                   CJ1W-SCU41-V1                                                                 RS-422A/485                          RS-232C

                                                   CS1W-SCU21-V1 (See note.)                                                     RS-232C                              RS-232C

                                                   CS1W-SCU31-V1                                                                 RS-422A/485                          RS-422A/485

Serial Communications  Boards                      CS1W-SCB21-V1 (See note.)                                                     RS-232C                              RS-232C

                                                   CS1W-SCB41-V1 (See note.)                                                     RS-232C                              RS-422A/485

CPU Units                                          CJ Series                                                                     ---                                  RS-232C

                                                   CS Series                                                                     ---                                  RS-232C

                                                   CP Series                                                                     RS-232C or RS-422A/485 can be used by adding                            an Option  Board.

Note: Use only products manufactured on or after December 20, 1999.

    For details, refer to the CS/CJ Series, Serial Communications Boards/Units Operation Manual (Cat. No. W336).

12           Modular Temperature Controller EJ1
MELSEC-Q/QnA/QnAS Series

           Name                                    Model    No.                             Communications ports

                                                                                      Channel 1              Channel  2

Q-compatible Serial                QJ71C24N                                         RS-232C             RS-422/485

Communications Unit                QJ71C24

                                   QJ71C24N-R2                                      RS-232C             RS-232C

                                   QJ71C24-R2

                                   QJ71C24N-R4                                      RS-422/485          RS-422/485

QnA-compatible Serial              AJ71QC24N                                        RS-232C             RS-422/485

Communications Unit                AJ71QC24N-R2                                     RS-232C             RS-232C

                                   AJ71QC24N-R4                                     RS-422              RS-422/485

QnAS-compatible Serial             A1SJ71QC24N                                      RS-232C             RS-422/485

Communications Unit                A1SJ71QC24N-R2                                   RS-232C             RS-232C

Note:  1.  Refer to the Mitsubishi Electric PLC documentation for information on MELSEC PLCs.

       2.  Direct connections to the EJ1 are possible only with RS-232C or RS-422.

       3.  More than one EJ1 Controller to one PLC is not possible even with RS-422 communications. Refer to Connecting EJ1 Controllers 1:N to a PLC,

           below, for product combinations that support 1:N connections.

       4.  Connection ability has been verified for the above MELSEC models. Design changes and other factors, however, may prevent normal connection.

           Always confirm operation in advance.

MELSEC-An/AnS Series               V1.1

                     Name                                        Model No.                                   Communications ports

An-compatible Computer Link Unit                 AJ71UC24                                       RS-232C or RS-422/485

AnS-compatible Computer Link Unit                A1SJ71UC24-R2                                  RS-232C

                                                 A1SJ71UC24-R4                                  RS-422/485

                                                 A1SJ71UC24-PRF                                 RS-232C

Note: Use a MELSEC-AnA/AnU CPU.

MELSEC-FX3UC Series                V1.1

                     Name                                        Model No.                                   Communications ports

Communications Adapter                           FX3U-232ADP                                    RS-232C

                                                 FX3U-485ADP                                    RS-485

Function Board                                   FX3U-232-BD                                    RS-232C

                                                 FX3U-485-BD                                    RS-485

Connecting EJ1 Controllers 1:N to a PLC                                 V1.1

The combinations of PLCs and HFUs that can be connected 1:N are listed below.

SYSMAC CS/CJ/CP Series

                     Name                                        Model No.                                   Communications ports

Serial Communications Units                      CJ1W-SCU31-V1                                  Port 1 or 2

                                                 CJ1W-SCU41-V1                                  Port 1

                                                 CS1W-SCU31-V1                                  Port 1 or 2

Serial Communications Board                      CS1W-SCB41-V1 (See note.)                      Port 2

CPU Units                                        CP Series                                      RS-422A/485 can be used by adding an  Option  Board.

EJ1N-HFU                                         EJ1N-HFUA-NFLK                                 Port C

                                                 EJ1N-HFUB-NFLK

Note: Use only products manufactured on or after December 20, 1999.

       For details, refer to the CS/CJ Series, Serial Communications Boards/Units           Operation Manual (Cat. No. W336).

MELSEC-Q/QnA/QnAS Series

                     Name                                                  Model No.

Serial Communications Units                      Channel 2 of QJ71C24N

                                                 QJ71C24N-R4

                                                 Channel 2 of A1SJ71QC24N

                                                 Channel 2 of AJ71QC24N

                                                 AJ71QC24N-R4

EJ1N-HFU                                         EJ1N-HFUA-NFL2

                                                 EJ1N-HFUB-NFL2

Note: Refer to the Mitsubishi Electric PLC documentation for information on MELSEC              PLCs.

                                                                                            Modular Temperature Controller EJ1                          13
Connection

■ External Connection

• Functional insulation is applied between the power supply and the I/O sections. If reinforced insulation is required, connect the input

and output terminals to devices without any exposed current-carrying parts or to devices with reinforced insulation suitable for the

maximum operating voltage of the power supply and I/O sections.

• To comply with the standards for noise terminal voltage for class A in EN 61326, install a noise filter (Densei Lamda MXB-1206-33 or

the equivalent) to the DC power line as close as possible to the Temperature Controller.

• Use an SELV power supply that provides overcurrent protection. An SELV circuit is one separated from the power supply with double

insulation or reinforced insulation, that does exceed an output voltage of 30 V r.m.s. and 42.4 V peak or 60 VDC max. The OMROM

S8VM or S8VS Series is recommended for the power supply.

EJ1N-TC4                                                                                        EJ1N-TC2

                             OUT2                                                               Models with               Models with

                       12 VDC            B1                   OUT4                              linear outputs            pulse outputs

                                                        A1    12 VDC                            OUT2                      OUT2

                             OUT1        B2                                                     4 to 20 mA DC/0 to 20 mA  12 VDC

                                 12 VDC                 A2    OUT3                                                                        B1                   OUT4

                                         B3                   12 VDC                            OUT1                      OUT1                        A1

                                                        A3                                                                                B2

                             A                                                                  4 to 20 mA DC/0 to 20 mA  12 VDC                      A2       OUT3

                                 CH2     B4                             A                                                                 B3

               mA            B                          A4    CH4                                                                                     A3

                                         B5                             B           mA                                    A       CH2     B4

               V             B                          A5                                                      mA                                    A4

                                         B6                             B           V                                     B               B5

                                                        A6                                                      V                                     A5            EV2

                             A   CH1     B7                                                                               B               B6              EV1

               mA                                       A7    CH3       A                                                                             A6

                             B           B8                                         mA                                    A

               V                                        A8              B                                                         CH1     B7                             Not provided

                             B           B9                                         V                           mA                                    A7                 on models

                                                        A9              B                                                 B               B8                   CT2       with linear

                                                                                                                V         B                           A8                 output.

               Analog        Pt  Thermo-                                                                                                  B9              CT1            Provided only

               input                 couple        CN1  G3ZA  connection      port                                                                    A9                 on models

                                                                                                                Analog    Pt      Thermo-                                with pulse

                                                                                                                                                                         output.

                                                                                                                input             couple      CN1    G3ZA connection port

EJ1N-HFU@-NFL@                                                                                  EJ1N-HFUB-DRT

                                                                                                DeviceNet Connector

                                         B1

                                                        A1

                       SUB4              B2                        EV4

                                 SUB3                   A2

                                         B3                   EV3                                                                 V+          Power line

                                                        A3

                                         B4

                                                        A4                                                                        CAN      H

                       SUB2              B5                        EV2                                                                        Communications line, high

                                 SUB1                   A5

                                         B6                   EV1

               RDB (+)           B (+)                  A6                                                                                    Shield

                                         B7                   SD         SDB (+)

               RDA (−)           A (−)                  A7

       Port C                            B8                   RD         SDA (−)                                                  CAN      L  Communications line, low

                                                        A8                              Port C

               Not used          Not used B9                  SG

               RS-422            RS-485                 A9              Not used                                                  V−

                                                        RS-232C          RS-422                                                               Power line

           RS-485 for port C and RS-232C can be switched.

           A separate EJ1 model must be used for

           RS-422 communications.

EJ1C-EDUA                                                                                       EJ1C-EDUC

Model with Screw Terminals                                                                      Model with Connector Terminal                 Block

                                                                                                                Port A connector

                       Port A connector

                                                        These two ports                                                                       These two ports

                             Port A      B (+)          cannot be used at                                       Port A        B (+)           cannot be used at

                                                1       the same time.                                                                 1      the same time.

                                 RS-485                                                                                   RS-485

                                                2                                                                             A (−)    2

                                         A (−)

                                                3                                                                                      3

                                 SUB2                                                                                     SUB2

                                                4                                                                                      4

                                        SUB1

                                                5

                             Port B      B (+)          These terminals are                                                            5

                                 RS-485         6                                                                         SUB1

                                                        used for distributed                                                           6

                                         A (−)  7       placement of Units

                                             +          when an HFU is used.                                    Port B        B (+)           These terminals are

                                        24 VDC  8                                                                                      7

                                                9                                                                         RS-485              used for distributed

                                             −                                                                                A (−)    8      placement of Units

                      Input  power supply                                                                                                     when an HFU is used.

                                                                                                                                  +    9

                                                                                                                          24 VDC

                                                                                                                                  −    10

                                                                                                                Input power supply

Note:  1.  To connect to the G3ZA, separately purchase a G3ZA Connecting Cable (EJ1C-CBLA050) and connect it to the G3ZA connection port (CN1) on the EJ1.

       2.  To connect to a computer using the port A connector, use a separately sold E58-CIFQ1 USB-Serial Conversion Cable. The Temperature Controller can be

           connected to a computer using USB.

       3.  Models with screw-less clamp terminals have terminals A10 and B10, but they are not used. Do not connect anything to them.

14             Modular Temperature Controller EJ1
Nomenclature                                and            Specification Settings

■ Part Names

                                                                       Operation Indicators

                 PWR       1                         COM1  Operation

Operation        RUN       2                EJ1N-TC  COM2              EJ1N-TC2/TC4

                 ERR       3                         COM3  Indicators

Indicators       ALM       4  OUT

PWR 1            OPN          789ABCDEF012                 COM1        Operation             Meaning: When SW2   Meaning: When SW2

RUN 2                           3456                       COM2        Indicators            No. 6 is OFF        No. 6 is ON      V1.2

ERR 3                      SW1                             COM3

ALM  4                                                                 PWR/1    V1.2   Lights when the power     Lit when output 1 is ON.

            SW1                                                        (green)         is ON.

                                                                       RUN/2    V1.2   Lights during operation.  Lit when output 2 is ON.

                              ON                                       (green)

                              1

                              2                                        ERR/3           Flashes or lights when    Lit when output 3 is ON.

                              3                                                 V1.2

            SW2  OUT  OPN     4                                        (red)           an error occurs.

                              5

                           6  6                                        ALM/4           Lights when an alarm is   Lit when output 4 is ON.

                              7                                                 V1.2

                              8                                        (red)           activated.

                      SW2

                                                                       COM 1 (orange)  Flashes during communications via port A on the

                                                                                       End Unit.

                                                                       COM 2 (orange)  Flashes during communications via port B on the

                                                                                       End Unit.

                                                                       COM 3 (orange)  Flashes during communications with the G3ZA.

                                                                       EJ1N-HFU@-NFL@

                                                                       Operation                           Meaning

                                                                       Indicators

                                                                       PWR (green)     Lit while the power is ON. (See note.)

                                                                       RUN (green)     ---

                                                                       ERR (red)       Flashes or lights when an error occurs.

                                                                       ALM (red)       Lights when an alarm is activated.

                                                                       COM 1 (orange)  Flashes during communications via port A on the

                                                                                       End Unit.

                                                                       COM 2 (orange)  Flashes when the EJ1 system is in operation.

                                                                       COM 3 (orange)  Flashes during communications via port C.

                                                                       Note: Some time is required for the indicators to light after the power

                                                                              is turned ON.

                                                                              Modular Temperature Controller EJ1                                15
■ Specification Settings

Switch Operation                                                                      SW2 Settings

• Check that the EJ1 is turned OFF before operating any switch                        EJ1N-TC2/TC4

other than pin 6 of SW2. Settings are read only when power is

turned ON.                                                                               SW2                         Meaning

• Set the switches with a small flat-blade screwdriver. Do not set               the  3        Set to ON when using the Modbus communications

switches midway between settings.                                                        V1.2

• SW1 is set to 1 and SW2 pins are all set to OFF in the default                               protocol for port B.

settings.                                                                                      OFF: The setting for port B communications protocol is

                                                                                                    used.

     SW1           F012              SW2                                                       ON: Modbus is used.

               BCDE    3456                  ON  1  2  34      5   6   7   8          4 to 5   Set the baud rate of port B.

                   789A                                                               V1.2     4 = OFF, 5 = OFF: Use the baud rate parameter setting for

                                                                                                                     port B (default: 9.6 kbps).

Setting the Unit Number                                                                        4 = ON, 5 = OFF: 19.2 kbps

                                                                                               4 = OFF, 5 = ON: 38.4 kbps

SW1 and SW2 are used together to set the unit number to between                                4 = ON, 5 = ON: 115.2 kbps

00 and 63. The factory setting is unit number 01.                                     6  V1.2  Set to ON to display the output status on the operation

SW2                                          SW1                                               indicators.

1    2     0   1     2       3   4   5    6  7      8  9   A   B   C   D      E  F             OFF: The operation status is displayed (PWR, RUN, ERR,

                                                                                                    and ALM).

OFF  OFF   00  01    02      03  04  05  06  07  08    09  10  11  12  13  14    15            ON: The output status is displayed (outputs 1, 2, 3, and 4).

ON   OFF   16  17    18      19  20  21  22  23  24    25  26  27  28  29  30    31            Note: Normally keep this pin set to OFF so that the

OFF  ON    32  33    34      35  36  37  38  39  40    41  42  43  44  45  46    47                 operation status can be checked.

ON   ON    48  49    50      51  52  53  54  55  56    57  58  59  60  61  62    63   7        ON: G3ZA Multi-channel Power Controller in operation

                                                                                               ON when using a G3PW Power Controller.             V1.1

                                                                                      8        Use when an HFU is used and Units are distributed. (Refer

                                                                                               to the User's Manual for details.)

                                                                                      Note: Make sure power to the Unit is turned OFF before making

                                                                                              settings for any pin other than pin 6.

                                                                                              Pin 6 can be turned ON or OFF while the power is ON.

                                                                                      EJ1N-HFU@-NFL@

                                                                                               SW2                           Meaning

                                                                                      3 to 7        Not used (OFF)

                                                                                      8             • EJ1N-HFU@-NFLK

                                                                                                            OFF: RS-485 is selected.

                                                                                                            ON: RS-232C is selected.

                                                                                                    • EJ1N-HFU@-NFL2

                                                                                                            OFF (Not used.)

16             Modular Temperature Controller EJ1
■    Part      Names (EJ1N-HFUB-DRT)

                                                                                                  Operation Indicators

                                                23  456  EJ1N
                                           9 01
               SW1                   x 10       78       DRT                                      EJ1N-HFUB-DRT

                                    NODE

                                     ADR        23                                                Operation Indicators                        Meaning

                                     x1    9 01     456  MS

                                                78                 Indicators                     MS                  Green  ON: The Unit condition is normal.

                                                         NS

                                    MAX    EF012345                                               Module                     Flashing: The connection configuration
                                                  6789
               SW2                  No.         ABCD     TS                                       status
                                                                                                                                         has not been set.

                                                  6      COPY                                                         Red    ON: Fatal error

                                                  5                                                                          Flashing: Non-fatal error

                                                  4      EDS

               SW3                                3      UP/DN                                    NS                  Green  ON: Communications established

                                                  2      TC2/4

                                                  1      MODE                                     Network                    Flashing: Communications not established

                                                  NO                                              status

                                                                                                                      Red    ON: Fatal communications error

                                                                                                                             Flashing: Non-fatal communications error

                                                                                                  TS                  Green  ON: Communicating with the Temperature

                                                                                                  Temperature                Controllers

                                                                                                  Controller                 Flashing: The copy operation is being

                                                                                                  communica-                             performed.

                                                                                                  tions status        Red    Flashing: Communications error with a

                                                                                                                                         Temperature Controller

                                                                                                                             Flashing: The copy operation failed.

■ Specification Settings

Switch Operation                                                                                  SW3 Settings

• Always turn OFF the DeviceNet communications power supply and                                       DIP switch                              Meaning

EDU power supply before setting the Unit. (See note.)                                             6 (COPY)       ---         Upload/Download

• Set the switches with a small flat-blade screwdriver. Do not set the                                                       OFF → ON (1 s min., 5 s max.) → OFF

switches midway between settings.

• The SW1 switches are set to 00, SW2 is set to 0, and SW3 pins are                               5              ---         Not used.

all set to OFF in the default settings.                                                           4 (EDS)        OFF         Use the OMRON Configurator.

Note: The setting of pin 3 on SW3 can be changed while the power is                                              ON          Use universal Configurator. (EDS files

     ON.                                                                                                                     supported)

SW1 Settings                                                                                      3 (UP/DN)      OFF         Upload (from Temperature Controller to

                                                                                                                             DeviceNet Communications Unit)

Use  these     switches  to  set         the        node        address  as    a  slave  in  the                 ON          Download (from DeviceNet Communications

DeviceNet network between 00 and 63 decimal (node addresses 64                                                               Unit to Temperature Controller)

to 99 cannot be used).                                                                            2 (TC2/4)      OFF         Simple allocation to TC2 Units.

                                 23                                                                              ON          Simple allocation to TC4 Units.

               x 10          9 01   456           DeviceNet node                                  1 (MODE)       OFF         I/O Allocation from the Configurator.

               NODE              78               address setting

               ADR               23                                                                              ON          Simple I/O Allocation

                         x1  9 01   456

                                 78

SW2 Settings                                                                                          1 23 45 6

Use this switch to set the highest communications unit number (0 to

F: 0 to 15 decimal) of the connected Temperature Controllers. This

setting is enabled only when DIP switch pin 1 is set to ON (simple I/O                                NO

allocations).

                             EF012 345     Highest communications
               MAX                   6789
                                           unit number
               No.                 ABCD

                                                                                                      Modular Temperature Controller EJ1                               17
Functional Upgrades V1.1                                  V1.2

Functions depend on the version that you are using. The functional upgrades are given below. Refer to the User's Manual (Cat. No. H142) for

details.

                     Version                              V1.1                                                     V1.2

Applicable Unit

Basic Units                   • Modbus communications can be used on port B.               •  Autotuning is provided for heating/cooling control.

(EJ1N-TC2/TC4)                • Software version 2 of the G3ZA Multi-channel Power         •  Self-tuning has been added.

                                 Controller can be used.                                   •  A switch can be used to display the output status on

                              Note: 1.       When more than one G3ZA Multi-channel            the operation indicators during operation.

                                             Power Controller is connected, version 1 and  •  Modbus communications can be used to read and

                                             version 2 can be mixed. (Up to 8 G3ZA Multi-     write all parameters, and to execute any of the

                                             channel Power Controllers can be                 operation commands.

                                             connected.)                                   •  A switch setting can be changed to use Modbus

                                 2.          Software version 2 of G3ZA Multi-channel         communications on port B.

                                             Power Controller can also be used with EJ1    •  A switch setting can be used to set the baud rate of

                                             version1.0.                                      port B.

                                                                                           •  A C0/80 status has been added to the variable types.

                                                                                           •  Up to eight G3PW Power Controllers can be

                                                                                              connected to one Basic Unit.

                                                                                           Note: 1.    The G3PW can be connected to EJ1 V1.1.

                                                                                              2.       The G3PW and G3ZA cannot be used

                                                                                                       together.

Advanced Unit                 •  Programless communications can be used with 1: N          •  Bit specification operation commands have been

(EJ1N-HFU@-NFL@)                 connections.                                                 added to the parameters that can be specified for

                              •  The maximum number of parameters that can be                 programless download settings. This simplifies the

                                 specified for programless upload/download settings           program when operation commands are executed.

                                 has been increased from 300 to 600 each.                  •  The G3ZA or G3PW Monitor parameter has been

                              •  Connection is now possible to MELSEC-QnA/An/                 added to the parameters that can be specified for

                                 AnS/FX3uc-series PLCs.                                       programless upload settings. Up to four G3ZA Multi-

                              •  A new setting read operation has been added to               channel Power Controllers or up to four G3PW Power

                                 programless communications: Setting Read 2.                  Controllers can be connected to one Basic Unit.

                              •  The speed of programless communications has been          •  The maximum number of parameters that can be

                                 increased.                                                   specified for programless upload/download setting

                              •  Either "continue" or "stop" can be selected for when         has been increased from 600 to 1200 each.

                                 errors occur in programless communications.               •  The maximum number of Basic Units that an HFU

                                                                                              with Programless Communications can control has

                                                                                              been increased from 16 to 32 Units.

                                                                                           •  Communications unit numbers 32 to 39 can be used

                                                                                              in the HFU via programless communications.

                                                                                              This allows the communications unit numbers of

                                                                                              Basic Units connected to an HFU to be numbered

                                                                                              sequentially, making it easy to copy HFU and Basic

                                                                                              Unit settings to other HFUs and Basic Units.

Support Software              CX-Thermo version 3.20 or higher                             CX-Thermo version 4.1 or higher

Identifying Upgraded Models

The new functionality can be used with version 1.2 (V1.2). Check the label on the Temperature Controller or the box to determine the version.

Models not marked "Ver. 1.1" are version 1.0.

          Box Label                                             Temperature Controller Label

                                 Version                                                                                    Version

Note: The above example is for version 1.2.

18               Modular Temperature Controller EJ1
Dimensions

Note: All units are in millimeters unless otherwise indicated.

■ Temperature   Controller

Basic Units

EJ1N-TC                                                                                                                                                   109 (Models with screw terminal blocks)

                                            31                                                            31                                              104.85 (Models with screw-less clamp

HFUs                                                                                                                                                      terminal blocks)

                PWR         1                                   COM1        PWR       1                                 COM1

                RUN         2               EJ1NT-C             COM2        RUN       2                        EJ1NT-C  COM2

EJ1N-HFU@-NFL@  ERR         3                                   COM3        ERR       3                                 COM3

                ALM         4  OUT                                          ALM       4  OUT

                OPN            789ABCDE                                     OPN          789ABCDE                                                                                                           27.0
                                                                                                   F 012
                               3456  F 012                                                   3456

                            SW1                                                       SW1

                               ON                                                          ON

                               1                                                         1

                               2                                                         2                                                95.4   90                                                         35.4

                               3                                                         3

                     OPN       4                                                 OPN     4

                OUT            5                                            OUT          5

                            6  6                                                      6  6

                               7                                                         7

                               8                                                         8

                     SW2                                                         SW2

                                                                                                                                                                                                            27.6

                Models with screw                                     Models with screw-less

                terminal blocks                                       clamp terminal blocks

HFUs                                                                                           29

EJ1N-HFUB-DRT                                                                                  24                                                         82.2

                                                                                         20                                                                     65

                                                                                      9 01 23  456        EJ1N

                                                                            10             78             DRT

                                                                      NODE
                                                                      ADR
                                                                                           23
                                                                                      9 01     456        MS
                                                                            1

                                                                                           78             NS

                                                                      MAX             EF012345
                                                                                               6789
                                                                      No.                  ABCD           TS

                                                                                               1 23 45 6  COPY

                                                                                                          EDS

                                                                                                          UP/DN

                                                                                                          TC2/4

                                                                90                             NO         MODE                            90

End Units                                                                                                                                                 76.2 (Model with Screw Terminals)

                                                                                                                                                          79.7 (Model with Connector Terminal Block)

EJ1C-EDU                                                              15.7                                                    15.7                                          60

                                                                                                                                                                                                      27.0

                                                                                                                                                95.4  90                                              35.4

                                                                                                                                                                                                      27.6

                                                                EDUA                                                          EDUC

                                                     Model with                                                               Model with

                                            Screw Terminals                                               Connector Terminal              Block

                                                                                                                                          Modular Temperature Controller EJ1                                      19
■ Options

Current Transformer           (Sold            Separately)

E54-CT1                                            21

                                                                                      2.8

                                                   15             5.8 dia.

                                                                                                 7.5

                                25      3

                                                                            10.5

                                                   40

                                                                  Two, 3.5 dia.

                                     10

                                                   30

E54-CT3                                                                           2.36     dia.

                                                   30

                                                                  12 dia.

                                                                                                      9

                                    40@

                                                                  Two, M3 (depth: 4)

                                     15

                                                   30

E54-CT3 Accessory

• Armature                                 Connection         Example

Approx. 3 dia.                                                          Armature

                                                   Plug

                                                                                  Lead

                   18

• Plug

Approx. 6 dia.

                (22)

Rail Mounting          Equipment (Order Separately)

DIN Rail                                                                                                         7.3±0.15

PFP-100N                        4.5

PFP-50N                                                                                                          35±0.3    27±0.15

                                                                                                                                    Note:  The figures in parentheses

                                           15  25  10    25                       25  10         25      15 (5)            1               are dimensions for the

                                                              1000 (500)                                 (See note.)                       PFP-50N.

                                                              (See note.)

End Plate                                          10

                                                         6.2      1.8

PFP-M                  M4 × 8

                       panhead

                       screw                             1

                       50                                         35.5      35.3

                                                             1.8

                       11.5

                                    10                                                     Note:         Two screws are included with the  EJ1C-EDU for the End Plate.

                                                         1.3                                             Always attach End Plates to both  sides.

                             M4 spring washer            4.8

20              Modular Temperature Controller EJ1
Safety Precautions

                              !CAUTION                                     7.  Allow as much space as possible between the product and

                                                                               devices that generate a powerful high-frequency or surge.

Do not touch the terminals while power is being supplied.                      Separate the high-voltage or large-current power lines from other

Doing so may occasionally result in minor injury due to                        lines, and avoid parallel or common wiring with the power lines

electric shock.                                                                when you are wiring to the terminals.

                                                                           8.  Use the product within the rated load and power supply.

Use a power supply that complies with the reinforced                       9.  Make sure that the rated voltage is attained within two seconds of

insulation specified in IEC 60664 for the EJ1 external                         turning ON the power.

power supply or the power supply connected to the EJ1.                     10.It takes 30 minutes from the time the Temperature Controller is

If non-compliant power supplies are used, electric shock                       turned ON until the current temperature is displayed. Always turns

may occasionally result in minor injury.                                       ON the power supply at least 30 minutes before starting

Do not allow pieces of metal, wire clippings, or fine                          temperature control.

metallic shavings or filings from installation to enter the                11.The switch or circuit breaker must be within easy reach of the

product. Doing so may occasionally result in electric                          operator, and must be marked as a disconnecting means for this

shock, fire, or malfunction.                                                   unit.

Do not use the product where subject to flammable or                       12.Do not use paint thinner or similar chemical to clean with. Use

explosive gas. Otherwise, minor injury from explosion                          standard grade alcohol.

may occasionally occur.                                                    13.Design the system (e.g., the control panel) allowing leeway for the

Never disassemble, modify, or repair the product or touch                      delay required before product outputs are valid after turning ON

any of the internal parts. Minor electric shock, fire, or                      power to the product.

malfunction may occasionally occur.                                        14.Never touch the electronic components, connectors, or patterns

                                                                               on product boards with your bare hands. Always hold the product

Tighten the terminal screws to between 0.40 and                                by the case. Inappropriately handling the product may

0.56 N·m. Loose screws may occasionally result in fire.                        occasionally damage internal components due to static electricity.

                                                                           15.Use a switch, relay, or other device with contacts to turn OFF the

Set the parameters of the product so that they are                             power supply quickly. Gradually lowering the voltage of the power

suitable for the system being controlled. If they are not                      supply may result in incorrect outputs or memory errors.

suitable, unexpected operation may occasionally result in                  16.Do not touch the electronic components with your hands or

property damage or accidents.                                                  subject them to shock when removing the terminal block.

A malfunction in the product may occasionally make                         17.Connect only the specified number of products in only a specified

control operations impossible or prevent alarm outputs,                        configuration.

resulting in property damage. To maintain safety in the                    18.Mount the product to a DIN Rail mounted vertically to the ground.

event of malfunction of the product, take appropriate                      19.Always turn OFF the power supply before wiring the product,

safety measures, such as installing a monitoring device                        replacing the product, or changing the product configuration.

on a separate line.                                                        20.Attach the enclosed cover seal to the connector opening on the

                                                                               left end product during installation.

■ Precautions for Safe Use                                                 21.Do not use port B on the end product when using port C on

                                                                               HFUs.

Observe the following points to ensure safe operation.                     22.Install the product only after reading the manual provided with the

1.  The product is designed for indoor use only. Do not use the                End Unit.

    product outdoors or in any of the following locations.

    • Places directly subject to heat radiated from heating equipment

    • Places subject to splashing liquid or oil atmosphere

    • Places subject to direct sunlight

    • Places subject to dust or corrosive gas (in particular, sulfide gas

    or ammonia gas)

    • Places subject to intense temperature change

    • Places subject to icing or condensation

    • Places subject to vibration or strong shocks

2.  Use and store the product within the rated temperature and

    humidity ranges. Provide forced-cooling if required.

3.  To allow heat to escape, do not block the area around the product.

    Do not block the ventilation holes on the product.

4.  Be sure to wire properly with correct polarity of terminals.

5.  Use specified size (M3, width 5.8 mm or less) crimped terminals

    for wiring. To connect bare wires to the terminal block, use copper

    braided or solid wires with a gage of AWG22 to AWG14 (equal to

    cross-sectional area of 0.326 to 2.081 mm2) for power supply

    lines and a gage of AWG28 to AWG16 (equal to cross-sectional

    area of 0.081 to 1.309 mm2). (The stripping length is 6 to 8 mm.)

6.  Do not wire terminals that do not have an identified use.

                                                                               Modular Temperature Controller EJ1                                  21
■ Precautions for Correct Use                                            Wiring    Screw-Less Clamp Terminals

                                                                                                     There are two holes for each terminal. The

Installation                                                                                         hole on the right is the operation hole and

                                                                         B1                          the hole on the left is the wire hole.

1.  Do not connect the End Unit directly to an HFU.                                A1

                                                                         B2                          Insert a flat-blade screwdriver with a width of

2.  Connect the End Unit to the right side of a Basic Unit.                        A2                2.5 mm into the operation hole, insert the

3.  Connect the HFU to the left side of the Basic Units.                 B3                          wire into the wire hole, and then remove the

                                                                                   A3

4.  Connection is not possible to CJ1-series PLCs.                       B4                          screwdriver. The wire will be clamped.

                                                                                   A4

5.  Use the EJ1G-@@ for gradient temperature control. When not           B5                          Use crimp terminals that are suitable for the

    using gradient temperature control, use the EJ1N-@@.                           A5                cross-sectional area of the wire.

                                                                         B6

6.  When removing the terminal block to replace a Unit, be sure that               A6                Recommended crimp terminals:

    the new Unit is the same as the Unit that is being replaced.         B7

                                                                                   A7                Weidmuller H-sleeve series

                                                                         B8

Service Life                                                             B9        A8

                                                                         B10       A9

1.  Use the product within the following temperature and humidity                  A10

    ranges:

    Temperature: −10°C to 55°C (with no condensation or icing)           Installation

    Humidity:     25% to 85%

    When the Temperature Controller is incorporated in a control         Connecting Units

    panel, make sure that the controller's ambient temperature and       1.  Align the connectors and connect the Units to each other.

    not the panel's ambient temperature does not exceed 55°C.                Connect an End Unit to the Unit on the right end.

2.  The service life of electronic devices like Temperature Controllers

    is determined not only by the number of times the relay is

    switched but also by the service life of internal electronic

    components. Component service life is affected by the ambient

    temperature: the higher the temperature, the shorter the service

    life and the lower the temperature, the longer the service life.

    Therefore, the service life can be extended by lowering the

    temperature of the Temperature Controller.

3.  Mounting two or more Temperature Controllers side by side, or

    mounting Temperature Controllers above each other may cause

    heat to build up inside the Temperature Controllers, which will

    shorten their service life. If the Temperature Controllers are

    mounted above each other or side by side, use forced cooling by      Note: 1.  Do not connect the End Unit directly to an HFU.

    fans or other means of air ventilation to cool down the                   2.   Connect the End Unit to the right side of a Basic Unit.

    Temperature Controllers.

    However, be sure not to cool only the terminals. Doing so will       2.  Slide the yellow sliders on the top and bottom of the Units until

    result in measurement errors.                                            they click into place.

Ensuring Measurement Accuracy

1.  When extending or connecting the thermocouple lead wire, be                                      Lock

    sure to use compensating wires that match the thermocouple

    types.                                                                         Slider

2.  When extending or connecting the lead wire of the platinum

    resistance thermometer, be sure to use wires that have low

    resistance and keep the resistance of the three lead wires the       3.  Attach the cover seal to the connector opening on the Unit on the

    same.                                                                    left end of the EJ1.

3.  Mount the Temperature Controller so that it is horizontally level.

4.  If the measurement accuracy is low, check to see if input shift has

    been set correctly.

Precautions for Operation

1.  A certain amount of time is required for the outputs to turn ON

    from the time the power supply is turned ON. Due consideration

    must be given to this time when incorporating Temperature                      Cover Seal

    Controllers in a sequence circuit.

2.  It takes 30 minutes from the time the Temperature Controller is

    turned ON until the current temperature is displayed. Always turns

    ON the power supply at least 30 minutes before starting

    temperature control.

3.  Avoid using the Temperature Controller near a radio, television

    set, or other wireless device. Its use would result in reception

    disturbance.

22             Modular Temperature Controller EJ1
Removing the Terminal Block                                                             Install the DIN Rail vertically to the ground.

1.  Press down the terminal block lever.                                                                  Correct                                                         Incorrect

                                                                                        Vertically                                                          Horizontally

                                                                                        Applicable DIN Rail (sold                                    separately): PFP-100N (100 cm),

                                                                                                                                                                 PFP-50N (50 cm)

                                                                                        Connecting to                                                the G3ZA (EJ1N-TC)

                                                      Lower the lever.

2.  Pull out the terminal block.

                                                      Pull out.

                                                                                        CN1

                                                                                                                                                     READY

                                                                                                                                                     SD/RD

                                                                                                                                                            SW1

                                                                                                                                                     OCC    SW2

                                                                                             CN1

                                                                                                                                                     ERROR

Mounting to the DIN Rail

Mounting                                                                                Connect the G3ZA                                                    G3ZA

Catch the hook located on the top of the Unit onto the DIN Rail and                     Connecting Cable to the

press the Unit until the Unit locks into place.                                         CN1 connector on the                                                     Connect the black line with a

                                                                                        bottom of the TC Unit.                                                   white stripe to terminal 7 on the

    (2) Catch the upper hook                                                                                                                                     G3ZA and the black line with no

       onto the DIN Rail.                                                                                                                                        stripe to terminal 8.

                                                                                                                                                            EJ1C-CBLA050 (Sold Separately)

                                                                                                                                                            (cable length: 5 m)

    (3) Press in                                      (4) Make sure the Unit            Refer to the “G3ZA Instruction Manual” for wiring methods.

       on the     (1) Lower the hooks.                           is locked into place.

       Unit.                                                                            Connecting to the G3PW (EJ1N-TC)

Dismounting

Pull down on the hook with a flat-blade screwdriver and lift up on the

Unit.

                                                                                                                                   ADJ      SET  EV

                                                                                                       %(IN)

                                                                                                       %(DUTY)                LVL

                                                                                                       %(OUT)

                                                                                                       %(PHASE)

                                                                                                       A                      ENT

                                                                                                       COMM                   RST

                                                                                                                                            G3PW

                                                                                                                         1            B(+)

                                                                                                                         2       RS-485

                                                                                                                                      A(-)

                                                                                                                         3         REMOTE SET        Set the baud rate to 57.6 kbps

                                                                                                                         4

                                                                                                                         5         DUTY SET          (default value) using key

                                                                                                                         6

                                                                                                                         7         +                 operations. For details, refer to
                                                                                                                                 ALARM1(NPN)
                                                                                                                         8
                                                                                                                                   -

                                                                                                                         9         +                 the G3PW Operation Manual.
                                                                                                                                 ALARM2(NPN)
                              Flat-blade Screwdriver                                                                     10
                                                                                                                                   -

                                                                                                                         11           EVENT

                                                                                                                         12

Mount one End Plate to each side of the EJ1C-EDU (PFP-M End                                                              13           RESET

                                                                                                                         14

Plates are included with the End Unit).

                                                                                                    1          2              3       4          5

                                                                                                                      +  -            100-240VAC
                                                                                                                      4-20mA

                                                                                                       +     1-5V        -            N          L

                                                                                                          See            N       L
                                                                                                       Manual

                                                                                                       Time-lag fuse

                                                                                                       Load              T1      L1

                                                                                                       Fast-acting fuse

                                                                                             Connect the black line with a white stripe to terminal 1 on

                                                                                             the G3PW and the black line with no stripe to terminal 2.

                                        PFP-M                                                EJ1-CBLA050 (order separately) (cable length: 5 m)

                                                                                        Refer to the G3PW Instruction Manual for wiring methods.

       Refer to the following manual for precautionary information and other information necessary to use the EJ1:

       EJ1 Modular Temperature Controller User’s Manual (Cat. No. H142)

                                                                                             Modular Temperature Controller EJ1                                                                 23
I/O Devices

■ Examples of EJ1-series Temperature Controllers/Output Devices

    Input device/sensor                                                                                                                       Temperature controller                                                                                                                                                          SSR                        Load

                                                                                                                                                             Voltage output                                                                                                                                                                            Heater                   Load

                                                                                                                                                                  terminal                                                                                                                                           INPUT         LOAD                                         power

                                                                                                                                              (for driving SSR)                                                                                                                                                                                                                 supply

                                                                                                                                                                                                                                                                                             Can be directly

                                                                                                                                                                                                                                                                                             connected.

    Analog quantities, such as temperature,                                                                                                                                                                                                                                                                                              G3PF (SSRs with built-in CTs)

    flow rate, and concentration                                                                                                                                                                                                                                                                    Number of SSRs That Can

                                                                                                                                                                                                                     EJ1                                                                            be Connected in Parallel             240 VAC, 25 A or 35 A

    Converters, Digital Panel Meters, Flow Meters,                                                                                                                                                                                                                                                                                       480 VAC, 25 A or 35 A

    Infrared Thermosensors, Displacement Sensors

                                                                                                                                                                   EJ1N-TC2@-QNHB                                                                                                                             4                    Rated input voltage:

                                                                                                                                                                                              PWR                                        COM1       PWR                           COM1                                             12 to 24 VDC

                                                                                                                                                                                              RUN                          EJ1-TC2       COM2       RUN                  EJ1-TC2  COM2

                                                                                                                                                                                              ERR                                        COM3       ERR                           COM3

                                                                                                                                                                                              ALM                                                   ALM

                                                                                                                                                                                                        ABCD                                                 ABCD
                                                                                                                                                                                                    6789       E0F1                                         6789   E0F1
                                                                                                                                                                                                         2345                                                    2345
                                                                                                                                                                                              SW1                                                   SW1                                                                            Built-in CT for heater

                                                                                                                                                                                                       ON                                                    ON                                                                    burnout detection and SSR

                                                                                                                                                                                                    1                                                       1                                                                      short-circuit detection.

                                                                                                                                                                                                    2                                                       2

                                                                                                                                                                                                    3                                                       3

                                                                                                                                                                                                    4                                                       4

                                                                                                                                                                                                    5                                                       5

                                                                                                                                                                                                    6                                                       6

                                                                                                                                                                                                    7                                                       7

                                                                                                                                                                                                    8                                                       8

                                                                                                                                                                                              SW2                                                   SW2

                                                                                                                                                                                                                                                                                                                                         G3PE (Single Phase)

                                                        ES1B                                                                                                                                                                                                                                                                       240 VAC, 15 A, 25 A, 35 A, or 45 A

    Infrared Thermosensor                                                                                                                     Two-channel SSR outputs can be                                                                                                                                                       480 VAC, 15 A, 25 A, 35 A, or 45 A

                                                                                                                                              connected to models with TC2@-                                                                                                                                  3                    Rated input voltage:

                                                                                                                                              QNHB.                                                                                                                                                                                12 to 24 VDC

                                                                                                                                              The number of SSRs that can be

                                                                                                                                              connected for each channel is listed                                                                                                                                                 Ultra-compact and slim

                                                                                                                                              on the right.                                                                                                                                                                        model combined with a

                                                                                                                                                                                                                                                                                                                                   heat radiator

    ES2-HB Humidity Sensor                                                                                                                                                                         EJ1N-TC4

                                                                                                                                                                                         PWR                                        COM1       PWR                                COM1                                                   G3PE (Three Phase)

    ES2-THB Temperature/Humidity Sensor                                                                                                                                                  RUN                         EJ1-TC2        COM2       RUN                       EJ1-TC2  COM2

                                                                                                                                                                                         ERR                                        COM3       ERR                                COM3

                                                                                                                                                                                         ALM                                                   ALM

                                                                                                                                                                                                   ABCD                                                    ABCD
                                                                                                                                                                                              6789      E0F12                                         6789   E0F1
                                                                                                                                                                                                                                                           2345
                                                                                                                                                                                         SW1       345                                           SW1                                                                               240 or 480 VAC, 15 A, 25 A, 35 A, or 45                                                                                                              A

                                                                                                                                                                                                   ON                                                    ON                                                   2                    Rated input voltage:

                                                                                                                                                                                              1                                                       1

                                                                                                                                                                                              2                                                       2

                                                                                                                                                                                              3                                                       3

                                                                                                                                                                                              4                                                       4

                                                                                                                                                                                              5                                                       5

                                                                                                                                                                                              6                                                       6                                                                            12 to 24 VDC

                                                                                                                                                                                              7                                                       7

                                                                                                                                                                                              8                                                       8

                                                                                                                                                                                         SW2                                                     SW2

                                                                                                                                                                                                                                                                                                                                   Three-phase batch

                                                                                                                                                                                                                                                                                                                                   control combined with

                                                                                                                                              Four-channel SSR outputs can be                                                                                                                                                      heat radiator

    Thermocouple/Platinum                                                                                                                     connected to models with TC4.

    Resistance Thermometer E52                                                                                                                The number of SSRs that can be                                                                                                                                                                                 G3PA

                                                                                                                                              connected for each channel is listed                                                                                                                                                 240 VAC, 10 A, 20 A,            40 A,        or     60                                                                                            A

                                                                                                                                              on the right.                                                                                                                                                                        480 VAC, 20 A, 30 A,            or 50        A

                                                                                                                                                                   EJ1N-TC2@-CNB                                                                                                                              3                    Rated input voltage:

                                                                                                                                                                                                                                                                                                                                   240 V: 5 to 24 VDC                      AG

                                                                                                                                                                   PWR                                               COM1           PWR                                           COM1                                             480 V: 12 to 24 VDC             OMRON

                                                                                                                                                                   RUN                             EJ1-TC2           COM2           RUN                                  EJ1-TC2  COM2                                                                             AGHTUR

                                                                                                                                                                   ERR                                               COM3           ERR                                           COM3                                                                             AG

                                                                                                                                                                   ALM                                                              ALM

                                                                                                                                                                             DEF                                                               DEF                                                                                 Ultra-compact and slim          AGHTURWNBVC

                                                                                                                                                                        89ABC34567  012                                                   89ABC34567  012

                                                                                                                                                                   SW1                                                              SW1

                                                                                                                                                                                                                                                                                                                                                                   AGHT

                                                                                                                                                                                                                                                                                                                                   model combined with a

                                                                                                                                                                                                                                                                                                                                   heat radiator

                                                                                                                                                                        ON                                                                     ON

                                                                                                                                                                        1                                                                 1

                                                                                                                                                                        2                                                                 2

                                                                                                                                                                        3                                                                 3

                                                                                                                                                                        4                                                                 4

                                                                                                                                                                        5                                                                 5

                                                                                                                                                                        6                                                                 6

                                                                                                                                                                        7                                                                 7                                                                                                                  G3NA

                                                                                                                                                                        8                                                                 8

                                                                                                                                                                   SW2                                                              SW2

    Single-phase Power Controller                                                                                                                                                                                                                                                                                                  240 VAC, 5 A, 10 A, 20 A, 40 A, 75 A, or 90                                                                                                          A

                                                        G3PW                                                                                                                                                                                                                                                                       480 VAC, 10 A, 20 A, 40 A, 75 A, or 90 A

                                                                                                                                                                                                                                                                                                              3                    Rated input voltage:

                                                                                                                                              · Two current output channels can                                                                                                                                                    5 to 24 VDC                                  AAGAGHHATTGUUHAARRTGGWOUHHWNRMTTBWUAUNRVRNGBCOWBDHVVNNSCCTABIODVUSLCRHIDOGWSLFIHONGLAFBHGGVHFCTU  A

                                       ADJ     SET  EV                            ADJ     SET  EV                            ADJ     SET  EV                 be connected to the TC2@-CNB.                                                                                                                    Four 480-VAC

                                                                                                                                                                                                                                                                                                                                                                                    A

                %(IN)                                      %(IN)                                      %(IN)                                                                                                                                                                                                   models

                %(DUTY)                                    %(DUTY)                                    %(DUTY)                                 · Up to eight G3ZA or G3PW can be

                %(OUT)                                     %(OUT)                                     %(OUT)

                %(PHASE)                                   %(PHASE)                                   %(PHASE)                                                                                                                                                                                                                     Standard model

                A                 ENT                      A                 ENT                      A                 ENT

                COMM              RST                      COMM              RST                      COMM              RST                                  connected to each Basic Unit.                                                                                                                    (10 A/20 A/40A)

                                               G3PW                                       G3PW                                       G3PW

                            1          B(+)                            1          B(+)                            1          B(+)                                                                                                                                                                                                  with screw terminals

                            2        RS-485                            2        RS-485                            2        RS-485

                                       A(-)                                       A(-)                                       A(-)

                            3          REMOTE SET                      3          REMOTE SET                      3          REMOTE SET                                                                                                                                                                       One 240-VAC

                            4                                          4                                          4

                            5          DUTY SET                        5          DUTY SET                        5          DUTY SET

                            6                                          6                                          6

                            7        ALARM1(NPN)                       7        ALARM1(NPN)                       7        ALARM1(NPN)                                                                                                                                                                        model

                            8                                          8                                          8                           Special Cable

                            9        ALARM2(NPN)                       9        ALARM2(NPN)                       9        ALARM2(NPN)

                            10                                         10                                         10

                            11         EVENT                           11         EVENT                           11         EVENT

                            12                                         12                                         12                                                                                                                                                                                          (75 A/95 A)

                            13         RESET                           13         RESET                           13         RESET            (Communications)                                                                                                                                                                                               G3NE

                            14                                         14                                         14

             1          2         3         4       5   1          2         3         4       5   1          2         3         4       5                                                                                                                                       Special Cable

                         +     -       100-240VAC                   +     -       100-240VAC                   +     -       100-240VAC
                         4-20mA                                     4-20mA                                     4-20mA

                +  1-5V        -            L       N      +  1-5V        -            L       N      +  1-5V        -            L       N                                                                                                                                                                                              240 VAC, 5 A, 10 A, or 20 A

                                                                                                                                                                                                                                                                                  (Communications)

                                                                                                                                                                                                                                                                                                              1                    Rated input voltage:

    Can be mounted side by side (See note.)                                                                                                                                                                                G3ZA                                                                                                          12 VDC

Note: Side-by-side mounting is possible only                                                                                                  Multi-channel Power Controller                                                                                                                                                       Compact low-cost

    for 20 A or 45 A models.                                                                                                                                                                                                                                                                                                       models with quick-

                                                                                                                                                             G3ZA                             SSR                                                     SSR                               SSR  SSR                                   connect terminals

    • Concept behind the Number of SSRs That                                                                                                                                                                                                                                                                                                                 G3NH

    Can Be Connected in Parallel

    (A): The maximum load current for the voltage                                                                                                                                                                                                                                                                                        240 or 440 VAC, 75 A or 150 A

                                                                                                                                              READY

                                                                                                                                              SD/RD

    output (to drive SSRs) for the Temperature                                                                                                               SW1

                                                                                                                                              OCC            SW2                                                                                                                                              4                    Rated input voltage:

                                                                                                                                              ERROR

    Controller is 21 mA.                                                                                                                                                                                                                                                                                                           5 to 24 VDC

    (B): The input impedance for SSRs is 7 mA

    (G3NA).                                                                                                                                                                                                                                                                                                                        For controlling

    In this case, the number of SSRs that can                                                                                                                                                                                                                                                                                      high-power heaters

    be connected in parallel is (A) ÷ (B),                                                                                                                                                                                 Eight Units max.∗

    therefore 3.

    The maximum load current in the connection                                                                                                ∗The G3ZA is available with 4 or 8 control

    example is 21 mA.                                                                                                                         points.

24                     Modular Temperature Controller EJ1
CX-Thermo Support Software Ver. 4.1

EST2-2C-MV4

Monitoring/Setting Support Software for E5CN/CN-H, E5AN/AN-H,

E5EN/EN-H, E5ZN, E5@R/@R-T, and EJ1 Temperature Controllers Enabling

Faster Parameter Setup, Device Adjustment, and Maintenance

• Enables editing and batch-downloading parameters from a personal

computer, reducing the work required to set parameters.

Usability is improved with table-formatted parameter editing from

version. 4.0.

• Supports Trend Monitoring:

Monitor data (PV, SP, MV, PID parameter, Alarm ON/OFF, etc.) for

up to 31 E5@N/@N-H Temperature Controllers.

Connect up to 64 EJ1N, 17 EJ1G, or 16 E5ZN Temperature

Controllers. (The Temperature Controllers must be from the same

series.)

• Supports parameter masks to hide parameters unnecessary to

display. (Supported only by the E5@N/@N-H and E5@R/@R-T).

• Logic operations enable setting inputs from external inputs (event

inputs) or temperature status, outputs to external outputs (control or

auxiliary outputs), and changing operating status with ON/OFF

delays.

(Supported only by the E5@N/@N-H).

• Easy adjustment of control performance by fine-tuning.

∗ Fine-tuning instructs the CX-Thermo to calculate a PID parameters by

directly inputting commands to improve response.

Ordering Information

■ List of Models

                    Name                              Model

CX-Thermo Support Software                  EST2-2C-MV4

Specifications

Compatible     Temperature            E5CN (available from April 2004)

devices        Controllers            E5AN, E5EN (available from February 2005),

                                      E5CN-H, E5AN-H, E5EN-H

                                      E5AR, E5ER

                                      E5AR-T, E5ER-T

                                      E5ZN

                                      EJ1N-TC4, EJ1N-TC2, EJ1N-HFU

                                      EJ1G-TC4, EJ1G-TC2, EJ1G-HFU

                                      G3ZA (only when connected to EJ1N-TC4, EJ1N-TC2, EJ1G-TC4, EJ1G-TC2)

                                      Note: Models with DeviceNet communications are not supported.

Personal       OS                     Windows 2000 (service pack 3 or higher), XP, or Vista

computer       CPU                    300 MHz min.

system

requirements   Memory                 128 MB min.

               Harddisk               300 MB min. available space

               CD-ROM                 One CD-ROM drive min.

               Monitor                SVGA (800 × 600) min.

               Communications  ports  • RS-232C port, or USB port, 1 port min.

Connection method                     •  An E58-CIFQ1 USB-Serial Conversion Cable is required to connect a computer to the setup tool port

                                         the E5@N, E5@N-H, or EJ1.

                                      •  A K3SC Interface Converter is used to connect a computer to models with RS-422/RS-485

                                         communications.

                                      •  An E58-CIFIR USB-Infrared Conversion Cable is required to wirelessly connect a computer to models

                                         with infrared communications (E5AN-H or E5EN-H).

                                                    CX-Thermo Support Software Ver. 4.1 EST2-2C-MV4                                         25
USB-Serial Conversion Cable

E58-CIFQ1

Cable for Support Software Enables

Connection Even with Temperature

Controllers Not Equipped with

Communications

• Easily set Temperature Controller parameters by connecting the

computer's USB port and an EJ1, or a new-model E5CN, E5AN,

or E5EN.

Ordering Information

               Model

E58-CIFQ1                             Note: Older models of the E5CN, E5AN, and E5EN are not supported.

Specifications

Applicable OS                         Windows 2000/XP

Applicable software                   Thermo Mini, CX-Thermo Ver. 3.0 or higher

Applicable models                     EJ1, E5CN, E5AN, E5EN Series (new models)

USB interface standard                Conforms to USB Specification 1.1.

DTE speed                             38,400 bps

Connector specifications              Computer: USB (type A plug)

                                      Temperature Controller: Serial

Power supply                          Bus power (Supplied from USB host controller.)

Power supply voltage                  5 VDC

Current consumption                   70 mA

Ambient  temperature range            Operating: 0°C to 55°C, Stored: −20°C to 60°C (with       no icing or condensation)

Ambient humidity range                Operating: 10% to 80% (with no condensation)

Weight                                Approx. 100 g

Note: A driver must be installed  in  the personal computer. Refer to installation information  in the operation manual for the   Conversion Cable.

Dimensions                                                                                                                        (Unit: mm)

USB-Serial Conversion Cable

E58-CIFQ1

                                                                                                (2,100)

                                                       250                       LED (SD)                                  1,765

                                      USB connector (type A plug)                               LED (RD)                          Serial connector

26            USB-Serial Conversion Cable E58-CIFQ1
Warranty and Application Considerations

                                             Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you

have any questions or comments.

                                             Warranty and Limitations of Liability

WARRANTY

OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or

other period if specified) from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,

MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER

ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET

THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR

IMPLIED.

LIMITATIONS OF LIABILITY

OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS,

OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON

CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.

In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE

PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,

INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE

MODIFICATION OR REPAIR.

                                             Application Considerations

SUITABILITY FOR USE

OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of

products in the customer's application or use of the products.

Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will

be used.

Know and observe all prohibitions of use applicable to this product.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT

ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON

PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR

SYSTEM.

                                                                   Disclaimers

PERFORMANCE DATA

Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a

warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application

requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.

CHANGE IN SPECIFICATIONS

Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with

your OMRON representative at any time to confirm actual specifications of purchased product.

DIMENSIONS AND WEIGHTS

Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

                 ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

                 To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

OMRON Corporation                            OMRON ELECTRONICS LLC                          Authorized Distributor:

Industrial Automation Company                One Commerce Drive Schaumburg,

Control Devices Division H.Q.                IL 60173-5302 U.S.A.

Analog Controller Division                   Tel: (1) 847-843-7900/Fax: (1) 847-843-7787

Shiokoji Horikawa, Shimogyo-ku,

Kyoto, 600-8530 Japan                        OMRON ASIA PACIFIC PTE. LTD.

Tel: (81) 75-344-7080/Fax: (81) 75-344-7149  No. 438A Alexandra Road # 05-05/08 (Lobby 2),

2-2-1 Nishikusatsu, Kusatsu-shi,             Alexandra Technopark, Singapore 119967

Shiga, 525-0035 Japan                        Tel: (65) 6835-3011/Fax: (65) 6835-2711

Tel: (81) 77-565-5216/Fax: (81) 77-565-5568

Regional Headquarters                        OMRON (CHINA) CO., LTD.

OMRON EUROPE B.V.                            Room 2211, Bank of China Tower,                © OMRON Corporation 2006  All Rights Reserved.

Wegalaan 67-69-2132 JD Hoofddorp             200 Yin Cheng Zhong Road,                      In the interest of product improvement,

The Netherlands                              PuDong New Area, Shanghai, 200120, China       specifications are subject to change without notice.

Tel: (31)2356-81-300/Fax: (31)2356-81-388    Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200                                           Printed in Japan

OMRON Industrial Automation Global: www.ia.omron.com                                        Cat. No. H144-E1-04                                   0908
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Omron:

EJ1N-TC4B  EJ1N-TC4A    EJ1C-EDUA-NFLK  EJ1N-TC2B-CNB   EJ1N-TC2A-CNB   EJ1N-TC2B-QNHB  EJ1N-TC2A-

QNHB  EJ1N-HFUA-NFL2    EJ1N-HFUA-NFLK  EJ1N-HFUB-NFLK  EJ1N-HFUB-NFL2  EJ1C-CBLA050

小广播

EJ1C-EDUA-NFLK器件购买:

该厂商的其它器件

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2017 EEWORLD.com.cn, Inc. All rights reserved