电子工程世界电子工程世界电子工程世界

型号

产品描述

搜索

E5CC-CX0AUM-000

器件型号:E5CC-CX0AUM-000
器件类别:热门应用    机电_工控_自动化   
厂商名称:OMRON
厂商官网:https://www.omron.com
下载文档

器件描述

Controllers Current 0 Aux Output 2 Alarms AC100-240

参数

产品属性属性值
Product AttributeAttribute Value
制造商:
Manufacturer:
Omron
产品种类:
Product Category:
Controllers
RoHS:YES
Analog / Digital:Digital
类型:
Type:
Digital Temperature Controller
Display Type:11-Segment, 4 Digit
工作电源电压:
Operating Supply Voltage:
100 VAC to 240 VAC
Mounting:Panel
大小:
Size:
48 mm x 48 mm
Number of Outputs:0
输出类型:
Output Type:
Linear Current
系列:
Series:
E5CC
商标:
Brand:
Omron Automation and Safety
Number of Inputs:1
工厂包装数量:
Factory Pack Quantity:
1
零件号别名:
Part # Aliases:
E5CCCX0AUM000
单位重量:
Unit Weight:
4.232875 oz

E5CC-CX0AUM-000器件文档内容

Digital Temperature Controller

E5CC-U (48 × 48 mm)

Large White PV Display That’s Easier to Read.

Easy to Use, from Model Selection to

Setup and Operation.

A Complete Range of I/O Capacities,

Functions, and Performance.

Handles More Applications.

• The white PV display with a height of 15.2 mm improves visibility.

• High-speed sampling at 50 ms.                                                                      48 × 48 mm

• Models are available with up to 2 auxiliary outputs, to cover                                              E5CC-U

a wide range of applications.                                         Refer to your OMRON website for the most recent information on

• E5CC: Short body with depth of only 60 mm.                          applicable safety standards.

• Set up the Controller without wiring the power supply by

connecting to the computer with a Communications Conversion                         Refer to Safety Precautions.

Cable (sold separately). Setup is easy with the CX-Thermo (sold

separately).

Main I/O Functions

Sensor Input                                  E5CC-U

Universal input

• Thermocouple                                                              Dual displays: PV/SV     4-digit displays

• Pt

• Analog current/voltage

      Indication Accuracy                                                   Control Output 1

      • Thermocouple input:                                                 • Relay output

      ±0.3% of PV                                                           • Voltage output (for driving SSR)

      • Pt input: ±0.2% of PV                                               • Linear current output

      • Analog input:

      ±0.2% of FS                                                           Control Output 2

                                                                            • None

      Sampling Period                                                       • Voltage output (for   driving  SSR)

      • 50 ms                                                               Auxiliary Outputs

Event Inputs                                                                • None

                                 • PF (shift) Key                           •1

• None                           • Temperature status display               •2

•2                               • Simple programming                       •3

•4                               • Independent heating and

                                 cooling PID control                        Transfer Output

Remote SP Input                  • Changed parameter display                • None

• None                           • Display brightness setting               •1

•1

Serial Communications

• None

• RS-485

This datasheet is provided as a guideline for selecting products.

Be sure to refer tothe following manuals for application precautions and other information required for operation before attempting

to use the product.

E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174)

E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)

                                                                                                                                      1
   E5CC-U

   Model Number Legend

   ●Plug-in Models

   E5CC-− @A@−        @     @   − UD  − @E -− @F− @@−  (Example:      E5CC-RW0AUM-000)
                      − B  − C

                   A        B            C             D        E            F

   Model      Control       No. of    Power      Terminal    Input                                                       Meaning

              outputs      auxiliary  supply           type     type  Options

              1 and 2      outputs    voltage

   E5CC                                                                                                             48 × 48 mm

                                                                                       Control output 1                              Control output  2

              RW                                                                       Relay output (SPDT)                             None

              QX                                                                       Voltage output (for driving SSR)                None

              CX                                                                       Linear current output*                          None

                         0                                                                                               None

                         1                                                                                               1

                         2                                                                                     2 (one common)

                                      A                                                                             100 to 240 VAC

                                      D                                                                                  24 VAC/DC

                                                 U                                                                  Plug-in model

                                                             M                                                      Universal input

                                                                                       HB alarm and HS  Communi-         Event inputs  Remote SP     Transfer  out-

                                                                                       alarm            cations                        Input            put

                                                                             000        ---                    ---             ---     ---              ---

   * The control output cannot be used as a transfer output.

   List of Models

                                                                      Options                                  Model                        Model

   Control output      No. of auxiliary     HB alarm and        No. of event                            Power supply voltage           Power supply voltage

                            outputs              HS alarm            inputs       Communications

                                                                                                        100 to 240 VAC                 24 VAC/DC

                       ---                                                                        E5CC-RW0AUM-000                    E5CC-RW0DUM-000

   Relay output        1                    ---                 ---               ---             E5CC-RW1AUM-000                    E5CC-RW1DUM-000

                       2                                                                          E5CC-RW2AUM-000                    E5CC-RW2DUM-000

                       ---                                                                        E5CC-QX0AUM-000                    E5CC-QX0DUM-000

   Voltage output      1                    ---                 ---               ---             E5CC-QX1AUM-000                    E5CC-QX1DUM-000

   (for driving SSR)

                       2                                                                          E5CC-QX2AUM-000                    E5CC-QX2DUM-000

                       ---                                                                        E5CC-CX0AUM-000                    E5CC-CX0DUM-000

   Linear current      1                    ---                 ---               ---             E5CC-CX1AUM-000                    E5CC-CX1DUM-000

   output

                       2                                                                          E5CC-CX2AUM-000                    E5CC-CX2DUM-000

   Heating and Cooling Control

   ●Using Heating and Cooling Control

   A Control Output Assignment

   An auxiliary output is used as the cooling control output.

   B Control

   If PID control is used, you can set PID control separately for heating and cooling.

   This allows you to handle control systems with different heating and cooling response characteristics.

2
                                                                                                          E5CC-U

Optional Products (Order Separately)

USB-Serial Conversion Cable                                            Front Covers

             Model                                                     Type                        Model

         E58-CIFQ2                                                     Hard Front Cover         Y92A-48H

                                                                       Soft Front Cover         Y92A-48D

Terminal Covers (for E5CC)

             Model                                                     CX-Thermo Support Software

         E53-COV17                                                                       Model

         E53-COV23                                                     EST2-2C-MV4

Note: The E53-COV10 cannot be used.                                    Note: CX-Thermo version 4.5 or higher is required for the E5CC.

Refer to page 14 for the mounted dimensions.                           CX-Thermo version 4.61 or higher is required for the E5CC-U.

Waterproof Packing                                                     For the system requirements for the CX-Thermo, refer to

                                                                       information on the EST2-2C-MV4 on the OMRON website

             Model                                                     (www.ia.omron.com).

         Y92S-P8

Note: The Waterproof Packing is provided only with E5CC

Controllers.

The E5CC-U cannot be waterproofed even if the Waterproof

Packing is attached.

Current Transformers (CTs)

Hole diameter                Model

5.8 mm                      E54-CT1

12.0 mm                     E54-CT3

Adapter

             Model

         Y92F-45

Note: Use this Adapter when the panelhas already been prepared for

an E5B@ Controller.

Waterproof Cover

             Model

         Y92A-48N

Mounting Adapter

             Model

         Y92F-49

Note: This Mounting Adapter is provdi ed with the Digital Temperature

Controller.

DIN Track Mounting Adapter

             Model

         Y92F-52

Sockets (for E5CC-U)

                  Type                          Model

Front-connecting Socket                         P2CF-11

Front-connecting Socket with Finger Protection  P2CF-11-E

Back-connecting Socket                          P3GA-11

Terminal Cover for Back-connecting socket       Y92A-48G

with Finger Protection

                                                                                                                                        3
   E5CC-U

   Specifications

   Ratings

   Power supply voltage                  A in model number: 100 to 240 VAC, 50/60 Hz

                                         D in model number: 24 VAC, 50/60 Hz; 24 VDC

   Operating voltage range               85% to 110% of rated supply voltage

                                         Models with option selection of 000: 5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or

   Power consumption                                                                  1.6 W max. at 24 VDC

                                         All other models: 6.5 VA max. at 100 to 240 VAC, adn 4.1 VA max. at 24 VAC or 2.3 W max. a2t 4 VDC

                                         Temperature input

                                         Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II

                                         Platinum resistance thermometer: Pt100 or JPt100

   Sensor input                          Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C

                                         Analog input

                                         Current input: 4 to 20 mA or 0 to 20 mA

                                         Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V

   Input impedance                       Current input: 150 Ω max., Voltage input: 1 MΩ min.

                                         (Use a 1:1 connection when connecting the ES2-HB/THB.)

   Control method                        ON/OFF control or 2-PID control (with auto-tuning)

                                         E5CC:    SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum ap-

                 Relay output                     plicable load: 5 V, 10 mA *

   Control                               E5CC-U:  SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applica-

   output                                         ble load: 5 V, 10 mA

                 Voltage output          Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit

                 (for driving SSR)

                 Linear current output   4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000*

                 Number of outputs       E5CC: 3

   Auxiliary                             E5CC-U: 1 or 2 (depends on model)

   output        Output specifications   SPST-NO relay outputs, 250 VAC, Models with 1 or 2 outputs: 3 A (resistive load), or Models with 3

                                         outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V

                 Number of inputs        2 or 4 (depends on model)

   Event input   External contact input  Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.

                 specifications          Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.

                                         Current flow: Approx. 7 mA per contact

   Transfer      Number of outputs       1 (only on models with a transfer output)

   output        Output specifications   Contact output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000

                                         Linear voltage output: 1 to 5 VDC, load: 1 kΩ max, resolution: Approx. 10,000

   Setting method                        Digital setting using front panel keys

   Remote SP input                       Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.)

                                         Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.)

   Indication method                     11-segment digital display and individual indicators

                                         Character height: PV: 15.2 mm, SV: 7.1 mm

   Multi SP                              Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or

                                         serial communications.

   Bank switching                        None

                                         Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater

                                         burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital

   Other functions                       filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root,

                                         MV change rate limit, simple calculations, temperature status display, simple programming, moving

                                         average of input value, and display brightness setting

   Ambient operating temperature         -10 to 55°C (with no condensation or icing),

                                         for 3-year warranty: -10 to 50°C (with no condensation or icing)

   Ambient operating humidity            25% to 85%

   Storage temperature                   -25 to 65°C (with no condensation or icing)

   Altitude                              2,000 m max.

   Recommended fuse                      T2A, 250 VAC, time lag, low shut-off capacity

   Installation environment              Installation Category II, Pollution Class 2 (IEC 61010-1 compliant)

   * You cannot select a relay output or linear current output for control output 2.

   Note: There are no optional functions for the E5CC-U. Refer to Model Number Legend and List of Models on page 4.

4
                                                                                                                                                                                                E5CC-U

Input Ranges

●Thermocouple/Platinum Resistance Thermometer (Universal inputs)

Sensor                                   Platinum resistance                                                               Thermocouple                                                  Infrared temperature

                        type              thermometer                                                                                                                                           sensor

Sensor                                                                                                                                                                                   10 to  60 to  115 to  140 to

specifica-                                Pt100          JPt100              K               J               T          E     L           U          N     R     S     B     W     PLII  70°C   120°C  165°C   260°C

                        tion

                              2300                                                                                                                                           2300

                              1800                                                                                                                                     1800

                              1700                                                                                                                         1700  1700

                              1600

Temperature range (°C)        1500

                              1400                                     1300                                                                          1300                          1300

                              1300

                              1200

                              1100

                              1000  850                                                850                                    850

                              900

                              800

                              700                                                                                       600

                              600         500.0          500.0                  500.0

                              500                                                               400.0  400      400.0               400      400.0

                              400                                                                                                                                                                              260

                              300                                                                                                                                                               120    165

                              200                 100.0         100.0                                                                                                                    90

                              100                                                                                                                                      100

                               0                  0.0           0.0                                                                                        0     0           0     0     0      0      0       0

                              -100                                              -20.0  -100     -20.0                         -100

                              -200  -200  -199.9         199.9         -200                            -200     -199.9  -200        -200     -199.9  -200

Set                     value       0     1           2  3      4      5        6      7        8      9        10      11    12    13       14      15    16    17    18    19    20    21     22     23      24

                        Shaded settings are the default settings.

The applicable standards for the input types are as follows:

K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1                                            JPt100: JIS C 1604-1989, JIS C 1606-1989

L: Fe-CuNi, DIN 43710-1985                                                                      Pt100: JIS C 1604-1997, IEC 60751

U: Cu-CuNi, DIN 43710-1985                                                                      PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)

W: W5Re/W26Re, ASTM E988-1990

●Analog input

Input type                                            Current                                Voltage

Input                                     4 to 20 mA     0 to 20 mA          1 to 5 V        0 to 5 V        0 to 10 V

specification

                                          Usable in the following ranges by scaling:

Setting range                             -1999 to 9999, -199.9 to 999.9,

                                          -19.99 to 99.99 or -1.999 to 9.999

Set value                                         25            26              27              28              29

                                                                                                                                                                                                                       5
   E5CC-U

   Alarm Outputs

   Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)

   Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.

   Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.

       To use alarm 1, set the output assignment to alarm 1.

   Set                                                Alarm output operation

   value          Alarm type              When alarm value X            When alarm value X                              Description of function

                                                   is positive               is negative

   0          Alarm function OFF                                Output OFF                         No alarm

                                                                                                   Set the upward deviation in the set point for the alarm upper

                                              ON      L     H                                      limit (H) and the lower deviation inthe set point for the alarm

   1          Upper- and lower-limit *1       OFF               PV      *2                         lower limit (L). The alarm is ON when the PV is outside this

                                                      SP

                                                                                                   deviation range.

   2                                          ON            X           ON        X                Set the upward deviation in the set point by setting the alarm

   (default)  Upper-limit                     OFF               PV      OFF                   PV   value (X). The alarm is ON when the PV is higher than the

                                                      SP                          SP               SP by the deviation or more.

                                              ON      X                 ON              X          Set the downward deviation in the set point by setting the

   3          Lower-limit                     OFF               PV      OFF                   PV   alarm value (X). The alarm is ON when the PV is lower than

                                                      SP                          SP               the SP by the deviation or more.

                                                                                                   Set the upward deviation in the set point for the alarm upper

              Upper- and lower-limit          ON      L     H                                      limit (H) and the lower deviation inthe set point for the alarm

   4          range *1                        OFF               PV      *3                         lower limit (L). The alarm is ON when the PV is inside this de-

                                                      SP

                                                                                                   viation range.

              Upper- and lower-limit          ON      L     H                                      A standby sequence is added to the upper- and lower-limit

   5          with standby sequence *1        OFF               PV      *4                         alarm (1). *6

                                          *5          SP

              Upper-limit with standby        ON            X           ON        X

   6          sequence                        OFF               PV      OFF                   PV   A standby sequence is added to the upper-limit alarm (2). *6

                                                      SP                          SP

              Lower-limit with standby        ON      X                 ON              X

   7          sequence                        OFF               PV      OFF                   PV   A standby sequence is added to the lower-limit alarm (3). *6

                                                      SP                          SP

              Absolute-value upper-lim-       ON         X              ON           X             The alarm will turn ON if the process value is larger than the

   8          it                              OFF               PV      OFF                   PV   alarm value (X) regardless of the set point.

                                                   0                                       0

                                              ON         X              ON           X             The alarm will turn ON if the process value is smaller thanthe

   9          Absolute-value lower-limit      OFF               PV      OFF                   PV   alarm value (X) regardless of the set point.

                                                   0                                       0

              Absolute-value upper-lim-       ON         X              ON           X             A standby sequence is added to the absolute-value upper-

   10         it with standby sequence        OFF               PV      OFF                   PV   limit alarm (8). *6

                                                   0                                       0

              Absolute-value lower-limit      ON         X              ON           X             A standby sequence is added to the absolute-value lower-

   11         with standby sequence           OFF               PV      OFF                   PV   limit alarm (9). *6

                                                   0                                       0

   12         LBA (alarm 1 type only)                                -                             *7

   13         PV change rate alarm                                   -                             *8

              SP absolute-value               ON         X              ON           X             This alarm type turns ON the alarm when the set point (SP)

   14         upper-limit alarm               OFF               SP      OFF                   SP   is higher than the alarm value (X).

                                                   0                                       0

              SP absolute-value               ON         X              ON           X             This alarm type turns ON the alarm when the set point (SP)

   15         lower-limit alarm               OFF               SP      OFF                   SP   is lower than the alarm value (X).

                                                   0                                       0

                                          Standard Control              Standard Control

                                              ON         X              ON           X

                                              OFF  0            MV      OFF                   MV

              MV absolute-value                                                            0       This alarm type turns ON the alarm when the manipulated

   16         upper-limit alarm *9        Heating/Cooling               Heating/Cooling            variable (MV) is higher than the alarm value (X).

                                          Control (Heating MV)          Control (Heating MV)

                                              ON         X

                                              OFF  0            MV      Always ON

                                          Standard Control              Standard  Control

                                              ON         X              ON           X

                                              OFF  0            MV      OFF                0  MV

   17         MV absolute-value           Heating/Cooling               Heating/Cooling            This alarm type turns ON the alarm when the manipulated

              lower-limit alarm *9        Control (Cooling MV)          Control (Cooling MV)       variable (MV) is lower than the alarm value (X).

                                              ON         X

                                              OFF  0            MV      Always ON

              RSP absolute-value              ON         X              ON           X             This alarm type turns ON the alarm when the remote SP

   18         upper-limit alarm *10           OFF               RSP     OFF                0  RSP  (RSP) is higher than the alarm value (X).

                                                   0

              RSP absolute-value              ON         X              ON           X             This alarm type turns ON the alarm when the remote SP

   19         lower-limit alarm *10           OFF               RSP     OFF                   RSP  (RSP) is lower than the alarm value (X).

                                                   0                                       0

6
                                                                                                                                                   E5CC-U

*1  With set values 1, 4 and 5, the upper and lower limit values can be set       *4   Set value: 5, Upper- and lower-limit with standby sequence

    independently for each alarm type, and are expressed as “L” and “H.”               For Upper- and Lower-Limit Alarm Described Above *2

*2  Set value: 1, Upper- and lower-limit alarm                                         • Case 1 and 2

    Case 1            Case 2                    Case 3 (Always ON)                     Always OFF when the upper-limit and lower-limit hysteresis overlaps.

                                                                       H<0, L<0        • Case 3: Always OFF

            L  H  SP  SP L    H                    H  SP    L

    H<0, L>0          H>0, L<0                                         H<0, L>0   *5.  Set value: 5, Upper- and lower-limit with standby sequence

    |H| < |L|         |H| > |L|                 H     L SP             |H| ≥ |L|       Always OFF when the upper-limit and lower-limit hysteresis overlaps.

                                                                       H>0, L<0   *6   Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.

                                                      SP H          L  |H| ≤ |L|       H174) for information on the operation of the standby sequence.

*3  Set value: 4, Upper- and lower-limit range                                    *7   Refer to the E5@C Digital Temperature Controllers User's Manual (Cat.

                                                                                       No.H174)  for information on the loop burnout alarm (LBA).

    Case 1            Case 2     Case 3 (Always OFF)                              *8   Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.

                                                                       H<0, L<0        H174) for information on the PV change rate alarm.

    L          H  SP  SP L    H                    H  SP    L                     *9   When heating/cooling control is performed, the MV absolute upper limit

    H<0, L>0          H>0, L<0                                         H<0, L>0        alarm functions only for the heating operation and the MV absolute lower

    |H| < |L|         |H| > |L|                 H     L SP             |H| ≥ |L|       limit alarm functions only for the cooling operation.

                                                                       H>0, L<0   *10  This value is displayed only when a remote SP input is used. It functions in

                                                      SP H     L       |H| ≤ |L|       both Local SP Mode and Remote SP Mode.

                                                                                       Remote SP input is supported only for the E5CC.

                                                                                                                                                                     7
   E5CC-U

   Characteristics

                                          E5CC

                                          Thermocouple:    (±0.3% of PV or ±1°C, whichever is greater) ±1 digit max. *1

                                          Platinum resistance thermometer: (±0.2% of PV or ±0.8°C, whichever is greater) ±1 digit

   Indication accuracy                    Analog input:    ±0.2% FS ±1 digit max.

   (at the ambient temperature of 23°C)   CT input:        ±5% FS ±1 digit max.

                                          E5CC-U

                                          Thermocouple:    (±1% of PV or ±2°C, whichever is greater) ±1 digit max. *1

                                          Platinum resistance thermometer: (±0.2% of PV or ±0.8°C, whichever is greater) ±1 digit

                                          Analog input:    ±0.2% FS ±1 digit max.

   Transfer output accuracy               ±0.3% FS max.

   Remote SP Input Type                   ±0.2% FS ±1 digit max.

   Influence of temperature       *2      Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.

                                          Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3

                                          Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.

   Influence of voltage   *2              Analog input: ±1%FS ±1 digit max.

                                          CT input: ±5% FS ±1 digit max.

                                          Remote SP      input: ±1% FS ±1 digit max.

   Input sampling period                  50 ms

   Hysteresis                             Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)

                                          Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)

   Proportional band (P)                  Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)

                                          Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)

   Integral time (I)                      0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4

   Derivative time (D)                    0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4

   Proportional band (P) for cooling      Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F)

                                          Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)

   Integral time (I) for cooling          0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4

   Derivative time (D) for cooling        0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4

   Control period                         0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)

   Manual reset value                     0.0 to 100.0% (in units of 0.1%)

   Alarm setting range                    -1999 to 9999 (decimal point position depends on input type)

   Influence of signal source resistance  Thermocouple: 0.1°C/Ω max. (100 Ωmax.)
                                          Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)

   Insulation resistance                  20 MΩ min. (at 500 VDC)

   Dielectric strength                    3,000 VAC, 50/60 Hz for 1 min between terminals of different charge

   Vibration   Malfunction                10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions

               Resistance                 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions

   Shock       Malfunction                100 m/s2, 3 times each in X, Y, and Z directions

               Resistance                 300 m/s2, 3 times each in X, Y, and Z directions

   Weight                                 E5CC: Controller: Approx. 120 g, Mounting Bracket: Approx. 10 g

                                          E5CC-U: Controller: Approx. 100 g, Mounting Bracket: Approx. 10 g

   Degree of protection                   E5CC: Front panel: IP66, Rear case: IP20, Terminals: IP00

                                          E5CC-U: Front panel: IP50, Rear case: IP20, Terminals: IP00

   Memory protection                      Non-volatile memory (number of writes: 1,000,000 times)

   Setup Tool                             E5CC: CX-Thermo version 4.5 or higher

                                          E5CC-U: CX-Thermo version 4.61 or higher

   Setup Tool port                        E5CC/E5CC-U top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB

                                                                          port on the computer. *5

   Standards   Approved standards         UL 61010-1*6, KOSHA certified (some models) *7, Korean Radio Waves Act (Act 10564)

               Conformed standards        EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *8

                                          EMI:                                                           EN61326

                                          Radiated Interference Electromagnetic Field Strength:          EN 55011 Group 1, class A

                                          Noise Terminal Voltage:                                        EN 55011 Group 1, class A

                                          EMS:                                                           EN 61326

   EMC                                    ESD Immunity:                                                  EN 61000-4-2

                                          Electromagnetic Field Immunity:                                EN 61000-4-3

                                          Burst Noise Immunity:                                          EN 61000-4-4

                                          Conducted Disturbance Immunity:                                EN 61000-4-6

                                          Surge Immunity:                                                EN 61000-4-5

                                          Voltage Dip/Interrupting Immunity:                             EN 61000-4-11

   *1  The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and U and

       L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is

       not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and

       S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C,

       whichever is greater) ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3% of PV or ±2°C, whichever is greater, ±1 digit max.

   *2  Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage

   *3  K thermocouple at -100°C max.: ±10°C max.

   *4  The unit is determined by the setting of the Integral/Derivative Time Unit parameter.

   *5  External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.

   *6  The E5CC-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket. The P3GA-11

       is not certified for UL listing.

   *7  Access the following website for information on certified models. http://www.ia.omron.com/support/models/index.html

   *8  Refer to information on maritime standards in Shipping Standards on page 56 for compliance with Lloyd's Standards.

       The E5CC-U is scheduled to obtain certification in January, 2014.

8
                                                                                                                                                                                                                                                                                                                    E5CC-U

USB-Serial Conversion Cable                                                                                                                                                                           Electrical Life Expectancy Curve for

   Applicable OS               Windows XP, Vista, or 7                                                                                                                                                Relays (Reference Values)

   Applicable software         CX-Thermo version 4.5 or higher (Version 4.61 or

                               higher is required for the E5CC-U.)

   Applicable models           E5@C-T Series, E5@C Series, and E5CB Series                                                                                                                                 Life (× 104 operations)  500

   USB interface standard      Conforms to USB Specification 2.0.                                                                                                                                                                   300

   DTE speed                   38400 bps

   Connector                   Computer: USB (type A plug)                                                                                                                                                                          100

   specifications              Digital Temperature Controller:

                               Special serial connector                                                                                                                                                                             50

   Power supply                Bus power (Supplied from USB host controller.)*                                                                                                                 MELSEC is a30registered trademark of Mitsubishi Electric Corporation.

   Power supply voltage        5 VDC                                                                                                                                                           KEYENCE is a registered trademark of Keyence Corporation.

   Current consumption         450 mA max.                                                                                                                                                     *1     A Temperature Controller with version 1.1 or higher is required.

                               4.7±0.2 VDC                                                                                                                                                            A Tempe1r0ature Controller with version 2.1 or higher is required for

   Output voltage              (Supplied from USB-Serial Conversion Cable to                                                                                                                          the FX Series or the KV Series.

                               the Digital Temperature Controller.)                                                                                                                            *2     Both the p5rograEm5CleCss communications and the component

                               250 mA max.                                                                                                                                                            communic3ations25s0uVpApC,o3r0t VthDeC copying.
                                                                                                                                                                                                                                                 (resistive load)
   Output current              (Supplied from USB-Serial Conversion Cable to
                                                                                                                                                                                               Current                              1Trancossφ =fo1 rmer                                    (Order Separately)
                               the Digital Temperature Controller.)

   Ambient operating           0 to 55°C (with no condensation or icing)                                                                                                                       Ratings                                   0          1   2          3                        4           5       6

   temperature                                                                                                                                                                                                                                                                              Switching current (A)

   Ambient operating           10% to 80%
   humidity

   Storage temperature         -20 to 60°C (with no condensation or icing)

   Storage humidity            10% to 80%

   Altitude                    2,000 m max.

   Weight                      Approx. 120 g

Windows is a registered trademark of Microsoft Corporation in the

United States and or other countries.                                                                                                                                                          Heater Burnout Alarms and SSR Failure

* Use a high-power port for the USB port.                                                                                                                                                      Alarms

Note: A driver must be installed on the computer. Refer to the

   Instruction Manual included with the Cable for the installation

   procedure.

ECxotemrmnaulnCicoantnioencstioSnpsecifications

                                               The E5CC-U is set for a K-type thermocouple (input type =                                                                                                   E5CC-                                       UM-000

                                               5) by default. An input error (s.err) will occur if the input                                                                                                                        Control output 1

                                               type setting does not agree with the temperature sensor.

                                               Check the input type.                                                                                                                                                                Auxiliary outputs 1 and 2

                                                                                                                                                                                                                                    Relay output

                                                                                                                                                                                                                                    250 VAC, 3 A (resistive load)

                                                                                                 Control output 1

                                                                                   I                                                                                                                                                Auxiliary output 1

                                                                                                                                                                                   Pt A                                                                Auxiliary output 2:

                                                                                      +                                                                                                                                                                Control output (cooling side)

                                                                               mA             V  TC                                                                                            *1     For heater burnout alarms, the heater current will be measured

                                                                                              −  −                                                                                 B                  when the control output is ON, and the output will turn ON if the

                                                                                      −  V                                                                                                            heater cuIrnrepunttpioswloerwseurppthlyan the set value (i.e., heater burnout

                                                                                              +  +                                                                                 B                  detection current value).

                                                                                      Sensor  (temperature/analog)                                                                           in*2put  For  SSR failure• 1a0la0rtmo s24, 0thVeAhCeatercurrent will be                                            measured when

                Control output 1                                                                                                                                                                      the  control outp•u2t4isVOACF/FD,Ca(nod ptholearoityu)tput will turn                                      ON if the heater

                                                                                                                                                                                                      current is higher than the set value (i.e., SSR failure detection

             Voltage output (for driving SSR)  Control output 1:                                                                                                                                      current value).

             12 VDC, 21 mA                                                               QX                                                                                                  M**o34deClTTsXhhweeithvv1aalluuee           is  30  ms    ffMoorrodRaaeWcclsoownnittthrroo1ll  period  of  0.1  s  or  0.2  s.

             Linear current output                       Models with 1                                                                                                                                                                   is  35  ms                                         period  of  0.1  s  or  0.2  s.

*  Tbeheinbdaivu40Lidodttaoourdaa22:tl00l5ey0mm, s0dAAeaΩtDDtauCCmsbainixt.gletnhgethC,osmtompubniticleantiogthnV(,fsooarltSnaD−dgerietvvtiOinengurgttSpicLSuaetRlv)peal.rity can            Linear Current                                            Relay Output

                                                                                                                                                                                             Output

                                                                                                                                                                                            −                                                Output 1

CommRSPelDuayT,on2u5tp0iucVt A(thCar,e3etAtieorminnalssusedF) unctionOustQput      1                                                                                               Output 1                                                      R

                                                                                   +                                                                                                     C  +

             (resistive load)

E5CC-U                                                                                                                                                                                                                                                                                                                            9
E5CC-U

       Isolation/Insulation Block Diagrams

   
    • E5CC-U

       Models with 2 Auxiliary Outputs

                                          Sensor input

       Power       Voltage output (for driving SSR) and linear      current  output

       supply

                                          Relay output

                         Auxiliary outputs 1 and 2

                :  Reinforced insulation

                :  Functional isolation

       Nomenclature

                                                                    Front panel

       E5CC-U            Temperature unit                                                                                     Top View of E5CC  Top View of E5CC-U

                     Operation indicators                                                    No. 1 display

                                                                                             PV or specified parameter

                                                                                             No. 2 display

                                                                                             SP or specified parameter value

                                                                                       Use the U D Keys to set the

                                                                                       parameter.

                                                                                                                                         Top-panel Setup Tool port

                   Press O Key once to go to Adjustment Level.                         Use S Key to change the digit (default setting).

                   Press O Key for at least 3 seconds to go to Initial Setting Level.

                                                                                       Use the M Key to change to another parameter.

    Dimensions                                                                                                                                                                (Unit: mm)

    Controllers

    E5CC-U                                                                   76.8

                                         48 × 48           4           58.6            14.2

                                                                                                            48 × 48

                                                                                       58

                                                                    Mounting Adapter

                                                                    (Accessory)

                     The Setup Tool port is on the top of the Temperature Controller.

                     It is used to connect the Temperature Controller to the computer to use the Setup Tool.

                     The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.

                     Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.

                     Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller.

                                                                Panel  Cutout

                         Mounted Separately                                            Group Mounted

                                                                                       (48 × number of units - 2.5)+10.0

                                                                                                                          • Recommended panel thickness is 1 to 5 mm.

                                                                                                      45+00.6             • Group mounting is not possible in the vertical direction. (Maintain

                                                                                                                          the specified mounting space between Controllers.)

                     60  min.                                                                                             • When two or more Controllers are mounted, make sure that the

                                                                                                                          surrounding temperature does not exceed the allowable operating

                                                                                                                          temperature specified in the specifications.

                                                           45+00.6                                                        • To attach the USB-Serial Conversion Cable to the control panel,

                                                                                                                          use a panel thickness of 1 to 2.5 mm.

                                                  45+00.6

10
                                                                                                                                   E5CC-U

Accessories (Order Separately)

● USB-Serial Conversion Cable

E58-CIFQ2

                                                                                                 (2,110)    (13)                                (5) (15)

                                                                    250                    (87)                             1,740

                                                                                   LED (RD)                          (250)

                                             USB connector (type A plug)

                                                                                                       LED (PWR)                   Serial connector

                                                                                                       LED (SD)

● Terminal Covers                            48                                 ● Terminal       Covers

E53-COV17                                                                       E53-COV23        (Three Covers       provided.)

                                                                                                                  2  3.8

                           48.8

                                                                                                            10

                                                                                                                                   Terminal Cover

                                                                                                                                   (E53-COV23)

                           22                                                                    44.8

                           9.1

● Terminal Cover (for  the P3GA-11 Back-connecting                        Socket)

Y92A-48G

                                Twelve, 6.4-dia.

                   34      Y92A-48G  UP      47.7×47.7                   48×48

                                       P  C

                                                  16.5  24.6

                                                              27.6

                                 47.4

                   Note: You  can attach     the P3GA-11 Back-connecting Socket for finger protection.

● Waterproof Packing                              The Waterproof Packing is provided only with the E5CC.

Y92S-P8 (for DIN 48 × 48)                         Order the Waterproof Packing separately if it becomes lost or damaged.

                                                  The Waterproof Packing can be used to achieve an IP66 degree of protection.

                                                  (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the

                                                  operating environment. Therefore, periodic replacement is recommended to ensure the level of

                                                  waterproofing specified in IP66. The time for periodic replacement depends on the operating

                                                  environment. Be sure to confirm this point at your site.

                                                  Consider three years a rough standard.)

                                                  The Waterproof Packing does not need to be attached if a waterproof structure is not required.

                                                  The E5CC-U cannot be waterproofed even if the Waterproof Packing is attached.

                                                                                                                                                          11
E5CC-U

    ● Adapter

    Y92F-45    Note: 1.  Use this Adapter when the Front Panel has already been prepared for the E5B@.

                     2.  Only black is available.

                     3.  You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial

                         Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel.

                                                                                                                         Fixture (Accessory)

                                                                             4.7                        76

                                                                                             69.6 to 77.6

                                                   72 × 72

                                                                                                                              67 × 67 87

    Mounted to E5CC                                                          Panel (1 to 8 mm)              Mounting Adapter

                                                   72 × 72                                                  Y92F-30

                                                                                                            (Accessory)

                                                                    48 × 48

                                                                    2.2           4.7

                                                                                             62.8

                                                                                  To back of the E5CC

    ● DIN Track Mounting Adapter

    Y92F-52    Note: This Adapter cannot be used together with the Terminal Cover.

                     Remove the Terminal Cover to use the Adapter.

                                                                                                                     This Adapter is used to mount the

                                                                                             61                      E5CC to a DIN Track.

                                                                                                                     If you use the Adapter, there is no

                                                                                                                     need for a plate to mount in the

                                                                                                                     panel or to drill mounting holes in

                                                                                                   3.5               the panel.

                                                   50                        38

    Mounted to E5CC

                                                            48

                                                                                       80.5

12
                                                                                                                                                                        E5CC-U

● Watertight          Cover                                                                 ● Mounting               Adapter

Y92A-48N                                                                                    Y92F-49

                                                  21.9      14                                                                     The Mounting Adapter is provided with the

                                                       (2)                                                                         Temperature Controller.

                                                                                                                                   Order this Adapter separately if it becomes

                                                                                                                                   lost or damaged.

          87.7  79.2                                                      69

                                                                          12

                      67.6

● Protective Cover                                                                          ● Protective Cover

Y92A-48D              Note: This Protective Cover cannot be used                            Y92A-48H

                             if the Waterproof Packing is installed.                                                               This Protective Cover is hard type.

                             This Protective Cover is soft type.                                                                   Please use it for the mis-operation

                             It is able to operate the controller with using                                                       prevention etc.

                             this cover.

● E5CC-U Wiring Socket

Front-connecting Socket

P2CF-11

                             Eleven, M3.5 × 7.5                           3                 4.5        Terminal  Layout/Internal Connections

                             sems screws                    7.8                                                      (Top View)

                                                                                                                     8   7   6  5                    Mounting Holes

                                                                                                                                   4

                                                                                                                                                     Two, 4.5 dia. mounting holes

                             70 max.                                                        35.4

                                                            Two,                                                                                            40±0.2

                                                            4.5-dia.                                                 9             3

                                                            holes                                                    10  11  1  2                   Note: Can also be mounted

                                                                                                                                                     to a DIN track

                                 4            50 max.                         31.2 max.

Note: 1.  A model with finger protection (P2CF-11-E) is also available.

2.        You cannot use the P2CF-11 or P2CF-11-E together with the                         Y92F-45.

Back-connecting Socket

P3GA-11

                                                                                                       Eleven, M3.5  Terminal Layout/Internal Connections

                                          27dia.                                         4       7  3  sems screws                    (Bottom View)

                                                                                                                                      5  6  7   8

                                                                                                                                      4

                             45                                               25.6

                                                                                                                                      3         9

                                                                                                                                      2  1  11  10

                                          45                4.5 16.3 6.2

                                                                                                                 6

                                                                                    8.7

Note: 1.  Using any other sockets will adversely affect accuracy. Use only the specified sockets.

2.        A Protective Cover for finger protection (Y92A-48G) is also available.

3.        You cannot use the P3GA-11 together with the Y92F-45.

                                                                                                                                                                                   1
    E5CC/E5CC-U/E5EC/E5AC/E5DC

Operation

Setting Levels Diagram

This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords.                                    Some

parameters are not displayed depending on the protect level setting and the conditions of use.

Control stops when you move from the operation level to the initial setting level.

                                                                                                                Press the O + M Keys for           Protect Level

                                               Only when Manual Mode   was used                                 at least 1 s

                                               just before power OFF                                                                      Used to set protection

                                                                                    Power  ON                                             for operations.

    Operation in progress                      Press the O Key                                                                                        Press the O + M

                                               for at least 1 s or     Level changes

                                               the S Key for at        automatically.                                                                 Keys for at least 3  s.*2

                                               least 1 s

                           Manual Control                                                                       Press the O Key once.     Adjustment Level

                           Level                                                Operation Level

                                                                                                                                          Used to change adjustment

                           Used to set the MV                               Used for SP, alarm                  Press the O Key once.     parameters (PID constants,

                           manually.           O Key for at                 values, and other basic                                       adjustment sensitivity, etc.).

                                               least 3 s while              settings and monitoring.

                                               a-m is
                                               displayed.*2

                                                                                                                Press the S Key.          Press the S Key.*3

                                      S Key for at least 1 s*1

                                                       Press the O     Key for                    Press the O Key                 Monitor/Setting

                                                       at least 3 s*2                             for at least 1 s.               Item Level

                                                                                                                                  Used to display

                                                                                                                                  specified monitor

                                                                                                                                  and setting items.

                                                                                                                Press O Key once                      Communications

                                                                            Initial Setting Level               (models with communications only).

                                                                                                                                                      Setting Level

                                                                            Used to set the input type                                                Used to set up

                                                                            and other basic settings.           Press the O Key once.                 communications.

                                               Release protection and

                                               then enter the password

    Stopped                                    (−169) for the amoV (Move                          Press the O Key for at least 1 s.

                                               to Advanced Setting

                                               Level) parameter.

                                                                            Advanced Function

                                                                                   Setting Level

                                                                            Used to set application functions.

                                                                Enter the password

                                                                (1201) for the Move to

                                                                Calibration Level

                                                                parameter.

                                                                            Calibration Level

*1  To use a key procedure to move to Manual Control Level, set the Auto/Manual Select Addition parameter to ON and set the                                                PF    Setting

    parameter to a-m (Auto/Manual).

*2  The No. 1 display will flash when the keys are pressed for 1 s or longer.

*3  Set the PF Setting parameter to pfdp (monitor/setting items).


                                                                                    E5CC/E5CC-U/E5EC/E5AC/E5DC

Error Displays (Troubleshooting)

When an error occurs, the No. 1 display or No. 2 display shows the error code.

Take necessary measure according to the error code, referring the following table.

Display       Name                       Meaning                                    Action                                      Operation

                                                                                                                 After the error occurs and it is

                        The input value exceeded the control        Check the wiring for input to be sure        displayed, the alarm output will

                        range.*                                     it is wired correctly, not broken, and       operate as if the upper limit was

                        The input type is not set correctly.        not shorted. Also check the input            exceeded.

                        The sensor is disconnected or short-        type.                                        It will also operate as if transfer

                        circuited.                                  If there are no problems in the wiring       output exceeded the upper limit.

                        The sensor is not wired correctly.          or input type settings, cycle the            If an input error is assigned to a

                        The sensor is not wired.                    power supply.                                control output or auxiliary output, the

                                                                    If the display remains the same,             output will turn ON when the input

s.err                   *  Control Range                            replace the Digital Temperature              error occurs.

         Input error    Temperature resistance                      Controller.                                  The error message will appear in the

                        thermometer or thermocouple input:          If the display is restored to normal,        display for the PV.

                           SP Lower Limit - 20°C to SP Upper        then the probable cause is external

                           Limit + 20°C                             noise affecting the control system.          Note: 1.  The heating and cooling

                           (SP Lower Limit - 40°F to SP Upper       Check for external noise.                              control outputs will turn

                           Limit + 40°F)                                                                                   OFF.

                        ESIB input:                                 Note: For a temperature resistance           2.        When the manual MV, MV

                           Same as specified input range.                       thermometer, the input is                  at stop, or MV at error is

                        Analog input:                                           considered disconnected if                 set, the control output is

                           Scaling range -5% to 105%                            the A, B, or B’ line is broken.            determined by the set

                                                                                                                           value.

                                          This is not an error. It

[[[[                                      is displayed when the                                                  Control continues and operation is

                        Below -1,999      control range is wider                                                 normal.

                                          than the display                                                       The value will appear in the display

         Display                          range and the PV                                                       for the PV.

         range                            exceeds the display                       -                            Refer to the E5@C Digital

         exceeded                         range. The PV is                                                       Temperature Controllers User’s

                                          displayed for the                                                      Manual (Cat. No. H174) for

]]]]                    Above 9,999       range that is given on                                                 information on the

                                          the left (the number                                                   controllable range.

                                          without the decimal

                                          point).

                                                                    First, cycle the power supply.

                                                                    If the display remains the same, the         The control outputs, auxiliary

e333     A/D            There is an error in the internal           controller must be repaired.                 outputs, and transfer outputs turn

         converter      circuits.                                   If the display is restored to normal,        OFF. (A current output will be approx.

         error                                                      then a probable cause can be                 0 mA and a linear voltage output will

                                                                    external noise affecting the control         be approx. 0V.)

                                                                    system. Check for external noise.

                                                                    First, cycle the power supply.

                                                                    If the display remains the same, the         The control outputs, auxiliary

e111     Memory         There is an error in the internal           controller must be repaired.                 outputs, and transfer outputs turn

         error          memory operation.                           If the display is restored to normal,        OFF. (A current output will be approx.

                                                                    then a probable cause can be                 0 mA and a linear voltage output will

                                                                    external noise affecting the control         be approx. 0V.)

                                                                    system. Check for external noise.

                                                                                                                 Control continues and operation is

                                                                                                                 normal.

                                                                                                                 The error message will appear forthe

ffff     Overcurrent    This error is displayed when the peak                       -                            following displays.

                        current exceeds 55.0 A.                                                                  Heater Current Value 1 Monitor

                                                                                                                 Heater Current Value 2 Monitor

                                                                                                                 Leakage Current Value 1 Monitor

                                                                                                                 Leakage Current Value 2 Monitor

                                                                                                                 The No. 1 display for the following

ct1                                                                                                              parameter flashes in Operation Level

                                                                                                                 or Adjustment Level.

ct2      HB or HS       If there is a HB or HS alarm, the No.                                                    Heater Current Value 1 Monitor

lcr1     alarm          1 display will flash in the relevant                        -                            Heater Current Value 2 Monitor

                        setting level.                                                                           Leakage Current Value 1 Monitor

lcr2                                                                                                             Leakage Current Value 2 Monitor

                                                                                                                 However, control continues and

                                                                                                                 operation is normal.

                        "----" will be displayed for the Valve

                        Opening Monitor parameter if any of

                        the following error occurs.
                        • Motor calibration has not been
         Potentiometer                                                                                           Close control: The control output is
                           performed.
         Input Error                                                                                             OFF or the value that is set for the
----                    • The wiring of the potentiometer is
         (Position-                                                 Check for the above errors.                  MV at PV Error parameter is output.
                           incorrect or broken.
         proportional                                                                                            Floating control: Operation will be

         Models Only)   • The potentiometer input value is                                                       normal.

                           incorrect (e.g., the input is out of

                           range or the potentiometer has

                           failed).

                                                                                                                                                          1
    E5CC/E5CC-U/E5EC/E5AC/E5DC

Operation

Parameters

The following pages describe the parameters set in each level. Pressing the M (Mode) Key at the last parameter in each level returns to the top

parameter in that level. Some parameters may not be displayed depending on the model and other settings.

                                                                                                                    Power ON                                                                                                                                  Press the S Key*2

                                                                                    Starting  in  Manual Mode.                                                                                       Press the O Key for at least 3 s.                                                       Press         the   S Key*2

                                                                                                     Manual Control Level                                                 Starting in                Other than the Auto/Manual Switch display

                                                                                                                                                                          Automatic                                                                           Initial Setting Level

                                 Press the S Key                                                                               Press the O                                Mode.

                                 for at least 1 s.                                                C       25  PID              Key or the S                                                                                                    Press the            Press the O Key for less than 1 s.

                                                                                                          0   Control          Key for at least                                                                                                O Key for

                                                     *1                                                       only             1 s.

                                                                                                  PV/MV                                              *1                                                                                        at least 1 s.        in-t Input Type

    Adjustment                   Press the O Key less than 1      s.                                                                                                                                                                                                           5

    Level                                                                                                                                   Operation Level                                                                                                                   M

                                 Press the O Key less than        1 s.                                                                                                                                                                                              in-h            Scaling Upper Limit

           Adjustment Level                                                                                                                                                                                                                                                   100

           Display                                                                                                                                                                                                                                                            M

           Displayed only                                                                                           25         Process Value/                             al1h              Alarm Value                                                             in-l

    l.adj  once when                                                                                                        0  Set Point 1                                               0  Upper Limit                                                                             Scaling Lower Limit

           entering              ins    Process Value Input           orl    MV Change Rate                                                                                                 1                                                                                  0

           adjustment level.     0.0    Shift                           0    Limit                                       M                                                       M                                                                                            M

    M                            M                                      M                                           25         Process Value/                             al1l              Alarm Value                                                                             Decimal Point

                                                                                                                            0  Set Point 2                                               0  Lower Limit                                                                       dp

    at     AT Execute/Cancel     inrt   Process Value Slope             db   Position                                                                                                       1                                                                                  0    For input type of analog

    off                          1.000  Coefficient                     2.0  Proportional                                M                                                       M                            Set either of these parameters.                                 M

                                 M                                           Dead Band                              a-m        Auto/Manual Switch                         al-2              Alarm

    M                                                                   M                                                      PID control only.                                            Value 2                                                                       d-u       Temperature Unit

           Communications        rss                                                                                           Added when                                                0                                                                                          °C, °F

    cmwt   Writing                      Remote SP Input Shift     oc-h       Open/Close           Press the              M auto/manual select                                                                                                                                  c             For input type of

    off                          0.0                                         Hysteresis           O Key                        addition is ON.                                   M                                                                                            M              temperature

                                                                        0.8                       for at      m-sp             Multi-SP Set                                                 Alarm Value

    M                            M                                      M                         least 3 s.                0  Point Selection                            al2h              Upper Limit                                                             sl-h            SP Upper Limit

    spmd   SP Mode               rsrt   Remote SP Input                      Extraction of                                                                                               0  2                                                                                 1300

    lsp                          1.000  Slope Coefficient         sqrp       Square Root                                 M                                                       M                                                                                            M

                                                                        0    Low-cut Point                          rsp        Remote SP Monitor                          al2l              Alarm Value                                                                                     Limit the set point

    M                            M                                      M                                                0.0                                                             0  Lower Limit                                                             sl-l            SP Lower Limit

                                 p      Proportional Band                                                                                                                                   2                                                                                 -200

    ct1    Heater Current 1                                       w1on       Work Bit 1                                  M                                                       M

    0.0    Value Monitor         8.0                                         ON Delay                                                                                                                         Set either of these parameters.                                 M

                                 M                                                                            sp-m             Set Point During                           al-3              Alarm

    M                                                                   M                                                   0  SP Ramp                                                   0  Value 3                                                                 cntl            PID ON/OFF

    hb1    Heater Burnout        i      Integral Time                                                                                                                                                                                                                         onof

           Detection 1           233                              w1of       Work Bit 1                                  M                                                       M                                                                                            M

    0.0                                                                      OFF Delay                        ct-1             Heater Current     1  Value                                  Alarm Value

    M                            M                PID settings                                                                 Monitor                                    al3h              Upper Limit                                                             s-hc            Standard or

                                 d      Derivative Time                 M                                                0.0                                                             0  3                                                                                 stnd  Heating/Cooling

    ct2    Heater Current 2                                       w2on       Work Bit 2                                  M                                                       M

    0.0    Value Monitor         40                                                                                                                                                                                                                                           M

                                 M                                           ON Delay                         ct-2             Heater Current     2  Value                al3l              Alarm Value

    M                                                                   M                                                      Monitor                                                      Lower Limit                                                                       st    ST (Self-tuning)

                                                                                                                         0.0                                                             0  3                                                                                       For input type of

    hb2    Heater Burnout        c-p    Proportional Band                                                                                                                                                                                                                     on    temperature, standard

           Detection 2           8.0    (Cooling)                 w2of       Work Bit 2                                  M                                                       M                            Set either of these parameters.                                 M     control, or PID

    0.0                                                                      OFF Delay                        lcr1             Leakage Current 1                                            Alarm

    M                            M                                      M                                                      Monitor                                    al-4              Value 4                                                                 ptrn            Program Pattern

                                                                                                                         0.0                                                             0                                                                                    off

    lcr1   Leakage Current    1  c-i    Integral Time             w3on                                                   M                                                       M                                                                                                  When assigning PID or

    0.0    Monitor               233    (Cooling)                            Work Bit 3                                                                                                                                                                                       M     control output to ON/OFF

                                                                             ON Delay                         lcr2             Leakage Current 2                          al4h              Alarm Value                                                                             output

    M                            M                                      M                                                0.0   Monitor                                                   0  Upper Limit                                                                       cp

           HS Alarm 1            c-d                                                                                                                                                        4                                                                                       Control Period (Heating)

    hs1                                 Derivative Time           w3of       Work Bit 3                                  M                                                       M                                                                                            20            Set the ON/OFF

    50.0                         40     (Cooling)                            OFF Delay                                                                                                                                                                                        M             output cycle.

    M                            M                                                                            prst             Program Start                              al4l              Alarm Value

                                                                        M                                           rset                                                                 0  Lower Limit                                                             c-cp            Control Period (Cooling)

    lcr2   Leakage Current    2                                                                                                                                                             4

           Monitor               c-db   Dead Band                 w4on       Work Bit 4                                  M                                                       M                                                                                            20

    0.0                          0.0                                         ON Delay                         sktr             Soak Time Remain                                                                                                                               M

    M                                                                                                                                                                                    o  MV Monitor

                                 M                                      M                                                   0                                                    0.0        (Heating)                                                               orev Direct/Reverse Operation

    hs2    HS Alarm 2            of-r   Manual Reset Value                                                               M                                                       M                                                                                            or-r

    50.0                                Clear the offset during   w4of       Work Bit 4

                                 50.0   stabilization of P or PD             OFF Delay                              r-s        RUN/STOP                                   c-o               MV Monitor                                                                        M

    M                            M      control.                                                                         run                                                                (Cooling)

                                                                        M                                                                                                        0.0                                                                                alt1 Alarm 1 Type

    sp-0   SP 0                  hys    Hysteresis (Heating)                                                             M                                                       M                                                                                             2

       0                         1.0                              w5on       Work Bit 5                       al-1             Alarm

                                                                             ON Delay                                          Value 1      Set either of                 v-m               Valve Opening                                                                     M

    M                            M      Hysteresis settings                                                                 0               these                                0.0        Monitor                                                                 alh1            Alarm 1

    sp-1   SP 1                  chys   Hysteresis (Cooling)            M                                                M                  parameters.                          M                                                                                            0.2   Hysteresis

       0                         1.0                              w5of       Work Bit 5                                                                                                                                                                                       M

    M                                                                        OFF Delay

                                 M                                      M                                 Press the O and M Keys for                                  Press the O and M Keys                   Press the O Key

    sp-2   SP 2                  soak   Soak Time                                                         at least 3 s.                                               for at least 1 s.                        less than 1 s.

       0                         1                                w6on       Work Bit 6                                                                                          Communications

    M                                                                        ON Delay                                       Protect Level                                        Setting Level

                                 M                                      M

    sp-3   SP 3                  wt-b   Wait Band                                                             The time taken to move to the protect level                        Displayed only for models with                                               * Used with programless communications

       0                                                          w6of       Work Bit 6                       can be adjusted by changing the "Move to                           communications. Changes are

                                 off                                         OFF Delay                        protect level time" setting.                                       effective after cycling power or

    M                                                                                                         pmov                                                               after a software reset.                                                                                                Upload

                                                                        M                                                   Move to Protect Level:                                                                                                                                          up     1

    sp-4   SP 4                  mv-s   MV at Stop                                                                       0  Displayed only when a                                                                                                                                                   0   Setting 1

                                                                  w7on                                        M             password is set. Restricts                           psel               Protocol Setting:                          maxu                 Highest

       0                         0.0                                         Work Bit 7                                     moving to protect level.                                                Switches between                                                Communications               M

    M                                                                        ON Delay                                                                                                          cwf  CompoWay/F and                                            0     Unit No.

                                 M                                                                                          Operation/Adjustment Protect:                                      M    Modbus.                                                   M *3                          up13        Upload

    sp-5                         mv-e   MV at PV Error                  M                                     oapt0         Restricts displaying and                                                                                                                                                0   Setting 13

           SP 5                                                                                                             modifying menus in operation,                        u-no               Communications                             area                 Area

       0                         0.0                              w7of       Work Bit 7                                     adjustment, and manual                                                  Unit No.                                                                                     M

    M                            M                                           OFF Delay                              M control levels.                                                          1                                                              0                                         Download

                                                                        M                                     icpt          Initial Setting/Communications Protect:                            M                                                              M                             dn     1    Setting 1

    sp-6   SP 6                  sprt   SP Ramp Set Value                                                                   This protect level restricts movement to                                                                                                                                0

                                                                  w8on                                                   1  the initial setting, communications setting,                 bps        Communications                             adrh                 First Address

       0                         off                                         Work Bit 8                             M and advanced function setting levels.                                         Baud Rate                                                       Upper Word                   M

    M                            M                                           ON Delay                                                                                                          9.6  CompoWay/F                                                0                             dn13        Download

                                                                        M                                     wtptoff       Setting Change Protect:                                            M    only                                                      M                                         Setting 13

    sp-7   SP 7                  sprl   SP Ramp Fall Value                                                                  Protects changes to setups by                                                                                                                                       1000

                                                                  w8of                                                      operating the front panel keys.                              len        Communications                             adrl                 First Address                M

       0                         same                                        Work Bit 8                             M                                                                               Data Length                                                     Lower Word

    M                            M                                           OFF Delay                                                                                                         7                                                              0                             copy           Copy

                                                                        M                                     pfpt PF Key Protect                                                              M                                                              M                                  off       *3

                                 ol-h   MV Upper Limit                                                              off                                                                             Communications                                                  Receive Data

                                 100.0                            plcm       Communications                         M                                                            sbit               Stop Bits                                  rwat                 Wait Time

                                                                      1234   Monitor                          chgp Changed Parameters Only                                                     2                                                              1000  *3                       sps        SP Slope

                                 M                                      M                                           off                                                                        M                                                              M                                 1.000      *3

                                 ol-l   MV Lower Limit                                                              M                                                            prty               Communications                             unit                 Communications               M

                                 0.0                                                                                                                                                        even    Parity                                                          Node Number

                                                                                                              pmsk Parameter Mask Enable:                                                                                                                     0                             spos           SP Offset

                                 M                                                                                  on      Displayed only when a                                              M                                                              M                                    0.0     *3

                                                                                                                            parameter mask is set.

                                                                                                                    M                                                            sdwt               Send Data Wait                                                                               M

                                                                                                              prlp          Password to Move to                                                20   Time

                                                                                                                         0  Protect Level:                                                     M                                               *1. When the PF Setting parameter is set to A-M.

                                                                                                                            Password setting                                                                                                   *2. When the PF Setting parameter is set to PFDP.

                                                                                                                    M                                                                                                                          *3. Used with component communications.


                                                                                                                                  E5CC/E5CC-U/E5EC/E5AC/E5DC

                    Monitor/Setting Item Level

                                25    Monitor/Setting  S                Monitor/Setting        S            Monitor/Setting          S                                       Monitor/Setting  S                 Monitor/Setting

                                      Item Display 1                    Item Display 2                      Item Display 3                                                   Item Display 4                     Item Display 5

                                   0

                           Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).

                           Press the O Key

                           for at least 1 s.

                                                       Advanced Function Setting Level

alt2   Alarm 2 Type

2

M                                                                                                                                                                        RT

alh2   Alarm 2                                            init       Parameter Initialization     ret       Automatic Display           rt                                                    sptr     SP Tracking

       Hysteresis                                         off                                     off       Return Time                 off                                                      off

0.2

M                                                         M                                       M                                     M                                                        M

alt3                                                      mspu       Number of Multi-SP           brgt      Display Brightness          hsu                              HS Alarm Use         p-db     PV Dead Band

       Alarm 3 Type                                       off        Points                       3                                                                 on                           0

2

M                                                         M                                       M                                     M                                                        M

alh3                                                      spru       SP Ramp Time Unit            a1lt      Alarm 1 Latch               hsl                              HS Alarm Latch       manl     Manual MV

       Alarm 3                                            m                                       off                                   off                                                      off   Limit Enable

0.2    Hysteresis

M                                                         M                                       M                                     M                                                        M

alt4                                                      rest       Standby Sequence             a2lt      Alarm 2 Latch               hsh                              HS Alarm Hysteresis  pmvd     Direct Setting of

       Alarm 4 Type                                       a          Reset                        off                                                               0.1                          off   Position Proportional

2                                                                                                                                                                                                      MV

M                                                         M                                       M                                     M                                                        M

alh4   Alarm 4                                            sb1n       Auxiliary Output 1           a3lt      Alarm 3 Latch               lba                              LBA Detection Time   pvrp     PV Rate of Change

       Hysteresis                                         n-o        Open in Alarm                off                                                               0                            20    Calculation Period

0.2

M                                                         M                                       M                                     M                                                        M

o1st                                                      sb2n       Auxiliary Output 2           a4lt      Alarm 4 Latch               lbal                             LBA Level            hctm     Heating/Cooling

       Control Output   1  Signal                         n-o        Open in Alarm                off                                                               8.0                          off   Tuning Method

4-20                                                                                                                                    M

M                                                         M                                       M                                                                                              M

                                                          sb3n       Auxiliary Output 3           prlt      Move to Protect Level       lbab                             LBA Band             ompw     Minimum Output

o2st   Control Output 2 Signal                            n-o        Open in Alarm                3         Time                                                    3.0                          1.0   ON/OFF Band

4-20                                                                                                                                    M

M                                                         M          Auxiliary Output 4           M                                                                                              M

trst                                                      sb4n       Open in Alarm                cjc       Cold Junction               out1                             Control Output 1        pf    PF  Setting

       Transfer Output Signal                             n-o                                               Compensation                                            o    Assignment              shft

4-20                                                                 (E5EC/E5AC only)             on        Method

M                                                         M                                       M                                     M                                                        M

                                                          hbu        HB ON/OFF                    a1on      Alarm 1 ON Delay            out2                             Control Output 2     pfd1     Monitor/Setting Item 1

tr-t   Transfer Output Type                               on                                      0                                     none                             Assignment

                                                                                                                                                                                                 1

off                                                                                               M                                     M                                                        M

M               Linear output                             M

tr-h   Transfer Output                                    hbl        Heater Burnout Latch         a2on      Alarm 2 ON Delay            sub1                             Auxiliary Output  1  pfd2     Monitor/Setting Item 2

       Upper Limit                                        off                                     0                                     alm1                             Assignment              0

100.0

M                                                         M                                       M                                     M                                                        M

                                                          hbh        Heater Burnout               a3on      Alarm 3 ON Delay            sub2                             Auxiliary Output  2  pfd3     Monitor/Setting Item 3

tr-l   Transfer Output                                               Hysteresis                                                                                          Assignment              0

0.0    Lower Limit                                        0.1                                     0                                     alm2

M                                                         M                                       M                                     M                                                        M

                                                          st-b       ST Stable Range              a4on      Alarm 4 ON Delay            sub3                             Auxiliary Output  3  pfd4     Monitor/Setting Item 4

ev-1   Event Input                                                                                0                                     alm3                             Assignment              0

msp0   Assignment 1                                       15.0

M                                                         M                                       M                                     M                                                        M

ev-2   Event Input                                        alfa       α                            a1of      Alarm 1 OFF Delay           sub4                             Auxiliary Output 4   pfd5     Monitor/Setting Item 5

       Assignment 2                                       0.65                                    0                                     alm4                             Assignment              0

stop                                                                                                                                                                     (E5EC/E5AC only)

M                                                         M                                       M                                     M                                                        M

ev-3                                                      tidu       Integral/Derivative          a2of      Alarm 2 OFF Delay           alma                             Integrated Alarm     spd1     PV/SP No. 1 Display

       Event Input                                        1          Time Unit                    0                                                                 49   Assignment              4     Selection

none   Assignment 3

M                                                         M                                       M                                     M                                                        M

       Event Input                                        at-g       AT Calculated Gain           a3of      Alarm 3 OFF Delay           t-u                              Soak Time Unit       spd2     PV/SP No. 2 Display

ev-4   Assignment 4                                       0.8                                     0                                                                 m                            0     Selection

none                                                                                                                                    M                                                        M

M                                                         M                                       M

                                                          at-h       AT Hysteresis                a4of      Alarm 4 OFF Delay           alsp                             Alarm SP Selection   odsl     MV Display Selection

ev-5   Event Input                                        0.8                                     0                                     sp-m                                                     o

none   Assignment 5

M      (E5EC/E5AC only)                                   M                                       M                                     M                                                        M

       Event Input                                        lcma       Limit Cycle MV               mvse      MV at Stop and Error        rs-t                             Remote SP Input      pvdp     PV Decimal Point

ev-6   Assignment 6                                       20.0       Amplitude                    off       Addition                    4-20                                                     on    Display

none   (E5EC/E5AC only)                                                                           M

M                                                         M                                                                             M                                                        M

clfl   Close/Floating                                     inf        Input Digital Filter         amad      Auto/Manual Select          rspu                             Remote SP Enable     pvst     PV Status Display

                                                          0.0                                     off       Addition                    off                                                      off   Function

flot

M                                                         M                                       M                                     M                                                        M

calb   Motor Calibration                                  mav        Moving Average Count         mant      Manual Output Method        rsph                             Remote SP            svst     SV Status Display

off                                                       off                                     hold                                  1300                             Upper Limit             off   Function

M                                                         M                                       M                                     M                                                        M

mot    Travel Time                                        o-dM ofpf  MV Display                   manM0i.0  Manual MV Initial Value     rspl                             Remote SP            d.ref    Display Refresh

                                                                                                                                        -200                             Lower Limit             0.25  Period

30

M                                                         M                                       M                                     M                                                        M

sqr    Extraction of Square                                                                                                                                                                   lcmt     LCT Cooling Output

       Root Enable                                                                                                                                                                               0.2   Minimum ON Time

off                                                                                                                                                                                                    (E5DC only)

M                                                                                                                                                                                                M

amov0  Move to Advanced Function                                                                                                                                                              cmov     Move to Calibration

       Setting Level:                                                                                                                                                                                  Level

       Displayed when initial                                                                                                                                                                    0

       setting/communications                                                                                                                                                                    M
Mprotect is set to 0.

Move by setting password (−169).

                                                                                                                                                                                                                                 
    E5CC/E5CC-U/E5EC/E5AC/E5DC

Safety Precautions

●   Be sure to read the precautions for all E5CC/E5EC/E5AC/E5DC models in the website at:

    http://www.ia.omron.com/.

Warning Indications                                                 Minor electric shock or fire may occasionally occur.

                     Indicates a potentially hazardous              Do not use any cables that are damaged.

           CAUTION   situation which, if not avoided, may

                     result in minor or moderate injury or in

                     property damage.                               Never disassemble, modify, or repair the product or

    Precautions for  Supplementary comments on what to              touch any of the internal parts. Minor electric shock,

    Safe Use         do or avoid doing, to use the product          fire, or malfunction may occasionally occur.

                     safely.                                        CAUTION - Risk of Fire and Electric Shock

    Precautions for  Supplementary comments on what to              a.   This product is UL listed*1 as Open Type Process

                     do or avoid doing, to prevent failure to            Control Equipment. It must be mounted in an

    Correct Use      operate, malfunction or undesirable                 enclosure that does not allow fire to escape

                     effect on product performance.                      externally.

Meaning of Product Safety Symbols                                   b. More than one disconnect switch may be required to de-

                                                                         energize the equipment before servicing the product.

                                                                    c.   Signal inputs are SELV, limited energy. *2

           Used to warn of the risk of electric shock under         d. Caution: To reduce the risk of fire or electric shock, do not

           specific conditions.                                          interconnect the outputs of different Class 2 circuits. *3

                                                                    If the output relays are used past their life expectancy,

                                                                    contact fusing or burning may occasionally occur.

           Used for general prohibitions for which there is no      Always consider the application conditions and use

           specific symbol.                                         the output relays within their rated load and electrical

                                                                    life expectancy. The life expectancy of output relays varies

           Used to indicate prohibition when there is a risk of     considerably with the output load and switching conditions.

           minor injury from electrical shock or other source       Even if you replace only the Main Unit of the E5DC, check

           if the product is disassembled.                          the condition of the Terminal Unit.

           Used for general CAUTION, WARNING, or                    If corroded terminals are used, contact failure in the

           DANGER precautions for which there is no                 terminals may cause the temperature inside the

           specified symbol. (This symbol is also used as the       Digital Controller to increase, possibly resulting in fire.

           alerting symbol, but shall not be used in this           If the terminals are corroded, replace the Terminal Unit as well.

           meaning on the product.)

                                                                    Tighten the terminal screws to the rated torque of

           Used for general mandatory action precautions            between 0.43 and 0.58 N•m. *4

           for which there is no specified symbol.                  Loose screws may occasionally result in fire.

                                                                    Set the parameters of the product so that they are

                            CAUTION                                 suitable for the system being controlled. If they are

                                                                    not suitable, unexpected operation may occasionally

Do not touch the terminals while power is being                     result in property damage or accidents.

supplied.

Doing so may occasionally result in minor injury due                A malfunction in the product may occasionally make

to electric shock.                                                  control operations impossible or prevent alarm

                                                                    outputs, resulting in property damage.

Electric shock may occur. Do not touch any cables or                To maintain safety in the event of malfunction of the

connectors with wet hands.                                          product, take appropriate safety measures, such as installing                       a

                                                                    monitoring device on a separate line.

Electric shock, fire, or malfunction may occasionally               *1.  E5CC, E5EC, E5AC, and E5DC Controllers that were shipped through

occur. Do not allow metal objects, conductors,                           November 2013 are UL recognized.

cuttings from installation work, or moisture to enter               *2.  An SELV (separated extra-low voltage) system is one with a

the Digital Temperature Controller or the Setup Tool                     power supply that has double or reinforced insulationbetween the

                                                                         primary and the secondary circuits and has an output voltage of

port or ports. Attach the cover to the front-panel Setup Tool port       30 V r.m.s. max. and 42.4 V peak max. or 60 VDC max.

whenever you are not using it to prevent foreign objects from       *3.  A class 2 circuit is one tested and certified by UL as having the current and

entering the port.                                                       voltage of the secondary output restricted to specific levels.

                                                                    *4.  The specified torque is 0.5 N·m for the E5CC-U.

Do not use the Digital Temperature Controller where

subject to flammable or explosive gas. Otherwise,

minor injury from explosion may occasionally occur.

Not doing so may occasionally result in fire. Do not

allow dirt or other foreign objects to enter the Setup

Tool port or ports, or between the pins on the

connectors on the Setup Tool cable.


                                                                                   E5CC/E5CC-U/E5EC/E5AC/E5DC

                   Precautions for Safe Use

Be sure to observe the following precautions to prevent malfunction         power to the load, self-tuning will not be performed properly and

or adverse affects on the performance or functionality of the product.      optimum control will not be achieved.

Not doing so may occasionally result in faulty operation.                   13.A switch or circuit breaker must be provided close to the product.

1.  This product is specifically designed for indoor use only.              The switch or circuit breaker must be within easy reach of the

    Do not use this product in the following places:                        operator, and must be marked as a disconnecting means for this

    •  Places directly subject to heat radiated from heating equipment.     unit.

    •  Places subject to splashing liquid or oil atmosphere.                14.Use a soft and dry cloth to clean the product carefully. Do not use

    •  Places subject to direct sunlight.                                   organic solvent, such as paint thinner, benzine or alcohol to clean

    •  Places subject to dust or corrosive gas (in particular, sulfide gas  the product.

       and ammonia gas).                                                    15.Design the system (e.g., control panel) considering the 2 seconds

    •                                                                       of delay that the product's output to be set after power ON.

       Places subject to intense temperature change.                        16.The output may turn OFFwhen you move to the initial setting level.

    •  Places subject to icing and condensation.                            Take this into consideration when performing control operations.

    •  Places subject to vibration and large shocks.                        17.The number of non-volatile memory write operations is limited.

2.  Use and store the product within the rated ambient temperature          Therefore, use RAM write mode when frequently overwriting data

    and humidity.                                                           during communications or other operations.

    Gang-mounting two or more Digital Temperature Controllers, or           18.Use suitable tools when taking the Digital Temperature

    mounting Digital Temperature Controllers above each other may           Temperature Controller apart for disposal. Sharp parts inside the

    cause heat to build up inside the Digital Temperature Controllers,      Digital Temperature Controller may cause injury.

    which will shorten their service life. In such a case, use forced       19.For compliance with Lloyd’s standards, the E5CC, E5CC-U,

    cooling by fans or other means of air ventilation to cool down the      E5EC, and E5AC must be installed under the conditions that are

    Digital Temperature Controllers.                                        specified in Shipping Standards.

3.  To allow heat to escape, do not block the area around the Digital       20.Do not connect cables to both the front Setup Tool port and the

    Temperature Controller.                                                 top-panel or bottom-panel Setup Tool port at the same time. The

    Do not block the ventilation holes on the Digital Temperature           Digital Controller may be damaged or may malfunction.

    Controller.                                                             21.Do not place heavy object on the Conversion Cable, bend the

4.  Be sure to wire properly with correct polarity of terminals.            cable past its natural bending radius, or pull on the cable with

5.  Use the specified size of crimped terminals (M3, width of 5.8 mm        undue force.

    or less) to wire the E5CC, E5EC, E5AC, or E5DC. To connect bare         22.Do not disconnect the Communications Conversion Cable or the

    wires to the terminal block of the E5CC, E5EC, E5AC, or E5DC,           USB-Serial Conversion Cable while communications are in

    use copper braided or solid wires with a gage of AWG24 to               progress. Damage or malfunction may occur.

    AWG18 (equal to a cross-sectional area of 0.205 to 0.8231 mm2).         23.Do not touch the external power supply terminals or other metal

    (The stripping length is 6 to 8 mm.) Up to two wires of the same        parts on the Digital Temperature Controller.

    size and type, or two crimped terminals can be inserted into a          24.Refer to the E5@C Digital Temperature Controllers User’s Manual

    single terminal.                                                        (Cat. No. H174) for information on the communications distances

    Use the specified size of crimped terminals (M3.5, width of 7.2 mm      and cables for the E5@C.

    or less) to wire the E5CC-U. To connect bare wires to the terminal      25.Do not bend the communications cables past their natural bending

    block of the E5CC-U, use copper braided or solid wires with a           radius. Do not pull on the communications cables.

    gage of AWG24 to AWG14 (equal to a cross-sectional area of              26.Do not turn the power supply tothe Digital Temperature Controller

    0.205 to 2.081 mm2). (The stripping length is 5 to 6 mm.)Up to two      ON or OFF while the USB-Serial Conversion Cable is connected.

    wires of the same size and type, or two crimped terminals can be        The Digital Temperature Controller may malfunction.

    inserted into a single terminal.                                        27.Make sure that the indicators on the USB-Serial Conversion Cable

6.  Do not wire the terminals that are not used.                            are operating properly. Depending on the application conditions,

7.  Use a commercial power supply for the power supply voltage input        deterioration in the connectors and cable may be accelerated, and

    to a Digital Temperature Controller with AC input specifications.       normal communications may become impossible. Perform

    Do not use the output from an inverter as the power supply.             periodic inspection and replacement.

    Depending on the output characteristics of the inverter,                28.Connectors may be damaged if they are inserted with excessive

    temperature increases in the Digital Temperature Controller may         force. When connecting a connector, always make sure that it is

    cause smoke or fire damage even if the inverter has a specified         oriented correctly. Do not force the connector if it does not connect

    output frequency of 50/60 Hz.                                           smoothly.

8.  To avoid inductive noise, keep thewiring for the product’s terminal     29.Noise may enter on the USB-Serial Conversion Cable, possibly

    block away from power cables carry high voltages or large               causing equipment malfunctions. Do not leave the USB-Serial

    currents. Also, do not wire power lines together with or parallel to    Conversion Cable connected constantly to the equipment.

    product wiring. Using shielded cables and using separate conduits       30.For the E5DC, when you attach the Main Unit to the Terminal Unit,

    or ducts is recommended.                                                make sure that the hooks on the Main Unit are securely inserted

    Attach a surge suppressor or noise filter to peripheral devices that    into the Terminal Unit.

    generate noise (in particular, motors, transformers, solenoids,         31.For the E5CC-U, when you attach the Main Unit to the socket,

    magnetic coils, or other equipment that have an inductance              make sure that the hooks on the socket are securely inserted into

    component).                                                             the Main Unit.

    When a noise filter is used at the power supply, first check the        32.Install the DIN Track vertically to the ground.

    voltage or current, and attach the noise filter as close as possible    33.For the E5DC, always turn OFF the power supply before

    to the product.                                                         connecting the Main Unit to or disconnecting the Main Unit from

    Allow as much space as possible between the product and                 the Terminal Unit, and never touch nor apply shock to the

    devices that generate powerful high frequencies (high-frequency         terminals or electronic components. When connecting or

    welders, high-frequency sewing machines, etc.) or surge.                disconnecting the Main Unit, do not allow the electronic

9.  Use this product within the rated load and power supply.                components to touch the case.

10.Make sure that the rated voltage is attained within two seconds of

    turning ON the power using a switch or relay contact. If the voltage

    is applied gradually, the power may not be reset or output

    malfunctions may occur.

11.Make sure that the Digital Temperature Controller has 30 minutes

    or more to warm up after turning ON the power before starting

    actual control operations to ensure the correct temperature

    display.

12.When executing self-tuning with E5@C, turn ON power to the load

    (e.g., heater) at the same time as or before supplying power to the

    product. If power is turned ON to the product before turning ON

                                                                                                                                                    
    E5CC/E5CC-U/E5EC/E5AC/E5DC

                  Shipping Standards

The E5CC, E5CC-U, E5EC, and E5AC comply with Lloyd's                          ●   Operating Precautions

standards. When applying the standards, the following installation            1.  When using self-tuning, turn ON power for the load (e.g., heater)

requirements must be met in the application.                                      at the same time as or before supplying power to the Digital

Application Conditions                                                            Controller. If power is turned ON for the Digital Controller before

                                                                                  turning ON power for the load, self-tuning will not be performed

●   Installation Location                                                         properly and optimum control will not be achieved.

The E5CC, E5CC-U, E5EC, and E5AC comply with installation                         When starting operation after the Digital Temperature Controller

category ENV1 and ENV2 of Lloyd's standards. Therefore, they must                 has warmed up, turn OFF the power and then turn it ON again at

be installed in a location equipped with air conditioning. They cannot            the same time as turning ON power for the load. (Instead of turning

be used on the bridge or decks, or in a location subject to strong                the Digital Temperature Controller OFF and ON again, switching

                                                                                  from STOP mode to RUN mode can also be used.)

vibration.                                                                    2.  Avoid using the Controller in places near a radio, television set, or

                                                                                  wireless installing. These devices can cause radio disturbances

               Precautions for Correct Use                                        which adversely affect the performance of the Controller.

●   Service Life                                                              ●   Others

                                                                              1.  Do not Connect or disconnect the Conversion Cable connector

1.  Use the product within the following temperature and humidity ranges:         repeatedly over a short period of time.

    Temperature:  -10 to 55°C (with no icing or condensation)                     The computer may malfunction.

    Humidity:     25% to 85%                                                  2.  After connecting the Conversion Cable to the computer, check the

    If the product is installed inside a control board, the ambient               COM port number before starting communications. The computer

    temperature must be kept to under 55°C, including the temperature             requires time to recognize the cable connection. This delay does

    around the product.                                                           not indicate failure.

2.  The service life of electronic devices like Digital Temperature           3.  Do not connect the Conversion Cable through a USB hub. Doing

    Controllers is determined not only by the number of times the relay is        so may damage the Conversion Cable.

    switched but also by the service life of internal electronic components.  4.  Do not use an extension cable to extend the Conversion Cable

    Component service life is affected by the ambient temperature: the            length when connecting to the computer. Doing so may damage

    higher the temperature, the shorter the service life and, the lower           the Conversion Cable.

    the temperature, the longer the service life. Therefore, the service      ●   Mounting

    life can be extended by lowering the temperature of the Digital           Mounting to a Panel

    Temperature Controller.

3.  When two or more Digital Temperature Controllers are mounted              E5CC

    horizontally close to each other or vertically next to one another,       There are two models of Terminal Covers that you can use with the E5CC.

    the internal temperature will increase due to heat radiated by the

    Digital Temperature Controllers and the service life will decrease.                         Terminal Cover                               Terminal Cover

    In such a case, use forced cooling by fans or other means of air                            (E53-COV17)                                  (E53-COV23)

                                                                                                (Sold separately)  Adapter

    ventilation to cool down the Digital Temperature Controllers. When

    providing forced cooling, however, be careful not to cool down the

    terminals sections alone to avoid measurement errors.

●   Measurement Accuracy

1.  When extending or connecting the thermocouple lead wire, be sure to

    use compensating wires that match the thermocouple types.

2.  When extending or connecting the lead wire of the platinum resistance         Water Proof Packing

    thermometer, be sure to use wires that have low resistance and keep                         Panel

    the resistance of the three lead wires the same.                          E5CC-U

3.  Mount the product so that it is horizontally level.                       For the Wiring Socket for the E5CC-U, purchase the P2CF-11 or

4.  If the measurement accuracy is low, check to see if input shift has

    been set correctly.                                                       PG3A-11 separately.

●   Waterproofing (Not applicable to the E5CC-U/

    E5DC.)

The degree of protection is as shown below. Sections without any

specification on their degree of protection or those with IP@0 are not

waterproof.

    Front panel: IP66, Rear case: IP20, Terminal section: IP00

When waterproofing is required, insert the Waterproof Packing on the

backside of the front panel. Keep the Port Cover on the front-panel

Setup Tool port of the E5EC/E5AC securely closed. The degree of               1.  For waterproof mounting, waterproof packing must be installed on the

protection when the Waterproof Packing is used is IP66. To maintain               Controller. Waterproofing is not possible when group mounting several

an IP66 degree of protection, the Waterproof Packing and the Port                 Controllers. Waterproof packing is not necessary when there is no

Cover for the front-panel Setup Tool port must be periodically                    need for the waterproofing function.

replaced because they may deteriorate, shrink, or harden depending                The E5CC-U cannot be waterproofed even if the Waterproof Packing

on the operating environment. The replacement period will vary with               is inserted.

the operating environment. Check the required period in the actual            2.  Insert the E5CC/E5CC-U into the mounting hole in the panel.

application. Use 3 years or sooner as a guideline. If the Waterproof          3.  Push the adapter from the terminals up to the panel, and

Packing and Port Cover are not periodically replaced, waterproof                  temporarily fasten the E5CC.

performance may not be maintained. If a waterproof structure is not           4.  Tighten the two fastening screws on the adapter.

required, then the Waterproof Packing does not need to be installed.              Alternately tighten the two screws little by little to maintain a

                                                                                  balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.


                                                                           E5CC/E5CC-U/E5EC/E5AC/E5DC

●   Precautions when Wiring

• Separate input leads and power lines in order to prevent external

    noise.

• Use a shielded, AWG24 to AWG18 (cross-sectional area of 0.205

    to 0.8231 mm2) twisted-pair cable. Use a shielded, AWG24 to

    AWG14 (cross-sectional area of 0.205 to 2.081 mm2) twisted-pair

    cable for the E5CC-U. The stripping length is 6 to 8 mm for the

    E5CC, E5EC, E5AC, or E5DC and 5 to 6 mm for the E5CC-U.

• Use crimp terminals when wiring the terminals.

• Use the suitable wiring material and crimp tools for crimp terminals.

• Tighten the terminal screws to a torque of 0.43 to 0.58 N·m.

    The specified torque is 0.5 N·m for the E5CC-U.

• For the E5CC, E5EC, E5AC, or E5DC, use the following types of

    crimp terminals for M3 screws.

                                          5.8 mm max.

                                          5.8 mm max.

•   For the E5CC-U,  use  the  following  types of crimp  terminals  for

    M3.5 screws.

                                          7.2 mm max.

                                          7.2 mm max.

Three-year Guarantee

●   Period of Guarantee                                                    Note: Average Operating Temperature

The guarantee period of the Unit is three years starting  from  the  date  Refer to the process temperature of the Unit mounted to a

the Unit is shipped from the factory.                                      control panel and connected to peripheral devices on condition

                                                                           that the Unit is in stable operation, sensor input type K is

Scope of Guarantee                                                         selected for the Unit, the positive and negative thermocouple

                                                                           input terminals of the Unit are short-circuited, and the ambient

The Unit is guaranteed under the                                           temperature is stable.

following operating conditions.           Top                              Should the Unit malfunction during the guarantee period, OMRON

1.  Average Operating Temperature                                          shall repair the Unit or replace any parts of the Unit at the expense of

    (see note): −10°C to 50°C                                              OMRON.

2.  Mounting Method: Standard mounting

                                          Bottom

                                                                                                                                                     
    MEMO

60
Terms and Conditions of Sale

1.   Offer; Acceptance. These terms and conditions (these "Terms") are deemed                              ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.

     part of all quotes, agreements, purchase orders, acknowledgments, price lists,                        BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE

     catalogs, manuals, brochures and other documents, whether electronic or in                            PRODUCTS         WILL     SUITABLY       MEET     THE       REQUIREMENTS                OF   THEIR

     writing, relating to the sale of products or services (collectively, the "Products")                  INTENDED USE. Omron further disclaims all warranties and responsibility of

     by Omron Electronics LLC and its subsidiary companies (“Omron”). Omron                                any type for claims or expenses based on infringement by the Products or oth-

     objects to any terms or conditions proposed in Buyer’s purchase order or other                        erwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obli-

     documents which are inconsistent with, or in addition to, these Terms.                                gation   hereunder      shall  be,  at  Omron’s   election,     to  (i)  replace        (in  the  form

2.   Prices; Payment Terms. All prices stated are current, subject to change with-                         originally     shipped  with   Buyer    responsible    for  labor   charges        for  removal   or

     out notice by Omron. Omron reserves the right to increase or decrease prices                          replacement thereof) the non-complying Product, (ii) repair the non-complying

     on any unshipped portions of outstanding orders. Payments for Products are                            Product, or (iii) repay or credit Buyer an amount equal to the purchase price of

     due net 30 days unless otherwise stated in the invoice.                                               the non-complying Product; provided that in no event shall Omron be responsi-

3.   Discounts. Cash discounts, if any, will apply only on the net amount of invoices                      ble for warranty, repair, indemnity or any other claims or expenses regarding

     sent to Buyer after deducting transportation charges, taxes and duties, and will                      the Products unless Omron’s analysis confirms that the Products were prop-

     be allowed only if (i) the invoice is paid according to Omron’s payment terms                         erly handled, stored, installed and maintained and not subject to contamina-

     and (ii) Buyer has no past due amounts.                                                               tion, abuse, misuse or inappropriate modification. Return of any Products by

4.   Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month or                         Buyer must be approved in writing by Omron before shipment. Omron Compa-

     the maximum legal rate, whichever is less, on any balance not paid within the                         nies shall not be liable for the suitability or unsuitability or the results from the

     stated terms.                                                                                         use of Products in combination with any electrical or electronic components,

5.   Orders. Omron will accept no order less than $200 net billing.                                        circuits, system assemblies or any other materials or substances or environ-

6.   Governmental Approvals. Buyer shall be responsible for, and shall bear all                            ments. Any advice, recommendations or information given orally or in writing,

     costs involved in, obtaining any government approvals required for the impor-                         are not to be construed as an amendment or addition to the above warranty.

     tation or sale of the Products.                                                                       See http://www.omron247.com or contact your Omron representative for pub-

7.   Taxes. All taxes, duties and other governmental charges (other than general                           lished information.

     real property and income taxes), including any interest or penalties thereon,                    14.  Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE

     imposed directly or indirectly on Omron or required to be collected directly or                       FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,

     indirectly by Omron for the manufacture, production, sale, delivery, importa-                         LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY

     tion, consumption or use of the Products sold hereunder (including customs                            WAY     CONNECTED         WITH      THE  PRODUCTS,          WHETHER      SUCH           CLAIM     IS

     duties and sales, excise, use, turnover and license taxes) shall be charged to                        BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.

     and remitted by Buyer to Omron.                                                                       Further, in no event shall liability of Omron Companies exceed the individual

8.   Financial. If the financial position of Buyer at any time becomes unsatisfactory                      price of the Product on which liability is asserted.

     to Omron, Omron reserves the right to stop shipments or require satisfactory                     15.  Indemnities. Buyer shall indemnify and hold harmless Omron Companies and

     security or payment in advance. If Buyer fails to make payment or otherwise                           their   employees       from   and  against  all  liabilities,  losses,  claims,        costs     and

     comply with these Terms or any related agreement, Omron may (without liabil-                          expenses (including attorney's fees and expenses) related to any claim, inves-

     ity and in addition to other remedies) cancel any unshipped portion of Prod-                          tigation, litigation or proceeding (whether or not Omron is a party) which arises

     ucts  sold  hereunder   and    stop   any  Products     in  transit  until  Buyer    pays  all        or is alleged to arise from Buyer's acts or omissions under these Terms or in

     amounts,    including   amounts     payable  hereunder,     whether  or     not  then      due,       any way with respect to the Products.        Without limiting the foregoing, Buyer (at

     which are owing to it by Buyer. Buyer shall in any event remain liable for all                        its own expense) shall indemnify and hold harmless Omron and defend or set-

     unpaid accounts.                                                                                      tle any action brought against such Companies to the extent based on a claim

9.   Cancellation;  Etc.    Orders    are  not  subject  to  rescheduling        or  cancellation          that any Product made to Buyer specifications infringed intellectual property

     unless Buyer indemnifies Omron against all related costs or expenses.                                 rights of another party.

10.  Force Majeure. Omron shall not be liable for any delay or failure in delivery                    16.  Property; Confidentiality. Any intellectual property in the Products is the exclu-

     resulting from causes beyond its control, including earthquakes, fires, floods,                       sive property of Omron Companies and Buyer shall not attempt to duplicate it

     strikes or other labor disputes, shortage of labor or materials, accidents to                         in  any  way     without  the   written  permission    of   Omron.       Notwithstanding          any

     machinery, acts of sabotage, riots, delay in or lack of transportation or the                         charges to Buyer for engineering or tooling, all engineering and tooling shall

     requirements of any government authority.                                                             remain the exclusive property of Omron. All information and materials supplied

11.  Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron:                            by Omron to Buyer relating to the Products are confidential and proprietary,

     a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship                        and Buyer shall limit distribution thereof to its trusted employees and strictly

          except in “break down” situations.                                                               prevent disclosure to any third party.

     b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall               17.  Export Controls. Buyer shall comply with all applicable laws, regulations and

          constitute delivery to Buyer;                                                                    licenses regarding (i) export of products or information; (iii) sale of products to

     c. All sales and shipments of Products shall be FOB shipping point (unless oth-                       “forbidden” or other proscribed persons; and (ii) disclosure to non-citizens of

          erwise stated in writing by Omron), at which point title and risk of loss shall                  regulated technology or information.

          pass from Omron to Buyer; provided that Omron shall retain a security inter-                18.  Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any right

          est in the Products until the full purchase price is paid;                                       and no course of dealing between Buyer and Omron shall operate as a waiver

     d. Delivery and shipping dates are estimates only; and                                                of rights by Omron. (b) Assignment. Buyer may not assign its rights hereunder

     e. Omron will package Products as it deems proper for protection against nor-                         without Omron's written consent. (c) Law. These Terms are governed by the

          mal handling and extra charges apply to special conditions.                                      law of the jurisdiction of the home office of the Omron company from which

12.  Claims. Any claim by Buyer against Omron for shortage or damage to the                                Buyer    is  purchasing   the     Products   (without  regard       to   conflict  of   law  princi-

     Products occurring before delivery to the carrier must be presented in writing                        ples).   (d) Amendment. These Terms constitute the entire agreement between

     to Omron within 30 days of receipt of shipment and include the original trans-                        Buyer and Omron relating to the Products, and no provision may be changed

     portation bill signed by the carrier noting that the carrier received the Products                    or waived unless in writing signed by the parties. (e) Severability. If any provi-

     from Omron in the condition claimed.                                                                  sion hereof is rendered ineffective or invalid, such provision shall not invalidate

13.  Warranties.    (a)  Exclusive  Warranty.   Omron’s   exclusive       warranty    is  that  the        any other provision. (f) Setoff. Buyer shall have no right to set off any amounts

     Products will be free from defects in materials and workmanship for a period of                       against the amount owing in respect of this invoice. (g) Definitions. As used

     twelve months from the date of sale by Omron (or such other period expressed                          herein, “including” means “including without limitation”; and “Omron Compa-

     in writing by Omron). Omron disclaims all other warranties, express or implied.                       nies” (or similar words) mean Omron Corporation and any direct or indirect

     (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION,                                           subsidiary or affiliate thereof.

     EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-

Certain Precautions on Specifications and Use

1.   Suitability of Use. Omron Companies shall not be responsible for conformity                           ADDRESS THE RISKS, AND THAT THE OMRON’S PRODUCT IS PROP-

     with any standards, codes or regulations which apply to the combination of the                        ERLY     RATED   AND      INSTALLED      FOR      THE  INTENDED          USE       WITHIN         THE

     Product in the Buyer’s application or use of the Product. At Buyer’s request,                         OVERALL EQUIPMENT OR SYSTEM.

     Omron will provide applicable third party certification documents identifying                    2.   Programmable Products. Omron Companies shall not be responsible for the

     ratings and limitations of use which apply to the Product. This information by                        user’s programming of a programmable Product, or any consequence thereof.

     itself is not sufficient for a complete determination of the suitability of the Prod-            3.   Performance      Data.    Data    presented  in   Omron     Company      websites,           catalogs

     uct in combination with the end product, machine, system, or other application                        and other materials is provided as a guide for the user in determining suitabil-

     or use. Buyer shall be solely responsible for determining appropriateness of                          ity and does not constitute a warranty. It may represent the result of Omron’s

     the particular Product with respect to Buyer’s application, product or system.                        test conditions, and the user must correlate it to actual application require-

     Buyer shall take application responsibility in all cases but the following is a                       ments. Actual performance is subject to the Omron’s Warranty and Limitations

     non-exhaustive list of applications for which particular attention must be given:                     of Liability.

     (i)   Outdoor use, uses involving potential chemical contamination or electrical                 4.   Change       in  Specifications.    Product  specifications     and      accessories         may  be

     interference, or conditions or uses not described in this document.                                   changed at any time based on improvements and other reasons. It is our prac-

     (ii)  Use in consumer products or any use in significant quantities.                                  tice to change part numbers when published ratings or features are changed,

     (iii) Energy control systems, combustion systems, railroad systems, aviation                          or when significant construction changes are made. However, some specifica-

     systems, medical equipment, amusement machines, vehicles, safety equip-                               tions of the Product may be changed without any notice. When in doubt, spe-

     ment, and installations subject to separate industry or government regulations.                       cial part numbers may be assigned to fix or establish key specifications for

     (iv) Systems, machines and equipment that could present a risk to life or prop-                       your application. Please consult with your Omron’s representative at any time

     erty. Please know and observe all prohibitions of use applicable to this Prod-                        to confirm actual specifications of purchased Product.

     uct.                                                                                             5.   Errors and Omissions. Information presented by Omron Companies has been

     NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS                                            checked and is believed to be accurate; however, no responsibility is assumed

     RISK  TO     LIFE   OR  PROPERTY         OR  IN  LARGE      QUANTITIES           WITHOUT              for clerical, typographical or proofreading errors or omissions.

     ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
OMRON AUTOMATION AND SAFETY • THE AMERICAS HEADQUARTERS • Hoffman Estates, IL USA • 847.843.7900 • 800.556.6766 • www.omron247.com

OMRON CANADA, INC. • HEAD OFFICE                                                            OMRON ARGENTINA • SALES OFFICE

Toronto, ON, Canada • 416.286.6465 • 866.986.6766 • www.omron247.com                        Cono Sur • 54.11.4783.5300

OMRON ELECTRONICS DE MEXICO • HEAD OFFICE                                                   OMRON CHILE • SALES OFFICE

México DF • 52.55.59.01.43.00 • 01-800-226-6766 • mela@omron.com                            Santiago • 56.9.9917.3920

OMRON ELECTRONICS DE MEXICO • SALES OFFICE                                                  OTHER OMRON LATIN AMERICA SALES

Apodaca, N.L. • 52.81.11.56.99.20 • 01-800-226-6766 • mela@omron.com                        54.11.4783.5300

OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICE

São Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br

OMRON EUROPE B.V. • Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. • +31 (0) 23 568 13 00 • www.industrial.omron.eu

Authorized Distributor:                                               Automation Control Systems

                                                                      • Machine Automation Controllers (MAC) • Programmable Controllers (PLC)

                                                                      • Operator interfaces (HMI) • Distributed I/O • Software

                                                                      Drives & Motion Controls

                                                                      • Servo & AC Drives • Motion Controllers & Encoders

                                                                      Temperature & Process Controllers

                                                                      • Single and Multi-loop Controllers

                                                                      Sensors & Vision

                                                                      • Proximity Sensors • Photoelectric Sensors • Fiber-Optic Sensors

                                                                      • Amplified Photomicrosensors • Measurement Sensors

                                                                      • Ultrasonic Sensors • Vision Sensors

                                                                      Industrial Components

                                                                      • RFID/Code Readers • Relays • Pushbuttons & Indicators

                                                                      • Limit and Basic Switches • Timers • Counters • Metering Devices

                                                                      • Power Supplies

                                                                      Safety

                                                                      • Laser Scanners • Safety Mats • Edges and Bumpers • Programmable Safety

                                                                      Controllers • Light Curtains • Safety Relays • Safety Interlock Switches

Cat. No. H04I-E-01                01/14        Note: Specifications are subject to change.        © 2014 Omron Electronics LLC           Printed in U.S.A.

                                                                      Printed on recycled paper.
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Omron:

E5CC-RW0AUM-000  E5CC-CX1AUM-000  E5CC-CX2DUM-000  E5CC-RW1DUM-000   E5CC-RW1AUM-000   E5CC-

CX2AUM-000  E5CC-CX0AUM-000  E5CC-RW2DUM-000  E5CC-CX1DUM-000  E5CC-RW0DUM-000  E5CC-

RW2AUM-000  E5CC-CX0DUM-000  E5CC-RW2AUM-800  E5CC-RW2DUM-800

小广播

E5CC-CX0AUM-000器件购买:

该厂商的其它器件

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2017 EEWORLD.com.cn, Inc. All rights reserved