    Digital Controller

    E5AK

                                                                                                              CSM_E5AK_DS_E_3_1

Advanced Digital Controllers Ideal for

Worldwide Use

• Modular structure

• High-accuracy: 100 ms sampling (for analog input)

• Auto-tuning and fuzzy self-tuning

• Conforms to international EMC and safety standards.

• IP66/NEMA4 (indoor use) front face

• Remote set point

• Serial communications (RS-232C, RS-422 and RS-485) and

transfer output (4 to 20 mA)

• Position-proportional control model

• Heating/cooling control

         Refer to Safety Precautions for All Temperature Controllers.  Refer to E5@K Operation for operating

                                                                       procedures.

Model Number Structure

■ Model Number Legend

E5AK- @@@ @ -500

           1           2

1.  Model

    AA:    Standard model

    PRR: Position-proportional model

    T:     Programmable type

2.  Number of alarms

    2:     Two alarms

                                                                                                                                 1
                                                                                                                                            E5AK

Ordering Information

■ List of Models

             Description                                    Model                                                     Specification

Base Unit                              E5AK-AA2 AC100-240                                      Standard model

                                       E5AK-AA2-500 AC100-240                                  Standard model with terminal cover

                                       E5AK-PRR2 AC100-240                                     Position-proportional model

                                       E5AK-PRR2-500 AC100-240                                 Position-proportional model with terminal    cover

                                       E5AK-TAA2 AC100-240                                     Standard model

                                       E5AK-TAA2-500 AC100-240                                 Standard model with terminal cover

                                       E5AK-TPRR2 AC100-240                                    Position-proportional model

                                       E5AK-TPRR2-500 AC100-240                                Position-proportional model with terminal    cover

Note: 1.  When using the heater burnout alarm function with a standard model, the Linear Output Unit cannot be used for the control outputs (heat).

2.        Be sure to specify the Current Transformer, Output Unit, and Option Unit when ordering.

3.        The Digital Controller provides transfer outputs at 4 to 20 mA for the PV and other values and control outputs at 4 to 20 mA for the current

          outputs.

             Description                                    Model                                                     Specification

Output Unit                            E53-R                                                   Relay

                                       E53-S                                                   SSR

                                       E53-Q                                                   Pulse (NPN) 12 VDC

                                       E53-Q3                                                  Pulse (NPN) 24 VDC

                                       E53-Q4                                                  Pulse (PNP) 24 VDC

                                       E53-C3                                                  Linear (4 to 20 mA)

                                       E53-C3D                                                 Linear (0 to 20 mA)

                                       E53-V34                                                 Linear (0 to 10 V)

                                       E53-V35                                                 Linear (0 to 5 V)

Note: The Digital Controller  uses  a  dedicated, high-resolution Output    Unit.  The  E53-C  Current Output Unit for the E5@X cannot  be  used  with  the

Digital Controller.

             Description                                    Model                                                     Specification

Option Unit                            E53-AKB                                                 Event input

                                       E53-EN01                                                Communication (RS-232C)

                                       E53-EN02                                                Communication (RS-422)

                                       E53-EN03                                                Communication (RS-485)

                                       E53-AKF                                                 Transfer output

Note: 1.  The Option Unit can be used either by the E5AK or E5EK.

2.        The E5AK allows a maximum of three Option Units to be mounted. Refer to page 8 for mounting combinations.

          The E5EK allows only one Option Unit to be mounted.

Inspection Report

The Digital Controller can be provided together with an inspection report.

Refer to the following legend with the suffix “K” when ordering a model provided together with an inspection report.

E5@K-AA2-K, E5@K-PRR2-K, E5@K-TAA2-K, E5@K-TPRR2-K, E53-AKF-K

                                                                                                                                                             2
                                                                                                                                            E5AK

■ Accessories (Order Separately)

                Name                                             Model                                           Hole diameter

Current Transformer        E54-CT1                                                            5.8 mm

                           E54-CT3                                                            12.0 mm

Note: No CT is required unless the heater burnout alarm function is used.

                Name                                             Model                                           Connectable models

Terminal Cover             E53-COV0809                                                        E5AK

Note: The E53-COV0809 comes in a set with the two types of Terminal Covers listed on page 8.

Unit Label                                                                        Mounting Bracket

Model                      Y92S-L1                                                Model                          Y92H-5

Waterproof Packing                                                                Note: This mounting bracket set is included with the Temperature

                                                                                  Controller. The set includes one bracket for the top and one for

                Model                                                             the bottom.

Y92S-P4

The Waterproof Packing is provided with the Digital Controller.

Specifications

■ Ratings

                   Item                                                                  100 to 240 VAC type

Supply voltage                      100 to 240 VAC, 50/60 Hz

Power consumption                   E5AK:   16 VA

Operating voltage range             85% to 110% of rated supply voltage

Input                               Thermocouple:                                 K, J, T, E, L, U, N, R, S, B, W, PLII

                                    Platinum resistance thermometer:              JPt100, Pt100

                                    Current input:                                4 to 20 mA, 0 to 20 mA

                                    Voltage input:                                1 to 5 V, 0 to 5 V, 0 to 10 V

Input impedance                     Current input: 150 Ω; Voltage input: 1 MΩ min.

Control output                      Standard Model, Programmable Model

                                    According to Output Unit (see Output Unit Ratings and Characteristics)

                                    Position-proportional Model

                                    2 Relay outputs: SPST-NO, 1 A at 250 VAC (including inrush current) *1

Auxiliary output                    SPST-NO, 3 A at 250 VAC (resistive load)

Control method *2                   ON/OFF or 2-PID control (with auto-tuning)

Setting method                      Digital setting using front panel keys

Indication method                   7-segment digital display and LEDs

Potentiometer                       100 Ω to 2.5 kΩ

Event input                         Contact input:               ON: 1 kΩ max., OFF: 100 kΩ min.

                                    No-contact input: ON: residual voltage: 1.5 V max., OFF: leakage current: 0.1 mA max.

Transfer output                     4 to 20 mA, permissible load impedance: 600 Ω max., resolution: approx. 2,600

Remote SP input                     Current input: 4 to 20 mA (Input impedance: 150 Ω)

Current Transformer input           Connect an exclusive Current Transformer (E54-CT1 or E54-CT3)

Other functions                     Standard

                                    Manual output, heating/cooling control, SP limiter, loop burnout alarm, SP ramp, MV limiter, MV

                                    change rate limiter, input digital filter, input shift, run/stop, protect functions, scaling function.

                                    Option

                                    Multiple SP, run/stop selection, transfer output functions

Degree of protection                Conforms to IEC IP66 and NEMA4 (Indoor use)

Note: Do not use the output from an inverter as the power supply. Refer to Safety Precautions for All Temperature Controllers.

       *1.All control outputs are isolated electrically from the input circuits.

       *2.The E5AK-T/-TP do not support fuzzy self-tuning.

                                                                                                                                                    3
                                                                                                                                             E5AK

■ Input Ranges

Platinum Resistance Thermometer

Input (switch selectable)          JPt100                    Pt100

Range          °C             −199.9 to 650.0          −199.9 to 650.0

               °F             −199.9 to 999.9          −199.9 to 999.9

Setting                       0                        1

Thermocouple

Input (switch      K1         K2       J1          J2        T          E      L1       L2       U         N         R      S      B       W  PLII

selectable)

(See note.)

Range    °C    −200        0.0 to  −100         0.0 to    −199.9    0 to   −100      0.0 to  −199.9    −200      0 to   0 to   100 to  0 to   0 to

               to          500.0   to 850       400.0     to 400.0  600    to 850    400.0   to 400.0  to        1,700  1,700  1,800   2,300  1,300

               1,300                                                                                   1,300

         °F    −300        0.0 to  −100         0.0 to    −199.9    0 to   −100      0.0 to  −199.9    −300      0 to   0 to   300 to  0 to   0 to

               to          900.0   to           750.0     to 700.0  1,100  to        750.0   to 700.0  to        3,000  3,000  3,200   4,100  2,300

               2,300               1,500                                   1,500                       2,300

Setting        2           3       4            5         6         7      8         9       10        11        12     13     14      15     16

Note: Setting number is factory-set to 2 (K1).

Thermocouple W is W/Re5-26 (tungsten rhenium 5, tungsten rhenium 26).

Current/Voltage

Input (switch selectable)              Current input                                    Voltage input

                                  4 to 20 mA           0 to 20 mA          1 to 5 V         0 to 5 V       0 to  10 V

Range                         One of following ranges depending on results of scaling

                              −1999 to 9999

                              −199.9 to 999.9

                              −19.99 to 99.99

                              −1.999 to 9.999

Setting                       17                   18                  19               20             21

                                                                                                                                                     4
                                                                                                                                          E5AK

■ Characteristics

Indication accuracy (See note 1.)   Thermocouple:

                                    (±0.3% of indication value or ±1°C, whichever greater) ±1 digit max.

                                    Platinum resistance thermometer:

                                    (±0.2% of indication value or ±0.8°C, whichever greater) ±1 digit max.

                                    Analog input: ±0.2% FS ±1 digit max.

Hysteresis                          0.01% to 99.99% FS (in units of 0.01% FS)

Proportional band (P)               0.1% to 999.9% FS (in units of 0.1% FS)

Integral (reset) time (I)           0 to 3,999 s (in units of 1 s)

Derivative (rate) time (D)          0 to 3,999 s (in units of 1 s)

Control period                      1 to 99 s (in units of 1 s)

Manual reset value                  0.0% to 100.0% (in units of 0.1%)

Alarm setting range                 −1,999 to 9,999 or −199.9 or 999.9 (decimal point position dependent on input type or result of scaling)

Set time (See note 2.)              0 to 99 hrs 59 min or 0 to 99 min 59 s

Program capacity (See note 2.)      8 patterns, 16 steps

Programming method (See note 2.)    Time or ramp setting method

Time accuracy (See note 2.)         ±0.2% (±500 ms) of the set value

Sampling period (See note 3.)       Temperature input:           250 ms

                                    Current/voltage input:       100 ms

Insulation resistance               20 MΩ min. (at 500 VDC)

Dielectric strength                 2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities

Vibration resistance                Malfunction:  10 to 55 Hz, 10 m/s2 (approx. 1G) for 10 min each in X, Y, and Z directions

                                    Destruction:  10 to 55 Hz, 20 m/s2 (approx. 2G) for 2 hrs each in X, Y, and Z directions

Shock resistance                    Malfunction:  200 m/s2 min. (approx. 20G), 3 times each in 6 directions

                                                  (100 m/s2 (approx. 10G) applied to the relay)

                                    Destruction:  300 m/s2 min. (approx. 30G), 3 times each in 6 directions

Ambient temperature                 Operating:    −10°C to 55°C (with no icing)/3-year warranty period: –10°C to 50°C

                                    Storage:      −25°C to 65°C (with no icing)

Ambient humidity                    Operating:    35% to 85%

Degree of protection                Front panel:  NEMA4 for indoor use (equivalent to IP66)

                                    Rear case:    IEC standard IP20

                                    Terminals:    IEC standard IP00

Memory protection                   Non-volatile memory (number of writings: 100,000 operations)

Weight                              E5AK:  approx. 450 g

                                    E5EK:  approx. 320 g

                                    Mounting bracket: approx. 65 g

EMC                                 Emission Enclosure:                     EN55011 Group 1 class A

                                    Emission AC Mains:                      EN55011 Group 1 class A

                                    Immunity ESD:                           EN61000-4-2: 4 kV contact discharge (level 2)

                                                                                             8 kV air discharge (level 3)

                                    Immunity RF-interference:               ENV50140:        10 V/m (amplitude modulated, 80 MHz to 1 GHz)

                                                                                             (level 3)

                                                                                             10 V/m (pulse modulated, 900 MHz)

                                    Immunity Conducted Disturbance:         ENV50141:        10 V (0.15 to 80 MHz) (level 3)

                                    Immunity Burst:                         EN61000-4-4: 2 kV power-line (level 3)

                                                                                             2 kV I/O signal-line (level 4)

Approved standards                  UL61010C-1, CSA 22.2 No. 61010-1

                                    Conforms to EN61326-1: 2006, EN61010-1 (IEC61010-1)

                                    Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered terminal cover is

                                    mounted.

Note: 1.  The indication accuracy of the K1, T, and N thermocouples at a temperature of −100°C or less is ±2°C ±1 digit maximum. The indication

          accuracy of the U, L1, and L2 thermocouples at any temperature is ±2°C ±1 digit maximum.

          The indication accuracy of the B thermocouple at a temperature of 400°C or less is unrestricted.

          The indication accuracy of the R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum.

          The indication accuracy of the W thermocouple at any temperature is (±0.3% of the indicated value or ±3°C, whichever is greater) ±1 digit

          maximum.

          The indication accuracy of the PLII thermocouple at any temperature is (±0.3% or ±2°C, whichever is greater) ±1 digit maximum.

     2.   For Programmable Models.

     3.   The sampling period of the standard model with CT and remote SP inputs is 250 ms.

                                                                                                                                                     5
                                                                                                                                            E5AK

■ Output Unit Ratings and Characteristics

                      Model                                                         Specifications

E53-R                 Relay output           5 A at 250 VAC (resistive load)

E53-S                 SSR output             1 A at 75 to 250 VAC (resistive load)

E53-Q                 Voltage output         NPN: 40 mA at 12 VDC         (with short-circuit protection)

E53-Q3                                       NPN: 20 mA at 24 VDC         (with short-circuit protection)

E53-Q4                                       PNP: 20 mA at 24 VDC         (with short-circuit protection)

E53-C3                Linear current output  4 to 20 mA, permissible load impedance: 600 Ω max., resolution: approx. 2,600

E53-C3D                                      0 to 20 mA, permissible load impedance: 600 Ω max., resolution: approx. 2,600

E53-V34               Linear voltage output  0 to 10 VDC, permissible load impedance: 1 kΩ min., resolution: approx. 2,600

E53-V35                                      0 to 5 VDC, permissible load impedance: 1 kΩ min., resolution: approx. 2,600

Note: An output relay (1 A at 250 VAC) is mounted on the position-proportional model. (When replacing, use the E53-R.)

■ Option Unit Ratings and Characteristics

                        Model                                                           Specifications

E53-AKB               Event input                     Contact input:

                                                      ON: 1 kΩ max., OFF: 100 kΩ min.

                                                      No-contact input:

                                                      ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.

E53-EN01              Communications         RS-232C  Transmission method:       Half-duplex

E53-EN02                                     RS-422   Synchronization method: Start-stop synchronization (asynchronous method)

E53-EN03                                     RS-485   Baud rate:                 1.2/2.4/4.8/9.6/19.2 kbps

                                                      Transmission code:         ASCII

E53-AKF               Transfer output                 4 to 20 mA:

                                                      Permissible load impedance: 600 Ω max.

                                                      Resolution: approx. 2,600

Note: Event input is used for switching the target value, run or stop command, or automatic and manual mode with an external signal input.

■ Current Transformer Ratings

Dielectric strength                    1,000 VAC (for 1 min)

Vibration resistance                   50 Hz, 98 m/s2 (10G)

Weight                                 E54-CT1: approx. 11.5 g; E54-CT3: approx. 50 g

Accessories (E54-CT3 only)             Armature: 2; Plug: 2

■ Heater Burnout Alarm

Max. heater current                                   Single-phase 50 A VAC (See note 1.)

Heater current value display accuracy                 ±5% FS±1 digit max.

Heater burnout alarm setting range                    0.1 to 49.9 A (in units of 0.1 A) (See note 2.)

Min. detection ON time                                190 ms (See note 3.)

Note: 1.  Use the K2CU-F@@A-@GS (with gate input terminals) for the detection of three-phase heater burnout.

2.        The heater burnout alarm is always OFF if the alarm is set to 0.0 A and always ON if the alarm is set to 50.0 A.

3.        No heater burnout detection or heater current value measurement is possible if the control output (heat) is ON for less than 190 ms.

                                                                                                                                                  6
                                                                                                              E5AK

Nomenclature

E5AK

Operation Indicators                                                           No. 1 Display

•  OUT1                                                                        Displays the process value or

   Lights when the pulse output                                                parameter symbols.

   function assigned to control output                                         No. 2 Display

   1 turns ON.                                                                 Displays the set point, manipulated

•  OUT2                                                                        variable, or parameter settings.

   Lights when the pulse output

   function assigned to control output

   2 turns ON.

•  SUB1

   Lights when the output function

   assigned to auxiliary output 1

   turns ON.

•  SUB2

   Lights when the output function

   assigned to auxiliary output 2

   turns ON.

•  MANU

   Lights when the manual operation

   mode.

•  STOP

   Lights during operation has

   stopped.

•  RMT

   Lights during remote operation.

•  AT

   Flashes during auto-tuning.

•  RSP

   Lights during remote SP opera-                                              Up Key/Down Key

   tion.                                                                       Press to increase or decrease the

•  Bar Graph                                                                   value on the No.2 display.

   On a standard model (E5AK-                                                  Display Key

   AA2), this bar graph indicates the

   manipulated variable (heat) in                                              Press for less than 1 s to shift the

   10% increments per single                                                   display to the next parameter. When

   segment. On a position-                                                     this key is pressed for 1 s or more,

   proportional model (E5AK-PRR2),                                             the menu screen will be displayed in

   this bar graph indicates the valve                                          any case.

   opening in 10% increments per        A/M Key

   single segment.                      Press to select the auto operation or

                                        manual operation.

                                                                                                                     7
                                                                                                                                   E5AK

Dimensions

Note: All units are in millimeters unless otherwise indicated.

E5AK

                                                                                                Panel Cutouts

                     96 × 96                                                                     110 min.

                                                                         91 × 91

                                                                                      120 min.

                                                                Note:             1.  Recommended panel thickness is 1 to 8 mm.

                                                                                  2.  Maintain the specified vertical and horizontal

                                                                                      mounting space between each Unit. Units must

                                                                                      not be closely mounted vertically or horizontally.

Accessories (Order   Separately)

Terminal Cover

E53-COV0809                                                                           E53-COV08

Current Transformer

E54-CT1                                                         E54-CT3

                                                                                                                        2.36 dia.

                              5.8 dia.                                                                         12 dia.

                                                                                      40x40

                                                                                                               Two, M3 (depth: 4)

                                                                                                                                          8
                                                                                                                             E5AK

Unit Label (Order Separately)

Y92S-L1

Waterproof Packing

Y92S-P4 (for DIN 96 × 96)

                               Order the Waterproof Packing separately if it becomes lost or damaged. (Refer to page 3.)

                               The Waterproof Packing can be used to achieve an IP66 degree of protection.

                               (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the

                               operating environment. Therefore, periodic replacement is recommended to ensure the level of

                               waterproofing specified in IP66. The time for periodic replacement depends on the operating

                               environment. Be sure to confirm this point at your site. Consider one year a rough standard.

                               OMRON shall not be liable for the level of water resistance if the customer does not perform periodic

                               replacement.)

                               The Waterproof Packing does not need to be attached if a waterproof structure is not required.

         ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

         To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                           In the interest of product improvement, specifications are subject to change without notice.

                                                                                                                                      9
                                                      Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or

comments.

                                                      Warranty and Limitations of Liability

WARRANTY

OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)

from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR

FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS.                     ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS

DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.                                OMRON DISCLAIMS ALL OTHER

WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY

OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS

IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT

LIABILITY.

In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS

OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT

SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

                                                      Application Considerations

SUITABILITY FOR USE

OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's

application or use of the products.

At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the

products.   This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,

machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given.             This is not intended to be an exhaustive list of all possible

uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:

•  Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.

•  Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,

   safety equipment, and installations subject to separate industry or government regulations.

•  Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE

SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND

INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

PROGRAMMABLE PRODUCTS

OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.

                                                                    Disclaimers

CHANGE IN SPECIFICATIONS

Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.

However, some specifications of the products may be changed without any notice.     When in doubt, special model numbers may be assigned to fix or

establish key specifications for your application on your request.  Please consult with your OMRON representative at any time to confirm actual

specifications of purchased products.

DIMENSIONS AND WEIGHTS

Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

PERFORMANCE DATA

Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent               the

result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON

Warranty and Limitations of Liability.

ERRORS AND OMISSIONS

The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,

typographical, or proofreading errors, or omissions.

                                                                                                                                                                         2009.4

                                                      In the interest of product improvement, specifications are subject to change without notice.

OMRON Corporation

Industrial Automation Company

http://www.ia.omron.com/

                                                                                                          (c)Copyright OMRON Corporation 2009 All Right Reserved.
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Omron:

E5AK-AA2-500    E53-AKF   E5AK-AA2-500 AC/DC24  E5AK-AA2B AC/DC24  E5AK-PRR2-500  E5AK-PRR2-500

AC/DC24  E5AK-TAA2-500 AC100-240  E5AK-TAA2-500 AC/DC24  E5AK-TAA2 AC100-240  E5AK-TAA2 AC/DC24

E5AK-TPRR2-500 AC100-240  E5AK-TPRR2-500 AC/DC24  E5AK-TPRR2 AC100-240  E5AK-TPRR2 AC/DC24       E5AK-

AA2-500 REFURB  E5AK-TAA2500AC/DC24  E5AK-AA2-B AC/DC24  E5AK-TAA2-500-AC/DC24

小广播

E53-AKF器件购买:

该厂商的其它器件

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2017 EEWORLD.com.cn, Inc. All rights reserved