Basic-type Digital Temperature Controller

E5GN (48 x 24 mm)

                                                                                                                            CSM_E5GN_DS_E_5_1

New 48 x 24-mm Basic Temperature

Controller with Enhanced Functions and

Performance. Improved Indication

Accuracy and Preventive Maintenance

Function.

• Indication Accuracy                                                                                                       E5GN--@-C

Thermocouple input: ±0.3% of PV (previous models: ±0.5%)                                       E5GN

                                                                                    Models with Screw Terminal  Models with Screwless Clamp

Pt input: ±0.2% of PV (previous models: ±0.5%)                                                 Blocks                       Terminal Blocks

                                                                                               48 × 24 mm                   48 × 24 mm

Analog input: ±0.2% FS (previous models: ±0.5%)

• Models are available with screw terminal blocks or screwless

clamp terminal blocks.

• A PV/SV-status display function can be set to automatically

alternate between displaying the status of the Temperature                                     Refer to Safety Precautions for E5@N/E5@N-H.

Controller (auto/manual, RUN/STOP, and alarms) and the PV or SV.                            Refer to Operation for E5@N/E5@N-H for operating

• Preventive maintenance for relays in the Temperature Controller                           procedures.

using a Control Output ON/OFF Counter.

• Switch the PV display between three colors.

• Compatible with Support Software (CX-Thermo version 4.2 or higher).

• Eleven-segment displays.

• Models are available with one or two alarm outputs.

Main I/O Functions

                     Event Inputs

                     • None             E5GN

                     • Two                                     Dual Display: PV                and SV      4-digit Display

Sensor Inputs                                                                                              • Auto/manual switching

• Universal thermocouple/Pt inputs                                                  Auxiliary  Outputs     • Temperature Controller status display

(Models with temperature inputs)                                                    • None                 • Simple program function

• Analog current/voltage inputs                                                     • One                  • Control output ON/OFF count alarm

(Models with analog inputs)                                                         • Two                  • PV change rate alarm

Indication Accuracy                                                                                        • Models also available with RS-232C

• Thermocouple input: ±0.3% of PV                                                                          communications

• Pt input: ±0.2% of PV                                                                                    • Models also available with RS-485

• Analog input: ±0.2% FS            Control Output 1                                                       communications

                                    • Relay output

Sampling Period                     • Voltage output (for  driving SSR)

• 250 ms                            • Current output

This datasheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions

and other information required for operation before attempting to use the product.

E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156)

E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158)

                                                                                                                                                    1
                                                                                                                             E5GN

Lineup

                                                                 Temperature input               1 control output   0, 1, or 2 auxiliary

                                                                                                                    outputs

                                     Screw terminal block                                                           0, 1, or 2 auxiliary

                                                                 Analog input                    1 control output   outputs

    E5GN

    Basic Type                                                                                                      0, 1, or 2 auxiliary

                                                                 Temperature input               1 control output   outputs

                                            Screwless clamp

                                            terminal block                                                          0, 1, or 2 auxiliary

                                                                 Analog input                    1 control output   outputs

Note: Models with one control output and one or two auxiliary outputs can be used for heating/cooling control.

Model Number Structure

Model Number Legend

Controllers                                                      4.  Input Type

    E5GN-@@@@@-@-@-@                                                 T: Universal thermocouple/platinum resistance thermometer input

            1      2  3  4  5  6  7      8                           L: Analog current/voltage input

1.  Control Output 1                                             5.  Power Supply Voltage

    R: Relay output                                                  Blank: 100 to 240 VAC

    Q: Voltage output (for driving SSR)                              D: 24 VAC/VDC

    C: Linear current output                                     6.  Terminal Type

2.  Auxiliary Outputs                                                Blank: Models with screw terminal block

    Blank: None                                                      C: Models with screwless clamp terminal block

    1: One output                                                7.  Case Color

    2: Two outputs                                                   Blank: Black

3.  Option                                                       8.  Communications Protocol

    Blank: None                                                      Blank: None

    01: RS-232C communications                                       FLK: CompoWay/F serial communications

    03: RS-485 communications

    B: Two event inputs

    H: Heater burnout/Heater short/Heater overcurrent detection

    (CT1)

Note: Models cannot be made for all combinations of options that are possible in the model number legend. Confirm model availability in Ordering

    Information before ordering.

* Auxiliary outputs are relay outputs that can be used for output alarms or processing results.

Supply Voltage Suffixes for Ordering

For 100 to 240 VAC, add a "AC100240" suffix.

For 24 VAC/VDC models, add a "ACDC24" suffix.

                                                                                                                                                  2
                                                                                                                                      E5GN

Ordering Information

Controllers with Screw Terminal Blocks

Models with Temperature Inputs

Models with One Control Output and a 100 to 240-VAC Power Supply (Add AC100240 to the Model number.)

                                                     Detection of                                                  Previous model

                                            No. of        heater

Case color  Control       Control         auxiliary  burnout,       No. of event  Transfer      Communi-      Thermocou-  Resistance  New model

            output        mode *1           outputs  SSR failure,        inputs   output *2          cations  ple input   thermome-

                                                     and heater                                                           ter input

                                                     overcurrent

                          Standard     ---                          ---                                       E5GN-RTC    E5GN-RP     E5GN-RT

                                                                                                ---           E5GN-R1TC   E5GN-R1P    E5GN-R1T

                                                                    2                                         ---         ---         E5GN-R1BT

                                       1             ---                                        RS-232C       ---         ---         E5GN-

                                                                                                                                      R101T-FLK

                                                                                                RS-485        E5GN        E5GN        E5GN-

            Relay output  Standard or                               ---           ---                         -R03TC-FLK  -R03P-FLK   R103T-FLK

                          heating/                                                                            ---         ---         E5GN-R2T

                          cooling                    Detection for

                                                     single-phase                               ---           ---         ---         E5GN-R2HT

                                       2             heaters

                                                                    2                                         ---         ---         E5GN-R2BT

                                                     ---            ---                         RS-485        ---         ---         E5GN-

                                                                                                                                      R203T-FLK

                          Standard     ---                          ---                                       E5GN-QTC    E5GN-QP     E5GN-QT

                                                                                                ---           E5GN-Q1TC   E5GN-Q1P    E5GN-Q1T

Black                                                               2                                         ---         ---         E5GN-Q1BT

                                       1             ---                                        RS-232C       ---         ---         E5GN-

                                                                                                                                      Q101T-FLK

            Voltage                                                                             RS-485        E5GN        E5GN        E5GN-

            output (for   Standard or                               ---           ---                         -Q03TC-FLK  -Q03P-FLK   Q103T-FLK

            driving SSR)  heating/                                                                            ---         ---         E5GN-Q2T

                          cooling                    Detection for

                                                     single-phase                               ---           ---         ---         E5GN-Q2HT

                                       2             heaters

                                                                    2                                         ---         ---         E5GN-Q2BT

                                                     ---            ---                         RS-485        ---         ---         E5GN-

                                                                                                                                      Q203T-FLK

                                                                    ---                         ---           ---         ---         E5GN-C1T

                          Standard or                               2             Transfer                    ---         ---         E5GN-C1BT

            Current       heating/     1             ---                          output using  RS-232C       ---         ---         E5GN-

            output        cooling                                                 control                                             C101T-FLK

                                                                    ---           output                                              E5GN-

                                                                                                RS-485        ---         ---         C103T-FLK

*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that

can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.

*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible

for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease

by one.

                                                                                                                                                         3
                                                                                                                                    E5GN

Models with One Control Output          and a 24-VAC/VDC Power Supply              (Add ACDC24 to the Model number.)

                                                      Detection of                                              Previous model

                                             No. of        heater

Case color  Control       Control          auxiliary  burnout,       No. of event  Transfer      Communi-               Resistance  New model

            output        mode *1            outputs  SSR failure,        inputs   output *2     cations   Thermocou-   thermome-

                                                      and heater                                           ple input    ter input

                                                      overcurrent

                          Standard      ---                          ---                                   E5GN-RTC     E5GN-RP     E5GN-RTD

                                                                                                 ---       E5GN-R1TC    E5GN-R1P    E5GN-R1TD

                                                                     2                                     ---          ---         E5GN-R1BTD

                                        1             ---                                        RS-232C   ---          ---         E5GN

                                                                                                                                    -R101TD-FLK

                                                                                                 RS-485    E5GN         E5GN        E5GN

            Relay output  Standard or                                ---           ---                     -R03TC-FLK   -R03P-FLK   -R103TD-FLK

                          heating/                                                                         ---          ---         E5GN-R2TD

                          cooling                     Detection for

                                                      single-phase                               ---       ---          ---         E5GN-R2HTD

                                        2             heaters

                                                                     2                                     ---          ---         E5GN-R2BTD

                                                      ---            ---                         RS-485    ---          ---         E5GN

                                                                                                                                    -R203TD-FLK

                          Standard      ---                          ---                                   E5GN-QTC     E5GN-QP     E5GN-QTD

                                                                                                 ---       E5GN-Q1TC    E5GN-Q1P    E5GN-Q1TD

                                                                     2                                     ---          ---         E5GN-

Black                                                                                                                               Q1BTD

                                        1             ---                                        RS-232C   ---          ---         E5GN-

                                                                                                                                    Q101TD-FLK

            Voltage                                                                              RS-485    E5GN         E5GN        E5GN

            output (for   Standard  or                               ---           ---                     -Q03TC-FLK   -Q03P-FLK   -Q103TD-FLK

            driving SSR)  heating/                                                                         ---          ---         E5GN-Q2TD

                          cooling                     Detection for

                                                      single-phase                                         ---          ---         E5GN-

                                                      heaters                                    ---                                Q2HTD

                                        2                                                                                           E5GN-

                                                                     2                                     ---          ---         Q2BTD

                                                      ---                                                                           E5GN

                                                                     ---                         RS-485    ---          ---         -Q203TD-FLK

                                                                     ---                         ---       ---          ---         E5GN-C1TD

                          Standard or                                2             Transfer                ---          ---         E5GN-C1BTD

            Current       heating/      1             ---                          output using  RS-232C   ---          ---         E5GN

            output        cooling                                                  control                                          -C101TD-FLK

                                                                     ---           output                                           E5GN

                                                                                                 RS-485    ---          ---         -C103TD-FLK

*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that

can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.

*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible

for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease

by one.

                                                                                                                                                         4
                                                                                                                                    E5GN

Models with Analog Inputs

Models with One Control Output         and a 100     to 240-VAC       Power Supply (Add AC100240            to the Model number.)

                                                     Detection of                                                Previous model

                                          No. of          heater

Case color  Control       Control         auxiliary  burnout,         No. of event  Transfer      Communi-  Thermocou-  Resistance  New model

            output        mode *1         outputs    SSR failure,          inputs   output *2     cations   ple input   thermome-

                                                     and heater                                                         ter input

                                                     overcurrent

            Relay output                                                                                    ---         ---         E5GN-

                                                                                                                                    R103L-FLK

            Voltage                                                                 ---           RS-485                            E5GN-

            output (for   Standard or                                                                       ---         ---         Q103L-FLK

Black       driving SSR)  heating/     1             ---              ---

                          cooling                                                   Transfer

            Current                                                                 output using  ---       ---         ---         E5GN-C1L

            output                                                                  control

                                                                                    output

Note: Models with analog inputs do not display the temperature unit.

*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that

can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.

*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible

for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease

by one.

Models with One Control Output         and a 24-VAC/VDC Power Supply (Add ACDC24 to the Model number.)

                                                     Detection of                                                Previous model

                          Control         No. of          heater

Case color  Control       mode *1         auxiliary  burnout,         No. of event  Transfer      Communi-  Thermocou-  Resistance  New model

            output                        outputs    SSR failure,          inputs   output *2     cations   ple input   thermome-

                                                     and heater                                                         ter input

                                                     overcurrent

            Relay output                                                                                    ---         ---         E5GN-

                                                                                                                                    R103LD-FLK

            Voltage       Standard or                                               ---           RS-485                            E5GN

            output (for   heating/                                                                          ---         ---         -Q103LD-FLK

Black       driving SSR)  cooling      1             ---              ---

                                                                                    Transfer

            Current                                                                 output using  ---       ---         ---         E5GN-C1LD

            output                                                                  control

                                                                                    output

*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that

can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.

*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible

for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease

by one.

                                                                                                                                                         5
                                                                                                                                      E5GN

Controllers with Screwless Clamp Terminal Blocks

Models with Temperature Inputs

Models with One Control Output and a 100 to 240-VAC Power Supply (Add                            AC100240     to the Model number.)

                                                      Detection                                                    Previous model

                                             No. of   of heater

Case color  Control       Control          auxiliary  burnout,       No. of event  Transfer      Communic     Thermocou-  Resistance  New model

            output        mode *1            outputs  SSR failure,        inputs   output *2          ations  ple input   thermome-

                                                      and heater                                                          ter input

                                                      overcurrent

                          Standard      ---                          ---                                      E5GN-RTC    E5GN-RP     E5GN-RT-C

                                                                                                 ---          E5GN-R1TC   E5GN-R1P    E5GN-R1T-C

                                                                     2                                        ---         ---         E5GN-R1BT-C

                                        1             ---                                        RS-232C      ---         ---         E5GN

                                                                                                                                      -R101T-C-FLK

                                                                                                 RS-485       E5GN        E5GN        E5GN

                          Standard  or                                                                        -R03TC-FLK  -R03P-FLK   -R103T-C-FLK

            Relay output  heating/                                   ---           ---                        ---         ---         E5GN-R2T-C

                          cooling                     Detection for

                                                      single-                                    ---          ---         ---         E5GN-R2HT-C

                                        2             phase

                                                      heaters

                                                                     2                                        ---         ---         E5GN-R2BT-C

                                                      ---            ---                         RS-485       ---         ---         E5GN

                                                                                                                                      -R203T-C-FLK

                          Standard      ---                          ---                                      E5GN-QTC    E5GN-QP     E5GN-QT-C

                                                                                                 ---          E5GN-Q1TC   E5GN-Q1P    E5GN-Q1T-C

Black                                                                2                                        ---         ---         E5GN-Q1BT-C

                                        1             ---                                        RS-232C      ---         ---         E5GN

                                                                                                                                      -Q101T-C-FLK

                                                                                                 RS-485       E5GN        E5GN        E5GN

            Voltage       Standard  or                                                                        -Q03TC-FLK  -Q03P-FLK   -Q103T-C-FLK

            output (for   heating/                                   ---           ---                        ---         ---         E5GN-Q2T-C

            driving SSR)  cooling                     Detection for

                                                      single-                                    ---          ---         ---         E5GN-Q2HT-C

                                        2             phase

                                                      heaters

                                                                     2                                        ---         ---         E5GN-Q2BT-C

                                                      ---            ---                         RS-485       ---         ---         E5GN

                                                                                                                                      -Q203T-C-FLK

                                                                     ---                         ---          ---         ---         E5GN-C1T-C

                          Standard  or                               2             Transfer                   ---         ---         E5GN-C1BT-C

            Current       heating/      1                                          output using  RS-232C      ---         ---         E5GN

            output        cooling                                                  control                                            -C101T-C-FLK

                                                                     ---           output                                             E5GN

                                                                                                 RS-485       ---         ---         -C103T-C-FLK

*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that

can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.

*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible

for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease

by one.

                                                                                                                                                         6
                                                                                                                                          E5GN

Models with  One Control Output and a 24-VAC/VDC                   Power Supply (Add ACDC24 to             the Model number.)

                                                     Detection                                                  Previous model

                                                     of heater

                                            No. of   burnout,           No. of

Case color   Control     Control          auxiliary       SSR           event   Transfer      Communic     Thermocou-   Resistance  New model

             output      mode *1          outputs    failure, and       inputs  output *2          ations  ple input    thermome-

                                                          heater                                                        ter input

                                                     overcurren

                                                            t

                         Standard      ---                         ---                                     E5GN-RTC     E5GN-RP     E5GN-RTD-C

                                                                                              ---          E5GN-R1TC    E5GN-R1P    E5GN-R1TD-C

                                                                   2                                       ---          ---         E5GN-R1BTD-C

                                       1             ---                                      RS-232C      ---          ---         E5GN

                                                                                                                                    -R101TD-C-FLK

                                                                                              RS-485       E5GN         E5GN        E5GN

            Relay        Standard  or                                                                      -R03TC-FLK   -R03P-FLK   -R103TD-C-FLK

            output       heating/                                  ---          ---                        ---          ---         E5GN-R2TD-C

                         cooling                     Detection

                                                     for single-                              ---          ---          ---         E5GN-R2HTD-C

                                       2             phase

                                                     heaters

                                                                   2                                       ---          ---         E5GN-R2BTD-C

                                                     ---           ---                        RS-485       ---          ---         E5GN

                                                                                                                                    -R203TD-C-FLK

                         Standard      ---                         ---                                     E5GN-QTC     E5GN-QP     E5GN-QTD-C

                                                                                              ---          E5GN-Q1TC    E5GN-Q1P    E5GN-Q1TD-C

Black                                                              2                                       ---          ---         E5GN-Q1BTD-C

                                       1             ---                                      RS-232C      ---          ---         E5GN

                                                                                                                                    -Q101TD-C-FLK

            Voltage                                                                           RS-485       E5GN         E5GN        E5GN

            output (for  Standard  or                                                                      -Q03TC-FLK   -Q03P-FLK   -Q103TD-C-FLK

            driving      heating/                                  ---          ---                        ---          ---         E5GN-Q2TD-C

            SSR)         cooling                     Detection

                                                     for single-                              ---          ---          ---         E5GN-Q2HTD-C

                                       2             phase

                                                     heaters

                                                                   2                                       ---          ---         E5GN-Q2BTD-C

                                                     ---           ---                        RS-485       ---          ---         E5GN

                                                                                                                                    -Q203TD-C-FLK

                                                                   ---                        ---          ---          ---         E5GN-C1TD-C

                         Standard or                               2            Transfer                   ---          ---         E5GN-C1BTD-C

            Current      heating/      1             ---                        output using  RS-232C      ---          ---         E5GN

            output       cooling                                                control                                             -C101TD-C-FLK

                                                                   ---          output                                              E5GN

                                                                                              RS-485       ---          ---         -C103TD-C-FLK

*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that

can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.

*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible

for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease

by one.

                                                                                                                                                         7
                                                                                                                                       E5GN

Models with Analog Inputs

Models with One Control Output      and a 100     to 240-VAC          Power Supply (Add AC100240           to the Model number.)

                                                  Detection of                                                  Previous model

                                       No. of          heater

Case color  Control    Control         auxiliary  burnout,            No. of event  Transfer      Communi  Thermocou-   Resistance  New model

            output     mode *1         outputs    SSR failure,             inputs   output *2     cations  ple input    thermome-

                                                  and heater                                                            ter input

                                                  overcurrent

                       Standard or                                                  Transfer

Black       Current    heating/     1             ---                 ---           output using  ---      ---          ---         E5GN-C1L-C

            output     cooling                                                      control

                                                                                    output

Note: Models with analog inputs do not display the temperature unit.

*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that

can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.

*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible

for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease

by one.

Models with One Control Output      and a 24-VAC/VDC Power Supply (Add ACDC24 to the Model number.)

                                                  Detection of                                                  Previous model

                                       No. of          heater

Case color  Control    Control         auxiliary  burnout,            No. of event  Transfer      Communi  Thermocou-   Resistance

            output     mode *1         outputs    SSR failure,             inputs   output *2     cations  ple input    thermome-   New model

                                                  and heater                                                            ter input

                                                  overcurrent

                       Standard or                                                  Transfer

Black       Current    heating/     1             ---                 ---           output using  ---      ---          ---         E5GN-C1LD-

            output     cooling                                                      control                                         C

                                                                                    output

*1. If heating/cooling control mode is used, an auxiliary output is used as a control output for the cooling side. The number of auxiliary outputs that

can be used will decrease by one. Also, the signal for the control output for the cooling side will be a relay output.

*2. A current control output can be used as the transfer output. In that case, an auxiliary output is used as the control output. (This is not possible

for models without an auxiliary output.) The control output will be a relay output. The number of auxiliary outputs that can be used will decrease

by one.

Accessories (Order Separately)

USB-Serial Conversion Cable

                       Model

                       E58-CIFQ1

Waterproof Packing

                       Model

                       Y92S-32

Current Transformers (CTs)

       Hole diameter                   Model

            5.8 dia.                   E54-CT1

            12.0 dia.                  E54-CT3

CX-Thermo Support Software

                       Model

                       EST2-2C-MV4

Note: The E5GN is supported by CX-Thermo version 4.2 and higher.

                                                                                                                                                         8
                                                                                                                                     E5GN

Specifications

Ratings

Power supply voltage             No D in model number: 100 to 240 VAC, 50/60 Hz

                                 D in model number: 24 VAC, 50/60 Hz; 24 VDC

Operating voltage range          85% to 110% of rated supply voltage

              E5GN               100 to 240 VAC: 5.5 VA (max.)

Power         Screw terminal     24 VAC/VDC: 3 VA/2 W (max.)

consump-      block

tion          E5GN-@-C           100 to 240 VAC: 5.5 VA (max.)

              Screwless clamp    24 VAC/VDC: 3 VA/2 W (max.)

              terminal block

                                 Models with temperature inputs

                                    Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II

                                    Platinum resistance thermometer: Pt100 or JPt100

Sensor input                        Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C

                                    Voltage input: 0 to 50 mV

                                 Models with analog inputs

                                    Current input: 4 to 20 mA or 0 to 20 mA

                                    Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V

Input impedance                  Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.)

Control method                   ON/OFF control or 2-PID control (with auto-tuning)

              Relay output       SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V,

                                 10 mA

Control       Voltage output

outputs       (for driving SSR)  Output voltage: 12 VDC ±15% (PNP), max. load current: 21 mA, with short-circuit protection circuit

              Current output     4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000

Auxiliary     Number of outputs  1 or 2 max. (Depends on the model.)

outputs       Output             Relay output: SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum

              specifications     applicable load: 5 V, 10 mA

              Number of inputs   2

Event         External contact   Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.

inputs        input              Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.

              specifications     Current flow: Approx. 7 mA per contact

Setting method                   Digital setting using front panel keys

Indication method                11-segment digital display and individual indicators (7-segment display also possible)

                                 Character height: PV: 7.5 mm, SV: 3.6 mm

Multi SP                         Up to four set points (SP0 to SP3) can be saved and selected using event inputs, key operations, or serial

                                 communications.

Bank switching                   Not supported

                                 Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout

Other functions                  detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop,

                                 protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, logic

                                 operations, PV/SV status display, simple program, automatic cooling coefficient adjustment

Ambient operating temperature    −10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C

Ambient operating humidity       25% to 85%

Storage temperature              −25 to 65°C (with no condensation or icing)

                                                                                                                                                9
                                                                                                                                                                                                          E5GN

Input Ranges

Thermocouple/Platinum Resistance Thermometer (Universal Inputs)

Input                              Platinum resistance                                                              Thermocouple                                                  Infrared temperature    Analog

Type                                  thermometer                                                                                                                                        sensor           input

                                                                                                                                                                                         60 to  115  140

Name                                  Pt100          JPt100               K               J               T       E     L           U          N  R       S     B     W     PL    10 to  120    to   to       0 to

                                                                                                                                                                            II    70°C   °C     165  260  50 mV

                                                                                                                                                                                                °C   °C

                        2300                                                                                                                                          2300

                        1800                                                                                                                                    1800

                        1700                                                                                                                      1700    1700

                        1600

                        1500

                        1400                                        1300                                                                    1300                            1300

Temperature range (°C)  1300                                                                                                                                                                              Usable

                        1200                                                                                                                                                                              in the

                        1100                                                                                                                                                                              following

                        1000    850                                                 850                                 850                                                                               ranges

                        900                                                                                                                                                                               by

                        800                                                                                                                                                                               scaling:

                        700                                                                                       600                                                                                     −1999 to

                        600           500.0          500.0                500.0                                                                                                                           9999 or

                        500                                                                                                                                                                               −199.9

                        400                                                                  400.0  400   400.0               400   400.0                                                                 to 999.9

                        300                                                                                                                                                                          260

                        200                                                                                                                                                              120    165

                        100                   100.0          100.0                                                                                                                90

                        0                                                                                                                                       100

                        −100.0                0.0            0.0                                                                                  0       0           0     0     0      0      0    0

                        −200.0                                            −20.0     −100     −20.0                      −100

                                −200  −199.9         −199.9         −200                            −200  −199.9  −200        −200  −199.9  −200

Setting                         0     1       2      3          4   5        6      7        8      9        10   11    12    13       14   15    16      17    18    24    25    19     20     21   22       23

number

Shaded settings are the default settings.

The applicable standards for the input types are as follows:

K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 584-1

L: Fe-CuNi, DIN 43710-1985

U: Cu-CuNi, DIN 43710-1985

W: W5Re/W26Re, ASTM E988-1990

JPt100: JIS C 1604-1989, JIS C 1606-1989

Pt100: JIS C 1604-1997, IEC 751

PL II: According to Platinel II electromotive force charts from BASF                                      (previously   Engelhard)

Models with Analog Inputs

                                Input Type                                Current                                          Voltage

Input specification                                          4 to 20 mA          0 to 20 mA               1 to 5 V          0 to 5 V           0 to 10 V

Setting range                                                Usable in the following ranges by scaling:

                                                             −1999 to 9999, −199.9 to 999.9, −19.99 to 99.99 or −1.999 to 9.999

Setting number                                               0                   1                  2                   3                   4

Shaded settings are the default settings.

                                                                                                                                                                                                                     10
                                                                                                                                                         E5GN

Alarm Outputs

Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit.

Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.

Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the

        following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR

        failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).

                                                                       Alarm output operation

Set value                      Alarm type                         When alarm value   When alarm value                  Description of function

                                                                      X is positive           X is negative

0                Alarm function OFF                               Output OFF                                 No alarm

                                                                  ON      L  H                               Set the deviation in the set point by setting the alarm

1 *1             Upper- and lower-limit                           OFF     SP         *2                      upper limit (H) and alarm lower limit (L).

                                                                  ON            X              X             Set the upward deviation in the set point by setting

2                Upper-limit                                      OFF                     ON                 the alarm value (X).

                                                                          SP              OFF  SP

                                                                  ON      X                       X          Set the downward deviation in the set point by setting

3                Lower-limit                                      OFF                     ON

                                                                          SP              OFF  SP            the alarm value (X).

                                                                  ON      L  H                               Set the deviation in the set point by setting the alarm

4 *1             Upper- and lower-limit range                     OFF                *3                      upper limit (H) and alarm lower limit (L).

                                                                          SP

                                                                  ON      L     H

5 *1             Upper- and lower-limit with                      OFF     SP         *4                      A standby sequence is added to the upper- and

                 standby sequence                                                                            lower-limit alarm (1). *6

                                                                  *5

                                                                  ON            X         ON   X             A standby sequence is added to the upper-limit alarm

6                Upper-limit with standby sequence                OFF                     OFF                (2). *6

                                                                          SP                   SP

                                                                  ON      X               ON      X          A standby sequence is added to the lower-limit alarm

7                Lower-limit with standby sequence                OFF                     OFF                (3). *6

                                                                          SP                   SP

                                                                  ON         X            ON   X             The alarm will turn ON if the process value is larger

8                Absolute-value upper-limit                       OFF                     OFF                than the alarm value (X) regardless of the set point.

                                                                       0                             0

                                                                  ON         X            ON   X             The alarm will turn ON if the process value is smaller

9                Absolute-value lower-limit                       OFF                     OFF                than the alarm value (X) regardless of the set point.

                                                                       0                             0

10               Absolute-value upper-limit with                  ON         X            ON      X          A standby sequence is added to the absolute-value

                 standby sequence                                 OFF  0                  OFF        0       upper-limit alarm (8). *6

                 Absolute-value lower-limit with                  ON         X            ON   X             A standby sequence is added to the absolute-value

11               standby sequence                                 OFF                     OFF                lower-limit alarm (9). *6

                                                                       0                             0

12               LBA (alarm 1 type only)                                             ---                     *7

13               PV change rate alarm                                                ---                     *8

*1. With set values 1, 4 and 5, the upper and lower limit values can                           *5. Set value: 5, Upper- and lower-limit with standby sequence

    be set independently for each alarm type, and are expressed as                                Always OFF when the upper-limit and lower-limit hysteresis

    “L” and “H.”                                                                                  overlaps.

*2. Set value: 1, Upper- and lower-limit alarm                                                 *6. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature

Case 1                 Case 2            Case 3   (Always ON)                                     Controllers User's Manual Basic Type (Cat. No. H156) for

                                                                      H < 0, L < 0                information on the operation of the standby sequence.

    L   H  SP          SP L    H              H   SP     L                                     *7. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature

   H < 0, L > 0        H > 0, L < 0                               H < 0, L > 0                    Controllers User's Manual Basic Type (Cat. No. H156) for

   ⏐H⏐ < ⏐L⏐           ⏐H⏐ > ⏐L⏐           H      L SP                ⏐H⏐ ≥ ⏐L⏐                   information on the loop burnout alarm (LBA).

                                                                  H > 0, L < 0                 *8. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature

                                                  SP H         L      ⏐H⏐ ≤ ⏐L⏐                   Controllers User's Manual Basic Type (Cat. No. H156) for

*3. Set value:     4,  Upper- and    lower-limit  range                                           information on the PV change rate alarm.

Case 1                 Case 2            Case 3 (Always OFF)

                                                                  H < 0, L < 0

    L   H  SP          SP L    H              H   SP     L

   H < 0, L > 0        H > 0, L < 0                               H < 0, L > 0

   ⏐H⏐ < ⏐L⏐           ⏐H⏐ > ⏐L⏐           H      L SP                ⏐H⏐ ≥ ⏐L⏐

                                                                  H > 0, L < 0

                                                  SP H      L         ⏐H⏐ ≤ ⏐L⏐

*4. Set value: 5, Upper- and lower-limit with standby sequence

    For Upper- and Lower-Limit Alarm Described Above

    • Case 1 and 2

        Always OFF when the upper-limit and lower-limit hysteresis

        overlaps.

    • Case 3: Always OFF

                                                                                                                                                                      11
                                                                                                                                                           E5GN

Characteristics

                                Thermocouple: *1

                                (±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max.

                                Platinum resistance thermometer input:

Indication accuracy             (±0.2% of indicated value or ±0.8°C, whichever is greater) ±1 digit max.

                                Analog input:

                                ±0.2% FS ±1 digit max.

                                CT input:

                                ±5% FS ±1 digit max.

                                Thermocouple input (R, S, B, W, PL II):

Influence of temperature *2     (±1% of PV or ±10°C, whichever is greater) ±1 digit max.

                                Other thermocouple input: *3

                                (±1% of PV or ±4°C, whichever is greater) ±1 digit max.

                                Platinum resistance thermometer input:

Influence of voltage *2         (±1% of PV or ±2°C, whichever is greater) ±1 digit max.

                                Analog input:

                                (±1%FS) ±1 digit max.

Input sampling period           250 ms

Hysteresis                      Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4

                                Models with analog input: 0.01 to 99.99% FS (in units of 0.01% FS)

Proportional band (P)           Models with thermocouple/platinum resistance thermometer input (universal input): 0.1 to 999.9 EU (in units of 0.1 EU) *4

                                Models with analog input: 0.1 to 999.9% FS (in units of 0.1% FS)

Integral time (I)               0 to 3999 s (in units of 1 s)

Derivative time (D)             0 to 3999 s (in units of 1 s) *5

Control period                  0.5, 1 to 99 s (in units of 1 s)

Manual reset value              0.0 to 100.0% (in units of 0.1%)

Alarm setting range             −1999 to 9999 (decimal point position depends on input type)

Affect of signal source         Thermocouple: 0.1°C/Ω max. (100 Ω max.)

resistance                      Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)

Insulation resistance           20 MΩ min. (at 500 VDC)

Dielectric strength             2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)

Vibration          Malfunction  10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions

resistance         Destruction  10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions

Shock              Malfunction  100 m/s2, 3 times each in X, Y, and Z directions

resistance         Destruction  300 m/s2, 3 times each in X, Y, and Z directions

Weight                          Controller: Approx. 90 g, Mounting Bracket: Approx. 10 g

Degree of protection            Front panel: IP66, Rear case: IP20, Terminals: IP00

Memory protection               Non-volatile memory (number of writes: 1,000,000 times)

Setup Tool                      CX-Thermo version 4.2 or higher

Setup Tool port                 Provided on the side of the E5GN. Connect this port to the computer when using the Setup Tool. An E58-CIFQ1 USB-Serial

                                Conversion Cable is required to connect the computer to the port on the side of the E5GN. *6

                   Approved     UL 61010-1, CSA C22.2 No. 1010-1

Standards          standards

                   Conformed    EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II

                   standards

                                EMI:                                                      EN 61326

                                Radiated Interference Electromagnetic Field Strength: EN 55011 Group        1,  class  A

                                Noise Terminal Voltage:                                   EN 55011 Group    1,  class  A

                                EMS:                                                      EN 61326

                                ESD Immunity:                                             EN 61000-4-2

EMC                             Electromagnetic Field Immunity:                           EN 61000-4-3

                                Burst Noise Immunity:                                     EN 61000-4-4

                                Conducted Disturbance Immunity:                           EN 61000-4-6

                                Surge Immunity:                                           EN 61000-4-5

                                Power Frequency Magnetic Field Immunity:                  EN 61000-4-8

                                Voltage Dip/Interrupting Immunity:                        EN 61000-4-11

*1. The indication accuracy of K thermocouples in the −200 to 1300°C range, T and N thermocouples at a temperature of −100°C max., and U

and L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.

is not specified. The indication accuracy of B thermocouples in the 400 to 800°C range is ±3°C max. The indication accuracy of the R and S

thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C,

whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ± 1 digit max.

*2. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage

*3. K thermocouple at −100°C max.: ±10° max.

*4. “EU” stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is °C or °F.

*5. When robust tuning (RT) is ON, the differential time is 0.0 to 999.9 (in units of 0.1 s).

*6. External serial communications (RS-232C or RS-485) and cable communications for the Setup Tool can be used at the same time.

                                                                                                                                                                 12
                                                                                                                                                                    E5GN

USB-Serial Conversion Cable                                                 Current Transformer (Order Separately)

Applicable OS           Windows 2000, XP, or Vista                          Ratings

Applicable software     CX-Thermo version 4 or higher                       Dielectric strength                               1,000 VAC for 1 min

Applicable models       E5AN/E5EN/E5CN/E5CN-U/E5AN-H/                       Vibration resistance                              50 Hz, 98 m/s2

                        E5EN-H/E5CN-H/E5GN                                                                                    E54-CT1: Approx. 11.5 g,

USB interface standard  Conforms to USB Specification 1.1.                  Weight                                            E54-CT3: Approx. 50 g

DTE speed               38400 bps                                           Accessories                                       Armatures (2)

                        Computer: USB (type A plug)                         (E54-CT3 only)                                    Plugs (2)

Connector               Temperature Controller: Setup Tool port

specifications          (on bottom of Controller)                           Heater Burnout Alarms, SSR Failure

Power supply            Bus power (Supplied from USB host                   Alarms, and Heater Overcurrent Alarms

                        controller.)

Power supply voltage    5 VDC                                               CT input                                             Models with detection for single-phase

                                                                            (for heater current                                  heaters: One input

Current consumption     70 mA                                               detection)

Ambient operating       0 to 55°C (with no condensation or icing)           Maximum heater current                               50 A AC

temperature                                                                 Input current indication

Ambient operating                                                           accuracy                                             ±5% FS ±1 digit max.

humidity                10% to 80%

                                                                            Heater burnout alarm                                 0.1 to 49.9 A (in units of 0.1 A)

Storage temperature     −20 to 60°C (with no condensation or                setting range *1                                     Minimum detection ON time: 100 ms

                        icing)                                              SSR failure alarm                                    0.1 to 49.9 A (in units of 0.1 A)

Storage humidity        10% to 80%                                          setting range *2                                     Minimum detection OFF time: 100 ms

Altitude                2,000 m max.                                        Heater overcurrent                                   0.1 to 49.9 A (in units of 0.1 A)

Weight                  Approx. 100 g                                       alarm setting range *3                               Minimum detection ON time: 100 ms

Note: A driver must be installed in the personal computer. Refer to         *1. For heater burnout alarms, the heater current will be measured

installation information in the operation manual for the                                             when the control output is ON, and the output assigned to the

Conversion Cable.                                                                                    alarm 1 function will turn ON if the heater current is lower than the

                                                                                                     set value (i.e., heater burnout detection current value).

Communications Specifications                                               *2. For SSR failure alarms, the heater current will be measured when

                                                                                                     the control output is OFF, and the output assigned to the alarm 1

Transmission line     RS-485: Multipoint                                                             function will turn ON if the heater current is higher than the set

connection method     RS-232C: Point-to-point                                                        value (i.e., SSR failure detection current value).

Communications        RS-485 (two-wire, half duplex), RS-232C               *3. For heater overcurrent alarms, the heater current will be

                                                                                                     measured when the control output is ON, and the output assigned

Synchronization       Start-stop synchronization                                                     to the alarm 1 function will turn ON if the heater current is higher

method                                                                                               than the set value (i.e., heater overcurrent detection current

Protocol              CompoWay/F, SYSWAY, or Modbus                                                  value).

Baud rate             1200, 2400, 4800, 9600, 19200, 38400, or              Electrical Life Expectancy Curve for

                      57600 bps                                             Relays (Reference Values)

Transmission code     ASCII

Data bit length *     7 or 8 bits                                           Life (× 104 operations)  500

Stop bit length *     1 or 2 bits                                                                    300

                                                                                                     200

                      Vertical parity (none, even, odd)                                              100

Error detection       Frame check sequence (FCS) with SYSWAY                                                                     E5GN

                      Block check character (BCC) with                                               50                          250 VAC, 30 VDC

                      CompoWay/F or CRC-16 Modbus                                                                                (resistive load)

                                                                                                     30                          cosφ = 1

Flow control          None                                                                           20

Interface             RS-485, RS-232C                                                                10

Retry function        None

                                                                                                     5

Communications        217 bytes                                                                      3

buffer                                                                                               2

Communications        0 to 99 ms                                                                     1

response wait time    Default: 20 ms                                                                      0.1  0.2  0.3  0.5  1  2       3   5     10

* The baud rate, data bit length, stop bit length, and vertical parity can                                                       Switching current (A)

be individually set using the Communications Setting Level.

                                                                                                                                                                            13
                                                                                                                                                                                E5GN

External Connections

• A voltage output (control output, for driving SSR) is not electrically                            ground. (If the control output terminals are connected to ground,

insulated from the internal circuits. When using a grounding                                        errors will occur in the measured temperature values as a result of

thermocouple, do not connect any of the control output terminals to                                 leakage current.)

E5GN                                                                                            Controllers

                                  The E5@N-@@@T@ is set for a K thermocouple

      Control output 1            (input type of 5) by default. If a difference sensor is

Relay output                      used, an input error (s.err) will occur. Check the

250 VAC, 2 A (resistive load)     setting of the input type parameter.

Voltage output (for driving SSR)

12 VDC, 21 mA                     RS-485                B  (+)          A (−)

                                  communications                                  DO NOT                                                 A heater burnout alarm, heater short

Current output                                                                    USE

0 to 20 mA DC                                                                                                                            alarm, heater overcurrent alarm, or

4 to 20 mA DC                     RS-232C                   SD          RD        SG                mA                                   input error is sent to the output to

                                                                                          +                       DO NOT                 which the alarm 1 function is assigned.

Load: 500 Ω max.                  communications                                                                  USE

                                                                CT                                             V        +  Analog input

Auxiliary outputs 1 and 2                                                         DO NOT  DO NOT

                                  CT input                                        USE     USE

Relay outputs                                                                                           ?

250 VAC, 2 A (resistive load)                                                                    A         B         B

                                                                                     EV2                                   Universal TC/Pt input

                                  Event input                              EV1                                 ?

                                                                                                                        +

                                                            7           8            9    10            11        12

                            • 100 to 240 VAC                1           2            3    4             5            6

                            • 24 VAC/VDC (no polarity)

                                                            Input power           +    Control          Auxiliary

                                                               supply                  output 1         output 1

                                                                                                        Terminal Arrangement

      Auxiliary output 2                                                                                Models with Screw                         Models with Screwless

      connection screws                                                                                 Terminal Blocks                           Clamp Terminal Blocks

                                                                                                            7     8     9  10  11  12             7     8     9      10     11     12

                13      14

                Auxiliary
                output 2

                                                                                                            1     2     3  4   5   6                 1     2      3      4      5      6

Wiring

E5GN                                                                                            E5GN-@-C

Models with Screw Terminal Blocks (M3 Screws)                                                   Models with Screwless Clamp Terminal Blocks

                                  M3 Screw Terminal Blocks                                                                               Models with Screwless Clamp Terminal Blocks

                                  • Crimp terminal shape: Forked or round                                                                • Wire stripping: 10 mm

                                  • Tightening torque for all terminals: 0.5 N•m                                                         • Ferrules: 8 to 12 mm

                                                                                                                                                                  0.8 to 1.4 mm

                                                           5.8 mm max.

                                                                                                                                                  10 mm                            8 to 12 mm

                                                           5.8 mm max.

                                                                                                                                                                                               14
                                                                                                                                                                                         E5GN

Nomenclature

E5GN

The front panel is the same  for the E5GN.

                                                                  No.1 display

                                                                                                                                        Operation indicators

                                 Temperature unit

                             Operation indicators                                                                                       No. 2 display

                                       Level Key

                                                                                    Mode Key  Down Key                      Up Key

Dimensions                                                                                                                                                                              (Unit: mm)

E5GN                                               48                     2                   99                                                               44.8

Models with Screw

Terminal Blocks

                             35                                   35                                                                             22                                  22

                                 24

                                                                                              Flush Mounting Adapter                 (Provided)

                                                                                    Waterproof Packing (Provided)

                                                       Panel      Cutout

                                 Mounted Separately                           Group Mounted                                          •  Recommended panel thickness is 1 to 5 mm.

                                       45+00.6                                (48 × number of units − 2.5)+10.0                      •  Group mounting is not possible in the vertical

                                                                                                                                        direction. (Maintain the specified mounting space

                                                                                                                                        between Controllers.)

                                                                                                                                     •  To mount the Controller so that it is waterproof, insert

                                                                                                                 22.2+00.3              the waterproof packing onto the Controller.

                                                                                                                                     •  When two or more Controllers are mounted, make

                                                                                                                                        sure that the surrounding temperature does not

                             40  min.                             Group mounting does not allow waterproofing.                          exceed the allowable operating temperature

                                                                                                                                        specified in the specifications.

                                                       22.2+00.3

E5GN-@-C                                           48                     2                   100                                                              44.8

Models with

Screwless Clamp

Terminal Blocks              35                                           35                                                                     22                                  22

                                 24

                                                                                              Flush Mounting Adapter                 (Provided)

                                                                                    Waterproof Packing (Provided)

                                                       Panel      Cutout                                                             •  Recommended panel thickness is 1 to 5 mm.

                                 Mounted Separately                       Group Mounted                                              •  Group mounting is not possible in the vertical

                                                                                                                                        direction. (Maintain the specified mounting space

                                       45+00.6                                (48 × number of units − 2.5)+10.0                         between Controllers.)

                                                                                                                                     •  When two or more Controllers are mounted, make

                                                                                                                                        sure that the surrounding temperature does not

                                                                                                                 22.2+00.3              exceed the allowable operating temperature

                                                                                                                                        specified in the specifications.

                             40  min.                             Group mounting does not allow waterproofing.

                                                       22.2+00.3

Accessories (Order Separately)

USB-Serial Conversion Cable

E58-CIFQ1

                                                                                                                            (2,100)

                                                                          250                 LED indicator (SD)                                               1,765

                                                       USB connector (type A plug)                                          LED indicator (RD)                            Serial connector

                                                                                                                                                                                                    15
                                                                                                                                                         E5GN

Waterproof Packing

Y92S-32 (for DIN 48 × 24)

                                    Order the Waterproof Packing separately if it becomes lost or damaged.

                                    The Waterproof Packing can be used to achieve an IP66 degree of protection.

                                    (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the

                                    operating environment. Therefore, periodic replacement is recommended to ensure the level of

                                    waterproofing specified in IP66. The time for periodic replacement depends on the operating

                                    environment. Be sure to confirm this point at your site. Consider one year a rough standard.

                                    OMRON shall not be liable for the level of water resistance if the customer does not perform

                                    periodic replacement.)

                                    The Waterproof Packing does not need to be attached if a waterproof structure is not required.

Current Transformers

E54-CT1                                                                      E54-CT1

                                    21                    2.8                Thru-current (Io) vs. Output Voltage

                                    15    5.8 dia.                           (Eo) (Reference Values)

                                                                     7.5     Maximum continuous heater current: 50 A (50/60 Hz)

                                                                             Number of windings: 400±2

                          25  3                                              Winding resistance: 18±2 Ω

                                                                             Output voltage (Eo) V (r.m.s.)  100 V      50 Hz

                                                    10.5

                                                                                                             10                    ∞

                                    40                                                                                             1 kΩ                  Distortion

                                          Two, 3.5 dia.                                                                                                  factor 10%

                                                                                                             1

                                                                                                                                                             3%

                              10                                                                                                                         1%

                                                                                                             100 mV

                                    30

                                                                                                             10                               100 Ω

E54-CT3                                                   2.36 dia.                                          1                                RL = 10 Ω

                                    30

                                          12 dia.                                                            100 µV

                                                                          9

                                                                                                             10

                                                                                                                     1         10  100 mA  1         10      100  1,000 A

                           40 × 40                                                                                                            Thru-current (Io) A (r.m.s.)

                                                                             E54-CT3

                                                                             Thru-current (Io) vs. Output Voltage

                                          Two, M3 (depth: 4)                 (Eo) (Reference Values)

                                                                             Maximum continuous heater current: 120 A (50/60 Hz)

                              15                                             (Maximum continuous heater current for the

                                                                             Temperature Controller is 50 A.)

                                    30                                       Number of windings: 400±2

                                                                             Winding resistance: 8±0.8 Ω

E54-CT3 Accessory                                                            Output voltage (Eo) V (r.m.s.)  100 V      50 Hz

                                                                                                                                                                  Distor-

• Armature                    Connection  Example                                                                                  ∞                              tion

                                                                                                             10                    1 kΩ                           factor

                                                                                                                                   500 Ω                          10%

                                          Armature                                                                                                                3%

Approx. 3 dia.                      Plug                                                                     1                                                   1%

                                                          Lead

                                                                                                             100 mV

                                                                                                                                              100 Ω

                                                                                                             10                               50 Ω

                      18                                                                                                                      RL = 10 Ω

• Plug                                                                                                       1

                                                                                                             100 µV

Approx. 6 dia.

                                                                                                             10

                (22)                                                                                                 1         10  100 mA  1         10      100  1,000 A

                                                                                                                                              Thru-current (Io) A (r.m.s.)

                                                                                                                                                                            16
Terms and Conditions of Sale

1.   Offer; Acceptance. These terms and conditions (these "Terms") are deemed                              ITY    OR    FITNESS    FOR     A   PARTICULAR       PURPOSE            OF  THE    PRODUCTS.

     part of all quotes, agreements, purchase orders, acknowledgments, price lists,                        BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE

     catalogs, manuals, brochures and other documents, whether electronic or in                            PRODUCTS         WILL     SUITABLY       MEET     THE       REQUIREMENTS                OF   THEIR

     writing, relating to the sale of products or services (collectively, the "Products")                  INTENDED USE. Omron further disclaims all warranties and responsibility of

     by Omron Electronics LLC and its subsidiary companies (“Omron”). Omron                                any type for claims or expenses based on infringement by the Products or oth-

     objects to any terms or conditions proposed in Buyer’s purchase order or other                        erwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obli-

     documents which are inconsistent with, or in addition to, these Terms.                                gation   hereunder      shall  be,  at  Omron’s   election,     to  (i)  replace        (in  the  form

2.   Prices; Payment Terms. All prices stated are current, subject to change with-                         originally     shipped  with   Buyer    responsible    for  labor   charges        for  removal   or

     out notice by Omron. Omron reserves the right to increase or decrease prices                          replacement thereof) the non-complying Product, (ii) repair the non-complying

     on any unshipped portions of outstanding orders. Payments for Products are                            Product, or (iii) repay or credit Buyer an amount equal to the purchase price of

     due net 30 days unless otherwise stated in the invoice.                                               the non-complying Product; provided that in no event shall Omron be responsi-

3.   Discounts. Cash discounts, if any, will apply only on the net amount of invoices                      ble for warranty, repair, indemnity or any other claims or expenses regarding

     sent to Buyer after deducting transportation charges, taxes and duties, and will                      the Products unless Omron’s analysis confirms that the Products were prop-

     be allowed only if (i) the invoice is paid according to Omron’s payment terms                         erly handled, stored, installed and maintained and not subject to contamina-

     and (ii) Buyer has no past due amounts.                                                               tion, abuse, misuse or inappropriate modification. Return of any Products by

4.   Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month or                         Buyer must be approved in writing by Omron before shipment. Omron Compa-

     the maximum legal rate, whichever is less, on any balance not paid within the                         nies shall not be liable for the suitability or unsuitability or the results from the

     stated terms.                                                                                         use of Products in combination with any electrical or electronic components,

5.   Orders. Omron will accept no order less than $200 net billing.                                        circuits, system assemblies or any other materials or substances or environ-

6.   Governmental Approvals. Buyer shall be responsible for, and shall bear all                            ments. Any advice, recommendations or information given orally or in writing,

     costs involved in, obtaining any government approvals required for the impor-                         are not to be construed as an amendment or addition to the above warranty.

     tation or sale of the Products.                                                                       See http://www.omron247.com or contact your Omron representative for pub-

7.   Taxes. All taxes, duties and other governmental charges (other than general                           lished information.

     real property and income taxes), including any interest or penalties thereon,                    14.  Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE

     imposed directly or indirectly on Omron or required to be collected directly or                       FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,

     indirectly by Omron for the manufacture, production, sale, delivery, importa-                         LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY

     tion, consumption or use of the Products sold hereunder (including customs                            WAY     CONNECTED         WITH      THE  PRODUCTS,          WHETHER         SUCH        CLAIM     IS

     duties and sales, excise, use, turnover and license taxes) shall be charged to                        BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.

     and remitted by Buyer to Omron.                                                                       Further, in no event shall liability of Omron Companies exceed the individual

8.   Financial. If the financial position of Buyer at any time becomes unsatisfactory                      price of the Product on which liability is asserted.

     to Omron, Omron reserves the right to stop shipments or require satisfactory                     15.  Indemnities. Buyer shall indemnify and hold harmless Omron Companies and

     security or payment in advance. If Buyer fails to make payment or otherwise                           their   employees       from   and  against  all  liabilities,  losses,     claims,     costs     and

     comply with these Terms or any related agreement, Omron may (without liabil-                          expenses (including attorney's fees and expenses) related to any claim, inves-

     ity and in addition to other remedies) cancel any unshipped portion of Prod-                          tigation, litigation or proceeding (whether or not Omron is a party) which arises

     ucts  sold  hereunder   and    stop   any  Products     in  transit  until  Buyer    pays  all        or is alleged to arise from Buyer's acts or omissions under these Terms or in

     amounts,    including   amounts     payable  hereunder,     whether  or     not  then      due,       any way with respect to the Products.        Without limiting the foregoing, Buyer (at

     which are owing to it by Buyer. Buyer shall in any event remain liable for all                        its own expense) shall indemnify and hold harmless Omron and defend or set-

     unpaid accounts.                                                                                      tle any action brought against such Companies to the extent based on a claim

9.   Cancellation;  Etc.    Orders    are  not  subject  to  rescheduling        or  cancellation          that any Product made to Buyer specifications infringed intellectual property

     unless Buyer indemnifies Omron against all related costs or expenses.                                 rights of another party.

10.  Force Majeure. Omron shall not be liable for any delay or failure in delivery                    16.  Property; Confidentiality. Any intellectual property in the Products is the exclu-

     resulting from causes beyond its control, including earthquakes, fires, floods,                       sive property of Omron Companies and Buyer shall not attempt to duplicate it

     strikes or other labor disputes, shortage of labor or materials, accidents to                         in  any  way     without  the   written  permission    of   Omron.       Notwithstanding          any

     machinery, acts of sabotage, riots, delay in or lack of transportation or the                         charges to Buyer for engineering or tooling, all engineering and tooling shall

     requirements of any government authority.                                                             remain the exclusive property of Omron. All information and materials supplied

11.  Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron:                            by Omron to Buyer relating to the Products are confidential and proprietary,

     a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship                        and Buyer shall limit distribution thereof to its trusted employees and strictly

          except in “break down” situations.                                                               prevent disclosure to any third party.

     b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall               17.  Export Controls. Buyer shall comply with all applicable laws, regulations and

          constitute delivery to Buyer;                                                                    licenses regarding (i) export of products or information; (iii) sale of products to

     c. All sales and shipments of Products shall be FOB shipping point (unless oth-                       “forbidden” or other proscribed persons; and (ii) disclosure to non-citizens of

          erwise stated in writing by Omron), at which point title and risk of loss shall                  regulated technology or information.

          pass from Omron to Buyer; provided that Omron shall retain a security inter-                18.  Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any right

          est in the Products until the full purchase price is paid;                                       and no course of dealing between Buyer and Omron shall operate as a waiver

     d. Delivery and shipping dates are estimates only; and                                                of rights by Omron. (b) Assignment. Buyer may not assign its rights hereunder

     e. Omron will package Products as it deems proper for protection against nor-                         without Omron's written consent. (c) Law. These Terms are governed by the

          mal handling and extra charges apply to special conditions.                                      law of the jurisdiction of the home office of the Omron company from which

12.  Claims. Any claim by Buyer against Omron for shortage or damage to the                                Buyer    is  purchasing   the     Products   (without  regard       to   conflict  of   law  princi-

     Products occurring before delivery to the carrier must be presented in writing                        ples).   (d) Amendment. These Terms constitute the entire agreement between

     to Omron within 30 days of receipt of shipment and include the original trans-                        Buyer and Omron relating to the Products, and no provision may be changed

     portation bill signed by the carrier noting that the carrier received the Products                    or waived unless in writing signed by the parties. (e) Severability. If any provi-

     from Omron in the condition claimed.                                                                  sion hereof is rendered ineffective or invalid, such provision shall not invalidate

13.  Warranties.    (a)  Exclusive  Warranty.   Omron’s   exclusive       warranty    is  that  the        any other provision. (f) Setoff. Buyer shall have no right to set off any amounts

     Products will be free from defects in materials and workmanship for a period of                       against the amount owing in respect of this invoice. (g) Definitions. As used

     twelve months from the date of sale by Omron (or such other period expressed                          herein, “including” means “including without limitation”; and “Omron Compa-

     in writing by Omron). Omron disclaims all other warranties, express or implied.                       nies” (or similar words) mean Omron Corporation and any direct or indirect

     (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION,                                           subsidiary or affiliate thereof.

     EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-

Certain Precautions on Specifications and Use

1.   Suitability of Use. Omron Companies shall not be responsible for conformity                           ADDRESS THE RISKS, AND THAT THE OMRON’S PRODUCT IS PROP-

     with any standards, codes or regulations which apply to the combination of the                        ERLY     RATED   AND      INSTALLED      FOR      THE  INTENDED             USE    WITHIN         THE

     Product in the Buyer’s application or use of the Product. At Buyer’s request,                         OVERALL EQUIPMENT OR SYSTEM.

     Omron will provide applicable third party certification documents identifying                    2.   Programmable Products. Omron Companies shall not be responsible for the

     ratings and limitations of use which apply to the Product. This information by                        user’s programming of a programmable Product, or any consequence thereof.

     itself is not sufficient for a complete determination of the suitability of the Prod-            3.   Performance      Data.    Data    presented  in   Omron     Company         websites,        catalogs

     uct in combination with the end product, machine, system, or other application                        and other materials is provided as a guide for the user in determining suitabil-

     or use. Buyer shall be solely responsible for determining appropriateness of                          ity and does not constitute a warranty. It may represent the result of Omron’s

     the particular Product with respect to Buyer’s application, product or system.                        test conditions, and the user must correlate it to actual application require-

     Buyer shall take application responsibility in all cases but the following is a                       ments. Actual performance is subject to the Omron’s Warranty and Limitations

     non-exhaustive list of applications for which particular attention must be given:                     of Liability.

     (i)   Outdoor use, uses involving potential chemical contamination or electrical                 4.   Change       in  Specifications.    Product  specifications     and      accessories         may  be

     interference, or conditions or uses not described in this document.                                   changed at any time based on improvements and other reasons. It is our prac-

     (ii)  Use in consumer products or any use in significant quantities.                                  tice to change part numbers when published ratings or features are changed,

     (iii) Energy control systems, combustion systems, railroad systems, aviation                          or when significant construction changes are made. However, some specifica-

     systems, medical equipment, amusement machines, vehicles, safety equip-                               tions of the Product may be changed without any notice. When in doubt, spe-

     ment, and installations subject to separate industry or government regulations.                       cial part numbers may be assigned to fix or establish key specifications for

     (iv) Systems, machines and equipment that could present a risk to life or prop-                       your application. Please consult with your Omron’s representative at any time

     erty. Please know and observe all prohibitions of use applicable to this Prod-                        to confirm actual specifications of purchased Product.

     uct.                                                                                             5.   Errors and Omissions. Information presented by Omron Companies has been

     NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS                                            checked and is believed to be accurate; however, no responsibility is assumed

     RISK  TO     LIFE   OR  PROPERTY         OR  IN  LARGE      QUANTITIES           WITHOUT              for clerical, typographical or proofreading errors or omissions.

     ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
Note:  This datasheet is provided as a guideline for selecting products. Do not use this document to operate the Unit.

       ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

       To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

       OMRON ELECTRONICS LLC • THE AMERICAS HEADQUARTERS

       Schaumburg, IL USA • 847.843.7900 • 800.556.6766 • www.omron247.com

       OMRON CANADA, INC. • HEAD OFFICE                                      OMRON ARGENTINA • SALES OFFICE

       Toronto, ON, Canada • 416.286.6465 • 866.986.6766 • www.omron247.com  Cono Sur • 54.11.4783.5300

       OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICE                         OMRON CHILE • SALES OFFICE

       São Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br            Santiago • 56.9.9917.3920

       OMRON ELECTRONICS MEXICO SA DE CV • HEAD OFFICE                       OTHER OMRON LATIN AMERICA SALES

       Apodaca, N.L. • 52.811.156.99.10 • 001.800.556.6766 • mela@omron.com  54.11.4783.5300

                                         © 2009 Omron Electronics LLC

       Cat. No. CMS_E5GN_E_5_1  12/09                 Specifications are subject to change without notice.
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Omron:

E5GN-R1TD ACDC24        E5GN-Q103TD-C-FLK AC/DC24  E5GN-Q103T-C-FLK AC100-240  E5GN-Q103TD-FLK

AC/DC24  E5GN-Q1TD-C AC/DC24  E5GN-Q1T-C AC100-240N6  E5GN-Q1TD AC/DC24        E5GN-QTD-C AC/DC24

E5GN-QT-C AC100-240N6   E5GN-QTD AC/DC24    E5GN-QT AC100-240  E5GN-R103TD-C-FLK AC/DC24  E5GN-

R103T-C-FLK AC100-240   E5GN-R103TD-FLK AC/DC24    E5GN-R103T-FLK AC100-240    E5GN-R1TD-C AC/DC24

E5GN-R1T-C AC100-240N6  E5GN-R1T AC100-240  E5GN-RTD-C AC/DC24  E5GN-RT-C AC100-240N6     E5GN-RTD

AC/DC24  E5GN-RT AC100-240  E5GN-Q103T-FLK AC100-240  E5GN-R1TD-AC/DC24
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

器件索引   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
搜索索引   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2020 EEWORLD.com.cn, Inc. All rights reserved