datasheet

电子工程世界电子工程世界电子工程世界

型号

产品描述

搜索
 

CP1E-N20DR-A

器件型号:CP1E-N20DR-A
器件类别:机电产品    工业自动化   
文件大小:26402.22KB,共44页
厂商名称:OMRON
厂商官网:https://www.omron.com
标准:  
下载文档

器件描述

controllers 12in 8outac PS rs232 20mm 0.5m ca

参数

Manufacturer: Omron
Product Category: Controllers
RoHS: Yes
Brand: Omron Automation and Safety

CP1E-N20DR-A器件文档内容

   New Product

SYSMAC CP-series CP1E CPU Units

CP1E-E@@D@-@
CP1E-N@@D@-@/NA20D@-@

The CP1E Package PLCs: Economical, Easy to use, and Efficient

The E-type Basic CPU Units provide cost
   performance and easy application with only basic
   functionality.

The N and NA-types Application CPU Units support
   Programmable Terminal connection, position control,
   and inverter connection

CP1E-E20DR-A  CP1E-N40DR-A

Features

Programming, setting, and monitoring with CX-Programmer.
Easy connection with computers using commercially available USB cables
With E30/40, N30/40/60 or NA20 CPU Units, Add I/O by Connecting Expansion I/O Units.
With E30/40, N30/40/60 or NA20 CPU Units, Add Analog I/O or Temperature Inputs by Connecting Expansion Units.
Quick-response inputs
Input interrupts
Complete High-speed Counter Functionality.
Versatile pulse control for Transistor Output for N14/20/30/40/60 or NA20 CPU Units.
PWM Outputs for Transistor Output for N14/20/30/40/60 or NA20 CPU Units.
Built-in RS-232C Port for N/NA-type CPU Units.
Mounting Serial Option Boards or Ethernet Option Board to N30/40/60 or NA20 CPU Units.
Built-in analog I/O, two inputs and one output, for NA-type CPU Units.

                                                                                                                 1
   CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@
   System Configuration

   Basic System Configuration Using an E-type CPU Unit

                                               CP1E CPU Unit  Expansion I/O Units                          Expansion Units                               DIN Track

   Support Software       Personal computer    CP1E-E30DR-A   20 or 40 I/O Points                                    Analog I/O
   CX-Programmer      IBM PC/AT or equivalent  CP1E-E40DR-A         8 inputs                                       Analog inputs
                                                                   8 outputs                                      Analog outputs
                                                                                                              Temperature sensors
                                                                  16 outputs                               CompoBus/S I/O Link Unit
                                                                  32 outputs

                                                              Up to 3 Units can be connected

                                                                                   When a two level layout is created by expansion and distance is required

                                               CP1E-E10D@-@                                                                     Expansion Units and      I/O Connecting Cable
                                               CP1E-E14DR-A                                            CP1E CPU Unit Expansion I/O Units
                                               CP1E-E20DR-A

                                                                                                                                                         CP1W-CN811

   Basic System Configuration Using an N/NA-type CPU Unit

       Battery                                 CP1E CPU Unit  Expansion I/O Units                          Expansion Units                               DIN Track
   CP1W-BAT01

   Support Software   Personal computer        CP1E-N30D -    20 or 40 I/O Points                                    Analog I/O
   CX-Programmer                               CP1E-N40D -         8 inputs                                        Analog inputs
                      IBM PC/AT or             CP1E-N60D -         8 outputs                                      Analog outputs
                      equivalent               CP1E-NA20D -                                                   Temperature sensors
                                                                 16 outputs                                CompoBus/S I/O Link Unit
   Built in RS-232C                            CP1E-N14D -       32 outputs
                                               CP1E-N20D -
    Programmable
    Terminal (PT)

   (NT Link/HOST Link)                                        Up to 3 Units can be connected

   General component    Inverter                                                                           *The CP1W-DAM01 LCD Option Board can not be used.

                                                              RS-232C Option Board                         RS-422A/485 Option Board                      Ethernet Option Board
                                                                    CP1W-CIF01
                                                                                                       Or  CP1W-CIF11                                Or  CP1W-CIF41
                                                                                                 COMM
   (No-protocol mode)                                                                                      CP1W-CIF12                                    CP1E PLCs are supported by
                               (Modbus-RTU)
                                                                                                                                                         CP1W-CIF41 version 2.0 or higher.

                                                                                                           COMM                                          IP ADDRESS:
                                                                                                                                                         SUBNET MASK:

   CP-series PLC or                                                                                                                                      COMM ERR       10BASE-T
                                                                                                                                                                       100BASE-TX

   CJ1M PLC           Host computer

                                                                                                       When a two level layout is created by expansion and distance is required

                                                                                                                                Expansion Units and      I/O Connecting Cable
                                                                                                       CP1E CPU Unit Expansion I/O Units

                      (Host Link)

   (Serial PLC Link)

                                                                                                                                                              CP1W-CN811

2
                                                      CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Ordering Information

International Standards
The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus,

   UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
Contact your OMRON representative for further details and applicable conditions for these standards.

E-type CP1E CPU Units (Basic Models)

                                 Specifications                            External        Current
                                                                            power    consumption (A)
Product                                                                     supply
name         Power       Inputs  Outputs  Output      Program      Data              5V    24 V                    Model  Standards
             Supply                        type       capacity   memory    (24 VDC)
                                                                 capacity      (A)                    CP1E-E10DR-A        UC1, N,
                                                                                                      CP1E-E10DT-A        L, CE
E-type                                    Relay                            --        0.08  0.04       CP1E-E10DT1-A
CPU Units                                                                                             CP1E-E10DR-D
with 10 I/O  100 to 240                   Transistor                       --        0.11  --
Points       VAC                          (sinking)

                                          Transistor                       --        0.11  --

                         6       4        (sourcing) 2K          2K
                                                          steps  words

                                          Relay                            --        0.08  0.04

             24 VDC                       Transistor                       --        0.11  --         CP1E-E10DT-D
                                          (sinking)
                                                                           --        0.11  --         CP1E-E10DT1-D
                                          Transistor
                                          (sourcing)

E-type

CPU Units

with 14 I/O

Points

             100 to 240  8       6        Relay       2K steps 2K words    --        0.16  0.07 CP1E-E14DR-A              UC1, N,
             VAC                                                                                                          L, CE

E-type

CPU Units

with 20 I/O

Points       100 to 240  12      8        Relay       2K steps 2K words    --        0.17  0.08 CP1E-E20DR-A              UC1, N,
             VAC                                                                                                          L, CE

E-type                                                                                                                    UC1, N,
                                                                                                                          L, CE
CPU Units
                                                                                                                          UC1, N,
with 30 I/O                                                                                                               L, CE

Points       100 to 240  18      12 Relay             2K steps 2K words    0.30      0.17  0.07 CP1E-E30DR-A
             VAC

E-type

CPU Units

with 40 I/O

Points       100 to 240  24      16 Relay             2K steps 2K words    0.30      0.17  0.09 CP1E-E40DR-A
             VAC

Note: There are no accessories included with E-type CP1E CPU Units. A Battery (CP1W-BAT01) cannot be used.

                                                                                                                                      3
   CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

   N/NA-type CP1E CPU Units (Application Models)

                                    Specifications                            External        Current
                                                                               power    consumption (A)
   Product                                                                     supply
   name         Power       Inputs  Outputs  Output      Program      Data              5V    24 V                     Model  Standards
                Supply                        type       capacity   memory    (24 VDC)
                                                                    capacity      (A)                    CP1E-N14DR-A         UC1, N,
                                                                                                         CP1E-N14DT-A         L, CE
   N-type                                    Relay                            --        0.17  0.07       CP1E-N14DT1-A
   CPU Units                                                                                             CP1E-N14DR-D         UC1, N,
   with 14 I/O  100 to 240                   Transistor                       --        0.22  0.02                            L, CE
   Points       VAC                          (sinking)
                                                                                                                              UC1, N,
                                             Transistor                       --        0.22  0.02                            L, CE

                            8       6        (sourcing) 8K          8K                                                        UC1, N,
                                                             steps  words                                                     L, CE
                                             Relay                            --        0.17  0.07
                                                                                                                              UC1, N,
                24 VDC                       Transistor                       --        0.22  0.02 CP1E-N14DT-D               L, CE
                                             (sinking)
                                             Transistor                       --        0.22  0.02 CP1E-N14DT1-D
                                             (sourcing)
   N-type                                                                     --        0.18  0.08 CP1E-N20DR-A
   CPU Units                                 Relay
   with 20 I/O  100 to 240
   Points       VAC                          Transistor
                                             (sinking)
                                                                              --        0.23  0.02 CP1E-N20DT-A

                                             Transistor                       --        0.23  0.02 CP1E-N20DT1-A
                                             (sourcing)

                            12      8                    8K steps 8K words

                                             Relay                            --        0.18  0.08 CP1E-N20DR-D

                24 VDC                       Transistor                       --        0.23  0.02 CP1E-N20DT-D
                                             (sinking)
                                                                              --        0.23  0.02 CP1E-N20DT1-D
                                             Transistor
                                             (sourcing)

   N-type                                    Relay                            0.30      0.21  0.07 CP1E-N30DR-A
   CPU Units
   with 30 I/O  100 to 240                   Transistor                       0.30      0.27  0.02 CP1E-N30DT-A
   Points       VAC                          (sinking)

                                             Transistor                       0.30      0.27  0.02 CP1E-N30DT1-A
                                                                               --
                                             (sourcing)

                            18      12                   8K steps 8K words

                                             Relay                                      0.21  0.07 CP1E-N30DR-D

                24 VDC                       Transistor                       --        0.27  0.02 CP1E-N30DT-D
                                             (sinking)
                                                                              --        0.27  0.02 CP1E-N30DT1-D
                                             Transistor
                                             (sourcing)

   N-type                                    Relay                            0.30      0.21  0.09 CP1E-N40DR-A
   CPU Units
   with 40 I/O  100 to 240                   Transistor                       0.30      0.31  0.02 CP1E-N40DT-A
   Points       VAC                          (sinking)

                                             Transistor                       0.30      0.31  0.02 CP1E-N40DT1-A
                                                                               --
                            24      16       (sourcing)  8K steps 8K words

                                             Relay                                      0.21  0.09 CP1E-N40DR-D

                24 VDC                       Transistor                       --        0.31  0.02 CP1E-N40DT-D
                                             (sinking)
                                                                              --        0.31  0.02 CP1E-N40DT1-D
                                             Transistor
                                             (sourcing)

                                             Relay                            0.30      0.21  0.13 CP1E-N60DR-A

   N-type       100 to 240                   Transistor                       0.30      0.31  0.02 CP1E-N60DT-A
                                             (sinking)
   CPU Units VAC

   with 60 I/O                               Transistor

   Points                                    (sourcing) 8K          8K        0.30      0.31  0.02 CP1E-N60DT1-A
                                                             steps  words
                            36      24

                                             Relay                            --        0.21  0.13 CP1E-N60DR-D

                24 VDC                       Transistor                       --        0.31  0.02 CP1E-N60DT-D
                                             (sinking)
                                                                              --        0.31  0.02 CP1E-N60DT1-D
                                             Transistor
                                             (sourcing)

4
                                                               CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

                                    Specifications                                External        Current
                                                                                   power    consumption (A)
Product                                                                            supply
name            Power                            Output      Program       Data                                      Model       Standards
               Supply                             type       capacity    memory   (24 VDC)
NA-type      100 to 240  Inputs  Outputs                                capacity      (A)   5V    24 V                           UC1, N,
CPU Units    VAC                                             8K                                                                  L, CE
with 20 I/O                                      Relay       steps     8K            0.30   0.18  0.11 CP1E-NA20DR-A
Points       24 VDC                                                    words
(Built-in                12      8                                                     --
analog)
                         (Built-in (Built-in     Transistor                            --   0.23  0.09 CP1E-NA20DT-D
                         analog analog           (sinking)

                         inputs: 2) outputs: 1)

                                                 Transistor                                 0.23  0.09 CP1E-NA20DT1-D
                                                 (sourcing)

Battery Set For N/NA-type CP1E CPU Units

             Note: Mount a Battery to an N/NA-type CPU Unit if the data in the following areas must be

                    backed up for power interruptions.                                                               CP1W-BAT01  CE

             DM Area (D) (except backed up words in the DM Area), Holding Area (H), Counter Completion Flags (C),

             Counter Present Values (C), Auxiliary Area (A), and Clock Function

             (Use batteries within two years of manufacture.)

Note: There are no accessories included with N/NA-type CP1E CPU Units. RS-232C connectors for the built-in RS-232C port and the Battery
        (CP1W-BAT01) are not included.

                                                                                                                                            5
   CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

   Options (for CP1E N30/40/60 or NA20 CPU Units)

   The Options cannot be used for CP1E N14/20 CPU Units and all E-type CPU Units.

   Product name                                                               Specifications                                Model    Standards
   RS-232C Option Board                                                                                                 CP1W-CIF01
                               One RS-232C Option Board can be mounted to the Option Board slot.                                     UC1, N,
                               For CP1E N30/40/60 or NA20 CPU Units only.                                               CP1W-CIF11   L, CE
                               One RS-232C connector is included.

   RS-422A/485 Option Board

   RS-422A/485 Isolated-type   One RS-422A/485 Option Board can be mounted to the Option Board slot.
   Option Board                For CP1E N30/40/60 or NA20 CPU Units only.

                                                                                                                        CP1W-CIF12   UC1, N,
                                                                                                                                     L, CE

   Ethernet Option Board       One Ethernet Option Board can be mounted to the Option Board slot.
                               CP1E CPU Units are supported by CP1W-CIF41 version 2.0 or higher.
                               For CP1E N30/40/60 or NA20 CPU Units only.                                               CP1W-CIF41   UC1, N,
                               When using CP1W-CIF41, CX-Programmer version 9.12 or higher is required.                              L, CE

   Note: It is not possible to use a CP-series Ethernet Option Board version 1.0 (CP1W-CIF41), LCD Option Board (CP1W-DAM01), or Memory Card
           (CP1W-ME05M) with a CP1E CPU Unit.

   Programming Devices

                                                                    Specifications

   Product name                                                                              Number of     Media        Model        Standards
                                                                                              licenses                                     --
                                                                                                                                           --
                               CX-One Lite is a subset of the complete CX-One package that

                               provides only the Support Software required for micro PLC

   FA Integrated Tool Package  applications.
   CX-One Lite
   Ver.4.@                     CX-One Lite runs on the following OS.                         1 license     CD     CXONE-LT01C-V4
                               Windows 2000 (Service Pack 4 or higher), XP, Vista, or 7

                               Note: Except for 64-bit version.

                               CX-One Lite Ver. 4.@ includes Micro PLC Edition CX-

                               Programmer Ver.9.@.

   FA Integrated Tool Package  CX-One is a comprehensive software package that integrates    1 license *1  DVD*2  CXONE-AL01D-V4
   CX-One                      Support Software for OMRON PLCs and components. CX-
   Package Ver. 4.@            One runs on the following OS.
                               OS: Windows 2000 (Service Pack 4 or higher), XP, Vista, or 7
                               Note: Except for 64-bit version.
                               CX-One Ver. 4.@ includes CX-Programmer Ver. 9.@.

   Note: 1. The E20, E30, E40, N20, N30 and N40 CPU Units are supported by CX-Programmer version 8.2 or higher.
               The E10, E14, N14, N60, and NA20 CPU Units are supported by CX-Programmer version 9.03 or higher.
               When Micro PLC Edition CX-Programmer is used, you need version 9.03 or higher.

           2. The CX-One and CX-One Lite cannot be simultaneously installed on the same computer.
   * 1 Multi licenses are available for the CX-One (3, 10, 30 or 50 licenses).
   * 2 The CX-One is also available on CD (CXONE-AL@@C-V4).

   The following tables lists the Support Software that can be installed from CX-One

   Support Software in CX-One                 CX-One Lite        CX-One               Support Software in CX-One        CX-One Lite  CX-One
                                                 Ver.4.@         Ver.4.@                                                   Ver.4.@   Ver.4.@
                                                                                                                              Yes
   Micro PLC Edition CX-Programmer Ver.9.@    Yes                   No    CX-Drive                             Ver.1.@        No       Yes
                                                                          CX-Process Tool                      Ver.5.@        No       Yes
   CX-Programmer               Ver.9.@        No                    Yes   Faceplate Auto-Builder for NS        Ver.3.@        Yes      Yes
                                                                          CX-Designer                          Ver.3.@        Yes      Yes
   CX-Integrator               Ver.2.@        Yes                   Yes   NV-Designer                          Ver.1.@        Yes      Yes
                                                                          CX-Thermo                            Ver.4.@        Yes      Yes
   Switch Box Utility          Ver.1.@        Yes                   Yes   CX-ConfiguratorFDT                   Ver.1.@        No       Yes
                                                                          CX-FLnet                             Ver.1.@        Yes      Yes
   CX-Protocol                 Ver.1.@        No                    Yes   Network Configurator                 Ver.3.@        Yes      Yes
                                                                          CX-Server                            Ver.4.@                 Yes
   CX-Simulator                Ver.1.@        Yes                   Yes

   CX-Position                 Ver.2.@        No                    Yes

   CX-Motion-NCF               Ver.1.@        No                    Yes

   CX-Motion-MCH               Ver.2.@        No                    Yes

   CX-Motion                   Ver.2.@        No                    Yes

   Note: For details, refer to the CX-One Catalog (Cat. No. R134).

6
                                                                  CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Expansion I/O Units and Expansion Units (for CP1E E30/40, N30/40/60, or NA20 CPU Units)

CP1E E10/14/20 or N14/20 CPU Units do not support Expansion I/O Units and Expansion Units.

Unit type Product name                            Specifications                                         Current    Model                Standards
                   Input Unit                         Outputs                                      consumption (A)

                                          Inputs                                      Output type  5V     24 V

                                          8                       --                    --         0.018      --    CP1W-8ED

                       Output Units                                           Relay                0.026  0.044     CP1W-8ER       U, C, N, L, CE
                                                                                                   0.075    --      CP1W-8ET
CP1W                                                                          Transistor                                           N, L, CE
Expansion I/O                                                                                      0.075    --      CP1W-8ET1      N, L, CE
Units                                     --                      8           (sinking)            0.042  0.090     CP1W-16ER      U, C, N, L, CE
                                                                                                   0.076            CP1W-16ET      N, L, CE
                       I/O Units                                              Transistor                    --
                                                                              (sourcing)           0.076            CP1W-16ET1
                       Analog Input Unit                                                           0.049    --      CP1W-32ER
                                                                              Relay                0.113  0.131     CP1W-32ET

                                                                              Transistor           0.113    --      CP1W-32ET1
                                                                                                   0.103            CP1W-20EDR1
                                          --                      16          (sinking)            0.130    --      CP1W-20EDT
                                                                                                          0.044
                                                                              Transistor           0.130            CP1W-20EDT1
                                                                              (sourcing)           0.080    --      CP1W-40EDR
                                                                                                   0.160            CP1W-40EDT
                                                                              Relay                         --
                                                                                                   0.160  0.090     CP1W-40EDT1
                                                                              Transistor
                                                                                                            --
                                          --                      32          (sinking)
                                                                                                            --
                                                                              Transistor
                                                                              (sourcing)

                                                                              Relay

                                                                              Transistor

                                          12                      8           (sinking)

                                                                              Transistor
                                                                              (sourcing)

                                                                              Relay

                                                                              Transistor

                                          24                      16          (sinking)

                                                                              Transistor
                                                                              (sourcing)

                                          4 analog inputs                                          0.100 0.090      CP1W-AD041     UC1, N, L, CE

                                           Input range: 0 to 5 V, 1 to 5 V, 0 to 10 V, 10 V,

                                          0 to 20 mA, or 4 to 20 mA.

                                          Resolution: 1/6000

              Analog Output Unit          2 analog outputs                                         0.040 0.095      CP1W-DA021        UC1, CE
                                                                                                                                   UC1, N, L, CE
                                           Output range: 1 to 5 V, 0 to 10 V, 10 V,

                                          0 to 20 mA, or 4 to 20 mA.

                                          Resolution: 1/6000

                                          4 analog outputs                                         0.080 0.124      CP1W-DA041

                                           Output range: 1 to 5 V, 0 to 10 V, 10 V,

                                          0 to 20 mA, or 4 to 20 mA.

                                          Resolution: 1/6000

              Analog I/O Unit             2 analog inputs and 1 analog output

                                           Input range: 0 to 5 V, 1 to 5 V, 0 to 10 V, 10 V,      0.083 0.110      CP1W-MAD11

CP1W                                      0 to 20 mA, or 4 to 20 mA.
Expansion
Units                                     Output range: 1 to 5 V, 0 to 10 V, 10 V,

                                          0 to 20 mA, or 4 to 20 mA.

                                          Resolution: 1/6000

              Temperature                 2 temperature sensor inputs                              0.040  0.059     CP1W-TS001
              Sensor Unit                 Sensor type: Thermocouple (J or K)                       0.040  0.059     CP1W-TS002
                                                                                                                    CP1W-TS101
                                          4 temperature sensor inputs
                                          Sensor type: Thermocouple (J or K)

                                          2 temperature sensor inputs                              0.054 0.073                     U, C, N, L, CE
                                          Sensor type: Platinum resistance thermometer

                                                           (Pt100 or JPt100)

                                          4 temperature sensor inputs                              0.054 0.073      CP1W-TS102
                                          Sensor type: Platinum resistance thermometer

                                                           (Pt100 or JPt100)

              CompoBus/S
              I/O Link Unit

                                          CompoBus/S slave                                         0.029      --    CP1W-SRT21
                                          8 inputs and 8 outputs

I/O Connecting Cable

Product name                                      Specifications                                       Model                  Standards

I/O Connecting Cable         80 cm (for CP1W Expansion I/O Units and Expansion Units)              CP1W-CN811       UC1, N, L, CE
                             Only one I/O Connecting Cable can be used in each PLC.

Note: An I/O Connecting Cable (approx. 6 cm) for horizontal connection is provided with CP1W Expansion I/O Units and Expansion Units.

                                                                                                                                                    7
   CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@
   General Specifications

   Type                                                       AC power supply models                                DC power supply models

   Model                                                         CP1E-@@@D@-A                                           CP1E-@@@D@-D

   Enclosure                                      Mounted in a panel

   Dimensions (H D W)                         CPU Unit with 10 I/O points (CP1E-E10D@-@): 90mm *1 85mm *2 66 mm
                                                  CPU Unit with 14 or 20 I/O points (CP1E-@14D@-@/@20D@-@): 90mm *1 85mm *2 86 mm
                                                  CPU Unit with 30 I/O points (CP1E-@30D@-@): 90mm *1 85mm *2 130 mm
                                                  CPU Unit with 40 I/O points (CP1E-@40D@-@): 90mm *1 85mm *2 150 mm
                                                  CPU Unit with 60 I/O points (CP1E-N60D@-@): 90mm *1 85mm *2 195 mm
                                                  CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D@-@): 90mm *1 85mm *2 130 mm

   Weight                                         CPU Unit with 10 I/O points (CP1E-E10D@-@): 300g max.
                                                  CPU Unit with 14 I/O points (CP1E-@14D@-@): 360g max.
                                                  CPU Unit with 20 I/O points (CP1E-@20D@-@): 370g max.
                                                  CPU Unit with 30 I/O points (CP1E-@30D@-@): 600g max.
                                                  CPU Unit with 40 I/O points (CP1E-@40D@-@): 660g max.
                                                  CPU Unit with 60 I/O points (CP1E-N60D@-@): 850g max.
                                                  CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D@-@): 680g max.

                           Supply voltage         100 to 240 VAC 50/60 Hz                             24 VDC

                           Operating voltage      85 to 264 VAC                                       20.4 to 26.4 VDC
                           range

                           Power consumption      15 VA/100 VAC max.                                  9 W max. (CP1E-E10D@-D)
                                                  25 VA/240 VAC max.                                  13 W max. (CP1E-N14D@-D/N20D@-D)
                                                  (CP1E-E10D@-A/@14D@-A/@20D@-A)
                                                                                                      20 W max.
                                                  50 VA/100 VAC max.                                  (CP1E-NA20D@-D/N30D@-D/N40D@-D/N60D@-D) *4
                                                  70 VA/240 VAC max.
                                                  (CP1E-NA20D@-A/@30D@-A/@40D@-A/N60D@-A)

   Electrical              Inrush current         120 VAC, 20 A for 8 ms max. for cold start at room  24 VDC, 30 A for 20 ms max. for cold start at room
   specifications                                 temperature                                         temperature
                                                  240 VAC, 40 A for 8 ms max. for cold start at room
                                                  temperature

                           External power supply  Not provided.                                       Not provided
                           *3                     (CP1E-E10D@-A/@14D@-A/@20D@-A)
                                                  24 VDC, 300 mA
                                                  (CP1E-NA20D@-A/@30D@-A/@40D@-A/N60D@-A)

                           Insulation resistance  20 M min. (at 500 VDC) between the external AC Except between DC primary current and DC

                                                  terminals and GR terminals                          secondary current

                           Dielectric strength    2,300 VAC 50/60Hz for 1 min between AC external Except between DC primary current and DC

                                                  and GR terminals Leakage current: 5 mA max.         secondary current

                           Power OFF detection    10 ms min.                                          2 ms min.
                           time

                           Ambient operating      0 to 55 C
                           temperature

                           Ambient humidity       10% to 90%

                           Atmosphere             No corrosive gas.

                           Ambient storage        -20 to 75 C (excluding battery)
                           temperature

                           Altitude               2,000 m max.

   Application             Pollution degree       2 or less: Conforms to JIS B3502 and IEC 61131-2.
   environment             Noise resistance       2 kV on power supply line (Conforms to IEC61000-4-4.)

                           Overvoltage category Category II: Conforms to JIS B3502 and IEC 61131-2.

                           EMC Immunity Level Zone B

                           Vibration resistance   Conforms to JIS 60068-2-6.
                                                  5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz
                                                  Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)

                           Shock resistance       Conforms to JIS 60068-2-27.
                                                  147 m/s2, 3 times in X, Y, and Z directions

   Terminal block                                 Fixed (not removable)

   Terminal screw size                            M3

   Applicable standards                           Conforms to EC Directive

   Grounding method                               Ground to 100  or less.

   * 1 Total of 110 mm with mounting brackets.
   * 2 Excluding cables.
   * 3 Use the external power supply to power input devices. Do not use it to drive output devices.
   * 4 This is the rated value for the maximum system configuration. Use the following formula to calculate power consumption for CPU Units with

        DC power.

        Formula: DC power consumption = (5V current consumption  5 V/70% (internal power efficiency) + 24V current consumption)  1.1(current

        fluctuation factor)

        The above calculation results show that a DC power supply with a greater capacity is required.

8
                                             CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@
Performance Specifications

Item                                                                  CP1E-@@D@-@                                       CP1E-N@@D@-@
                                                                                                                       CP1E-NA@@D@-@

Program capacity                                      2 K steps (8 Kbytes) including the symbol table,    8 K steps (32 Kbytes) including the symbol table,

                                                      comments, and program indices of the CX-Programmer comments, and program indices of the CX-Programmer

Control method                                        Stored program method

I/O control method                                    Cyclic scan with immediate refreshing

Program language                                      Ladder diagram

Instructions                                          Approximately 200

Processing       Overhead processing time             0.4 ms
speed            Instruction execution times
                                                      Basic instructions (LD): 1.19 s min.
                                                      Special instructions (MOV): 7.9 s min.

Number of CP1W-series Expansion Units                 CP1E-E10D@-@/@14D@-@/@20D@-@: None
connected                                             CP1E-@30D@-@/@40D@-@/N60D@-@/NA20D@-@: 3 units

Maximum number of I/O points                          CP1E-E10D@-@ : 10
                                                      CP1E-@14D@-@ : 14
                                                      CP1E-@20D@-@ : 20
                                                      CP1E-@30D@-@ : 150 (30 built in, 40 3 expansion)
                                                      CP1E-@40D@-@ : 160 (40 built in, 40 3 expansion)
                                                      CP1E-N60D@-@ : 180 (60 built in, 40 3 expansion)
                                                      CP1E-NA20D@-@: 140 (20 built in, 40 3 expansion)

Built-in I/O                                          CP1E-E10D@-@ : 10 (6 inputs, 4 outputs)
                                                      CP1E-@14D@-@ : 14 (8 inputs, 6 outputs)
                                                      CP1E-@20D@-@ : 20 (12 inputs, 8 outputs)
                                                      CP1E-@30D@-@ : 30 (18 inputs, 12 outputs)
                                                      CP1E-@40D@-@ : 40 (24 inputs, 16 outputs)
                                                      CP1E-N60D@-@ : 60 (36 inputs, 24 outputs)
                                                      CP1E-NA20D@-@: 20 (12 inputs, 8 outputs)

                                       High-speed     Incremental Pulse Inputs                            Incremental Pulse Inputs
                                       counter mode/   10 kHz: 6 counters                                  100 kHz: 2 counters,10 kHz: 4 counters
                                       maximum                    5 counters (only for 10 I/O points)
                                       frequency                                                          Up/Down Inputs
                                                      Up/Down Inputs                                       100 kHz: 1 counters,10 kHz: 1 counters
                 High-speed                            10 kHz: 2 counters
                 counters                                                                                 Pulse + Direction Inputs
                                                      Pulse + Direction Inputs                             100 kHz: 2 counters
                                                       10 kHz: 2 counters
                                                                                                          Differential Phase Inputs (4x)
                                                      Differential Phase Inputs (4x)                       50 kHz: 1 counter, 5 kHz: 1 counter
                                                       5 kHz: 2 counters

                                       Counting       Linear mode
                                       mode           Ring mode

Built-in input                         Count value    32 bits
functions
                                       Counter reset  Phase Z and software reset (excluding increment pulse input)
                                       modes          Software reset

                                       Control        Target Matching
                                       method         Range Comparison

                 Input interrupts                     6 inputs (4 inputs only for 10 I/O points)
                                                      Interrupt input pulse width: 50 s min.

                 Quick-response Inputs                6 inputs (4 inputs only for 10 I/O points)
                                                      Input pulse width: 50 s min.

                 Normal input          Input          Delays can be set in the PLC Setup (0 to 32 ms, default: 8 ms).
                                       constants      Set values: 0, 1, 2, 4, 8, 16, or 32 ms

                                       Pulse output                                                       Pulse + Direction Mode
                                       method and                                                         1 Hz to 100 kHz: 2 outputs
                                       output
                                       frequency

                                       Output mode                                                        Continuous mode (for speed control)
                                                                                                          Independent mode (for position control)
                 Pulse outputs         Number of      Pulse output function not included
                 (Models with          output pulses                                                      Relative coordinates: 0000 0000 to 7FFF FFFF hex
                 transistor                                                                               (0 to 2147483647)
                 outputs only)         Acceleration/                                                      Absolute coordinates: 8000 0000 to 7FFF FFFF hex
                                       deceleration                                                       (-2147483647 to 2147483647)
Built-in output                        curves
functions                                                                                                 Trapezoidal acceleration and deceleration
                                       Changing SVs                                                       (Cannot perform S-curve acceleration and
                                       during                                                             deceleration.)
                                       instruction
                                       execution                                                          Only target position can be changed.

                                       Origin                                                             Included
                                       searches
                                                                                                          2.0 to 6,553.5 Hz (in increments of 0.1 Hz) with 1 output
                        Pulse outputs  Frequency      PWM output function not included                    or 2 Hz to 32,000 Hz (in increments of 1 Hz) with 1 output
                        (Models with                                                                      0.0% to 100.0% (in increments of 0.1%)
                        transistor     Duty factor    Analog function not included                        Accuracy: +1%/-0% at 2 Hz to 10,000 Hz and
                        outputs only)                 2 adjusters (Setting range: 0 to 255)
                                       Output mode                                                                      +5%/-0% at 10,000 Hz to 32,000 kHz
Built-in analog                        Analog input                                                       Continuous Mode
                                       Analog output                                                      Setting range: 0 to 6,000 (2 channels only for NA-type)
Analog adjusters                                                                                          Setting range: 0 to 6,000 (1 channels only for NA-type)

                                                                                                                                                                      9
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

    Item                                                                               CP1E-E@@D@-@                                       CP1E-N@@D@-@
                                                                Conforming to USB 2.0 B type connector                                   CP1E-NA@@D@-@

                      B-type Peripheral USB Port                5 m max.
                                              Transmission
                                              distance                                                               Interface: Conforms to EIA RS-232C.

                      Built-in RS-232C port                                                                          Half duplex
                                              Communications
                                              method            No built-in RS-232C port                             Start-stop
                                              synchronization                                                        1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps
                                              Baud rate
                                              Transmission                                                           15 m max.
                                              distance

                                                     Supported                                                         Host Link
                                                     protocol                                                          1:N NT Link
                                                                                                                      No-protocol mode
    Communications                                                                                                    Serial PLC Links (master, slave)
                            Serial Option port                                                                         Modbus-RTU Easy Master

                                       Mountable                                                                     1 port (Option Board can be mounted only to N30/40/
                                       Option Boards                                                                 60 and NA20 CPU Units.)

                                       Communications                                                                  One RS-232C port: CP1W-CIF01
                                       method                                                                         One RS-422A/485 port (not isolated): CP1W-CIF11
                                       synchronization                                                                One RS-422A/485 port (isolated): CP1W-CIF12
                                       Baud rate                                                                      One Ethernet port: CP1W-CIF41

                                                                Option Board cannot be mounted.                      Depends on Option Board.

                                                                                                                     Depends on Option Board.

                                                                                                                     1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps

                                       Compatible                                                                     Host Link
                                       protocols                                                                      1:N NT Link
                                                                                                                      No-protocol mode
                                                                                                                      Serial PLC Links (master, slave)
                                                                                                                      Modbus-RTU Easy Master

    Number of tasks                                             17
                                                                  One cyclic execution task
    Maximum subroutine number                                     One scheduled interrupt task (always interrupt task 1)
    Maximum jump number                                           Six input interrupt tasks (interrupt tasks 2 to 7)
    Scheduled interrupt tasks                                     Sixteen high-speed counter interrupt tasks (interrupt tasks 1 to 16)

    Clock                                                       128

                                                                128

                                                                1 interrupt task

                                                                Clock function not included.                         Included.
                                                                The time of error occurrence displays 01-01-01
                                                                01:01:01 Sunday                                      Accuracy (monthly deviation):
                                                                                                                     -4.5 min to -0.5 min at ambient temperature of 55oC,
                                                                                                                     -2.0 min to +2.0 min at ambient temperature of 25oC,
                                                                                                                     -2.5 min to +1.5 min at ambient temperature of 0oC

                      Built-in EEPROM                           Ladder programs and parameters are automatically saved to built-in EEPROM
                                                                A section of the Data Memory Area can be saved to the built-in EEPROM.

    Memory            Battery backup With                       Battery cannot be mounted.                           CP1W-BAT01 can be used.
    backup            CP1W-BAT01 Battery                                                                             Maximum battery service life: 5 years
                      (Sold separately)                                                                              Backup Time
                                                                                                                     Guaranteed value (ambient temperature: 55oC):
                                                                                                                     13,000 hours (approx. 1.5 years)
                                                                                                                     Effective value (ambient temperature: 25oC):
                                                                                                                     43,000 hours (approx. 5 years)

                      Input Bits                                1,600 bits (100 words): CIO 0.00 to CIO 99.15 (CIO 00 to CIO 99)
                      Output Bits
    CIO Area          Serial PLC Link Words                     1,600 bits (100 words): CIO 100.00 to CIO 199.15 (CIO 100 to CIO 199)
    Work Area (W)
                                                                1,440 bits (90 words): CIO 200.00 to CIO 289.15 (words CIO 200 to CIO 289)

                                                                1,600 bits (100 words): W0.00 to W99.15 (W0 to W99)

    Holding Area (H)                                            800 bits (50 words): H0.00 to H49.15 (H0 to H49)
                                                                Bits in this area maintain their ON/OFF status when operating mode is changed.

    Auxiliary Area (A)                                          Read-only: 7,168 bits (448 words) A0 to A447
                                                                Read/write: 4,896 bits (306 words) in words A448 to A753
    Temporary Relay Area (TR) (TR Area)
    Timer Area (T)                                              16 bits: TR0 to TR15
    Counter Area (C)
                                                                256 timer numbers (T0 to T255 (separate from counters))

                                                                256 counter numbers (C0 to C255 (separate from timers))

    Data Memory Area (D)                                        2 Kwords: D0 to D2047                                8 Kwords: D0 to D8191
                                                                Of these, 1,500 words can be saved to the backup     Of these, 7,000 words can be saved to the backup
                                                                memory (built-in EEPROM) using settings in the       memory (built-in EEP-ROM) using settings in the
                                                                Auxiliary Area.                                      Auxiliary Area

    Operating modes                                             PROGRAM mode: Program execution is stopped.
                                                                                         Preparations can be executed prior to program execution in this mode.

                                                                MONITOR mode: Programs are executed.
                                                                                        Some operations, such as online editing, and changes to present values in I/O memory, are
                                                                                        enabled in this mode.

                                                                RUN mode: Programs are executed.
                                                                                This is the normal operating mode.

10
                                                           CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Function Specifications

Function                                                        Function description

Cycle time Minimum cycle time                                   Makes the cycle time consistent.
management Monitoring the cycle time                            Monitors the cycle time.

                          High-speed   High-speed pulse inputs  High-speed pulses from devices such as a rotary encoder are counted.
                          counter                               The counted values are stored in the Auxiliary Area.
                          inputs       Input pulse frequency    Interrupt tasks can be executed when target is reached or by range comparison.
                                       measurement
                                                                The frequency of pulses input by the PRV instruction is measured.

                          Interrupt inputs                      Relevant interrupt tasks are executed during the cycle when the CPU Unit built-in inputs
                                                                turn ON or turn OFF.

            Inputs        Quick-response inputs                 Inputs can be read without being affected by cycle time.
                                                                Use the quick-response inputs to read signals shorter than the cycle time.

                          Normal       I/O          Cyclic      The CPU Unit's built-in I/O are cyclically refreshed.
                          inputs       refreshing   refreshing
                                                                I/O refreshing by immediate refreshing instructions
                                                    Immediate
                                                    refreshing  Input constants can be set for Basic I/O Units.
                                                                The response time can be increased to reduce the effects of chattering and noise at input
CPU Unit                               Input response times     contacts. The response time can be decreased to enable detecting shorter input pulses.
built-in
functions

            Outputs       Pulse        Pulse control            A pulse signal is output and positioning or speed control is performed with a servo driver
                          outputs      Origin positioning       that accepts a pulse input.
                          (Models                               Continuous mode for speed control or independent mode for position control can be used.
                          with                                  There are functions for changing to positioning during speed control and for changing the
                          transistor                            target value during positioning.
                          outputs
                          only)                                 Origin searches and origin returns

                          PWM outputs                           Pulses for which the duty ratio (ratio between ON time and OFF time during one pulse

                          (Models with transistor outputs only) cycle) can be set are output.

                          Normal       Load OFF function        All of the outputs on the CPU Unit's I/O can be turned OFF when an error occurs in RUN
                          outputs                               or MONITOR mode.

            Built-in      Analog input                          Convert analog signal into digital value range from 0 to 6,000.
            analog        Analog output                         Convert digital value range from 0 to 6,000 into analog signal.

            Functions     I/O          Cyclic refreshing        The Expansion I/O Units and Expansion Units are cyclically refreshed.
            supported                                           I/O refreshing by IORF instruction
            by both       refreshing Refreshing by IORF
            Expansion                                           All of the outputs on Expansion I/O Units and Expansion Units are turned OFF (0000 hex)
Expansion   I/O Unit and  Load OFF function                     when an error occurs in RUN or MONITOR mode.
I/O Units   Expansion
and         Unit                                                The response time can be increased to reduce the effects of chattering and noise at input
Expansion                                                       contacts. The response time can be decreased to enable detecting shorter input pulses.
Units       Expansion     Input response times
            I/O Units

            Expansion     Unit error detection                  Errors in Expansion Units are detected. The CPU Unit is notified that the Expansion Unit
            Units                                               stopped due to an error.

Memory      Holding I/O memory when changing operating modes    The status of I/O memory can be held when the operating mode is changed.
management                                                      The forced-set/reset status can be held when the operating mode is changed.
functions   Automatic backup to the backup memory
            (built-in EEPROM)                                   Automatic backup of ladder programs and parameter area to the backup memory
                                                                (built-in EEPROM)

            Peripheral    Peripheral bus (toolbus)              For communications with programming device (CX-Programmer).
            USB port

            Serial port (N/NA-type only)                        --

                          Host Link (SYSWAY) communications     Host Link commands can be sent from a PT or a computer to read/write I/O memory, and
                                                                perform other operations for PLC.

Communic                  No-protocol communications            I/O instructions for communications ports (TXD/RXD instructions) can be used for data
ations                    NT Link communications                transfer with peripheral devices such as bar code readers.

                                                                I/O memory in the PLC can be allocated and directly linked to various PT functions,
                                                                including status control areas, status notification areas, touch switches, lamps, memory
                                                                tables, and other objects.

                          Serial PLC Links                      Up to ten words per Unit can be shared by up to nine CPU Units, including one Polling Unit
                                                                and eight Polled Units.
                                                                Note: Programmable Terminal (PT) cannot be connected.

                          Modbus-RTU Easy Master function       Modbus-RTU commands are sent by the Modbus-RTU Master function. Modbus slaves,
                                                                such as inverters, can be easily controlled with serial communications.

            Scheduled interrupts                                Tasks can be executed at a specified interval (1.0 ms min., Unit: 0.1 ms).

Interrupt   Interrupt inputs                                    Interrupt tasks are processed when the built-in input turns ON or OFF.
            High-speed counter interrupts
                                                                This function counts input pulses with the CPU Unit's built-in high-speed counter and
                                                                executes an interrupt task when the count reaches the preset value or falls within a preset
                                                                range (target value or zone comparison).

                                                                                                                                                             11
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

    Function                                                                                               Function description

    Power supply Memory protection                                    Holding Area data, DM Area data, Counter Completion Flags, and counter present values
    management                                                        are held even when power is turned OFF.
                                                                      This function can be used only with an N/NA-type CPU Unit and only when the Battery Set
                                                                      (sold separately) is mounted.

                     Number of power interruptions counter            The number of times power has been interrupted is counted.

                     Online editing                                   The program can be changed during operation in MONITOR mode or PROGRAM mode.

                     Force-set/reset                                  Specified bits can be set or reset.

    Debugging        Differentiate monitoring                         ON/OFF changes in specified bits can be monitored.
                     Storing the stop position at errors              The location and task number where execution stopped for a program error is recorded.

                     Program check                                    The programs can be checked for items such as no END instruction and FALS/FAL errors
                                                                      at startup.

                     Error Log                                        Details and the time of occurrence of error codes predefined by the CPU Unit are stored.

                     CPU error detection                              CPU Unit WDT errors are detected.

                     User-defined failure diagnosis                   Errors can be generated for user-specified conditions:
                                                                      Non-fatal errors (FAL) and fatal errors (FALS).

                     Load OFF function                                The built-in outputs, Expansion I/O Unit outputs, and Expansion Unit outputs are turned
                                                                      OFF.

                                      System FAL error detection      This function generates a non-fatal (FAL) error when the user-defined conditions are met
                                      (User-defined non-fatal error)  in program.

                                      Backup memory error detection   This function detects when data in the backup memory (built-in EEPROM) that stores the
                                                                      ladder program is corrupted.

                     Non-fatal error  PLC Setup error detection       This function detects setting errors in the PLC Setup.

                     detection        Option Board errors             This function detects when the Option Board is malfunctioning or disconnected.

                                      Battery error detection         This function detects when the battery voltage is low or the battery is disconnected.
                                      (N/NA-type CPU Units only)      Note: This function is valid only when a battery is mounted and the Do not detect battery

                                                                               error Check Box is cleared in the PLC Setup.

                                      Built-in analog error           This function detects when a built-in analog I/O error occurs and stops the operation of built-
                                                                      in analog I/O.

                                      Memory error detection          This function detects errors that occur in memory of the CPU Unit.

                                      I/O bus error detection         This function detects errors that occur during data transfer between the CPU Unit and
                                                                      another Unit.

    Self-diagnosis                    Too Many I/O Points Error       This function detects when more than the maximum number of CP1W Expansion I/O Units
    and restoration                   Detection                       and Expansion Units are connected to the PLC.

                                      Program error detection         This function detects when there is an error in the program.
                                                                      See the following for details.

                                          Instruction processing error This function detects an error when the given data value is invalid when executing an

                                          detection                   instruction, or execution of instruction between tasks was attempted.

                                          Indirect DM addressing BCD  This function detects an error when an indirect DM address in BCD mode is not BCD.
                                          error

                     Fatal Error          Illegal area access error   This function detects an error when an attempt is made to access an illegal area with an
                     Detection            detection                   instruction operand.

                                          No END error detection      This function detects an error when there is no END instruction at the end of the program.

                                          Task error detection        The execution condition for an interrupt task was met but there is no interrupt task with the
                                                                      specified number.

                                          overflow error detection    This function detects an error when too many differentiated instructions are entered or
                                                                      deleted during online editing (131,072 times or more).

                                          Invalid instruction error   This function detects an error when an attempt is made to execute an instruction that is not
                                          detection                   defined in the system.

                                          User program area overflow This function detects an error when instruction data is stored after the last address in user

                                          error detection             program area.

                                      Cycle time exceeded error       This function monitors the cycle time (10 to 1,000 ms) and stops the operation when the set
                                      detection                       value is exceeded.

                                      System FALS error detection     This function generates a fatal (FALS) error when the user-defined conditions are met in
                                      (user-defined fatal error)      program.

    Maintenance Automatic online connection via network               This function enables automatically connecting to the PLC online when the CX-Programmer
                                                                      is directly connected by a serial connection (peripheral USB port or serial port).

    Security         Read protection using password                   This function protects user memory.
    functions        Write protection from FINS commands              Read protection: Set a password using the CX-Programmer.
                                                                      Overwrite protection is not provided.

                                                                      This function prohibits writing by using FINS commands sent over the network.

12
                                                                                  CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Internal Memory in the CPU Units

CPU Unit Memory Backup Structure

The internal memory in the CPU Unit consists of built-in RAM and built-in EEPROM. The built-in RAM is used as execution memory and the built-
in EEPROM is used as backup memory.

                                                               CPU Unit

Built-in EEPROM                                                                   Built-in RAM

Backup memory                                                                   Execution Memory

          User Program Area                                     Automatic backup  User Program Area
          (Backup)                                              Read at startup
                                                                                                            Area where data is backed up
PLC Setup                                                       Automatic backup  PLC Setup                 even if the power supply is
                                                                Read at startup                             interrupted for longer than the
                                                                                                            back-up time of the built-in
                                                                                                            capacitor.

                                                                                  I/O Memory Areas          Area where data is cleared if
                                                                                                            the power supply is
DM Area                      Backup using bit in Auxiliary Area                   DM Area                   interrupted for longer than the
                              DM Area data read at startup                                                  back-up time of the built-in
                                                                                                            capacitor.

Data is retained even if the power                              If a CP1W-BAT01 Battery (sold
supply is interrupted for longer                                separately) is mounted to an N/NA-type
than the backup time of the built-in                            CPU Unit, which is normally backed up
capacitor.                                                      by a built-in capacitor, data will be
                                                                backed up by the battery.

Precautions for Correct Use

Create a system and write the ladder programs so that problems will not occur in the system if the data in these area may be unstable.
Data in areas such as the DM area (D), Holding Area (H), the Counter Present Values (C) and the status of Counter Completion Flags (C), which

   is retained by the battery, may be unstable when the power supply is turned off (Except for the DM area that are retained by the built-in EEP-
   ROM using the Auxilliary Area bit.)
The error log, and clock data (N/NA-type CPU Unit only) in the Auxiliary Area will become unstable. Other words and bits in the Auxiliary Area
   will be cleared to their default values.
The built-in capacitor's backup time varies with the ambient temperature as shown in the following graph.

                             Backup time of built-in capacitor  50 hours                          CP1E E-type CPU Unit
                                                                40 hours                          CP1E N/NA-type CPU Unit

                                                                25 hours          40                    60
                                                                20 hours

                                                                 9 hours
                                                                 7 hours

                                                                            25

                                                                                  Ambient temperature

                                                                                                                                             13
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

I/O Memory Areas

Data can be read and written to I/O memory from the ladder programs. I/O memory consists of an area for I/O with external devices, user areas,
and system areas.

                                                         Input bits (starting from CIO 0)                    System Areas

                                                              User Areas                                      Auxiliary Area
                                                                                                                     (A)
                               Work Area (W)                  DM Area (D)                   Timer Area (T)
                              Holding Area (H)                                             Counter Area (C)  Condition Flags
                                                                                                              Clock Pulses

                                                         Output bits (starting from CIO 100)

I/O Memory Areas

                        Name                                  No. of bits  Word addresses                    Remarks

                        Input Bits                       1,600 bits (100 words) CIO 0 to CIO 99  For NA-type, CIO90, CIO91 is occupied by analog input 0, 1.

    CIO Area            Output Bits                      1,600 bits (100 words) CIO 100 to CIO 199 For NA-type, CIO190 is occupied by analog output 0.

                        Serial PLC Link Words 1,440 bits (90 words) CIO 200 to CIO 289                                        --

    Work Area (W)                                        1,600 bits (100 words) W0 to W99                                     --

    Holding Area (H)                                     800 bits (50 words) H0 to H49           Data in this area is retained during power interruptions if a
                                                                                                 Battery Set (sold separately) is mounted to an N/NA-type CPU
                                                                                                 Unit.

                                     E-type CPU Unit     2K words          D0 to D2047           Data in specified words of the DM Area can be retained in the
    Data Memory Area (D)                                 8K words          D0 to D8191           built-in EEPROM in the backup memory by using a bit in the
                                                                                                 Auxiliary Area.
                                     N/NA-type CPU Unit                                          Applicable words: D0 to D1499

                                                                                                                         (One word can be specified at a time.)

                                                                                                 Data in specified words of the DM Area can be retained in the
                                                                                                 built-in EEPROM in the backup memory by using a bit in the
                                                                                                 Auxiliary Area.
                                                                                                 Applicable words: D0 to D6999

                                                                                                                         (One word can be specified at a time.)

    Timer Area (T)      Present values                   256               T0 to T255                                         --

                        Timer Completion Flags 256                                                                            --

    Counter Area (C)    Present values                   256               C0 to C255            Data in this area is retained during power interruptions if a
                                                                                                 Battery Set (sold separately) is mounted to an N/NA-type CPU
                                                                                                 Unit.

                        Counter Completion Flags 256                                                                          --

    Auxiliary Area (A)  Read only                        7168 bits (448 words) A0 to A447        Data in this area is retained during power interruptions if a
                        Read-write                       4,896 bits (306 words) A448 to A753     Battery Set (sold separately) is mounted to an N/NA-type CPU
                                                                                                 Unit.

14
                                             CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Backing Up and Restoring DM Area Data

The contents of the DM Area (D) will become unstable if the power supply is interrupted for longer than the backup time of the built-in capacitor
(50 hours for an E-type CPU Unit, 40 hours for an N/NA-type CPU Unit without a Battery).
The contents of the specified words in the DM Area data can be backed up from RAM to the built-in EEPROM backup memory during operation
by turning ON a bit in the Auxiliary Area. The number of DM Area words to back up is specified in the Number of CH of DM for backup Box in the
PLC Setup. If the Restore D0- from backup memory Check Box is selected in the PLC Setup, the backup data will automatically be restored to
RAM when the power is turned back ON so that data is not lost even if power is interrupted.

                                                                                                          CP1E CPU Unit

                                                                                                                                A751.15 (DM Backup Save Start Bit) turned ON

                                                       Built-in RAM                  Built-in EEPROM Backup Memory
                                                DM Area (D)                            DM backup data
                                          D0
                                                                     Data backed up
                                      D(n-1)
Specified number of words

                                                                     Data restored

Specify the number of words starting                                 DM backup data is restored to the RAM when power supply is
from D0 in the Number of CH of DM                                    turned ON again if the Restore D0- from backup memory Check
for backup Box in the Startup Data                                   Box is selected in the Startup Data Read Area in the PLC Setup.
Read Area in PLC Setup.

Conditions for Executing Backup

Specified words starting from D0 in the RAM can be saved to the built-in EEPROM backup memory by turning ON A751.15.
(These words are called the DM backup words and the data is called the DM backup data.)
A751.15 (DM Backup Save Start Bit) can be used in any operating mode (RUN, MONITOR, or PROGRAM mode).

Words That Can Be Backed Up

E-type CP1E CPU Units: D0 to D1499
N/NA-type CP1E CPU Units: D0 to D6999

Number of Words To Back Up

The number of words to back up starting from D0 is set in the Number of CH of DM for backup Box in the Startup Data Read Area in the PLC Setup.

Restoring DM Backup Data to RAM When Power Is Turned ON

The DM backup data can be restored to RAM when power is turned ON by selecting the Restore D0- from backup memory Check Box in the
Startup Data Read Area in the PLC Setup.
The DM backup data will be read from the backup memory even if the Clear retained memory area (HR/DM/CNT) Check Box is selected in the
PLC Setup.

                                                                                                                                      15
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Built-in Inputs

Terminal Arrangements

Input Terminal Arrangement for CPU Unit with 10 I/O Points

AC power supply models

                 CIO 0

   L1 L2/N COM 01 03 05

    NC  00 02 04

DC power supply models
                 CIO 0

   + - COM 01 03 05

    NC  00 02 04

Input Terminal Arrangement for CPU Unit with 14 I/O Points

AC power supply models

                 CIO 0
   L1 L2/N COM 01 03 05 07 NC NC

    NC  00 02 04 06 NC NC

DC power supply models
                 CIO 0

   + - COM 01 03 05 07 NC NC

    NC  00 02 04 06 NC NC

Input Terminal Arrangement for CPU Unit with 20 I/O Points

AC power supply models

                 CIO 0
   L1 L2/N COM 01 03 05 07 09 11

    NC  00 02 04 06 08 10

DC power supply models

                 CIO 0
    + - COM 01 03 05 07 09 11

    NC  00 02 04 06 08 10

Input Terminal Arrangement for CPU Unit with 30 I/O Points

AC power supply models

        CIO 0                  CIO 1

    L1 L2/N COM 01 03 05 07 09 11 01 03 05

        00 02 04 06 08 10 00 02 04 NC

DC power supply models

        CIO 0                  CIO 1

    + - COM 01 03 05 07 09 11 01 03 05

    NC  00 02 04 06 08 10 00 02 04 NC

16
                        CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Input Terminal Arrangement for CPU Unit with 40 I/O Points

AC power supply models

    CIO 0               CIO 1

L1 L2/N COM 01 03 05 07 09 11 01 03 05 07 09 11

    00 02 04 06 08 10 00 02 04 06 08 10

DC power supply models

    CIO 0               CIO 1

+ - COM 01 03 05 07 09 11 01 03 05 07 09 11

NC  00 02 04 06 08 10 00 02 04 06 08 10

Input Terminal Arrangement for CPU Unit with 60 I/O Points

AC power supply models

    CIO 0               CIO 1                               CIO 2

L1 L2/N COM 01 03 05 07 09 11 01 03 05 07 09 11 01 03 05 07 09 11

    00 02 04 06 08 10 00 02 04 06 08 10 00 02 04 06 08 10

DC power supply models

    CIO 0               CIO 1                               CIO 2

+ - COM 01 03 05 07 09 11 01 03 05 07 09 11 01 03 05 07 09 11

NC  00 02 04 06 08 10 00 02 04 06 08 10 00 02 04 06 08 10

Input Terminal Arrangement for CPU Unit with 20 I/O Points and Built-in Analog

AC power supply models

    CIO 0               CIO 90 CIO 91

L1 L2/N COM 01 03 05 07 09 11 I IN0 AG I IN1

    00 02 04 06 08 10 VIN0 COM0 VIN1 COM1

DC power supply models

    CIO 0               CIO 90 CIO 91

+ - COM 01 03 05 07 09 11 I IN0 AG I IN1

NC  00 02 04 06 08 10 VIN0 COM0 VIN1 COM1

                                                                                17
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Allocating Built-in Inputs to Functions

Input terminals are allocated functions by setting parameters in the PLC Setup. Set the PLC Setup so that each terminal is used for only one function.

                                                                                      Settings in PLC Setup

                   Input terminal block  Interrupt input setting on       High-speed counter 0 to 3 setting on          Origin search settings on Pulse
                                          Built-in Input Tab Page                  Built-in Input Tab Page                      Output 0/1 Tab Page
    CPU Unit with
      I/O Points   Terminal              Normal Interrupt  Quick          Single-phase     Two-phase      Two-phase
                     block                                                 (increment      (differential     (pulse/
                     label   Terminal    Normal Input        Quick-       pulse input)     phase x4 or                  CPU Unit with           CPU Unit with
                             number       input interrupt  response                                        direction)   20 to 60 points         14 I/O points
                                                                                            up/down)
                                                              input

                             00          Normal    --             --      Counter 0,       Counter 0, phase Counter 0,  --                              --
                                         input 0
                                                                          increment input A or up input   pulse input

                             01          Normal    --             --      Counter 1,       Counter 0, phase Counter 1,  --                              --
                                         input 1
                                                                          increment input B or down input pulse input

                             02          Normal Interrupt Quick-response Counter 2,        Counter 1, phase Counter 0,  --                              --

                                         input 2 input 2 input 2          increment input A or up input   direction

         10                              Normal Interrupt Quick-response                   Counter 1, phase Counter 1,                          Pulse 0, Origin
                                         input 3 input 3 input 3                           B or down input direction
                  CIO 0      03                                           --                                            --                      proximity input
        14
                                                                                                                                                signal

                             04          Normal Interrupt Quick-response Counter 3,        Counter 0, phase Counter 0,  --                              --

                                         input 4 input 4 input 4          increment input Z or reset input reset input

                                         Normal Interrupt Quick-response Counter 4,        Counter 1, phase Counter 1,                          Pulse 1, Origin

                             05          input 5 input 5 input 5          increment input Z or reset input reset input  --                      proximity input

                                                                                                                                                signal

                             06          Normal Interrupt Quick-response Counter 5,        --                --         Pulse 0: Origin Pulse 0, Origin

                                         input 6 input 6 input 6          increment input                               input signal            input signal

                             07          Normal Interrupt Quick-response  --               --                --         Pulse 1: Origin Pulse 1, Origin
                                         input 7 input 7 input 7
                                                                                                                        input signal            input signal

                             08          Normal    --             --      --               --                --         --                              --
                                         input 8

                             09          Normal    --             --      --               --                --         --                              --
                                         input 9

        20

                             10          Normal    --             --      --               --                --         Pulse 0: Origin                 --
                                         input 10                                                                       proximity input signal

                             11          Normal    --             --      --               --                --         Pulse 1: Origin                 --
                                         input 11                                                                       proximity input signal

                                         Normal

    30                       00 to 05 input 12     --             --      --               --                --         --                              --

                   CIO 1                 to17
                                         Normal

    40                       06 to 11 input 18     --             --      --               --                --         --                              --

                                         to 23

                                         Normal

    60             CIO 2 00 to 11 input 24         --             --      --               --                --         --                              --

                                         to 35

                                                                                                                        These functions are supported only by
                                                                                                                        N/NA-type CPU Units with transistor
                                                                                                                        outputs.

18
                                   CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Built-in Outputs

Terminal Arrangements                     Output Terminal Arrangement for CPU Unit
                                            with 14 I/O Points
Output Terminal Arrangement for CPU Unit
  with 10 I/O Points                      AC power supply model
                                          DC power supply model
AC power supply model
DC power supply model

00 01 02 03                                00 01 02 03 04 05 NC

COM COM NC COM NC                         COM COM NC COM NC COM NC

CIO 100                                    CIO 100

Output Terminal Arrangement for CPU Unit with 20 I/O Points

AC power supply model
DC power supply model

00 01 02 03 04 05 07

COM COM NC COM NC COM 06

CIO 100

Output Terminal Arrangement for CPU Unit with 30 I/O Points

AC power supply model                     DC power supply model

+ 00 01 02 04 05 07 00 02                  NC 00 01 02 04 05 07 00 02

- COM COM COM 03 COM 06 COM 01 03         NC COM COM COM 03 COM 06 COM 01 03

CIO 100                   CIO 101          CIO 100                               CIO 101

Output Terminal Arrangement for CPU Unit with 40 I/O Points

AC power supply model

+ 00 01 02 03 04 06 00 01 03 04 06

- COM COM COM COM 05 07 COM 02 COM 05 07

              CIO 100     CIO 101
DC power supply model

NC 00 01 02 03 04 06 00 01 03 04 06

NC COM COM COM COM 05 07 COM 02 COM 05 07

CIO 100                   CIO 101

Output Terminal Arrangement for CPU Unit with 60 I/O Points

AC power supply model

+ 00 01 02 04 05 07 00 02 04 05 07 00 02 04 05 07

- COM COM COM 03 COM 06 COM 01     03 COM 06 COM 01                03 COM 06
                                                          CIO 102
          CIO 100         CIO 101
DC power supply model

NC 00 01 02 04 05 07 00 02 04 05 07 00 02 04 05 07

NC COM COM COM 03 COM 06 COM 01 03 COM 06 COM 01 03 COM 06

CIO 100                   CIO 101          CIO 102

Output Terminal Arrangement for CPU Unit with 20 I/O Points and Built-in Analog

AC power supply model                     DC power supply model

+ 00 01 02 04 05 07 NC IOUT0               NC 00 01 02 04 05 07 NC IOUT0

- COM COM COM 03 COM 06 NC VOUT0 COM0     NC COM COM COM 03 COM 06 NC VOUT0 COM0

CIO 100                   CIO 190          CIO 100                               CIO 190

                                                                                          19
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Allocating Built-in Output Terminals to Functions

Output terminals are allocated functions by setting parameters in the PLC Setup. Set the PLC Setup so that each terminal is used for only one function.

    CPU Unit with     Output terminal  Other than those        When a pulse output instruction     Setting in PLC Setup            When the PWM
       I/O points            block        shown right           (SPED, ACC, PLS2, or ORG) is                                  instruction is executed
                                                                                                 Origin search setting on
                    Terminal Terminal   Normal output                          executed         Pulse Output 0/1 Tab Page        Variable duty ratio
                   block label number                                                                                                pulse output
                                                               Fixed duty ratio pulse output                                         PWM output

                                                               Pulse + direction                Use

                              00 Normal output 0               Pulse output 0 (pulse)           --                            --

                              01 Normal output 1               Pulse output 1 (pulse)           --                            PWM output 0

            10

                              02 Normal output 2               Pulse output 0 (direction)       --                            --

                              03 Normal output 3               Pulse output 1 (direction)       --                            --

                     CIO 100  04 Normal output 4               --                               Pulse 0: Error counter reset  --
            14                05 Normal output 5                                                           output

                                                               --                               Pulse 1: Error counter reset  --
                                                                                                           output

                              06 Normal output 6               --                               --                            --

        20

                              07 Normal output 7               --                               --                            --

        30                    00 to 03 Normal output 8 to 11   --                               --                            --

                   CIO 101

    40                        04 to 07 Normal output 12 to 15  --                               --                            --

    60             CIO 102 00 to 07 Normal output 16 to 23     --                               --                            --

                                                               These functions are supported only by N/NA-type CPU Units with transistor outputs.

20
                                                   CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

I/O Specifications for CPU Units

Input Specifications

Item                                                                                                                 Specification

Input type                        High-speed counter inputs or Normal                                    High-speed counter inputs, interrupt
                                  Inputs                                                                 input, quick-response inputs, or Normal Normal inputs
Input bits                                                                                               Inputs
                                  CIO 0.00 to CIO 0.01
Input voltage                                                                                            CIO 0.02 to CIO 0.07 *1                              CIO 0.08 to CIO 0.11,
Applicable sensors                24 VDC, +10%, -15%                                                                                                          CIO 1.00 to CIO 1.11 and
Input Impedance                   2-wire and 3-wire sensors                                                                                                   CIO 2.00 to CIO 2.11 *1
Input current                     3.3 k
ON voltage/current                7.5 mA typical                                                         3.3 k                                                4.8 k
OFF voltage/current               3 mA min. at 17.0 VDC min.                                             7.5 mA typical                                       5 mA typical
ON response time *2               1 mA max. at 5.0 VDC max.                                              3 mA min. at 17.0 VDC min.                           3 mA min. at 14.4 VDC min.
                                  E-type CPU Unit: 50 s min.                                            1 mA max. at 5.0 VDC max.                            1 mA max. at 5.0 VDC max.
OFF response time *2              N/NA-type CPU Unit: 2.5 s min.
                                  E-type CPU Unit: 50 s min.                                            50 s max.                                           1 ms max.
                                  N/NA-type CPU Unit: 2.5 s min.
                                                                                                         50 s max.                             1 ms max.
                                                               E-type CPU Unit
                                  Input 0.00 to 0.07                                                                                           N/NA-type CPU Unit
                                                                                                                     Input 0.00 to 0.01

                                       IN           Input indicator                                                                               IN          Input indicator
                                                   1000pF                                                                                                      1000pF
                                             3.3k                                                                                                       3.3k
                                       IN          910                                                   Internal                                 IN          4.3k                    Internal
                                    COM                                                                  circuits                              COM                                    circuits

Circuit configuration             Input 0.08 to 0.11, 1.00 to 1.11                                                   Input 0.02 to 0.07                              Input indicator
                                                                                                                                                                   1000pF
                                                           IN                                                                                 IN
                                                                                    Input indicator750   Internal                                             910                     Internal
                                                                                                         circuits                                   3.3k                              circuits
                                                           IN 4.8k                                                                            IN
                                                       COM                                                                                COM

                                                                                                                     Inputs CIO 0.08 to CIO 0.11, CIO 1.00 to CIO 1.11 and
                                                                                                                     CIO 2.00 to CIO 2.11

                                                                                                                                              IN
                                                                                                                                                                        Input indicator

                                                                                                                                                   IN 4.8k    750                     Internal
                                                                                                                                               COM                                    circuits

* 1 The bits that can be used depend on the model of CPU Unit.
* 2 The response time is the delay caused by hardware. The delay set in the PLC Setup (0 to 32 ms, default: 8 ms) for a normal input must be

     added to this value.

Pulse plus direction input mode,    Differential phase mode
Increment mode
Up/down input mode

     N/NA-type: 0.00/0.01                               N/NA-type: 0.00/0.01

                  10.0 s min.                                       20.0 s min.

ON                             90%  ON                                                                                    90%
                                    OFF                                                                                   50%
                               50%  ON                                                                                    10%
                                    OFF
OFF                            10%

     2.5 s             2.5 s                                                                                         90%

     min.              min.                                                                                          50%

                                                                                                                     10%

                                                        T1                                           T2  T3  T4    T1, T2, T3, T4: 2.5 s min.

     E-type: 0.00 to 0.07                               E-type: 0.00 to 0.03
     N/NA-type: 0.02 to 0.07                            N/NA-type: 0.02/0.03

                   100 s min.                                        200 s min.

ON                             90%  ON                                                                                    90%
                                    OFF                                                                                   50%
                               50%  ON                                                                                    10%
                                    OFF
OFF                            10%

     50 s              50 s                                                                                          90%

     min.              min.                                                                                          50%

                                                                                                                     10%

                                                        T1                                           T2  T3  T4    T1, T2, T3, T4: 50 s min.

                                                                                                                                                                                                21
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Output Specifications

Output Specifications for Relay Outputs

    Item                                                                                      Specification
                                                                    250 VAC/2 A (cos = 1)
    Maximum switching capacity                                      2 A, 24 VDC (4 A/common)
                                                                    5 VDC, 10 mA
    Minimum switching capacity                                      200,000 operations (24 VDC)
                                                                    70,000 operations (250 VAC, cos = 0.4)
    Service life of    Electrical        Resistive load             20,000,000 operations
    relay              Mechanical        Inductive load             15 ms max.
                                                                    15 ms max.
    ON delay

    OFF response time

                                                                    Output indicator  OUT

    Circuit configuration                                           Internal          OUT
                                                                    circuits
                                                                                      COM 250 VAC, 2A,
                                                                                             24 VDC, 2 A
                                                                                             max.

Estimating the Service Life of Relays

Under normal conditions, the service life of output contacts is as shown above. The service life of relays is as shown in the following diagram as a guideline

                           CP1E-@@DR-@

    1000

                  700      125-VAC resistive load

                  500

                  300      30-VDC/250-VAC
                  200
                           resistive load

    Life (x 104)  100
                   70
                   50

                  30
                  20

                  10 125 VAC cos= 0.4

                   7

                   5 250 VAC cos= 0.4/
                   3 30 VDC,  = 7ms

                   2

                  1

                  0.1 0.2 0.3 0.5 0.7 1  2 3 5 7 10

                       Contact current (A)

Relationship between Continuous Simultaneous ON Rate and Ambient Temperature

There are restrictions on the power supply voltage and output load current imposed by the ambient temperature. Make sure that the power supply
voltage and output load current are within the following ranges.

                       CP1E-N14DR-D/CP1E-N20DR-D                              CP1E-N30DR-D                               CP1E-N40DR-D

                 100%                                                 100%                                         100%
                          Power voltage
                             21.6 VDC                                           Power voltage                              Power voltage
                                                                                  21.6 VDC                                  21.6 VDC
                   50%                                                                                             50%
                           Power voltage                               50%
                             20.4 VDC                                           Power voltage                            Power voltage
                                                                                  20.4 VDC                               20.4 VDC
                    0%
                                                40 45 55C               0%                                        0%    30               45 50 55C
                                                                                                  35 45 55C
                               Ambient temperature                                                                       Ambient temperature
                                                                                      Ambient temperature
    CP1E-@14DR-A/CP1E-@20DR-A/CP1E-N20DT@-@                                                                              CP1E-N60DR-D
                 100%                                                            CP1E-NA20DR-A
                                                                                                                   100%
                   50%                                              100%
                                                                                                                          Power voltage
                                                                      80%                                                    21.6 VDC

                                                                                                                   50%
                                                                                                                          Power voltage
                                                                                                                             20.4 VDC

                       0%                                           0%                                             0%
                                                           50 55C                                        50 55C                             40 45 55C

                                 Ambient temperature                           Ambient temperature                           Ambient temperature

Note: The above restrictions apply to the relay output load current from the CPU Unit even if Expansion I/O Units are not connected.

22
                                                            CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Output Specifications for Transistor Outputs (Sinking or Sourcing)

Normal Outputs

                                                                                    Specification

Item                                       CIO 100.00 and CIO 100.01                           CIO 100.02 to CIO 100.07, CIO 101.00 to CIO 101.07
                                                                                                            and CIO 102.00 to CIO 102.07 *2
Maximum switching capacity
                            0.3 A/output, 0.9 A/common *1                                      CP1E-N20D@-@: 1.8 A/Unit CP1E-N30D@-@: 2.7 A/Unit
Minimum switching capacity  4.5 to 30 VDC                                                      CP1E-NA20D@-@: 1.8 A/Unit
Leakage current
Residual voltage            CP1E-E10D@-@: 0.9 A/Unit CP1E-N14D@-@: 1.5 A/Unit
ON response time            CP1E-N40D@-@: 3.6 A/Unit CP1E-N60D@-@: 5.4 A/Unit
OFF response time
Fuse                        1 mA 4.5 to 30 VDC

                            0.1mA max.

                            E-type CPU Unit: 1.5 V max.                                        1.5V max.
                            N/NA-type CPU Unit: 0.6 V max.

                            0.1 ms max.                                                        0.1 ms max.

                            E-type CPU Unit: 1 ms max.                                         1 ms max.
                            N/NA-type CPU Unit: 0.1 ms max.

                            Not provided.

                            N/NA-type CPU Unit:                                                E-type CPU Unit:
                            Normal outputs CIO 100.00 to CIO 100.01 (sinking)                  Normal outputs CIO 100.00 to CIO 100.03 (sinking)
                                                                                               N/NA-type CPU Unit:
                                                                                               Normal outputs CIO 100.02 to CIO 102.07 (sinking)

                                                              OUT L              ~                                        OUT L~
                                                              OUT L                                                       OUT L
                            Internal            Internal                            24 VDC,               Internal                24 VDC,
                            circuits            circuits      COM()                4.5 to 30             circuits        COM()  4.5 to 30
                                                                                    VDC                                           VDC

Circuit configuration       N/NA-type CPU Unit:                                                E-type CPU Unit:
                            Normal outputs CIO 100.00 to CIO 100.01 (sourcing)                 Normal outputs CIO 100.01 to CIO 100.03 (sourcing)
                                                                                               N/NA-type CPU Unit:
                                                                                               Normal outputs CIO 100.02 to CIO 102.07 (sourcing)

                            Internal            Internal      COM(+)                24 VDC,               Internal        COM(+)  24 VDC,
                            circuits            circuits                            4.5 to 30             circuits                4.5 to 30
                                                              OUT L                 VDC                                   OUT L   VDC
                                                              OUT L                                                       OUT L
                                                                                 ~

                                                                                                                          ~

Note: Do not connect a load to an output terminal or apply a voltage in excess of the maximum switching capacity.

* 1 Also do not exceed 0.9 A for the total for CIO 100.00 to CIO 100.03. (CIO 100.00 to CIO 100.03 is different common.)
* 2 The bits that can be used depend on the model of CPU Unit.

Pulse Outputs (CIO 100.00 and CIO 100.01)

Item                                                      Specification
Maximum switching capacity
Minimum switching capacity  100 mA/4.5 to 26.4 VDC
Maximum output frequency    7 mA/4.5 to 26.4 VDC
                            100 kHz

                            OFF 90%

Output waveform             ON 10%

                                                    4s min.                     2s min.

Note: 1. The load for the above values is assumed to be the resistance load, and does not take into account the impedance for the connecting
            cable to the load.

        2. Due to distortions in pulse waveforms resulting from connecting cable impedance, the pulse widths in actual operation may be smaller

    than the values shown above.
3. The OFF and ON refer to the output transistor. The output transistor is ON at level "L".

PWM Output (CIO 100.01)

Item                                                              Specification
Maximum switching capacity  30 mA/4.5 to 26.4 VDC
Maximum output frequency    32 kHz
                            For ON duty +1%, .0%:10 kHz output
PWM output accuracy         For ON duty +5%, .0%: 0 to 32 kHz output

                            OFF

Output waveform             ON

                                                     tON     ON duty= tON 100%
                                                T                           T

Note: The OFF and ON refer to the output transistor. The output transistor is ON at level "L".

                                                                                                                                                   23
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Built-in Analog I/O (NA-type CPU Units)

Analog Input Specifications

                         Item                            Voltage input                                     Current input

    Number of inputs                           2 inputs (Allocated 2 words: CIO 90 to CIO 91.)

    Input signal range                         0 to 5 V, 1 to 5 V, 0 to 10 V, or -10 to 10 V 0 to 20 mA or 4 to 20 mA

    Max. rated input                           15 V                                          30 mA

    External input impedance                   1 M min.                                       Approx. 250

    Resolution                                 1/6000

    Overall accuracy          At 25C          0.3% full scale                               0.4% full scale
                              0 to 55C
                                               0.6% full scale                               0.8% full scale

    A/D conversion data       -10 to +10 V     F448 to 0BB8 hex FS
                              Other ranges
                                               0000 to 1770 hex FS

    Averaging function                         Supported (Set for individual inputs in the PLC Setup.)

    Open-circuit detection function            Supported (Value when disconnected: 8000 hex)

Analog Output Specifications

                         Item                            Voltage output                                         Current output

    Number of outputs                          1 output (Allocated 1 word: CIO 190.)          0 to 20 mA or 4 to 20 mA
                                                                                              600 max.
    Output signal range                        0 to 5 V, 1 to 5 V, 0 to 10 V, or -10 to 10 V  ---

    Allowable external output load resistance  1 k min.

    External input impedance                   0.5max.

    Resolution                                 1/6000

    Overall accuracy          At 25C          0.4% full scale *
                              0 to 55C        0.8% full scale *

    D/A conversion data       -10 to +10 V     F448 to 0BB8 hex FS
                              Other ranges     0000 to 1770 hex FS

* In 0 to 20 mA mode, accuracy cannot be ensured at 0.2 mA or less.

Shared I/O Specifications

                         Item                                                                    Specification

    Conversion time                            2 ms/point (6 ms total for 2 analog inputs and 1 analog output.)
    Isolation method
                                               Photocoupler isolation between analog I/O terminals and internal circuits.
                                               No isolation between analog I/O signals.

24
                                             CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Specifications of Expansion I/O Units and Expansion Units

Expandable CPU Units

Expansion I/O Units and Expansion Units cannot be connected to E10/14/20 or N14/20 CPU Units.
A total of up to three Expansion I/O Units and Expansion Units can be connected to an E30/40, N30/40/60 or NA20 CPU Unit.

CP1E E10/14/20 or N14/20 CPU Unit

                                                                                                                      CP-series Expansion Units and Expansion I/O
                                                                                                                      Units cannot be connected.

CP1E E30/40, N30/40/60 or NA20 CPU Unit

                                                                           A total of up to three CP-series Expansion I/O Units
                                                                           and Expansion Units can be connected.

                                                  NC      NC      COM 01          03      05      07      09      11      01      03      05      07  09     11            NC      NC      COM 01          03      05      07      09      11      01      03      05      07      09 11                NC      NC      COM 01          03      05      07      09      11      01      03      05      07      09      11

                                                      NC      NC      00      02      04      06      08      10      00      02      04      06      08 10                    NC      NC      00      02      04      06      08      10      00      02      04      06      08  10                       NC      NC      00      02      04      06      08      10      00      02      04      06      08      10

                                                                          CH                                              CH                                                                       CH                                              CH                                                                           CH                                              CH

                                           IN     CH                                                                                              40EDR                IN  CH                                                                                              40EDR                    IN  CH                                                                                              40EDR
                                          OUT          00 01 02 03 04 05 06 07 08 09 10 11                                                                            OUT       00 01 02 03 04 05 06 07 08 09 10 11                                                                                OUT       00 01 02 03 04 05 06 07 08 09 10 11

                                                  CH                                                                                                                       CH                                                                                                                           CH
                                                       00 01 02 03 04 05 06 07 08 09 10 11                                                                                      00 01 02 03 04 05 06 07 08 09 10 11                                                                                          00 01 02 03 04 05 06 07 08 09 10 11

                                                  CH                                                                                                                       CH                                                                                                                           CH
                                                       00 01 02 03 04 05 06 07                                                                                                  00 01 02 03 04 05 06 07                                                                                                      00 01 02 03 04 05 06 07

                                                  CH                                                                                                                       CH                                                                                                                           CH
                                                       00 01 02 03 04 05 06 07                                                                                                  00 01 02 03 04 05 06 07                                                                                                      00 01 02 03 04 05 06 07

                                                                  CH                                          CH                                                 EXP                       CH                                          CH                                                 EXP                           CH                                          CH                                                      EXP

                                                          NC  00      01      02      04      05      07      00      02      04      05      07                                   NC  00      01      02      04      05      07      00      02      04      05      07                                       NC  00      01      02      04      05      07      00      02      04      05      07

                                                      NC COM COM COM 03 COM 06 COM 01                                     03 COM 06                                            NC COM COM COM 03 COM 06 COM 01                                     03 COM 06                                                NC COM COM COM 03 COM 06 COM 01                                     03 COM 06

Connection Methods

Connection cables for the Expansion I/O Units and Expansion Units are used to connect the Units. The length can be extended by using a CP1W-
CN811 I/O Connection Cable (length: 800 m).

Maximum Number of I/O Points for an Expanded System

               Built-in I/O on CPU Unit                           Built-in Analog                                                                                           Total number of                                                                                                                        Number of inputs: 24
                                                                                                                                                                      Expansion I/O Units and                                                                                                                     Number of outputs: 16
     CPU Unit                                                                                                                                                         Expansion Units that can                                                                                                 Total number of I/O points when three CP1W-40ED@
                                                                                                                                                                                                                                                                                                          Expansion I/O Units are connected
CP1E-E10D@-@                                                                                                                                                                  be connected
CP1E-@14D@-@       Total  Number of Number of                             AD                                                          DA                                                                                                                                                                    Total                                                                                       Number of                    Number of
CP1E-@20D@-@                                                                                                                                                          Not possible.                                                                                                                                                                                                                        inputs                      outputs
CP1E-@30D@-@   10             inputs     outputs
CP1E-@40D@-@   14                                                                                                                                                     3 Units maximum
CP1E-N60D@-@   20         6           4                                                                                                                                                                                                                                                        10                                                                                       6                                        4
CP1E-NA20D@-@  30
               40         8           6                                                                                                                                                                                                                                                        14                                                                                       8                                        6
               60
               20         12          8                       None None                                                                                                                                                                                                                        20                                                                                       12                                       8

                          18          12                                                                                                                                                                                                                                                       150                                                                                      90                                       60

                          24          16                                                                                                                                                                                                                                                       160                                                                                      96                                       64

                          36          24                                                                                                                                                                                                                                                       180                                                                                      108                                      72

                          12          8                       2                                                           1                                                                                                                                                                    140                                                                                      84                                       56

Restrictions on External Power Supply Capacity

The following restrictions apply when using the CPU Unit's external power supply.

AC-power-supply E30/40, N30/40/60 or NA20 CPU Unit

The power supply capacity is restricted for AC-power-supply E30/40, N30/40/60 or NA20 CPU Units. It may not be possible to use the full 300 mA
of the external power supply, though a CPU Unit can connect any CP-series Expansion I/O Unit or Expansion Unit.
The entire 300 mA from the external power supply can be used if Expansion Units and Expansion I/O Units are not connected.
Refer to the CP1E CPU Unit Hardware Manual (Cat. No. W479) for details.

AC-power-supply or DC-power-supply E10/14/20, N14/20 CPU Unit

There is no external power supply on AC-power-supply or DC-power-supply E10/14/20, N14/20 CPU Units.

                                                                                                                                                                                                                                                                                                                                                                                                                                                25
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Specifications of Expansion I/O Units

Input Specifications (CP1W-40EDR/40EDT/40EDT1/20EDR1/20EDT/20EDT1/8ED)

                       Item                                       Specification
    Input voltage
    Input impedance                24 VDC +10%/-15%
    Input current                  4.7 k
    ON voltage                     5 mA typical
    OFF voltage                    14.4 VDC min.
    ON delay                       5.0 VDC max.
    OFF delay                      1 ms max. *
                                   1 ms max. *

                                   IN

                                                               Input LED

    Circuit configurationLife ( 104) IN 4.7 k                                                                                       Internal
                                                                                                                   750 COM           circuits

Note: Do not apply voltage in excess of the rated voltage to the input terminal.
* The response time is the hardware delay value. The delay set in the PLC Setup (0 to 32 ms, default: 8 ms) must be added to this value. For the

  CP1W-40EDR/EDT/EDT1, a fixed value of 16 ms must be added.

Output Specifications
  Relay Outputs (CP1W-40EDR/32ER/20EDR1/16ER/8ER)

                             Item                                                                                        Specification

    Max. switching capacity                           2 A, 250 VAC (cos = 1),
                                                      2 A, 24 VDC (4 A/common)

    Min. switching capacity                           5 VDC, 10 mA

    Service life of  Electrical    Resistive load 150,000 operations (24 VDC)
    relay            Mechanical    Inductive load 100,000 operations (240 VAC, cos = 0.4)
    (See note.)
                                                          20,000,000 operations

    ON delay                                          15 ms max.

    OFF delay                                         15 ms max.

                                                                                                                                                         v

                                                                                                                         Output LED  OUT

    Circuit configuration                               Internal                                                                     OUT
                                                        circuits
                                                                                                                                     COM Maximum
                                                                                                                                           250 VAC: 2 A
                                                                                                                                           24 VDC: 2 A

Note: 1. Estimating the Service Life of Relays
            The service life of output contacts is as shown in the following diagram.

                                   120 VAC resistive load

                     300           24 VDC  = 7 ms

                     200           120 VAC cos = 0.4

                     100           240 VAC cos = 0.4

                                   24 VDC/240 VAC resistive load

                     50

                     30
                     20

                     10

                     5

                     3                                                                                                   Switching rate: 1,800 operations/hour

                     2

                     0.1           0.2 0.3 0.5 0.7 1  2 35

                                   Contact current (A)

26
                                        CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@Output load current(%)

2. Restrictions of CP1W-16ER/32ER
    Limit the output load current to satisfy the following derating curve.

        100

          50

                              0                   43                    55

                                 Ambient temperature(C)

3. CP1W-32ER's maximum number of simultaneously ON output points is 24 (75%).
    Relation between Number of ON Outputs and Ambient Temperature (CP1W-32ER)

Number of inputs          75
   ON simultaneously (%)

                              0                                   55

                                 Ambient temperature (C)

4. According to the ambient temperature, there are restrictions on power supply voltage and output load current for the CPU Units
    connected with the Expansion I/O Units (CP1W-8ER/16ER/20EDR1/32ER/40EDR). Use the PLC in the range of the power supply
    voltage and output load current as show below.
    The ambient temperature is restricted for the power-supply CPU Units (CP1E-N/NA@@@@-@). Derating curve of the output load current
    for Expansion I/O Units (CP1W-8ER/16ER/20EDR1/32ER/40EDR).

Connected to CP1E-N30DR-D                                         Connected to CP1E-N40DR-D            Connected to CP1E-N30DT@-D       Connected to CP1E-N40DT@-D
100%                                                              100%                                 100%
                                                                                                                                        100%
                                  Power voltage:                  50%   Power                                  Power voltage:            50%  Power
                                  21.6 VDC                              voltage:                               21.6 VDC                       voltage:
                          50%                                           21.6 VDC                       50%                                    21.6 VDC

                                Power voltage:                          Power                                Power voltage:                   Power
                                20.4 VDC                                voltage:                             20.4 VDC                         voltage:
                                                                        20.4 VDC                                                              20.4 VDC
                          0%
                                                   35 45 55C     0%                                   0%    35 45 55C                 0%
                                                                                                                                                                35 45 55C
                                             Ambient temperature            30             45 50 55C        Ambient temperature
                                                                                                                                                          Ambient temperature

                                                                            Ambient temperature

Connected to                                                      Connected to CP1E-NA20DT@-D Connected to CP1E-NA20DR-A

CP1E-N60DR-D/CP1E-N60DT@-D

100%                                                              100%                                 100%

         Power voltage:                                                    Power voltage:              80%
         21.6 VDC                                                          21.6 VDC

50%                                                               50%

                                 Power voltage:                         Power voltage:
                                 20.4 VDC                               20.4 VDC

                          0%                                      0%                                   0%                      50 55C
                                                                                                             Ambient temperature
                                                  40 45 55C                               40 45 55C

                                 Ambient temperature                        Ambient temperature

                                                                                                                                                                               27
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Transistor Outputs (Sinking or Sourcing)

                   Item                CP1W-40EDT            CP1W-32ET                 Specification            CP1W-16ET          CP1W-8ET
                                      CP1W-40EDT1           CP1W-32ET1                 CP1W-20EDT              CP1W-16ET1         CP1W-8ET1
    Max. switching capacity      4.5 to 30 VDC        4.5 to 30 VDC                   CP1W-20EDT1        4.5 to 30 VDC     4.5 to 30 VDC
    *1                           0.3 A/output         0.3 A/output               24 VDC +10%/-5%         0.3 A/output      0.3 A/output
                                 0.9 A/common         0.9 A/common               0.3 A/output            0.9 A/common      0.9 A/common
    Leakage current              3.6 A/Unit           7.2 A/Unit                 0.9 A/common            3.6 A/Unit        1.8 A/Unit
    Residual voltage             0.1 mA max.          0.1 mA max.                1.8 A/Unit              0.1 mA max.       0.1 mA max.
    ON delay                     1.5 V max.           1.5 V max.                 0.1 mA max.             1.5 V max.        1.5 V max.
                                 0.1 ms max.          0.1 ms max.                1.5 V max.              0.1 ms max.       0.1 ms max.
    OFF delay                    1 ms max.            1 ms max.                  0.1 ms.                 1 ms max.         1 ms max.
                                 24 VDC +10%/-5%      24 VDC +10%/-5%            1 ms max.               24 VDC +10%/-5%   24 VDC +10%/-5%
    Max. number of               5 to 300 mA          5 to 300 mA                24 VDC +10%/-5%         5 to 300 mA       5 to 300 mA
    Simultaneously ON                                                            5 to 300 mA
    Points of Output             16 pts (100%)        24 pts (75%)                                       16 pts (100%)     8 pts (100%)
    Fuse *2                                                                      8 pts (100%)
                                 1 fuse/common

                                 Sinking Outputs                                             Sourcing Outputs

                                    Output LED                                               Output LED

                                    Internal                      OUT                                          COM (+)
                                    circuits                            L
                                                                                                                         24 VDC/4.5
    Circuit configuration                                                    L               Internal          OUT to 30 VDC
                                                                        OUT                  circuits
                                                                                 24 VDC/4.5                          L
                                                                                 to 30 VDC
                                                                                                                     L
                                                                        COM (-)                                OUT

*1 If the ambient temperature is maintained below 50C, up to 0.9 A/common can be used.
                    (A)
                    0.9
                    0.8
    Total current for common

                              0  Ambient temperature  50 55 (C)

*2 The fuse cannot be replaced by the user. Replace the Unit if the fuse breaks due to an short-circuit or overcurrent.
*3 Do not connect a load to an output terminal or apply a voltage in excess of the maximum switching capacity.

28
                                                                CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Specifications of Expansion Units

Analog Input Units

                         Model                                                            CP1W-AD041
                          Item
Number of inputs                                                Voltage Input                                   Current Input

                                           4 inputs (4 words allocated)

Input signal range                         0 to 5 VDC, 1 to 5 VDC,                             0 to 20 mA or 4 to 20 mA
                                           0 to 10 VDC, or 10 to 10 VDC

Max. rated input                           15 V                                               30 mA

External input impedance                   1 M min.                                            Approx. 250

Resolution                                 1/6000 (full scale)

Overall accuracy                25C       0.3% full scale                                     0.4% full scale
                                0 to 55C
                                           0.6% full scale                                     0.8% full scale

A/D conversion data                        16-bit binary (4-digit hexadecimal)
                                           Full scale for 10 to 10 V: F448 to 0BB8 Hex
                                           Full scale for other ranges: 0000 to 1770 Hex

Averaging function                         Supported (Set in output words n+1 and n+2.)
Open-circuit detection function
Conversion time                            Supported
Isolation method
Current consumption                        2 ms/point (8 ms/all points)

                                           Photocoupler isolation between analog I/O terminals and internal circuits. No isolation between analog I/O signals.

                                           5 VDC: 100 mA max.; 24 VDC: 90 mA max.

Analog Output Units

                  Model                                                               CP1W-DA021/CP1W-DA041

                    Item                                        Voltage Output                                  Current Output

            Number of outputs              CP1W-DA021: 2 outputs (2 words allocated)
                                           CP1W-DA041: 4 outputs (4 words allocated)

            Output signal range            1 to 5 VDC, 0 to 10 VDC, or 10 to 10 VDC           0 to 20 mA or 4 to 20 mA

            External output allowable      2 k min.                                            350  max.
            load resistance                                                                    ---

Analog      External output impedance 0.5  max.
output
section     Resolution                     1/6000 (full scale)

            Overall             25C       0.4% full scale
            accuracy            0 to 55C  0.8% full scale

            D/A conversion data            16-bit binary (4-digit hexadecimal)
                                           Full scale for 10 to 10 V: F448 to 0BB8 Hex
                                           Full scale for other ranges: 0000 to 1770 Hex

Conversion time                            CP1W-DA021: 2 ms/point (4 ms/all points)
                                           CP1W-DA041: 2 ms/point (8 ms/all points)

Isolation method                           Photocoupler isolation between analog I/O terminals and internal circuits. No isolation between analog I/O signals.

Current consumption                        CP1W-DA021: 5 VDC: 40 mA max.; 24 VDC: 95 mA max.
                                           CP1W-DA041: 5 VDC: 80 mA max.; 24 VDC: 124 mA max.

                                                                                                                                                                29
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Analog I/O Units

                                     Model                                                               CP1W-MAD11
                                       Item
                           Number of inputs                                              Voltage I/O                                   Current I/O

                                                                       2 inputs (2 words allocated)

                           Input signal range                          0 to 5 VDC, 1 to 5 VDC,                        0 to 20 mA or 4 to 20 mA
                                                                       0 to 10 VDC, or -10 to 10 VDC

                           Max. rated input                            15 V                                          30 mA
                           External input impedance
                           Resolution                                  1 M min.                                       Approx. 250

    Analog Input           Overall accuracy                            1/6000 (full scale)
    Section
                                                      25C             0.3% full scale                                0.4% full scale
                                                      0 to 55C
                                                                       0.6% full scale                                0.8% full scale

                           A/D conversion data                         16-bit binary (4-digit hexadecimal)
                                                                       Full scale for -10 to 10 V: F448 to 0BB8 hex
                                                                       Full scale for other ranges: 0000 to 1770 hex

                           Averaging function                          Supported (Settable for individual inputs via DIP switch)
                           Open-circuit detection function
                           Number of outputs                           Supported

                                                                       1 output (1 word allocated)

                           Output signal range                         1 to 5 VDC, 0 to 10 VDC, or                    0 to 20 mA or 4 to 20 mA
                                                                       -10 to 10 VDC,

                           Allowable external output load resistance   1 k min.                                       600  max.

    Analog Output          External output impedance                   0.5  max.
    Section
                           Resolution                                  1/6000 (full scale)

                           Overall accuracy           25C             0.4% full scale
                                                      0 to 55C
                                                                       0.8% full scale

                           Set data (D/A conversion)                   16-bit binary (4-digit hexadecimal)
                                                                       Full scale for -10 to 10 V: F448 to 0BB8 hex
                                                                       Full scale for other ranges: 0000 to 1770 hex

    Conversion time                                                    2 ms/point (6 ms/all points)
    Isolation method
    Current consumption                                                Photocoupler isolation between analog I/O terminals and internal circuits.
                                                                       No isolation between analog I/O signals.

                                                                       5 VDC: 83 mA max., 24 VDC: 110 mA max.

Temperature Sensors Units

                   Item                         CP1W-TS001                    CP1W-TS002                 CP1W-TS101                       CP1W-TS102

                                       Thermocouples                                                  Platinum resistance thermometer

    Temperature sensors                Switchable between K and J, but same type must be used for     Switchable between Pt100 and JPt100, but same type must
                                       all inputs.                                                    be used for all inputs.

    Number of inputs                   2                               4                              2                                4

    Allocated input words              2                               4                              2                                4

    Accuracy                           (The larger of 0.5% of converted value or 2C) 1 digit      (The larger of 0.5% of converted value or 1C) 1 digit
                                       max. *                                                         max.

    Conversion time                    250 ms for 2 or 4 input points

    Converted temperature data         16-bit binary data (4-digit hexadecimal)

    Isolation                          Photocouplers between all temperature input signals

    Current consumption                5 VDC: 40 mA max., 24 VDC: 59 mA max.                          5 VDC: 54 mA max., 24 VDC: 73 mA max.

* Accuracy for a K-type sensor at -100C or less is 4C 1 digit max.

The rotary switch is used to set the temperature range.

    Setting                                     CP1W-TS001/TS002                                                      CP1W-TS101/TS102

          0                      Input type           Range (C)          Range (F)               Input type         Range (C)                    Range (F)
          1                K                                                                 Pt100
          2                                     -200 to 1,300             -300 to 2,300      JPt100                   -200.0 to 650.0     -300.0 to 1,200.0
          3                J                                                                 ---
          4 to F           ---                  0.0 to 500.0              0.0 to 900.0       ---                      -200.0 to 650.0     -300.0 to 1,200.0
                                                                                             ---
                                                -100 to 850               -100 to 1,500

                                                0.0 to 400.0              0.0 to 750.0                                Cannot be set.

                                                Cannot be set.

CompoBus/S I/O Link Unit

    Model number                                                           CP1W-SRT21
    Master/slave                       CompoBus/S Slave
    Number of I/O points               8 input points, 8 output points
    Number of words allocated in CPU
    Unit I/O memory                    1 input word, 1 output word

    Node number setting                Set using the DIP switch
                                       (Set before turning on the CPU Unit's power supply.)

30
                                                           CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

External Interfaces

The CP1E CPU Units provide the following external interfaces.                                                           N-type

E10/14/20 or N14/20 CPU Units

                                                  E-type
                                   Power supply input terminals

Input terminal block                                   Ground terminal
                                                       Input terminals
Input indicators
                                                                                                                                       Built-in RS-232C
Peripheral                                                                                                                             communications
USB port                                                                                                                               status indicator
Analog
adjusters                                                                                                                              Built-in
Operation indicators                                                                                                                   RS-232C port
Output terminals
                                                       Output indicators              Battery
                                                                                      cover
                                                       Output terminal
                                                       block

Note: Terminal Block (Fixed)

E30/40, N30/40/60 or NA20 CPU Units

                                 E-type                                                                       N-type/NA-type

                Power supply          Input terminals                                             Built-in RS-232C communications
                input terminals                                                                   status indicator

Input terminal                                             Ground                     Battery                                                  Analog input
block                                                      terminal                   cover                                                    terminal
                                                                                                                                               (NA-type only)
Input                                                      Expansion
indicators                                                 I/O Unit                                                                            Analog output
Peripheral                                                 connector                                                                           terminals
USB port                                                                                                                                       (NA-type only)
                                                           Output
Analog                                                     indicators
adjusters
                                                           Output
Operation                                                  terminal
indicators                                                 block

                      External power     Output terminals
                         supply
                                                                                                  Built-in RS-232C              Serial Option
                                                                                                  port                          Board slot

Note: Terminal Block (Fixed)

Serial Communications Port for N/NA-type CPU Units

The Serial Communication Port can be used for a CP1E N/NA-type CPU Unit.

                                                                 Optional Serial Communication Board

                                      CP1E N30/40/60             Model number                     Port                      Maximum     Connection method
                                      or NA20 CPU Units                                                                  transmission
                                                                                                                                       Connector
Built-in                                                         CP1W-CIF01                       One RS-232C port          distance   (D-sub, 9 pin female)
RS-232C port                                                     CP1W-CIF11                                             15 m           Terminal block
                                                                 CP1W-CIF12                       One RS-422A/485 port                 (using ferrules)
                                                                 CP1W-CIF41                       (not isolated)        50 m           Terminal block
                                                                                                  One RS-422A/485 port                 (using ferrules)
                                                                                                  (isolated)            500 m          Connector
                                                                                                                                       (RJ45, 8 pin modular)
                                                                                                  One Ethernet port     100 m

                                                                        IP ADDRESS:
                                                                        SUBNET MASK:

                                                                          COMM ERR     10BASE-T
                                                                                      100BASE-TX

CP1W-CIF01                       CP1W-CIF11/12                   CP1W-CIF41
RS-232C Option                   RS-422A/485 Option              Ethernet Option
Board                            Board                           Board version 2.0 or higher

                                                                                                                                                               31
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Built-in RS-232C Port and CP1W-CIF01 RS-232C Option Board

                  Front                  Back                 RS-232C Connector

Communications Status Indicator                                     5                    1     Pin            Abbr.     Signal name         Signal direction

                       COMM                                                                 1                 FG        Frame ground                          --

                                                                                            2                 SD (TXD) Send data            Output

                                                                                            3                 RD (RXD) Receive data         Input

                                                                    9                    6  4                 RS (RTS) Request to send      Output
                                                                                                              CS (CTS) Clear to send        Input
                                                                                            5

                                                                                            6                 5V        Power supply                          --

    RS-232 Connector                     CPU Unit Connector                                 7                 DR (DSR) Data set ready       Input

                                                                                            8                 ER (DTR) Data terminal ready Output

                                                                                            9                 SG (0 V) Signal ground                          --

                                                                                            Connector         FG        Frame Ground                          --
                                                                                            hood

                                                                                            Note: Do not use the 5-V power from pin 6 of the RS-232C port for
                                                                                                    anything but CJ1W-CIF11 RS-422A Conversion Adapter,
                                                                                                    NT-AL001 RS-232C/RS-422A Conversion Adapter and
                                                                                                    NV3W-M@20L Programmable Terminal.
                                                                                                    The external device or the CPU Unit may be damaged.

CP1W-CIF11/CIF12 RS-422A/485 Option Board

                  Front                  Back                                            RS-422A/485 Terminal Block

Communications Status Indicator

           COMM                                        CPU Unit                                                         Tighten the terminal block screws
    RDA- RDB+ SDA- SDB+ FG                             Connector                                                        to a torque of 0.28 Nm.

                                                       DIP Switch for                    RDA-                       FG
                                                       Operation Settings                          RDB+ SDA-  SDB+

RS-422A/485 Connector

CP1W-CIF41 Ethernet Option Board version 2.0 or higher

    Front                                                           Rear

    IP ADDRESS:               Label
    SUBNET MASK:
                              Attach the label here to show
    COMM ERR       10BASE-T   IP address and subnet mask.
                  100BASE-TX
                              Ethernet Connector

                              Used to connect the Ethernet
                              twisted-pair cable.

    LED Indicators                                            CPU Unit connector

    Display the operating status of
    the Option Board.

Specifications                                                                              FINS Communications Service Specifications

    Type                                 100/10Base-TX (Auto-MDIX)                          Number of nodes             254
    Support Software                                                                        Message Length
                                         CX-Programmer version 9.12 or higher               Date Length                 552 bytes max.
                  Media access method                                                       Number of buffer
                  Modulation method      CSMA/CD                                            Protocol name               540 bytes max.
                  Transmission paths                                                                                    (except for FINS header 10 byte and Command
                                         Baseband                                           Protocol used               header 2 byte.)
                  Baud rate
                                         Star form                                          Number of connections       8k byte
    Transfer                                                                                Port number
                  Transmission           100 Mbit/s           10 Mbit/s                                                 FINS/UDP method FINS/TCP method
                  media                  (100Base-TX)         (10Base-TX)                   Protection

                  Transmission Distance   Half/full auto-negotiation for each port                                     UDP/IP                             TCP/IP
                  Number of cascade       Link speed auto-sensing for each port
                  connections                                                                                           The selection of UDP/IP or TCP/IP is
                                          Unshielded          Unshielded                                              made from the FINS/TCP Tab by the Web
                                           twisted-pair         twisted-pair                                            browser function.
                                           (UDP) cable          (UDP) cable
                                           Categories: 5, 5e    Categories: 3, 4, 5, 5e                                                ---                 2

                                          Shielded twisted-   Shielded twisted-                                       9600 (default)                     9600 (default)
                                           pair (STP) cable     pair (STP) cable                                        Can be changed.                    Can be changed.
                                           Categories:          Categories:
                                           100 at 5, 5e         100 at 3, 4, 5, 5e                                                                         Yes (Specification

                                                                                                                                                           of client IP

                                         100 m (distance between hub and node)                                          No                                 addresses when

                                                                                                                                                           unit is used as a

                                         No restrictions if switching hubs are used.                                                                       server)

32
                                                            CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Connecting to Support Software

Operating Environment and System Configuration

The following system is required to operate the CX-Programmer. Make sure your system provides the following conditions and has the necessary
components.

         Item                                         Description

Supported computer           IBM PC/AT or equivalent

CD-ROM or DVD-ROM drive One or more

Supported Operating Systems  Windows 2000 (Service Pack 4 or higher), XP, Vista, or 7
                             (except 64-bit edition)

CPU                          Pentium II 333 MHz or faster

RAM                          256 MB min. 512 MB or more recommended

Available hard disk space    600 MB min.

Display                      800 x 600 SVGA min.

PLC and connection port      USB port, RS-232C port, RS-422A/485 port or Ethernet port

Connecting Methods

Using commercially available USB cable, connect the CX-Programmer to the peripheral USB port on the CPU Unit.
Host link connection can be made with RS-232C port to connect the Programming Device (CX-Programmer).

                  CX-Programmer

                                      USB port

         A connector                            CP1E CPU Unit

Commercially available
USB cable

                             B connector

         Peripheral USB port
         (Conforming to USB 2.0, B connector)

Connecting Cable

Use the following cable to connect the CP1E CPU Unit to the computer running the Support Software.

USB port                                  Port at computer          Network type                          Model numbers           Length
                                               USB port     (communications mode)                                             Less than 5 m
                    Port at Unit                                                        Commercially available USB cable
                                                                  USB 2.0 (or 1.1)      (A connector - B connector)
Peripheral USB port
(Conforming to USB 2.0, B connector)

RS-232C Port for N/NA-type CPU Units

         Port at Unit                     Port at computer Communications mode          Model         Connecting Cable               Remarks
                                                                                                                Length
                                                                                                                              With anti-static
                                                                                        XW2Z-200S-CV                      2m  connectors

RS-232C Port or                           RS-232C port *    Host Link                   XW2Z-500S-CV                      5m  With anti-static
CP1W-CIF01                                                  (SYSWAY)                                                          connectors
(Add this to the option board slot.)
                                                                                        XW2Z-200S-V                       2m              ---

                                                                                        XW2Z-500S-V                       5m              ---

Note: Connectable with CX-Programmer Ver.9.1 or higher only.
* Use the USB-Serial Conversion Cable CS1W-CIF31 together to connect a PLC to a personal computer's USB port.

                                                                                                                                                33
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@
Unit Versions

                 Units       Model numbers                   Unit version
    CP1E CPU Units                                   Unit version 1.@
                        CP1E-E@@D@-@
                        CP1E-N@@D@-@
                        CP1E-NA@@D@-@

Unit Versions and Programming Devices

The following tables show the relationship between unit versions and CX-Programmer versions.

Unit Versions and Programming Devices

                                                                                                                  Required Programming Device *

    CPU Unit            Functions                    CX-Programmer               Micro PLC Edition CX-Programmer                                                    CX-
                                                                                                                                                              Programmer
                                       Ver.8.1 or        Ver.8.2       Ver.9.03    Ver.8.1 or      Ver.8.2       Ver.9.0                            Ver.9.03
                                         lower                        or higher       lower                                                        or higher    for CP1E
                                                     Not support.                              Not support.  Not support.                                         Ver.1.0
    CP1E-E10D@-@        Unit version   Not support.                 Yes          Not support.                                                    Yes
    CP1E-@14D@-@        1.@ functions                Yes            Supports                   Yes           Yes                                 Supports     Not support.
    CP1E-N60D@-@                                     Does not       Smart Input  Not support.  Does not      Supports                            Smart Input
    CP1E-NA20D@-@                                    support        function.                  support       Smart Input                         function.    Yes
                                                     Smart Input                               Smart Input   function.                                        Supports
CP1E-E20/30/40D@-A      Unit version   Not support.  function.      Yes                        function.                                         Yes          Smart Input
CP1E-N20/30/40D@-@      1.@ functions                               Supports                                                                     Supports     function.
                                                                    Smart Input                                                                  Smart Input
                                                                    function.                                                                    function.

* A Programming Console cannot be used.

34
                                                 CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Programming Instructions

Sequence Input Instructions                      Comparison Instructions

                 Instruction           Mnemonic           Instruction                 Mnemonic
LOAD
LOAD NOT                      LD                                                LD,AND,OR+=
AND                           LD NOT
AND NOT                       AND                                               LD,AND,OR+<>
OR                            AND NOT
OR NOT                        OR                 Input Comparison Instructions  LD,AND,OR+<
AND LOAD                      OR NOT             (unsigned)                     LD,AND,OR+<=
OR LOAD                       AND LD
NOT                           OR LD                                             LD,AND,OR+>
CONDITION ON                  NOT
CONDITION OFF                 UP                                                LD,AND,OR+>=
                              DOWN
                                                                                LD,AND,OR+=+L

                                                                                LD,AND,OR+<>+L

                                                 Input Comparison Instructions  LD,AND,OR+<+L
                                                 (double, unsigned)             LD,AND,OR+<=+L

                                                                                LD,AND,OR+>+L

Sequence Output Instructions                                                    LD,AND,OR+>=+L

                                                                                LD,AND,OR+=+S

                 Instruction           Mnemonic                                 LD,AND,OR+<>+S
OUTPUT
OUTPUT NOT                    OUT                Input Comparison Instructions  LD,AND,OR+<+S
KEEP                          OUT NOT            (signed)                       LD,AND,OR+<=+S
DIFFERENTIATE UP              KEEP
DIFFERENTIATE DOWN            DIFU                                              LD,AND,OR+>+S
SET                           DIFD
RESET                         SET                                               LD,AND,OR+>=+S
MULTIPLE BIT SET              RSET
MULTIPLE BIT RESET            SETA                                              LD,AND,OR+=+SL
SINGLE BIT SET                RSTA
SINGLE BIT RESET              SETB                                              LD,AND,OR+<>+SL
                              RSTB
                                                 Input Comparison Instructions  LD,AND,OR+<+SL
                                                 (double, signed)               LD,AND,OR+<=+SL

                                                                                LD,AND,OR+>+SL

                                                                                LD,AND,OR+>=+SL

                                                                                =DT

Sequence Output Instructions                                                    <>DT

                 Instruction           Mnemonic  Time Comparison Instructions    END                                                                             <=DT
NO OPERATION                  END
INTERLOCK                     NOP                                               >DT
INTERLOCK CLEAR               IL
MULTI-INTERLOCK               ILC                                               >=DT
DIFFERENTIATION HOLD
MULTI-INTERLOCK               MILH               COMPARE                        CMP
DIFFERENTIATION RELEASE
MULTI-INTERLOCK CLEAR         MILR               DOUBLE COMPARE                 CMPL
JUMP
JUMP END                      MILC               SIGNED BINARY COMPARE          CPS
CONDITIONAL JUMP              JMP
FOR LOOP                      JME                DOUBLE SIGNED BINARY           CPSL
BREAK LOOP                    CJP                COMPARE
NEXT LOOP                     FOR
                              BREAK              TABLE COMPARE                  TCMP
                              NEXT
                                                 UNSIGNED BLOCK COMPARE         BCMP

                                                 AREA RANGE COMPARE             ZCP

                                                 DOUBLE AREA RANGE COMPARE ZCPL

                                                 Data Movement Instructions

                                                                  Instruction         Mnemonic
                                                 MOVE
Timer and Counter Instructions                   DOUBLE MOVE                    MOV
                                                 MOVE NOT                       MOVL
         Instruction                   Mnemonic  MOVE BIT                       MVN
                                                 MOVE DIGIT                     MOVB
TIMER                         TIM                MULTIPLE BIT TRANSFER          MOVD
                              TIMX               BLOCK TRANSFER                 XFRB
COUNTER                       CNT                BLOCK SET                      XFER
                              CNTX               DATA EXCHANGE                  BSET
HIGH-SPEED TIMER              TIMH               SINGLE WORD DISTRIBUTE         XCHG
                              TIMHX              DATA COLLECT                   DIST
ONE-MS TIMER                  TMHH                                              COLL
                              TMHHX
ACCUMULATIVE TIMER            TTIM
                              TTIMX
LONG TIMER                    TIML
                              TIMLX
REVERSIBLE COUNTER            CNTR
                              CNTRX
RESET TIMER/COUNTER           CNR
                              CNRX

                                                                                                 35
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Data Shift Instructions                           Conversion Instructions

                     Instruction        Mnemonic             Instruction              Mnemonic
    SHIFT REGISTER
    REVERSIBLE SHIFT REGISTER     SFT             BCD-TO-BINARY                 BIN
    WORD SHIFT                    SFTR
    ARITHMETIC SHIFT LEFT         WSFT            DOUBLE BCD-TO-DOUBLE          BINL
    ARITHMETIC SHIFT RIGHT        ASL             BINARY
    ROTATE LEFT                   ASR
    ROTATE RIGHT                  ROL             BINARY-TO-BCD                 BCD
    ONE DIGIT SHIFT LEFT          ROR
    ONE DIGIT SHIFT RIGHT         SLD             DOUBLE BINARY-TO-DOUBLE BCD BCDL
    SHIFT N-BITS LEFT             SRD
    DOUBLE SHIFT N-BITS LEFT      NASL            2'S COMPLEMENT                NEG
    SHIFT N-BITS RIGHT            NSLL
    DOUBLE SHIFT N-BITS RIGHT     NASR            DATA DECODER                  MLPX
                                  NSRL
                                                  DATA ENCODER                  DMPX

                                                  ASCII CONVERT                 ASC

                                                  ASCII TO HEX                  HEX

                                                  Logic Instructions

                                                                   Instruction        Mnemonic
                                                  LOGICAL AND
Increment/Decrement Instructions                  DOUBLE LOGICAL AND            ANDW
                                                  LOGICAL OR                    ANDL
                     Instruction        Mnemonic  DOUBLE LOGICAL OR             ORW
    INCREMENT BINARY                              EXCLUSIVE OR                  ORWL
    DOUBLE INCREMENT BINARY       ++              DOUBLE EXCLUSIVE OR           XORW
    DECREMENT BINARY              ++L             COMPLEMENT                    XORL
    DOUBLE DECREMENT BINARY       --              DOUBLE COMPLEMENT             COM
    INCREMENT BCD                 --L                                           COML
    DOUBLE INCREMENT BCD          ++B
    DECREMENT BCD                 ++BL            Special Math Instructions
    DOUBLE DECREMENT BCD          --B
                                  --BL                             Instruction        Mnemonic
                                                  ARITHMETIC PROCESS
Symbol Math Instructions                          BIT COUNTER                   APR
                                                                                BCNT

    Instruction                         Mnemonic  Floating-point Math Instructions

    SIGNED BINARY ADD WITHOUT     +                                Instruction                   Mnemonic
    CARRY                                         FLOATING TO 16-BIT            FIX
                                                  FLOATING TO 32-BIT            FIXL
    DOUBLE SIGNED BINARY ADD      +L              16-BIT TO FLOATING            FLT
    WITHOUT CARRY                                 32-BIT TO FLOATING            FLTL
                                                  FLOATING-POINT ADD            +F
    SIGNED BINARY ADD WITH CARRY +C               FLOATING-POINT SUBTRACT       -F
                                                  FLOATING-POINT DIVIDE         /F
    DOUBLE SIGNED BINARY ADD      +CL             FLOATING-POINT MULTIPLY       *F
    WITH CARRY                                                                  LD, AND, OR+=F
                                                  Floating Symbol Comparison    LD, AND, OR+<>F
    BCD ADD WITHOUT CARRY         +B                                            LD, AND, OR+                                                   FLOATING- POINT TO ASCII      LD, AND, OR+<=F
    DOUBLE BCD ADD WITHOUT CARRY +BL              ASCII TO FLOATING-POINT       LD, AND, OR+>F
                                                                                LD, AND, OR+>=F
    BCD ADD WITH CARRY            +BC                                           FSTR
                                                                                FVAL
    DOUBLE BCD ADD WITH CARRY +BCL

    SIGNED BINARY SUBTRACT        -
    WITHOUT CARRY

    DOUBLE SIGNED BINARY          -L
    SUBTRACT WITHOUT CARRY

    SIGNED BINARY SUBTRACT WITH   -C
    CARRY

    DOUBLE SIGNED BINARY          -CL
    SUBTRACT WITH CARRY

    BCD SUBTRACT WITHOUT CARRY -B

    DOUBLE BCD SUBTRACT           -BL             Table Data Processing Instructions
    WITHOUT CARRY

    BCD SUBTRACT WITH CARRY       -BC                              Instruction        Mnemonic
                                                  SWAP BYTES
    DOUBLE BCD SUBTRACT WITH      -BCL            FRAME CHECKSUM                SWAP
    CARRY                                                                       FCS

    SIGNED BINARY MULTIPLY        *               Data Control Instructions

    DOUBLE SIGNED BINARY MULTIPLY *L

    BCD MULTIPLY                  *B                         Instruction              Mnemonic

    DOUBLE BCD MULTIPLY           *BL             PID CONTROL WITH AUTOTUNING PIDAT

    SIGNED BINARY DIVIDE          /               TIME-PROPORTIONAL OUTPUT TPO

    DOUBLE SIGNED BINARY DIVIDE /L                SCALING                       SCL

    BCD DIVIDE                    /B              SCALING 2                     SCL2

    DOUBLE BCD DIVIDE             /BL             SCALING 3                     SCL3

                                                  AVERAGE                       AVG

36
                                              CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Subroutine Instructions

                 Instruction        Mnemonic
SUBROUTINE CALL
SUBROUTINE ENTRY              SBS
SUBROUTINE RETURN             SBN
                              RET

Interrupt Control Instructions

                 Instruction        Mnemonic
SET INTERRUPT MASK
CLEAR INTERRUPT               MSKS
DISABLE INTERRUPTS            CLI
ENABLE INTERRUPTS             DI
                              EI

High-speed Counter and Pulse Output
Instructions

                 Instruction        Mnemonic
MODE CONTROL
HIGH-SPEED COUNTER PV READ    INI
COMPARISON TABLE LOAD         PRV
SPEED OUTPUT                  CTBL
SET PULSES                    SPED
PULSE OUTPUT                  PULS
ACCELERATION CONTROL          PLS2
ORIGIN SEARCH                 ACC
PULSE WITH VARIABLE DUTY      ORG
FACTOR
                              PWM

Step Instructions

                 Instruction        Mnemonic
STEP DEFINE
STEP START                    STEP
                              SNXT

I/O Unit Instructions

                 Instruction        Mnemonic
I/O REFRESH
7-SEGMENT DECODER             IORF
DIGITAL SWITCH INPUT          SDEC
MATRIX INPUT                  DSW
7-SEGMENT DISPLAY OUTPUT      MTR
                              7SEG

Serial Communications Instructions

                 Instruction        Mnemonic
TRANSMIT
RECEIVE                       TXD
                              RXD

Clock Instructions

                 Instruction        Mnemonic
CALENDAR ADD
CALENDAR SUBTRACT             CADD
CLOCK ADJUSTMENT              CSUB
                              DATE

Failure Diagnosis Instructions

                 Instruction        Mnemonic
FAILURE ALARM
SEVERE FAILURE ALARM          FAL
                              FALS

Other Instructions

                 Instruction        Mnemonic
SET CARRY
CLEAR CARRY                   STC
EXTEND MAXIMUM CYCLE TIME     CLC
                              WDT

                                              37
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Dimensions                                                                                                                              (Unit: mm)

CP1E CPU Unit

CPU Units with 10 I/O Points

                66                                                                                      85

                56                                                                                                               8

    110 100 90

                                                                         Two, 4.5 dia.                  85
                                                                                                                              8
CPU Units with 14 or 20 I/O Points

                                               86
                                               76

    110 100 90

                         Two, 4.5 dia.

CPU Units with 30 I/O Points
  CPU Units with 20 I/O Points and Built-in Analog

                    130                                                                                                          85

                    120                                                                                                              8

    110 100 90

                                                                                        Four, 4.5 dia.

38
CPU Units with 40 I/O Points                                                              CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

                                                               150                                                                        85
                                                               140                                                                                               8

110 100 90

                                                                                          Four, 4.5 dia.

CPU Units with 60 I/O Points                                                                                              85
                                                                                                                                                8
                                                                                     195
                                                                                     185

110 100 90

                                                                                                          Four, 4.5 dia.

                                                                                                                                                   39
CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Expansion I/O Units and Expansion Units

CP1W-8E@@/CP1W-SRT21

       5           66                              50
                                                               8
                   560.2

    1000.2
               90

    5                          Two, 4.5 dia.

CP1W-20ED@/CP1W-16E@@/CP1W-AD041/CP1W-DA021/CP1W-DA041/CP1W-MAD11/CP1W-TS@@@

                       86                                     50
                                                                          8
       5               760.2

    1000.2
               90

    5                               Two, 4.5 dia.

CP1W-40ED@/CP1W-32E@@

                               150                                           50
                               140                                                       8

    110 100 90

                                              Four, 4.5 dia.

40
                                    CP1E-E@@D@-@ CP1E-N@@D@-@/NA20D@-@

Related Manuals

Manual name               Cat. No.      Model numbers  Application                                  Contents

SYSMAC CP Series CP1E     W479      CP1E-E@@D@-@       To learn the hardware specifications of the  Describes the following information for
CPU Unit Hardware Manual            CP1E-N@@D@-@       CP1E PLCs
                                    CP1E-NA@@D@-@                                                   CP1E PLCs.
                                                                                                      Overview and features
                                    CP1E-E@@D@-@                                                      Basic system configuration
                                    CP1E-N@@D@-@                                                      Part names and functions
                                    CP1E-NA@@D@-@                                                    Installation and settings
                                                                                                      Troubleshooting
                                    CP1E-E@@D@-@
                                    CP1E-N@@D@-@       Use this manual together with the CP1E CPU Unit Software Manual (Cat. No. W480) and
                                    CP1E-NA@@D@-@      CP1E CPU Unit Instructions Reference Manual (Cat. No. W483).

SYSMAC CP Series CP1E     W480      CS1G/H-CPU@@H      To learn the software specifications of the  Describes the following information for
CPU Unit Software Manual            CS1G/H-CPU@@-V1    CP1E
                                    CS1D-CPU@@H                                                     CP1E PLCs.
                                    CS1D-CPU@@S                                                       CPU Unit operation
                                    CS1W-SCU@@-V1                                                    Internal memory
                                    CS1W-SCB@@-V1                                                    Programming
                                    CJ1G/H-CPU@@H                                                    Settings
                                    CJ1G-CPU@@P                                                       CPU Unit built-in functions
                                    CJ1M-CPU@@                                                       Interrupts
                                    CJ1G-CPU@@                                                       High-speed counter inputs
                                    CJ1W-SCU@@-V1                                                    Pulse outputs
                                    CP1L-L10D@-@                                                      Serial communications
                                    CP1L-L14D@-@                                                      Analog I/O function
                                    CP1L-L20D@-@                                                      Other functions
                                    CP1L-M30D@-@
                                    CP1L-M40D@-@       Use this manual together with the CP1E CPU Unit Hardware Manual (Cat. No. W479)
                                    CP1L-M60D@-@       and CP1E CPU Unit Instructions Reference Manual (Cat. No. W483).
                                    CP1E-E@@D@-@
SYSMAC CP Series CP1E     W483      CP1E-N@@D@-@       To learn programming instructions in detail  Describes each programming instruction in
CPU Unit Instructions               CP1E-NA@@D@-@                                                   detail.
Reference Manual                                                                                    When programming, use this manual
                                                                                                    together with the CP1E CPU Unit
                                                                                                    Hardware Manual (Cat. No. W479) and
                                                                                                    CP1E CPU Unit Software Manual (Cat. No.
                                                                                                    W480).

                                                       To learn communications commands for         Describes 1) C-mode commands and 2)
                                                       CS/CJ/CP/NSJ-series Controllers in detail    FINS commands in detail.
                                                                                                    Read this manual for details on C-mode
CS/CJ/CP/NSJ Series                                                                                 and FINS commands addressed to CPU
Communications Commands                                                                             Units.
Reference Manual
                          W342                         Note: This manual describes commands addressed to CPU Units. It does not cover
                                                                commands addressed to other Units or ports (e.g., serial communications ports
                                                                on CPU Units, communications ports on Serial Communications Units/Boards,
                                                                and other Communications Units).

SYSMAC CP Series          W461                         To learn the basic setup methods of the      Describes the following information for
CP1L/CP1E CPU Unit                                     CP1L/CP1E PLCs                               CP1L/CP1E PLCs.
Introduction Manual                                                                                  Basic configuration and component

                                                                                                       names
                                                                                                      Mounting and wiring
                                                                                                      Programming, data transfer, and

                                                                                                       debugging using the CX-Programmer
                                                                                                      Application program examples

                                                                                                                                               41
                                                                             MEMO

42
Terms and Conditions of Sale

1. Offer; Acceptance. These terms and conditions (these "Terms") are deemed                      ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.
     part of all quotes, agreements, purchase orders, acknowledgments, price lists,              BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
     catalogs, manuals, brochures and other documents, whether electronic or in                  PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
     writing, relating to the sale of products or services (collectively, the "Products")        INTENDED USE. Omron further disclaims all warranties and responsibility of
     by Omron Electronics LLC and its subsidiary companies ("Omron"). Omron                      any type for claims or expenses based on infringement by the Products or oth-
     objects to any terms or conditions proposed in Buyer's purchase order or other              erwise of any intellectual property right. (c) Buyer Remedy. Omron's sole obli-
     documents which are inconsistent with, or in addition to, these Terms.                      gation hereunder shall be, at Omron's election, to (i) replace (in the form
                                                                                                 originally shipped with Buyer responsible for labor charges for removal or
2. Prices; Payment Terms. All prices stated are current, subject to change with-                 replacement thereof) the non-complying Product, (ii) repair the non-complying
     out notice by Omron. Omron reserves the right to increase or decrease prices                Product, or (iii) repay or credit Buyer an amount equal to the purchase price of
     on any unshipped portions of outstanding orders. Payments for Products are                  the non-complying Product; provided that in no event shall Omron be responsi-
     due net 30 days unless otherwise stated in the invoice.                                     ble for warranty, repair, indemnity or any other claims or expenses regarding
                                                                                                 the Products unless Omron's analysis confirms that the Products were prop-
3. Discounts. Cash discounts, if any, will apply only on the net amount of invoices              erly handled, stored, installed and maintained and not subject to contamina-
     sent to Buyer after deducting transportation charges, taxes and duties, and will            tion, abuse, misuse or inappropriate modification. Return of any Products by
     be allowed only if (i) the invoice is paid according to Omron's payment terms               Buyer must be approved in writing by Omron before shipment. Omron Compa-
     and (ii) Buyer has no past due amounts.                                                     nies shall not be liable for the suitability or unsuitability or the results from the
                                                                                                 use of Products in combination with any electrical or electronic components,
4. Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month or                 circuits, system assemblies or any other materials or substances or environ-
     the maximum legal rate, whichever is less, on any balance not paid within the               ments. Any advice, recommendations or information given orally or in writing,
     stated terms.                                                                               are not to be construed as an amendment or addition to the above warranty.
                                                                                                 See http://www.omron247.com or contact your Omron representative for pub-
5. Orders. Omron will accept no order less than $200 net billing.                                lished information.
6. Governmental Approvals. Buyer shall be responsible for, and shall bear all               14. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE
                                                                                                 FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
     costs involved in, obtaining any government approvals required for the impor-               LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY
     tation or sale of the Products.                                                             WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS
7. Taxes. All taxes, duties and other governmental charges (other than general                   BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
     real property and income taxes), including any interest or penalties thereon,               Further, in no event shall liability of Omron Companies exceed the individual
     imposed directly or indirectly on Omron or required to be collected directly or             price of the Product on which liability is asserted.
     indirectly by Omron for the manufacture, production, sale, delivery, importa-          15. Indemnities. Buyer shall indemnify and hold harmless Omron Companies and
     tion, consumption or use of the Products sold hereunder (including customs                  their employees from and against all liabilities, losses, claims, costs and
     duties and sales, excise, use, turnover and license taxes) shall be charged to              expenses (including attorney's fees and expenses) related to any claim, inves-
     and remitted by Buyer to Omron.                                                             tigation, litigation or proceeding (whether or not Omron is a party) which arises
8. Financial. If the financial position of Buyer at any time becomes unsatisfactory              or is alleged to arise from Buyer's acts or omissions under these Terms or in
     to Omron, Omron reserves the right to stop shipments or require satisfactory                any way with respect to the Products. Without limiting the foregoing, Buyer (at
     security or payment in advance. If Buyer fails to make payment or otherwise                 its own expense) shall indemnify and hold harmless Omron and defend or set-
     comply with these Terms or any related agreement, Omron may (without liabil-                tle any action brought against such Companies to the extent based on a claim
     ity and in addition to other remedies) cancel any unshipped portion of Prod-                that any Product made to Buyer specifications infringed intellectual property
     ucts sold hereunder and stop any Products in transit until Buyer pays all                   rights of another party.
     amounts, including amounts payable hereunder, whether or not then due,                 16. Property; Confidentiality. Any intellectual property in the Products is the exclu-
     which are owing to it by Buyer. Buyer shall in any event remain liable for all              sive property of Omron Companies and Buyer shall not attempt to duplicate it
     unpaid accounts.                                                                            in any way without the written permission of Omron. Notwithstanding any
9. Cancellation; Etc. Orders are not subject to rescheduling or cancellation                     charges to Buyer for engineering or tooling, all engineering and tooling shall
     unless Buyer indemnifies Omron against all related costs or expenses.                       remain the exclusive property of Omron. All information and materials supplied
10. Force Majeure. Omron shall not be liable for any delay or failure in delivery                by Omron to Buyer relating to the Products are confidential and proprietary,
     resulting from causes beyond its control, including earthquakes, fires, floods,             and Buyer shall limit distribution thereof to its trusted employees and strictly
     strikes or other labor disputes, shortage of labor or materials, accidents to               prevent disclosure to any third party.
     machinery, acts of sabotage, riots, delay in or lack of transportation or the          17. Export Controls. Buyer shall comply with all applicable laws, regulations and
     requirements of any government authority.                                                   licenses regarding (i) export of products or information; (iii) sale of products to
11. Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron:                   "forbidden" or other proscribed persons; and (ii) disclosure to non-citizens of
     a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship              regulated technology or information.
                                                                                            18. Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any right
        except in "break down" situations.                                                       and no course of dealing between Buyer and Omron shall operate as a waiver
     b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall          of rights by Omron. (b) Assignment. Buyer may not assign its rights hereunder
                                                                                                 without Omron's written consent. (c) Law. These Terms are governed by the
        constitute delivery to Buyer;                                                            law of the jurisdiction of the home office of the Omron company from which
     c. All sales and shipments of Products shall be FOB shipping point (unless oth-             Buyer is purchasing the Products (without regard to conflict of law princi-
                                                                                                 ples). (d) Amendment. These Terms constitute the entire agreement between
        erwise stated in writing by Omron), at which point title and risk of loss shall          Buyer and Omron relating to the Products, and no provision may be changed
        pass from Omron to Buyer; provided that Omron shall retain a security inter-             or waived unless in writing signed by the parties. (e) Severability. If any provi-
        est in the Products until the full purchase price is paid;                               sion hereof is rendered ineffective or invalid, such provision shall not invalidate
     d. Delivery and shipping dates are estimates only; and                                      any other provision. (f) Setoff. Buyer shall have no right to set off any amounts
     e. Omron will package Products as it deems proper for protection against nor-               against the amount owing in respect of this invoice. (g) Definitions. As used
        mal handling and extra charges apply to special conditions.                              herein, "including" means "including without limitation"; and "Omron Compa-
12. Claims. Any claim by Buyer against Omron for shortage or damage to the                       nies" (or similar words) mean Omron Corporation and any direct or indirect
     Products occurring before delivery to the carrier must be presented in writing              subsidiary or affiliate thereof.
     to Omron within 30 days of receipt of shipment and include the original trans-
     portation bill signed by the carrier noting that the carrier received the Products
     from Omron in the condition claimed.
13. Warranties. (a) Exclusive Warranty. Omron's exclusive warranty is that the
     Products will be free from defects in materials and workmanship for a period of
     twelve months from the date of sale by Omron (or such other period expressed
     in writing by Omron). Omron disclaims all other warranties, express or implied.
     (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION,
     EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-

Certain Precautions on Specifications and Use

1. Suitability of Use. Omron Companies shall not be responsible for conformity                   ADDRESS THE RISKS, AND THAT THE OMRON'S PRODUCT IS PROP-
     with any standards, codes or regulations which apply to the combination of the              ERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
     Product in the Buyer's application or use of the Product. At Buyer's request,               OVERALL EQUIPMENT OR SYSTEM.
     Omron will provide applicable third party certification documents identifying          2. Programmable Products. Omron Companies shall not be responsible for the
     ratings and limitations of use which apply to the Product. This information by              user's programming of a programmable Product, or any consequence thereof.
     itself is not sufficient for a complete determination of the suitability of the Prod-  3. Performance Data. Data presented in Omron Company websites, catalogs
     uct in combination with the end product, machine, system, or other application              and other materials is provided as a guide for the user in determining suitabil-
     or use. Buyer shall be solely responsible for determining appropriateness of                ity and does not constitute a warranty. It may represent the result of Omron's
     the particular Product with respect to Buyer's application, product or system.              test conditions, and the user must correlate it to actual application require-
     Buyer shall take application responsibility in all cases but the following is a             ments. Actual performance is subject to the Omron's Warranty and Limitations
     non-exhaustive list of applications for which particular attention must be given:           of Liability.
     (i) Outdoor use, uses involving potential chemical contamination or electrical         4. Change in Specifications. Product specifications and accessories may be
     interference, or conditions or uses not described in this document.                         changed at any time based on improvements and other reasons. It is our prac-
     (ii) Use in consumer products or any use in significant quantities.                         tice to change part numbers when published ratings or features are changed,
     (iii) Energy control systems, combustion systems, railroad systems, aviation                or when significant construction changes are made. However, some specifica-
     systems, medical equipment, amusement machines, vehicles, safety equip-                     tions of the Product may be changed without any notice. When in doubt, spe-
     ment, and installations subject to separate industry or government regulations.             cial part numbers may be assigned to fix or establish key specifications for
     (iv) Systems, machines and equipment that could present a risk to life or prop-             your application. Please consult with your Omron's representative at any time
     erty. Please know and observe all prohibitions of use applicable to this Prod-              to confirm actual specifications of purchased Product.
     uct.                                                                                   5. Errors and Omissions. Information presented by Omron Companies has been
     NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS                                  checked and is believed to be accurate; however, no responsibility is assumed
     RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT                                     for clerical, typographical or proofreading errors or omissions.
     ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
OMRON ELECTRONICS LLC THE AMERICAS HEADQUARTERS Schaumburg, IL USA 847.843.7900 800.556.6766 www.omron247.com

OMRON CANADA, INC. HEAD OFFICE                                      OMRON ARGENTINA SALES OFFICE
Toronto, ON, Canada 416.286.6465 866.986.6766                     Cono Sur 54.11.4783.5300
www.omron247.com
                                                                      OMRON CHILE SALES OFFICE
OMRON ELETRNICA DO BRASIL LTDA HEAD OFFICE                         Santiago 56.9.9917.3920
So Paulo, SP, Brasil 55.11.2101.6300 www.omron.com.br
                                                                      OTHER OMRON LATIN AMERICA SALES
OMRON ELECTRONICS MEXICO SA DE CV HEAD OFFICE                       54.11.4783.5300
Apodaca, N.L. 52.811.156.99.10 001.800.556.6766 mela@omron.com

Omron Europe B.V. Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. Tel: +31 (0) 23 568 13 00 Fax: +31 (0) 23 568 13 88 www.industrial.omron.eu

Cat. No. P061-E1-06 09/10  Note: Specifications are subject to change.                                  2010 Omron Electronics LLC
This datasheet has been downloaded from:
            datasheet.eeworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company

小广播

CP1E-N20DR-A器件购买:

该厂商的其它器件

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2017 EEWORLD.com.cn, Inc. All rights reserved