器件描述

controllers temperature display

参数

Manufacturer: Omron
Product Category: Controllers
RoHS: No
Brand: Omron Automation and Safety
Factory Pack Quantity: 1

E5LC-7器件文档内容

   New Product

Electronic Thermostat

E5L

Ideal for Simple Built-in Control.

A high switching capacity of 10 A at 250 VAC enables
  direct load switching.

A sensor is provided to enable immediate application.
Sockets with finger protection (PTF14A-E) or without

  finger protection (PTF14A) can be used.
Simple operation and settings. Even simpler with digital

  models.

Model Number Structure

Model Number Legend

E5L-@@                             2. Set temperature
                                   -30-20 : -30 to +20C
           12                      0-50 : 0 to +50C
                                   0-100 : 0 to +100C
1. Setting and Indication Methods  100-200 : +100 to +200C
A: Analog setting, no display
C: Digital setting, display

Ordering Information

Electronic Thermostats

E5L-A@

Size           Type                           Control method    Control                Model
                                                                output       E5L-A -30-20
                                                                             E5L-A 0-50
45 35 mm     Plug-in                        ON/OFF operation  Relay        E5L-A 0-100
                                                                             E5L-A 100-200
E5L-C@         Type                           Control method    Control
                                                                output                 Model
         Size                                                                E5L-C -30-20
                                                                             E5L-C 0-100
45 35 mm     Plug-in                        ON/OFF operation  Relay        E5L-C 100-200

Note: The E5L-C is not available with a set temperature range of 0 to 50C.

Options (Order Separately)

Sockets

         Type                      Model

                                    PTF14A
Front-connecting Socket

                                    PTF14A-E

                                                                                              1
   E5L

   Ratings and Characteristics

   Ratings

   Item              Model                            E5L-A@                                                E5L-C@

   Power supply voltage 100 to 240 VAC, 50/60 Hz

   Operating voltage range 85% to 110% of the rated supply voltage

   Power consumption           Approx. 3 VA

   Inputs                      Element-interchangeable thermistor

   Control method              ON/OFF control
   Control output
   Setting method              SPDT contacts, 250 VAC, 10 A, cos = 1 (resistive load) SPST-NO contacts, 250 VAC, 10 A, cos = 1 (resistive load)

                               Analog setting                                       Digital settings using keys on front panel

   Indication method           No display                                           LCD digital display (character height: 12 mm)
   Other functions
                                                                                     Setting protection (key protection)
                                                                                     Input shift
                                                                                     Direct/reverse operation

   Ambient temperature -10 to 55C (with no icing or condensation)

   Ambient humidity            25% to 85%

   Storage temperature -25C to 65C (with no icing or condensation)

   Note: Do not use the output from an Inverter as the power supply.

   Characteristics

   Item              Model                            E5L-A@                                                E5L-C@
                                                          ---
   Indication accuracy                                    ---                       (1C + 1 digit) max.*
                                                                                    (1C + 1 digit) max.*
   Setting accuracy

   Hysteresis                  -30 to 20C models: Approx. 0.5 to 2.5C (variable)  1 to 9C (in increments of 1C)
                               0 to 50C models: Approx. 0.5 to 4C (variable)
                               0 to 100C models: Approx. 0.5 to 4C (variable)
                               100 to 200C models: Approx. 0.7 to 4C (variable)

   Repeat accuracy             1% FS max.                                                                   ---

   Minimum scale               -30 to 20C models and 0 to 50C models: 5C                                 ---
   (standard scale)            0 to 100C models and 100 to 200C models: 10C

   Influence of temperature                           ---
   Influence of voltage                                                                        ((1% of PV or 2C, whichever is greater) +1 digit) max.

                                                      ---

   Sampling period                                    ---                           2s

   Insulation resistance       100 M max. (at 500 VDC)

   Dielectric strength         2,300 VAC, 50/60 Hz for 1 min (between charged terminals and uncharged metallic parts, between power supply
                               terminals and input terminals, between power supply terminals and output terminals, and between input terminals
                               and output terminals)

   Vibration (malfunction) Frequency of 10 to 55 Hz, 0.5-mm double amplitude for 10 min each in X, Y, and Z directions

   Vibration (destruction)     Frequency of 10 to 55-Hz, 0.75-mm double amplitude for 2 h each in X, Y, and Z directions
   Shock (malfunction)
                               147 m/s2, 3 times each in 6 directions               100 m/s2, 3 times each in 6 directions

   Shock (destruction)         294 m/s2, 3 times each in 6 directions

   Electrical life expectancy  100,000 operations min (at maximum applicable load)
   (control output relay)

   Memory protection                                  ---                           Non-volatile memory (100,000 write operations)

   Weight (Thermostat)         Approx. 80 g (Thermostat only)
   Degree of protection        Front panel: IP40, Terminals: IP00

   Approved standards                                                               ---

   Conformed standards EN 61010-1 (IEC 61010-1), Pollution Degree 2, Overvoltage Category II

                               EMI:                                      EN61326-1

                               Radiated EMI:                             EN55011 Group1 ClassA

                               Conducted EMI:                            EN55011 Group1 ClassA

                               EMS:                                      EN61326-1

   EMC Directives              Electrostatic discharge immunity:         EN61000-4-2

                               Electromagnetic field strength immunity:  EN61000-4-3

                               Burst noise immunity:                     EN61000-4-4

                               Conducted disturbance immunity:           EN61000-4-6

                               Surge immunity:                           EN61000-4-5

                               Voltage dip and power interruption immunity: EN6100-4-11

   * The accuracy of the accessory thermistor is not included.

2
                                                                                                                                                                              E5L

External Connections                                                                                                                       E5L-C@

                                          E5L-A@

                                                                                      Control output*                                                            Control output*

                                                  250 VAC, 10 A                                                                                             250 VAC, 10 A

Element-                                                                                                    Element-
interchangeable                                                                                             interchangeable
Thermistor                                                                                                  Thermistor

                               Input power supply: 100 to 240 VAC                                                            Input power supply: 100 to 240 VAC

* Control output Heating load: Terminals 8 and 12                                                           * Control outputs: Terminals 8 and 12

                 Cooling load: Terminals 4 and 12                                                           Use the keys on the front panel to set direct/reverse operation.

Be careful of the cooling load contacts, because they will be electrically

charged even when the E5L input power supply is OFF.

Note: For thermistor wiring, separate the input power supply and load lines as much as possible to avoid the influence of inductive noise.

Nomenclature                                                                                                              Operation Indicator

E5L-A@                                                                                                                    Operation                    Output status
                                                                                                                          indicator
           Operation indicator                                                                                                             Heating load          Cooling load
                                                                                                                          Lit red.
                                                                                                    Hysteresis            Not lit.                 ON                 OFF
                                                                                                    adjuster (DIFF.)
                                                                                                                                           OFF                        ON

                                Temperature dial

E5L-C@                                                                                                                    Operation Indicator: ON

          Operation indicator                                                                                             Operation                    Output status
          Set value indicator                                                                                             indicator
         Protection indicator                                                                       Process value                          Reverse               Direct operation
                                                                                                    and set value         Lit              operation
                                                                                                    display               Not lit
                                                                                                                                               ON                     ON

                                                                                                                                           OFF                        OFF

                                Mode Key                                              Down Key      Up Key                Set Value Indicator: SV

                                                                                                                          Lit when the set value is displayed.

                                                                                                                          Setting Protection Indicator:

                                                                                                                          Lit when setting protection is set.

Dimensions                                                                                                                                                                 (Unit: mm)

Thermostats

E5L-A@

                                                                                  35

                                                                                                45                 (4.6)     64                        6.4

                                                                                                                             75.0

E5L-C@

                                                  35

                                                                                                45                           64                        6.4

                                                                                                                                     70.4

                                                                                                                                                                                       3
   E5L

   Wiring Connection Sockets (Order Separately)

                                             Dimensions                                                                                            Terminal                   Mounting Hole
                                                                                                                                             Arrangement and                    Dimensions
                                                                                                                                           Internal Connections
                                                                                                                                                                                  (TOP VIEW)
          PTF14A                             PTF14A-E Socket with Finger Protection                                                               (TOP VIEW)              Note: Can be mounted to

   Two, 4.5 x 6    70.2                3.4                                Two, 4.5 x 6          70.2                3.4                            4321                         a DIN Track.
   mounting holes                                                                                                                                    8765
                          14, M3.5 x 8                                     mounting holes
                          Sems screws
                                                                                                        14, M3.5 x 8
                                                                                                        Sems screws

   78.5 max.                                 35.4 78.5 max.                                                                          35.5                                 680.3

                                                                                                                                           12 11 10 9

                                                                                                                                           14             13

              45.5 max.           8                                                        45.5 max.                         8                                                     360.2
                         30 max.                                                                                  33 max.
                                                                                                                                                                                        Two, M4 or
                                                                                                                                                                                        4.5-dia. holes

   Accessories

   E52-THE-E5L Element-interchangeable Thermistor                                                                                    Temperature Range

    Included with the following models: -30 to 20C, 0 to 50C, and 0 to                                                             Temperature  Color        Nominal    Thermistor
    100C.                                                                                                                                range   code        resistance   constant

                                                                                                                                     -30 to 20C  Blue        6 k (0C)               Lead wires

                         (5.5-dia.)          Color code                                  PVC cable (12/0.18)                         0 to 100C*  Black       6 k (0C)

                                                                                                                                                                0.55 k    3,390 K     Heat-resistant
                                                                                                                                                                (200C)   3,390 K     PVC cable

                                                                                                                                 10  100 to 200C Yellow                  4,300 K PTFE
                                                                                                                        30
                                                                       30                   500                                      Note: PVC cable is heat resistant from -40 to 105C.
                                                                           PTFE cable (7/0.2)                 Color code                     PTFE cable is heat resistant from -40 to 250C.
   Included with 100 to 200C Models.
                                                                                                                                     * Use a 0 to 100C thermistor for 0 to 50C applications.
                                                   5-dia. max.
                                                                                                                                     Tolerance

                                                                                                                      10 Measured temperature                             Tolerance

                                                                                                              15  60                       -30 to 100C                   2C max.

                                        30                                                 500

                                                                                                                                           100 to 200C       Measured temperature 2% max.

    Mounting Brackets (Two)

   Temperature Sensors (Order Separately)

   E52-THE5A, E52-THE6D, and E52-THE6F Temperature Sensors can be ordered separately. For details, refer to an OMRON Web site.

4
                                                                                                         E5L
Operating the E5L-C@

                                                        Power ON

Setting Protection                                                                                       Press the                         Temperature Input Shift                    Direct/Reverse
                                                                                                         and Keys                                                                     Operation
                                 Press the                                                               for at least 1 s.                 Press the Key
                                 and Keys                                                                                                  for at least 3 s.         Press the Key
                                 for at least 1 s.
                                                                                                                                                                     for at least 3 s.

                                                                                                                            Process value

Set temperature                   Process value
display                           display

          Press the and Keys for at least 1 s.                                                                                                                  Press the Key for at least 3 s.

                                                                                                                                           Press the Key                                Control stops.
                                                                                                                                           for less than 1 s.

                                                                                                                                               Set
                                                                                                                                               temperature

                                                                                                                                           Press the Key
                                                                                                                                           for less than 1 s.

                                                                                                                                               Hysteresis

                                                                                                                                           Press the Key
                                                                                                                                           for less than 1 s.

Set temperature                                                                                                                            Setting the Temperature Input Shift

1. Press the Key to enter the Set Temperature Mode.                                                                                        1. Press the Key for at least 3 s to enter the Temperature Input
                                                                                                                                               Shift Mode.
2. Press the and Keys to set the temperature. The display
    will continue to change for as long as the key is held down.                                                                           2. Press the and Keys to set the value. Each time the key is
                                                                                                                                               pressed, the setting will change by 1C. The setting will not
Note: The default setting is the lowest temperature in the range.                                                                              continue to change as the key is held down. The key must be
                                                                                                                                               released after each change.
Setting the Hysteresis                                                                                                                         The input shift can be set from -9 to 9C, in increments of 1C.

1. Press the Key to enter the Hysteresis Mode.                                                                                             Note: 1. The default setting is 0C.
                                                                                                                                                   2. The control output turns OFF while this setting is being
2. Press the and Keys to set the value. Each time the key is                                                                                           made.
    pressed, the setting will change by 1C. The setting will not
    continue to change even if the key is held down. The key must be                                                                       Input shift display       Thermistor measured  Tempera-
    released after each change. The hysteresis can be set from 1 to                                                                                                        temperature    ture dis-
    9C, in increments of 1C.
                                                                                                                                                                                             play
Note: The default setting is 1C.

Hysteresis                                                                                               Display                           (No shift)                25C                               25C

          +1C

                                                                                                                                           (+9C shift)              25C                               34C

          +5C

                                                                                                                                           (-9C shift)              25C                               16C

          +9C

Reverse Operation (Heating Control) Direct Operation (Cooling Control)                                                                     Setting Direct or Reverse Operation

Control output (relay)                                                                                                                     1. Press the Key for at least 3 s to enter the Direct/Reverse
                                                                            Control output (relay)                                             Selection Mode.
          Hysteresis (1C set)                                                                           Hysteresis (1C set)
                                                                                                                                 Power ON  2. Press the and Keys to set the value. Direct operation can
Power ON
                                                                                                                                               be set by pressing the Key, and reverse operation can be set
                 OFF                                                                                OFF
                                                                                                                                               by pressing the Key.
Example:        Set temperature:                                                                    Set temperature                        Note: 1. The default setting is for reverse operation.
   64C                 65C                                                                         example: -5C
                                                                                                                                                   2. The control output turns OFF while this setting is being
                                                                                                                                                       made.

                                                                                                                     -4C

                                                                                                                                           Direct/reverse operation  Display

                                                                                                                                           Reverse operation

                                                                                                                                           Direct operation

                                                                                                                                                                                                                 5
   E5L

   Setting Protection

   1. Setting Protection (Process Value Display)
       Press the and Keys simultaneously while the process
       value is being displayed to change to the setting protection state.

   2. Setting Protection (Set Temperature Display)
       From the Setting Protection (process value display) Mode, press

       the and Keys simultaneously to change to the setting
       protection (set temperature display) state.
   3. From the Setting Protection (set temperature display) Mode, press

       the and Keys simultaneously to return to the process
       value display with no setting protection.

   Display example                         Display

   Process value display

        Set temperature display

   Note: 1. Setting protection disables key operations to prevent the
               settings from being changed accidentally. will be lit
               while protection is in effect.

           2. Protection will be maintained even when the power supply
               is turned OFF and ON.

   Error Displays and Causes

   E5L-A@

   When a thermistor disconnection occurs, the built-in relay operates at the OFF side (when NO contacts are used).

    Thermistor                     NO contacts                                         NC contacts
                        (Terminal numbers 8 and 12)                         (Terminal numbers 4 and 12)
   Disconnection
    Short-circuit                 * Heating load                                      * Cooling load

                                         OFF                                                  ON

                                         OFF                                                  ON

   E5L-C@

   When an error occurs, the display shows the error code. Take the necessary measures, referring to the following table.

        Display           Meaning                    Cause                                                                 Control output

        FFF (lit)       Overflow           The process value is higher than the set  Reverse operation: OFF
                                           temperature range.                        Direct operation: ON

        --- (lit)       Underflow          The process value is lower than the set   Reverse operation: ON
                                           temperature range                         Direct operation: OFF

        FFF (flashing)  Thermistor short-  The thermistor is short-circuited.        Reverse operation: OFF
                        circuited                                                    Direct operation: OFF

        --- (flashing)  Thermistor         The thermistor is disconnected.           Reverse operation: OFF
                        disconnected                                                 Direct operation: OFF

        E11 (lit)       Memory error       The thermostat has failed.                OFF

   Note: 1. Errors are not displayed while settings are being changed, except for memory errors. The control output status will be as shown in the
               above table while the set temperature or hysteresis is being set. The control output will be OFF while the temperature input shift or direct/
               reverse operation setting is being set. Key operations will be possible when an error occurs, except for a memory error.

           2. The setting protection indicator ( ) and set value indicator ("SV") will be continued even when settings are protected, except when a
               memory error occurs.

6
Safety Precautions                                                                                            E5L

                              CAUTION                                            Precautions for Safe Use

Do not touch the terminals while power is being supplied.       Be sure to observe the following precautions to prevent failure to
Doing so may occasionally result in minor injury due to         operate, malfunction, or adverse effects on the performance and
electric shock.                                                 functions of the Thermostat. Not doing so may occasionally result in
                                                                unexpected events.
Do not allow pieces of metal, wire clippings, or fine metallic  1. The Product is designed for indoor use only.
shavings or filings from installation to enter the Product.
Doing so may occasionally result in electric shock, fire, or         Do not use the Product outdoors or in any of the following
malfunction.                                                         locations.
                                                                  Locations directly subject to heat radiated from heating
Do not use the Product where subject to flammable or                 equipment
explosive gas. Otherwise, minor injury from explosion may         Locations subject to water or oil
occasionally occur.                                              Locations subject to direct sunlight
                                                                  Locations subject to dust or corrosive gas (in particular, sulfide
Never disassemble, modify, or repair the Product or touch            gas and ammonia gas)
any of the internal parts. Minor electric shock, fire, or         Locations subject to sudden or extreme temperature changes
malfunction may occasionally occur.                               Locations subject to icing or condensation
                                                                  Locations subject to vibration or shock
If the output relays are used past their life expectancy,       2. Use and store the Product within the rated temperature and
contact fusing or burning may occasionally occur. Always             humidity ranges. Provide forced cooling if required.
consider the application conditions and use the output          3. To allow heat to escape, do not block the area around the
relays within their rated load and electrical life expectancy.       Product.
The life expectancy of output relays varies considerably        4. Be sure to wire the Product properly with the correct terminal
with the output load and switching conditions.                       polarity.
                                                                5. Use the specified size of crimped terminals for wiring (M3.5, width
Tighten the terminal screws to between 0.74 and 0.90 Nm.            of 6.8 mm or less). To connect bare wires to the terminals, use
Loose screws may occasionally result in fire.                        copper wires with a gauge of AWG24 to AWG14 (equal to a
                                                                     cross-sectional area of 0.205 to 2.081 mm2). (The stripping length
Set the parameters and wiring of the Product so that they            is 5 to 6 mm.) Do not connect more than two wires or two crimp
are suitable for the system being controlled. Unexpected             terminals to one terminal. When connecting two wires, they must
operation may occasionally result in property damage or              be of the same size and type.
accidents.                                                      6. Do not connect anything to terminals that are not used.
                                                                7. Allow as much space as possible between the Thermostat and
A malfunction in the Product may occasionally make                   devices that generate powerful high frequencies or surges.
control operations impossible or prevent alarm outputs,              Separate the wiring to the Thermostat from high-voltage or high-
resulting in property damage. To maintain safety in the              current lines, and do not place the wiring to the Thermostat in
event of malfunction of the Product, take appropriate safety         parallel with or in the same wiring paths as power lines.
measures, such as installing a monitoring device on a           8. Use this Product within the rated load and power supply
separate line.                                                       specifications.
                                                                9. Turn ON the power supply at least 30 minutes prior to starting
                                                                     control operations.
                                                                10. A switch or circuit breaker must be provided close to the
                                                                     Thermostat. The switch or circuit breaker must be within easy
                                                                     reach of the operator, and must be marked as a disconnecting
                                                                     means for the Thermostat.
                                                                11. Do not use paint thinner or similar solvents to clean the
                                                                     Thermostat. Use standard grade alcohol.
                                                                12. Design the system (e.g., the control panel) considering the 2.5
                                                                     second of delay between turning ON the Thermostat and
                                                                     stabilization of the Thermostat's output.

                                                                                                                                         7
   E5L

           Precautions for Correct Use

   Mounting the Thermostat

   1. Using the PTF14A Socket or PTF14A-E Socket with Finger
       Protection, mount the Thermostat to the bracket that is provided.

   (4.6)               (4.6)

   (98.6)              (98.6)

           E5L+PTF14A         E5L+PTF14A-E

   2. The structure does not allow the case to be removed. Do not apply
       excessive force when mounting the Thermostat.

   Settings

   1. E5L-A@ Temperature Dial
    The temperature dial has some backlash. To adjust the

      temperature more accurately, turn the dial clockwise when
      adjusting the temperature.
    Do not change the setting of the temperature dial more than 20
      times.
    Do not attempt to turn the dial past the range of the setting scale.
      Applying excessive force may damage the Thermostat.
   2. E5L-A@ Hysteresis Dial
    This dial can be used to set hysteresis for the ON/OFF operation.
      Turn the dial clockwise to reduce the hysteresis and
      counterclockwise to increase the hysteresis. Increase the
      hysteresis to extend the life of the relay by preventing relay
      chattering caused by the control output turning ON and OFF
      frequently.
    Do not change the setting of the temperature dial more than 20
      times.

   Mounting the Thermistor

    Select a location for the temperature sensor of the thermistor
      where the temperature distribution of sensing objects will not be
      changed by installation.

    Insert the temperature sensor as far in as possible.
    When measuring fluid temperature, the thermistor should be

      installed against the current. Before mounting, take factors such as
      the bending moment of inertia and vibration into consideration.
    Do not apply mechanical force to the temperature-sensing part of
      the thermistor.
    The E52-THE@@ Thermistor can be used for applications that
      require metal protective tubing. Consult with your OMRON
      representative.

   Other Precautions

    Do not use the E5L-C@ if the front sheet is peeling or torn.
    Use appropriate tools to disassemble the Thermostat for disposal.

8
MEMO

                                           9
                                                                             MEMO

10
Warranty and Application Considerations

                                             Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.

                                                   Warranty and Limitations of Liability

WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or
other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER
ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET
THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED.

LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS,
OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,
INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE
MODIFICATION OR REPAIR.

                                                         Application Considerations

SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of
products in the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.

                                                                     Disclaimers

PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.

CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with
your OMRON representative at any time to confirm actual specifications of purchased product.

DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
OMRON Corporation                            OMRON ELECTRONICS LLC                          Authorized Distributor:
                                             One Commerce Drive Schaumburg,
Industrial Automation Company                IL 60173-5302 U.S.A.
                                             Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
Control Devices Division H.Q.
                                             OMRON ASIA PACIFIC PTE. LTD.
Analog Controller Division                   No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Shiokoji Horikawa, Shimogyo-ku,              Alexandra Technopark, Singapore 119967
Kyoto, 600-8530 Japan                        Tel: (65) 6835-3011/Fax: (65) 6835-2711
Tel: (81) 75-344-7080/Fax: (81) 75-344-7149
2-2-1 Nishikusatsu, Kusatsu-shi,
Shiga, 525-0035 Japan
Tel: (81) 77-565-5216/Fax: (81) 77-565-5568

Regional Headquarters                        OMRON (CHINA) CO., LTD.

OMRON EUROPE B.V.                            Room 2211, Bank of China Tower,                OMRON Corporation 2009 All Rights Reserved.
                                                                                            In the interest of product improvement,
Wegalaan 67-69-2132 JD Hoofddorp             200 Yin Cheng Zhong Road,                      specifications are subject to change without notice.

The Netherlands                              PuDong New Area, Shanghai, 200120, China

Tel: (31)2356-81-300/Fax: (31)2356-81-388    Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200                           Printed in Japan
                                                                                                                          0309 (0309)
OMRON Industrial Automation Global: www.ia.omron.com                                        Cat. No. H162-E1-01
This datasheet has been downloaded from:
            datasheet.eeworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company

小广播

E5LC-7器件购买:

该厂商的其它器件

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2017 EEWORLD.com.cn, Inc. All rights reserved