      Digital Process Controller Series

    E5K

   Advanced Process Digital
   Controllers with Fuzzy Logic

   D Field configurable outputs, options.
   D 100 ms sampling (for analog input).
   D Advanced PID, or fuzzy self-tuning.
   D Conforms to UL, CSA and CE standards.
   D Water-resistant front panel meets IP66/NEMA 4X.
   D Remote set point with optional event input board.
   D Set point ramp.
   D Serial communications available.
   D Front panel programming.
   D Heat only or heat/cool control.
   D Auxiliary outputs (SPST) standard; two for E5AK/E5EK,

      one for E5CK.
   D 3-year warranty.

   Ordering Information

   Note: Order Control Output Boards and Option Boards separately below.

                                Description                    DIN size       Supply voltage                    Model
   Standard model                                           1/4 DIN       100 to 240 VAC      E5AK-AA2-500
   Position-proportional model (See Note 3)                 (96 x 96 mm)  100 to 240 VAC      E5AK-PRR2-500
   Standard model                                                         100 to 240 VAC      E5EK-AA2-500
   Position-proportional model (See Note 3)                 1/8 DIN       100 to 240 VAC      E5EK-PRR2-500
   Standard model                                           (48 x 96 mm)  100 to 240 VAC      E5CK-AA1-500
   Non-standard model with built-in quick auto-tune button                100 to 240 VAC      E5CK-AA1-302
   (See Nomenclature section for details)                   1/16 DIN
                                                            (48 x 48 mm)

   Note: 1.    When using the heater burnout alarm function with a standard model, the Linear Output Module cannot be used for the control
               outputs (heat). The Digital Controller provides transfer outputs at 4 to 20 mA for the PV and other values and control outputs at
           2.  4 to 20 mA for the current outputs.
           3.
           4.  E5EK-PRR2/E5AK-PRR2 controllers are supplied with dedicated relay output.

               Position-proportional models are intended for motorized valves (not 4-20 mA modulating valves). These use two relays ("open"
               and "close") which will turn a motor clockwise or counter-clockwise, thus opening or closing the valve.

               Part numbers ending in --500 include a Finger Safe cover.

1              Digital Process Controller E5K
J Optional Output Boards

   Description              Specifications                    Compatible   Max. quantity                     Model
                                                               controller
Relay                       SPST, 5 A, 250 VAC          E5AK/E5EK          2              E53-R
SSR (solid state relay)     1 A, 75 to 250 VAC          E5AK/E5EK
Voltage pulse               NPN, 12 VDC                 E5AK/E5EK          2              E53-S
                            NPN, 24 VDC                 E5AK/E5EK
Linear current              PNP, 24 VDC                 E5AK/E5EK          2              E53-Q
                            4 to 20 mA                  E5AK/E5EK
Linear voltage              0 to 20 mA                  E5AK/E5EK          2              E53-Q3
                            0 to 10 VDC                 E5AK/E5EK
Relay/Relay                 0 to 5 VDC                  E5AK/E5EK          2              E53-Q4
Relay/Pulse                 SPST/SPST, 5 A, 250 VAC     E5CK
                            SPST, 5 A/NPN, 24 VDC       E5CK               2              E53-C3
Relay/Linear current        SPST, 5 A/PNP, 24 VDC       E5CK
                            SPST, 5 A/4 to 20 mA        E5CK               2              E53-C3D
Relay/Linear voltage        SPST, 5 A/0 to 20 mA        E5CK
Pulse/Pulse                 SPST, 5 A/0 to 10 VDC       E5CK               2              E53-V34
                            NPN/NPN, 24 VDC             E5CK
Computer communications     PNP/PNP, 24 VDC             E5CK               2              E53-V35
                            RS-232C                     E5AK/E5EK
                            RS-232C                     E5CK               1              E53-R4R4
                            RS-422                      E5AK/E5EK
                            RS-485                      E5AK/E5EK          1              E53-Q4R4
                                                        E5CK
                                                        E5AK/E5EK          1              E53-Q4HR4
                                                        E5CK
                                                        E5AK/E5EK          1              E53-C4R4
                                                        E5CK
                                                                           1              E53-C4DR4

                                                                           1              E53-V44R4

                                                                           1              E53-Q4Q4

                                                                           1              E53-Q4HQ4H

                                                                           3/1            E53-AK01

                                                                           1              E53-CK01

                                                                           3/1            E53-AK02

                                                                           3/1            E53-AK03

                                                                           1              E53-CK03

Event input                 For remote set point                           3/1            E53-AKB
Transfer output             For remote set point
                            4 to 20 mA                                     1              E53-CKB
                            4 to 20 mA
                                                                           3/1            E53-AKF

                                                                           1              E53-CKF

Note: If the control period is less than 5 seconds, use an SSR (solid state relay) or pulse voltage output.

J Accessories (Order Separately)

         Description        Specifications              Compatible         Max. quantity                     Model
                                                         controller
Current transformer; order
only if using heater        50 A load, 5.8 mm hole dia. E5AK/E5EK          1              E54-CT1
burnout alarm function
Terminal cover (supplied    120 A load, 12 mm hole dia. E5AK/E5EK          1              E54-CT3
with Standard models)
                            Provides finger protection  E5AK               1              E53-COV0809
Software                    from terminals (VDE0106     E5CK
                            part 100)                   E5EK               1              E53-COV07
                                                        All
                            For setup and monitoring;                      1              E53-COV08
                            requires optional computer
                            communications board                           1              Thermo Tools

                                                                                          (See Note)

Note: Contact Omron for current version information.

2  Digital Process Controller E5K
Input Types (selectable with input jumper connector)
Thermocouple

   Input (field     K1 K2 J1 J2                       T       E      L1 L2              U        N      R      S       B            W PLII
   selectable)
  (See Notes)       --200  0.0     --100  0.0        --199.9  0      --100  0.0        --199.9   --200  0      0       100          0      0
Range C            to     to      to     to         to       to     to     to         to        to     to     to      to           to     to
                    1,300  500.0   850    400.0      400.0    600    850    400.0      400.0     1,300  1,700  1,700   1,800        2,300  1,300
                F
                    --300  0.0     --100  0.0        --199.9  0      --100  0.0        --199.9   --300  0      0       300          0      0
                    to     to      to     to         to       to     to     to         to        to     to     to      to           to     to
                    2,300  900.0   1,500  750.0      700.0    1,100  1,500  750.0      700.0     2,300  3,000  3,000   3,200        4,100  2,300

Note: 1. Setting number is factory-set to 2 (K1).
        2. Thermocouple W is W/Re5-26 (tungsten rhenium 5, tungsten rhenium 26).

Platinum Resistance Thermometer (RTD's)

Range               Input (field selectable)                                   JPt100                                        Pt100
                                                 C           --199.9 to 650.0                          --199.9 to 650.0
                                                 F           --199.9 to 999.9                          --199.9 to 999.9

Current/Voltage                                      Current input                                      Voltage input
         Input (field selectable)                                                                          0 to 5 V

                                          4 to 20 mA          0 to 20 mA               1 to 5 V                                     0 to 10 V

Note: When a current/voltage input is selected, the decimal point is fully adjustable.

                                                                            Digital Process Controller E5K 3
Specifications

J Ratings

Model                                                    E5jK Standard

Supply voltage                                           100--240 VAC, 50/60 Hz

Operating voltage range                                  85% to 110% of rated supply voltage

Power consumption                           E5AK         16 VA

                                            E5EK         15 VA

                                            E5CK         10 VA (at 100 VAC)
                                                         14 VA (at 240 VAC)

Input              Thermocouple                          K, J, T, E, L, U, N, R, S, B, W, PLII

                   Platinum resistance                   JPt100, Pt100
                   thermometer (RTD)

                   Current input                         4 to 20 mA, 0 to 20 mA

                   Voltage input                         1 to 5 V, 0 to 5 V, 0 to 10 V

Mean Time Between Failure                                15.4 years (135,000 hours)

Control output     Relay                                 SPST, 3 A at 250 VAC (resistive load)
(See Note 1)                                             Mechanical life expectancy: 10,000,000 operations min.
                                                         Electrical life expectancy: 100,000 operations min.

                   Voltage                  NPN          20 mA at 12/24 VDC (with short-circuit protection)
                   (pulse)                  PNP
                                            0 to 10 VDC  20 mA at 24 VDC (with short-circuit protection)
                   Linear                                Permissible load impedance: 1 k min.
                   voltage                               Resolution: Approximately 2600 steps

                   Linear                   4 to 20 mA   Permissible load impedance: 500  max.
                   current                               Resolution: Approximately 2600 steps

                                            0 to 20 mA   Permissible load impedance: 500  max.
                                                         Resolution: Approximately 2600 steps

Auxiliary output   SPST-NO                  E5AK         3 A at 250 VAC (resistive load)

                                            E5EK         3 A at 250 VAC (resistive load)

                                            E5CK         1A at 250 VAC (resistive load)

Control method (See Note 2)                              ON/OFF, Advanced PID Control (with auto-tuning) or Self-tuning

Setting method                                           Digital setting using front panel keys or communications features

Indication method -- 7-seg. digital display and LEDs E5AK: PV = 15 mm, SP = 10.5 mm
                                                                             E5EK: PV = 14 mm, SP = 9.5 mm
                                                                             E5CK: PV = 12 mm, SP = 8 mm

Potentiometer for valve positioning                      100  to 2.5 k
(for E5AK-PRR and E5EK-PRR only)

Event input        Contact                  ON           1 k max.
                   input                    OFF          100 k min.

                                No-contact  ON           residual voltage: 1.5 V max.
                                input       OFF
                                                         leakage current: 0.1 mA max.
Transmission output                                      4 to 20 mA, permissible load impedance: 600  max.,
                                                         resolution: Approximately 2600 steps

Remote SP input                             Current      4 to 20 mA (Input impedance: 150 )
(for E5AK and E5EK only)                    input

Current Transformer input (for E5AK and E5EK             Connect only an Omron Current Transformer (E54-CT1 or E54-CT3)
only)

Other functions    Standard                              Manual output, heating/cooling control, SP limiter, loop burnout alarm, SP
                                                         ramp, MV limiter, MV change rate limiter, input digital filter, input shift,
                                                         run/stop, protect functions

                   Option                                Multiple SP, run/stop selection, transfer output functions, auto/manual
                                                         Communications (RS-232C, RS-422, or RS-485), Loop Break Alarm, and
                                                         Transfer Output.

Standards                                   UL           File No.: E68481

                                            CSA          File No.: LR59623

                                            CE           File No.: EN50081-2; EN50082-2; IEC 1010-1

Note: 1. All control outputs are insulated from the input circuit.
        2. Fuzzy self-tuning is available only when using the Digital Controller in standard control operation with temperature input.

4            Digital Process Controller E5K
J Characteristics

Indication accuracy (See Note)           Thermocouple:
                                         0.3% of indication value or 1C, whichever is greater, 1 digit max.

                                         Platinum resistance thermometer:
                                         0.2% of indication value or 0.8C, whichever is greater, 1 digit max.

                                         Analog input: 0.2% (of indication value) 1 digit max.

Hysteresis                               0.01% to 99.99% FS (in units of 0.01% FS)

Proportional band (P)                    0.1% to 999.9% FS (in units of 0.1% FS)

Integral (reset) time (I)                0 to 3,999 s (in units of 1 s)

Derivative (rate) time (D)               0 to 3,999 s (in units of 1 s)

Control period                           1 to 99 s (in units of 1 s)

Manual reset value                       0.0% to 100.0% (in units of 0.1%)

Alarm setting range                      --1,999 to 9,999 or --199.9 or 999.9 (decimal point position dependent on input type)

Sampling period             Temperature 250 ms scan rate
                            input

                            Analog       100 ms scan rate
                            input

Insulation resistance                    200 M min. (at 500 VDC)

Dielectric strength         Malfunction  2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Vibration resistance        Mechanical   10 to 55 Hz, 10 m/s2 (approx. 1G) for 10 min each in X, Y, and Z directions
                            Malfunction  10 to 55 Hz, 20 m/s2 (approx. 2G) for 2 hrs each in X, Y, and Z directions
Shock resistance                         200 m/s2 min. (approx. 20G), 3 times each in 6 directions
                                         (100 m/s2 (approx. 10G) applied to the relay)

Ambient temperature         Mechanical   300 m/s2 min. (approx. 30G), 3 times each in 6 directions
                            Operating    --10C to 55C (14F to 131F ) with no icing; with 3-year warranty period: --10C to 50C
                                         (14F to 122F )

                            Storage      --25C to 65C (--13F to 149F ) with no icing

Ambient humidity            Operating 35% to 85% RH

Enclosure ratings           Front panel NEMA 4X for indoor use (equivalent to IP66)

                            Rear case IEC standard IP20

                            Terminals IEC standard IP00

Memory protection                        Non-volatile memory (number of writings: 100,000 operations)

Weight                      E5AK         Approx. 450 g

                            E5EK         Approx. 320 g

                            Mounting     Approx. 65 g
                            bracket

                            E5CK         Approx. 170 g

                            Adapter      Approx. 10 g

EMC                                      Emission Enclosure:                      EN55011 Group 1 class A
                                         Emission AC Mains:                       EN55011 Group 1 class A
                                         Immunity ESD:                            EN61000-4-2: 4 kV contact discharge (level 2)
                                         Immunity RF-interference:
                                                                                                       8 kV air discharge (level 3)
                                         Immunity Conducted Disturbance:          ENV50140: 10 V/m (amplitude modulated,
                                         Immunity Burst:
                                                                                                       80 MHz to 1 GHz) (level 3)
                                                                                                       10 V/m (pulse modulated, 900
                                                                                                       MHz)
                                                                                  ENV50141: 10 V (0.15 to 80 MHz) (level 3)
                                                                                  EN61000-4-4: 2 kV power-line (level 3)
                                                                                                       2 kV I/O signal-line (level 4)

Standards -- Approvals                   UL1092, CSA22.2 No. 14, CSA22.2 No. 1010-1
                                         Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
                                         Conforms to VDE0106/part 100 (Finger Protection)

Note: Indication Accuracy --

                Of the K1, T, and N thermocouples at a temperature of -100C or less: 2C 1 digit maximum.
                Of the U, L1, and L2 thermocouples at any temperature: 2C 1 digit maximum.
                Of the B thermocouple at a temperature of 400C or less: unrestricted.
                Of the R and S thermocouples at a temperature of 200C or less: 3C 1 digit maximum.
                Of the W thermocouple at any temperature: 0.3% of the indicated value or 3C, (whichever is greater) 1 digit maximum.
                Of the PLII thermocouple at any temperature: 0.3% or 2C, whichever is greater 1 digit maximum.

                                                                         Digital Process Controller E5K 5
J Option Board Ratings and Characteristics

Event inputs     Interface          Contact input:
Communications                      ON: 1 k max., OFF: 100 k min.
                 Transmission
Transfer output  method             No-contact input:
                                    ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.
                 Synchronization
                 method             RS-232C and RS-485; RS-422 for E5AK and E5EK only

                 Baud rate          Half-duplex

                                    Start-stop synchronization (asynchronous method)

                                    1.2/2.4/4.8/9.6/19.2 kbps

                                    4 to 20 mA:

                                    Permissible load impedance: E5AK and E5EK = 600  max.
                                                               E5CK = 500  max.

                                    Resolution:                E5AK and E5EK = approx. 2,600 steps

                                                               E5CK = approx. 2,600 steps

                                    RS-232C Peer-to-peer only; maximum cable length = 15 m (49.2 feet)
                                    RS-422 and RS-485 32 controller maximum to host computer; maximum cable length = 500 m
                                    (1640 feet)

J Current Transformer Ratings

Part number                         E54-CT1                                          E54-CT3
Max. continuous heater current      50 amps                                          120 amps (See Note 1)
Dielectric strength                 1,000 VAC (for 1 min)
Vibration resistance                50 Hz, 98 m/s2 (10G)                             Approx. 50 g
Weight                              Approx. 11.5 g                                   Armature: 2; Plug: 2
Accessories                         -- --

Note: 1. Use within the max. heater current rating of controller table shown below.

J Heater Burnout Alarm

Max. heater current                 Single-phase 50 A AC
Heater current value display        5% FS 1 digit max.
accuracy
                                    0.1 to 49.9 A (in units of 0.1 A) (See Note 1)
Heater burnout alarm setting range  190 ms (See Note 2)
Min. detection ON time

Note: 1. The heater burnout alarm is always OFF if the alarm is set to 0.0 A and always ON if the alarm is set to 50.0 A.

        2. No heater burnout detection or heater current value measurement is possible if the control output (heat) is ON for less than
             190 ms.

6  Digital Process Controller E5K
Nomenclature                  No. 1 display          Operation Indicators
                              No. 2 display
J E5AK                        Up Key/Down Key         OUT1

Operation                No. 1 display                  Lit when control output 1 turns ON.
Indicators               No. 2 display
A/M Key                  Up Key/Down Key             OUT2
Display Key
                                    No. 1 display        Lit when control output 2 turns ON.
J E5EK                              No. 2 display
                                    Up Key/Down Key   SUB1
Operation Indicators
            Display Key            No. 1 display         Lit when the output function assigned
                 A/M Key           No. 2 display         to auxiliary output 1 turns ON.
                                   Up Key/Down Key
J E5CK                                                SUB2 (for E5AK and E5EK only)

Operation                                               Lit when the output function assigned
Indicators                                              to auxiliary output 2 turns ON.

      A/M Key                                        MANU
Display Key
                                                         Lit when the manual operation mode
J E5CK-302                                               is being used.

Operation                                             STOP
Indicators
                                                         Lit when control operation has been
    AT Key                                               stopped.
Display Key
                                                      RMT

                                                         Lit during remote communications
                                                         operation.

                                                      AT

                                                         Flashes during auto-tuning.
                                                         Auto-tuning is completed when this
                                                         LED stops flashing.

                                                      RSP (for E5AK and E5EK only)

                                                         Lit during remote SP operation.

                                                      Bar Graph (for E5AK only)

                                                         On a standard model (E5AK-AA2), this
                                                         bar graph indicates the manipulated
                                                         variable (heat) in 10% increments per
                                                         single segment. On a position-propor-
                                                         tional model (E5AK-PRR2), this bar
                                                         graph indicates the valve opening in
                                                         10% increments per single segment.

                                                     No. 1 Display
                                                     Displays the process value or parameter
                                                     symbols.

                                                     No. 2 Display
                                                     Displays the set point, set point during SP
                                                     ramp, manipulated variable, or parameter
                                                     settings.

                                                     A/M Key
                                                     Press to select the auto operation or manu-
                                                     al operation.

                                                     Up Key/Down Key
                                                     Press to increase or decrease the value on
                                                     the No.2 display.

                                                     Display Key
                                                     Press quickly (for less than 1 s) to shift the
                                                     display to the next parameter. When this key
                                                     is pressed for 1 s or more, the menu screen
                                                     will be displayed in any case.

                                                      AT

                                                         Press key for automatic tuning.

                                                      A/M

                                                         This feature is located in level one.
                                                         (Replaced AT feature in level one).

                                                     Digital Process Controller E5K 7
Operation

J Operating Parameters                                               To Access Protect Mode
                                                                     Press and hold the A/M Key and the Display Key for more than
Mode Selection                                                       1 second.

Press the Display Key for 1 sec. min. to switch to modes other than  To Return to the Main PV/SP Display from the Protect Mode
the manual or protect mode.                                          Press and hold the A/M Key and the Display Key for more than
The figure below (Menu Display) shows all modes in the order that    1 second.
they are displayed. Some parameters are not displayed, depending
on the protect mode setting and the option boards used.              To Access Manual Mode
                                                                     Press and hold the A/M Key for more than 1 second.
Menu Display
                                                                     To switch parameters within a mode, use the Display Key.
              1 second min.                                          Press the display key for less than one second to move between
                                                                     parameters.
                             Level 0 mode
                                                                     Note: 1. In Level 0 mode, Level 1 mode, and Level 2 mode:
              1 second min.                                                         The controller will maintain control of the process.

                             Level 1 mode

                             Level 2 mode

                             Setup mode

                             Expansion mode                          2. In Setup mode, Expansion mode, Option mode,
                             Option mode                                 and Calibration mode: Control of the process is not
                             Calibration mode                            maintained. The outputs are inactive.

                                                                     3. Option Mode will be accessible only when an option
                                                                         board is installed in the controller.

J Parameters And Menus -- For Setting The Controller

Protect Mode  Limits use of the menu and A/M Keys.
              The protect function prevents unwanted modification of parameters and can also be used to prevent switching between
              the auto and manual operation.

Manual Mode   Sets the controller to manual operation mode.
              You can only manually adjust the manipulated variable (MV) in this mode.

Level 0 Mode  For normal operation.
              Change: the set point during operation, and start or stop Controller operation; and, (only in this mode) monitor the
              process value, ramp SP, and manipulated variable.

Level 1 Mode  For adjusting primary control parameters.
              Execute: AT (auto-tuning); set alarm values; set the control period; and, set PID parameters.

Level 2 Mode  For adjusting secondary control parameters.
              Set parameters for: limiting the manipulated variable and set point; switch between the remote and local modes; set the
              loop break alarm (LBA), alarm hysteresis, and the digital filter value of inputs.

Setup Mode    For setting the basic specifications.
              Set parameters for: input type, scaling, output assignments and direct/reverse operation.

Expansion Mode For setting expanded functions.

                              Set: ST (self-tuning), SP setting limiter. Select: advanced PID or ON/OFF control. Specify the standby sequence

                              resetting method. Initialize parameters; and, set the time for automatic return to the monitoring display.

Option Mode   For setting option functions.
              Set: the communications conditions; transfer: output and event input parameters to match the type of Option Board
              installed in the Controller. This mode will be accessible only when an option board is installed in the controller.

Calibration Mode For calibrating inputs and transfer output.

                              Calibrate the selected input type. Transfer output can be calibrated only when the Communications Unit (E53-CKF) has

                              been installed in the Controller.

8            Digital Process Controller E5K
Dimensions

Unit: mm (inch)

J E5AK

                                          96 (3.78) x 96 (3.78)  13.5       100 (3.94)                                  Panel Cutouts
                                                                 (0.53)
                                                                                                                                                   110 min.
                                                                                        91 (3.58) x 91 (3.58)
                                                                                            112 (4.41)         120 min.

                                                     Note: 1. Recommended panel thickness is 1 to 8 mm.

                                                             2. Maintain the specified vertical and horizontal mounting space between each Unit.
                                                                  Units must not be closely mounted vertically or horizontally.

J E5EK                                    48 (1.89)              13.5       100 (3.94)                           Panel Cutouts
J E5CK                                                           (0.53)
                                                                                                                         60 min.

                                                       96                               91 (3.58)
                                                     (3.78)                                112 (4.41)

                                                                                                       120 min.

                                                     Note: 1. Recommended panel thickness is 1 to 8 mm.

                                                               2. Maintain the specified vertical and horizontal mounting space between each Unit.
                                                                    Units must not be closely mounted vertically or horizontally.

                                                           58 (2.28)          13        100 (3.94)
                                                     53 (2.09) x 53 (2.09)  (0.51)

                                                                                                                 48 (1.89)

                 Panel Cutouts                                                                                                                      44.8 (1.76) x 44.8 (1.76)

                                 65 min.             Note: 1. Recommended panel thickness is 1 to 5 mm.
                                                               2. Maintain the specified vertical and horizontal mounting space between each Unit.
60 min.              +0.6                                           Units must not be closely mounted, either vertically or horizontally.
                     0
                 45

                           45  +0.6
                               0

                                                                                        Digital Process Controller E5K 9
J E5CK-302

The E5CK-302 model has the same dimension and cutouts as the E5CK.

J Accessories (Order Separately)

Terminal Cover for E5AK                                                                                             22.05    Terminal Cover for E5EK
                                                                                                                    (0.87)
E53-COV0809                                                                                                                  E53-COV08

                                            43.2 (1.70)                                                                                                                    43.2 (1.70)

         89 (3.50)                                                                                       89 (3.50)                                89 (3.50)
                                            1.5 3                                                                                                                                   1.5 3
                                                                                    33

Terminal Cover for E5CK

E53-COV07

                                                                   44.3
                                                                  (1.74)

                                            44.3
                                           (1.74)

Current Transformer (E5AK and E5EK only for Heater Burnout Alarm)

E54-CT1                                                                                                             E54-CT3

                                                         21 (0.83)        5.8 dia.   2.8                                                   30                  2.36 dia.
                                                         15 (0.59)        (0.23)    (0.11)                                                (1.18)
                                                                                                                                                  12 dia.
                                                                                             7.5 (0.30)                                           (0.47)

           25       3                                                                                                        40 (1.57)
         (0.98)  (0.12)                                                                                                      x 40 (1.57)

                                                         40 (1.57)

           10                                                                                                                                              Two, M3 (depth: 4)
         (0.39)
                                                                                                                             15
                                                         30 (1.18)
                                                                                                                                               30
                                                                                                                                             (1.18)

10       Digital Process Controller E5K
Installation

J Remove Controller From Rear Housing

E5AK and E5EK

To pull out the internal mechanism from the housing, use a Phillips screwdriver matching the screw on the lower part of the front panel.
1. Turn the screw counterclockwise while pressing the hook on the upper part of the front panel.
2. Carefully pull out the internal mechanism while holding the left and right sides of the front panel.

                                  Hook

E5CK

      Terminals                                 First, while pressing the hooks on the left and right sides of the
                                                front panel, pull the internal mechanism from the housing.
                        Output
                        Board

                                Housing (case)

Input Type                      Front Panel
Jumper Connector

                Option
                Board

                                                Digital Process Controller E5K 11
J Settings

Note: Always turn off the power supply to the Digital Controller before changing any switch settings.

On a standard model, set up the Output Modules for control outputs 1 and 2 before mounting the Controller.

On a position-proportional model, the Relay Output Module is already set. Do not change that set-up parameter. Do not replace with
other Output Modules.

Setting Up and Removing the Output Module

Setting Up the Output Module                               Removing the Output Module

When setting up the Output Modules, pull out the internal  To replace the Output Module, use a flat-blade screwdriver to
mechanism from the housing and insert the Output Modules   push up the Output Module.
into the sockets for control outputs 1 and 2.

Setting Up the Option/Output Board                         2. Insert the Option Boards into the sockets for options 1 to 3.
                                                                The following diagram shows the relationship between the
E5AK                                                            Option Boards and mounting positions.
1. Remove the Power Board and Option Boards in the order

     shown in the following diagram.

    Power  Option
    board  board

                                                           3. Mount the option boards and the power board in the
                                                                order shown.

12         Digital Process Controller E5K
E5EK                                                              2. Insert the Option Board into the socket for option 1. The
                                                                       following diagram shows the relationship between the
1. Remove the Power Board in the order shown in the following          Option Board and mounting position.
     diagram.

           Power                                                  3. Mount the option boards and the power board in the order
           board                                                       shown.

E5CK                                                              Set up the Option Board

1. Two rectangular holes are provided on the Power Board         1. Place the bottom of the Controller facing up, fit the board
      (right side of Controller). Fit the two protrusions of the      horizontally into the connector on the power board (right
      output board into these two holes.                              side of controller).

2. With the output board fitted into the Power Board, fit the    2. With the Power Board connected, fit the board vertically
      output board into the connector on the control board (left      into the connector on the control board (left side of
      side of Controller).                                            Controller).
                      1
                                                                                                                         1
          2
                                                                                                                 2

                                                                  Digital Process Controller E5K 13
J Mounting Controller                                                                               3. Tighten the mounting bracket screws on the upper and lower
                                                                                                         parts in small increments alternately and equally until the
E5AK and E5EK                                                                                            ratchet start to slide.

1. Insert the controller into the panel's mounting hole at the
     position shown in the figure below.

2. Fit the mounting bracket (accessory) into the mounting
     slots on the top and bottom of the rear case.

E5CK

1. Insert the E5CK Controller into the cutout on the panel,
      as shown in the figure here.

2. Push the adapter along the Controller body from the ter-
      minals up to the panel, and fasten temporarily.

3. Tighten the two mounting screws on the adapter. When
      tightening screws, tighten the two screws alternately
      keeping the torque to approximately 0.29 to 0.39 N S m,
      or 3 to 4 kgf S cm.

                                               Adapter

                                                                                 Panel

                                                                                 Watertight gasket

14  Digital Process Controller E5K
J Mounting Terminal Cover                                       E5CK

E5AK and E5EK                                                     1. The E5CK-AA1-500 Controller is provided with a Terminal
                                                                       Cover (E53-COV07). Fasten the Terminal Cover as fol-
1. Fasten the terminals covers as follows by using the plastic         lows by using the plastic pin.
     pins. Plastic pins are provided with the terminal covers.

                                                                              E5CK
                                                                E53--COV07

J Wiring Terminals for E5AK                                     Wiring

E5AK Terminal Arrangement                                       In the following wiring diagrams, the left side of the terminal
                                                                numbers indicate the inside of the Controller.
AC100--240V~
50/60 Hz                                                        Power Supply

              OPTION   OPTION                                   Input power to terminal numbers 9 and 10. Power specifications
                  2        1                                    are as follows: 100 to 240 VAC, 50/60 Hz, approx. 16 VA

         OPTION        SENSOR
              3         INPUT

TRSF: Transfer output
EV1 to 4: Event input
PTMR: Potentiometer
RSP: Remote SP input

                                                                Digital Process Controller E5K 15
Wiring Terminals for E5EK                     Power supply

E5EK Terminal Arrangement                     Input power to terminal numbers 9 and 10. Power specifications
                                              are as follows: 100 to 240 VAC, 50/60 Hz, approx. 15 VA

AC100--240V~
50/60 Hz

                               OPTION
                                   1

                               SENSOR
                                INPUT

    TRSF:     Transfer output
    EV1/2:    Event input
    PTMR:     Potentiometer
    RSP:      Remote SP input

J Wiring Terminals for E5CK                   Wiring Precautions

E5CK Terminal Arrangement                      To protect the Controller and its lines from external noise, use
                                                   the wire ducts to separate input leads and power lines.
                 OUT1
                                              Use solderless terminals when wiring the Controller.
100--240VAC   5  11 12   10                   Tighten the terminal screws using a torque no greater than
SUB1
              4          9             OUT2        0.78 N S m, or 8 kgf S cm max. DO NOT tighten the terminal
                                       INPUT       screws too tightly.
              3          8
                                              Power Supply
              2          7
                                              Input 100 to 240 VAC to terminal numbers 4 and 5.

              1  13 14   6

                                              5  11 12  10

                                              4         9

                 OPTION                       3         8

                                              2         7

                                              1  13 14  6

16           Digital Process Controller E5K
J Input Wiring

E5AK

Connect the sensor input to terminal numbers 11 to 14 and 33 as follows according to the input type.

E5EK

Connect the sensor input to terminal numbers 11 to 14 and 23 as follows according to the input type.

E5CK

Connect the sensor input to terminal numbers 6 to 8 as indicated here, according to the input type.

5  11 12 10                      8                  8                         8                                  8

4         9                   -                     7              -                                  -

                                 7                                            7                                  7
                                                                  V                                   mA
3         8                                                  6
                                                                              6                                  6
2         7                            6    Platinum resistance
                                            thermometer (RTD)      +                                  +
   13 14     Input type       +
                                                                 Voltage input                         Current input
             Internal jumper  Thermocouple
             setting                                                      V                                 I
1         6

                                            TC  PT

Match the inputs with the internal jumper settings for each input type. For thermocouple or platinum resistance thermometer inputs, set
the internal jumper to a common position (TC/PT) as the temperature input.

                                                       Digital Process Controller E5K 17
J Control Output

E5AK Control Output

Terminal numbers 7 and 8 are for control output 1 (OUT1), and terminal numbers 5 and 6 are for control output 2 (OUT2). The following
diagrams show the available Output Modules and their internal circuits.

E5EK Control Output

Terminal numbers 7 and 8 are for control output 1 (OUT1), and terminal numbers 5 and 6 are for control output 2 (OUT2). The following
diagrams show the available Output Modules and their internal circuits.

With E53-Vjj Output Modules, approx. 2 V is output for one second after the power is interrupted.

E5AK-PRR2/E5EK-PRR2 Controllers

The E5AK-PRR2 and E5EK-PRR2 Controllers are supplied with relay output. This relay output is not compatible with any other module.
When replacing the Output Module, use the E53-R. The following diagrams show the relationship between terminals and open/close relay
settings.

    8  6

    7      5

Open   Close

18     Digital Process Controller E5K
E5CK Control Output

Terminal numbers 11 and 12 are for control output 1 (OUT1). The five output types and internal circuits are available according to the
Output Board.

                                                       +               +                  +                     +                 +

5   11 12 10                          11                           11                 11                    11                11

                                                       v                  L                      L                     L  mA

4              9                                                                                         V                           L

3              8                               12                   12       GND   12                           12                       12
                                        Relay
2              7     Output type      E53-R4R4                        -                 -                          -                      -
                     Part number
                                                                NPN               PNP                      0 to 10 V      4 to 20 mA/0 to 20 mA

1   13 14      6                                            E53-Q4R4             E53-Q4HR4               E53-V44R4               E53-C4R4
                                                            E53-Q4Q4             E53-Q4HQ4H                                      E53-C4DR4

Terminal numbers 9 and 10 are for control output 2 (OUT2). The three output types and internal circuits are available according to the
Output Board.

                                                                                      +                         +

                                                       10                    +v   10                        10

                                                                                             L                         L

                                                         9                           9              GND       9
                                                   Relay                                  -                         -
                   Output type
                                                                                  NPN                       PNP

                   Part number        E53-R4R4 /E53-V44R4                        E53-Q4Q4           E53-Q4HQ4H
                                      E53-Q4R4 /E53-C4R4
                                      E53-Q4HR4/E53-C4DR4

J Auxiliary Output                                                        E5EK

E5AK                                                                      Terminal numbers 3 and 4 are for auxiliary output 1 (SUB1) and
                                                                          terminal numbers 1 and 2 are for auxiliary output 2 (SUB2). The
Terminal numbers 3 and 4 are for auxiliary output 1 (SUB1) and            following diagrams show the internal equalizing circuits for the
terminal numbers 1 and 2 are for auxiliary output 2 (SUB2). The           auxiliary outputs:
following diagrams show the internal equalizing circuits for the
auxiliary outputs:

10         30 31 32 20             4                                      10 21 22 20                      4

9          29        19                                                   9           19                   3
                                                                                                    Auxiliary output 1
8          28        18            3                                      8           18
                                                                                                           2
7          27        17            Auxiliary output 1                     7           17
6          26        16                                                                                    1
                                                                          6           16            Auxiliary output 2

5          25        15            2                                      5           15

4          24        14                                                   4           14

3          23        13                                                   3           13

2          22        12            1                                      2           12

1          21 33 11                Auxiliary output 2                     1 23 11

Output specifications are as follows: SPST-NO, 3 A at 250 VAC             Output specifications are as follows: SPST-NO, 3 A at 250 VAC

E5CK

Terminal numbers 2 and 3 are for auxiliary output 1 (SUB1). The
internal equalizing circuit for auxiliary output 1 is as follows:

5   11 12      10

4              9

                                3

3              8

2              7                2

1   13 14      6

                                                                             Digital Process Controller E5K 19
J CT Input/Potentiometer (for E5AK and E5EK only)

E5AK CT Input/Potentiometer                                      E5EK CT Input/Potentiometer

When using the HBA function on the E5AK-AA2 Controller,          When using the HBA function on the E5EK-AA2 Controller,
connect Current Transformer input (CT) to terminal numbers 15    connect Current Transformer input (CT) to terminal numbers 15
to 17. When monitoring the valve opening on the E5AK-PRR2        to 17. When monitoring the valve opening on the E5EK-PRR2
Controller, connect the potentiometer (PTMR) to terminal         Controller, connect the potentiometer (PTMR) to terminal
numbers 15 to 17. Connect each of these inputs as follows:       numbers 15 to 17. Connect each of these inputs as follows:

10  30 31 32 20       17                                         10 21 22 20  17

9   29  19            16        CT                               9  19        16        CT

8   28  18                                                       8  18

7   27  17            15                                         7  17        15

6   26  16            CT input                                   6  16        CT input
                          O                                                       O
5   25  15                                                       5  15
                      17                                                      17
4   24  14            16 W                                       4  14        16 W
                      15 C                                                    15 C
3   23  13                                                       3  13

2   22  12                                                       2  12

1   21 33 11          Potentiometer                              1 23 11      Potentiometer

For details on CT inputs, refer to Appendix, About Current       For details on CT inputs, refer to Appendix, About Current
Transformer in your User's Manual. For details on the            Transformer in your User's Manual. The potentiometer cannot be
potentiometer, refer to the Instruction Manual for the valve     used simultaneously with remote SP input. For details on the
connected to the Controller. The variable resistance range is    potentiometer, refer to the Instruction Manual for the valve
100  to 2.5 k.                                                   connected to the Controller. The variable resistance range is 100
                                                                  to 2.5 k.

J Remote Set Point Input (for E5AK and E5EK only)

E5AK Remote SP Input                                             E5EK Remote SP Input

Connect the input (RSP) to be used as the remote SP to terminal  Connect the input (RSP) to be used as the remote SP to terminal
numbers 21 and 22. Only 4 to 20 mA inputs can be connected.      numbers 15 and 16. However, note that the potentiometer cannot
Connect the input as follows:                                    be used simultaneously with remote SP input. Only 4 to 20 mA
                                                                 inputs can be connected. Connect the input as follows:

10  30 31 32 20

9   29  19                                                       10 21 22 20

8   28  18                                                       9  19

7   27  17            22 +                                       8  18        16 +
                               4 to 20 mA                                              4 to 20 mA
6   26  16                                                       7  17
                      21 --                                                   15 --
5   25  15                                                       6  16

4   24  14                                                       5  15

3   23  13                                                       4  14

2   22  12                                                       3  13

1   21 33 11                                                     2  12

                                                                 1 23 11

20  Digital Process Controller E5K
J Option Board Wiring

E5AK

Connect event inputs 1 and 2 (EV1/2) to terminal numbers 18 to 20, and event events 3 and 4 (EV3/4) to terminal numbers 24 to 26.
However, note that terminal numbers 18 to 20 cannot be used on Controllers with a communications function. Connect the event inputs as
follows:

10           30 31 32 20

9            29             19

8            28             18

7            27             17

6            26             16

5            25             15

4            24             14

3            23             13

2            22             12

1            21 33 11

Terminals 18 and 24 (COM) are connected internally.

                        SD      32 SDA    32 A                     +                      +                       +
                  20                SDB           B  EV1 20                 EV3 26                           30

                        RD      31        31                       +                      +      4 to 20 mA           L
                  19            19 RDA    19 A       EV2 19                 EV4 25
                                20 RDB    20 B
                        SG      18 SG                COM 18                 COM 24
                  18                                               --                     --

                                                       Event input 1 and 2                                   29
                                                       (no contact)                                               --

Option type       RS-232C       RS-422    RS-485                            Event input 3 and 4  Transfer output
Part number       E53-AK01      E53-AK02  E53-AK03                          (no contact)

Use event inputs under the following conditions:

Contact input                             ON: 1 k max.
No-contact input                          OFF: 100 k min.

                                          ON: Residual voltage 1.5 V max.,
                                          OFF: Leakage current 0.1 mA max.

Communications

Terminal numbers 18 to 20, 31 and 32 can be used only on Controllers with Communications Units (E53-AK01/02/03). For details on wir-
ing, refer to Chapter 6, Using the Communications Function in your User's Manual.

                                                                            Digital Process Controller E5K 21
E5EK

Connect event inputs 1 and 2 (EV1/2) to terminal numbers 18 to 20. However, note that terminal numbers 18 to 20 cannot be used on
Controllers with a communications function. Connect the event inputs as follows:

10 21 22 20

9            19

8            18

7            17

6            16

5            15

4            14

3            13

2            12

1 23 11

                  20 SD       22 SDA            A             +                        +                              +
                         RD       SDB   22         EV1 20               EV1 20                                   21

                  19          21                B              +                       +             4 to 20 mA           L
                         SG   19 RDA    21         EV2 19               EV2 19
                              20 RDB    19 A                                                                     22
                  18          18 SG     20 B       COM 18 --            COM 18                                        --
                                                                                       --
                    RS-232C    RS-422
Option type         E53-AK01            RS-485     Event input 1 and 2  Event input 1 and 2          Transfer output
Part number                   E53-AK02  E53-AK03         E53-AKB        (no contact)                     E53-AKF

                                                                            E53-AKB

Use event inputs under the following conditions:

Contact input                           ON: 1 k max., OFF: 100 k min.
No-contact input
                                        ON: Residual voltage 1.5 V max.,
                                        OFF: Leakage current 0.1 mA max.

Communications
Terminal numbers 18 to 20, 31 and 32 can be used only on Controllers with Communications Units (E53-AK01/02/03). For details on
wiring, refer to Chapter 6, Using the Communications Function in your User's Manual.

E5CK

Terminal numbers 1, 13, and 14 are valid only when the Option Board is set in the Controller

The following four connections are possible depending on the model of the Option Board.

5   11 12         10                                              +SD             A+                        +
                                                            13             13                          13
4                 9                                                                     13
                                                                   --R            B --  14                     4 to 20 mA
3                 8                                         14 D           14            1             14 --
                                                                                        Event input     1
2                 7                                                 SG      1           E53-CKB
                                                             1                                       Transfer output
1   13 14         6           Option type                               RS-485
                              Part number          RS-232C                                            E53-CKF
                                                   E53-CK01             E53-CK03

22           Digital Process Controller E5K
J Connection Example of Digital Controller And SSR

Digital Controller                                            SSR                     Load
                                                                                      Heater
                         +                     +

Voltage output                                    INPUT           LOAD                              Power supply
terminal (for driv-                                                                                 for load
ing SSR)

             --                                --

                            Connectable

                                                                                                     Power SSR

E5AK/E5EK

Digital Controller with
Voltage Output
(12 VDC, 40 mA max.)

E5CK

Digital Controller with
Voltage Output
(12 VDC, 20 mA max.)

Model                       G3PA/G3PB                              G3NA                              G3NE
Appearance

SSRs                        E5AK/E5EK: 8 pcs.                      E5AK/E5EK: 5 pcs.                 E5AK/E5EK: 2 pcs.
connected                   E5CK: 4 pcs.                           E5CK: 2 pcs.                      E5CK: 1 piece
in parallel
                            5 to 24 VDC                            5 to 24 VDC                       12 VDC
Rated
input                       Thin, SSR with built-in heat sink;     Standard model with screw termi-  Compact, low-cost model with tab
voltage                     1-phase and 3-phase models             nals                              terminals

Features

                                                                         Digital Process Controller E5K 23
Precautions

J Precautions when Wiring

Use wire ducts to separate input leads and power lines in          Tighten the terminal screws using a torque no greater than
     order to protect the Controller and its lines from external          0.78 N S m, or 8 kgf S cm max. Take care not to tighten the
     noise.                                                               terminal screws too tightly.

Solderless terminals are recommended when wiring the Con-
     troller.

Power Blocks

The E5AK/E5EK has independent power supplies for each of the terminal blocks shown below.

E5AK                               E5EK                                                    E5CK

                       *                                          *      *                                  *

      10  30 31 32 20                     10 21 22 20                                            5 11 12 10

      9   29  19                          9                          19

      8   28  18                          8                          18                          4  9

      7   27  17                          7                          17

      6   26  16                          6                          16                          3  8

      5 * 25  15                          5                          15                    *

      4   24  14                          4                          14                          2  7

      3   23  13                          3                          13

      2   22  12                          2                          12                          1 13 14 6

      1   21 33 11                        1 23 11

* Uses same internal power supply

Note: Terminals 21 and 22 of the E5EK belong to the B block when a transfer output is set to option 1 and to the C block for other
         Option Boards.

J Operating Environment                                              Connection

Keep within the rated ambient operating temperature, ambi-          To reduce inductive noise influence, the lead wires connect-
     ent operating humidity, and storage temperature ranges.              ing the input type to the Digital Controller must be separated
                                                                          from the power lines and load lines.
Use the Unit according to the vibration resistance, shock
     resistance, and enclosure ratings.                               Use the specified compensating conductors for thermocou-
                                                                          ples. Use lead wires having a small resistance for platinum
Do not use the Unit in places with corrosive gas or excessive           resistance thermometers.
     dust.
                                                                     Connection Example
Do not use the Unit near machines generating high-frequen-          Wire the terminals of the Unit using solderless terminals.
     cy noise.                                                       The tightening torque applied to the terminal screws of the

J Correct Use                                                             Unit must be approximately 0.78 N S m or 8 kgf S cm.
                                                                     Use the following type of solderless terminals for M3.5 screws.
Mounting
                                                                                                        7.2 mm max.
The dimensions of the Digital Controller conform to DIN
     43700.                                                                                             7.2 mm max.

Recommended panel thickness is 1 to 8 mm.
Mount the Unit horizontally.

24        Digital Process Controller E5K
J Operation                                                            Do not use excessive force when pulling out the internal
                                                                          mechanism from the housing. Protect the internal connector or
For models with alarm functions: The alarm outputs of a mod-            electronic parts of the Unit from shock. Protect against static
    el with an alarm function may not turn ON properly when the           discharge when changing the settings of the internal switch.
    model malfunctions. The use of alarm equipment with the               Changing the settings on a grounded conductive mat is rec-
    model is recommended.                                                 ommended.

The parameters and internal switch are set before shipping so       When connecting the Control Output Unit to the Temperature
    that the Unit will function normally. Change the settings of the      Controller or Digital Controller, make sure that the Control
    parameters and internal switch according to the application, if       Output Unit is a suitable type. The use of an improper type of
    necessary.                                                            Control Output Unit may cause the system to malfunction.

Several seconds are required until the relay is turned ON after      The heater burnout alarm will not be available if the Linear
    power has been supplied to the Digital Controller. You must           Output Unit is used.
    take this time delay into consideration when designing se-
    quenced circuits which incorporate a Digital Controller.

                                                                      Digital Process Controller E5K 25
Terms and Conditions of Sale

1. Offer; Acceptance. These terms and conditions (these "Terms") are deemed                      ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.
     part of all quotes, agreements, purchase orders, acknowledgments, price lists,              BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
     catalogs, manuals, brochures and other documents, whether electronic or in                  PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
     writing, relating to the sale of products or services (collectively, the "Products")        INTENDED USE. Omron further disclaims all warranties and responsibility of
     by Omron Electronics LLC and its subsidiary companies ("Omron"). Omron                      any type for claims or expenses based on infringement by the Products or oth-
     objects to any terms or conditions proposed in Buyer's purchase order or other              erwise of any intellectual property right. (c) Buyer Remedy. Omron's sole obli-
     documents which are inconsistent with, or in addition to, these Terms.                      gation hereunder shall be, at Omron's election, to (i) replace (in the form
                                                                                                 originally shipped with Buyer responsible for labor charges for removal or
2. Prices; Payment Terms. All prices stated are current, subject to change with-                 replacement thereof) the non-complying Product, (ii) repair the non-complying
     out notice by Omron. Omron reserves the right to increase or decrease prices                Product, or (iii) repay or credit Buyer an amount equal to the purchase price of
     on any unshipped portions of outstanding orders. Payments for Products are                  the non-complying Product; provided that in no event shall Omron be responsi-
     due net 30 days unless otherwise stated in the invoice.                                     ble for warranty, repair, indemnity or any other claims or expenses regarding
                                                                                                 the Products unless Omron's analysis confirms that the Products were prop-
3. Discounts. Cash discounts, if any, will apply only on the net amount of invoices              erly handled, stored, installed and maintained and not subject to contamina-
     sent to Buyer after deducting transportation charges, taxes and duties, and will            tion, abuse, misuse or inappropriate modification. Return of any Products by
     be allowed only if (i) the invoice is paid according to Omron's payment terms               Buyer must be approved in writing by Omron before shipment. Omron Compa-
     and (ii) Buyer has no past due amounts.                                                     nies shall not be liable for the suitability or unsuitability or the results from the
                                                                                                 use of Products in combination with any electrical or electronic components,
4. Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month or                 circuits, system assemblies or any other materials or substances or environ-
     the maximum legal rate, whichever is less, on any balance not paid within the               ments. Any advice, recommendations or information given orally or in writing,
     stated terms.                                                                               are not to be construed as an amendment or addition to the above warranty.
                                                                                                 See http://www.omron247.com or contact your Omron representative for pub-
5. Orders. Omron will accept no order less than $200 net billing.                                lished information.
6. Governmental Approvals. Buyer shall be responsible for, and shall bear all               14. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE
                                                                                                 FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
     costs involved in, obtaining any government approvals required for the impor-               LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY
     tation or sale of the Products.                                                             WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS
7. Taxes. All taxes, duties and other governmental charges (other than general                   BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
     real property and income taxes), including any interest or penalties thereon,               Further, in no event shall liability of Omron Companies exceed the individual
     imposed directly or indirectly on Omron or required to be collected directly or             price of the Product on which liability is asserted.
     indirectly by Omron for the manufacture, production, sale, delivery, importa-          15. Indemnities. Buyer shall indemnify and hold harmless Omron Companies and
     tion, consumption or use of the Products sold hereunder (including customs                  their employees from and against all liabilities, losses, claims, costs and
     duties and sales, excise, use, turnover and license taxes) shall be charged to              expenses (including attorney's fees and expenses) related to any claim, inves-
     and remitted by Buyer to Omron.                                                             tigation, litigation or proceeding (whether or not Omron is a party) which arises
8. Financial. If the financial position of Buyer at any time becomes unsatisfactory              or is alleged to arise from Buyer's acts or omissions under these Terms or in
     to Omron, Omron reserves the right to stop shipments or require satisfactory                any way with respect to the Products. Without limiting the foregoing, Buyer (at
     security or payment in advance. If Buyer fails to make payment or otherwise                 its own expense) shall indemnify and hold harmless Omron and defend or set-
     comply with these Terms or any related agreement, Omron may (without liabil-                tle any action brought against such Companies to the extent based on a claim
     ity and in addition to other remedies) cancel any unshipped portion of Prod-                that any Product made to Buyer specifications infringed intellectual property
     ucts sold hereunder and stop any Products in transit until Buyer pays all                   rights of another party.
     amounts, including amounts payable hereunder, whether or not then due,                 16. Property; Confidentiality. Any intellectual property in the Products is the exclu-
     which are owing to it by Buyer. Buyer shall in any event remain liable for all              sive property of Omron Companies and Buyer shall not attempt to duplicate it
     unpaid accounts.                                                                            in any way without the written permission of Omron. Notwithstanding any
9. Cancellation; Etc. Orders are not subject to rescheduling or cancellation                     charges to Buyer for engineering or tooling, all engineering and tooling shall
     unless Buyer indemnifies Omron against all related costs or expenses.                       remain the exclusive property of Omron. All information and materials supplied
10. Force Majeure. Omron shall not be liable for any delay or failure in delivery                by Omron to Buyer relating to the Products are confidential and proprietary,
     resulting from causes beyond its control, including earthquakes, fires, floods,             and Buyer shall limit distribution thereof to its trusted employees and strictly
     strikes or other labor disputes, shortage of labor or materials, accidents to               prevent disclosure to any third party.
     machinery, acts of sabotage, riots, delay in or lack of transportation or the          17. Export Controls. Buyer shall comply with all applicable laws, regulations and
     requirements of any government authority.                                                   licenses regarding (i) export of products or information; (iii) sale of products to
11. Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron:                   "forbidden" or other proscribed persons; and (ii) disclosure to non-citizens of
     a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship              regulated technology or information.
                                                                                            18. Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any right
        except in "break down" situations.                                                       and no course of dealing between Buyer and Omron shall operate as a waiver
     b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall          of rights by Omron. (b) Assignment. Buyer may not assign its rights hereunder
                                                                                                 without Omron's written consent. (c) Law. These Terms are governed by the
        constitute delivery to Buyer;                                                            law of the jurisdiction of the home office of the Omron company from which
     c. All sales and shipments of Products shall be FOB shipping point (unless oth-             Buyer is purchasing the Products (without regard to conflict of law princi-
                                                                                                 ples). (d) Amendment. These Terms constitute the entire agreement between
        erwise stated in writing by Omron), at which point title and risk of loss shall          Buyer and Omron relating to the Products, and no provision may be changed
        pass from Omron to Buyer; provided that Omron shall retain a security inter-             or waived unless in writing signed by the parties. (e) Severability. If any provi-
        est in the Products until the full purchase price is paid;                               sion hereof is rendered ineffective or invalid, such provision shall not invalidate
     d. Delivery and shipping dates are estimates only; and                                      any other provision. (f) Setoff. Buyer shall have no right to set off any amounts
     e. Omron will package Products as it deems proper for protection against nor-               against the amount owing in respect of this invoice. (g) Definitions. As used
        mal handling and extra charges apply to special conditions.                              herein, "including" means "including without limitation"; and "Omron Compa-
12. Claims. Any claim by Buyer against Omron for shortage or damage to the                       nies" (or similar words) mean Omron Corporation and any direct or indirect
     Products occurring before delivery to the carrier must be presented in writing              subsidiary or affiliate thereof.
     to Omron within 30 days of receipt of shipment and include the original trans-
     portation bill signed by the carrier noting that the carrier received the Products
     from Omron in the condition claimed.
13. Warranties. (a) Exclusive Warranty. Omron's exclusive warranty is that the
     Products will be free from defects in materials and workmanship for a period of
     twelve months from the date of sale by Omron (or such other period expressed
     in writing by Omron). Omron disclaims all other warranties, express or implied.
     (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION,
     EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-

Certain Precautions on Specifications and Use

1. Suitability of Use. Omron Companies shall not be responsible for conformity                   ADDRESS THE RISKS, AND THAT THE OMRON'S PRODUCT IS PROP-
     with any standards, codes or regulations which apply to the combination of the              ERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
     Product in the Buyer's application or use of the Product. At Buyer's request,               OVERALL EQUIPMENT OR SYSTEM.
     Omron will provide applicable third party certification documents identifying          2. Programmable Products. Omron Companies shall not be responsible for the
     ratings and limitations of use which apply to the Product. This information by              user's programming of a programmable Product, or any consequence thereof.
     itself is not sufficient for a complete determination of the suitability of the Prod-  3. Performance Data. Data presented in Omron Company websites, catalogs
     uct in combination with the end product, machine, system, or other application              and other materials is provided as a guide for the user in determining suitabil-
     or use. Buyer shall be solely responsible for determining appropriateness of                ity and does not constitute a warranty. It may represent the result of Omron's
     the particular Product with respect to Buyer's application, product or system.              test conditions, and the user must correlate it to actual application require-
     Buyer shall take application responsibility in all cases but the following is a             ments. Actual performance is subject to the Omron's Warranty and Limitations
     non-exhaustive list of applications for which particular attention must be given:           of Liability.
     (i) Outdoor use, uses involving potential chemical contamination or electrical         4. Change in Specifications. Product specifications and accessories may be
     interference, or conditions or uses not described in this document.                         changed at any time based on improvements and other reasons. It is our prac-
     (ii) Use in consumer products or any use in significant quantities.                         tice to change part numbers when published ratings or features are changed,
     (iii) Energy control systems, combustion systems, railroad systems, aviation                or when significant construction changes are made. However, some specifica-
     systems, medical equipment, amusement machines, vehicles, safety equip-                     tions of the Product may be changed without any notice. When in doubt, spe-
     ment, and installations subject to separate industry or government regulations.             cial part numbers may be assigned to fix or establish key specifications for
     (iv) Systems, machines and equipment that could present a risk to life or prop-             your application. Please consult with your Omron's representative at any time
     erty. Please know and observe all prohibitions of use applicable to this Prod-              to confirm actual specifications of purchased Product.
     uct.                                                                                   5. Errors and Omissions. Information presented by Omron Companies has been
     NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS                                  checked and is believed to be accurate; however, no responsibility is assumed
     RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT                                     for clerical, typographical or proofreading errors or omissions.
     ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
                OMRON ELECTRONICS LLC THE AMERICAS HEADQUARTERS
            Schaumburg, IL USA 847.843.7900 800.556.6766 www.omron247.com

OMRON CANADA, INC. HEAD OFFICE                                  OMRON ARGENTINA SALES OFFICE
Toronto, ON, Canada 416.286.6465 866.986.6766 www.omron.ca  Cono Sur 54.11.4787.1129

OMRON ELETRNICA DO BRASIL LTDA HEAD OFFICE                     OMRON CHILE SALES OFFICE
So Paulo, SP, Brasil 55.11.2101.6300 www.omron.com.br        Santiago 56.2206.4592

OMRON ELECTRONICS MEXICO SA DE CV HEAD OFFICE                   OTHER OMRON LATIN AMERICA SALES
Apodaca, N.L. 52.811.156.99.10 mela@omron.com                 56.2206.4592

H301-E3-02  Note: Specifications are subject to change.                      2008 Omron Electronics LLC  Printed in U.S.A.
This datasheet has been downloaded from:
            datasheet.eeworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

器件索引   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2020 EEWORLD.com.cn, Inc. All rights reserved