电子工程世界电子工程世界电子工程世界

产品描述

搜索
 

E5GN-R1TD ACDC24

器件型号:E5GN-R1TD ACDC24
器件类别:热门应用    机电/工控/自动化   
文件大小:61235.79KB,共17页
厂商名称:OMRON
厂商官网:https://www.omron.com
标准:
下载文档

器件描述

控制器 univ In relay out 1 aux srwl 24vac/vdc

参数
制造商: Omron
产品种类: 控制器
RoHS:
模拟/数字: Digital
控制方法: ON/OFF
类型: Digital Temperature Controller
显示器类型: 11-Segment, 4 Digit
电压额定值: 24 VAC, 24 VDC
安装: Panel
大小: 99 mm x 48 mm x 35 mm
特点: Compatible with Support Software (CX-Thermo version 4.2 or higher)
输入类型: Thermocouple
输出类型: Relay

E5GN-R1TD ACDC24器件文档内容

Basic-type Digital Temperature Controller

E5GN (48 x 24 mm)

                                                                                                                             CSM_E5GN_DS_E_5_1

New 48 x 24-mm Basic Temperature
Controller with Enhanced Functions and
Performance. Improved Indication
Accuracy and Preventive Maintenance
Function.

Indication Accuracy                                                              E5GN                                  E5GN--@-C
Thermocouple input: 0.3% of PV (previous models: 0.5%)          Models with Screw Terminal               Models with Screwless Clamp
Pt input: 0.2% of PV (previous models: 0.5%)
Analog input: 0.2% FS (previous models: 0.5%)                                  Blocks                             Terminal Blocks
                                                                               48 24 mm                                48 24 mm

Models are available with screw terminal blocks or screwless

clamp terminal blocks.

A PV/SV-status display function can be set to automatically          Refer to Safety Precautions for E5@N/E5@N-H.
alternate between displaying the status of the Temperature

Controller (auto/manual, RUN/STOP, and alarms) and the PV or SV.  Refer to Operation for E5@N/E5@N-H for operating
Preventive maintenance for relays in the Temperature Controller  procedures.

using a Control Output ON/OFF Counter.

Switch the PV display between three colors.

Compatible with Support Software (CX-Thermo version 4.2 or higher).

Eleven-segment displays.

Models are available with one or two alarm outputs.

Main I/O Functions

                            Event Inputs  E5GN
                            None
                            Two                              Dual Display: PV and SV                      4-digit Display

Sensor Inputs                                                                            Auxiliary Outputs   Auto/manual switching
Universal thermocouple/Pt inputs                                                       None             Temperature Controller status display
                                                                                          One               Simple program function
(Models with temperature inputs)                                                         Two               Control output ON/OFF count alarm
Analog current/voltage inputs                                                                              PV change rate alarm
                                          Control Output 1                                                   Models also available with RS-232C
(Models with analog inputs)               Relay output
                                           Voltage output (for driving SSR)                                 communications
Indication Accuracy                        Current output                                                   Models also available with RS-485
Thermocouple input: 0.3% of PV
Pt input: 0.2% of PV                                                                                      communications
Analog input: 0.2% FS

Sampling Period
250 ms

This datasheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156)
E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158)

                                                                                 1
                                                                                                                E5GN

Lineup

E5GN                        Screw terminal block             Temperature input  1 control output                0, 1, or 2 auxiliary
                                                                 Analog input   1 control output                outputs
Basic Type                    Screwless clamp                                   1 control output
                                terminal block               Temperature input  1 control output                0, 1, or 2 auxiliary
                                                                Analog input                                    outputs

                                                                                                                0, 1, or 2 auxiliary
                                                                                                                outputs

                                                                                                                0, 1, or 2 auxiliary
                                                                                                                outputs

Note: Models with one control output and one or two auxiliary outputs can be used for heating/cooling control.

Model Number Structure

Model Number Legend                                          4. Input Type
                                                                 T: Universal thermocouple/platinum resistance thermometer input
Controllers                                                      L: Analog current/voltage input

  E5GN-@@@@@-@-@-@                                           5. Power Supply Voltage
                                                                 Blank: 100 to 240 VAC
                  12345 6 7 8                                    D: 24 VAC/VDC

1. Control Output 1                                          6. Terminal Type
    R: Relay output                                              Blank: Models with screw terminal block
    Q: Voltage output (for driving SSR)                          C: Models with screwless clamp terminal block
    C: Linear current output
                                                             7. Case Color
2. Auxiliary Outputs                                             Blank: Black
    Blank: None
    1: One output
    2: Two outputs

3. Option                                                    8. Communications Protocol

Blank: None                                                  Blank: None

01: RS-232C communications                                   FLK: CompoWay/F serial communications

03: RS-485 communications

B: Two event inputs

H: Heater burnout/Heater short/Heater overcurrent detection
    (CT1)

Note: Models cannot be made for all combinations of options that are possible in the model number legend. Confirm model availability in Ordering
        Information before ordering.

* Auxiliary outputs are relay outputs that can be used for output alarms or processing results.

Supply Voltage Suffixes for Ordering
For 100 to 240 VAC, add a "AC100240" suffix.

For 24 VAC/VDC models, add a "ACDC24" suffix.

                                                                                                                                                  2
                                                                                                                                                 E5GN

Ordering Information

Controllers with Screw Terminal Blocks

Models with Temperature Inputs

Models with One Control Output and a 100 to 240-VAC Power Supply (Add AC100240 to the Model number.)

                                                                  Detection of                                               Previous model
                                                                      heater
Case color  Control  Control                            No. of                   No. of event  Transfer      Communi-   Thermocou-   Resistance  New model
            output   mode *1                           auxiliary    burnout,         inputs    output *2       cations    ple input  thermome-
                                                       outputs    SSR failure,                                                                   E5GN-RT
                                                                   and heater                                                         ter input  E5GN-R1T
                                                                  overcurrent                                                                    E5GN-R1BT
                                                                                                                                                 E5GN-
                     Standard     ---                                            ---                                    E5GN-RTC E5GN-RP         R101T-FLK
                                                                                                                                                 E5GN-
                                                                                                             ---        E5GN-R1TC E5GN-R1P       R103T-FLK
                                                                                                                                                 E5GN-R2T
                                                                                 2                                      ---          ---
                                                                                                                                                 E5GN-R2HT
                                  1                               ---                                        RS-232C ---             ---
                                                                                                                                                 E5GN-R2BT
                                                                                                             RS-485     E5GN         E5GN        E5GN-
                                                                                                                                                 R203T-FLK
            Relay output Standard or                                             ---           ---                      -R03TC-FLK -R03P-FLK     E5GN-QT
                                heating/                                                                                                         E5GN-Q1T
                                cooling                                                                                 ---          ---         E5GN-Q1BT
                                                                                                                                                 E5GN-
                                                    2             Detection for                              ---        ---          ---         Q101T-FLK
                                                                  single-phase                                                                   E5GN-
                                                                  heaters                                                                        Q103T-FLK
                                                                                                                                                 E5GN-Q2T
                                                                                      2                                 ---          ---
                                                                  ---                                                                            E5GN-Q2HT
                                                                                                             RS-485     ---          ---
                                                                                      ---                                                        E5GN-Q2BT
                                                                                                                                                 E5GN-
                     Standard     ---                                            ---                                    E5GN-QTC E5GN-QP         Q203T-FLK
                                                                                                                                                 E5GN-C1T
                                                                                                             ---        E5GN-Q1TC E5GN-Q1P       E5GN-C1BT
                                                                                                             RS-232C                             E5GN-
Black                                                                            2                                      ---          ---         C101T-FLK
                                                                                                                                                 E5GN-
                                  1                               ---                                                   ---          ---         C103T-FLK

            Voltage                                                                                          RS-485     E5GN         E5GN
            output (for Standard or
            driving SSR) heating/                                                ---           ---                      -Q03TC-FLK -Q03P-FLK

                                cooling                                                                                 ---          ---
                                                    2
                                                                  Detection for                              ---        ---          ---
                                                                  single-phase
                                                                  heaters

                                                                                 2                                      ---          ---

                                                                  ---                                        RS-485     ---          ---
                                                                                      ---

                                                                                 ---                         ---        ---          ---

                     Standard or                                                 2             Transfer                 ---          ---

            Current  heating/     1                               ---                          output using  RS-232C ---             ---
            output
                     cooling                                                                   control

                                                                                 ---           output

                                                                                                             RS-485     ---          ---

*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that
     can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.

*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible
     for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease
     by one.

                                                                                                                                                            3
                                                                                                                                                 E5GN

Models with One Control Output and a 24-VAC/VDC Power Supply (Add ACDC24 to the Model number.)

                                                                  Detection of                                               Previous model
                                                                      heater
Case color  Control  Control                            No. of                   No. of event  Transfer      Communi-   Thermocou-   Resistance   New model
            output   mode *1                           auxiliary    burnout,         inputs    output *2       cations    ple input  thermome-
                                                       outputs    SSR failure,                                                                   E5GN-RTD
                                                                   and heater                                                         ter input  E5GN-R1TD
                                                                  overcurrent                                                                    E5GN-R1BTD
                                                                                                                                                 E5GN
                     Standard     ---                                            ---                                    E5GN-RTC E5GN-RP         -R101TD-FLK
                                                                                                                                                 E5GN
                                                                                                             ---        E5GN-R1TC E5GN-R1P       -R103TD-FLK
                                                                                                                                                 E5GN-R2TD
                                                                                 2                                      ---          ---
                                                                                                                                                 E5GN-R2HTD
                                  1                               ---                                        RS-232C ---             ---
                                                                                                                                                 E5GN-R2BTD
                                                                                                             RS-485     E5GN         E5GN        E5GN
                                                                                                                                                 -R203TD-FLK
            Relay output Standard or                                             ---           ---                      -R03TC-FLK -R03P-FLK     E5GN-QTD
                                heating/                                                                                                         E5GN-Q1TD
                                cooling                                                                                 ---          ---         E5GN-
                                                                                                                                                 Q1BTD
                                                    2             Detection for                              ---        ---          ---         E5GN-
                                                                  single-phase                                                                   Q101TD-FLK
                                                                  heaters                                                                        E5GN
                                                                                                                                                 -Q103TD-FLK
                                                                                 2                                      ---          ---         E5GN-Q2TD

                                                                  ---                                        RS-485     ---          ---         E5GN-
                                                                                      ---                                                        Q2HTD

                     Standard     ---                                            ---                                    E5GN-QTC E5GN-QP         E5GN-
                                                                                                                                                 Q2BTD
                                                                                                             ---        E5GN-Q1TC E5GN-Q1P       E5GN
                                                                                                                                                 -Q203TD-FLK
                                                                                 2                                      ---          ---         E5GN-C1TD
                                                                                                                                                 E5GN-C1BTD
Black                                                                                                                                            E5GN
                                                                                                                                                 -C101TD-FLK
                                  1                               ---                                        RS-232C ---             ---         E5GN
                                                                                                                                                 -C103TD-FLK
            Voltage                                                                                          RS-485     E5GN         E5GN
            output (for Standard or
            driving SSR) heating/                                                ---           ---                      -Q03TC-FLK -Q03P-FLK

                                cooling                                                                                 ---          ---
                                                    2
                                                                  Detection for                              ---        ---          ---
                                                                  single-phase
                                                                  heaters

                                                                                      2                                 ---          ---
                                                                  ---
                                                                                                             RS-485     ---          ---
                                                                                      ---

                                                                                 ---                         ---        ---          ---

                     Standard or                                                 2             Transfer                 ---          ---

            Current  heating/     1                               ---                          output using  RS-232C ---             ---
            output
                     cooling                                                                   control

                                                                                 ---           output

                                                                                                             RS-485     ---          ---

*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that
     can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.

*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible
     for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease
     by one.

                                                                                                                                                              4
                                                                                                                                   E5GN

Models with Analog Inputs

Models with One Control Output and a 100 to 240-VAC Power Supply (Add AC100240 to the Model number.)

                                                     Detection of                                              Previous model
                                                         heater
Case color  Control       Control          No. of                  No. of event  Transfer      Communi-   Thermocou-   Resistance  New model
            output        mode *1         auxiliary    burnout,        inputs    output *2       cations    ple input  thermome-
                                          outputs    SSR failure,
                                                      and heater                                                        ter input
                                                     overcurrent

            Relay output                                                                                  ---          ---         E5GN-
                                                                                                                                   R103L-FLK

            Voltage                                                              ---           RS-485                              E5GN-
                                                                                                                                   Q103L-FLK
            output (for Standard or                                                                       ---          ---

Black       driving SSR) heating/      1             ---           ---

                          cooling                                                Transfer

            Current                                                              output using  ---        ---          ---         E5GN-C1L
            output                                                               control

                                                                                 output

Note: Models with analog inputs do not display the temperature unit.

*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that
     can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.

*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible
     for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease
     by one.

Models with One Control Output and a 24-VAC/VDC Power Supply (Add ACDC24 to the Model number.)

                                                     Detection of                                              Previous model
                                                         heater
Case color  Control       Control          No. of                  No. of event  Transfer      Communi-   Thermocou-   Resistance   New model
            output        mode *1         auxiliary    burnout,        inputs    output *2       cations    ple input  thermome-
                                          outputs    SSR failure,                                                                  E5GN-
                                                      and heater                                                        ter input  R103LD-FLK
                                                     overcurrent                                                                   E5GN
                                                                                                                                   -Q103LD-FLK
            Relay output                                                                                  ---          ---
                                                                                                                                   E5GN-C1LD
            Voltage       Standard or                                            ---           RS-485
            output (for   heating/
            driving SSR)  cooling                                                                         ---          ---

Black                                  1             ---           ---

                                                                                 Transfer

            Current                                                              output using  ---        ---          ---
            output                                                               control

                                                                                 output

*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that
     can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.

*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible
     for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease
     by one.

                                                                                                                                                         5
                                                                                                                                                E5GN

Controllers with Screwless Clamp Terminal Blocks

Models with Temperature Inputs

Models with One Control Output and a 100 to 240-VAC Power Supply (Add AC100240 to the Model number.)

                                                                  Detection                                                 Previous model
                                                                   of heater
Case color  Control  Control                           No. of      burnout,     No. of event  Transfer      Communic   Thermocou-   Resistance  New model
            output   mode *1                          auxiliary  SSR failure,      inputs     output *2        ations    ple input  thermome-
                                                      outputs    and heater
                                                                 overcurrent                                                         ter input

                     Standard ---                                               ---                                    E5GN-RTC E5GN-RP E5GN-RT-C

                                                                                                            ---        E5GN-R1TC E5GN-R1P E5GN-R1T-C

                                                                                2                                      ---          ---         E5GN-R1BT-C

                                  1                              ---                                        RS-232C ---             ---         E5GN
                                                                                                                                                -R101T-C-FLK

                                                                                                            RS-485     E5GN         E5GN        E5GN

            Relay output Standard or                                                                                   -R03TC-FLK -R03P-FLK -R103T-C-FLK
                               heating/
                               cooling                                          ---           ---                      ---          ---         E5GN-R2T-C

                                                   2             Detection for                              ---        ---          ---         E5GN-R2HT-C
                                                                 single-
                                                                 phase
                                                                 heaters

                                                                                    2                                  ---          ---         E5GN-R2BT-C
                                                                 ---
                                                                                                            RS-485     ---          ---         E5GN
                                                                                    ---                                                         -R203T-C-FLK

                     Standard ---                                               ---                                    E5GN-QTC E5GN-QP E5GN-QT-C

                                                                                                            ---        E5GN-Q1TC E5GN-Q1P E5GN-Q1T-C

Black                                                                           2                                      ---          ---         E5GN-Q1BT-C

                                  1                              ---                                        RS-232C ---             ---         E5GN
                                                                                                                                                -Q101T-C-FLK

                                                                                                            RS-485     E5GN         E5GN        E5GN

            Voltage                                                                                                    -Q03TC-FLK -Q03P-FLK -Q103T-C-FLK
            output (for Standard or
            driving SSR) heating/                                               ---           ---                      ---          ---         E5GN-Q2T-C

                               cooling                           Detection for                              ---        ---          ---         E5GN-Q2HT-C
                                                   2             single-
                                                                 phase
                                                                 heaters

                                                                                2                                      ---          ---         E5GN-Q2BT-C

                                                                 ---                                        RS-485     ---          ---         E5GN
                                                                                    ---                                                         -Q203T-C-FLK

                                                                                ---                         ---        ---          ---         E5GN-C1T-C

                     Standard or                                                2             Transfer                 ---          ---         E5GN-C1BT-C

            Current  heating/     1                                                           output using  RS-232C ---             ---         E5GN
            output                                                                                                                              -C101T-C-FLK
                     cooling                                                                  control

                                                                                ---           output                                            E5GN
                                                                                                                                                -C103T-C-FLK
                                                                                                            RS-485     ---          ---

*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that
     can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.

*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible
     for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease
     by one.

                                                                                                                                                              6
                                                                                                                                                  E5GN

Models with One Control Output and a 24-VAC/VDC Power Supply (Add ACDC24 to the Model number.)

                                                           Detection                                                          Previous model
                                                           of heater
Case color  Control      Control                No. of     burnout,                     No. of  Transfer      Communic   Thermocou-   Resistance     New model
            output       mode *1               auxiliary                                event   output *2        ations    ple input  thermome-
                                               outputs        SSR                       inputs                                                    E5GN-RTD-C
                                                          failure, and                                                                 ter input  E5GN-R1TD-C
                                                                                                                                                  E5GN-R1BTD-C
                                                             heater                                                                               E5GN
                                                          overcurren                                                                              -R101TD-C-FLK
                                                                                                                                                  E5GN
                                                                 t                                                                                -R103TD-C-FLK
                                                                                                                                                  E5GN-R2TD-C
                         Standard ---                                   ---                                              E5GN-RTC E5GN-RP
                                                                                                                                                  E5GN-R2HTD-C
                                                                                                              ---        E5GN-R1TC E5GN-R1P
                                                                                                                                                  E5GN-R2BTD-C
                                                                        2                                                ---          ---         E5GN
                                                                                                                                                  -R203TD-C-FLK
                                      1                   ---                                                 RS-232C ---             ---         E5GN-QTD-C
                                                                                                                                                  E5GN-Q1TD-C
                                                                                                              RS-485     E5GN         E5GN        E5GN-Q1BTD-C
                                                                                                                                                  E5GN
            Relay        Standard or                                                                                     -R03TC-FLK -R03P-FLK     -Q101TD-C-FLK
            output       heating/                                                                                                                 E5GN
                         cooling                                        ---                     ---                      ---          ---         -Q103TD-C-FLK
                                                                                                                                                  E5GN-Q2TD-C
                                            2             Detection                                           ---        ---          ---
                                                          for single-                                                                             E5GN-Q2HTD-C
                                                          phase
                                                          heaters                                                                                 E5GN-Q2BTD-C
                                                                                                                                                  E5GN
                                                                        2                                                ---          ---         -Q203TD-C-FLK
                                                                                                                                                  E5GN-C1TD-C
                                                          ---                                                 RS-485     ---          ---         E5GN-C1BTD-C
                                                                             ---                                                                  E5GN
                                                                                                                                                  -C101TD-C-FLK
                         Standard ---                                                                                    E5GN-QTC E5GN-QP         E5GN
                                                                                   ---                                                            -C103TD-C-FLK
                                                                                                              ---        E5GN-Q1TC E5GN-Q1P
                                                                                                              RS-232C
Black                                                                   2                                                ---          ---

                                      1                   ---                                                            ---          ---

            Voltage                                                                                           RS-485     E5GN         E5GN
            output (for
            driving      Standard or                                                                                     -Q03TC-FLK -Q03P-FLK
            SSR)         heating/
                         cooling                                        ---                     ---                      ---          ---

                                                          Detection                                           ---        ---          ---
                                                          for single-
                                      2                   phase
                                                          heaters

                                                                        2                                                ---          ---

                                                          ---                                                 RS-485     ---          ---
                                                                             ---

                                                                        ---                                   ---        ---          ---

                         Standard or                                    2                       Transfer                 ---          ---
                                                                                                                                      ---
            Current      heating/     1                   ---                                   output using  RS-232C ---
            output
                         cooling                                                                control

                                                                        ---                     output

                                                                                                              RS-485     ---          ---

*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that
     can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.

*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible
     for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease
     by one.

                                                                                                                                                                 7
                                                                                                                                            E5GN

Models with Analog Inputs

Models with One Control Output and a 100 to 240-VAC Power Supply (Add AC100240 to the Model number.)

                                                               Detection of                                             Previous model
                                                                   heater
Case color  Control  Control                         No. of                  No. of event  Transfer      Communi   Thermocou-   Resistance  New model
            output   mode *1                        auxiliary    burnout,        inputs    output *2      cations    ple input  thermome-
                                                    outputs    SSR failure,
                                                                and heater                                                       ter input
                                                               overcurrent

                     Standard or                                                           Transfer

Black       Current  heating/                    1             ---           ---           output using  ---       ---          ---         E5GN-C1L-C
            output                                                                         control
                     cooling
                                                                                           output

Note: Models with analog inputs do not display the temperature unit.
*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that

     can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.
*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible

     for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease

     by one.

Models with One Control Output and a 24-VAC/VDC Power Supply (Add ACDC24 to the Model number.)

                                                               Detection of                                             Previous model
                                                                   heater
Case color  Control  Control                         No. of                  No. of event  Transfer      Communi   Thermocou-   Resistance   New model
            output   mode *1                        auxiliary    burnout,        inputs    output *2      cations    ple input  thermome-
                                                    outputs    SSR failure,                                                                 E5GN-C1LD-
                                                                and heater                                                       ter input  C
                                                               overcurrent

                     Standard or                                                           Transfer

Black       Current  heating/                    1             ---           ---           output using  ---       ---          ---
            output                                                                         control
                     cooling
                                                                                           output

*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that
     can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.

*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible
     for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease

     by one.

Accessories (Order Separately)

USB-Serial Conversion Cable

                        Model
                     E58-CIFQ1

Waterproof Packing

                                         Model
                                        Y92S-32

Current Transformers (CTs)                           Model
                                                    E54-CT1
           Hole diameter                            E54-CT3
                5.8 dia.
               12.0 dia.

CX-Thermo Support Software

                                         Model
                                    EST2-2C-MV4
Note: The E5GN is supported by CX-Thermo version 4.2 and higher.

                                                                                                                                                         8
                                                                                                                      E5GN

Specifications

Ratings

Power supply voltage          No D in model number: 100 to 240 VAC, 50/60 Hz
                              D in model number: 24 VAC, 50/60 Hz; 24 VDC

Operating voltage range       85% to 110% of rated supply voltage

Power      E5GN               100 to 240 VAC: 5.5 VA (max.)
consump-   Screw terminal     24 VAC/VDC: 3 VA/2 W (max.)
tion       block
                              100 to 240 VAC: 5.5 VA (max.)
           E5GN-@-C           24 VAC/VDC: 3 VA/2 W (max.)
           Screwless clamp
           terminal block

Sensor input                  Models with temperature inputs
                                Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
                                Platinum resistance thermometer: Pt100 or JPt100
                                Infrared temperature sensor: 10 to 70C, 60 to 120C, 115 to 165C, or 140 to 260C
                                Voltage input: 0 to 50 mV

                              Models with analog inputs
                                Current input: 4 to 20 mA or 0 to 20 mA
                                Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V

Input impedance               Current input: 150  max., Voltage input: 1 M min. (Use a 1:1 connection when connecting the ES2-HB.)

Control method                ON/OFF control or 2-PID control (with auto-tuning)

Control    Relay output       SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V,
outputs                       10 mA
           Voltage output
           (for driving SSR)  Output voltage: 12 VDC 15% (PNP), max. load current: 21 mA, with short-circuit protection circuit

           Current output     4 to 20 mA DC/0 to 20 mA DC, load: 500  max., resolution: approx. 10,000

Auxiliary  Number of outputs 1 or 2 max. (Depends on the model.)
outputs
           Output             Relay output: SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum
           specifications     applicable load: 5 V, 10 mA

           Number of inputs 2

Event      External contact   Contact input: ON: 1 k max., OFF: 100 k min.
inputs     input              Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
           specifications     Current flow: Approx. 7 mA per contact

Setting method                Digital setting using front panel keys

Indication method             11-segment digital display and individual indicators (7-segment display also possible)
                              Character height: PV: 7.5 mm, SV: 3.6 mm

Multi SP                      Up to four set points (SP0 to SP3) can be saved and selected using event inputs, key operations, or serial
                              communications.

Bank switching                Not supported

Other functions               Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout
                              detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop,
                              protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, logic
                              operations, PV/SV status display, simple program, automatic cooling coefficient adjustment

Ambient operating temperature -10 to 55C (with no condensation or icing), for 3-year warranty: -10 to 50C

Ambient operating humidity    25% to 85%

Storage temperature           -25 to 65C (with no condensation or icing)

                                                                                                                                             9
                                                                                                                                                                                                       E5GN

Input Ranges

Thermocouple/Platinum Resistance Thermometer (Universal Inputs)

Input                           Platinum resistance                                                      Thermocouple                                                            Infrared temperature    Analog
Type                                 thermometer                                                                                                                                          sensor           input
                                                                                                                                                                                                            0 to
Name                                   Pt100         JPt100               K             J        T       EL           U             N   R  S  B    W                       PL    10 to  60 to  115  140   50 mV
                                                                                                                                                                            II   70C   120     to   to
                                                                                                                                                                                         C    165  260  Usable
                                                                                                                                                                                               C   C   in the
                                                                                                                                                                                                         following
                        2300                                                                                                                                         2300                                ranges
                        1800                                                                                                                               1800                                          by
                        1700                                                                                                            1700 1700                                                        scaling:
                                                                                                                                                                                                         -1999 to
                        1600                                                                                                                                                                             9999 or
                                                                                                                                                                                                         -199.9
                        1500                                                                                                                                                                             to 999.9

                        1400                                        1300                                                         1300                                      1300                              23
                        1300
Temperature range (C)
                        1200

                        1100

                        1000                                                       850                          850
                                  850

                         900

                        800

                        700                                                                              600

                        600            500.0         500.0                500.0

                        500                                                             400.0 400 400.0               400 400.0

                        400                                                                                                                                                                         260

                        300                                                                                                                                                             120 165

                        200                   100.0          100.0                                                                                                               90

                        100                                                                                                                   100

                        0                     0.0            0.0                                                                        0  0       0                       0     0      0      0    0

                        -100.0                                            -20.0 -100 -20.0                      -100

                        -200.0 -200 -199.9           -199.9         -200                      -200 -199.9 -200        -200 -199.9 -200

Setting                         0      1      2      3          4   5        6     7       8  9 10 11 12 13 14 15 16 17 18 24 25 19 20 21 22
number

Shaded settings are the default settings.
The applicable standards for the input types are as follows:
K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
W: W5Re/W26Re, ASTM E988-1990
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)

Models with Analog Inputs

                                Input Type                                Current                                  Voltage

Input specification                                          4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V

Setting range                                                Usable in the following ranges by scaling:
                                                             -1999 to 9999, -199.9 to 999.9, -19.99 to 99.99 or -1.999 to 9.999

Setting number                                               0                  1             2                 3                4

Shaded settings are the default settings.

                                                                                                                                                                                                                    10
                                                                                                                                                                 E5GN

Alarm Outputs

Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit.
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.

Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the
        following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR
        failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).

                                                                                       Alarm output operation

Set value                     Alarm type                                          When alarm value When alarm value                     Description of function

                                                                                      X is positive       X is negative

0                Alarm function OFF                                               Output OFF                                  No alarm
1 *1             Upper- and lower-limit
                                                                                  ON     LH                                   Set the deviation in the set point by setting the alarm
                                                                                                                              upper limit (H) and alarm lower limit (L).
                                                                                  OFF    SP          *2

                                                                                  ON        X                  X              Set the upward deviation in the set point by setting
                                                                                                                              the alarm value (X).
2                Upper-limit                                                      OFF                     ON
                                                                                                                              Set the downward deviation in the set point by setting
                                                                                         SP               OFF  SP             the alarm value (X).

                                                                                  ON     X                                X

3                Lower-limit                                                      OFF                     ON

                                                                                         SP               OFF  SP

                                                                                  ON     LH                                   Set the deviation in the set point by setting the alarm
                                                                                                                              upper limit (H) and alarm lower limit (L).
4 *1             Upper- and lower-limit range                                     OFF                *3

                                                                                         SP

5 *1             Upper- and lower-limit with                                      ON     LH          *4                       A standby sequence is added to the upper- and
6                standby sequence                                                 OFF     SP                                  lower-limit alarm (1). *6

                                                                                  *5                                          A standby sequence is added to the upper-limit alarm
                                                                                                                              (2). *6
                 Upper-limit with standby sequence                                ON       X                           X
                                                                                  OFF    SP               ON

                                                                                                          OFF  SP

7                Lower-limit with standby sequence                                ON     X                                 X  A standby sequence is added to the lower-limit alarm
                                                                                  OFF     SP              ON                  (3). *6

                                                                                                          OFF  SP

8                Absolute-value upper-limit                                       ON     X                ON   X              The alarm will turn ON if the process value is larger
                                                                                                          OFF      0          than the alarm value (X) regardless of the set point.
                                                                                  OFF 0
                                                                                                          ON   X              The alarm will turn ON if the process value is smaller
9                Absolute-value lower-limit                                       ON     X                OFF      0          than the alarm value (X) regardless of the set point.

                                                                                  OFF 0                   ON   X              A standby sequence is added to the absolute-value
                                                                                                          OFF      0          upper-limit alarm (8). *6
10               Absolute-value upper-limit with                                  ON     X
                 standby sequence
                                                                                  OFF 0

                 Absolute-value lower-limit with                                  ON     X                ON   X              A standby sequence is added to the absolute-value
                 standby sequence                                                                         OFF      0          lower-limit alarm (9). *6
11                                                                                OFF 0

12               LBA (alarm 1 type only)                                                             ---                           *7

13               PV change rate alarm                                                                ---                           *8

*1. With set values 1, 4 and 5, the upper and lower limit values can                                           *5. Set value: 5, Upper- and lower-limit with standby sequence
     be set independently for each alarm type, and are expressed as                                                 Always OFF when the upper-limit and lower-limit hysteresis
                                                                                                                    overlaps.
     "L" and "H."
*2. Set value: 1, Upper- and lower-limit alarm                                                                 *6. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature
                                                                                                                    Controllers User's Manual Basic Type (Cat. No. H156) for
Case 1           Case 2           Case 3 (Always ON)                                                                information on the operation of the standby sequence.

       L H SP    SP L H                     H SP L                                H < 0, L < 0                 *7. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature
                                          H L SP                                                                    Controllers User's Manual Basic Type (Cat. No. H156) for
   H < 0, L > 0  H > 0, L < 0                                                     H < 0, L > 0                      information on the loop burnout alarm (LBA).
   H < L         H > L                                                            H  L
                                                                                  H > 0, L < 0                 *8. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature
                                                                          SP H L  H  L                              Controllers User's Manual Basic Type (Cat. No. H156) for
                                                                                                                    information on the PV change rate alarm.
*3. Set value: 4, Upper- and lower-limit range

Case 1           Case 2           Case 3 (Always OFF)                             H < 0, L < 0
                                         H SP L
       L H SP      SP L H                                                         H < 0, L > 0
  H < 0, L > 0      H > 0, L < 0      H L SP                                      H  L
   H < L            H > L

                                              SP H L                              H > 0, L < 0
                                                                                  H  L

*4. Set value: 5, Upper- and lower-limit with standby sequence
     For Upper- and Lower-Limit Alarm Described Above

    Case 1 and 2
     Always OFF when the upper-limit and lower-limit hysteresis
     overlaps.

    Case 3: Always OFF

                                                                                                                                                                                       11
                                                                                                                 E5GN

Characteristics

Indication accuracy             Thermocouple: *1
                                  (0.3% of indicated value or 1C, whichever is greater) 1 digit max.
Influence of temperature *2
                                Platinum resistance thermometer input:
Influence of voltage *2           (0.2% of indicated value or 0.8C, whichever is greater) 1 digit max.

Input sampling period           Analog input:
Hysteresis                        0.2% FS 1 digit max.

Proportional band (P)           CT input:
                                  5% FS 1 digit max.
Integral time (I)
                                Thermocouple input (R, S, B, W, PL II):
Derivative time (D)               (1% of PV or 10C, whichever is greater) 1 digit max.

Control period                  Other thermocouple input: *3
                                  (1% of PV or 4C, whichever is greater) 1 digit max.
Manual reset value
                                Platinum resistance thermometer input:
Alarm setting range               (1% of PV or 2C, whichever is greater) 1 digit max.

Affect of signal source         Analog input:
resistance                        (1%FS) 1 digit max.

Insulation resistance           250 ms

Dielectric strength             Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4
                                Models with analog input: 0.01 to 99.99% FS (in units of 0.01% FS)
Vibration          Malfunction
resistance         Destruction  Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4
                                Models with analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Shock              Malfunction
resistance         Destruction  0 to 3999 s (in units of 1 s)

Weight                          0 to 3999 s (in units of 1 s) *5

Degree of protection            0.5, 1 to 99 s (in units of 1 s)

Memory protection               0.0 to 100.0% (in units of 0.1%)

Setup Tool                      -1999 to 9999 (decimal point position depends on input type)

Setup Tool port                 Thermocouple: 0.1C/ max. (100  max.)
                                Platinum resistance thermometer: 0.1C/ max. (10  max.)
                   Approved
                   standards    20 M min. (at 500 VDC)

                   Conformed    2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
                   standards
                                10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions

                                10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions

                                100 m/s2, 3 times each in X, Y, and Z directions

                                300 m/s2, 3 times each in X, Y, and Z directions

                                Controller: Approx. 90 g, Mounting Bracket: Approx. 10 g

                                Front panel: IP66, Rear case: IP20, Terminals: IP00

                                Non-volatile memory (number of writes: 1,000,000 times)

                                CX-Thermo version 4.2 or higher

                                Provided on the side of the E5GN. Connect this port to the computer when using the Setup Tool. An E58-CIFQ1 USB-Serial
                                Conversion Cable is required to connect the computer to the port on the side of the E5GN. *6

                                UL 61010-1, CSA C22.2 No. 1010-1

Standards

                                EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II

                                EMI:                                      EN 61326

                                Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A

                                Noise Terminal Voltage:                   EN 55011 Group 1, class A

                                EMS:                                      EN 61326

                                ESD Immunity:                             EN 61000-4-2

EMC                             Electromagnetic Field Immunity:           EN 61000-4-3

                                Burst Noise Immunity:                     EN 61000-4-4

                                Conducted Disturbance Immunity:           EN 61000-4-6

                                Surge Immunity:                           EN 61000-4-5

                                Power Frequency Magnetic Field Immunity:  EN 61000-4-8

                                Voltage Dip/Interrupting Immunity:        EN 61000-4-11

*1. The indication accuracy of K thermocouples in the -200 to 1300C range, T and N thermocouples at a temperature of -100C max., and U
     and L thermocouples at any temperatures is 2C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400C max.
     is not specified. The indication accuracy of B thermocouples in the 400 to 800C range is 3C max. The indication accuracy of the R and S
     thermocouples at a temperature of 200C max. is 3C 1 digit max. The indication accuracy of W thermocouples is 0.3 of PV or 3C,
     whichever is greater, 1 digit max. The indication accuracy of PL II thermocouples is 0.3 of PV or 2C, whichever is greater, 1 digit max.

*2. Ambient temperature: -10C to 23C to 55C, Voltage range: -15% to 10% of rated voltage
*3. K thermocouple at -100C max.: 10 max.
*4. "EU" stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is C or F.
*5. When robust tuning (RT) is ON, the differential time is 0.0 to 999.9 (in units of 0.1 s).

*6. External serial communications (RS-232C or RS-485) and cable communications for the Setup Tool can be used at the same time.

                                                                                                                                                           12
                                                                                                                                                               E5GN

USB-Serial Conversion Cable                                                 Current Transformer (Order Separately)
                                                                            Ratings
Applicable OS        Windows 2000, XP, or Vista

Applicable software CX-Thermo version 4 or higher                           Dielectric strength 1,000 VAC for 1 min

Applicable models    E5AN/E5EN/E5CN/E5CN-U/E5AN-H/                          Vibration resistance 50 Hz, 98 m/s2
                     E5EN-H/E5CN-H/E5GN
                                                                                                                           E54-CT1: Approx. 11.5 g,
USB interface standard Conforms to USB Specification 1.1.                   Weight                                         E54-CT3: Approx. 50 g

DTE speed            38400 bps                                              Accessories                                    Armatures (2)
                                                                            (E54-CT3 only)                                 Plugs (2)
                     Computer: USB (type A plug)
Connector            Temperature Controller: Setup Tool port                Heater Burnout Alarms, SSR Failure
specifications       (on bottom of Controller)                              Alarms, and Heater Overcurrent Alarms

Power supply         Bus power (Supplied from USB host
                     controller.)
                                                                            CT input
Power supply voltage 5 VDC                                                  (for heater current                               Models with detection for single-phase
                                                                            detection)                                        heaters: One input
Current consumption 70 mA

Ambient operating    0 to 55C (with no condensation or icing)              Maximum heater current 50 A AC
temperature
                                                                            Input current indication
Ambient operating                                                           accuracy                                          5% FS 1 digit max.
humidity
                     10% to 80%

Storage temperature  -20 to 60C (with no condensation or                   Heater burnout alarm                              0.1 to 49.9 A (in units of 0.1 A)
                     icing)                                                 setting range *1                                  Minimum detection ON time: 100 ms

Storage humidity     10% to 80%                                             SSR failure alarm                                 0.1 to 49.9 A (in units of 0.1 A)
                                                                            setting range *2                                  Minimum detection OFF time: 100 ms

Altitude             2,000 m max.                                           Heater overcurrent                                0.1 to 49.9 A (in units of 0.1 A)

Weight               Approx. 100 g                                          alarm setting range *3 Minimum detection ON time: 100 ms

Note: A driver must be installed in the personal computer. Refer to         *1. For heater burnout alarms, the heater current will be measured
        installation information in the operation manual for the                 when the control output is ON, and the output assigned to the
        Conversion Cable.                                                        alarm 1 function will turn ON if the heater current is lower than the
                                                                                 set value (i.e., heater burnout detection current value).
Communications Specifications
                                                                            *2. For SSR failure alarms, the heater current will be measured when
Transmission line RS-485: Multipoint                                             the control output is OFF, and the output assigned to the alarm 1
connection method RS-232C: Point-to-point                                        function will turn ON if the heater current is higher than the set
                                                                                 value (i.e., SSR failure detection current value).
Communications RS-485 (two-wire, half duplex), RS-232C
                                                                            *3. For heater overcurrent alarms, the heater current will be
Synchronization      Start-stop synchronization                                  measured when the control output is ON, and the output assigned
method                                                                           to the alarm 1 function will turn ON if the heater current is higher
                                                                                 than the set value (i.e., heater overcurrent detection current
Protocol             CompoWay/F, SYSWAY, or Modbus                               value).

Baud rate            1200, 2400, 4800, 9600, 19200, 38400, or               Electrical Life Expectancy Curve for
                     57600 bps                                              Relays (Reference Values)

Transmission code ASCII

Data bit length * 7 or 8 bits                                               Life ( 104 operations)  500
                                                                                                     300
Stop bit length * 1 or 2 bits                                                                        200

Error detection      Vertical parity (none, even, odd)                                               100
                     Frame check sequence (FCS) with SYSWAY                                                                                          E5GN
                     Block check character (BCC) with
                     CompoWay/F or CRC-16 Modbus                                                     50                       250 VAC, 30 VDC

                                                                                                                              (resistive load)

                                                                                                     30                       cos = 1

Flow control         None                                                                            20

Interface            RS-485, RS-232C                                                                 10

Retry function       None                                                                            5

Communications       217 bytes                                                                       3
buffer                                                                                               2

Communications 0 to 99 ms                                                                           1
response wait time Default: 20 ms
                                                                                                          0.1 0.2 0.3 0.5  1  23 5                         10
* The baud rate, data bit length, stop bit length, and vertical parity can
  be individually set using the Communications Setting Level.                                                                 Switching current (A)

                                                                                                                                                                      13
External Connections                                                                                                                     E5GN

A voltage output (control output, for driving SSR) is not electrically                       ground. (If the control output terminals are connected to ground,
   insulated from the internal circuits. When using a grounding                                 errors will occur in the measured temperature values as a result of
   thermocouple, do not connect any of the control output terminals to                          leakage current.)

E5GN                                                                                         Controllers

         Control output 1         The E5@N-@@@T@ is set for a K thermocouple
Relay output                      (input type of 5) by default. If a difference sensor is
250 VAC, 2 A (resistive load)     used, an input error (s.err) will occur. Check the
Voltage output (for driving SSR)  setting of the input type parameter.
12 VDC, 21 mA
                                  RS-485          B (+)      A (-)
Current output
0 to 20 mA DC                     communications                                     DO NOT                                                   A heater burnout alarm, heater short
4 to 20 mA DC                                                                        USE                                                      alarm, heater overcurrent alarm, or
Load: 500  max.                                                                                                                               input error is sent to the output to
                                  RS-232C         SD         RD SG + mA                                                 DO NOT                which the alarm 1 function is assigned.
    Auxiliary outputs 1 and 2                                                                                           USE
Relay outputs                     communications
250 VAC, 2 A (resistive load)
                                                         CT         DO NOT                   DO NOT                  V          Analog input
                                                                    USE                      USE                           +

                                  CT input

                                  Event input                                       A                               ?BB
                                                                        EV2                          ?                              Universal TC/Pt input

                                                                EV1                                                            +

                                                  7          8                       9       10 11 12

100 to 240 VAC                                  1          2                       3       4       5                  6
24 VAC/VDC (no polarity)

                                                  Input power + Control                              Auxiliary
                                                  supply                             output 1        output 1

                                                                                                     Terminal Arrangement

Auxiliary output 2                                                                                   Models with Screw                        Models with Screwless
connection screws                                                                                    Terminal Blocks                          Clamp Terminal Blocks

         13 14                                                                                                       7 8 9 10 11 12                        7 8 9 10 11 12
          Auxiliary
          output 2

                                                                                                                     123456                                123456

Wiring                                                                                       E5GN-@-C
                                                                                             Models with Screwless Clamp Terminal Blocks
E5GN
Models with Screw Terminal Blocks (M3 Screws)

                                  M3 Screw Terminal Blocks                                                                                    Models with Screwless Clamp Terminal Blocks
                                  Crimp terminal shape: Forked or round
                                  Tightening torque for all terminals: 0.5 Nm                                                               Wire stripping: 10 mm

                                                                        5.8 mm max.                                                            Ferrules: 8 to 12 mm

                                                                        5.8 mm max.                                                                                              0.8 to 1.4 mm

                                                                                                                                                           10 mm  8 to 12 mm

                                                                                                                                                                                                14
Nomenclature                                                                               No.1 display                                                                         E5GN

E5GN                                                                                                                                                    Operation indicators
                                                                                                                                                        No. 2 display
The front panel is the same for the E5GN.

                                                          Temperature unit
                                                      Operation indicators

                            Level Key

                                                                                                             Mode Key  Down Key                Up Key

Dimensions                                                                                                                                                                                 (Unit: mm)

E5GN                                                                        48                2                        99                                              44.8
Models with Screw

Terminal Blocks

                   35                                                                      35                                                                      22         22
                       24

                                                                                                                                Flush Mounting Adapter (Provided)
                                                                                                             Waterproof Packing (Provided)

                                                                                Panel Cutout

                   Mounted Separately                                                          Group Mounted                                             Recommended panel thickness is 1 to 5 mm.
                                                                                                                                                         Group mounting is not possible in the vertical
                            45+00.6                                                            (48 number of units - 2.5)+10.0
                                                                                                                                                          direction. (Maintain the specified mounting space
                                                                                                                                    22.2+00.3             between Controllers.)
                                                                                                                                                         To mount the Controller so that it is waterproof, insert
                   40 min.                                                                 Group mounting does not allow waterproofing.                   the waterproof packing onto the Controller.
                                                                                                                                                         When two or more Controllers are mounted, make
                                                                                                                                                          sure that the surrounding temperature does not
                                                                                                                                                          exceed the allowable operating temperature
                                                                                                                                                          specified in the specifications.

                                                                                22.2+00.3

E5GN-@-C                                                                    48                 2                       100                                             44.8
Models with
Screwless Clamp    35                                                                      35                                                                      22         22
Terminal Blocks        24

                                                                                                                                Flush Mounting Adapter (Provided)
                                                                                                             Waterproof Packing (Provided)

                                                                                Panel Cutout                                                             Recommended panel thickness is 1 to 5 mm.
                                                                                                                                                         Group mounting is not possible in the vertical
                   Mounted Separately                                                         Group Mounted
                                                                                                                                                          direction. (Maintain the specified mounting space
                            45+00.6                                                              (48 number of units - 2.5)+10.0                        between Controllers.)
                                                                                                                                                         When two or more Controllers are mounted, make
                                                                                                                                    22.2+00.3             sure that the surrounding temperature does not
                                                                                                                                                          exceed the allowable operating temperature
                                                                                                                                                          specified in the specifications.

                   40 min.                                                                 Group mounting does not allow waterproofing.

                                                                                22.2+00.3

Accessories (Order Separately)

USB-Serial Conversion Cable

E58-CIFQ1

                                                                                                                                               (2,100)

                                                                                              250                      LED indicator (SD)                              1,765

                                                                                USB connector (type A plug)                                    LED indicator (RD)             Serial connector

                                                                                                                                                                                                                    15
                                                                                                                                                                                        E5GN

Waterproof Packing

Y92S-32 (for DIN 48 24)

                                                         Order the Waterproof Packing separately if it becomes lost or damaged.
                                                         The Waterproof Packing can be used to achieve an IP66 degree of protection.
                                                         (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the
                                                         operating environment. Therefore, periodic replacement is recommended to ensure the level of
                                                         waterproofing specified in IP66. The time for periodic replacement depends on the operating
                                                         environment. Be sure to confirm this point at your site. Consider one year a rough standard.
                                                         OMRON shall not be liable for the level of water resistance if the customer does not perform
                                                         periodic replacement.)
                                                         The Waterproof Packing does not need to be attached if a waterproof structure is not required.

Current Transformers

E54-CT1                                                  21                               2.8                      E54-CT1
E54-CT3                                                  15                                          7.5           Thru-current (Io) vs. Output Voltage
                                                                                                                   (Eo) (Reference Values)
                                                                        5.8 dia.

                                              25 3                                10.5                             Maximum continuous heater current: 50 A (50/60 Hz)Output voltage (Eo) V (r.m.s.)
                                                     10                                                            Number of windings: 4002
                                                         40                                                        Winding resistance: 182
                                                40 40                    Two, 3.5 dia.
                                                                                                                         100 V 50 Hz

                                                                                                                                                         10                                 Distortion
                                                                                                                                                          1                                 factor 10%
                                                                                                                                                                1 k
                                                                                                                                                   100 mV                                   3%
                                                                                                                                                                                        1%

                                                         30                                                                                        10                         100

                                                                                            2.36 dia.                                              1                       RL = 10
                                                         30
                                                                                                                                                   100 V
                                                                          12 dia.
                                                                                                                9

                                                                                                                                                   10

                                                                                                                                                   1            10 100 mA 1         10  100 1,000 A

                                                                                                                                                                              Thru-current (Io) A (r.m.s.)

                                                                                      Two, M3 (depth: 4)           E54-CT3
                                              15
                                                                                                                   Thru-current (Io) vs. Output Voltage
                                                                      30
                                                                                                                   (Eo) (Reference Values)

                                                                                                                   Maximum continuous heater current: 120 A (50/60 Hz)
                                                                                                                   (Maximum continuous heater current for the
                                                                                                                   Temperature Controller is 50 A.)
                                                                                                                   Number of windings: 4002
                                                                                                                   Winding resistance: 80.8

E54-CT3 Accessory                             Connection Example                                                   Output voltage (Eo) V (r.m.s.)  100 V 50 Hz                             Distor-
                                                                                                                                                      10                                   tion
Armature                                                    Armature                                                                                 1        1 k                       factor
                                                                                                                                                                                           10%
  Approx. 3 dia.                                                                                                                                                500
                                                                                                                                                                                          3%
                                          18             Plug                                                                                                                           1%

Plug                                                                           Lead

                                                                                                                                                   100 mV                      100
                                                                                                                                                         10                   50
                                                                                                                                                          1
                                                                                                                                                                              RL = 10

Approx. 6 dia.                                                                                                                                     100 V       10 100 mA  1        10  100 1,000 A
                                 (22)
                                                                                                                                                        10
                                                                                                                                                           1

                                                                                                                                                                              Thru-current (Io) A (r.m.s.)

                                                                                                                                                                                                            16
Terms and Conditions of Sale

1. Offer; Acceptance. These terms and conditions (these "Terms") are deemed                      ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.
     part of all quotes, agreements, purchase orders, acknowledgments, price lists,              BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
     catalogs, manuals, brochures and other documents, whether electronic or in                  PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
     writing, relating to the sale of products or services (collectively, the "Products")        INTENDED USE. Omron further disclaims all warranties and responsibility of
     by Omron Electronics LLC and its subsidiary companies ("Omron"). Omron                      any type for claims or expenses based on infringement by the Products or oth-
     objects to any terms or conditions proposed in Buyer's purchase order or other              erwise of any intellectual property right. (c) Buyer Remedy. Omron's sole obli-
     documents which are inconsistent with, or in addition to, these Terms.                      gation hereunder shall be, at Omron's election, to (i) replace (in the form
                                                                                                 originally shipped with Buyer responsible for labor charges for removal or
2. Prices; Payment Terms. All prices stated are current, subject to change with-                 replacement thereof) the non-complying Product, (ii) repair the non-complying
     out notice by Omron. Omron reserves the right to increase or decrease prices                Product, or (iii) repay or credit Buyer an amount equal to the purchase price of
     on any unshipped portions of outstanding orders. Payments for Products are                  the non-complying Product; provided that in no event shall Omron be responsi-
     due net 30 days unless otherwise stated in the invoice.                                     ble for warranty, repair, indemnity or any other claims or expenses regarding
                                                                                                 the Products unless Omron's analysis confirms that the Products were prop-
3. Discounts. Cash discounts, if any, will apply only on the net amount of invoices              erly handled, stored, installed and maintained and not subject to contamina-
     sent to Buyer after deducting transportation charges, taxes and duties, and will            tion, abuse, misuse or inappropriate modification. Return of any Products by
     be allowed only if (i) the invoice is paid according to Omron's payment terms               Buyer must be approved in writing by Omron before shipment. Omron Compa-
     and (ii) Buyer has no past due amounts.                                                     nies shall not be liable for the suitability or unsuitability or the results from the
                                                                                                 use of Products in combination with any electrical or electronic components,
4. Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month or                 circuits, system assemblies or any other materials or substances or environ-
     the maximum legal rate, whichever is less, on any balance not paid within the               ments. Any advice, recommendations or information given orally or in writing,
     stated terms.                                                                               are not to be construed as an amendment or addition to the above warranty.
                                                                                                 See http://www.omron247.com or contact your Omron representative for pub-
5. Orders. Omron will accept no order less than $200 net billing.                                lished information.
6. Governmental Approvals. Buyer shall be responsible for, and shall bear all               14. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE
                                                                                                 FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
     costs involved in, obtaining any government approvals required for the impor-               LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY
     tation or sale of the Products.                                                             WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS
7. Taxes. All taxes, duties and other governmental charges (other than general                   BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
     real property and income taxes), including any interest or penalties thereon,               Further, in no event shall liability of Omron Companies exceed the individual
     imposed directly or indirectly on Omron or required to be collected directly or             price of the Product on which liability is asserted.
     indirectly by Omron for the manufacture, production, sale, delivery, importa-          15. Indemnities. Buyer shall indemnify and hold harmless Omron Companies and
     tion, consumption or use of the Products sold hereunder (including customs                  their employees from and against all liabilities, losses, claims, costs and
     duties and sales, excise, use, turnover and license taxes) shall be charged to              expenses (including attorney's fees and expenses) related to any claim, inves-
     and remitted by Buyer to Omron.                                                             tigation, litigation or proceeding (whether or not Omron is a party) which arises
8. Financial. If the financial position of Buyer at any time becomes unsatisfactory              or is alleged to arise from Buyer's acts or omissions under these Terms or in
     to Omron, Omron reserves the right to stop shipments or require satisfactory                any way with respect to the Products. Without limiting the foregoing, Buyer (at
     security or payment in advance. If Buyer fails to make payment or otherwise                 its own expense) shall indemnify and hold harmless Omron and defend or set-
     comply with these Terms or any related agreement, Omron may (without liabil-                tle any action brought against such Companies to the extent based on a claim
     ity and in addition to other remedies) cancel any unshipped portion of Prod-                that any Product made to Buyer specifications infringed intellectual property
     ucts sold hereunder and stop any Products in transit until Buyer pays all                   rights of another party.
     amounts, including amounts payable hereunder, whether or not then due,                 16. Property; Confidentiality. Any intellectual property in the Products is the exclu-
     which are owing to it by Buyer. Buyer shall in any event remain liable for all              sive property of Omron Companies and Buyer shall not attempt to duplicate it
     unpaid accounts.                                                                            in any way without the written permission of Omron. Notwithstanding any
9. Cancellation; Etc. Orders are not subject to rescheduling or cancellation                     charges to Buyer for engineering or tooling, all engineering and tooling shall
     unless Buyer indemnifies Omron against all related costs or expenses.                       remain the exclusive property of Omron. All information and materials supplied
10. Force Majeure. Omron shall not be liable for any delay or failure in delivery                by Omron to Buyer relating to the Products are confidential and proprietary,
     resulting from causes beyond its control, including earthquakes, fires, floods,             and Buyer shall limit distribution thereof to its trusted employees and strictly
     strikes or other labor disputes, shortage of labor or materials, accidents to               prevent disclosure to any third party.
     machinery, acts of sabotage, riots, delay in or lack of transportation or the          17. Export Controls. Buyer shall comply with all applicable laws, regulations and
     requirements of any government authority.                                                   licenses regarding (i) export of products or information; (iii) sale of products to
11. Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron:                   "forbidden" or other proscribed persons; and (ii) disclosure to non-citizens of
     a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship              regulated technology or information.
                                                                                            18. Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any right
        except in "break down" situations.                                                       and no course of dealing between Buyer and Omron shall operate as a waiver
     b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall          of rights by Omron. (b) Assignment. Buyer may not assign its rights hereunder
                                                                                                 without Omron's written consent. (c) Law. These Terms are governed by the
        constitute delivery to Buyer;                                                            law of the jurisdiction of the home office of the Omron company from which
     c. All sales and shipments of Products shall be FOB shipping point (unless oth-             Buyer is purchasing the Products (without regard to conflict of law princi-
                                                                                                 ples). (d) Amendment. These Terms constitute the entire agreement between
        erwise stated in writing by Omron), at which point title and risk of loss shall          Buyer and Omron relating to the Products, and no provision may be changed
        pass from Omron to Buyer; provided that Omron shall retain a security inter-             or waived unless in writing signed by the parties. (e) Severability. If any provi-
        est in the Products until the full purchase price is paid;                               sion hereof is rendered ineffective or invalid, such provision shall not invalidate
     d. Delivery and shipping dates are estimates only; and                                      any other provision. (f) Setoff. Buyer shall have no right to set off any amounts
     e. Omron will package Products as it deems proper for protection against nor-               against the amount owing in respect of this invoice. (g) Definitions. As used
        mal handling and extra charges apply to special conditions.                              herein, "including" means "including without limitation"; and "Omron Compa-
12. Claims. Any claim by Buyer against Omron for shortage or damage to the                       nies" (or similar words) mean Omron Corporation and any direct or indirect
     Products occurring before delivery to the carrier must be presented in writing              subsidiary or affiliate thereof.
     to Omron within 30 days of receipt of shipment and include the original trans-
     portation bill signed by the carrier noting that the carrier received the Products
     from Omron in the condition claimed.
13. Warranties. (a) Exclusive Warranty. Omron's exclusive warranty is that the
     Products will be free from defects in materials and workmanship for a period of
     twelve months from the date of sale by Omron (or such other period expressed
     in writing by Omron). Omron disclaims all other warranties, express or implied.
     (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION,
     EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-

Certain Precautions on Specifications and Use

1. Suitability of Use. Omron Companies shall not be responsible for conformity                   ADDRESS THE RISKS, AND THAT THE OMRON'S PRODUCT IS PROP-
     with any standards, codes or regulations which apply to the combination of the              ERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
     Product in the Buyer's application or use of the Product. At Buyer's request,               OVERALL EQUIPMENT OR SYSTEM.
     Omron will provide applicable third party certification documents identifying          2. Programmable Products. Omron Companies shall not be responsible for the
     ratings and limitations of use which apply to the Product. This information by              user's programming of a programmable Product, or any consequence thereof.
     itself is not sufficient for a complete determination of the suitability of the Prod-  3. Performance Data. Data presented in Omron Company websites, catalogs
     uct in combination with the end product, machine, system, or other application              and other materials is provided as a guide for the user in determining suitabil-
     or use. Buyer shall be solely responsible for determining appropriateness of                ity and does not constitute a warranty. It may represent the result of Omron's
     the particular Product with respect to Buyer's application, product or system.              test conditions, and the user must correlate it to actual application require-
     Buyer shall take application responsibility in all cases but the following is a             ments. Actual performance is subject to the Omron's Warranty and Limitations
     non-exhaustive list of applications for which particular attention must be given:           of Liability.
     (i) Outdoor use, uses involving potential chemical contamination or electrical         4. Change in Specifications. Product specifications and accessories may be
     interference, or conditions or uses not described in this document.                         changed at any time based on improvements and other reasons. It is our prac-
     (ii) Use in consumer products or any use in significant quantities.                         tice to change part numbers when published ratings or features are changed,
     (iii) Energy control systems, combustion systems, railroad systems, aviation                or when significant construction changes are made. However, some specifica-
     systems, medical equipment, amusement machines, vehicles, safety equip-                     tions of the Product may be changed without any notice. When in doubt, spe-
     ment, and installations subject to separate industry or government regulations.             cial part numbers may be assigned to fix or establish key specifications for
     (iv) Systems, machines and equipment that could present a risk to life or prop-             your application. Please consult with your Omron's representative at any time
     erty. Please know and observe all prohibitions of use applicable to this Prod-              to confirm actual specifications of purchased Product.
     uct.                                                                                   5. Errors and Omissions. Information presented by Omron Companies has been
     NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS                                  checked and is believed to be accurate; however, no responsibility is assumed
     RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT                                     for clerical, typographical or proofreading errors or omissions.
     ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
Note: This datasheet is provided as a guideline for selecting products. Do not use this document to operate the Unit.

                    ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

                       To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

    OMRON ELECTRONICS LLC THE AMERICAS HEADQUARTERS
Schaumburg, IL USA 847.843.7900 800.556.6766 www.omron247.com

OMRON CANADA, INC. HEAD OFFICE                                      OMRON ARGENTINA SALES OFFICE
Toronto, ON, Canada 416.286.6465 866.986.6766 www.omron247.com  Cono Sur 54.11.4783.5300

OMRON ELETRNICA DO BRASIL LTDA HEAD OFFICE                         OMRON CHILE SALES OFFICE
So Paulo, SP, Brasil 55.11.2101.6300 www.omron.com.br            Santiago 56.9.9917.3920

OMRON ELECTRONICS MEXICO SA DE CV HEAD OFFICE                       OTHER OMRON LATIN AMERICA SALES
Apodaca, N.L. 52.811.156.99.10 001.800.556.6766 mela@omron.com  54.11.4783.5300

Cat. No. CMS_E5GN_E_5_1 12/09   2009 Omron Electronics LLC
                                     Specifications are subject to change without notice.
This datasheet has been downloaded from:
            datasheet.eeworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

器件索引   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2020 EEWORLD.com.cn, Inc. All rights reserved