控制器 Temperature Control On/Off

参数
产品属性属性值
制造商:Omron
产品种类:控制器
发货限制:Mouser目前不销售该产品。
RoHS:N
系列:E5C2
商标:Omron Automation and Safety
产品类型:Controllers
工厂包装数量:1
子类别:Controllers
零件号别名:E5C2Q20K32572AC120
单位重量:100 g

E5C2-Q20K-32/572-AC120器件文档内容

    Temperature Controller

    E5C2

                                                                                                                                                      CSM_E5C2_DS_E_4_1

DIN-sized (48 x 48 mm) Temperature

Controller with Analog Setting

• Compact, low-cost Temperature Controller.

• Incorporates proportional control and reset adjustment function.

• Consecutive mounting possible using mounting adapter.

• Incorporates a plug-in socket, thus allows to DIN-track and flush

mounting.

         Refer to Safety Precautions for All Temperature

         Controllers.

Model Number Structure

■ Model Number                        Legend

E5C2- @ @ @ @

    1          2  3    4   5

1.  Control Outputs                                        3.   Input                                                         Note: A functional explanation is provided

    R:   Relay                                                  K:       K-type thermocouple                                         here for illustration, but models are

2.  Control Method                                              J:       J-type thermocouple                                         not necessarily available for all

    20:  ON-OFF control                                         P-D:     Platinum resistance thermometer                             possible combinations. Refer to

                                                                         (Pt100)                                                     Ordering Information when ordering.

    40:  Proportional control                                                                                                        Examples

                                                                G:       Thermistor with replaceable ele-                         • Relay control output, ON/OFF

                                                                         ment                                                        control, type-K thermocouple input:

                                                                                                                                     E5C2-R20K

                                                                                                                                  • Relay control output, proportional

                                                                                                                                     control, thermocouple input: E5C2-

                                                                                                                                     R40P-D

Ordering Information

■ Temperature Controllers

                                             Input                          Thermocouple                            Resistance Thermometer                   Thermistor

                                                                    K (CA)                          J (IC)               Platinum resistance                 Thermistor

                                                           Chromel vs. alumel                 Iron  vs. constantan       thermometer Pt100                 (replaceable element)

                                             1,200                                     1,200                                                               Themistor nominal resistance

                               Standard      1,000                              1,000                                                                 6 kΩ   6 kΩ   30 kΩ  550 Ω  4 kΩ

                                      scale  800                          800                                                                         (0°C)  (0°C)  (0°C) (200°C)(200°C)

                                      (°C)   600                     600

                                             400                400                                         400                                  400

                                             300           300                                      300                                     300                                   300

                                             200      200                                     200                                      200                          150    200

                                             100                                                                    50   80   50  100                 50     100

                                             0                                                                                                                             100    150

                                             −100     0    0    0     0     0   0      0      0     0       0                 0   0    0    0    0           0      50

                                                                                                                    −50  −20                          −50

         Indica-                             Minimum

Setting  tion     Control             scale division  5    10   10   20     20  25     25     5     10      10      2    2    1   2    5    10   10   2      2      2      2             2

method   method   mode        Output         (°C)

Analog   No       ON/OFF      Relay   Model           E5C2-R20K                               E5C2-R20J             E5C2-R20P-D                       E5C2-R20G

setting  indi-    Propor-                             E5C2-R40K                               E5C2-R40J             E5C2-R40P-D                       ---

         cation   tional      Relay   Model

                  (P)

Note: When placing an order, specify the temperature range and supply voltage in addition to the model number.

                                                                                                                                                                                            1
                                                                                                                                              E5C2

Standard Models (Power Supply: 100 to 120 VAC)

                       Indication method       No indication                                   Indication method               No indication

                             Control mode   ON/OFF          Proportional                             Control mode  ON/OFF          Proportional (P)

                                                                  (P)               Input              Output                      Relay

            Input                 Output               Relay              Input/  Resis-   Platinum    −50 to 50   E5C2-R20P-D     E5C2-R40P-D

Input/  Thermo-    K (CA)      0  to 200    E5C2-R20K  E5C2-R40K          stan-   tance    resistance  −20 to 80   E5C2-R20P-D     E5C2-R40P-D

stan-   couple     Chromel     0  to 300    E5C2-R20K  E5C2-R40K          dard    Ther-    thermom-

dard               vs. alumel                                             scale   mome-    eter Pt100  0 to 50     E5C2-R20P-D     E5C2-R40P-D

scale                          0  to 400    E5C2-R20K  E5C2-R40K          (°C)    ter                  0 to 100    E5C2-R20P-D     E5C2-R40P-D

(°C)                           0  to 600    E5C2-R20K  E5C2-R40K

                                                                                                       0 to 200    E5C2-R20P-D     E5C2-R40P-D

                               0  to 800    E5C2-R20K  E5C2-R40K                                       0 to 300    E5C2-R20P-D     E5C2-R40P-D

                               0  to 1,000  E5C2-R20K  E5C2-R40K                                       0 to 400    E5C2-R20P-D     E5C2-R40P-D

                               0  to 1,200  E5C2-R20K  E5C2-R40K                  Ther-    THE (re-    −50 to 50   E5C2-R20G       ---

                   J (IC)      0  to 200    E5C2-R20J  E5C2-R40J                  mistor   placeable   0 to 100    E5C2-R20G       ---

                   Iron vs.    0  to 300    E5C2-R20J  E5C2-R40J                           element)

                   constantan                                                                          50 to 150   E5C2-R20G       ---

                               0  to 400    E5C2-R20J  E5C2-R40J                                       100 to 200  E5C2-R20G       ---

Note: Ask your OMRON representative about models with 200 to 240                                       150 to 300  E5C2-R20G       ---

        VAC power supply.

■ Accessories (Order Separately)

Sockets                                                                   Protective Cover

                           Name                               Model                    Type                        Model

Front Connecting Socket                                P2CF-08            Hard Protective Cover        Y92A-48B

Back Connecting Socket                                 P3G-08

Front Connecting Socket with Finger Protection         P2CF-08-E

Protective Cover (for finger protection)               Y92A-48G

Specifications

■ Ratings                                                                 ■ Characteristics

Supply voltage         100 to120 VAC 50/60 Hz                             Setting accuracy      ±2% FS max.

                       200 to 240 VAC 50/60 Hz (See note 1.)              Hysteresis            Approx. 0.5% FS (fixed)

Operating voltage      90% to 110% of rated supply voltage                Proportional band     3% FS (fixed)

range                                                                     Control period        Approx. 20 s

Power                  Approx. 3 VA                                       Reset range           5 ±1% FS min. (See note 1.)

consumption                                                               Insulation            20 MΩ min. (at 500 VDC)

Input                  Thermocouple (with sensor burnout detection        resistance

                       circuit), platinum resistance thermometer, or      Dielectric strength   2,000 VAC, 50/60 Hz for 1 min between charged termi-

                       thermistor with replaceable element                                      nals and uncharged metallic parts

Control method         ON/OFF or proportional control                     Vibration             Malfunction: 10 to 55 Hz, 0.15-mm single amplitude for

                                                                          resistance                          10 min each in X, Y, and Z directions

Setting method         Analog setting                                                           Destruction: 16.7 Hz, 2-mm double amplitude for 2 hrs

Indication             No indication                                                                          each in X, Y, and Z directions

method                                                                    Shock resistance      Malfunction: 147 m/s2, 3 times each in 6 directions

Control output         Relay output: SPDT, 3 A at 250 VAC, resistive                            Destruction: 294 m/s2, 3 times each in 6 directions

                                       load (switching capacity: 330 VA)  Life expectancy       Electrical:     100,000 operations min. (3 A at 110 VAC,

                                                                                                              resistive load)

Ambient operat-        −10°C to 55°C (with no icing or condensation)      Weight                Approx. 200 g (with flush-mounting adapter)

ing temperature                                                           Degree of protection  Front panel: IEC standard IP40 (See note 2.)

Ambient operat-        45% to 85%                                                               Terminals:      IEC standard IP00

ing humidity                                                              Applicable Socket     P2CF-08 (order separately),

                                                                                                P3G-08 (order separately)

Note: 1.    Specify either 100/110/120 VAC or 200/220/240 VAC when        Applicable Protec-    Y92A-48B (order separately)

            ordering.                                                     tive Cover

        2.  Do not use an inverter output as the power supply. (Refer to

            Safety Precautions for All Temperature Controllers.)          Note: 1.    No reset function is incorporated by any E5C2 model with

                                                                                      ON/OFF control.

                                                                                      The reset function is used to correct offset for proportional

                                                                                      control. If there is an offset below the set value, turn the

                                                                                      reset adjustment clockwise.

                                                                                  2.  A special Watertight Cover is used to achieve this degree of

                                                                                      protection (IP66, NEMA4). Refer to Y92A-@@N.

                                                                                                                                                          2
                                                                                                                                        E5C2

■ Connections

Connecting the Input                                                      Output

• Connect a thermocouple, the E52-THE@ Thermistor (replaceable            •  If the load circuit is a heating control system, be sure to connect the

   element) or a platinum resistance thermometer to terminals 1              load to terminals 4 and 5. If the load circuit is a cooling control

   (positive) and 2 (negative) on the E5C2 as shown in the following         system, be sure to connect the load to terminals 4 and 6.

   illustration.                                                          •  We recommend using an external relay to extend the electrical life

                                                                             of internal relays when driving a large capacity load. This is

                                                                             particularly important when the output relay is switched frequently

                  Platinum resistance                                        (e.g., with proportional control).

                  thermometer input

                                                                          Power Supply

   Thermocouple input                                                     •  If a single power supply is used for the E5C2 and the load, the

                                                                             supply voltage of the power supply may vary greatly when the load

                                                                             is open or closed if the capacity of the power supply is not large

                                                                             enough. Make sure that the capacity of the power supply is large

                                       Power supply                          enough so that the supply voltage range will be always from 90% to

                                       100/110/120 VAC (same model) or       110% of the rated supply voltage.

   Thermistor with                     200/220/240 VAC (same model)

   replaceable element                 50/60 Hz                           •  The E5C2 operates at either 50 or 60 Hz.

•  On the E52-@@1D, the lead wires are thermocouple element wires,        •  Different models must be order for 100 to 120 VAC and 200 to

   making them difficult to solder because solder will not stick to them     240 VAC.

   easily. Remove the crimp terminal and polish the ends before

   attempting to solder them.

Nomenclature

   Temperature setting knob                                               Operation Indicator

                                                                               Indicator                         Output

                                       Operation indicator                                NO contacts (4 and 5) NC contacts (4 to 6)

                                                                          Red  Lit        ON                           OFF

                                                                               Not lit    OFF                          ON

                               RESET adjustment shaft

                               No reset function is incorporated by any

                               E5C2 model with ON/OFF control.

                                                                                                                                                      3
                                                                                                                                                    E5C2

Dimensions

Note: All units are in millimeters unless otherwise indicated.

                                                                                                                   Terminal Arrangement

                            48 x 48                                                                                (Bottom View)

                                                                                          44.8 x 44.8

Dimensions with Flush-mounting Adapter (Accessory),

and Back Connecting Socket (Sold Separately)                                              Panel

                                                                          Flush-mounting        Y92F-30  Flush-mounting adapter

                                                                          adapter                                               P3G-08 Back

                                                                                                                                connecting socket

                                                                                                         Tightening screw

                                                                                                         (96)

              Panel Cutout                                      Side-by-side Mounting

                                                                of N Controllers

                                                                                          Qty.   2       3      4       5       6

                                                                                          L      93+01  141+01  189+01  237+01  285+01

              60 min.

                                                                Note: 1. Recommended panel thickness is 1 to 4 mm.

                                                                          2. Close side-by-side mounting is possible (in a              single  direction).

■ Accessories (Order Separately)

Connection Sockets

P2CF-08 Front Connecting Socket

                                                                                             Terminal Arrangement/                      Mounting Holes

                                                                                             Internal Connections

                            Eight, M3.5 x 7.5 sems                                           (Top View)

                                                                                                                                        Two, 4.5 dia. or two, M4

                            70 max.

                                                                Two,

                                                                4.5-dia.                                                        Note: Can also be

                                                                holes                                                                   mounted to a

                                                                                                                                        DIN track.

                                       50 max.

                                                                          20 max.

                                                                          Note: A  finger-protection  model     (P2CF-08-E) is also available.

P3G-08  Back  Connecting  Socket (for  Flush Mounting)                                                                  Terminal Arrangement/

                          27 dia.                                                                                       Internal Connections

                                                                                                                        (Bottom View)

                                                                          Note: A Protective Cover for finger protection (Y92A-48G) is also available.

                                                                                                                                                                  4
                                                                                                                                   E5C2

Hard Protective Cover                                                   Applicable Thermistor

A Hard Protective Cover (Y92A-48B) is available. It can be used in      Connect a Thermistor with a replaceable element (E52-THE5A, E52-

the following cases.                                                    THE6D, or E52-THE6F) to the E5C2-R20G. Refer to E52 for details.

• To protect the setting section, against dust and dirt

• To prevent accidently changing settings by touching the front of the

Controller.

• To protect the Controller from water drips

Appearance

Model                                              Y92A-48B

Safety Precautions

Refer to Safety Precautions for All Temperature Controllers.

■ Correct Use

Mounting                                                                The P3G-08 can be wired in the same way as the P2CF-08.

Track Mounting (E5C2 with P2CF-08)

When mounting two or more E5C2 models with track-mounting

sockets, leave a space of approximately 20 mm on both sides of the

sockets where hooks are located.

                                               Hook                     Dismounting

                                                     Duct               If flush mounted, loosen the screw of the adapter and disengage the

                                                                        hooks for dismounting.

                             P2CF-08

                      Panel                    20

Flush Mounting

Insert E5C2 into the square hole of the panel and insert an adapter

from the back so that there will be no space between E5C2 and the

panel. Then, secure the E5C2 with a screw.                              Temperature Setting

                                                                        Do not turn the temperature setting knob of the E5C2 with excessive

                                                                        force, otherwise the stopper of the knob may break.

                                                                        Others

                                                                        •  Do not remove the housing of the E5C2, otherwise the housing

                             Tightening screw                              may break.

                                                                        •  To clean the surface of the E5C2, use a soft cloth wet with neutral

                                                                           detergent or alcohol. Do not use any organic solvent, such as paint

                                                                           thinner or benzine, strong acid or strong alkali to clean the surface

                                                                           of the E5C2, otherwise the surface of the E5C2 will become

                                                                           damaged.

                      ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

                      To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                                  In the interest of product improvement, specifications are subject to change without notice.

                                                                                                                                                  5
                                                      Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or

comments.

                                                      Warranty and Limitations of Liability

WARRANTY

OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)

from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR

FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS.                     ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS

DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.                                OMRON DISCLAIMS ALL OTHER

WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY

OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS

IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT

LIABILITY.

In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS

OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT

SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

                                                      Application Considerations

SUITABILITY FOR USE

OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's

application or use of the products.

At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the

products.   This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,

machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given.             This is not intended to be an exhaustive list of all possible

uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:

•  Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.

•  Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,

   safety equipment, and installations subject to separate industry or government regulations.

•  Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE

SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND

INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

PROGRAMMABLE PRODUCTS

OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.

                                                                    Disclaimers

CHANGE IN SPECIFICATIONS

Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.

However, some specifications of the products may be changed without any notice.     When in doubt, special model numbers may be assigned to fix or

establish key specifications for your application on your request.  Please consult with your OMRON representative at any time to confirm actual

specifications of purchased products.

DIMENSIONS AND WEIGHTS

Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

PERFORMANCE DATA

Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent               the

result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON

Warranty and Limitations of Liability.

ERRORS AND OMISSIONS

The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,

typographical, or proofreading errors, or omissions.

                                                                                                                                                                         2011.4

                                                      In the interest of product improvement, specifications are subject to change without notice.

OMRON Corporation

Industrial Automation Company

http://www.ia.omron.com/

                                                                                                          (c)Copyright OMRON Corporation 2011 All Right Reserved.
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Omron:

E5C2R20J0200C3239       E5C2-Q20K-2192F-AC240  E5C2-Q20K-32/572-AC120  E5C2R20J0200C32392F-AC240

E5C2R20PDIN-50/50C-AC120
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

器件索引   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2020 EEWORLD.com.cn, Inc. All rights reserved