E5CK-TAA1 AC100-240器件文档内容

    Digital Controller

    E5CK

                                                                                                                               CSM_E5CK_DS_E_3_1

Advanced, Compact Digital Controllers

• IP66/NEMA4 (indoor use) front face.

• Modular structure, one-stock type.

• Heating/cooling control.

• Serial communications (RS-232C and RS-485).

• Temperature and analog inputs.

• High-accuracy: 100 ms sampling (for analog input).

• Advanced tuning which includes fuzzy self-tuning.

• Conforms to international EMC and safety standards.

         Refer to Safety Precautions for All Temperature Controllers.         Refer to E5@K Operation for operating

                                                                              procedures.

Model Number Structure

■ Model Number Legend

Refer to the following when ordering set models.

E5CK-@@@@

           1  2  3  4

1.  Constant Value/Program                                                    3.  Auxiliary Output

    Blank:Constant value                                                          1:   Auxiliary output (1 point)

    T:   Program                                                              4.  Option

2.  Control Output 1/Control Output 2                                             01:  RS-232C serial communication

    AA:  Without Output Unit (field interchangeable)                              03:  RS-485 serial communication

    RR:  Relay/Relay                                                              B:   Event input (1 point)

    QR:  Pulse (NPN)/Relay                                                        F:   Transfer output (4 to 20 mA)

    CR:  Linear (4 to 20 mA)/Relay

    VR:  Linear (0 to 10 V)/Relay

    QQ:  Pulse (NPN)/Pulse (NPN)

Note: E5CK-VR1 and E5CK-QQ1 are not available, but with options.

Ordering Information

■ List of Models

                  Description                                          Model                                         Specification

Base Unit                                         E5CK-AA1 AC100-240                                Base Unit

                                                  E5CK-AA1-500 AC100-240                            Base Unit with terminal cover

                                                  E5CK-TAA1 AC100-240                               Standard model

                                                  E5CK-TAA1-500 AC100-240                           Standard model with terminal cover

Note: A single Output Unit and Option  Unit  can  be mounted to each Base Unit.

                  Description                                          Model                                         Specification

Output Unit                                       E53-R4R4                                          Relay/Relay

                                                  E53-Q4R4                                          Pulse (NPN)/Relay

                                                  E53-Q4HR4                                         Pulse (PNP)/Relay

                                                  E53-C4R4                                          Linear (4 to 20 mA)/Relay

                                                  E53-C4DR4                                         Linear (0 to 20 mA)/Relay

                                                  E53-V44R4                                         Linear (0 to 10 V)/Relay

                                                  E53-Q4Q4                                          Pulse (NPN)/Pulse (NPN)

                                                  E53-Q4HQ4H                                        Pulse (PNP)/Pulse (PNP)

                                                                                                                                                  1
                                                                                                                                           E5CK

                  Description                                        Model                                                Specification

Option Unit                                     E53-CK01                                               RS-232C

                                                E53-CK03                                               RS-485

                                                E53-CKB                                                Event input: 1 point

                                                E53-CKF                                                Transfer output (4 to 20 mA)

Inspection Report

The Digital Controller can be provided together with an inspection report.

Refer to the following legend with the suffix “K” when ordering a model provided   together  with  an  inspection report.

E5CK-AA1-K, E53-CKF-K

■ Accessories (Order Separately)

             Name                               Model

Terminal Cover                    E53-COV07

             Name                               Model

Rubber Packing                    Y92S-29

Note: The Rubber Packing is provided with the Digital Controller.

Specifications

■ Ratings

                    Item                                                             100 to 240 VAC type

Supply voltage                             100 to 240 VAC, 50/60 Hz

Power consumption                          15 VA

Operating voltage range                    85% to 110% of rated supply voltage

Input                                      Thermocouple:                           K, J, T, E, L, U, N, R, S, B, W, PLII

                                           Platinum resistance thermometer:        JPt100, Pt100

                                           Current input:                          4 to 20 mA, 0 to 20 mA

                                           Voltage input:                          1 to 5 V, 0 to 5 V, 1 to 10 V

Input impedance                            Current input: 150 Ω

                                           Voltage input: 1 MΩ min.

Control output                             According to Output Unit (see Output Unit Ratings and Characteristics)

Auxiliary output                           SPST-NO, 1 A at 250 VAC (resistive load)

Control method                             ON/OFF or 2-PID control (with auto-tuning)

Setting method                             Digital setting using front panel keys

Indication method                          7-segment digital display and LEDs

Other functions                            According to Option Unit (see Output Unit Ratings and Characteristics)

Note: 1.   Do not use the output from an inverter as the power supply. Refer to Safety Precautions for All Temperature       Controllers.

       2.  The E5CK-T does not support fuzzy self-tuning.

■ Input Ranges

Platinum Resistance Thermometer

Input (switch selectable)         JPt100                   Pt100

Range               °C         −199.9 to 650.0    −199.9 to 650.0

                    °F         −199.9 to 999.9    −199.9 to 999.9

Resolution (°C/°F)             0                  1

(main setting and alarm)

                                                                                                                                                 2
                                                                                                                                            E5CK

Thermocouple

Input (switch           K1     K2       J1         J2      T          E       L1       L2       U         N         R      S      B       W  PLII

selectable)

(See note.)

Range       °C      −200    0.0 to  −100        0.0 to  −199.9     0 to   −100      0.0 to  −199.9    −200      0 to   0 to   100 to  0 to   0 to

                    to      500.0   to 850      400.0   to 400.0   600    to 850    400.0   to 400.0  to        1,700  1,700  1,800   2,300  1,300

                    1,300                                                                             1,300

            °F      −300    0.0 to  −100        0.0 to  −199.9     0 to   −100      0.0 to  −199.9    −300      0 to   0 to   300 to  0 to   0 to

                    to      900.0   to          750.0   to 700.0   1,100  to        750.0   to 700.0  to        3,000  3,000  3,200   4,100  2,300

                    2,300           1,500                                 1,500                       2,300

Resolution (°C/     2       3       4           5       6          7      8         9       10        11        12     13     14      15     16

°F) (main setting

and alarm)

Note: Setting number is factory-set to 2 (K1).

Thermocouple W is W/Re 5-26 (tungsten rhenium 5, tungsten rhenium 26).

Current/Voltage

Input (switch selectable)               Current input                                  Voltage input

                                   4 to 20 mA          0 to 20 mA         1 to 5 V         0 to 5 V       0 to  10 V

Range                          One of following ranges depending on results of scaling

                               −1999 to 9999

                               −199.9 to 999.9

                               −19.99 to 99.99

                               −1.999 to 9.999

Resolution (°C/°F)             17                  18                 19               20             21

(main setting and alarm)

                                                                                                                                                    3
                                                                                                                                     E5CK

■ Characteristics

Indication accuracy (See    note.)  Thermocouple:

                                    (±0.3% of indication value or ±1°C, whichever greater) ±1 digit max.

                                    Platinum resistance thermometer:

                                    (±0.2% of indication value or ±0.8°C, whichever greater) ±1 digit max.

                                    Analog input: ±0.2% FS ±1 digit max.

Hysteresis                          0.01% to 99.99% FS (in units of 0.01% FS)

Proportional band (P)               0.1% to 999.9% FS (in units of 0.1% FS)

Integral (reset) time (I)           0 to 3,999 s (in units of 1 s)

Derivative (rate) time (D)          0 to 3,999 s (in units of 1 s)

Control period                      1 to 99 s (in units of 1 s)

Manual reset value                  0.0% to 100.0% (in units of 0.1%)

Alarm setting range                 −1,999 to 9,999 or −199.9 or 999.9 (decimal point position dependent on input type)

Set time                            0 to 99 hrs 59 min or 0 to 99 min 59 s

Program capacity                    4 patterns, 16 steps (possible to use up to 4 patterns with the communications function.)

Programming method                  Time or ramp setting method

Time accuracy                       ±0.2% (±500 ms) of the set value

Sampling period                     Temperature input:           250 ms

                                    Current/voltage input:       100 ms

Insulation resistance               20 MΩ min. (at 500 VDC)

Dielectric strength                 2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities

Vibration resistance                Malfunction:  10 to 55 Hz, 10 m/s2 (approx. 1G) for 10 min each in X, Y, and Z directions

                                    Destruction:  10 to 55 Hz, 20 m/s2 (approx. 2G) for 2 hrs each in X, Y, and Z directions

Shock resistance                    Malfunction:  200 m/s2 min. (approx. 20G), 3 times each in 6 directions

                                                  (100 m/s2 (approx. 10G) applied to the relay)

                                    Destruction:  300 m/s2 min. (30G), 3 times each in 6 directions

Ambient temperature                 Operating:    −10°C to 55°C (with no icing)/3-year warranty period: –10°C to 50°C

                                    Storage:      −25°C to 65°C (with no icing)

Ambient humidity                    Operating:    35% to 85%

Degree of protection                Front panel:  NEMA4 for indoor use (equivalent to IP66)

                                    Rear case:    IEC standard IP20

                                    Terminals:    IEC standard IP00

Memory protection                   Non-volatile memory (number of writings: 100,000 operations)

Weight                              Approx. 170 g;

                                    Adapter: approx. 10 g

EMC                                 Emission Enclosure:                     EN55011 Group 1 class A

                                    Emission AC Mains:                      EN55011 Group 1 class A

                                    Immunity ESD:                           EN61000-4-2:       4 kV contact discharge (level 2)

                                                                                               8 kV air discharge (level 3)

                                    Immunity RF-interference:               ENV50140:          10 V/m (amplitude modulated, 80 MHz to 1 GHz)

                                                                                               (level 3)

                                                                                               10 V/m (pulse modulated, 900 MHz)

                                    Immunity Conducted Disturbance:         ENV50141:          10 V (0.15 to 80 MHz) (level 3)

                                    Immunity Burst:                         EN61000-4-4:       2 kV power-line (level 3)

                                                                                               2 kV I/O signal-line (level 4)

Approved standards                  UL61010C-1, CSA 22.2 No. 61010-1

                                    Conforms to EN61326-1: 2006, EN61010-1 (IEC61010-1)

                                    Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered terminal cover is

                                    mounted.

Note: The indication accuracy of the K1, T, and N thermocouples at a temperature of −100°C or less is ±2°C ±1 digit maximum. The indication

     accuracy of the U, L1, and L2 thermocouples at any temperature is ±2°C ±1 digit maximum.

     The indication accuracy of the B thermocouple at a temperature of 400°C or less is unrestricted.

     The indication accuracy of the R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum.

     The indication accuracy of the W thermocouple at any temperature is (±0.3% of the indicated value or ±3°C, whichever is greater) ±1 digit

     maximum.

     The indication accuracy of the PLII thermocouple at any temperature is (±0.3% or ±2°C, whichever is greater) ±1 digit maximum.

                                                                                                                                                4
                                                                                                                         E5CK

■ Output           Unit Ratings and Characteristics

Model              Control output 1/Control       output  2              Output Type                     Specifications

E53-R4R4           Relay / Relay                                      Relay                250 VAC. 3 A

E53-Q4R4           Voltage (NPN) / Relay                              Voltage (NPN)        12 VDC, 20 mA (with short-circuit protection)

E53-Q4HR4          Voltage (PNP) / Relay                              Voltage (PNP)        12 VDC, 20 mA (with short-circuit protection)

E53-C4R4           4 to 20 mA / Relay                                 0 to 10 V            0 to 10 VDC, Permissible load impedance:

                                                                                           1 kΩ min., Resolution: Approx. 2600

E53-C4DR4          0 to 20 mA / Relay                                 4 to 20 mA           4 to 20 mA, Permissible load impedance:

E53-V44R4          0 to 10 mA / Relay                                                      500 Ω max., Resolution: Approx. 2600

E53-Q4Q4           Voltage (NPN) / Voltage (NPN)

E53-Q4HQ4H         Voltage (PNP) / Voltage (PNP)

■ Option           Unit Ratings and Characteristics

                   Model                                                              Specifications

E53-CKB            Event input                     Contact input:

                                                   ON: 1 kΩ max., OFF: 100 kΩ min.

                                                   No-contact input:

                                                   ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.

E53-CK01           Communications         RS-232C  Transmission method:       Half-duplex

E53-CK03                                  RS-485   Synchronization method:    Start-stop synchronization (asynchronous  method)

                                                   Baud rate:                 1.2/2.4/4.8/9.6/19.2 kbps

E53-CKF            Transfer output                 4 to 20 mA DC:

                                                   Permissible load impedance: 500 Ω max.

                                                   Resolution: approx. 2,600

Note: Event input  is used for switching the target value, run or stop command, or automatic and manual mode with an external signal input.

                                                                                                                                             5
                                                                                                                                           E5CK

Nomenclature

Operation Indicators                                                                                     No. 1 Display

•  OUT1                                                                                                  Displays the process value or

   Lights when the pulse output                                                                          parameter symbols.

   function assigned to control                                                                          No. 2 Display

   output 1 turns ON.                                                                                    Displays the set point, set point

•  OUT2                                                                                                  during SP ramp, manipulated

   Lights when the pulse output                                                                          variable, or parameter settings.

   function assigned to control

   output 2 turns ON.

•  SUB1

   Lights when the output

   function assigned to auxiliary

   output 1 turns ON.

•  MANU

   Lights when the manual

   operation mode.

•  STOP

   Lights during operation has

   stopped.                                                                                              Up Key/Down Key

•  RMT

   Lights during remote                                                                                  Press to increase or decrease the

   operation.                                                                                            value on the No.2 display.

•  AT                                                                                                    Display Key

   Flashes during auto-tuning.                                                                           Press for less than 1 s to shift the

                                                               A/M Key                                   display to the next parameter. When

                                                               Press to select the  auto  operation  or  this key is pressed for 1 s or more,

                                                               manual operation.                         the menu screen will be displayed in

                                                                                                         any case.

Dimensions

Note: All units are in millimeters unless  otherwise  indicated.

E5CK                                                  58

                                                      53 × 53           13                100

                                                                                                         44.8 × 44.8  48

                                           Panel    Cutouts

                                                    65 min.

                           60 min.         45+00.6

                                                                            Note:   1.    Recommended panel thickness is 1 to 5 mm.

                                                      45+00.6                       2.    Maintain the specified vertical and horizontal

                                                                                          mounting space between each Unit. Units must not

                                                                                          be closely mounted vertically or horizontally.

                                                                                                                                                 6
                                                                                                                        E5CK

Terminal Cover

E53-COV07

                                (With rivet)

Unit Label (Order  Separately)

Y92S-L1

           ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

           To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                   In the interest of product improvement, specifications are subject to change without notice.

                                                                                                                              7
                                                      Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or

comments.

                                                      Warranty and Limitations of Liability

WARRANTY

OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)

from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR

FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS.                     ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS

DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.                                OMRON DISCLAIMS ALL OTHER

WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY

OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS

IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT

LIABILITY.

In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS

OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT

SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

                                                      Application Considerations

SUITABILITY FOR USE

OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's

application or use of the products.

At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the

products.   This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,

machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given.             This is not intended to be an exhaustive list of all possible

uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:

•  Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.

•  Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,

   safety equipment, and installations subject to separate industry or government regulations.

•  Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE

SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND

INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

PROGRAMMABLE PRODUCTS

OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.

                                                                    Disclaimers

CHANGE IN SPECIFICATIONS

Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.

However, some specifications of the products may be changed without any notice.     When in doubt, special model numbers may be assigned to fix or

establish key specifications for your application on your request.  Please consult with your OMRON representative at any time to confirm actual

specifications of purchased products.

DIMENSIONS AND WEIGHTS

Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

PERFORMANCE DATA

Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent               the

result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON

Warranty and Limitations of Liability.

ERRORS AND OMISSIONS

The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,

typographical, or proofreading errors, or omissions.

                                                                                                                                                                         2009.4

                                                      In the interest of product improvement, specifications are subject to change without notice.

OMRON Corporation

Industrial Automation Company

http://www.ia.omron.com/

                                                                                                          (c)Copyright OMRON Corporation 2009 All Right Reserved.
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Omron:

E5CK-AA1-500  E53-CK03  E53-Q4R4  E5CK-AA1-500 AC/DC24V  E5CK-AA1-AC/DC24   E5CK-RR1  E5CK-TAA1-

500 AC/DC24  E5CK-TAA1 AC100-240  E5CK-TAA1 AC/DC24  E53-Q4HR4  E53-Q4HQ4H  E53-Q4Q4
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2020 EEWORLD.com.cn, Inc. All rights reserved