61F-GPN-V50 AC240器件文档内容

Water Leak Alarm/Detector

61F-WLA/-GPN-V50

Eliminate Problems Caused from Water Leakage
0 to 50 k: variable operating resistance to detect virtually any

liquid.
Two types available: Water Leak Alarm (61F-WLA) and plug-in

Water Leak Detector (61F-GPN-V50).
24 VAC interelectrode voltage causes no electrolytic corrosion.
Suggested applications include computer room, power plant,

factory, library, warehouse, and basement use.
Conforms to EMC/IEC Standards (61F-GPN-V50).
Approved by UL/CSA (61F-GPN-V50)

Ordering Information

Water Leak Alarm                 61F-WLA      When ordering, to complete the part number, be sure to specify the
Water Leak Detector              61F-GPN-V50  desired operating voltage.

                                              Example: 61F-WLA [120/240 VAC]
                                                                                          Desired supply voltage

Specifications

Ratings/Characteristics

                           Item                                  Water Leak Alarm                    Water Leak Detector
Model                                         61F-WLA                               61F-GPN-V50
Supply voltage                                100/200, 110/220, 120/240 VAC         100, 110, 120, 200, 220, 240 VAC
Interelectrode voltage                        24 VAC
Operating current                             3 mA (AC) max.                        3.2 VA max.
Power consumption                             8.0 VA max.
Sensitivity                                   Variable (0 to 50 k:)                 Scale 0: 10 k:
Error (against the scale)                     Scale 0: 10 k:                        Scale 50: r10 k:(see note 2)
                                              Scale 50: r10 k:(see note 2)          3 A 250 VAC, DPDT cosI=1
Contact ratings                               3 A 250 VAC, SPDT cosI=1              1 A 250 VAC, DPDT cosI=0.4
                                              1 A 250 VAC, SPDT cosI=0.4            Provided (Operation indicator)
Indicator                                     Provided (Power and Leak indicators)  Not provided
Alarm buzzer                                  Provided                              Not provided
Test switch                                   Provided
Ambient temperature                           10qC to 50qC
Ambient humidity                              45% to 85%

Note: 1. For detecting leakage of water with high resistivity, use K7L-U/-UD ultra high-sensitivity models.
        2. The Detector may not operate around the setting value of "0." Adjust the sensitivity depending on the actual application.

http://www.ia.omron.com/                      (c)Copyright OMRON Corporation 2007 All Rights Reserved.                                1
                                                                                                               61F-WLA/-GPN-V50

Operation

Internal Circuit

Connections

61F-WLA Water Leak Alarm                        Power                              Alarm LED
                                                supply
         Fuse                                   LED

             Rectification/                             Level       Amplification
             smoothing                                  detection   circuit
             circuit                                    switching
                                                        circuit                                  Alarm buzzer

             Rectification/
             smoothing
             circuit

                         Test switch

    100, 110, 120 VAC                                               Sensor cable
    power source

   200, 220, 240 VAC
   power source

61F-GPN-V50 Water Leak Detector

                                                        Rectifier/                               Level
                                                                                                 detector
                                                24 VAC  smoothing                                switching     Amplifier
                                                        circuit                                  circuit                 Relay

             AC power source

                                                24 VAC                               Rectifier/
                                                                                     smoothing
                                                                                     circuit

                                                                   Sensitivity
                                                                   adjuster

                                                                    Sensor cable

61F-GPN-V50 Water Leak Detector

      To Sensor
      Cable

               Bottom view
                               AC power source

             http://www.ia.omron.com/                                                            (c)Copyright OMRON Corporation 2007 All Rights Reserved.  2
                                                                               61F-WLA/-GPN-V50

Operating Principle

When the two conductive cores of the Sensor Cable are contacted by                        Core
a liquid, a weak alternating current (as small as 3 mA max.) flows                        Core
across the cores. This current is amplified to operate a relay.
                                                                               Liquid
In practice, leakage will be detected if water drops are present
between the core wire and the Electrode (F03-15 Sensor Cable) or
ing section (F03-16PE Sensor Cable). (Refer to the specifications on
page 4)

Sensor Cable Protective Cover

                Item                            F03-25                         F03-26PES
Appearance

Suggested use                                   Adhesive
Construction
                                                                               Adhesive
Comments
                      Fixes the F03-15 Sensor Cable on the floor surface. Fixes the F03-16PE Sensor Cable on the floor sur-

                      Attach the sticker on a smooth surface. To attach it on face. Attach the sticker on a smooth surface. To at-

                      a concrete floor, use a concrete bonding agent.  tach it on a concrete floor, use a concrete bonding

                                                                       agent.

                      http://www.ia.omron.com/                         (c)Copyright OMRON Corporation 2007 All Rights Reserved.     3
Dimensions                                                                                   61F-WLA/-GPN-V50

Note: All units are in millimeters unless otherwise indicated.                    Three, M5 or 6-dia.
61F-WLA Water Leak Alarm                                                          mounting holes

61F-GPN-V50 Water Leak Detector

Accessories (Order Separately)

Connecting Sockets (for 61F-GPN-V50 Water Leak Detector)

PF113A-E Track-mounted Socket                                                     Top view

                                                Eleven, M3.5 x 5
                                                sems screws

                                                                                            Two, M4 or 4.5 dia. holes  61F-
                                                                                                      340.2           GPN-V50

          52 max.

                                                                         31 max.                                       PF113A-E
                                                                                                                       PFC-N8 Holding
                                                                  Two, 2 dia.                                          Bracket
                                                                  holes
PL11 Back-connecting Socket                                                       Two, 3.5 dia. or M3
                                                                                  mounting holes                       61-      Approx. 75
                          51 max.                                                                                      GPN-V50
                                                                                       31 dia. hole

                   35 max.  Approx. 20.5                                                                                        Approx. 16

                                                                                                                       PL11

Important: Install the Water Leak Detector socket with the keyway facing down.

Sensor Cable                                                                                           Crimped electrode pair Stainless steel core
                                                                                                                                       (0.3 x 12 braided)
    F03-15

                              Sheath: Transparent vinyl chloride                                                 Transparent vinyl chloride
                              Core: Stainless steel SUS304
                                                                                                       333 mm
                            Sheath: Transparent vinyl chloride                                         (3 electrode pairs per meter)
                            Core: Stainless steel SUS316
F03-16PE                                                                                    1.2        20              4
                                                                                            1.7

                                                                                  8         4

                                                                                                       Detecting Polyethylene
                                                                                                       section

          http://www.ia.omron.com/                                                (c)Copyright OMRON Corporation 2007 All Rights Reserved.                 4
                                                                            61F-WLA/-GPN-V50

Safety Precautions

                           !WARNING

Do not touch the terminals while power is being supplied.
Doing so may possibly result in electric shock. Make sure
that the terminal cover is installed before using the
product.

                           !CAUTION

Do not attempt to disassemble, repair, or modify the
product. Doing so may occasionally result in minor or
moderate injury due to electric shock.

Precautions for Safe Use

(1) Use only F03-15 or F03-16 Sensor Cable. Other water conduc-
       tors may cause the Water Leak Alarm/Detector to malfunction,
       or not operate at all because of mismatched sensitivity.

(2) Place the Sensor Cable at a location where water leakage is
       most likely to occur. For example, consider the following loca-
       tions:

Under a raised floor; on the highest floor of a building; on the ceiling

In the vicinity of an air conditioner, or on the floor near a humidifier

On the floor near a feed-water pipe, conduit; hot-water pipe.

On top of a power, or control panel

(3) Secure the Sensor Cable so that they touch the floor surface or
    the wall near a pipe arrangement. Cover the Sensor Cable with a
    F03-25 or F03-26 Protective Cover if they are installed at a loca-
    tion crowed with people. However, place the cover such a manner
    that water can easily reach the Sensor Cable.

(4) Keep the temperature at the installation site to within 55qC. Do
     not install the Water Leak Alarm/Detector/Sensor cable in the
     proximity of heat-generating equipment (such as that having a
     coil or wire winding). Also, do not use it in a highly humid loca-
     tion, or at a location that is subjected to corrosive gases. Do not
     place the Water Leak Alarm/Detector side-by-side with a high-
     capacity contactor that produces an inrush current when it oper-
     ates, as such arrangement may cause chattering to occur, con-
     sequently causing a malfunction of the Water Leak Alarm/
     Detector.

(5) Wiring distance of the Sensor Cable varies depending on the
     water quality. When using IV cables, wire the Sensor Cable to
     the length specified in the following table.

(6) Mount the 61F-WLA Water Leak Alarm/Detector on a sturdy wall
     surface which is not subjected to vibration or shock. Do not use
     double-sided adhesive tape, otherwise, the Detector may detach
     when the adhesive tape deteriorates due to aging.

(7) When wiring the Sensor on conductive objects like metal objects,
     use the F03-16.

(8) When measuring insulation resistance, do not conduct a megger
     test between the electrode terminals.

             IV Cable         Sensor Cable
0m
10 to 150 m            200 m
200 to 300 m           150 m
350 to 400 m           100 m
                       50 m

Note: IV cable: 2 mm2

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                  In the interest of product improvement, specifications are subject to change without notice.

http://www.ia.omron.com/                                                    (c)Copyright OMRON Corporation 2007 All Rights Reserved.  5
                                                                 Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.

                                                      Warranty and Limitations of Liability
WARRANTY

OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if
specified) from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL
LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR
STRICT LIABILITY.

In no event shall responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

                                                             Application Considerations
SUITABILITY FOR USE

OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the product.

At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:

Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.

Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety
   equipment, and installations subject to separate industry or government regulations.

Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

                                                                        Disclaimers
CHANGE IN SPECIFICATIONS

Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the product may be changed without any notice. When in doubt, special model numbers may be assigned to fix
or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased product.

DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

ERRORS AND OMISSIONS
The information in this catalog has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.

PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent
the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.

PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.

COPYRIGHT AND COPY PERMISSION
This catalog shall not be copied for sales or promotions without permission.

This catalog is protected by copyright and is intended solely for use in conjunction with the product. Please notify us before copying or reproducing this
catalog in any manner, for any other purpose. If copying or transmitting this catalog to another, please copy or transmit it in its entirety.

OMRON Corporation                                                                                                                                      2007. 3
                               In the interest of product improvement, specifications are subject to change without notice.
Industrial Automation Company
                                                      (c)Copyright OMRON Corporation 2007 All Rights Reserved.
http://www.ia.omron.com/
This datasheet has been downloaded from:
            datasheet.eeworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

器件索引   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2020 EEWORLD.com.cn, Inc. All rights reserved