电子工程世界电子工程世界电子工程世界

型号

产品描述

搜索

E5EC-TQX4A5M-019

器件型号:E5EC-TQX4A5M-019
器件类别:热门应用    机电_工控_自动化   
厂商名称:OMRON
厂商官网:https://www.omron.com
下载文档

器件描述

Controllers Volt,HB, 6 event Trans AC volt

参数

产品属性属性值
Product AttributeAttribute Value
制造商:
Manufacturer:
Omron
产品种类:
Product Category:
Controllers
Analog / Digital:Digital
类型:
Type:
Programmable Temperature Controller
Display Type:11-Segment, 4 Digit
工作电源电压:
Operating Supply Voltage:
240 VAC
Mounting:Panel
大小:
Size:
48 mm x 96 mm
Number of Outputs:1
输出类型:
Output Type:
Voltage
系列:
Series:
E5EC-T
商标:
Brand:
Omron Automation and Safety
Number of Inputs:6
工厂包装数量:
Factory Pack Quantity:
1
零件号别名:
Part # Aliases:
E5ECTQX4A5M019
单位重量:
Unit Weight:
8.818490 oz

E5EC-TQX4A5M-019器件文档内容

New Product

Digital Temperature Controller

E5@C/E5@C-T

E5@C Series That Pursues Greater Visibility with Large White PV Display.
Models with Push-In Plus Terminal Blocks That Reduce Wiring Work, DIN

Track-mounting Models That Are Ideal for Connecting to PLCs, Plug-in

Models That Are Convenient for Maintenance, and Programmable Models for

a Wider Range of Application. A Wide Lineup of Models to Meet a Wide

Range of User Needs.

Digital Temperature Controllers: E5@C Series

                    Models with Screw Terminal Blocks/

48 × 24 mm          Models with Screwless Clamp               E5GC    page 2

                    Terminal Blocks

                    Models with Screw Terminal Blocks         E5CC    page 18

48 × 48 mm          Models with Push-In Plus Terminal Blocks  E5CC-B  page 18

                      Plug-in Models                          E5CC-U  page 18

                    Models with Screw Terminal Blocks         E5EC    page 40

48 × 96 mm

                    Models with Push-In Plus Terminal Blocks  E5EC-B  page 40

96 × 96 mm          Models with Screw Terminal Blocks         E5AC    page 40

DIN 22.5-mm-wide    Models with Screw Terminal Blocks         E5DC    page 58

Controllers That

Mount to DIN Track

Programmable Digital Temperature Controllers: E5@C-T Series

48 × 48 mm          Models with Screw Terminal Blocks         E5CC-T  page 74

48 × 96 mm          Models with Screw Terminal Blocks         E5EC-T  page 92

96 × 96 mm          Models with Screw Terminal Blocks         E5AC-T  page 92

                                                                               1
   Digital Temperature Controller
   E5GC
                                           (48 × 24 mm)

   Easy Operation and High Performance of

   the E5@C Series in a Compact 48 × 24-

   mm Body

   • A compact body of 48 × 24 × 90 mm (W × H × D) that is ideal for

   small equipment, laboratory instruments, and others.

   • White PV display with a height of 10.5 mm for high visibility even

   with the compact body.

   • Removable terminal block to simplify maintenance. Select from                 48 × 24 mm               48 × 24 mm

   screw terminal blocks or screwless clamp terminal blocks for the                Models with Screw     Models with Screwless

   wiring method.                                                                  Terminal Blocks       Clamp Terminal Blocks

                                                                                   E5GC-@6                  E5GC-@C

   • High-speed sampling at 50 ms.

   • Easy connections to a PLC with programless communications.                    Refer to your OMRON website for the most recent

   • Set up the Controller without wiring the power supply by                      information on applicable safety standards.

   connecting to the computer with a Communications Conversion                     Refer to Safety Precautions on 118.

   Cable (sold separately). Setup is easy with the CX-Thermo (sold

   separately).

   Main I/O Functions

   Sensor Input                                          E5GC

   Universal input

   • Thermocouple                                                                  Dual displays: PV/SV     4-digit             displays

   • Pt

   • Analog current/voltage

                 Indication Accuracy                                               Control Output 1

                 • Thermocouple input:                                             • Relay output

                 ±0.3% of PV                                                       • Voltage output (for driving SSR)

                 • Pt input: ±0.2% of PV                                           • Linear current output

                 • Analog input: ±0.2% of  FS

                 Sampling Period                                                   Auxiliary Outputs

                 • 50 ms

                                               • PF (shift) Key                    • None

   Event Inputs                                • Temperature status display        •1

   • None                                      • Simple programming                •2

   •1                                          • Independent heating and

   •2                                          cooling PID control

                                               • Changed parameter display

   Serial Communications                       • Display brightness setting

   • None                                      • Simple transfer output (only on

                                               models with liner current outputs)

   • RS-485                                    • Work Bit Message

   This datasheet is provided as a guideline for selecting products.

   Be sure to refer to the following manuals for application precautions and other information required for operation before attempting

   to use the product.

   E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174)

   E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)

2
                                                                                                                                        E5GC

Model Number Legend and Standard Models

Model Number Legend

E5GC-− @− @       − @ − @ − @ − M-@−@−@−(Example: E5GC-RX1A6M-015)
           A      BC     DE         F

               A         B          C         D                E          F

Model      Control       No. of     Power  Terminal            Input                                        Meaning

           outputs 1  auxiliary  supply       type             type       Options

           and 2        outputs  voltage

E5GC                                                                                                        48 × 24 mm

                                                                                     Control output 1                        Control output 2

           RX                                                                        Relay output                                 None

           QX                                                                        Voltage output                               None

                                                                                     (for driving SSR)

      *1 CX                                                                          Linear current output                        None

                  *2 0                                                                                      None

                      1                                                                                     1

                      2                                                                                     2

                                 A                                                                          100 to 240 VAC

                                 D                                                                          24 VAC/DC

                                           6                                            Screw terminal blocks (with cover)

                                           C                                         Screwless clamp terminal blocks *6

                                                            M                                               Universal input

                                                                                     HB alarm and HS alarm  Communications              Event inputs

                                                                          000        ---                                  ---                  ---

                                                                          015        ---                                  RS-485               ---

                                                                     *3   016        ---                                  ---                  1

                                                               *3, *4     023        1                                    ---                  ---

                                                                     *5   024        ---                                  ---                  2

*1. The control output can be used as a simple transfer output.
*2. Only option 000 can be selected if an auxiliary output is zero.
*3. Option 016 and 023 can be selected only if two auxiliary outputs are selected.
*4. Option with HB and HS alarms (023) cannot be selected if a linear current output is selected for the control output.
*5. Option 024 can be selected only if one auxiliary output is selected.
*6. The specifications are different for Temperature Controllers with Push-In Plus terminal blocks. Refer to Precautions when Wiring on page 124.

Heating and Cooling Control

Using Heating and Cooling Control

A Control Output Assignment

An auxiliary output is used as the cooling control output.

B Control

If PID control is used, you can set PID control separately for heating and cooling.

This allows you to handle control systems with different heating and cooling response characteristics.

                                                                                                                                                      3
   E5GC

   Optional Products (Order Separately)

   USB-Serial Conversion Cable                                                         Waterproof Packing

                Model                                                                                Model

               E58-CIFQ2                                                                             Y92S-P12

   Communications Conversion Cable                                                     Note: This Waterproof Packing is provided with the Digital

                                                                                       Temperature Controller.

                Model                                                                  Draw-out Jig

               E58-CIFQ2-E

   Note: Always use this product together with the E58-CIFQ2.                                        Model

   This Cable is used to connect to the bottom-panel Setup Tool                                      Y92F-55

   port.

   Current Transformers (CTs)                                                          CX-Thermo Support Software

   Hole diameter                      Model                                                          Model

   5.8 mm                    E54-CT1                                                   EST2-2C-MV4

   5.8 mm                    E54-CT1L*                                                 Note: CX-Thermo version 4.62 or higher is required for the E5GC.

   12.0 mm                   E54-CT3                                                   For the system requirements for the CX-Thermo, refer to

   12.0 mm                   E54-CT3L*                                                 information on the EST2-2C-MV4 on the OMRON website

                                                                                       (www.ia.omron.com).

   *Lead wires are included  with these CTs. If UL  certification  is  required,  use

   these CTs.

   Mounting Adapter

                Model

               Y92F-53 (2pcs)

   Note: This Mounting Adapter is provided with the Digital Temperature

   Controller.

4
                                                                                                                                          E5GC

Specifications

Ratings

Power supply voltage                  A in model number: 100 to 240 VAC, 50/60 Hz

                                      D in model number: 24 VAC, 50/60 Hz; 24 VDC

Operating voltage range               85 to 110% of rated supply voltage

Power consumption                     5.9 VA max. at 100 to 240 VAC, and 3.2 VA max. at 24 VAC or 1.8 W max. at 24 VDC

                                      Temperature input

                                      Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL II

                                      Platinum resistance thermometer: Pt100 or JPt100

Sensor input                          Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C

                                      Analog input

                                      Current input: 4 to 20 mA or 0 to 20 mA

                                      Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V

Input impedance                       Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/

                                      THB.)

Control method                        ON/OFF control or 2-PID control (with auto-tuning)

           Relay output               SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5

Control                               V, 10 mA (reference value)

output     Voltage output             Output voltage 12 VDC ±20% (PNP), max. Load current: 21 mA, with short-circuit protection circuit

           (for driving SSR)

           Linear current output      4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: Approx. 10,000

Auxiliary  Number of outputs          1 or 2 (depends on model)

output     Output specifications      SPST-NO relay outputs, 250 VAC, 2 A (resistive load),

                                      Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value)

           Number of inputs           1 or 2 (depends on model)

Event      External contact input     Contact input ON: 1 kΩ max., OFF: 100 kΩ min.

input      specifications             Non-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max.

                                      Current flow: approx. 7 mA per contact

Setting method                        Digital setting using front panel keys

Indication method                     11-segment digital displays and individual indicators

                                      Character height: PV: 10.5 mm, SV: 5.0 mm

Multi SP                              Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or

                                      serial communications. *

Bank switching                        None

                                      Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater

                                      burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter,

Other functions                       self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV

                                      change rate limit, logic operations, temperature status display, simple programming, moving average of

                                      input value, display brightness setting, simple transfer output, and work bit message

Ambient operating temperature         −10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting (with

                                      no condensation or icing)

Ambient operating humidity            25 to 85%

Storage temperature                   −25 to 65°C (with no condensation or icing)

Altitude                              2,000 m max.

Recommended fuse                      T2A, 250 VAC, time-lag, low-breaking capacity

Installation environment              Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1)

* There are up to four event inputs.

                                                                                                                                                  5
   E5GC

   Input Ranges

   Thermocouple/Platinum Resistance Thermometer (Universal inputs)

   Sensor                              Platinum resistance                                                                 Thermocouple                                                Infrared temperature

   type                                thermometer                                                                                                                                            sensor

   Sensor                              Pt100            JPt100              K               J               T         E      L           U         N     R     S     B     C/W   PLII  10 to  60 to  115 to  140 to
                                                                                                                                                                                       70°C   120°C  165°C   260°C
   specification

                           2300                                                                                                                                            2300

                           1800                                                                                                                                      1800

                           1700                                                                                                                          1700  1700

                           1600

                           1500

                           1400                                       1300                                                                         1300                          1300

   Temperature range (°C)  1300

                           1200

                           1100

                           1000  850                                                  850                                    850

                           900

                           800

                           700                                                                                        600

                           600         500.0          500.0                    500.0

                           500                                                                 400.0  400      400.0               400      400.0

                           400                                                                                                                                                                               260

                           300                                                                                                                                                                120    165

                           200                 100.0          100.0                                                                                                                    90

                           100                                                                                                                                       100

                           -100                0.0            0.0                                                                                        0     0           0     0     0      0      0       0

                           -200                                                -20.0  -100     -20.0                         -100

                                 -200  -199.9         -199.9          -200                            -200  -199.9    -200         -200  -199.9    -200

   Set value                     0     1       2        3     4       5        6      7         8     9        10     11     12    13       14     15    16    17    18    19    20    21     22     23      24

                           Shaded settings are the default settings.

   The applicable standards for the input types are as follows:

   K, J, T, E, N, R, S, B: JIS C 1602-2015, IEC 60584-1                                        JPt100: JIS C 1604-1989, JIS C 1606-1989

   L: Fe-CuNi, DIN 43710-1985                                                                  Pt100: JIS C 1604-1997, IEC 60751

   U: Cu-CuNi, DIN 43710-1985                                                                  PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)

   C/W: W5Re/W26Re, JIS C 1602-2015, ASTM E988-1990

   Analog input

                           Input type                   Current                                       Voltage

   Input specification                         4 to 20 mA     0 to 20 mA              1 to 5 V        0 to 5 V        0 to 10 V

                                               Usable in the following ranges by scaling:

   Setting range                               -1999 to 9999, -199.9 to 999.9,

                                               -19.99 to 99.99 or -1.999 to 9.999

   Set value                                        25                26              27              28                 29

6
                                                                                                                                                E5GC

Alarm Types

Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (See note.)

Auxiliary outputs are allocated to alarms. ON delays and OFF delays (0 to 999 s) can also be specified.

Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.

    To use alarm 1, set the output assignment to alarm 1.

Set                                                 Alarm output operation

value             Alarm type            When alarm value X           When alarm value X                           Description of function

                                                 is positive              is negative

0          Alarm function OFF                                 Output OFF                     No alarm

                                                                                             Set the upward deviation in the set point for the alarm upper

1          Upper- and lower-limit *1        ON      L     H          *2                      limit (H) and the lower deviation in the set point for the alarm

                                            OFF     SP        PV                             lower limit (L). The alarm is ON when the PV is outside this

                                                                                             deviation range.

2                                                         X               X                  Set the upward deviation in the set point by setting the alarm

           Upper-limit                      ON                       ON                      value (X). The alarm is ON when the PV is higher than the

(default)                                   OFF     SP        PV     OFF    SP           PV  SP by the deviation or more.

                                                    X                              X         Set the downward deviation in the set point by setting the

3          Lower-limit                      ON                       ON                      alarm value (X). The alarm is ON when the PV is lower than

                                            OFF     SP        PV     OFF    SP           PV  the SP by the deviation or more.

                                                                                             Set the upward deviation in the set point for the alarm upper

4          Upper- and lower-limit           ON      L     H          *3                      limit (H) and the lower deviation in the set point for the alarm

           range *1                         OFF     SP        PV                             lower limit (L). The alarm is ON when the PV is inside this

                                                                                             deviation range.

5          Upper- and lower-limit with      ON      L     H          *4                      A standby sequence is added to the upper- and lower-limit

           standby sequence *1          *5  OFF     SP        PV                             alarm (1). *6

6          Upper-limit with standby         ON            X          ON   X                  A standby sequence is added to the upper-limit alarm (2). *6

           sequence                         OFF     SP        PV     OFF    SP           PV

7          Lower-limit with standby         ON      X                ON            X         A standby sequence is added to the lower-limit alarm (3). *6

           sequence                         OFF     SP        PV     OFF    SP           PV

8          Absolute-value upper-            ON         X             ON         X            The alarm will turn ON if the process value is larger than the

           limit                            OFF  0            PV     OFF              0  PV  alarm value (X) regardless of the set point.

9          Absolute-value lower-limit       ON         X             ON         X            The alarm will turn ON if the process value is smaller than the

                                            OFF  0            PV     OFF              0  PV  alarm value (X) regardless of the set point.

           Absolute-value upper-                       X                        X            A standby sequence is added to the absolute-value upper-

10         limit with standby               ON                       ON

           sequence                         OFF  0            PV     OFF              0  PV  limit alarm (8). *6

11         Absolute-value lower-limit       ON         X             ON         X            A standby sequence is added to the absolute-value lower-

           with standby sequence            OFF  0            PV     OFF              0  PV  limit alarm (9). *6

12         LBA (alarm 1 type only)                                -                          *7

13         PV change rate alarm                                   -                          *8

14         SP absolute-value                ON         X             ON         X            This alarm type turns ON the alarm when the set point (SP)

           upper-limit alarm                OFF  0            SP     OFF              0  SP  is higher than the alarm value (X).

15         SP absolute-value                ON         X             ON         X            This alarm type turns ON the alarm when the set point (SP)

           lower-limit alarm                OFF  0            SP     OFF              0  SP  is lower than the alarm value (X).

                                        Standard Control             Standard Control

                                            ON         X             ON         X

                                            OFF  0            MV     OFF                 MV

           MV absolute-value                                                          0      This alarm type turns ON the alarm when the manipulated

16         upper-limit alarm *9         Heating/Cooling              Heating/Cooling         variable (MV) is higher than the alarm value (X).

                                        Control (Heating MV)         Control (Heating MV)

                                            ON         X

                                            OFF  0            MV     Always ON

                                        Standard Control             Standard Control

                                            ON         X             ON         X

                                            OFF  0            MV     OFF              0  MV

17         MV absolute-value            Heating/Cooling              Heating/Cooling         This alarm type turns ON the alarm when the manipulated

           lower-limit alarm *9         Control (Cooling MV)         Control (Cooling MV)    variable (MV) is lower than the alarm value (X).

                                            ON         X

                                            OFF  0            MV     Always ON

                                                                                                                                                               7
   E5GC

   *1. With set values 1, 4, and 5, the upper- and lower-limit values can       *4. Set value: 5, Upper- and lower-limit with standby sequence
        be set independently for each alarm type, and are expressed as          For Upper- and Lower-Limit Alarm Described Above at *2

        “L” and “H.”                                                            • In cases 1 and 2 above, the alarm is always OFF if the upper-

   *2. Set value: 1, Upper- and lower-limit alarm                               and lower-limit hysteresis overlaps.

        Case 1             Case 2     Case 3 (Always OFF)                       • In case 3, the alarm is always OFF.

                                                                     H<0, L<0   *5. Set value: 5, Upper- and lower-limit alarm with standby sequence

                L  H  SP   SP L    H     H               SP    L                The alarm is always OFF if upper- and lower-limit hysteresis

                H<0, L>0   H>0, L<0                                  H<0, L>0   overlaps.

                |H| < |L|  |H| > |L|  H            L SP              |H| ≥ |L|  *6. Refer to the E5@C Digital Temperature Controllers User’s Manual

                                                                     H>0, L<0   (Cat. No. H174) for information on the operation of the standby

                                                         SP H     L  |H| ≤ |L|  sequence.

   *3.  Set value: 4,      Upper- and lower-limit range                         *7. Refer to the E5@C Digital Temperature Controllers User’s Manual
                                                                                (Cat. No. H174) for information on the LBA.
        Case 1             Case 2     Case 3 (Always ON)

                                                                     H<0, L<0   *8. Refer to the E5@C Digital Temperature Controllers User’s Manual
                                                                                (Cat. No. H174) for information on the PV change rate alarm.
        L          H  SP   SP L    H     H               SP    L

        H<0, L>0           H>0, L<0                                  H<0, L>0   *9. When heating/cooling control is performed, the MV absolute-

        |H| < |L|          |H| > |L|  H            L SP              |H| ≥ |L|  value upper-limit alarm functions only for the heating operation

                                                                     H>0, L<0   and the MV absolute-value lower-limit alarm functions only for the

                                                         SP H     L  |H| ≤ |L|  cooling operation.

8
                                                                                                                                      E5GC

Characteristics

                                   Thermocouple:         (±0.3 % of indication value or ±1°C, whichever is greater) ±1 digit max.*1

Indication accuracy                Platinum resistance thermometer: (±0.2 % of indication value or ±0.8°C, whichever is greater) ±1 digit max.

(at the temperature of 23°C)       Analog input:         ±0.2% FS ±1 digit max.

                                   CT input:             ±5% FS ±1 digit max.

Simple transfer output accuracy    ±0.3% FS max.*2

Influence of temperature       *3  Thermocouple input (R, S, B, C/W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit max.

Influence of voltage   *3          Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max.    *4

                                   Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max.

Influence of EMS.                  Analog input: ±1% FS ±1 digit max.

(at EN 61326-1)                    CT input: ±5% FS ±1 digit max.

Input sampling period              50 ms

Hysteresis                         Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)

                                   Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)

Proportional band (P)              Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)

                                   Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)

Integral time (I)                  0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5

Derivative time (D)                0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5

Proportional band (P) for cooling  Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)

                                   Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)

Integral time (I) for cooling      0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5

Derivative time (D) for cooling    0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5

Control period                     0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)

Manual reset value                 0.0% to 100.0% (in units of 0.1%)

Alarm setting range                −1,999 to 9,999 (decimal point position depends on input type)

Influence of signal source         Thermocouple: 0.1°C/Ω max. (100 Ω max.), Platinum resistance thermometer: 0.1°C/Ω          max.   (10   Ω  max.)

resistance

Insulation resistance              20 MΩ min. (at 500 VDC)

Dielectric strength                100 to 240 VAC: 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge

                                   24 VAC/DC: 2,300 VAC, 50/60 Hz for 1 min between terminals of different charge

Vibration   Malfunction            10 to 55 Hz, 20 m/s2 for 10 min each in X, Y and Z directions

            Resistance             10 to 55 Hz, 20 m/s2 for 2 hr each in X, Y, and Z directions

Shock       Malfunction            100 m/s2, 3 times each in X, Y, and Z directions

            Resistance             300 m/s2, 3 times each in X, Y, and Z directions

Weight                             Controller: Approx. 80 g, Adapter: Approx. 4 g × 2

Degree of protection               Front panel: IP66, Rear case: IP20, Terminals: IP00

Memory protection                  Non-volatile memory (number of writes: 1,000,000 times)

Setup Tool                         CX-Thermo version 4.62 or higher

                                   E5GC   side panel:     An E58-CIFQ2 USB-Serial Conversion Cable is used to connect a USB port on the

Setup Tool  port                   E5GC   bottom panel:   computer. *6
                                                          An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion Cable

                                                          are used together to connect a USB port on the computer. *6

            Approved standards     cULus: UL 61010-1/CSA C22.2 No.61010-1, Korean wireless regulations (Radio law: KC Mark) (Some

Standards                          models only.) *7

            Conformed standards    EN 61010-1 (IEC 61010-1)

                                   EMI:                                                          EN61326-1 *8

                                   Radiated Interference Electromagnetic Field Strength:         EN55011    Group 1, class A

                                   Noise Terminal Voltage:                                       EN55011    Group 1, class A

                                   EMS:                                                          EN61326-1 *8

EMC                                ESD Immunity:                                                 EN61000-4-2

                                   Electromagnetic Field Immunity:                               EN61000-4-3

                                   Burst Noise Immunity:                                         EN61000-4-4

                                   Conducted Disturbance Immunity:                               EN61000-4-6

                                   Surge Immunity:                                               EN61000-4-5

                                   Voltage Dip/Interrupting Immunity:                            EN61000-4-11

*1. The indication accuracy of K thermocouples in the −200 to 1,300°C range, T and N thermocouples at a temperature of −100°C max., and U
and L thermocouples at any temperature is ±2°C ±1 digit max. The indication accuracy of B thermocouples at a temperature of 400°C max. is

not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max.

The indication accuracy of R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of C/W

thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max.

The indication accuracy of PLII thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.

*2. However, the precision between 0 and 4 mA for a 0 to 20 mA output is ±1% FS max.
*3. Ambient temperature: −10°C to 23°C to 55°C, Voltage range: −15% to 10% of rated voltage
*4. K thermocouple at −100°C max.: ±10°C max.
*5. The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*6. External serial communications (RS-485) and USB-Serial Conversion Cable communications can be used at the same time.
*7. Refer to your OMRON website for the most recent information on applicable models.
*8. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)

                                                                                                                                                     9
E5GC

USB-Serial Conversion Cable                                                                                               When Digital Temperature Controllers are connected,

    Applicable OS           Windows XP/Vista/7/8/10 *1                                                                    set points and RUN/STOP commands can be sent

    Applicable software     CX-Thermo version 4.62 or higher                      Component                               from the Digital Temperature Controller that is set as

                                                                                  Communi-                                the master to the Digital Temperature Controllers that

    Applicable models       E5@C-T Series, E5@C Series, and E5CB Series           cations                                 are set as slaves.

    USB interface standard  Conforms to USB Specification 2.0                                                             Slope and offsets can be set for the set point.

    DTE speed               38,400 bps                                                                                    Number of connected Digital Temperature

                            Computer: USB (Type A plug)                                                                   Controllers: 32 max. (including master)

    Connector               Digital Temperature Controller: Special serial                                                When Digital Temperature Controllers are connected,

    specifications          connector                                             Copying *                               the parameters can be copied from the Digital

    Power supply            Bus power (Supplied from the USB host controller) *2                                          Temperature Controller that is set as the master to the

                                                                                                                          Digital Temperature Controllers that are set as slaves.

    Power supply voltage    5 VDC                                                 MELSEC is a registered trademark of Mitsubishi Electric Corporation.

    Current                 450 mA max.                                           KEYENCE is a registered trademark of Keyence Corporation.

    consumption                                                                   * Both the programless communications and the component

    Output voltage          4.7±0.2 VDC (Supplied from USB-Serial Conversion      communications support the copying.

                            Cable to the Digital Temperature Controller.)         Current Transformer (Order Separately)

    Output current          250 mA max. (Supplied from USB-Serial Conversion      Ratings

                            Cable to the Digital Temperature Controller.)

    Ambient operating       0 to 55°C (with no condensation or icing)                                                                  E54-CT1                         E54-CT1L

    temperature                                                                                                                        E54-CT3                         E54-CT3L

    Ambient operating       10% to 80%                                            Dielectric strength                               1,000 VAC for 1 min          1,500 VAC for 1 min

    humidity                                                                      Vibration resistance                                               50 Hz, 98 m/s2

    Storage temperature     −20 to 60°C (with no condensation or icing)                                                             E54-CT1: Approx. 11.5 g      E54-CT1L: Approx. 14 g

    Storage humidity        10% to 80%                                            Weight                                            E54-CT3: Approx. 50 g        E54-CT3L: Approx. 57 g

    Altitude                2,000 m max.                                                                                            E54-CT3 Only

    Weight                  Approx. 120 g                                         Accessories                                       Armatures (2)                None

Windows is a registered trademark of Microsoft Corporation in the                                                                   Plugs (2)

United States and or other countries.

*1. CX-Thermo version 4.65 or higher runs on Windows 10.                          Heater Burnout Alarms and SSR Failure
*2. Use a high-power port for the USB port.
Note: A driver must be installed on the computer. Refer to the Instruction        Alarms

           Manual included with the Cable for the installation procedure.         CT input (for heater                                 Models with detection for single-phase

Communications Specifications                                                     current detection)                                   heaters: One input

    Transmission line                                                             Maximum heater current                               50 A AC

    connection method              RS-485: Multidrop                              Input current                                        ±5% FS ±1 digit max.

    Communications                 RS-485 (two-wire, half duplex)                 indication accuracy

    Synchronization method         Start-stop synchronization                     Heater burnout alarm                                 0.1 to 49.9 A (in units of 0.1 A)

    Protocol                       CompoWay/F, or Modbus                          setting range *1                                     Minimum detection ON time: 100 ms *3

    Baud rate *                    9,600, 19,200, 38,400, or 57,600 bps           SSR failure alarm setting                            0.1 to 49.9 A (in units of 0.1 A)

                                                                                  range *2                                             Minimum detection OFF time: 100 ms

    Transmission code              ASCII                                                                                               *4

    Data bit length *              7 or 8 bits                                    *1. For heater burnout alarms, the heater current will be measured
                                                                                                           when the control output is ON, and the output will turn ON if the
    Stop bit length *              1 or 2 bits
                                                                                                           heater current is lower than the set value (i.e., heater burnout
                                   Vertical parity (none, even, odd)
                                                                                                           detection current value).
                                   Block check character (BCC)
    Error detection                                                               *2. For SSR failure alarms, the heater current will be measured when
                                   with CompoWay/F or                                                      the control output is OFF, and the output will turn ON if the heater

                                   CRC-16 with Modbus                                                      current is higher than the set value (i.e., SSR failure detection

    Flow control                   None                                                                    current value).

    Interface                      RS-485                                         *3. The value is 30 ms for a control period of 0.1 s or 0.2 s.
                                                                                  *4. The value is 35 ms for a control period of 0.1 s or 0.2 s.
    Retry function                 None

    Communications buffer          217 bytes                                      Electrical Life Expectancy Curve for

    Communications                 0 to 99 ms                                     Control Output Relay (Reference Values)

    response wait time             Default: 20 ms

* The baud rate, data bit length, stop bit length, and vertical parity can        Life (× 104 operations)  500
    be individually set using the Communications Setting Level.
                                                                                                           300

Communications Functions                                                                                   200

                  You can use the memory in the PLC to read and write                                      100                         E5GC

                  E5@C parameters, start and stop operation, etc.                                          50                          250 VAC, 30 VDC

                  The E5@C automatically performs communications with                                                                  (resistive load)

                                                                                                           30                          cosφ = 1

                  PLCs. No communications programming is required.                                         20

    Programless   Number of connected Digital Temperature

    communica-    Controllers: 32 max. (Up to 16 for the FX Series)                                        10

    tions         Applicable PLCs                                                                          5
                  OMRON PLCs               CS Series, CJ Series, CP
                                           Series, NJ Series, or NX1P
                  Mitsubishi Electric PLCs MELSEC Q Series, L Series,                                      3

                                           FX3 Series, or iQ-R Series                                      2

                  KEYENCE PLCs             KEYENCE KV Series                                               1

                                                                                                                0.1  0.2  0.3  0.5  1          2  3  5       10

                                                                                                                                       Switching current (A)

10
                                                                                                                                                                                               E5GC

External Connections

E5GC

Control Outputs

Relay output                                                                                                   E5GC-@ @ @ @ @ M - @ @ @

250 VAC, 2 A                                                                                                            (1)    (2)(3)(4)(5)     (6)

(resistive load)                                                                                                                      ↑

Voltage output (for driving SSR)                                                                                               Terminal type

12 VDC, 21 mA                              Auxiliary outputs 1, 2

Linear current output                                                              The E5GC is set for a K-type thermocouple (input type = 5) by

0 to 20 mA DC                           Relay outputs                              default. An input error (s.err) wil occur if the input type setting

4 to 20 mA DC                           250 VAC, 2 A                               does not agree with the temperature sensor. Check the input type.

Load: 500 Ω max.                        (resistive load)

                  (6) Options                                                                                                        Use no-voltage inputs for the event inputs.

                  015                                016                           023                    024                        The polarity for non-contact inputs is given in parentheses.

                  Communications                     Event input            1      CT input               Event inputs  1 and  2

                  (RS-485)                                                                                EV2  (−)

                                  RS-485                           (−)                       CT

                                                     EV1                                                  EV1

                  B(+)                     A(−)

                                  7     8  9                       7     8     9          7      8  9          7    8   9

                                                                                                                                                (5) Sensor (Temperature/Analog) Input

                                                                                                                                                               −         +           +  mA  −

                  (3) Input Power Supply                                                                                                        TC      10      11       12       I  10  11     12

                  100 to 240 VAC                 24 VAC/DC                                                                                                           B   B               −   V     +

                                                                                                 7  8     9  10     11  12                              A

                                  1     2            1                2

                                                                                                                                                Pt      10      11       12  V       10  11     12

                                                                                                 1  2     3    4    5   6

                                                 (no polarity)

                                                                                                                        (2) Auxiliary    Outputs

                  (1) Control Outputs                                                                                      Auxiliary         Auxiliary outputs    1,  2

                                                                                                                           output 1                  Auxiliary

                  RX                             QX                                CX                                                                output 2

                  Relay output                   Voltage output (for driving SSR)  Linear current output                                     9

                                     R                  Q                                 C

                                                     +             −                   +     −

                                                                                                                             5    6                     5         6

                                  3     4            3             4                   3     4                          Auxiliary               Auxiliary

                                                                                                                        output 1                output 1

Note: 1.   The application of the terminals depends on the model.

       2.  Do not wire the terminals that are shown with a gray background.

       3.  When complying with EMC standards, the cable that connects the sensor must be 30 m or less.

           If the cable length exceeds 30 m, compliance with EMC standards will not be possible.

       4.  Connect M3 crimped terminals.

       5.  Due to UL Listing requirements, use the E54-CT1L or E54-CT3L Current Transformer with the factory wiring (internal wiring).

           Use a UL category XOBA or XOBA7 current transformer that is UL Listed for field wiring (external wiring) and not the factory wiring

           (internal wiring).

Isolation/Insulation Block Diagrams

                                           Sensor input and CT input

                                        Communications and event inputs

       Power      Voltage output (for driving SSR) and linear current                  output

       supply

                                                     Relay output

                                           Auxiliary outputs 1 and 2

                  : Reinforced insulation

                  : Functional isolation

Note:  Auxiliary  outputs 1 to 2 are not insulated.

                                                                                                                                                                                                      11
E5GC

Terminal Block Appearance

    E5GC-@6                                                                                         E5GC-@C

    Controllers with Screw Terminal Blocks (M3 Screws)                                              Controllers with Screwless Clamp Terminal Blocks

                                           Controllers with Screw Terminal Blocks                                                    Controllers with Screwless Clamp Terminals Blocks

                                           • Terminal type: Forked or round crimped terminals                                        • Wire stripping length: 8 to 12 mm

                                           • Tightening torque for all terminals: 0.43 to 0.58 N·m                                   • Ferrules: 8 to 12 mm

                                                                                                                                                                 0.8 to 1.4 mm

                                                       5.8 mm max.

                                                                                                                                     8 to 12 mm                                 8 to 12 mm

                                                       5.8 mm max.

Wires:AWG24 to AWG18 (equal to a cross-sectional area of 0.21 to 0.82 mm2) braided or solid wires

Note: Refer to Precautions When Wiring E5GC (Controllers with Screwless Clamp Terminal Blocks) on                                    page 125 for information on wiring

    Controllers with screwless clamp terminal blocks.

Nomenclature

E5GC                                               Front panel

                                                                                                                                     Left Side View of the E5GC

                                                                                                    No. 1 display                                                    Left-panel

                                                                                                                                                                     Setup Tool

             Temperature unit                                                                       PV or specified parameter                                        port

                                                                                                    No.2 display

                                                                                                    SP or specified parameter value  Bottom View of E5GC

             Operation indicators

      Press O Key once to go to Adjustment Level.

      Press O Key for at least 3 seconds                                           Use the U D Keys to set the parameter.

      to go to the Initial Setting Level.                                                                                                                 Bottom-panel Setup

                                                                                                                                                          Tool port

                                           Use the M Key to change                 Use S Key to change the

                                           to another parameter.                   digit (default setting).

12
                                                                                                                                                            E5GC

Dimensions                                                                                                                                                  (Unit: mm)

Controllers

E5GC-@6                                                                                           Waterproof Packing (Accessory)

Controllers with Screw                                                                            Mounting Adapter (Accessory)

Terminal Blocks                                     63.6            4                             90                            Terminal Cover (Accessory)

                                                    48                                                                                  44.8

                                                                       1

                                     24                          40.8                                                22                       22

                 • Use two Mounting Adapters, either on the top and bottom or on the right and left.

                 • Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller. The E58-

                    CIFQ2 USB-Serial Conversion Cable is required to connect to the port on the side panel. The E58-CIFQ2 USB-Serial Conversion Cable

                    and E58-CIFQ2-E Communications Conversion Cable are required to connect to the port on the bottom panel. (You cannot leave either

                    port connected constantly during operation.)

                    Mounted Separately                  Horizontally Group Mounted

                                                                L1

                                                                                22.2+00.3             To mount the Temperature Controller so that it is waterproof,

                 40 min                                                                               insert the Waterproof Packing onto the Temperature Controller.

                            45+0.60                       L1=(48×n-2.5)   +1.0                        Group mounting does not allow waterproofing.

                                                                          +0

                                         22.2+00.3  n: Number of mounted Controllers (2 ≤ n ≤ 6)

                 •  To install the Temperature Controller, insert it into a square hole in a panel with a thickness of 1 to 8 mm, and then insert the enclosed

                    adapter so that it locks into the grooves on the top and bottom or on the left and right of the rear case.

                 •  Tighten the two mounting screws on the top and bottom or on the right and left of the Mounting Adapters alternately little by little to main-

                    tain a balance, and tighten them to a torque of between 0.29 and 0.39 N·m.

                 •  When two or more Temperature Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable

                    operating temperature range given below.

                         Horizontal group mounting: −10 to 55°C

                 •  Use Temperature Controllers with Screwless Clamp Terminal Blocks for vertical group mounting.

E5GC-@C                                                                                           Waterproof Packing (Accessory)

Controllers with Screwless                                                                        Mounting Adapter (Accessory)

Clamp Terminal Blocks                               63.6          4                               93

                                                    48                                                                                  44.8

                                                                     1

                                     24                         40.8                                                 22                       22

                 • Use two Mounting Adapters, either on the top and bottom or on the right and left.

                 • Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller. The E58-

                    CIFQ2 USB-Serial Conversion Cable is required to connect to the port on the side panel. The E58-CIFQ2 USB-Serial Conversion Cable

                    and E58-CIFQ2-E Communications Conversion Cable are required to connect to the port on the bottom panel. (You cannot leave either

                    port connected constantly during operation.)

                    Mounted Separately              Horizontally Group Mounted                        Vertically Group Mounted

                                                              L1                                      45  +0.6

                                                                                                          +0

                                                                                22.2+00.3                                         To mount the Temperature Controller so

                 40 min                                                                                                           that it is waterproof, insert the Waterproof

                            45+0.60                       L1=(48×n-2.5)   +1.0                                                    Packing onto the Temperature Controller.

                                                                          +0

                                                    n: Number of mounted Controllers (2 ≤ n ≤ 6)                     L2           Group mounting does not allow waterproof-

                                         22.2+00.3                                                                                ing.

                                                                                                      L2=(24×n-1.5)  +1.0

                                                                                                                     +0

                 •  To install the Temperature Controller, insert it into a square hole in a panel with a thickness of 1 to 8 mm, and then insert the enclosed

                    adapter so that it locks into the grooves on the top and bottom or on the left and right of the rear case.

                 •  Tighten the two mounting screws on the top and bottom or on the right and left of the Mounting Adapters alternately little by little to main-

                    tain a balance, and tighten them to a torque of between 0.29 and 0.39 N·m.

                 •  When two or more Temperature Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable

                    operating temperature range given below.

                        Horizontal group mounting: −10 to 55°C

                        Vertical group mounting of two Controllers: −10 to 45°C

                        Vertical group mounting of three or more Controllers: −10 to 40°C

                 •  If you use vertical group mounting, you cannot draw out the interior body of the Controller.

                                                                                                                                                                                13
E5GC

Accessories (Order Separately)

USB-Serial Conversion Cable                                                                                (2110)

E58-CIFQ2                                                          250                                                                                              263                     1510

                                                                                            LED (RD)

                                                    USB connector

                                                    (type A plug)                                                                                                                                     Serial connector

                                                                                                           LED (PWR)

                                                                                                           LED (SD)

Conversion Cable

E58-CIFQ2-E

         Conversion Cable                           Connecting to                 the  E58-CIFQ2  USB-Serial Conversion Cable

                                                                                                           (2110)

             (1510)                                                          250                                                                                    263                     1510

Note: Always use this product together     with the     E58-CIFQ2.                          E58-CIFQ2 (Order separately)                                                                 Conversion Cable

Current Transformers

E54-CT1                                                                                                                   Thru-current (Io) vs. Output                                              Voltage (Eo)

                                                    21                            2.8                                     (Reference Values)

                                  Filler            15             5.8 dia.                                               E54-CT1 or E54-CT1L

                                  (epoxy)

                                                                   Case                7.5                                Maximum continuous heater current:                                        50 A (50/60 Hz)

                                                                                                                          Number of windings:                                                       400±2

                           25     2.5                                                                                     Winding resistance:                                                       18±2 Ω

                                                                   10.5                                                   Output voltage (Eo) V (r.m.s.)  100V

                                                                                                                                                                    Frequency: 50 Hz

                                                    40                            10                                                                      10                          ∞                   Distortion

                                  5                                                                                                                                          1kΩ                          factor

                                                                   Two, 3.5  dia.                                                                                                                         10%

                                                                                                                                                          1

                                                                                                                                                                                                          3%

                                                                                                                                                                                                      1%

                                                    30                                                                                                    100mV

                                                                                                                                                          10                                100Ω

E54-CT1L                                                                                                                                                  1                                 RL=10Ω

                                                    21

                               8                    15                                                                                                    100μV

                                                                                                                                                          10

                                                                                                                                                                 1       10  100mA       1        10      100  1,000A

                                                                                                                                                                                            Thru-current (Io) A (r.m.s.)

                     115±5                                         Cable (AWG18)

                                  (12)                             Shrinkable tube

                                                                   Case (PBT)               Mark (yellow)

                                          5.8 dia.                 Filler (epoxy)

                     25           2.5

                                                                   10.5

                                                    40                                 10

                                  5                                Two, 3.5 dia.

                                                    30

14
                                                                                                                                                                                 E5GC

E54-CT3                                                                            2.36  dia.         Thru-current (Io) vs. Output Voltage (Eo)

                                                    30                                                (Reference Values)

                          Filler                             12 dia.

                          (epoxy)                                                                     E54-CT3 or E54-CT3L

                                                                                                   9

                                                             Case                                     Maximum continuous heater current: 120 A (50/60 Hz)

                                                             (PBT)

                                                                                                      (Maximum continuous heater current for an OMRON

                                 40 × 40                                                              Digital Temperature Controller is 50 A.)

                                                                                                      Number of windings:                                               400±2

                                                                                                      Winding resistance:                                               8±0.8 Ω

                                                                                                      Output voltage (Eo) V (r.m.s.)  100V      Frequency: 50 Hz

                                                    40                             15                                                                                                Distortion

                                                                                                                                      10                          ∞                  factor

                                                                                                                                                    1kΩ                              10%

                                                                                                                                                    500Ω                             3%

                                    8                                                                                                 1                                          1%

                                                        Two, M3       (depth:  4)                                                     100mV

E54-CT3 Accessories                                 30                                                                                                                  100Ω

•  Armature               Connection                Example                                                                           10                                50Ω

                                                                                                                                                                        RL=10Ω

                                                        Armature                                                                      1

Approx. 3 dia.                            Plug

                                                             Lead                                                                     100μV

                                                                                                                                      10

                                                                                                                                             1  10  100mA            1  10      100  1,000A

                      18

                                                                                                                                                                        Thru-current (Io) A (r.m.s.)

• Plug

Approx. 6 dia.

                (22)

E54-CT3L                         8              30

                          100±5

                                                             Cable (AWG18)

                                                                  Case (PBT)

                              12.0                                Filler (epoxy)

                              dia.

                          40

                                                40                                             15

                                                        Two, M3

                                                        (depth: 4)

                          8

                                                30

                                                                                                                                                                                                      15
E5GC

    Mounting Adapter

    Y92F-53 (Two provided.)

One pair is provided with the Temperature

Controller. Order this Adapter separately if it                                   34.7

becomes lost or damaged.

                                                                        12

                                                                  11.8  9.4

    Waterproof Packing

    Y92S-P12

                                                  The Waterproof Packing is provided with the Temperature Controller.

                                                  Order the Waterproof Packing separately if it becomes lost or damaged.

                                                  The Waterproof Packing can be used to achieve an IP66 degree of protection.

                                                  (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating

                                                  environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing

                                                  specified in IP66. The time for periodic replacement depends on the operating environment.

                                                  Be sure to confirm this point at your site. Consider three years a rough standard.)

    Draw-out Jig

    Y92F-55

    Use this Draw-out Jig to remove the interior

    body of the Digital Temperature Controller

    from the case to perform maintenance

    without removing the terminal wiring.

                                                            32.9

                                                  15        30.5  1.4

                                                                            27.4

                                                      28.7              22

                                                                  20

                                                                                  23

16
MEMO

      17
       Digital Temperature Controller
       E5CC/E5CC-B/E5CC-U (48 × 48 mm)

Large White PV Display That’s Easier to Read.                                                                                            *

Easy to Use, from Model Selection to                                                                             (E5CC/-U)   (E5CC-B)

Setup and Operation.                                                                                       * CSA conformance evaluation by UL.

Models with Push-In Plus Terminal

Blocks Added to Lineup.

    •  The white PV display with a height of 15.2 mm improves visibility.

    •  High-speed sampling at 50 ms.

    •  Select from models with screw terminal blocks, models with                  48 × 48 mm                    48 × 48 mm          48 × 48 mm

       Push-In Plus terminal blocks for reduced wiring work, and                   Screw Terminal          Push-In Plus              Plug-in Models

                                                                                   Blocks              Terminal Blocks                   E5CC-U

       Plug-in Models that can be removed from the terminal block.                 E5CC                          E5CC-B

    •  Short body with depth of only 60 mm. (Screw Terminal Blocks)                Refer to your OMRON website for the most recent information on

                                                                                   applicable safety standards.

    •  Easy connections to a PLC with programless communications.

       Use component communications to link Temperature                                                Refer to Safety Precautions on 118.

       Controllers to each other.

    •  Set up the Controller without wiring the power supply by connecting to the computer with a Communications

       Conversion Cable (sold separately). Setup is easy with the CX-Thermo (sold separately).

Main I/O Functions

                                              E5CC/E5CC-B/E5CC-U

       Sensor Input

       Universal input

       • Thermocouple                                                                          Dual displays: PV/SV          4-digit displays

       • Pt

       • Analog current/voltage                                                                Control Output 1

                                                                                               • Relay output

                 Indication Accuracy                                                           • Voltage output

                 • Thermocouple  input                                                             (for driving SSR)

                  ±0.3%PV                                                         • Linear current output

                 ±1%PV

                 • Pt input: ±0.2% of PV

                 • Analog input: ±0.2% of FS                                                   Control Output 2

                                                                                                                       

                            Sampling Period                                                    • None                        • None

                            • 50 ms                                                            • Voltage output

                                                                                                   (for driving SSR)

       Event Inputs

                                                                        Auxiliary Outputs

       • None    • None       • None          • PF (shift) Key                                                         

       •2        •2                           • Temperature status display                     •3                •  2                • None

       •4                                     • Simple programming                                                                   •1

                                              • Independent heating and                                                              •2

       Remote SP Input                        cooling PID control

                         • Changed parameter display

       • None    • None                       • Display brightness setting                     Transfer Output

       •1                                                                                                      

                                                                                                   • None                    • None

       Serial Communications                                                                       •1

               

       • None               • None

       • RS-485

       This datasheet is provided as a guideline for selecting products.

       Be sure to refer to the following manuals for application precautions and other information required for operation before attempting

       to use the product.

       E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174)

       E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)

18
                                                                                                           E5CC/E5CC-B/E5CC-U

Model Number Legend and Standard Models

Model Number Legend

Models with Screw Terminal Blocks

E5CC-− @@−     3  − @  5  − M -− @− @@−       (Example: E5CC-RX3A5M-000)
               −       −
           A   BC      DE       F

                  A                B          C              D        E      F

Model          Control outputs     No. of  Power    Terminal       Input                                                 Meaning

               1 and 2          auxiliary  supply            type     type   Options

                                outputs    voltage

E5CC                                                                                                            48 × 48 mm

                                                                                                       Control output 1              Control output 2

           RX                                                                                              Relay output                        None

           QX                                                                                              Voltage output                      None

                                                                                                       (for driving SSR)

*1 *3      CX                                                                                     Linear current output *2                     None

           QQ                                                                                              Voltage output            Voltage output

                                                                                                       (for driving SSR)             (for driving SSR)

           CQ                                                                                     Linear current output *2           Voltage output

                                                                                                                                     (for driving SSR)

                                3                                                                          3 (one common)

                                           A                                                               100 to 240 VAC

                                           D                                                                    24 VAC/DC

                                                    5                                                      Screw terminal blocks (with cover)

                                                                   M                                       Universal input

                                                                                             HB alarm and  Communications  Event     Remote     Transfer

                                                                                             HS alarm                      inputs    SP Input   output

                                                                             000             ---           ---              ---      ---             ---

                                                                         *1  001             1             ---                    2  ---             ---

                                                                                             2

                                                                         *1  003             (for 3-phase  RS-485           ---      ---             ---

                                                                                             heaters)

                                                                         *3  004             ---           RS-485                 2  ---             ---

                                                                             005             ---           ---                    4  ---             ---

                                                                             006             ---           ---                    2             Provided.

                                                                             007             ---           ---                    2  Provided.       ---

*1. Options with HB and HS alarms (001 and 003) cannot be selected if a linear current output is selected for the control output.
*2. The control output cannot be used as a transfer output.
*3. Option 004 can be selected only when "CX" is selected for the control outputs.
Note: Draw-out-type models of the E5CC are available. Ask your OMRON representative for details.

Heating and Cooling Control

Using Heating and Cooling Control

A Control Output Assignment

If there is no control output 2, an auxiliary output is used as the cooling control output.

If there is a control output 2, the two control outputs are used for heating and cooling.

(It does not matter which output is used for heating and which output is used for cooling.)

B Control

If PID control is used, you can set PID control separately for heating and cooling.

This allows you to handle control systems with different heating and cooling response characteristics.

                                                                                                                                                           19
E5CC/E5CC-B/E5CC-U

Model Number Legend

Models with Push-In Plus Terminal Blocks

E5CC-@@         2  @B    M -@@@               (Example: E5CC-RX2ABM-000)
           −A−  − B − C −D − E −F−−

                   A               B          C                D         E      F

    Model      Control outputs     No. of  Power            Terminal  Input                                           Meaning

                1 and 2         auxiliary  supply              type      type   Options

                                outputs    voltage

E5CC                                                                                                         48 × 48 mm

                                                                                                   Control output 1               Control output 2

           RX                                                                                           Relay output                       None

           QX                                                                                          Voltage output                      None

                                                                                                   (for driving SSR)

      *1 CX                                                                                   Linear current output *2                     None

                                2                                                                       2 (one common)

                                           A                                                            100 to 240 VAC

                                           D                                                                 24 VAC/DC

                                                            B                                           Push-in plus terminal blocks

                                                                      M                                 Universal input

                                                                                         HB alarm and   Communications  Event     Remote    Transfer

                                                                                         HS alarm                       inputs    SP Input  output

                                                                                000      ---            ---             ---           ---        ---

                                                                            *1  001      1              ---                    2      ---        ---

                                                                            *1  002      1              RS-485          ---           ---        ---

                                                                                004      ---            RS-485                 2      ---        ---

                                                                                006      ---            ---                    2      ---   Provided.

*1. Options with HB and HS alarms (001, 002) cannot be selected if a linear current output is selected for the control output.
*2. The control output cannot be used as a transfer output.

Heating and Cooling Control

Using Heating and Cooling Control

A Control Output Assignment

An auxiliary output is used as the cooling control output.

B Control

If PID control is used, you can set PID control separately for heating and cooling.

This allows you to handle control systems with different heating and cooling response characteristics.

20
                                                                                                                    E5CC/E5CC-B/E5CC-U

Model Number Legend

Plug-in Models

E5CC-@@            @ @ U M -000                         (Example: E5CC-RW0AUM-000)

           A       BC    DE           F

                A        B            C          D         E            F

Model      Control       No. of   Power       Terminal  Input                                                       Meaning

           outputs  auxiliary     supply         type      type  Options

           1 and 2     outputs    voltage

E5CC                                                                                                        48 × 48 mm

                                                                                  Control output 1                             Control output  2

           RW                                                                     Relay output (SPDT)                             None

           QX                                                                     Voltage output (for driving SSR)                None

           CX                                                                     Linear current output *                         None

                    0                                                                                               None

                    1                                                                                               1

                    2                                                                                      2 (one common)

                                 A                                                                          100 to 240 VAC

                                 D                                                                                  24 VAC/DC

                                              U                                                             Plug-in model

                                                        M                                                   Universal input

                                                                                  HB alarm and HS  Communi-         Event inputs  Remote SP       Transfer

                                                                                  alarm            cations                        Input           output

                                                                        000          ---               ---                ---     ---             ---

* The control output can be used as a simple transfer output for the Digital Temperature Controllers manufactured in May 2014 or later.

List of Models

                                                                 Options                                   Model                       Model

Control output      No. of auxiliary     HB alarm and      No. of event                            Power supply voltage           Power supply voltage

                         outputs              HS alarm          inputs       Communications

                                                                                                   100 to 240 VAC                 24 VAC/DC

                    ---                                                                      E5CC-RW0AUM-000                   E5CC-RW0DUM-000

Relay output        1                    ---               ---               ---             E5CC-RW1AUM-000                   E5CC-RW1DUM-000

                    2                                                                        E5CC-RW2AUM-000                   E5CC-RW2DUM-000

                    ---                                                                      E5CC-QX0AUM-000                   E5CC-QX0DUM-000

Voltage output      1                    ---               ---               ---             E5CC-QX1AUM-000                   E5CC-QX1DUM-000

(for driving SSR)

                    2                                                                        E5CC-QX2AUM-000                   E5CC-QX2DUM-000

                    ---                                                                      E5CC-CX0AUM-000                   E5CC-CX0DUM-000

Linear current      1                    ---               ---               ---             E5CC-CX1AUM-000                   E5CC-CX1DUM-000

output

                    2                                                                        E5CC-CX2AUM-000                   E5CC-CX2DUM-000

Heating and Cooling Control

Using Heating and Cooling Control

A Control Output Assignment

An auxiliary output is used as the cooling control output.

B Control

If PID control is used, you can set PID control separately for heating and cooling.

This allows you to handle control systems with different heating and cooling response characteristics.

                                                                                                                                                            21
E5CC/E5CC-B/E5CC-U

Optional Products (Order Separately)

USB-Serial Conversion Cable                                                    Front Covers

                  Model                                                        Type                         Model

                E58-CIFQ2                                                      Hard Front Cover             Y92A-48H

Terminal Covers (for E5CC)                                                     Soft Front Cover             Y92A-48D

                  Model                                                        CX-Thermo Support Software

                E53-COV17                                                                        Model

         E53-COV23 (3pcs)                                                      EST2-2C-MV4

Note: The E53-COV10 cannot be used.                                            Note: CX-Thermo version 4.5 or higher is required for the E5CC.

    Refer to page 33 for the mounted dimensions.                               CX-Thermo version 4.61 or higher is required for the E5CC-U.

Waterproof Packing                                                             CX-Thermo version 4.65 or higher is required for the E5CC-B.

                                                                               CX-Thermo version 4.67 or higher is required for the E5CC-B

                  Model                                                        linear current output type.

                Y92S-P8                                                        For the system requirements for the CX-Thermo, refer to

Note: The Waterproof Packing is provided only with E5CC/E5CC-B                 information on the EST2-2C-MV4 on the OMRON website

    Controllers.                                                               (www.ia.omron.com).

    The E5CC-U cannot be waterproofed even if the Waterproof

    Packing is attached.

Current Transformers (CTs)

    Hole diameter                     Model

    5.8 mm                   E54-CT1

    5.8 mm                   E54-CT1L *

    12.0 mm                  E54-CT3

    12.0 mm                  E54-CT3L *

ˎ-FBEXJSFTBSFJODMVEFEXJUIUIFTF$5T*G6-DFSUJGJDBUJPOJTSFRVJSFE
VTF

    UIFTF$5T

Adapter

                  Model

                Y92F-45

Note: Use this Adapter when the panel has already been prepared for

    an E5B@ Controller.

Waterproof Cover

                  Model

                Y92A-48N

Mounting Adapter

                  Model

                Y92F-49

Note: This Mounting Adapter is provided with the Digital Temperature

    Controller.

DIN Track Mounting Adapter (for E5CC)

                  Model

                Y92F-52

Sockets (for E5CC-U)

                   Type                             Model

    Front-connecting Socket                         P2CF-11

    Front-connecting Socket with Finger Protection  P2CF-11-E

    Back-connecting Socket                          P3GA-11

    Terminal Cover for Back-connecting socket       Y92A-48G

    with Finger Protection

22
                                                                                                  E5CC/E5CC-B/E5CC-U

Specifications

Ratings

Power supply voltage                  A in model number: 100 to 240 VAC, 50/60 Hz

                                      D in model number: 24 VAC, 50/60 Hz; 24 VDC

Operating voltage range               85% to 110% of rated supply voltage

                                      Models with option selection of 000:5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or

Power consumption                     1.6 W max. at 24 VDC

                                      All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC

                                      Temperature input

                                      Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL II

                                      Platinum resistance thermometer: Pt100 or JPt100

Sensor input                          Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C

                                      Analog input

                                      Current input:     4 to 20 mA or 0 to 20 mA

                                      Voltage input:     1 to 5 V, 0 to 5 V, 0 to 10 V,or 0 to 50 mV (The 0 to 50 mV range applies to the

                                                         E5CC-U only for those manufactured in May 2014 or later.)

Input impedance                       Current input: 150 Ω max., Voltage input: 1 MΩ min.

                                      (Use a 1:1 connection when connecting the ES2-HB/THB.)

Control method                        ON/OFF control or 2-PID control (with auto-tuning)

                                      E5CC/E5CC-B: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations,

              Relay output                          minimum applicable load: 5 V, 10 mA (reference value)

Control                               E5CC-U:       SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations,

output                                              minimum applicable load: 5 V, 10 mA (reference value)

              Voltage output          Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit

              (for driving SSR)

              Linear current output   4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000

                                      E5CC: 3

              Number of outputs       E5CC-B: 2

Auxiliary                             E5CC-U: 1 or 2 (depends on model)

output                                SPST-NO relay outputs, 250 VAC, Models with 1 output: 3 A (resistive load), E5CC-U models with 2

              Output specifications   outputs: 3 A (resistive load), E5CC-B models with 2 outputs: 2 A (resistive load), Models with 3

                                      outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at

                                      5 V (reference value)

              Number of inputs        E5CC: 2 or 4 (depends on model)

Event                                 E5CC-B: 2 (depends on model)

input *1      External contact input  Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.

              specifications          Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.

                                      Current flow: Approx. 7 mA per contact

Transfer      Number of outputs       1 (only on models with a transfer output)

output *1     Output specifications   Current output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000

                                      Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., resolution: Approx. 10,000

Setting method                        Digital setting using front panel keys

Remote SP input *1 *2                 Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.)

                                      Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.)

Indication method                     11-segment digital display and individual indicators

                                      Character height: PV: 15.2 mm, SV: 7.1 mm

Multi SP *3                           Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations,

                                      or serial communications.

Bank switching                        None

                                      Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater

                                      burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital

Other functions                       filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root,

                                      MV change rate limit, logic operations, temperature status display, simple programming, moving

                                      average of input value, and display brightness setting

Ambient operating temperature         −10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting

                                      (with no condensation or icing)

Ambient operating humidity            25% to 85%

Storage temperature                   -25 to 65°C (with no condensation or icing)

Altitude                              2,000 m max.

Recommended fuse                      T2A, 250 VAC, time-lag, low-breaking capacity

Installation environment              Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1)

*1. There are no optional functions for the E5CC-U. Refer to Model Number Legend and List of Models on page 21.
*2. This function is not supported by the E5CC-B. Refer to Model Number Legend on page 20.
*3. With the E5CC-B, there can be up to four set points if event inputs are used to select them.

                                                                                                                                                      23
E5CC/E5CC-B/E5CC-U

Input Ranges

Thermocouple/Platinum Resistance Thermometer (Universal inputs)

    Sensor                               Platinum resistance                                                                Thermocouple                                                   Infrared temperature

    type                                  thermometer                                                                                                                                             sensor

    Sensor                                Pt100          JPt100               K               J               T          E     L           U          N     R      S     B     C/W   PLII  10 to  60 to  115 to  140 to
                                                                                                                                                                                           70°C   120°C  165°C   260°C
    specification

                            2300                                                                                                                                               2300

                            1800                                                                                                                                         1800

                            1700                                                                                                                            1700   1700

                            1600

                            1500

                            1400                                       1300                                                                           1300                           1300

    Temperature range (°C)  1300

                            1200

                            1100

                            1000    850                                                 850                                    850

                            900

                            800

                            700                                                                                          600

                            600           500.0          500.0                   500.0

                            500                                                                  400.0  400      400.0               400      400.0

                            400                                                                                                                                                                                  260

                            300                                                                                                                                                                   120    165

                            200                   100.0         100.0                                                                                                                      90

                            100                                                                                                                                          100

                            0                     0.0           0.0                                                                                             0  0           0     0     0      0      0       0

                            -100                                                 -20.0  -100     -20.0                         -100

                            -200    -200  -199.9         199.9         -200                             -200     -199.9  -200        -200     -199.9  -200

    Set value                       0     1       2      3      4          5     6      7        8      9        10      11    12    13       14      15    16     17    18    19    20    21     22     23      24

                            Shaded  settings are  the default   settings.

The applicable standards for the input types are as follows:

K, J, T, E, N, R, S, B: JIS C 1602-2015, IEC 60584-1                                             JPt100: JIS C 1604-1989, JIS C 1606-1989

L: Fe-CuNi, DIN 43710-1985                                                                       Pt100: JIS C 1604-1997, IEC 60751

U: Cu-CuNi, DIN 43710-1985                                                                       PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)

C/W: W5Re/W26Re, JIS C 1602-2015, ASTM E988-1990

Analog input

    Input type                                           Current                                                         Voltage

    Input                                 4 to 20 mA            0 to 20 mA              1 to 5 V              0 to 5 V         0 to 10 V              0 to 50 mV*

    specification

                                          Usable in the following ranges by scaling:

    Setting range                         -1999 to 9999, -199.9 to 999.9,

                                          -19.99 to 99.99 or -1.999 to 9.999

    Set value                                     25                   26                  27                    28                  29                     30

* The range applies to the E5CC-U only for those manufactured in May 2014 or later.

24
                                                                                                                    E5CC/E5CC-B/E5CC-U

Alarm Types

Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)

Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.

Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.

    To use alarm 1, set the output assignment to alarm 1.

Set                                                 Alarm output operation

value             Alarm type            When alarm value X            When alarm value X                            Description of function

                                                 is positive               is negative

0          Alarm function OFF                                 Output OFF                       No alarm

                                                                                               Set the upward deviation in the set point for the alarm upper

1          Upper- and lower-limit *1        ON      L     H           *2                       limit (H) and the lower deviation in the set point for the alarm

                                            OFF     SP        PV                               lower limit (L). The alarm is ON when the PV is outside this

                                                                                               deviation range.

2                                                         X                X                   Set the upward deviation in the set point by setting the alarm

           Upper-limit                      ON                        ON                       value (X). The alarm is ON when the PV is higher than the

(default)                                   OFF     SP        PV      OFF   SP            PV   SP by the deviation or more.

                                                    X                               X          Set the downward deviation in the set point by setting the

3          Lower-limit                      ON                        ON                       alarm value (X). The alarm is ON when the PV is lower than

                                            OFF     SP        PV      OFF   SP            PV   the SP by the deviation or more.

                                                                                               Set the upward deviation in the set point for the alarm upper

4          Upper- and lower-limit           ON      L     H           *3                       limit (H) and the lower deviation in the set point for the alarm

           range *1                         OFF     SP        PV                               lower limit (L). The alarm is ON when the PV is inside this

                                                                                               deviation range.

5          Upper- and lower-limit with      ON      L     H           *4                       A standby sequence is added to the upper- and lower-limit

           standby sequence *1          *5  OFF     SP        PV                               alarm (1). *6

6          Upper-limit with standby         ON            X           ON   X                   A standby sequence is added to the upper-limit alarm (2). *6

           sequence                         OFF     SP        PV      OFF   SP            PV

7          Lower-limit with standby         ON      X                 ON            X          A standby sequence is added to the lower-limit alarm (3). *6

           sequence                         OFF     SP        PV      OFF   SP            PV

8          Absolute-value upper-            ON         X              ON         X             The alarm will turn ON if the process value is larger than the

           limit                            OFF  0            PV      OFF              0  PV   alarm value (X) regardless of the set point.

9          Absolute-value lower-limit       ON         X              ON         X             The alarm will turn ON if the process value is smaller than the

                                            OFF  0            PV      OFF              0  PV   alarm value (X) regardless of the set point.

           Absolute-value upper-                       X                         X             A standby sequence is added to the absolute-value upper-

10         limit with standby               ON                        ON

           sequence                         OFF  0            PV      OFF              0  PV   limit alarm (8). *6

11         Absolute-value lower-limit       ON         X              ON         X             A standby sequence is added to the absolute-value lower-

           with standby sequence            OFF  0            PV      OFF              0  PV   limit alarm (9). *6

12         LBA (alarm 1 type only)                                 -                           *7

13         PV change rate alarm                                    -                           *8

14         SP absolute-value                ON         X              ON         X             This alarm type turns ON the alarm when the set point (SP)

           upper-limit alarm                OFF  0            SP      OFF              0  SP   is higher than the alarm value (X).

15         SP absolute-value                ON         X              ON         X             This alarm type turns ON the alarm when the set point (SP)

           lower-limit alarm                OFF  0            SP      OFF              0  SP   is lower than the alarm value (X).

                                        Standard Control              Standard Control

                                            ON         X              ON         X

                                            OFF  0            MV      OFF                 MV

           MV absolute-value                                                           0       This alarm type turns ON the alarm when the manipulated

16         upper-limit alarm *9         Heating/Cooling               Heating/Cooling          variable (MV) is higher than the alarm value (X).

                                        Control (Heating MV)          Control (Heating MV)

                                            ON         X

                                            OFF  0            MV      Always ON

                                        Standard Control              Standard Control

                                            ON         X              ON         X

                                            OFF  0            MV      OFF              0  MV

17         MV absolute-value            Heating/Cooling               Heating/Cooling          This alarm type turns ON the alarm when the manipulated

           lower-limit alarm *9         Control (Cooling MV)          Control (Cooling MV)     variable (MV) is lower than the alarm value (X).

                                            ON         X

                                            OFF  0            MV      Always ON

18         RSP absolute-value               ON         X              ON         X             This alarm type turns ON the alarm when the remote SP

           upper-limit alarm *10            OFF               RSP     OFF              0  RSP  (RSP) is higher than the alarm value (X).

                                                 0

19         RSP absolute-value               ON         X              ON         X             This alarm type turns ON the alarm when the remote SP

           lower-limit alarm *10            OFF  0            RSP     OFF              0  RSP  (RSP) is lower than the alarm value (X).

                                                                                                                                                                 25
E5CC/E5CC-B/E5CC-U

*1. With set values 1, 4 and 5, the upper and lower limit values can    *4. Set value: 5, Upper- and lower-limit with standby sequence
    be set     independently for each alarm type, and are expressed as
                                                                        For Upper- and Lower-Limit Alarm Described Above *2
    “L” and “H.”
                                                                        • Case 1 and 2
*2. Set value: 1, Upper- and lower-limit alarm
                                                                        Always OFF when the upper-limit and lower-limit hysteresis overlaps.

    Case 1            Case 2     Case 3 (Always ON)                     • Case 3: Always OFF

                                                            H<0, L<0    *5. Set value: 5, Upper- and lower-limit with standby sequence

            L  H  SP  SP L    H     H           SP    L

    H<0, L>0          H>0, L<0                              H<0, L>0    Always OFF when the upper-limit and lower-limit hysteresis

    |H| < |L|         |H| > |L|  H              L SP        |H| ≥ |L|   overlaps.

                                                            H>0, L<0    *6. Refer to the E5@C Digital Temperature Controllers User's Manual
                                                                        (Cat. No. H174) for information on the operation of the standby
                                                SP H     L  |H| ≤ |L|
                                                                        sequence.
*3. Set value: 4, Upper- and lower-limit range
                                                                        *7. Refer to the E5@C Digital Temperature Controllers User's Manual
    Case 1            Case 2     Case 3 (Always OFF)                    (Cat. No.H174)  for information on the loop burnout alarm (LBA).

                                                            H<0, L<0    *8. Refer to the E5@C Digital Temperature Controllers User's Manual

    L          H  SP  SP L    H     H           SP    L

    H<0, L>0          H>0, L<0                              H<0, L>0    (Cat. No. H174) for information on the PV change rate alarm.

    |H| < |L|         |H| > |L|  H              L SP        |H| ≥ |L|   *9. When heating/cooling control is performed, the MV absolute
                                                                        upper limit alarm functions only for the heating operation and the
                                                            H>0, L<0
                                                                        MV absolute lower limit alarm functions only for the cooling
                                                SP H     L  |H| ≤ |L|
                                                                        operation.

                                                                        *10.This value is displayed only when a remote SP input is used. It
                                                                        functions in both Local SP Mode and Remote SP Mode.

                                                                        Remote SP input is supported only for the E5CC.

26
                                                                                                             E5CC/E5CC-B/E5CC-U

Characteristics

                                       E5CC/E5CC-B

                                       Thermocouple:    (±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1

                                       Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.

Indication accuracy                    Analog input:    ±0.2% FS ±1 digit max.

(at the ambient temperature of 23°C)   CT input:        ±5% FS ±1 digit max.

                                       E5CC-U

                                       Thermocouple:    (±1% of indication value or ±2°C, whichever is greater) ±1 digit max. *1

                                       Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.

                                       Analog input:    ±0.2% FS ±1 digit max.

Transfer output accuracy               ±0.3% FS max.

Simple transfer output accuracy        ±0.3% FS max.*2

Remote SP Input Type                   ±0.2% FS ±1 digit max.

Influence of temperature *3            Thermocouple input (R, S, B, C/W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit max.

                                       Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *4
                                       Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
Influence of voltage *3
                                       Analog input: ±1%FS ±1 digit max.
Influence of EMS.
                                       CT input: ±5% FS ±1 digit max.
(at  EN 61326-1)
                                       Remote SP      input: ±1% FS ±1 digit max.

Input sampling period                  50 ms

Hysteresis                             Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)

                                       Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)

Proportional band (P)                  Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)

                                       Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)

Integral time (I)                      0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5

Derivative time (D)                    0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5

Proportional band (P) for cooling      Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)

                                       Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)

Integral time (I) for cooling          0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5

Derivative time (D) for cooling        0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5

Control period                         0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)

Manual reset value                     0.0 to 100.0% (in units of 0.1%)

Alarm setting range                    -1999 to 9999 (decimal point position depends on input type)

Influence of signal source resistance  Thermocouple: 0.1°C/Ω max. (100 Ωmax.)

                                       Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)

Insulation resistance                  20 MΩ min. (at 500 VDC)

Dielectric strength                    3,000 VAC, 50/60 Hz for 1 min between terminals of different charge

Vibration   Malfunction                10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions

            Resistance                 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions

Shock       Malfunction                100 m/s2, 3 times each in X, Y, and Z directions

            Resistance                 300 m/s2, 3 times each in X, Y, and Z directions

Weight                                 E5CC/E5CC-B: Controller: Approx. 120 g, Adapter: Approx. 10 g

                                       E5CC-U: Controller: Approx. 100 g, Adapter: Approx. 10 g

Degree of protection                   E5CC/E5CC-B: Front panel: IP66, Rear case: IP20, Terminals: IP00

                                       E5CC-U: Front panel: IP50, Rear case: IP20, Terminals: IP00

Memory protection                      Non-volatile memory (number of writes: 1,000,000 times)

                                       E5CC: CX-Thermo version 4.5 or higher

Setup Tool                             E5CC-B: CX-Thermo version 4.65 or higher *7

                                       E5CC-U: CX-Thermo version 4.61 or higher

Setup Tool port                        E5CC/E5CC-B/E5CC-U top panel:               An E58-CIFQ2 USB-Serial Conversion Cable is used to connect

                                                                                   to a USB port on the computer. *6

*1. The indication accuracy of K thermocouples in the -200 to 1,300°C range, T and N thermocouples at a temperature of -100°C max., and U and
     L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is

     not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and

     S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of C/W thermocouples is (±0.3% of PV or ±3°C,

     whichever is greater) ±1 digit max. The indication accuracy of PL II thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.

*2. However, the precision between 0 and 4 mA for a 0 to 20 mA output is ±1% FS max.
*3. Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*4. K thermocouple at -100°C max.: ±10°C max.
*5. The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*6. External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
*7. CX-Thermo version 4.67 or higher is required for the E5CC-B linear current output type.

                                                                                                                                                         27
E5CC/E5CC-B/E5CC-U

               Approved standards     cULus: UL 61010-1/CSA C22.2 No.61010-1 *8, KOSHA (S Mark) certification (Some models only.) *9,
                                      Korean wireless regulations (Radio law: KC Mark) (Some models only.) *9, Lloyd's standards *10
    Standards

               Conformed standards    EN 61010-1 (IEC 61010-1)

                                      EMI:                                                   EN 61326-1 *11

                                      Radiated Interference Electromagnetic Field Strength:  EN 55011 Group 1, class A

                                      Noise Terminal Voltage:                                EN 55011 Group 1, class A

                                      EMS:                                                   EN 61326-1 *11

    EMC                               ESD Immunity:                                          EN 61000-4-2

                                      Electromagnetic Field Immunity:                        EN 61000-4-3

                                      Burst Noise Immunity:                                  EN 61000-4-4

                                      Conducted Disturbance Immunity:                        EN 61000-4-6

                                      Surge Immunity:                                        EN 61000-4-5

                                      Voltage Dip/Interrupting Immunity:                     EN 61000-4-11

*8. The E5CC-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket. The P3GA-11
    is not certified for UL listing.

*9. Access the following website for information on certified models. http://www.ia.omron.com/support/models/index.html
*10.Refer to information on maritime standards in Shipping Standards on page 120 for compliance with Lloyd's Standards.
*11.Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)

28
                                                                                                                                       E5CC/E5CC-B/E5CC-U

USB-Serial Conversion Cable                                                                                                         When Digital Temperature Controllers are

Applicable OS               Windows XP/Vista/7/8/10 *1                                                                              connected, set points and RUN/STOP

                            CX-Thermo version 4.5 or higher                                                                         commands can be sent from the Digital

                            (Version 4.61 or higher is required for the          Component                                          Temperature Controller that is set as the

Applicable software         E5CC-U, Version 4.65 or higher is required           Communications *1                                  master to the Digital Temperature

                            for the E5CC-B *3.)                                                                                     Controllers that are set as slaves.

Applicable models           E5@C-T Series, E5@C Series, and E5CB Series                                                             Slope and offsets can be set for the set point.

                                                                                                                                    Number of connected Digital Temperature

USB interface standard      Conforms to USB Specification 2.0.                                                                      Controllers: 32 max. (including master)

DTE speed                   38400 bps                                                                                               When Digital Temperature Controllers are

Connector                   Computer: USB (type A plug)                                                                             connected, the parameters can be copied

specifications              Digital Temperature Controller:                      Copying *2                                         from the Digital Temperature Controller that is

                            Special serial connector                                                                                set as the master to the Digital Temperature

Power supply                Bus power (Supplied from USB host controller.)*2                                                        Controllers that are set as slaves.

Power supply voltage        5 VDC                                                MELSEC is a registered trademark of Mitsubishi Electric Corporation.

Current consumption         450 mA max.                                          KEYENCE is a registered trademark of Keyence Corporation.

                            4.7±0.2 VDC                                          *1. A Temperature Controller with version 1.1 or higher is required.
                                                                                                          A Temperature Controller with version 2.1 or higher is required for
Output voltage              (Supplied from USB-Serial Conversion Cable
                                                                                                          the FX Series or the KV Series.
                            to the Digital Temperature Controller.)
                                                                                 *2. Both the programless communications and the component
                            250 mA max.                                                                   communications support the copying.

Output current              (Supplied from USB-Serial Conversion Cable           Current Transformer (Order Separately) Ratings

                            to the Digital Temperature Controller.)

Ambient operating           0 to 55°C (with no condensation or icing)                                                                  E54-CT1                        E54-CT1L

temperature                                                                                                                            E54-CT3                        E54-CT3L

Ambient operating humidity  10% to 80%                                           Dielectric strength                                1,000 VAC for 1 min         1,500 VAC for 1 min

Storage temperature         -20 to 60°C (with no condensation or icing)          Vibration resistance                                              50 Hz, 98 m/s2

Storage humidity            10% to 80%                                           Weight                                             E54-CT1: Approx. 11.5 g     E54-CT1L: Approx. 14 g

Altitude                    2,000 m max.                                                                                            E54-CT3: Approx. 50 g       E54-CT3L: Approx. 57 g

Weight                      Approx. 120 g                                                                                           E54-CT3 Only

Windows is a registered trademark of Microsoft Corporation in the                Accessories                                        Armatures (2)               None

United States and or other countries.                                                                                               Plugs (2)

*1. CX-Thermo version 4.65 or higher runs on Windows 10.                         Heater Burnout Alarms and SSR Failure Alarms
*2. Use a high-power port for the USB port.
*3. CX-Thermo version 4.67 or higher is required for the E5CC-B                                                                     Models with detection for single-phase

linear current output type.                                                      CT input (for heater                               heaters: One input

Note: A driver must be installed on the computer. Refer to the Instruction       current detection)                                 Models with detection for singlephase or

Manual included with the Cable for the installation procedure.                                                                      three-phase heaters: Two inputs

Communications Specifications                                                    Maximum heater current                             50 A AC

Transmission line                                                                Input current                                      ±5% FS ±1 digit max.

connection method           RS-485: Multidrop                                    indication accuracy

Communications              RS-485 (two-wire, half duplex)                       Heater burnout alarm                               0.1 to 49.9 A (in units of 0.1 A)

Synchronization method      Start-stop synchronization                           setting range *1                                   Minimum detection ON time: 100 ms *3

                                                                                 SSR failure alarm                                  0.1 to 49.9 A (in units of 0.1 A)

Protocol                    CompoWay/F, or Modbus                                setting range *2                                   Minimum detection OFF time: 100 ms *4

Baud rate *                 9600, 19200, 38400, or 57600 bps                     *1. For heater burnout alarms, the heater current will be measured

Transmission code           ASCII                                                                         when the control output is ON, and the output will turn ON if the

Data bit length *           7 or 8 bits                                                                   heater current is lower than the set value (i.e., heater burnout

Stop bit length *           1 or 2 bits                                                                   detection current value).

                            Vertical parity (none, even, odd)                    *2. For SSR failure alarms, the heater current will be measured when the
                                                                                                          control output is OFF, and the output will turn ON if the heater current
Error detection             Block check character (BCC) with
                                                                                                          is higher than the set value (i.e., SSR failure detection current value).
                            CompoWay/F or CRC-16 Modbus
                                                                                 *3. The value is 30 ms for a control period of 0.1 s or 0.2 s.
Flow control                None                                                 *4. The value is 35 ms for a control period of 0.1 s or 0.2 s.

Interface                   RS-485                                               Electrical Life Expectancy Curve for

Retry function              None                                                 Control Output Relays (Reference Values)

Communications buffer       217 bytes

Communications              0 to 99 ms                                           Life (× 104 operations)  500

response wait time          Default: 20 ms                                                                300

* The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
                                                                                                          100
Communications Functions
                                                                                                          50
                            You can use the memory in the PLC to read and write
                                                                                                          30
                            E5@C parameters, start and stop operation, etc. The
                            E5@C automatically performs communications with
                            PLCs. No communications programming is required.
                                                                                                          10
                            Number of connected Digital Temperature

                            Controllers: 32 max. (Up to 16 for the FX Series)                             5

Programless                 Applicable PLCs                                                                       E5CC/E5CC-B

communications *1           OMRON PLCs                                                                    3       250 VAC, 30 VDC

                                   CS Series, CJ Series, CP Series,                                               (resistive load)

                                   NJ Series, or NX1P                                                             cosφ = 1

                            Mitsubishi Electric PLCs                                                      1    0  1         2       3  4           5         6

                                   MELSEC Q Series, L Series, FX3 Series,

                                   or iQ-R Series                                                                                      Switching current (A)

                            KEYENCE PLCs

                                   KEYENCE KV Series

                                                                                                                                                                                        29
E5CC/E5CC-B/E5CC-U

External Connections

E5CC (Screw Terminal Blocks)

          Control output 1

          Relay output                                                                                   E5CC- @ @           3  @         5  M - @@@

          250 VAC, 3A                                                                                                (1)     (2) (3) (4) (5)           (6)

          (resistive load)

          Voltage output                                                                                                                  ↑

          (for driving SSR)                                                 Auxiliary outputs 1, 2, 3                           Terminal type

          12 VDC, 21 mA                      Control output 2            Relay outputs

          Linear current output              Voltage output                   Models with 3 auxiliary         The E5CC is set for a K-type thermocouple (input type = 5) by

          0 to 20 mA DC                                                       outputs: 250 VAC, 2 A           default. An input error (s.err) will occur if the input type setting does

          4 to 20 mA DC                      (for driving SSR)                (resistive load)

          Load: 500 Ω max.                   12 VDC, 21 mA                                                    not agree with the temperature sensor. Check the input type.

    (1) Control outputs 1, 2                                                QQ

                  RX             QX                       CX                                             CQ

          Models with        Models with 1            Models with        Models with 2             Models with 2 Outputs: Linear Current          (2) Auxiliary Outputs

          1 Relay            Voltage Output           1 Linear           Voltage Outputs           Output and Voltage (for Driving SSR)                     Auxiliary outputs 1, 2, 3

          Output             (for Driving SSR)        Current Output     (for Driving SSR)

          1            OUT1  1          OUT1          1            OUT1  1             OUT1           1           OUT1                                          7
                                                                +                   +Q                        +C                                                       Auxiliary output 3
                       R             +  Q                          C                                                                                            8
                                     -
          2                  2                        2         -        2          -  Q              2       -   Q                                                    Auxiliary output 2

          3                  3                        3                  3          +  OUT2           3       +   OUT2                                          9      Auxiliary output 1

                                                                                                                                                                10     ●  ●

                                                                                                   1          13         7

                                                                                                   2          14         8

    (5) Sensor (Temperature/Analog) Input                                                          3          15         9                        (3) Input Power Supply

                  TC         Pt         I             V                                            4          16         10                         100 to 240 VAC           24 VAC/DC

                  4       A  4       +  4             4                                            5          17         11

               -          B      mA                -                                               6          18         12                                 11                    11

                  5       B  5       -  5             5

                  6          6          6       V     6                                                                                                     12                    12

          +                                        +

                                                                                                                                                                             (no polarity)

    (6) Options

          001                           003                           004                                005                              006                                007

          Event Inputs 1                Communications                Communications                     Event Inputs                     Event Inputs                       Event Inputs

          and 2, and CT1                (RS-485), CT1,                (RS-485), and                      1 to 4                           1 and 2, and                       1 and 2, and

                                        and CT2                       Event Inputs 3 and        4                                         Transfer Output                    Remote SP Input

          (-)         13                        B(+)  13                      B(+)     13                (-)         13                                 13                                 13

                                            RS-485                         RS-485                                                            (-)                             (-)

               EV1    14                        A(-)  14                      A(-)     14                     EV1    14                           EV1   14                           EV1   14

          EV2         15                              15                               15                EV2         15                        EV2      15                        EV2      15

                      16                              16                 (-)           16                (-)         16                                 16          +        +             16

          CT1         17                   CT1        17                               17                            17                                 17      +   V             V    +   17

                                                COM                           EV3                             EV3                                                                      mA

                      18                CT2           18                               18                            18                                 18      I   -        -             18

                                                                           EV4                           EV4

                                                                                                                                Use no-voltage inputs for the event inputs.

                                                                                                                                The polarity for non-contact inputs is given in parentheses.

Note: 1.  The application of the terminals depends on the model.

    2.    Do not wire the terminals that are shown with a gray background.

    3.    When complying with EMC standards, the cable that connects the sensor must be 30 m or less.

          If the cable length exceeds 30 m, compliance with EMC standards will not be possible.

    4.    Connect M3 crimped terminals.

    5.    Due to UL Listing requirements, use the E54-CT1L or E54-CT3L Current Transformer with the factory wiring (internal wiring).

          Use a UL category XOBA or XOBA7 current transformer that is UL Listed for field wiring (external wiring) and not the factory wiring

          (internal wiring).

30
                                                                                                                                        E5CC/E5CC-B/E5CC-U

E5CC-B (Push-In             Plus   Terminal Blocks)

                                                                               E5CC- @ @           2  @    B    M - @@@

                                                                                   (1)          (2) (3) (4) (5)             (6)

       Control output 1                                                                                    ↑

Relay output                                                                                          Terminal type

       250 VAC, 3A

       (resistive load)                   Auxiliary outputs 1, 2               The E5CC is set for a K-type thermocouple

Voltage output                        Relay outputs                            (input type = 5) by default. An input error

       (for driving SSR)                outputs: 250 VAC, 2 A                  (s.err) will occur if the input type setting does

       12 VDC, 21 mA                    (resistive load)                       not agree with the temperature sensor. Check

                                                                               the input type.

(1) Control output 1

          RX                      QX                      CX

Models with                    Models with 1          Models with 1

1 Relay Output                 Voltage Output         Linear Current Output

                               (for Driving SSR)

1               OUT1           1      +     OUT1      1           +  OUT1

2               R              2      −     Q         2           −  C

                                                                                                                                               (2) Auxiliary Outputs

                                                                                                1          17                  9

                                                                                                2          18               10                 Auxiliary output 2     9

                                                                                                3          19               11                                     10

                                                                                                4          20               12                                               *

(5) Sensor (Temperature/Analog) Input                                                           5          21               13                                     11

                                                                                                                                               Auxiliary output 1

           TC       Pt             I              V                                             6          22               14                                     12

           6    A        6     +   6              6                                             7          23               15

       -   7    B        7     mA  7           -  7                                             8          24               16

           8    B        8     -   8        V     8                                                                                            (3) Input Power Supply

       +                                       +                                                                                               100 to 240 VAC            24 VAC/DC

(6) Options                                                                                                                                    13                        13

001                                   002                         004                                 006                                          *                            *

Event Inputs 1                        Communications              Communications                      Event Inputs                             14                        14

and 2, and CT1                        (RS-485), CT1               (RS-485), and                       1 and 2, and                             15                        15

                                                                  Event Inputs 3 and 4                Transfer Output                              *                            *

           (-)                                                                                             (-)                                 16                        16

                17                    B(+)        17                   B(+)    17                               17

                            *                             *                        *                                           *                                         (no polarity)

           (-)  18                RS-485          18              RS-485       18                          (-)  18

EV1             19                    A(-)        19                   A(-)    19                     EV1       19

                20                                20      *                    20  *                            20

EV2                                                                       (-)                         EV2

                21                                21                           21                               21

CT1                                CT1                                    (-)      *                                              +

                22                                22                           22                               22

                23                                23                           23                               23          +     V  Transfer

                                                                     EV3                                                       I     Output

                24                                24                 EV4       24                               24                -

                                                                          Use no-voltage inputs for the event inputs.

                                                                          The polarity for non-contact inputs is given in parentheses.

Note:  1.  The application of the terminals depends on the model.

       2.  Do not wire the terminals that are shown with a gray background.

       3.  When complying with EMC standards, the cable that connects the sensor must be 30 m or less.

           If the cable length exceeds 30 m, compliance with EMC standards will not be possible.

       4.  Refer to Wiring Precautions for E5@C-B (Controllers with Push-In Plus Terminal Blocks) on page 126 for wire specifications and wiring

           methods.

       5.  Common terminals are indicated with asterisks (*). You can use the input power supply and communications common terminals for

           crossover wiring. Do not exceed the maximum number of Temperature Controllers given below if you use crossover wiring for the input

           power supply.

           100 to 240 VAC Controllers: 16 max.

           24 VAC/VDC Controllers: 8 max.

           Wiring Example:                    13

                                              14

                                              15

                                              16

                               To another E5@C

       6.  Due to UL Listing requirements, use the E54-CT1L or E54-CT3L Current Transformer with the factory wiring (internal wiring). Use a UL

           category XOBA or XOBA7 current transformer that is UL Listed for field wiring (external wiring) and not the factory wiring (internal wiring).

                                                                                                                                                                                        31
E5CC/E5CC-B/E5CC-U

E5CC-U (Plug-in Models)

                                         The E5CC-U is set for a K-type thermocouple (input type =                E5CC-                    UM-000

                                         5) by default. An input error (s.err) will occur if the input                    Control output 1

                                         type setting does not agree with the temperature sensor.

                                         Check the input type.                                                            Auxiliary outputs 1, 2

                                                                                                                          Relay output

                                                                                                                          250 VAC, 3 A (resistive load)

                                                                                     Control output 1

                                                                                                                          Auxiliary output 1

                                                                I                                                                       Auxiliary output 2:

                                                                   +                     Pt  A                                          Control output (cooling

                                                  mA                           V     TC

                                                                               −     −       B

                                                                   −        V

                                                                               +     +       B                            Input power supply

                                                                   Sensor (temperature/analog) input                              • 100 to 240 VAC

    Control output 1                                                                                                              • 24 VAC/DC (no polarity)

    Voltage output (for driving SSR)              Control output 1:

    12 VDC, 21 mA                                                     QX                                     CX                               RW

    Linear current output                         Models with 1                                           Models with 1                    Models with 1

    4 to 20 mA DC                                 Voltage Output                                          Linear Current                   Relay Output

    0 to 20 mA DC                                 (for Driving SSR)                                       Output

    Load: 500 Ω max.                                            −                                         −               Output 1

    Relay output (three terminals used)           Output 1                                   Output 1                             R

    SPDT, 250 VAC, 3 A                            Q             +                                      C

    (resistive load)                                                                                      +

Note: 1.  The application of the terminals depends on the model.

    2.    Do not wire the terminals that are shown with a gray background.

    3.    When complying with EMC standards, the cable that connects the sensor must be 30 m or less.

          If the cable length exceeds 30 m, compliance with EMC standards will not be possible.

    4.    Connect M3.5 crimped terminals.

Isolation/Insulation Block Diagrams

E5CC                                                                                                              E5CC-U

Models with 3 Auxiliary Outputs                                                                                   Models with           2  Auxiliary Outputs

                           Sensor input, CT inputs, and remote SP input                                                                                           Sensor input

                                         Communications and event inputs                                                  Power               Voltage output (for driving SSR) and linear  current  output

    Power                                Voltage output (for driving SSR),                                                supply

    supply                               linear current output, and transfer output                                                                               Relay output

                                                                                                                                                             Auxiliary outputs 1 and 2

                                                  Relay output

                                                 Auxiliary outputs 1, 2, 3                                                              :  Reinforced insulation

                                                                                                                                        :  Functional isolation

                        : Reinforced insulation

                        : Functional isolation

    Note: Auxiliary outputs 1 to 3 are not insulated.

E5CC-B

Models with             2 Auxiliary Outputs

                                         Sensor input and CT input

                                         Communications and event inputs

    Power                                Voltage output (for driving SSR),

    supply                               linear current output and transfer output

                                                  Relay output

                                                  Auxiliary outputs 1, 2

                        :  Reinforced insulation

                        :  Functional isolation

32
                                                                                                                                       E5CC/E5CC-B/E5CC-U

Nomenclature

E5CC                                             Front panel

E5CC-B       Temperature unit                                                                                             Top View of E5CC  Top View of E5CC-B            Top View of E5CC-U

E5CC-U  Operation indicators                                                               No. 1 display

                                                                                      PV or specified parameter

                                                                                           No. 2 display

                                                                                      SP or specified parameter value

                                                                                      Use the U D Keys to set the

                                                                                      parameter.

                                                                                                                                            Top-panel Setup Tool port

Press O Key once to go to Adjustment Level.                                     Use S Key to change the digit (default setting).

Press O Key for at least 3 seconds to go to Initial Setting     Level.

                                                                                Use the M Key to change to another parameter.

Dimensions                                                                                                                                                                    (Unit: mm)

Controllers

E5CC

                                                             4           73.1

                                                                         60

                               48 × 48                          1                                                         44.8 × 44.8

                                                                                           44.8 × 44.8    48.8     58

                                    Waterproof Packing             Mounting Adapter

                                    (Accessory)                    (Accessory)             Terminal Cover

                                                                                           (E53-COV17)

                                                                                           (Sold separately)

E5CC-B                                                                   (71.4)

                                                             4               67.4

                                    48 × 48                         (1)                                                   44.8 × 44.8

                                                                                           44.8 × 44.8     58

                                        Waterproof Packing               Mounting Adapter

                                        (Accessory)                      (Accessory)

              The Setup Tool port is on the top of the Temperature Controller.

              It is used to connect the Temperature Controller to the computer to use the Setup Tool.

              The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.

              Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.

              Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller.

                                                             Panel  Cutout

                              Mounted Separately                                   Group Mounted

                                                                                (48 × number of units - 2.5)+10.0

                                                                                                                       •  Recommended panel thickness is 1 to 5 mm.

                                                                                                          45+00.6      •  Group mounting is not possible in the vertical direction. (Maintain

                                                                                                                          the specified mounting space between Controllers.)

              60              min.                                                                                     •  To mount the Controller so that it is waterproof, insert the water-

                                                                                                                          proof packing onto the Controller.

                                                                                                                       •  When two or more Controllers are mounted, make sure that the

                                                 45+00.6                                                                  surrounding temperature does not exceed the allowable operating

                                                                                                                          temperature specified in the specifications.

                                        45+00.6                                                                        •  Use a control panel thickness of 1 to 3 mm if the Y92A-48N and a

                                                                                                                          USB-Serial Conversion Cable are used together.

                                                                                                                                                                                               33
E5CC/E5CC-B/E5CC-U

E5CC-U                                                                76.8

                         48 × 48                    4                 58.6          14.2

                                                                                            44.8 × 44.8

                                                                                    58

                                                                Mounting Adapter

                                                                (Accessory)

                         The Setup Tool port is on the top of the Temperature Controller.

                         It is used to connect the Temperature Controller to the computer to use the Setup Tool.

                         The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.

                         Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.

                         Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller.

                                                       Panel Cutout

                         Mounted Separately                                  Group Mounted

                                                                             (48 × number of units - 2.5)+10.0

                                                                                                                •  Recommended panel thickness is 1 to 5 mm.

                                                                                            45+00.6             •  Group mounting is not possible in the vertical direction. (Maintain

                                                                                                                   the specified mounting space between Controllers.)

                         60 min.                                                                                •  When two or more Controllers are mounted, make sure that the

                                                                                                                   surrounding temperature does not exceed the allowable operating

                                                       45+00.6                                                     temperature specified in the specifications.

                                                                                                                •  Use a control panel thickness of 1 to 3 mm if the Y92A-48N and a

                                                                                                                   USB-Serial Conversion Cable are used together.

                                   45+00.6

Accessories   (Order Separately)

USB-Serial Conversion Cable

E58-CIFQ2                                                                                                          (2110)

                                                                      250                                                         263                                 1510

                                                                                            LED (RD)

                                              USB connector

                                              (type A plug)                                                        LED (PWR)                                                Serial connector

                                                                                                                   LED (SD)

Terminal Covers                               48                                          Terminal Covers

E53-COV17                                                                                 E53-COV23 (Three Covers provided.)

                                                                                                                               2  3.8

                         48.8

                                                                                                                           10

                                                                                                                                                                       Terminal Cover

                                                                                                                                                                       (E53-COV23)

                         22                                                                                        44.8

                         9.1

    Terminal Cover (for  the P3GA-11 Back-connecting Socket)

    Y92A-48G                      Twelve, 6.4-dia.

                 34      Y92A-48G  UP         47.7×47.7                      48×48

                                        P  C

                                                       16.5     24.6

                                                                      27.6

                                                                             Note: You can attach the P3GA-11 Back-connecting Socket                             for  finger protection.

                                  47.4

34
                                                                                                                                E5CC/E5CC-B/E5CC-U

Waterproof Packing                                  The Waterproof Packing is provided only with the E5CC/E5CC-B.

Y92S-P8 (for DIN 48 × 48)                           It is not included with the E5CC-U.

                                                    Order the Waterproof Packing separately if it becomes lost or damaged.

                                                    The Waterproof Packing can be used to achieve an IP66 degree of protection.

                                                    (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the

                                                    operating environment. Therefore, periodic replacement is recommended to ensure the level of

                                                    waterproofing specified in IP66. The time for periodic replacement depends on the operating

                                                    environment. Be sure to confirm this point at your site.

                                                    Consider three years as a rough standard.)

                                                    The E5CC-U cannot be waterproofed even if the Waterproof Packing is attached.

Current Transformers

E54-CT1                                                                                         Thru-current (Io) vs. Output                                              Voltage (Eo)

                                                    21                 2.8                      (Reference Values)

                                  Filler            15  5.8 dia.                                E54-CT1 or E54-CT1L

                                  (epoxy)

                                                        Case                7.5                 Maximum continuous heater current:                                        50 A (50/60 Hz)

                                                                                                Number of windings:                                                       400±2

                           25     2.5                                                           Winding resistance:                                                       18±2 Ω

                                                        10.5                                    Output voltage (Eo) V (r.m.s.)  100V

                                                                                                                                          Frequency: 50 Hz

                                                    40                 10                                                       10                          ∞                   Distortion

                                  5                                                                                                           1kΩ                               factor

                                                        Two, 3.5  dia.                                                                                                          10%

                                                                                                                                1

                                                                                                                                                                                3%

                                                                                                                                                                            1%

                                                    30                                                                          100mV

                                                                                                                                10                                100Ω

E54-CT1L                                                                                                                        1                                 RL=10Ω

                                                    21

                               8                    15                                                                          100μV

                                                                                                                                10

                                                                                                                                       1  10  100mA            1        10      100  1,000A

                                                                                                                                                                  Thru-current (Io) A (r.m.s.)

                    115±5                               Cable (AWG18)

                                  (12)                  Shrinkable tube

                                                        Case (PBT)               Mark (yellow)

                                          5.8 dia.      Filler (epoxy)

                           25     2.5

                                                        10.5

                                                    40                      10

                                  5                     Two, 3.5 dia.

                                                    30

                                                                                                                                                                                                35
E5CC/E5CC-B/E5CC-U

E54-CT3                                                                                2.36  dia.         Thru-current (Io) vs. Output Voltage (Eo)

                                                        30                                                (Reference Values)

                              Filler                             12 dia.

                              (epoxy)                                                                     E54-CT3 or E54-CT3L

                                                                                                       9

                                                                 Case                                     Maximum continuous heater current: 120 A (50/60 Hz)

                                                                 (PBT)

                                                                                                          (Maximum continuous heater current for an OMRON

                                     40 × 40                                                              Digital Temperature Controller is 50 A.)

                                                                                                          Number of windings:                                               400±2

                                                                                                          Winding resistance:                                               8±0.8 Ω

                                                                                                          Output voltage (Eo) V (r.m.s.)  100V      Frequency: 50 Hz

                                                        40                             15                                                                                                Distortion

                                                                                                                                          10                          ∞                  factor

                                                                                                                                                        1kΩ                              10%

                                                                                                                                                        500Ω                             3%

                                        8                                                                                                 1                                          1%

                                                            Two, M3       (depth:  4)                                                     100mV

E54-CT3 Accessories                                     30                                                                                                                  100Ω

    •  Armature               Connection                Example                                                                           10                                50Ω

                                                                                                                                                                            RL=10Ω

                                                            Armature                                                                      1

    Approx. 3 dia.                            Plug

                                                                 Lead                                                                     100μV

                                                                                                                                          10

                                                                                                                                                 1  10  100mA            1  10      100  1,000A

                          18

                                                                                                                                                                            Thru-current (Io) A (r.m.s.)

    • Plug

    Approx. 6 dia.

                    (22)

E54-CT3L                             8              30

                              100±5

                                                                 Cable (AWG18)

                                                                      Case (PBT)

                                  12.0                                Filler (epoxy)

                                  dia.

                              40

                                                    40                                             15

                                                            Two, M3

                                                            (depth: 4)

                              8

                                                    30

36
                                                                                                        E5CC/E5CC-B/E5CC-U

Adapter

Y92F-45  Note: 1.    Use this Adapter when the Front Panel has already been prepared for the E5B@.

                 2.  Only black is available.

                 3.  You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial

                     Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel.

                 4.  You cannot use it together with the Y92F-49 Adapter that is enclosed with the Controller.

                                                                                                                     Fixture (Accessory)

                                                                         4.7                        76

                                                                                         69.6 to 77.6

                                               72 × 72

                                                                                                                          67 × 67 87

Mounted to E5CC                                                          Panel (1 to 8 mm)              Mounting Adapter

                                               72 × 72                                                  Y92F-30

                                                                                                        (Accessory)

                                                                48 × 48

                                                                2.2           4.7

                                                                                         62.8

                                                                              To back of the E5CC

DIN Track Mounting Adapter

Y92F-52  Note: This Adapter cannot be used together with the Terminal Cover.

                 Remove the Terminal Cover to use the Adapter.

                                                                                                                 This Adapter is used to mount the

                                                                                         61                      E5CC to a DIN Track.

                                                                                                                 If you use the Adapter, there is no

                                                                                                                 need for a plate to mount in the

                                                                                                                 panel or to drill mounting holes in

                                                                                               3.5               the panel.

                                               50                        38

Mounted to E5CC

                                                        48

                                                                                   80.5

                                                                                                                                                      37
E5CC/E5CC-B/E5CC-U

    Watertight Cover                                                                         Mounting Adapter

    Y92A-48N                                                                                 Y92F-49

                                                 21.9       14                                                                     The Mounting Adapter is provided with the

                                                       (2)                                                                         Temperature Controller.

                                                                                                                                   Order this Adapter separately if it becomes

                                                                                                                                   lost or damaged.

          87.7  79.2                                                  69

                                                                           12

                       67.6

    Protective  Cover                                                                        Protective Cover

    Y92A-48D           Note: This Protective Cover cannot be used                            Y92A-48H

                             if the Waterproof Packing is installed.                                                               This Protective Cover is hard type.

                         This Protective Cover is soft type.                                                                       Please use it for the mis-operation

                         It is able to operate the controller with using                                                           prevention etc.

                         this cover.

E5CC-U Wiring Socket

Front-connecting Socket

P2CF-11

                             Eleven, M3.5 × 7.5                            3                 4.5        Terminal  Layout/Internal Connections

                             sems screws                    7.8                                                       (Top View)

                                                                                                                      8  7   6  5                    Mounting Holes

                                                                                                                                   4

                                                                                                                                                     Two, 4.5 dia. mounting holes

                             70 max.                                                         35.4

                                                            Two,                                                                                            40±0.2

                                                            4.5-dia.                                                  9            3

                                                            holes                                                     10 11  1  2                   Note: Can also be mounted

                                                                                                                                                     to a DIN track

                                 4            50 max.                          31.2 max.

Note: 1.  A model with finger protection (P2CF-11-E) is also available.

    2.    You cannot use the P2CF-11 or P2CF-11-E together with the                          Y92F-45.

Back-connecting Socket

P3GA-11

                                                                                                        Eleven, M3.5  Terminal Layout/Internal Connections

                                      27dia.                                              4       7  3  sems screws                   (Bottom View)

                                                                                                                                      5  6  7   8

                                                                                                                                      4

                             45                                               25.6

                                                                                                                                      3         9

                                                                                                                                      2  1  11  10

                                          45                4.5 16.3  6.2

                                                                                                                  6

                                                                                    8.7

Note: 1.  Using any other sockets will adversely affect accuracy. Use only the specified sockets.

    2.    A Protective Cover for finger protection (Y92A-48G) is also available.

    3.    You cannot use the P3GA-11 together with the Y92F-45.

38
MEMO

      39
    Digital Temperature Controller
    E5EC/E5EC-B/E5AC
                                                                                                (48 × 96 mm/96 × 96 mm)

Large White PV Display That’s Easier to Read.                                                                                   *

Easy to Use, from Model Selection to                                                                        (E5EC/AC) (E5EC-B)

Setup and Operation.                                                                                * CSA conformance evaluation by UL.

Models with Push-In Plus Terminal

Blocks Added to 48 × 96-mm Lineup.

    • A white LCD PV display with a height of approx. 18 mm for the

    E5EC/E5EC-B and 25 mm for the E5AC improves visibility.

    • High-speed sampling at 50 ms.

    • With 48 x 96-mm Controllers, you can select between screw

    terminal blocks or Push-In Plus terminal blocks to save wiring work.

    • Short body with depth of only 60 mm. (Screw Terminal Blocks)              48 × 96 mm          48 × 96 mm

    • Easy connections to a PLC with programless communications.                Screw Terminal  Push-In Plus              96 × 96 mm

    Use component communications to link Temperature Controllers                Blocks              Terminal         Screw Terminal Blocks

                                                                                E5EC                Blocks                   E5AC

    to each other.                                                                                  E5EC-B

    • Tool ports are provided both on the top panel and the front panel.        Refer to your OMRON website for the most recent

                                                                                information on applicable safety standards.

    Set up the Controller without wiring the power supply by                                  Refer to Safety Precautions on page 118.

    connecting to the computer with a Communications Conversion

    Cable (sold separately). Setup is easy with the CX-Thermo (sold             separately).

Main I/O Functions

    Sensor Input                        E5EC/E5EC-B                     E5AC

    Universal input

    • Thermocouple

    • Pt                                                                                        Three-level Display

    • Analog current/voltage                                                                    PV, SV, and MV displayed           4-digit

                                                                                                at the same time.                  displays

          Indication Accuracy

          • Thermocouple input:                                                                 Control Output 1

          ±0.3% of PV                                                                           • Relay output

          • Pt input: ±0.2% of PV                                                               • Voltage output

          • Analog input: ±0.2% of  FS                                                          (for driving SSR)

                                                                                                • Linear current output

          Sampling Period

          • 50 ms                                                                               Control Output 2

                                                                                                              

                                                                                                • Voltage output         • None

    Event Inputs                                                                                (for driving SSR)

    • None                                                                                      • Relay output

    •2                                  • PF (shift) Key                                        • Linear current output

    •4                                  • Setup Tool port on front panel

    •6                                  • Temperature status display                            Auxiliary Outputs

                                        • Simple programming                                                  

    Remote SP Input                     • Independent heating and                               •4                       •2

    • None                              cooling PID control                                                              •4

    •1                                  • Changed parameter display

                                        • Display brightness setting                            Transfer Output

    Serial Communications                                                                       • None

    • None                                                                                      •1

    • RS-485

    This datasheet is provided as a guideline for selecting products.

    Be sure to refer to the following manuals for application precautions and other information required for operation before attempting

    to use the product.

    E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174)

    E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)

40
                                                                                                           E5EC/E5EC-B/E5AC

Model Number Legend and Standard Models

Model Number Legend

Models with Screw Terminal Blocks

E5EC-− @@−      4    − @  5   − M -− @− @@−  (Example:       E5EC-RX4A5M-000)
                −         −
            A   BC         DE         F

E5AC-− @@−      4    − @  5   − M -− @− @@−  (Example:       E5AC-RX4A5M-000)
                −         −
            A   BC         DE         F

                        A                    B         C        D         E          F

Model           Control outputs          No. of     Power    Terminal  Input                                             Meaning

                     1 and 2             auxiliary  supply      type   type   Options

                                         outputs    voltage

E5EC                                                                                                            48 × 96 mm

E5AC                                                                                                            96 × 96 mm

                                                                                                       Control output 1               Control output 2

            RX                                                                                             Relay output                        None

            QX                                                                                          Voltage output                         None

                                                                                                       (for driving SSR)

        *2  CX                                                                                         Linear current output                   None

            QQ                                                                                          Voltage output                Voltage output

                                                                                                       (for driving SSR)              (for driving SSR)

            QR                                                                                          Voltage output                Relay output

                                                                                                       (for driving SSR)

            RR                                                                                             Relay output               Relay output

        *2  CC                                                                                         Linear current output          Linear current

                                                                                                                                               output

        *2  CQ                                                                                         Linear current output          Voltage output

                                                                                                                                      (for driving SSR)

                                                                                                                                      Position-

            PR                                                                               Position-proportional relay output       proportional relay

                                                                                                                                               output

                                 *3   4                                                      4 (auxiliary outputs 1 and 2 with same common and

                                                                                                  auxiliary outputs 3 and 4 with same common)

                                                    A                                                      100 to 240 VAC

                                                    D                                                           24 VAC/DC

                                                             5                                             Screw terminal blocks (with cover)

                Control outputs 1     and 2                            M                                   Universal input

            For RX,

            QX, QQ,       For CX or   For PR                                                 HB alarm                         Event   Remote     Transfer

            QR, RR, or    CC                                                                 and           Communications     inputs  SP Input   output

            CQ                                                                               HS alarm

            Selectable    Selectable  Selectable                                     000          ---      ---                ---     ---              ---

Option                    Selectable  Selectable                                     004          ---      RS-485             2       ---              ---

selection                 Selectable                                                 005          ---      ---                4       ---              ---

conditions                                                                                        2

*1          Selectable                                                               009     (for 3-phase  RS-485             2       ---              ---

                                                                                             heaters)

            Selectable                                                               010          1        ---                4       ---              ---

            Selectable                                                               011          1        ---                6       Provided.  Provided.

                          Selectable                                                 013          ---      ---                6       Provided.  Provided.

                          Selectable  Selectable                                     014          ---      RS-485             4       Provided.  Provided.

*1. The options that can be selected depend on the type of control output.
*2. The control output cannot be used as a transfer output.
*3. A model with four auxiliary outputs must be selected.
Note: Draw-out-type models of the E5EC and E5AC are available. Ask your OMRON representative for details.

Heating and Cooling Control

Using Heating and Cooling Control

A Control Output Assignment

If there is no control output 2, an auxiliary output is used as the cooling control output.

If there is a control output 2, the two control outputs are used for heating and cooling.

(It does not matter which output is used for heating and which output is used for cooling.)

B Control

If PID control is used, you can set PID control separately for heating and cooling.

This allows you to handle control systems with different heating and cooling response characteristics.

                                                                                                                                                            41
E5EC/E5EC-B/E5AC

Model Number Legend

Models with Push-In Plus Terminal Blocks

E5EC-− @@−    − @  − @  B  M   -− @− @@−  (Example:         E5EC-RX4ABM-000)
                        −  −
           A  BC           DE       F

              A            B              C        D                E      F

    Model     Control      No. of      Power    Terminal                                                              Meaning

              outputs   auxiliary      supply      type     Input type     Options

              1 and 2      outputs     voltage

E5EC                                                                                                         48 × 96 mm

                                                                                                    Control output 1                  Control output 2

      *1 RX                                                                                             Relay output                       None

      *2 QX                                                                                             Voltage output                     None

                                                                                                    (for driving SSR)

      *2 CX                                                                                         Linear current output *3               None

                        2                                                                               2 independent points

                        4                                                                 4 (auxiliary outputs 1 and 2 with same common and auxiliary

                                                                                                    outputs 3 and 4 with same common)

                                    A                                                                   100 to 240 VAC

                                    D                                                                        24 VAC/DC

                                                B                                                       Push-in plus terminal blocks

                                                            M                                           Universal input

                                                                                          HB alarm                            Event   Remote    Transfer

                                                                                          and           Communications        inputs  SP Input  output

                                                                                          HS alarm

                                                                           000                 ---      ---                    ---    ---        ---

                                                                       *1  004                 ---      RS-485                 2      ---        ---

                                                                       *2  008                 1        RS-485                 2      ---        ---

                                                                       *2  010                 1        ---                    4      ---        ---

                                                                       *2  011                 1        ---                    6      Provided. Provided.

                                                                       *1  014                 ---      RS-485                 4      Provided. Provided.

*1. Option 004 and 014 cannot be selected if RX or QX is selected for the control output.
*2. Option 008, 010 and 011 cannot be selected if CX is selected for the control output.
*3. The control output cannot be used as a simple transfer output.

Heating and Cooling Control

Using Heating and Cooling Control

A Control Output Assignment

An auxiliary output is used as the cooling control output.

B Control

If PID control is used, you can set PID control separately for heating and cooling.

This allows you to handle control systems with different heating and cooling response characteristics.

42
                                                                                                   E5EC/E5EC-B/E5AC

Optional Products (Order Separately)

USB-Serial Conversion Cable                                           Current Transformers (CTs)

             Model                                                    Hole diameter                Model

       E58-CIFQ2                                                      5.8 mm          E54-CT1

Communications Conversion Cable                                       5.8 mm          E54-CT1L *

             Model                                                    12.0 mm         E54-CT3

       E58-CIFQ2-E                                                    12.0 mm         E54-CT3L *

Note: Always use this product together with the E58-CIFQ2.            * Lead wires are included with these CTs. If UL certification is
                                                                      required, use these CTs.
This Cable is used to connect to the front-panel Setup Tool
                                                                      CX-Thermo Support Software
port.

Terminal Covers (for E5EC/E5AC)                                                Model

                                                                             EST2-2C-MV4

             Model                                                    Note: CX-Thermo version 4.5 or higher is required for the E5EC/

E53-COV24 (3pcs)                                                      E5AC.

Note: The Terminal Covers E53-COV24 are provided with the Digital     CX-Thermo version 4.65 or higher is required for the E5EC-B.

Temperature Controller.                                               CX-Thermo version 4.67 or higher is required for the E5CC-B

Waterproof Packing                                                    linear current output type.

                                                                      For the system requirements for the CX-Thermo, refer to

Applicable Controller        Model                                    information on the EST2-2C-MV4 on the OMRON website

E5EC/E5EC-B                  Y92S-P9                                  (www.ia.omron.com).

E5AC                     Y92S-P10

Note: This Waterproof Packing is provided with the Digital

Temperature Controller.

Waterproof Cover

Applicable Controller        Model

E5EC/E5EC-B              Y92A-49N

E5AC                     Y92A-96N

Front Port Cover

             Model

       Y92S-P7

Note: This Front Port Cover is provided with the Digital Temperature

Controller.

Mounting Adapter

             Model

       Y92F-51 (2pcs)

Note: This Mounting Adapter is provided with the Digital Temperature

Controller.

                                                                                                                                        43
E5EC/E5EC-B/E5AC

Specifications

Ratings

    Power supply voltage                     A in model number: 100 to 240 VAC, 50/60 Hz

                                             D in model number: 24 VAC, 50/60 Hz; 24 VDC

    Operating voltage range                  85 to 110% of rated supply voltage

                                     E5EC/   Models with option selection of 000: 6.6 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or

                                     E5EC-B                                          2.3 W max. at 24 VDC

    Power consumption                        All other models: 8.3 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC

                                             Models with option selection of 000: 7.0 VA max. at 100 to 240 VAC, and 4.2 VA max. at 24 VAC or

                                     E5AC                                            2.4 W max. at 24 VDC

                                             All other models: 9.0 VA max. at 100 to 240 VAC, and 5.6 VA max. at 24 VAC or 3.4 W max. at 24 VDC

                                             Temperature input

                                             Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL II

                                             Platinum resistance thermometer: Pt100 or JPt100

    Sensor input                             Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C

                                             Analog input

                                             Current input: 4 to 20 mA or 0 to 20 mA

                                             Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V

    Input impedance                          Current input: 150 Ω max., Voltage input: 1 MΩ min.

                                             (Use a 1:1 connection when connecting the ES2-HB/THB.)

    Control method                           ON/OFF or 2-PID control (with auto-tuning)

                  Relay output               SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations,

    Control                                  minimum applicable load: 5 V, 10 mA (reference value)

    output        Voltage output             Output voltage: 12 VDC ±20% (PNP), max. load current: 40 mA, with short-circuit protection circuit

                  (for driving SSR)          (The maximum load current is 21 mA for models with two control outputs.)

                  Linear current output      4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000

                  Number of outputs          E5EC/E5AC: 4

    Auxiliary                                E5EC-B: 2 or 4 (depends    on    model)

    output                                   SPST-NO. relay outputs, 250 VAC, Models with 2 outputs: 3 A (resistive load),

                  Output specifications      Models with 4 outputs: 2 A (resistive load),

                                             Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value)

                  Number of inputs           2, 4 or 6 (depends on model)

    Event input   External contact input     Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.

                  specifications             Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.

                                             Current flow: Approx. 7 mA per contact

    Transfer      Number of outputs          1 (only on models with a transfer output)

    output        Output specifications      Current output: 4 to 20 mA DC, Load: 500 Ω max., Resolution: Approx. 10,000

                                             Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., Resolution: Approx. 10,000

    Remote SP input                          Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.)

                                             Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.)

    Potentiometer input *                    100 Ω to 10 kΩ

    Setting method                           Digital setting using front panel keys

                                             11-segment digital display and individual indicators

                                             Character height: E5EC/E5EC-B:          PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mm

    Indication method                                           E5AC:                PV: 25.0 mm, SV: 15.0 mm, MV: 9.5 mm

                                             Three displays Contents: PV/SV/MV, PV/SV/Multi-SP, or PV/SV/Remaining soak time, etc

                                             Numbers of digits: 4 digits each for PM, SV, and MV displays

    Multi SP                                 Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations,

                                             or serial communications.

    Bank switching                           None

                                             Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater

                                             burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital

    Other functions                          filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root,

                                             MV change rate limit, logic operations, temperature status display, simple programming, moving

                                             average of input value, and display brightness setting

    Ambient operating temperature            −10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting

                                             (with no condensation or icing)

    Ambient operating humidity               25 to 85%

    Storage temperature                      -25 to 65°C (with no condensation or icing)

    Altitude                                 2,000 m max.

    Recommended fuse                         T2A, 250 VAC, time-lag, low-breaking capacity

    Installation environment                 Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1)

* This function is not supported by the E5EC-B. Refer to Model Number Legend on page 42.

44
                                                                                                                                                                   E5EC/E5EC-B/E5AC

Input Ranges

Thermocouple/Platinum Resistance Thermometer (Universal inputs)

Sensor                             Platinum resistance                                                                     Thermocouple                                              Infrared temperature

type                                thermometer                                                                                                                                             sensor

Sensor                              Pt100          JPt100                K               J               T              E  L           U         N     R     S     B     C/W   PLII  10 to  60 to  115 to  140 to
                                                                                                                                                                                     70°C   120°C  165°C   260°C
specification

                        2300                                                                                                                                             2300

                        1800                                                                                                                                       1800

                        1700                                                                                                                           1700  1700

                        1600

                        1500

Temperature range (°C)  1400                                       1300                                                                          1300                          1300

                        1300

                        1200

                        1100

                        1000  850                                                  850                                     850

                        900

                        800

                        700                                                                                         600

                        600         500.0          500.0                    500.0

                        500                                                                 400.0  400      400.0                400      400.0

                        400                                                                                                                                                                                260

                        300                                                                                                                                                                 120    165

                        200                 100.0          100.0                                                                                                                     90

                        100                                                                                                                                        100

                        -100                0.0            0.0                                                                                         0     0           0     0     0      0      0       0

                        -200                                                -20.0  -100     -20.0                          -100

                              -200  -199.9         -199.9          -200                            -200     -199.9  -200         -200  -199.9    -200

Set value                     0     1       2      3       4       5        6      7        8      9        10      11     12    13       14     15    16    17    18    19    20    21     22     23      24

                        Shaded settings are the default settings.

The applicable standards for the input types are as follows:

K, J, T, E, N, R, S, B: JIS C 1602-2015, IEC 60584-1                                        JPt100: JIS C 1604-1989, JIS C 1606-1989

L: Fe-CuNi, DIN 43710-1985                                                                  Pt100: JIS C 1604-1997, IEC 60751

U: Cu-CuNi, DIN 43710-1985                                                                  PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)

C/W: W5Re/W26Re, JIS C 1602-2015, ASTM E988-1990

Analog input

Input type                                      Current                                     Voltage

Input                               4 to 20 mA        0 to 20 mA         1 to 5 V           0 to 5 V        0 to 10 V

specification

                                    Usable in the following ranges by scaling:

Setting range                       -1999 to 9999, -199.9 to 999.9,

                                    -19.99 to 99.99 or -1.999 to 9.999

Set value                                   25             26               27                 28                   29

                                                                                                                                                                                                                   45
E5EC/E5EC-B/E5AC

Alarm Types

Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)

Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.

Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.

        To use alarm 1, set the output assignment to alarm 1.

    Set                                                Alarm output operation

    value             Alarm type            When alarm value X           When alarm value X                             Description of function

                                                    is positive               is negative

    0          Alarm function OFF                                Output OFF                        No alarm

                                                                                                   Set the upward deviation in the set point for the alarm upper

    1          Upper- and lower-limit *1    ON         L     H           *2                        limit (H) and the lower deviation in the set point for the alarm

                                            OFF        SP        PV                                lower limit (L). The alarm is ON when the PV is outside this

                                                                                                   deviation range.

    2                                                        X                   X                 Set the upward deviation in the set point by setting the alarm

               Upper-limit                  ON                           ON                        value (X). The alarm is ON when the PV is higher than the

    (default)                               OFF        SP        PV      OFF     SP           PV   SP by the deviation or more.

                                            ON         X                 ON             X          Set the downward deviation in the set point by setting the

    3          Lower-limit                  OFF                  PV      OFF                  PV   alarm value (X). The alarm is ON when the PV is lower than

                                                       SP                        SP                the SP by the deviation or more.

                                                                                                   Set the upward deviation in the set point for the alarm upper

    4          Upper- and lower-limit       ON         L     H           *3                        limit (H) and the lower deviation in the set point for the alarm

               range *1                     OFF        SP        PV                                lower limit (L). The alarm is ON when the PV is inside this

                                                                                                   deviation range.

    5          Upper- and lower-limit with  ON         L     H           *4                        A standby sequence is added to the upper- and lower-limit

               standby sequence *1          *5 OFF     SP        PV                                alarm (1). *6

    6          Upper-limit with standby     ON               X           ON      X                 A standby sequence is added to the upper-limit alarm (2). *6

               sequence                     OFF        SP        PV      OFF     SP           PV

    7          Lower-limit with standby     ON         X                 ON             X          A standby sequence is added to the lower-limit alarm (3). *6

               sequence                     OFF        SP        PV      OFF     SP           PV

    8          Absolute-value upper-        ON            X              ON          X             The alarm will turn ON if the process value is larger than the

               limit                        OFF     0            PV      OFF               0  PV   alarm value (X) regardless of the set point.

    9          Absolute-value lower-limit   ON            X              ON          X             The alarm will turn ON if the process value is smaller than the

                                            OFF     0            PV      OFF               0  PV   alarm value (X) regardless of the set point.

               Absolute-value upper-                      X              ON          X             A standby sequence is added to the absolute-value upper-

    10         limit with standby           ON

               sequence                     OFF     0            PV      OFF               0  PV   limit alarm (8). *6

    11         Absolute-value lower-limit   ON            X              ON          X             A standby sequence is added to the absolute-value lower-

               with standby sequence        OFF     0            PV      OFF               0  PV   limit alarm (9). *6

    12         LBA (alarm 1 type only)                                -                            *7

    13         PV change rate alarm                                   -                            *8

    14         SP absolute-value            ON            X              ON          X             This alarm type turns ON the alarm when the set point (SP)

               upper-limit alarm            OFF     0            SP      OFF               0  SP   is higher than the alarm value (X).

    15         SP absolute-value            ON            X              ON          X             This alarm type turns ON the alarm when the set point (SP)

               lower-limit alarm            OFF     0            SP      OFF               0  SP   is lower than the alarm value (X).

                                            Standard Control             Standard Control

                                            ON            X              ON          X

                                            OFF     0            MV      OFF                  MV

               MV absolute-value                                                           0       This alarm type turns ON the alarm when the manipulated

    16         upper-limit alarm *9         Heating/Cooling              Heating/Cooling           variable (MV) is higher than the alarm value (X).

                                            Control (Heating MV)         Control (Heating MV)

                                            ON            X

                                            OFF     0            MV      Always ON

                                            Standard Control             Standard Control

                                            ON            X              ON         X

                                            OFF     0            MV      OFF               0  MV

    17         MV absolute-value            Heating/Cooling              Heating/Cooling           This alarm type turns ON the alarm when the manipulated

               lower-limit alarm *9         Control (Cooling MV)         Control (Cooling MV)      variable (MV) is lower than the alarm value (X).

                                            ON            X

                                            OFF     0            MV      Always  ON

    18         RSP absolute-value           ON            X              ON          X             This alarm type turns ON the alarm when the remote SP

               upper-limit alarm *10        OFF                  RSP     OFF               0  RSP  (RSP) is higher than the alarm value (X).

                                                    0

    19         RSP absolute-value           ON            X              ON          X             This alarm type turns ON the alarm when the remote SP

               lower-limit alarm *10        OFF     0            RSP     OFF               0  RSP  (RSP) is lower than the alarm value (X).

46
                                                                                              E5EC/E5EC-B/E5AC

*1. With set values 1, 4 and 5, the upper and lower limit values can   *4. Set value: 5, Upper- and lower-limit with standby sequence
be set independently for each alarm type, and are expressed as
                                                                       For Upper- and Lower-Limit Alarm Described Above *2
“L” and “H.”
                                                                       • Case 1 and 2
*2. Set value: 1, Upper- and lower-limit alarm
                                                                          Always OFF when the upper-limit and lower-limit hysteresis overlaps.

Case 1         Case 2     Case 3 (Always ON)                           •  Case 3: Always OFF

                                                            H<0, L<0   *5. Set value: 5, Upper- and lower-limit with standby sequence

L       H  SP  SP L    H     H                  SP    L                Always OFF when the upper-limit and lower-limit hysteresis

H<0, L>0       H>0, L<0                                     H<0, L>0   overlaps.

|H| < |L|      |H| > |L|  H                     L SP        |H| ≥ |L|  *6. Refer to the E5@C Digital Temperature Controllers User's Manual

                                                            H>0, L<0   (Cat. No. H174) for information on the operation of the standby

                                                SP H     L  |H| ≤ |L|  sequence.

*3. Set value: 4, Upper- and lower-limit range                         *7. Refer to the E5@C Digital Temperature Controllers User's Manual

Case 1         Case 2     Case 3 (Always OFF)                          (Cat. No. H174) for information on the loop burnout alarm (LBA).

                                                            H<0, L<0   This setting cannot be used with a position-proportional model.

L       H  SP  SP L    H     H                  SP    L                *8. Refer to the E5@C Digital Temperature Controllers User's Manual

H<0, L>0       H>0, L<0                                     H<0, L>0   (Cat. No. H174) for information on the PV change rate alarm.

|H| < |L|      |H| > |L|  H                     L SP        |H| ≥ |L|  *9. When heating/cooling control is performed, the MV absolute

                                                            H>0, L<0   upper limit alarm functions only for the heating operation and the

                                                SP H     L  |H| ≤ |L|  MV absolute lower limit alarm functions only for the cooling

                                                                       operation.

                                                                       *10.This value is displayed only when a remote SP input is used. It
                                                                       functions in both Local SP Mode and Remote SP Mode.

                                                                                                                                                47
E5EC/E5EC-B/E5AC

Characteristics

                                       Thermocouple:    (±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1

    Indication accuracy                Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.

    (at the ambient temperature of     Analog input:    ±0.2% FS ±1 digit max.

    23°C)                              CT input:        ±5% FS ±1 digit max.

                                       Potentiometer input: ±5% FS ±1 digit max.

    Transfer output accuracy           ±0.3% FS max.

    Remote SP Input Type               ±0.2% FS ±1 digit max.

    Influence of temperature *2        Thermocouple input (R, S, B, C/W, PL II): (±1% of indication value or ±10°C, whichever is greater) ±1 digit max.

                                       Other thermocouple input: (±1% of indication value or ±4°C, whichever is greater) ±1 digit max. *3
                                       Platinum resistance thermometer: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
    Influence of voltage *2
                                       Analog input: ±1%FS ±1 digit max.
    Influence of EMS.
                                       CT input: ±5% FS ±1 digit max.
    (at EN 61326-1)
                                       Remote SP      input: ±1% FS ±1 digit max.

    Input sampling period              50ms

    Hysteresis                         Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or°F)

                                       Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)

    Proportional band (P)              Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)

                                       Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)

    Integral time (I)                  Standard, heating/cooling, or Position-proportional (Close): 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s)

                                       Position-proportional (Floating): 1 to 9999 s (in units of 1 s), 0.1 to 999.9 s (in units of 0.1 s)*4

    Derivative time (D)                0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4

    Proportional band (P) for cooling  Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)

                                       Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)

    Integral time (I) for cooling      0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4

    Derivative time (D) for cooling    0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4

    Control period                     0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)

    Manual reset value                 0.0 to 100.0% (in units of 0.1%)

    Alarm setting range                -1999 to 9999 (decimal point position depends on input type)

    Influence of signal source         Thermocouple: 0.1°C/Ω max. (100 Ω max.)

    resistance                         Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)

    Insulation resistance              20 MΩ min. (at 500 VDC)

    Dielectric strength                3,000 VAC, 50/60 Hz for 1 min between terminals of different charge

    Vibration   Malfunction            10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions

                Resistance             10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions

    Shock       Malfunction            100 m/s2, 3 times each in X, Y, and Z directions

                Resistance             300 m/s2, 3 times each in X, Y, and Z directions

    Weight                             E5EC/E5EC-B: Controller: Approx. 210 g, Adapter: Approx. 4 g × 2

                                       E5AC:            Controller: Approx. 250 g, Adapter: Approx. 4 g × 2

    Degree of protection               Front panel: IP66, Rear case: IP20, Terminals: IP00

    Memory protection                  Non-volatile memory (number of writes: 1,000,000 times)

    Setup Tool                         E5EC/E5AC:     CX-Thermo version 4.5 or higher

                                       E5EC-B:        CX-Thermo version 4.65 or higher *9

                                       E5EC/E5EC-B/E5AC top panel:         An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a

    Setup Tool port                                                        USB port on the computer.*5
                                       E5EC/E5EC-B/E5AC front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion

                                                                           Cable are used together to connect to a USB port on the computer.*5

                Approved standards     cULus: UL 61010-1/CSA C22.2 No.61010-1, Korean wireless regulations (Radio law: KC Mark) (Some

    Standards                          models only.) *6, Lloyd's standards *7

                Conformed standards    EN 61010-1 (IEC 61010-1)

                                       EMI                                                      EN 61326-1 *8

                                       Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A

                                       Noise Terminal Voltage:                                  EN 55011 Group 1, class A

                                       EMS:                                                     EN 61326-1 *8

    EMC                                ESD Immunity:                                            EN 61000-4-2

                                       Electromagnetic Field Immunity:                          EN 61000-4-3

                                       Burst Noise Immunity:                                    EN 61000-4-4

                                       Conducted Disturbance Immunity:                          EN 61000-4-6

                                       Surge Immunity:                                          EN 61000-4-5

                                       Voltage Dip/Interrupting Immunity:                       EN 61000-4-11

*1. The indication accuracy of K thermocouples in the -200 to 1,300°C range, T and N thermocouples at a temperature of -100°C max., and U and L
    thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max.

    is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and

    S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of C/W thermocouples is (±0.3% of PV or ±3°C,

    whichever is greater) ±1 digit max. The indication accuracy of PL II thermocouples is (±0.3% of PV or ±2°C, whichever is greater) ±1 digit max.

*2. Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*3. K thermocouple at -100°C max.: ±10°C max.
*4. The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5. External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
*6. Refer to your OMRON website for the most recent information on applicable models.
*7. Refer to information on maritime standards in Shipping Standards on page 120 for compliance with Lloyd's Standards.
*8. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
*9. CX-Thermo version 4.67 or higher is required for the E5CC-B linear current output type.

48
                                                                                                                                  E5EC/E5EC-B/E5AC

USB-Serial Conversion Cable                                                                                          When Digital Temperature Controllers are

Applicable OS           Windows XP/Vista/7/8/10 *1                                                                   connected, set points and RUN/STOP

                        E5EC/E5AC:CX-Thermo version 4.5 or higher                                                    commands can be sent from the Digital

Applicable software     E5EC-B:CX-Thermo version 4.65 or higher *3            Component                              Temperature Controller that is set as the

Applicable models       E5@C-T Series, E5@C Series, and E5CB Series           Communications *1                      master to the Digital Temperature

                                                                                                                     Controllers that are set as slaves.

USB interface standard  Conforms to USB Specification 2.0.                                                           Slope and offsets can be set for the set point.

DTE speed               38,400 bps                                                                                   Number of connected Digital Temperature

Connector               Computer: USB (type A plug)                                                                  Controllers: 32 max. (including master)

specifications          Digital Temperature Controller:                                                              When Digital Temperature Controllers are

                        Special serial connector                                                                     connected, the parameters can be copied

Power supply            Bus power (Supplied from USB host controller.) *2     Copying *2                             from the Digital Temperature Controller that is

Power supply voltage    5 VDC                                                                                        set as the master to the Digital Temperature

Current consumption     450 mA max.                                                                                  Controllers that are set as slaves.

                        4.7±0.2 VDC                                           MELSEC is a registered trademark of Mitsubishi Electric Corporation.

Output voltage          (Supplied from USB-Serial Conversion Cable            KEYENCE is a registered trademark of Keyence Corporation.

                        to the Digital Temperature Controller.)               *1. A Temperature Controller with version 1.1 or higher is required.
                                                                                                       A Temperature Controller with version 2.1 or higher is required for
                        250 mA max.
                                                                                                       the FX Series or the KV Series.
Output current          (Supplied from USB-Serial Conversion Cable
                                                                              *2. Both the programless communications and the component
                        to the Digital Temperature Controller.)                                        communications support the copying.

Ambient operating       0 to 55°C (with no condensation or icing)             Current Transformer (Order Separately) Ratings

temperature

Ambient operating       10% to 80%                                                                                                E54-CT1                      E54-CT1L

humidity                                                                                                                          E54-CT3                      E54-CT3L

Storage temperature     -20 to 60°C (with no condensation or icing)           Dielectric strength                    1,000 VAC for 1 min                 1,500 VAC for 1 min

Storage humidity        10% to 80%                                            Vibration resistance                                         50 Hz, 98 m/s2

Altitude                2,000 m max.                                          Weight                                 E54-CT1: Approx. 11.5 g             E54-CT1L: Approx. 14 g

Weight                  Approx. 120 g                                                                                E54-CT3: Approx. 50 g               E54-CT3L: Approx. 57 g

Windows is a registered trademark of Microsoft Corporation in the                                                    E54-CT3 Only

United States and or other countries.                                         Accessories                            Armatures (2)                       None

*1. CX-Thermo version 4.65 or higher runs on Windows 10.                                                             Plugs (2)

*2. Use a high-power port for the USB port.                                   Heater Burnout Alarms and SSR Failure Alarms
*3. CX-Thermo version 4.67 or higher is required for the E5CC-B
linear current output type.
                                                                                                                     Models with detection for singlephase
Note: A driver must be installed on the computer. Refer to the Instruction
                                                                              CT input (for heater                   heaters: One input
Manual included with the Cable for the installation procedure.
                                                                              current detection)                     Models with detection for singlephase or

Communications Specifications                                                                                        three-phase heaters: Two inputs

Transmission line                                                             Maximum heater                         50 A AC

connection method       RS-485: Multidrop                                     current

Communications          RS-485 (two-wire, half duplex)                        Input current                          ±5% FS ±1 digit max.

                                                                              indication accuracy

Synchronization method  Start-stop synchronization                            Heater burnout alarm                   0.1 to 49.9 A (in units of 0.1 A)

Protocol                CompoWay/F, or Modbus                                 setting range *1                       Minimum detection ON time: 100 ms *3

Baud rate *             9600, 19200, 38400, or 57600 bps                      SSR failure alarm                      0.1 to 49.9 A (in units of 0.1 A)

Transmission code       ASCII                                                 setting range *2                       Minimum detection OFF time: 100 ms *4

Data bit length *       7 or 8 bits                                           *1. For heater burnout alarms, the heater current will be measured
                                                                                                       when the control output is ON, and the output will turn ON if the
Stop bit length *       1 or 2 bits
                                                                                                       heater current is lower than the set value (i.e., heater burnout
                        Vertical parity (none, even, odd)
                                                                                                       detection current value).
Error detection         Block check character (BCC) with
                                                                              *2. For SSR failure alarms, the heater current will be measured when the
                        CompoWay/F or CRC-16 Modbus                                                    control output is OFF, and the output will turn ON if the heater current

Flow control            None                                                                           is higher than the set value (i.e., SSR failure detection current value).

Interface               RS-485                                                *3. The value is 30 ms for a control period of 0.1 s or 0.2 s.

Retry function          None                                                  *4. The value is 35 ms for a control period of 0.1 s or 0.2 s.

Communications buffer   217 bytes                                             Electrical Life Expectancy Curve for

Communications          0 to 99 ms                                            Control Output Relays (Reference Values)

response wait time      Default: 20 ms

* The baud rate, data bit length, stop bit length, and vertical parity can    Life (× 104 operations)  500

be individually set using the Communications Setting Level.                                            300

Communications Functions                                                                                             E5EC/E5EC-B/E5AC

                        You can use the memory in the PLC to read and write                            100           250 VAC, 30 VDC

                        E5@C parameters, start and stop operation, etc. The                                          (resistive load)

                        E5@C automatically performs communications with                                50            cosφ = 1

                        PLCs. No communications programming is required.                               30

                        Number of connected Digital Temperature Controllers:

                        32 max. (Up to 16 for the FX Series)

Programless             Applicable PLCs                                                                10

communications *1       OMRON PLCs

                               CS Series, CJ Series, CP Series,                                        5

                               NJ Series, or NX1P                                                      3

                        Mitsubishi Electric PLCs

                               MELSEC Q Series, L Series, FX3 Series,

                               or iQ-R Series                                                          1

                        KEYENCE PLCs                                                                        0  1  2  3            4        5  6

                               KEYENCE KV Series                                                                                  Switching current (A)

                                                                                                                                                                                  49
E5EC/E5EC-B/E5AC

External Connections

E5EC/E5AC (Screw Terminal Blocks)

                           E5EC- @ @                    4     @     5     M - @@@                 E5AC- @ @             4         @     5    M - @@@

                                              (1)      (2) (3) (4) (5)          (6)                             (1)     (2) (3) (4) (5)                     (6)                The E5EC is set for a K-type thermocouple (input

                                                                    ↑                                                                   ↑                                      type = 5) by default. An input error (s.err) will occur

                                                           Terminal type                                                   Terminal type                                       if the input type setting does not agree with the

                                                                                                                                                                               temperature sensor. Check the input type.

       Control output 1                       Control output 2                  Auxiliary outputs 1, 2, 3, 4            (6) Options

    Relay output                         Relay output                        Relay output                                         004                            005                   009                                010

       250 VAC, 5 A                           250 VAC, 5 A                      Models with 4 auxiliary                           Communications                 4 event  inputs       Communications, 2 event            4 event inputs

       (resistive load)                       (resistive load)                  outputs: 250 VAC, 2 A                             and 2 event inputs                                   inputs, and 2 CT inputs            and 1 CT input

    Voltage output                       Voltage output                         (resistive load)                                     B(+)       13                        13                 B(+)     13

       (for driving SSR)                      (for driving SSR)                                                                   RS-485                    (-)                         RS-485                       (-)            13

       12 VDC, 40 mA                          12 VDC, 21 mA                                                                            A(-)     14                  EV3   14                 A(-)     14                  EV3       14

       When There Is a                   Linear current output                                                                                  15           EV4          15                          15                 EV4        15

       Control Output 2:                      0 to 20 mA DC                                                                    (-)              16          (-)           16            (-)           16             (-)            16

       21 mA                                  4 to 20 mA DC                                                                                     17                        17                          17                            17

    Linear current output                     Load: 500 Ω max.                                                                         EV1      18                  EV1   18                 EV1      18                  EV1       18

       0 to 20 mA DC                                                                                                              EV2                        EV2                        EV2                              EV2

       4 to 20 mA DC                                                                                                                            19                        19                          19                 CT1        19

       Load: 500 Ω max.                                                                                                                         20                        20            CT1           20                            20

                                                                                                                                                                                             COM

                                                                                                                                                21                        21            CT2           21                            21

(1) Control output

        RX                        QX                          CX                                                                                    011

    Models with            Models with 1                Models with 1                                                                               6 event Inputs, 1 CT input,

    1 Relay Output         Voltage Output               Linear Current Output                                                                       transfer output, and remote SP input

                           (for Driving SSR)

        3           OUT1       3         +    OUT1            3        +  OUT1       (3) Input Power        Supply                                                                (-)        13

        4           R          4         -    Q                        -  C                                                                                                                  14

                                                              4                      100 to 240 VAC           24 VAC/DC                                                                EV3

        5                      5                              5                                                                                                                   EV4        15

                                                                                                     1                  1                                   (-)           28      (-)        16

        6                      6                              6                                                         2                                                 29                 17

                                                                                                     2                                                              EV5                EV1

       QQ                                     QR                                                                (no polarity)                                EV6          30      EV2        18

    Models with 2 Voltage         Models with Voltage Output (for                                                                                            +            31                 19

    Outputs (for Driving SSR)     Driving SSR) and Relay Output                                                                                     Transfer V        +   32       CT1       20

                    OUT1                            OUT1                                                                                            output            I

        3        +  Q                 3          +  Q                                1               25     13                                                   -        33                 21

        4        -                    4          -                                   2               26     14                                               +        +   34

        5                             5                                              3               27     15                                      Remote V        mA    35

                 +  Q                               R                                                                                               SP input              36
                                                                                                                                                                 -
        6        -                    6                                              4               28     16
                    OUT2                            OUT2

    RR                 PR                     CC                                     5               29     17                                      013                                          014

    Models with 2      Models with 2          Models with 2                          6               30     18                                      6 event Inputs, transfer                     Communications, 4 event Inputs,

    Relay Outputs      Position-proportional  Linear Current                         7               31     19                                      output, and remote SP input                  transfer output, and remote SP input

                       Relay Output   Open    Outputs                                8               32     20                                                                                                                 B(+)

    3            OUT1  3                         3               OUT1                                                                                                     (-)           13                                    RS-485      13

                 R                    R                    +     C                   9               33     21                                                                          14                                                14
                                                           -
    4                  4                         4                                   10              34     22                                                                    EV3                                          A(-)
                                                                                                                                                                                        15                                                15
                                                                                                                                                                              EV4
    5                  5                         5         +                         11              35     23                                                        28  (-)                         (-)            28                   16
                                                                 C                                                                                  (-)                                 16                                (-)
                 R                    R                    -
    6                  6                         6                                   12              36     24                                                                                                       29
                 OUT2                 Close                      OUT2                                                                                                 29                17                    EV5                         17
                                                                                                                                                            EV5                   EV1                                          EV1
    CQ                                                                                                                                                                                                               30                   18
                                                                                                                                                        EV6           30      EV2       18            EV6                      EV2

    Models with 2 Outputs: Linear Current Output                                                                                                         +            31                19                 +         31                   19

    and Voltage (for Driving SSR)                                                                                                            Transfer V          +                           Transfer         V  +   32                   20

                                                                                                                                             output              I    32                20   output              I

        3        +  OUT1             (2) Auxiliary Outputs                                        Potentiometer Input                                    -            33                21                 -         33                   21

                 -  C                                                                                                                                    +            34                                   +         34

        4                                     Auxiliary outputs 1, 2, 3, 4                               O      19                           Remote V            +                           Remote           V  +

        5                                           7                                                           20                                           mA       35                     SP input-           mA  35

                 +  Q                                   Auxiliary output 4                               W                                   SP inpu-t                36                                             36

        6        -  OUT2                            8                                                    C      21

                                                    9   Auxiliary output 3

                                                    10  Auxiliary output 2                                                                                          Use no-voltage inputs for the event inputs.

                                                    11                               (5) Sensor (Temperature/Analog) Input                                          The polarity for non-contact inputs is given in parentheses.

                                                    12  Auxiliary output 1                           TC             Pt              I               V

                                                                                                     22       A     22         +    22              22

                                                                                                  -  23         B   23  mA          23          -   23

                                                                                                     24         B 24           -    24       V      24

                                                                                           +                                                    +

                                                                                                                Note: 1.          The application of the terminals depends on the model.

                                                                                                                        2.        Do not wire the terminals that are shown with a gray background.

                                                                                                                        3.        When complying with EMC standards, the cable that connects the

                                                                                                                                  sensor must be 30 m or less. If the cable length exceeds 30 m,

                                                                                                                                  compliance with EMC standards will not be possible.

                                                                                                                        4.        Connect M3 crimped terminals.

                                                                                                                        5.        Due to UL Listing requirements, use the E54-CT1L or E54-CT3L

                                                                                                                                  Current Transformer with the factory wiring (internal wiring).

                                                                                                                                  Use a UL category XOBA or XOBA7 current transformer that is UL

                                                                                                                                  Listed for field wiring (external wiring) and not the factory wiring

                                                                                                                                  (internal wiring).

50
                                                                                                                                                                         E5EC/E5EC-B/E5AC

E5EC-B (Push-In Plus Terminal Blocks)

                                                   E5EC- @ @                @        @  B  M - @@@                            (6) Options

                                                                    (1)     (2) (3) (4) (5)      (6)                          004                                         008

                                                                                                                              Communications, 2 event inputs              Communications, 2 event inputs, and 1     CT  input

                                                                                        ↑                                          B(+)                                          B(+)

                                                                                  Terminal type                                                      17                                     17

                                                                                                                                                         *                                            *

Control output 1                       Auxiliary outputs 1, 2, 3, 4                                                           RS-485                 18                   RS-485            18

                                                                                        The E5EC is set for a K-type                                 19                                     19

Relay output                           Relay output                                     thermocouple (input type = 5) by           A(-)                  *                       A(-)                 *

250 VAC, 5 A                           Model with 2 auxiliary                           default. An input error (s.err) will                         20                                     20

(resistive load)                       outputs: 250 VAC, 3 A                            occur if the input type setting does

Voltage output                         (resistive load)                                 not agree with the temperature                     (-)       21                             (-)     21

(for driving SSR)                      Models with 4 auxiliary                          sensor. Check the input type.                                    *                                            *

12 VDC, 40 mA                          outputs: 250 VAC, 2 A                                                                               (-)       22                             (-)     22

                                       (resistive load)

                                                                                                                                        EV1          23                           EV1       23

(1) Control output                                            (3) Input Power Supply

RX                              QX                                      100 to 240 VAC           24 VAC/DC                              EV2          24                          EV2        24

Models with                     Models with 1                                                                                                        25                                     25

1 Relay Output                  Voltage Output                                    1                   1                                                                        CT1

                                (for Driving SSR)                                       *                               *                            26                                     26

                       OUT1                    OUT1                               2                   2

5                      R            5      +Q                                                                                 010                                 011

6                                   6      -                                      3                   3                       4 event inputs and 1 CT input       6 event Inputs, 1 CT input, transfer

                                                                                        *                               *                                         output, and remote SP input

                                                                                  4                   4                                    (-)                              (-)                            (-)

CX                                                                                                   (no polarity)                                   17                          37                             17

Models with 1 linear                                                                                                                       (-)           *                  (-)                *           (-)          *

current Output                                                                                                                                       18                          38                             18

5                   +  OUT1                                                                                                                          19                          39                             19

                       C                                                                   1     33   17                                EV3                               EV5                            EV3

6                   −                                                                      2     34   18                                             20                          40                             20

                                                                                           3     35   19                                EV4                               EV6                            EV4

                                                                                                                                           (-)       21                          41                        (-)  21

(2) Auxiliary Outputs                                                                      4     36   20                                   (-)           *                                         +       (-)          *

    Auxiliary outputs           1,  2  Auxiliary outputs            1,  2,  3, 4           5     37   21                                             22                          42                             22

                                                                                           6     38   22                                             23                          43         +      V            23

                          9                                      9                         7     39   23                                EV1                                                    I         EV1

                                       Auxiliary output 4                                  8     40   24                                EV2          24                          44                -     EV2    24

                       10                                     10                           9     41   25                                             25                          45         Transfer            25

                                                                            *                                                      CT1                                                      output

                       11                                     11                           10    42   26                                                          +              46                   CT1

Auxiliary output 2                     Auxiliary output 3                                  11    43   27                                             26                  V                                      26

                       12                                     12                           12    44   28                                                       Remote       +    47

                                                                                           13    45   29                                                       SP input     mA

                       13                                     13                                                              014                                      -         48

                                       Auxiliary output 2                                  14    46   30

                       14                                     14                           15    47   31                      Communications, 4 event inputs, transfer output, and remote             SP input

                                                                            *              16    48   32                                        (-)  37                             B(+)       17

                       15                                     15                                                                                (-)      *                                            *

Auxiliary output 1                     Auxiliary output 1                                                                                            38                     RS-485             18

                       16                                     16

                                                                                                                                           EV5       39                             A(-)       19

                                                                                                                                                                                                      *

                                                                                                                                           EV6       40                                        20

(5) Sensor (Temperature/Analog) Input                                                                                                                41                                (-)     21

          TC                    Pt              I                   V                                                                                                                  (-)            *

                          A                                                                                                                          42  +     +                               22

          30                    30     +       30                   30                                                                               43           Transfer                     23

    -                        B         mA                     -                                                                                                V  output            EV1

          31                 B  31     -       31                   31                                                                               44     I                       EV2        24

          32                    32             32          V        32                                                                                         −                               25

    +                                                         +                                                                                      45

                                                                                                                                        +            46                                        26

                                                                                                                                        V       +    47

                                                                                                                              Remote

                                                                                                                              SP input       mA      48

                                                                                                                                        -

                                                                                                                                        Use no-voltage inputs for the event inputs.

                                                                                                                                        The polarity for non-contact inputs is given in parentheses.

Note: 1.  The application of the terminals depends on the model.

    2.    Do not wire the terminals that are shown with a gray background.

    3.    When complying with EMC standards, the cable that connects the sensor must be 30 m or less. If the cable length exceeds 30 m,

          compliance with EMC standards will not be possible.

    4.    Refer to Wiring Precautions for E5@C-B (Controllers with Push-In Plus Terminal Blocks) on page 126 for wire specifications and wiring methods.

    5.    Common terminals are indicated with asterisks (*). You can use the input power supply and communications common terminals for crossover wiring.

          Do not exceed the maximum number of Temperature Controllers given below if you use crossover wiring for the input power supply.

          100 to 240 VAC Controllers: 16 max.

          24 VAC/VDC Controllers: 8 max.

          Wiring Example:                                     1

                                                              2

                                                              3

                                                              4

    6.                                 To another E5@C
          Due to UL Listing requirements, use the E54-CT1L or E54-CT3L Current Transformer with the factory wiring (internal wiring).

          Use a UL category XOBA or XOBA7 current transformer that is UL Listed for field wiring (external wiring) and not the factory wiring (internal wiring).

                                                                                                                                                                                                                               51
E5EC/E5EC-B/E5AC

Isolation/Insulation Block Diagrams

Models with 2 Auxiliary Outputs                                                                           Models with 4 Auxiliary Outputs

                          Sensor input, CT inputs, and remote SP input                                            Sensor input, CT inputs, potentiometer input, and remote SP input

                                 Communications and event inputs                                                  Communications and event inputs

             Voltage output (for driving SSR) and transfer output                                                 Voltage output (for driving SSR),

    Power                                                                                                 Power   linear current output, and transfer output

    Supply                                                                                                Supply

                                     Relay output                                                                                          Relay output

                                     Auxiliary output 1                                                                                    Auxiliary outputs 1, 2

                                     Auxiliary output 2                                                                                    Auxiliary outputs 3, 4

            : Reinforced insulation                                                                               : Reinforced insulation

            : Functional isolation                                                                                : Functional isolation

                                                                                                          Note: Auxiliary outputs 1 to 2 and 3 to 4 are not insulated.

Nomenclature

E5EC/E5EC-B

                                        Front panel

                                                                                No. 1 display

                                                                        PV or specified parameter                 Top View of E5EC                Top View of E5EC-B

      Temperature unit

    Operation indicators                                                        No. 2 display

                                                                        SP or specified parameter value

                                                                                No. 3 display

    Front-panel Setup Tool port                                         Manipulated value or other value

                                                                                Use the U D Keys to set

                                                                                the parameter.

                                                                                Use S Key to change the

                                                                                digit (default setting).

                                                                                Use the M Key to change to                                 Top-panel

    Press O Key once to go to Adjustment Level.                                 another parameter.                                         Setup

                                                                                                                                           Tool port

    Press O Key for at least 3 seconds

    to go to Initial Setting Level.

E5AC

                                        Front Panel

                                                                                                                                                         Top       View  of  E5AC

    Temperature unit                                                            No. 1 display

    Operation indicators                                                        PV or specified parameter

                                                                                No. 2 display

                                                                                SP or specified parameter value

    Front-panel Setup Tool port                                                 No. 3 display

                                                                                Manipulated value or other value

                                                                                Press the U or D Key to set       the parameter.                                                     Top-panel

                                                                                                                                                                                     Setup

                                                                                                                                                                                     Tool port

                                                                                Press the S Key to change the digit (default setting).

    Press the O Key once to go to the Adjustment Level.                         Press the M Key to change to another parameter.

    Press the O Key for at least 3 seconds to go to the Initial Setting Level.

52
                                                                                                                                                 E5EC/E5EC-B/E5AC

Dimensions                                                                                                                                                           (Unit: mm)

Controllers

E5EC

                                                                                    4       (64)

                                                      48                            1       60                       44

                                             96                                                          110                            91

                                                      Waterproof

                                                      Packing (Accessory)              Mounting Adapter

                                                                                       (Accessory)

E5EC-B                                                                              4       (71.4)

                                                                                            67.4

                                                      48                               (1)                                     44

                                             96                                                                 110                         91

                                                      Waterproof Packing               Mounting Adapter

                                                      (Accessory)                      (Accessory)

•  Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller. The E58-

   CIFQ2 USB-Serial Conversion Cable is required to connect to the port on the top panel. The E58-CIFQ2 USB-Serial Conversion Cable and

   E58-CIFQ2-E Communications Conversion Cable are required to connect to the port on the front panel. (You cannot leave either port

   connected constantly during operation.)

        Mounted Separately                       Group Mounted *                                         E5EC:

                                                 (48 × number of units − 2.5)+10.0                  *

                  45+0.06                                                                                Selections for Control Outputs 1 and 2: QQ, QR, RR, CC, PR, or CQ

                                                                                                         If you also specify 011, 013, or 014 for the option selection and use

                                                                                                         group mounting, the ambient temperature must be 45°C or less.

                                                                                                         Maintain the following spacing when more than one Digital

                                                                       92+00.8                           Controller is installed at an ambient temperature of 55°C.

                                                                                                                                        60 min.

                                                                                                                               45-00.6

        120 min.                                 Group mounting does not

                                                 allow waterproofing.

                                                                                                                                                 92+00.8

                                    92-00.8

                                                                                                                     120 min.

   •  Recommended panel thickness is 1 to 8 mm.

   •  Group mounting is not possible in the vertical direction. (Maintain the

      specified mounting space between Controllers.)

   •  To mount the Controller so that it is waterproof, insert the waterproof

      packing onto the Controller.

   •  When two or more Controllers are mounted, make sure that the sur-

      rounding temperature does not exceed the allowable operating tem-

      perature specified in the specifications.

                                                                                                                                                                                 53
E5EC/E5EC-B/E5AC

E5AC                                                                                                     (64)

                                                                                                   4     60

                                                                    96 x 96                           1                                          91 x 91

                                                                                                                     110                         91

                                                                              Waterproof

                                                                              Packing (Accessory)  Mounting Adapter

                                                                                                   (Accessory)

                                           •  Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the

                                              Digital Temperature Controller. The E58-CIFQ2 USB-Serial Conversion Cable is required to

                                              connect to the port on the top panel. The E58-CIFQ2 USB-Serial Conversion Cable and E58-

                                              CIFQ2-E Communications Conversion Cable are required to connect to the port on the front panel.

                                              (You cannot leave either port connected constantly during operation.)

              Mounted Separately           Group Mounted                                              • Recommended panel thickness is 1 to 8 mm.

                                           (96 × number of units − 3.5)+10.0                          • Group mounting is not possible in the vertical direction. (Maintain the

              92+00.8                                                                                 specified mounting space between Controllers.)

                                                                                                      • To mount the Controller so that it is waterproof, insert the waterproof

                                                                                                      packing onto the Controller.

                                                                                                      • When two or more Controllers are mounted, make sure that the sur-

                                                                              92+00.8                 rounding temperature does not exceed the allowable operating tem-

                                                                                                      perature specified in the specifications.

    120 min.                               Group mounting does not

                                           allow waterproofing.

                                  92+00.8

54
                                                                                                         E5EC/E5EC-B/E5AC

Accessories (Order Separately)

USB-Serial Conversion Cable

E58-CIFQ2                                                                      (2110)

                                                  250                                               263                      1510

                                                                    LED (RD)

                                   USB connector

                                   (type A plug)                                                                                     Serial  connector

                                                                               LED (PWR)

                                                                               LED (SD)

Conversion Cable

E58-CIFQ2-E

           Conversion Cable                   Connecting to    the  E58-CIFQ2  USB-Serial Conversion Cable

                                                                                            (2110)

                      (1510)                              250                                            263                       1510

                                                                    E58-CIFQ2  (Order Separately)                     Conversion Cable

Note: Always use this product together with  the E58-CIFQ2.

Terminal Covers                                   Waterproof Packing

E53-COV24 (Three Covers provided.)                Y92S-P9 (for DIN 48 × 96)

                      2       3.8                                              The Waterproof Packing is provided with the Temperature

                                                                               Controller.

                                                                               Order the Waterproof Packing separately if it becomes lost or

                  10                                                           damaged.

                                                                               The degree of protection when the Waterproof Packing is used

                                                                               is IP66.

                                                                               Also, keep the Port Cover on the front-panel Setup Tool port

                                                                               of the E5EC/E5EC-B/E5AC securely closed.

                                                                               To maintain an IP66 degree of protection, the Waterproof

             91                                                                Packing and the Port Cover for the front-panel Setup Tool port

                                                                               must be periodically replaced because they may deteriorate,

                                                                               shrink, or harden depending on the operating environment.

                                                  Y92S-P10 (for DIN 96 × 96)   The replacement period will vary with the operating

                                                                               environment.

                                                                               Check the required period in the actual application.

                                                                               Use 3 years or sooner as a guideline.

Setup Tool  Port  Cover       for  top panel                        Mounting Adapter

Y92S-P7                                                             Y92F-51 (Two Adapters           provided.)

                                   Order this Port Cover                                                        One pair is provided with the

                                   separately if the Port Cover on                                              Controller.

                                   the front-panel Setup Tool port                                              Order this Adapter

                                   is lost or damaged. The                                                      separately if it becomes lost

                                   Waterproof Packing must be                                                   or damaged.

                                   periodically replaced because

                                   it may deteriorate, shrink, or

                                   harden depending on the

                                   operating environment.

                                                                                                                                                        55
E5EC/E5EC-B/E5AC

Watertight Cover                                                                         Watertight Cover

Y92A-49N (48 × 96)                                                                       Y92A-96N (96 × 96)

                                                          21.9  (2)                                                                                                            21.9      (2)

          131.7                                                                          131.7

                    67.6                                  28.9                                                                               115.6                             28.9

Current   Transformers

E54-CT1                                                                                                 Thru-current (Io) vs. Output                                                   Voltage (Eo)

                                                      21                       2.8                      (Reference Values)

                                    Filler            15        5.8 dia.                                E54-CT1 or E54-CT1L

                                    (epoxy)

                                                                Case                7.5                 Maximum continuous heater current:                                             50 A (50/60 Hz)

                                                                                                        Number of windings:                                                            400±2

                          25        2.5                                                                 Winding resistance:                                                            18±2 Ω

                                                                10.5                                         Output voltage (Eo) V (r.m.s.)  100V

                                                                                                                                                       Frequency: 50 Hz

                                                      40                       10                                                            10                          ∞                    Distortion

                                    5                                                                                                                      1kΩ                                factor

                                                                Two, 3.5  dia.                                                                                                                10%

                                                                                                                                             1

                                                                                                                                                                                             3%

                                                                                                                                                                                         1%

                                                      30                                                                                     100mV

                                                                                                                                             10                                100Ω

E54-CT1L                                                                                                                                     1                                 RL=10Ω

                                                      21

                                 8                    15                                                                                     100μV

                                                                                                                                             10

                                                                                                                                                    1  10  100mA            1        10       100  1,000A

                                                                                                                                                                               Thru-current (Io) A (r.m.s.)

                          115±5                                 Cable (AWG18)

                                    (12)                        Shrinkable tube

                                                                Case (PBT)               Mark (yellow)

                                            5.8 dia.            Filler (epoxy)

                          25        2.5

                                                                10.5

                                                      40                            10

                                    5                           Two, 3.5 dia.

                                                      30

56
                                                                                                                                                E5EC/E5EC-B/E5AC

E54-CT3                                                                            2.36  dia.         Thru-current (Io) vs. Output Voltage (Eo)

                                                    30                                                (Reference Values)

                          Filler                             12 dia.

                          (epoxy)                                                                     E54-CT3 or E54-CT3L

                                                                                                   9

                                                             Case                                     Maximum continuous heater current: 120 A (50/60 Hz)

                                                             (PBT)

                                                                                                      (Maximum continuous heater current for an OMRON

                                 40 × 40                                                              Digital Temperature Controller is 50 A.)

                                                                                                      Number of windings:                                               400±2

                                                                                                      Winding resistance:                                               8±0.8 Ω

                                                                                                      Output voltage (Eo) V (r.m.s.)  100V      Frequency: 50 Hz

                                                    40                             15                                                                                                Distortion

                                                                                                                                      10                          ∞                  factor

                                                                                                                                                    1kΩ                              10%

                                                                                                                                                    500Ω                             3%

                                    8                                                                                                 1                                          1%

                                                        Two, M3       (depth:  4)                                                     100mV

E54-CT3 Accessories                                 30                                                                                                                  100Ω

•  Armature               Connection                Example                                                                           10                                50Ω

                                                                                                                                                                        RL=10Ω

                                                        Armature                                                                      1

Approx. 3 dia.                            Plug

                                                             Lead                                                                     100μV

                                                                                                                                      10

                                                                                                                                             1  10  100mA            1  10      100  1,000A

                      18

                                                                                                                                                                        Thru-current (Io) A (r.m.s.)

• Plug

Approx. 6 dia.

                (22)

E54-CT3L                         8              30

                          100±5

                                                             Cable (AWG18)

                                                                  Case (PBT)

                              12.0                                Filler (epoxy)

                              dia.

                          40

                                                40                                             15

                                                        Two, M3

                                                        (depth: 4)

                          8

                                                30

                                                                                                                                                                                                      57
    Digital Temperature Controller
    E5DC (22.5 mm Wide, and DIN Track-mounting Type)

The E5DC Mounts to DIN Track and Is Ideal

for Connections to HMIs and PLCs.

It provides the Same Easy Operation and

Advanced Performance as the Rest of the

E5@C Series.

    • A slim body at 85 × 22.5 mm (D × W) that fits into narrow control

    panels and mounts to DIN Track.

    • Removable terminal block for easy replacement to simplify maintenance.

    • High-speed sampling at 50 ms for applications with high-speed

    temperature increases.

    • Easy connections to a PLC with programless communications.                        22.5 mm Wide, and

    • Set up the Controller without wiring the power supply by connecting               DIN Track-mounting Type

    to the computer with a Communications Conversion Cable (sold separately).                      E5DC

    Setup is easy with the CX-Thermo (sold separately).                         Refer to your OMRON website for the most recent

    • Models are available with up to 2 auxiliary outputs and 1 event input to  information on applicable safety standards.

    complete basic functions.                                                       Refer to Safety Precautions on page 118.

    • A white PV display (height: 8.5 mm) is easy to read when setting up,

    checking alarms, and making settings in a control panel.

Main I/O Functions

    Sensor Input                                                       E5DC

    Universal input

    • Thermocouple

    • Pt                                                                        Dual displays: PV/SV           4-digit  displays

    • Analog current/voltage

          Indication Accuracy                                                   Control Output 1

          • Thermocouple input:                                                 • Relay output

          ±0.3% of PV                                                           • Voltage output (for driving  SSR)

          • Pt input: ±0.2% of PV                                               • Linear current output

          • Analog input:

          ±0.2% of FS

                                                                                Auxiliary Outputs

          Sampling Period                                                       • None

          • 50 ms                                                               •2

    Event Inputs

    • None                           • PF (shift) Key

    •1                               • Temperature status display

    Serial Communications            • Simple programming

    • None                           • Independent heating and

                                     cooling PID control

    • RS-485                         • Changed parameter display

                                     • Display brightness setting

    This datasheet is provided as a guideline for selecting products.

    Be sure to refer to the following manuals for application precautions and other information required for operation before attempting

    to use the product.

    E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174)

    E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)

58
                                                                                                                                                 E5DC

Model Number Legend and Standard Models

Model Number Legend

Models with Screw Terminal Blocks

E5DC-− @@−         − @ − @ − @ − M-@−@−@−(Example: E5DC-RX0ASM-015)
        A          BC     DE            F

                A           B           C            D              E         F

Model   Control        No. of           Power        Terminal     Input                                              Meaning

        output 1   auxiliary            supply       type         type        Options

                   outputs           voltage

E5DC                                                                                                 22.5 mm wide and mounts to DIN Track

                                                                                       Control output 1                               Control output 2

        RX                                                                                           Relay output                          None

        QX                                                                                        Voltage output                           None

                                                                                                  (for driving SSR)

        *1 CX                                                                          Linear current output *1                            None

                   0                                                                                                      None

                   2                                                                                                 2 (one common)

                                     A                                                                               100 to 240 VAC

                                     D                                                                               24 VAC/DC

                                                S                                      Screw terminal blocks (Main Unit and Terminal Unit together)

                                                U                                                      Main Unit only (no Terminal Unit)

                                                               M                                                     Universal input

                                                                                       HB alarm and HS alarm                Communications       Event input

                                                                        *2    000                      ---                            ---               ---

                                                                        *3    002                      1                          RS-485                ---

                                                                        *4    015                      ---                        RS-485                ---

                                                                        *5    016                      ---                            ---               1

                                                                        *3    017                      1                              ---               1

*1. The control output can be used as a simple transfer output for the Digital Temperature Controllers manufactured in July 2014 or later.
*2. Option 000 can be selected only if two auxiliary outputs are selected.
*3. Options 002 and 017 can be selected only if the control output is a relay output or voltage output and two auxiliary outputs are selected.
*4. Option 015 cannot be selected if the control output is a relay output or voltage output and two auxiliary outputs are selected.
*5. Options 016 can be selected only if the control output is a linear current output and two auxiliary outputs are selected.

List of Models

                   No. of auxiliary                                 Options                                          Model                  Model

Control output     outputs              HB alarm and HS        No.  of event  inputs   Communications       Power supply voltage           Power supply voltage

                                           alarm                                                            100 to 240 VAC                 24 VAC/DC

                       ---                                                             RS-485          E5DC-RX0ASM-015                E5DC-RX0DSM-015

                                                ---                                                    E5DC-RX0AUM-015                E5DC-RX0DUM-015

                                                                         ---           ---             E5DC-RX2ASM-000                E5DC-RX2DSM-000

Relay output                                                                                           E5DC-RX2AUM-000                E5DC-RX2DUM-000

                       2                                                               RS-485          E5DC-RX2ASM-002                E5DC-RX2DSM-002

                                     Detection for single-                                             E5DC-RX2AUM-002                E5DC-RX2DUM-002

                                     phase heater                        1             ---             E5DC-RX2ASM-017                E5DC-RX2DSM-017

                                                                                                       E5DC-RX2AUM-017                E5DC-RX2DUM-017

                       ---                                                             RS-485          E5DC-QX0ASM-015                E5DC-QX0DSM-015

                                                ---                                                    E5DC-QX0AUM-015                E5DC-QX0DUM-015

                                                                         ---           ---             E5DC-QX2ASM-000                E5DC-QX2DSM-000

Voltage output                                                                                         E5DC-QX2AUM-000                E5DC-QX2DUM-000

(for driving SSR)      2                                                               RS-485          E5DC-QX2ASM-002                E5DC-QX2DSM-002

                                     Detection for single-                                             E5DC-QX2AUM-002                E5DC-QX2DUM-002

                                     phase heater                        1             ---             E5DC-QX2ASM-017                E5DC-QX2DSM-017

                                                                                                       E5DC-QX2AUM-017                E5DC-QX2DUM-017

                       ---                                                             RS-485          E5DC-CX0ASM-015                E5DC-CX0DSM-015

                                                                                                       E5DC-CX0AUM-015                E5DC-CX0DUM-015

                                                                         ---           ---             E5DC-CX2ASM-000                E5DC-CX2DSM-000

Linear current                                  ---                                                    E5DC-CX2AUM-000                E5DC-CX2DUM-000

output                 2                                                               RS-485          E5DC-CX2ASM-015                E5DC-CX2DSM-015

                                                                                                       E5DC-CX2AUM-015                E5DC-CX2DUM-015

                                                                         1             ---             E5DC-CX2ASM-016                E5DC-CX2DSM-016

                                                                                                       E5DC-CX2AUM-016                E5DC-CX2DUM-016

Heating and Cooling Control

Using Heating and Cooling Control

A Control Output Assignment                                                            B Control