Monitoring Relays
True RMS 3-Phase, 3-Phase+N, Multi-function
Type DPB71

                                                                   TRMS 3-phase over and under voltage,
                                                                    phase sequence and phase loss monitoring relay

                                                                   Detects when all 3 phases are present and have the
                                                                    correct phase sequence

                                                                   Detects if all the 3-phase-phase or phase-neutral volt-
                                                                    ages are within the set limits

                                                                   Upper and lower limits separately adjustable
                                                                   Measures on own power supply
                                                                   Selection of measuring range by DIP-switches
                                                                   Adjustable voltage on relative scale
                                                                   Adjustable delay function (0.1 to 30 s)
                                                                   Output: 5 A SPDT relay N.E.
                                                                   For mounting on DIN-rail in accordance with

                                                                    DIN/EN 50 022
                                                                   35.5 mm DIN-rail housing
                                                                   LED indication for relay, alarm and power supply ON

Product Description                                               Ordering Key                     DPB 71 C M23

3-phase or 3-phase+neutral          Supply ranges from 208 to     Housing
line voltage monitoring relay       480 VAC covered by two        Function
for phase sequence, phase           multivoltage relays.          Type
loss, over and under voltage        35.5 mm wide housing suit-    Item number
(separately adjustable set          able both for back and front  Output
points) with built-in time          panel mounting.               Power supply
delay function.

Type Selection

Mounting                            Output                        Supply: 208 to 240 VAC           Supply: 380 to 480 VAC

DIN-rail                            SPDT                          DPB 71 C M23                     DPB 71 C M48

Input Specifications                                              Output Specifications

Input                               Terminals L1, L2, L3, N       Output                           SPDT relay
L1, L2, L3, N                      Measure on own supply          Rated insulation voltage        250 VAC

Note: Connect the neutral only                                    Contact ratings (AgSnO2)         
if it is intrinsically at the star                                                                 5 A @ 250 VAC
centre                                                            Resistive loads      AC 1        5 A @ 24 VDC
                                                                                                   2.5 A @ 250 VAC
                                                                                       DC 12       2.5 A @ 24 VDC

                                                                  Small inductive loads AC 15

Measuring ranges                                                                       DC 13
208 to 240  VAC
380 to 480  VAC                    177 to 275  VAC               Mechanical life                   30 x 106 operations
                                    323 to 550  VAC
                                                                  Electrical life                   105 operations
Ranges                                                                                             (at 5 A, 250 V, cos  = 1)

Upper level                         +2 to +22%                    Operating frequency               7200 operations/h

                                    of the nominal voltage

Lower level                         -22 to -2%                    Dielectric strength

                                    of the nominal voltage        Dielectric voltage               2 kVAC (rms)

Note: The input voltage                                           Rated impulse withstand volt. 4 kV (1.2/50 s)

must not exceed the maximum

rated voltage or drop below                                       Supply Specifications

the minumum rated voltage

reported above.                                                   Power supply                     Overvoltage cat. III
                                                                   Rated operational voltage       (IEC 60664, IEC 60038)
Hysteresis                                                         through terminals:              L1, L2, L3, N
                                                                             M23 - Delta Voltage:  208 to 240 VAC 15%
Set points from 2 to 5%             1%                                                             45 to 65 Hz
                                                                             M48 - Delta Voltage:  380 to 480 VAC 15%
Set points from 5 to 22%            2%                                                             45 to 65 Hz
                                                                              M48 - Star Voltage:  220 to 277 VAC 15%
                                                                                                   45 to 65 Hz
                                                                  Rated operational power
                                                                   DPB71CM23                       13 VA @ 230 VAC, 50 Hz
                                                                   DPB71CM48                       13 VA @ 400 VAC, 50 Hz
                                                                                                   Supplied by L1 and L3

Specifications are subject to change without notice (23.10.06)                                                                1
DPB71

General Specifications

Power ON delay                 1 s 0.5 s or 6 s 0.5 s      Environment                     IP 20
Reaction time                                                   Degree of protection           3
                               < 200 ms                         Pollution degree               -20 to 60C, R.H. < 95%
Incorrect phase sequence or   (input signal variation from     Operating temperature          -30 to 80C, R.H. < 95%
total phase loss              -20% to +20% or from             Storage temperature
Voltage level                 +20% to -20% of set value)                                      35.5 x 81 x 67.2 mm
                               < 200 ms (delay < 0.1 s)        Housing                         PA66
Alarm ON delay                < 200 ms (delay < 0.1 s)         Dimensions                     Approx. 100 g
Alarm OFF delay               (15 min warm-up time)            Material
Accuracy                        1000 ppm/C                                                   Max. 0.5 Nm
Temperature drift             10% on set value 50 ms      Weight                          according to IEC 60947
Delay ON alarm                0.5% on full-scale                                            UL, CSA
Repeatability                                                 Screw terminals                 Yes
Indication for                 LED, green                       Tightening torque              Electromagnetic Compatibility
Power supply ON               LED, red (flashing 2 Hz                                         According to EN 61000-6-2
Alarm ON                      during delay time)              Approvals                       According to EN 61000-6-3
                               LED, yellow
Output relay ON                                               CE Marking

                                                               EMC
                                                                Immunity
                                                                Emissions

Mode of Operation

Connected to the 3 phases      or drops below the lower set    Example 1                       Example 2
(and neutral) DPB71 oper-      level, the red LED starts                                       (load monitoring)
ates when all 3 phases are     flashing 2 Hz and the output    (mains network monitoring)      The relay releases in case of
present at the same time,      relay releases after the set                                    interruption of one or more
the phase sequence is cor-     time period. If the phase       The relay monitors over and     phases, when one or more
rect and the phase-phase (or   sequence is wrong or one                                        voltages drop below the
phase-neutral) voltage levels  phase is lost, the output       under voltage, phase loss       lower set level or exceed the
are within set limits.         relay releases immediately.                                     upper set level.
                               Only 200 ms delay occurs.       and  correct    phase
If one or more phase-phase     The failure is indicated by
or phase-neutral voltages      the red LED flashing 5 Hz       sequence.
exceeds the upper set level    during the alarm condition.

Function/Range/Level and Time Delay Setting

Adjust the input range set-    as shown below.                 Centre knob:                    Lower knob:
ting the DIP switches 3 and                                    Setting of upper level on rel-  Setting of delay on alarm
4 as shown below.              Selection of level and time     ative scale.                    time on absolute scale (0.1
Select the desired function    delay:                                                          to 30 s).
setting the DIP switches 1     Upper knob:                           Power ON delay
and 2 as shown below.          Setting of lower level on rel-        ON: 6 s 0.5 s
To access the DIP swiches      ative scale.                          OFF: 1 s 0.5 s
open the grey plastic cover                                          Monitored voltage
                                                                     ON: Phase-Neutral
                                                                     OFF: Phase-Phase
                                                                     Measuring range

                                                                    SW3        ON              ON   OFF    OFF
                                                                                                           OFF
                                                                    SW4        ON              OFF  ON   240 VAC

                                                                    M23 Ph-Ph  208 VAC 220 VAC 230 VAC   480 VAC
                                                                    Voltage
                                                                               380 VAC 400 VAC 415 VAC   277 VAC
                                                                    M48 Ph-Ph
                                                                    Voltage    220 VAC 230 VAC 240 VAC

                                                                    M48 Ph-N
                                                                    Voltage

2                                                                   Specifications are subject to change without notice (23.10.06)
DPB71

Operation Diagrams

Wiring Diagrams                                                                            Example 2
                                                                                                  N
  Example 1                                                                                       L3
             N                                                                                    L2
             L3                                                                                   L1
             L2
             L1                                                                                        m<3

                                                 m                                                     U                      m

m<3                               L1 L2 L3  16      18                                              L1         L1 L2 L3  16      18
                                                                                                            L3
     U                             N             15                                                             N             15

L1
      L3

Dimensions                                       67.2
                                                                18.7
                             35.5

2

                                81
                                                                                       45

Specifications are subject to change without notice (23.10.06)                                                                        3
This datasheet has been downloaded from:
            datasheet.eeworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company

小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2017 EEWORLD.com.cn, Inc. All rights reserved