Floatless Level Switch (Compact Type)

61F-G@N

Improved Design for a More Lightweight                                                                   CSM_61F-G_N_DS_E_3_1
Construction and Reduced Standby Power
Consumption.                                                                                                   Position of
                                                                                                               LED Indicator
Standby power reduced to 85% or less of previous models.                            Note: LED indicator is provided on
(Applicable to 61F-GN.)                                                                      Controllers manufactured in
                                                                                              August 1999 or later.
Weighs only 85% or less of previous models. (Applicable to                                  It is not mounted on the case
61F-G3N/-G4N.)                                                                               surface. It can be seen
                                                                                              through the case.
Easy identification of operating status with LED operation
indicator.

Increased reliability of internal relay (micro load: 5 VDC, 1 mA)
to enable PLC input.

Electrode terminals and other wiring terminals are separated for
easy wiring.

Select from three mounting methods: JEM, DIN rail mounting,
or screw mounting.

Note: LED operation indicator is provided on Controllers manufactured in
        August 1999 or later.

          Refer to Safety Precautions for Floatless Level
          Controllers.

Model Number Structure

Model Number Legend

61F-@N@                                          2. Type
                                                     Blank: General-purpose
          12                                         L 2KM: Long-distance (for 2 km)
                                                     L 4KM: Long-distance (for 4 km)
1. Controller Application                            H: High-sensitivity
                                                     D: Low-sensitivity
    G: Automatic water supply and                    R: Two-wire
          drainage

    G1: Automatic water supply with idling
          prevention or water shortage alarm

    G2: Automatic water supply and
          drainage with abnormal water
          increase alarm

    G3: Automatic water supply and
          drainage with full tank and water
          shortage alarm

    G4: Automatic water supply with water
          level indicator for water supply tank
          and water receiving tank and
          prevention of idling due to water
          shortage

    I: Liquid level indication and alarm (no
          two-wire models)

                                                                                                                               1
                                                                                                  61F-G@N

Ordering Information

                       Classification by     General-   Long-distance High-sensitivity Low-sensitivity                             Two wire
                               application   purpose
                                                        (between        (for high    (for low

                                                        Controller and  specific     specific

Classification by                                       Electrodes)     resistance)  resistance)
control purpose
                                                        (See note 2.)

Controller GN Models                         61F-GN     61F-GNL         61F-GNH      61F-GND            61F-GNR

            G1N Models w/pump idling         61F-G1N    61F-G1NL        61F-G1NH     61F-G1ND           61F-G1NR
                               prevention

                       w/alarm for
                   abnormally low level

            G2N Models  w/alarm for abnormally 61F-G2N  61F-G2NL        61F-G2NH     61F-G2ND           61F-G2NR
                               high level               61F-G3NL        61F-G3NH     61F-G3ND           61F-G3NR
                                                        61F-G4NL        61F-G4NH     61F-G4ND           61F-G4NR
            G3N Models  w/alarm for abnormally 61F-G3N  61F-INL         61F-INH      61F-IND            61F-INR
                               high and low levels      61F-11NL        61F-11NH     61F-11ND           61F-11NR

            G4N Models w/level display of    61F-G4N

                   water source and tank

            IN Models Level indication with  61F-IN
                               alarm

Relay unit                                   61F-11N

Note: 1. : Automatic water supply and drainage control, : Automatic water supply control
        2. Subclassified into 2 km and 4 km models according to the model of relay unit used. Specify 2 km or 4 km when ordering.
        3. When ordering, specify the desired operating voltage at the end of the model number.
             Example: 61F-GN[110/220 VAC]
                                                             Desired supply voltage

        4. Contact your OMRON representative for products with voltages other than those listed above.

                                                                                                                                             2
                                                                                                                                                         61F-G@N

Specifications

Standard Models

                      Type General-purpose Controllers 61F-@N Long-distance                              61F-@NL 2KM (2 km)        High-sensitivity Controllers 61F-@NH
                                                                                         Controllers     61F-@NL 4KM (4 km)
Items

Controlling materials and For control of ordinary purified water and   For control of ordinary purified water and                  For control of liquids with high specific

operating conditions     wastewater                                    wastewater. Particularly in cases where the                 resistance, such as distilled water

                                                                       distance between the pumps and water tanks or

                                                                       between supply and receiver tanks are far apart

                                                                       or where remote control is required.

Rated voltage            100/200, 110/220 or 120/240 VAC, 50/60 Hz (both supported on same model)

Allowable voltage        85% to 110% of rated voltage
fluctuation range

Inter-electrode voltage 8 VAC

Inter-electrode current Approx. 1 mA AC max.

Power consumption        GN@: 3 VA max., G1N@, G2N@, IN@: 4 VA max., G3N@: 5.5 VA max., G4N@: 8.5 VA max.

Inter-electrode operation 0 to approx. 4 k                             0 to 1.8 k (for 2 km)                                       Approx. 10 k to 40 k (See note 4.)
resistance                                                             0 to 0.7 k (for 4 km)

(recommended values)

Inter-electrode release  Approx. 15 k to                               4 k to  (for 2 km)                                          Approx. 100 k to
resistance                                                             2.5 k to  (for 4 km)
(recommended values)

Cable length             1 km max.                                     2 km max.                                                   50 m max.
(See note 2.)                                                          4 km max.

Output                   3 A, 200 VAC (Resistive load)

Ambient operating        -10 to 55C
temperature

Ambient operating        45% to 85%
humidity

Insulation resistance    100 M min. (at 500 VDC)
(See note 3.)

Dielectric strength      2,000 VAC, 50/60 Hz for 1 min.
(See note 3.)

Life expectancy          Electrical: 250,000 operations min.
                         Mechanical: 10,000,000 operations min.

Weight                   GN models: 315 g; G1N, G2N, IN models: 410 g; G3N models: 625g; G4N models: 870 g

Internal Circuit Diagrams Example: 61F-GN                              Example: 61F-GNL                                            Example: 61F-GNH

                               S2            S1               S0       S2                                S1               S0       S2                S1               S0

                                     Tb                Tc          Ta             Tb                               Tc          Ta             Tb               Tc          Ta

                                                           U                                                           U                                           U

                                     0 V Transformer                              0 V Transformer                                             0 V Transformer

                                                 24 V  61F-11N     U                                         24 V  61F-11N     U                         24 V  61F-11N     U
                                                       Relay Unit                                                  Relay Unit                                  Relay Unit
                                   100 V                                          100 V                                                100 V

                                   200 V         8V                               200 V                      8V                        200 V             8V

                                          U                                                           U                                           U

                               E3            E2               E1       E3                                E2               E1       E3                E2               E1

Note: 1. The @ in the model name represents G, G1, G2, G3, G4, or I.
        2. The length when using completely insulated, 600-V, 3-core (0.75 mm2) cabtire cables. Usable cable lengths will become shorter as the
            cable diameter or number of cores becomes larger due to increased floating capacity. For details, refer to Safety Precautions for Floatless
            Level Controllers.

        3. The insulation resistance and dielectric strength are the values between power terminals and Electrode terminals, between power
            terminals and contact terminals, and between Electrode terminals and contact terminals. For details, refer to Safety Precautions for
            Floatless Level Controllers.

        4. Application is possible with 10 k or less, however, this may cause reset failures.

                                                                                                                                                                               3
                                                                                                                                         61F-G@N

                   Type Low-sensitivity Controller 61F-@ND             Two-wire Controller 61F-@NR              Relay Unit

Items                                                                                                          The Relay Unit can be replaced without
                                                                                                               removing the wires for maintenance
Controlling materials  For control of liquids with low specific        For control of ordinary purified water  inspections. It can also be replaced with
and operating                                                                                                  other Relay Units.
conditions             resistance, such as salt water, wastewater, or wastewater. Used with a Two-wire
                                                                                                               Compatibility with
                       acid chemicals, or alkaline chemicals           Electrode Holder (incorporating a       General Purpose Model
                                                                                                               (61F-11N)
                                                                       resistor of 6.8 k)

Rated voltage          100/200, 110/220 or 120/240 VAC, 50/60 Hz (supported by the same model)

Allowable Voltage      85% to 110% of rated voltage
Fluctuation

Inter-electrode voltage 8 VAC

Inter-electrode current Approx. 1 mA AC max.

Power consumption GN@: 3 VA max., G1N@, G2N@, IN@: 4 VA max., G3N@: 5.5 VA max.,
                                  G4N@: 8.5 VA max.

Inter-electrode        0 to approx. 1.8 k                              Approx. 0 to 1.1 k                      General-     61F-11N                ---
                                                                                                               purpose
operation resistance                                                                                           Controller

(recommended values)                                                                                           Long-
                                                                                                               distance
Inter-electrode release Approx. 5 k to                                 Approx. 15 k to                         Controllers  61F-11NL (for 2 km) Provided
resistance                                                                                                                  61F-11NL (for 4 km)
                                                                                                               High-
(recommended values)                                                                                           sensitivity  61F-11NH
                                                                                                               Controllers
Cable length           1 km max.                                       800 m max.
(See note 2.)                                                                                                  Low-
                                                                                                               sensitivity
Output                 3 A, 200 VAC (Resistive load)                                                           Controller

Ambient operating      -10 to 55C                                                                             Two-wire     61F-11ND
temperature                                                                                                    Controller

Ambient operating      45% to 85%
humidity
                                                                                                                            61F-11NR               Not
                                                                                                                                                   provided
Insulation resistance 100 M min. (at 500 VDC)
(See note 3.)

Dielectric strength    2,000 VAC, 50/60 Hz for 1 min.                                                          Terminal Arrangement
(See note 3.)

Life expectancy        Electrical: 250,000 operations min.                                                                  ESS S
                       Mechanical: 10,000,000 operations min.
                                                                                                                            10 9      8    7 11

Weight                 GN models: 315 g; G1N, G2N, IN models: 410 g; G3N models: 625g;                                      8 V 24 V 24 V
                       G4N models: 870 g

Internal Circuit       Example: 61F-GND                                Example: 61F-GNR                                     Relay Unit Circuit
Diagrams

                               S2            S1               S0       S2          S1              S0

                                   Tb                  Tc          Ta      Tb               Tc            Ta

                                                           U                                    U

                                   0 V Transformer                         0V Transformer                      45           6         1  2      3

                                                 24 V  61F-11ND    U                   24V  61F-11ND      U    Tb1 Ta1 Tc1 Tc2 Ta2 Tb2
                                                       Relay Unit                           Relay Unit
                                   100 V                                   100V

                                   200 V         8V                        200V        8V              U

                                          U                                                                           Ordering Example

                               E3            E2               E1       E3                          E1          If you order the components listed
                                                                                                               above, the corresponding Relay Unit
Note: 1. The @ in the model name represents G, G1, G2, G3, G4, or I.                                           will be supplied with the Controller.

        2. The length when using completely insulated, 600-V, 3-core (0.75 mm2) cabtire cables.                Example: If a 61F-GN Controller is
            Usable cable lengths will become shorter as the cable diameter or number of cores                               ordered, a 61F-11N Relay
            becomes larger due to increased floating capacity. For details, refer to Safety                                 Unit will also be included.
            Precautions for Floatless Level Controllers.

        3. The insulation resistance and dielectric strength are the values between power
            terminals and Electrode terminals, between power terminals and contact terminals,
            and between Electrode terminals and contact terminals. For details, refer to Safety
            Precautions for Floatless Level Controllers.

        4. Application is possible with 10 k or less, however, this may cause reset failures.

                                                                                                                                                             4
Connections                                                                                                               61F-G@N

Automatic Water Supply Control                                                                               Compact Model
                                                                                                             61F-GN

                                                                                                                Dimensions
                                                                                                                page 16

                                                 Automatic Water Supply Control

Connections

Connect contactor coil terminal to Tb.
Connect to power supply terminals.

  S0-S1: 110 VAC
  S0-S2: 220 VAC

220-VAC power supply
        RST

                                          61F-GN

MCCB

                                                  Ta               0 V 24 V                                  E1
                                                                                        61F-11N U
                                             S0                 U

                                                  Tc                                    Relay Unit

                                             S1                    110 V                                     E2

                                                   Tb                                                     U
                                             S2
                                                                   220 V       8V                            E3

                                                                           Transformer

        Contactor                                                                                            (See note 1.)

Motor protection                                                                                                                         PS-3S
               relay
                                                                                                             Water                   E1         Stop
                                                                                                             tank           E3 E2               Start

                                                       Water supply
                                                           source

                      M                   P

                      Note: 1. Be sure to ground the common Electrode E3 (the longest Electrode).
                              2. The above wiring diagram is for a rated voltage of 110/220 VAC.

Principles of Operation                                                                                                                  Relay Unit LayoutPowe r
                                                                                                                                                          supply
The pump stops (U indicator ON)                                                                                                                  U1
when the water level reaches E1 and
starts (U indicator OFF) when the
water level drops below E2.

                                                  Water supply             E1           (U indicator ON)
                                             P

                                                 Pump OFF

                                             Pump ON                                    (U indicator OFF)

                                                                       E2
                                                                   E3

                                                                                                                                                                  5
                                                                                                                             61F-G@N

Automatic Drainage Control                                                                                    Compact Model
                                                                                                              61F-GN

                                                                                                                 Dimensions
                                                                                                                 page 16

                                                        Automatic Drainage Control

Connections

Connect the contactor coil terminal to Ta.
Connect to power supply terminals.

  S0-S1: 110 VAC
  S0-S2: 220 VAC

    220-VAC power supply                      61F-GN
             RST

MCCB

                                                        Ta             0 V 24 V                               E1
                                                                                            61F-11N U
                                                 S0             U

                                                        Tc                       Relay Unit

                                                 S1                   110 V                                   E2

                                                       Tb                                              U
                                                 S2
                                                                      220 V  8V                               E3

                                                                             Transformer

        Contactor                                (See note 1.)

Motor protection                                 PS-3S
relay

                                                                       E1    Start

                                              Wastewater        E3 E2        Stop
                                              tank

                                    M         P

                                                                                                                  Reservoir

                   Note: 1. Be sure to ground the common Electrode E3 (the longest Electrode).
                           2. The above wiring diagram is for a rated voltage of 110/220 VAC.

Principles of Operation                                                                                                      Relay Unit LayoutPowe r
                                                                                                                                supply
The pump starts (U indicator ON)                                                                                                   U
  when the water level reaches E1                                                                                                     1
  and stops (U indicator OFF) when
  the water level drops below E2.

                                              Pump ON             E1         (U indicator ON)

                                              Pump OFF                       (U indicator OFF)
                                                                                      P
                                                              E2                              Water drainage
                                                          E3

                                                                                                                                                6
                                                                                                                                                         61F-G@N

Automatic Water Supply Control with                                                                                      Compact Model
Pump Idling Prevention                                                                                                   61F-G1N

                                                                                                                                     Dimensions
                                                                                                                                     page 16

                                   Automatic Water Supply Control with Pump Idling Prevention

Connections

Connect to power supply                 220-VAC power supply
  terminals.                                       RST
  S0-S1: 110 VAC
  S0-S2: 220 VAC

Insert a pushbutton switch       MCCB
  (NO contact) between E1' and
  E3 as shown by the dotted                                                 61F-G1N
  line.

Do not press the pushbutton                                                    Tc2         U1               24 V       61F-11N     U1          E1
  switch if the pump stops (U1                                              S0                           0V              Relay Unit
  indicator OFF) during normal                                     B                                                                        U2
  operation after an alarm is                                                    Tb2                  110 V   24 V       61F-11N     U2
  given for a low water level                                   Alarm Bell  S1                        220 V              Relay Unit              E2
  (e.g., the water level does not
  reach E2').                                                               S2                                8V                                 E3
                                                                                 Ta1
Test Operation/                                                                                   U2     Transformer                             E1'                          (Pushbutton switch)
Recovering from                                                                  Tb1
Power Interruptions                                                                                                                         U1

                                                                                                                                                 E2'

If the water supply source level

has not yet reached E1' when

starting the pump or after

recovering from a power

interruption, press the            Contactor
pushbutton switch to start the
                                                                                                                         (See note 1.)

pump (U1 indicator ON) by                                                                                                                                PS-3S

momentarily short-circuiting E1'

and E3.                            Motor                                                                                             Water           E1         Stop
                                                                                                                                     tank       E2              Start
                                   Protection                                                     PS-3S                                     E3

                                   Relay

                                                                            Water            E1'

                                                                            supply                Water
                                                                                                  shortage
                                                                            source      E2'

                                                      M          P                  E3

                                               Note: 1. Be sure to ground the common Electrode E3 (the longest Electrode).
                                                       2. The above wiring diagram is for a rated voltage of 110/220 VAC.

Principles of Operation                               Water supply source                                                                Note

The pump starts (U2 indicator                                                                   Relay Unit Layout       Length of Electrode E1'
  OFF) when the water level                                                                                                 When installing the Controller in
  drops below E2 and stops (U2                        Water        E1'      (U1 indicator ON)            UU   Powe r        locations where there is a possibility of
  indicator ON) when water level                      shortage  E2'         (U1 indicator OFF)            21     supply     momentary power interrupts or blackouts,
  reaches E1.                                                                                                               the length of E1' should be made so that
                                                         E3                                                                 the amount of water corresponding to
The pump is forced to stop                                                                                                one pump cycle does not expose the
  when the water supply source                        BL                                                                    Electrodes. This will prevent the E2'
  level drops below E2' (U1                                  Water tank                                                     self-holding circuit from failing.
  indicator OFF) to prevent the
  pump from idling and gives an         Water supply                                                                          Float Water supply source
  alarm.
                                   P

                                          Pump OFF               E1         (U2 indicator ON)

                                                                                                                                                    E1'  Amount of water for
                                                                                                                                                         one pump cycle
                                                                                                                                                E2'
                                          Pump ON                           (U2 indicator OFF)                                              E3

                                                             E2
                                                         E3

                                                                                                                                                                                                   7
                                                                                                                                                                 61F-G@N

Automatic Water Supply Control with                                                                                                    Compact Model
Abnormal Water Shortage Alarm                                                                                                          61F-G1N

                                                                                                                                       Dimensions
                                                                                                                                       page 16

                                Automatic Water Supply Control with Abnormal Water Shortage Alarm

Connections

Connect to power supply           220-VAC power supply                  61F-G1N
  terminals.                                 RST
  S0-S1: 110 VAC                                                               Tc2               U1                                             E1
  S0-S2: 220 VAC                MCCB                                      S0
                                                                                                               0V  24 V   61F-11N      U1  U2
Insert a pushbutton switch                           B                       Tb2                          110 V         Relay Unit
  (NO contact) between E3                                                 S1                                                                    E2
  and E4.                                                     Alarm Bell                                                  61F-11N      U2
                                                                          S2                                       24 V   Relay Unit
If the pump stops upon                                                       Ta1
  releasing the pushbutton
  switch, keep pressing the                                                    Tb1
  pushbutton switch.

Connect the E4 electrode for
  the water shortage alarm to
  the E1' terminal.

Test Operation/                                                                                            220 V  8V                                 E3
Recovering from
Power Interruptions                                                                                  U2     Transformer                              E1'                        (Pushbutton switch)

If the water level has not yet                                                                                                             U1              (E4)
reached E4 when starting the
pump or after recovering from                                                                                                                         E2'
a power interruption, press
the pushbutton switch to start Contactor                                                                                               (See note 1.)
the pump by short-circuiting
E3 and E4 (U1 indicator ON).                                                                                                                                                     PS-4S

                                                      Motor                                                                                           Water                  E1                       Stop
                                                      Protection                                                                                      tank               E2
                                                      Relay                                                                                                      E3 E4                                Start
                                                                                                                                                                                                      Water
                                                                                        Water supply                                                                                                  shortage
                                                                                        source

                                                                  M  P

                                                                  Note: 1. Be sure to ground the common Electrode E3 (the longest Electrode).
                                                                          2. The above wiring diagram is for a rated voltage of 110/220 VAC.

Principles of Operation                                                                 Water supply source                                                      Relay Unit Layout

The pump stops (U2 indicator                                            Water supply                                                                                 UU        Powe r
  ON) when the water level                                                                                                                                                21        supply
  reaches E1 and starts (U2                                          P
  indicator OFF) when water level                                                                       E1         (U2 indicator ON)
  drops below E2.                                                          Pump OFF

If the water level drops below E4                                       Pump ON                                  (U2 indicator OFF)
  for any reason, an alarm is given                                                                                (U1 indicator OFF)
  (U1 indicator OFF).                                                                  Water
                                                                                       shortage
                                                                                                    E2
                                                                                                 E4

                                                                          BL
                                                                                            E3

                                                                                                                                                                                                                8
                                                                                                                                                 61F-G@N

Automatic Water Supply with                                                                          Compact Model
Abnormal Water Increase Alarm                                                                        61F-G2N

                                                                                                                    Dimensions
                                                                                                                    page 16

                                Automatic Water Supply with Abnormal Water Increase Alarm

Connections                     220-VAC power supply
                                         RST
Connect power supply
  terminal S2 to terminal Tb1.

Connect to power supply
  terminals.
  S0-S1: 110 VAC
  S0-S2: 220 VAC

                                                                    61F-G2N

                                MCCB

                                                                            Ta2                  0V                                              E1
                                                                                              110 V
                                                                    S0                        220 V                 24 V  61F-11N        U1  U2
                                                                                                                          Relay Unit
                                                 B                          Tc2  U1

                                               Alarm Bell           S1                                                    61F-11N        U2      E2
                                                                                                                          Relay Unit
                                                                                                                    24 V

                                                                            Ta1                                                                  E3

                                                                    S2           U2                                 8V

                                                                            Tc1                      Transformer                                 E4

                                                                            Tb1

                                Contactor                                                                                 (See note 1.)

                                                                                                                                                            PS-4S

                                Motor                                                                                           Water                   E4         Full tank
                                Protection                                                                                      tank                E1             Stop
                                Relay
                                                                                Water supply                                                    E2                 Start
                                                                                source                                                       E3

                                            M                    P                                                                               Reservoir

                                            Note: 1. Be sure to ground the common Electrode E3 (the longest Electrode).
                                                    2. The above wiring diagram is for a rated voltage of 110/220 VAC.

Principles of Operation                            Water supply                      BL                                                          Relay Unit Layout Powe r
                                                                                                                                                                      supply
The pump starts (U2 indicator OFF)        P                                    Upper limit                                                           UU
  when the water level reaches E2 and                Pump OFF                                                                                             21
  stops (U2 indicator ON) when the
  water level rises above E1.                                               E4   (U1 indicator ON)

If the water level reaches E4 for any
  reason, an alarm is given (U1
  indicator ON).

                                                                                                 (U2 indicator ON)

                                                                            E1

                                               Pump ON                           (U2 indicator OFF)

                                                                        E2
                                                                    E3

                                                                                                                                                                              9
                                                                                                                                       61F-G@N

Automatic Drainage Control with                                                                                Compact Model
Abnormal Water Increase Alarm                                                                                  61F-G2N

                                                                                                                   Dimensions
                                                                                                                   page 16

                              Automatic Drainage Control with Abnormal Water Increase Alarm

Connections                   220-VAC power supply
                                       RST
Connect power supply S2 to
  terminal Ta1.                                                 61F-G2N

Connect to power supply     MCCB
  terminals.
  S0-S1: 110 VAC
  S0-S2: 220 VAC

                                                                    Ta2                    0V                                          E1
                                                                                        110 V
                                                                S0                      220 V           24 V       61F-11N     U1  U2
                                                                                                                   Relay Unit
                                                      B             Tc2          U1

                                                    Alarm Bell  S1                                                 61F-11N     U2      E2
                                                                                                                   Relay Unit
                                                                                                        24 V

                                                                    Ta1                                                                E3

                                                                S2               U2                     8V

                                                                    Tc1                         Transformer                            E4

                                                                    Tb1

                              Contactor                         (See note 1.)

                              Motor                                                             PS-4S
                              Protection
                              Relay                             Wastewater tank

                                                                                            E4          Full tank

                                                                                        E1              Start

                                                                                 E3 E2                  Stop

                                          M         P

                                                                                                                                   Reservoir

                                          Note: 1. Be sure to ground the common Electrode E5 (the longest Electrode).
                                                  2. The above wiring diagram is for a rated voltage of 110/220 VAC.

Principles of Operation                             Water tank                                                                         Relay Unit Layout

The pump starts (U2 indicator ON)       BL                        Upper limit                                                              UUPowe r
  when the water level reaches E1 and      Pump ON                                                                                              21supply
  stops (U2 indicator OFF) when the                             E4               (U1 indicator ON)
  water level drops below E2.
                                                                                     (U2 indicator ON)
If the water level reaches E4 for any
  reason, an alarm is given (U1                                 E1
  indicator ON).

                                          Pump OFF                               (U2 indicator OFF)

                                                        E2                                 P
                                                    E3
                                                                                                           Water drainage

                                                                                                                                                          10
                                                                                                                                                   61F-G@N

Automatic Water Supply Control with                                                                        Compact Model
Full Tank and Water Shortage Alarm                                                                         61F-G3N

                                                                                                           Dimensions
                                                                                                           page 17

                Automatic Water Supply Control with Full Tank and Water Shortage Alarm

Connections

Connect contactor coil terminal to Tb.

Connect to power supply terminals.

S0-S1: 110 VAC

S0-S2: 220 VAC  220-VAC power supply                                  61F-G3N

                                          RST                                Ta                      Transformer
                                                                       S0
                                                                                                     0V    24 V
                                                                             Tc                                     To 61F-11N
                MCCB                                                   S1           U2

                                                                             Tb         110 V                       Relay Unit   E1
                                                                       S2                                  24 V

                                                  Upper limit         LH                     220 V           8V                       E2
                                                                            B1          U1
                                                    PL                                  U3                 61F-11N U1            U2
                                                                      Lc                                   Relay Unit
                                                  Lower limit                           U1                                            E3
                                                                            B2          U3                 61F-11N U2
                                                    PL                LL                                   Relay Unit                 E4

                                                                                                           61F-11N U3                 E5
                                                                                                           Relay Unit

                                                     B                                                     (See note 1.)

                                                          Alarm Bell

                Contactor

                                                                                                                                                   PS-5S

                Motor                                                                                                     Water                E1         Full tank
                Protection                                                                                                tank              E2            Stop
                Relay                                                                                                                   E3
                                                                      Water supply                                                                        Start
                                                                      source                                                        E4                    Water shortage
                                                                                                                                 E5

                                               M  P

                                      Note: 1. Be sure to ground the common Electrode E5 (the longest Electrode).
                                              2. The above wiring diagram is for a rated voltage of 110/220 VAC.

Principles of Operation                                 Water supply                                 LH B                                          Relay Unit LayoutPowe r
                                                                                                                                                             supply
The pump starts (U2 indicator ON)               P                                     Upper limit                                                     UUU
  when the water level reaches E2 and                       Pump OFF                                                                                      321
  stops (U2 indicator OFF) when the
  water level drops below E3.                                                       E1  (U1 indicator ON)

If the water level rises to E1 for any                                                               (U2 indicator ON)
  reason, the upper-limit indicator turns
  ON and an alarm is given (U1 indicator                                            E2
  ON). If the water level drops below E4
  for any reason, the lower-limit indicator          Pump ON                                     (U2 indicator OFF)
  turns ON and an alarm is given (U3
  indicator OFF).                                                            E3         Lower (U3 indicator OFF)

                                                                          E4            limit
                                                                      E5
                                                                                                    LL B

                                                                                                                                                                          11
                                                                                                                                                  61F-G@N

Automatic Drainage Control with                                                                                     Compact Model
Full Tank and Water Shortage Alarm                                                                                  61F-G3N

                                                                                                                    Dimensions
                                                                                                                    page 17

                Automatic Drainage Control with Full Tank and Water Shortage Alarm

Connections

Connect contactor coil terminal to Ta.

Connect to power supply terminals.

S0-S1: 110 VAC

S0-S2: 220 VAC  220-VAC power supply                                      61F-G3N

                                             RST                                  Ta                            Transformer
                                                                            S0
                                                                                                        0V          24 V
                                                                                  Tc                                         To 61F-11N
                MCCB                                                        S1                    U2

                                                                                  Tb                    110 V                Relay Unit    E1
                                                                            S2                                      24 V

                                                           Upper limit    LH                                 220 V    8V                      E2
                                                                                B1                      U1
                                                             PL                                         U3          61F-11N U1           U2
                                                                          LC                                        Relay Unit
                                                           Lower limit          B2                      U1                                    E3
                                                                                                        U3          61F-11N U2
                                                             PL           LL                                        Relay Unit                E4

                                                                                                                    61F-11N U3                E5
                                                                                                                    Relay Unit

                Contactor                                     B

                Motor                                      Alarm Bell
                Protection
                Relay                                      (See note 1.)

                                                                                             PS-5S

                                                                                         E1             Full tank
                                                                                                        Start
                                                           Wastewater                E2                 Stop
                                                                                                        Water shortage
                                                           tank                  E3
                                                                          E5 E4
                                                  M        P

                                                                                                                                Reservoir

                                          Note: 1. Be sure to ground the common Electrode E5 (the longest Electrode).
                                                  2. The above wiring diagram is for a rated voltage of 110/220 VAC.

Principles of Operation                                                                           LH B                                     Relay Unit LayoutPowe r
                                                                                                                                                     supply
The pump starts (U2 indicator ON)                                                  Upper limit                                                UUU
  when the water level reaches E2 and                                                                                                             321
  stops (U2 indicator OFF) when the
  water level reaches E3.                                                 E1                 (U1 indicator ON)

If the water level rises to E1 for any          Pump ON                                    (U2 indicator ON)
  reason, the upper-limit indicator turns
  ON and an alarm is given (U1 indicator                                  E2
  ON). If the water level drops below E4
  for any reason, the lower-limit indicator  Pump OFF                                        (U2 indicator OFF)
  turns ON and an alarm is given (U3                                                         (U3 indicator OFF)
  indicator OFF).                                                    E3
                                                                                                LL B
                                                                  E4                 Lower
                                                              E5                     limit

                                                                                                                                                              12
                                                                                                                                                                                  61F-G@N

Water Source Level Indication with                                                                                                        Compact Model
Prevention of Pump Idling Due to Water                                                                                                    61F-G4N
Shortage, and Automatic Water Supply
Control with Indication of Water Level in                                                                                                    Dimensions
Elevated Tank                                                                                                                                page 17

Water Source Level Indication with Prevention of Pump Idling Due to Water Shortage, and Automatic Water Supply Control with
                                                             Indication of Water Level in Elevated Tank

Connections              220-VAC power supply                                                      61F-G4N

                                                      RST                                              S0                                 Transformer
                                                                                                       S1
Connect to power supply

terminals.                                                                                                           X 0V                 24 V
                                                                                                                                                  To 61F-11N
S0-S1: 110 VAC                                                MCCB                                              U2
S0-S2: 220 VAC                                                                                                                                    Relay Unit
                                                                                                                    MY3 Relay

                                                                                                       S2                      110 V      24 V

Insert a pushbutton switch                                                                           Tc       X                         8V
  (NO contact) between E2
  and E8 as shown by the                                                                                                       220 V                          E1
  dotted line.
                                                                                                       Tc2      U5

Do not press the                                                                                     TA                                                     E2
  pushbutton switch if the
  pump stops during normal                                                                                                                             U2
  operation after an alarm is
  given for low water level                                                                                                                                   E3
  (i.e., the water level has not
  reached E3).                                                                                         B                                                      E8                           (Pushbutton switch)

Test Operation/                                                         BH1 Elevated                                U4                                       E4
Recovering from
Power Interruptions                                                               tank repletion  BH1                                    61F-11N U3          E5
                                                                                                                                          Relay Unit
When starting the pump and                                               BL1 Elevated              BL1          U1
after recovering from a power
interruption, if the water                                                         tank water                   U3                        61F-11N U2          E6
source level has not yet
reached E2 (U2 indicator                                                 BH shortage               BH2                                    Relay Unit
OFF), press the pushbutton                                                   2 Water supply
switch to start the pump by                                                        source upper                      X                    61F-11N U4          E7
momentarily short-circuiting
E2 and E8.                                                               BL limit                  BL2                                    Relay Unit          E8
                                                                             2 Water supply
                                                                                   source lower                      U4                   61F-11N U5

                                                                         LH limit                  LH1                                    Relay Unit
                                                                             1 Elevated
                                                                                   tank repletion                       U1

                                                                         LL1 Elevated                  LL1                                61F-11N U1   U5

                                                                                   tank water      LH2          U3                        Relay Unit

                                                                         LH shortage               LL2          X
                                                                             2 Water supply
                                                              Contactor            source upper

                                                                         LL limit
                                                                             2 Water supply
                                                                                   source lower
                                                                                   limit

                                                              (See note 1.)                                                                                                                PS-5S

                                                              Motor Protection Relay

                                                                                                       PS-4S                                                      Water                E4                       Full tank
                                                                                                                                                                  tank              E5                          Stop
                                                                                                            Upper limit
                                                                         Water                     E1                                                                           E6                              Start
                                                                         supply                             ON                                                           E8 E7                                  Water
                                                                                                                                                                                                                shortage

                                                                         source         E2                  OFF
                                                                                                            Lower limit
                                                           M  P                     E3
                                                                                 E8

                                  Note: 1. Be sure to ground the common Electrode E8 (the longest Electrode).
                                          2. The above wiring diagram is for a rated voltage of 110/220 VAC.

Principles of Operation                                                                                Relay Unit Layout                                           Precaution

Insert four Electrodes in the water supply source and five                                           UU   U   U   U       X  Powe r                   Length of Electrode E2
  Electrodes in the elevated water tank.                                                                54   3   2   1            supply                  When installing the Controller in locations
                                                                                                                                                          where there is a possibility of momentary
The lower-limit indicator for the water supply source remains                                                                                           power interruptions or blackouts, the
  ON while the water source level is below E3 (U2 indicator                                                                                               length of E2 should be made so that the
  OFF).                                                                                                                                                   amount of water corresponding to one
                                                                                                                                                          pump cycle does not expose the
When the water level rises to E2, the lower-limit indicator turns OFF (U2 indicator                                                                     Electrodes. This will prevent the E3
  ON) and the pump is ready for operation.                                                                                                                self-holding circuit from failing.

When the water level reaches E1, the upper-limit indicator turns ON (U3 indicator
  ON).

The water-shortage indicator for the elevated tank remains ON while the water level                                                                      Float Water supply source
  in the elevated tank is below E7. The indicator turns OFF (U1 indicator ON) when the
  water level rises to E7.

The pump stops (U5 indicator ON) when the water level reaches E5 and starts (U5                                                                                             E1      Float valve open
  indicator OFF) when the water level drops below E6.                                                                                                                                 Amount of water for
                                                                                                                                                                          E2          one pump cycle
If the water level reaches E4 for any reason, the tank repletion indicator for the                                                                              E8 E3
  elevated tank turns ON (U4 indicator ON).

                                                                                                                                                                                                                13
                                                                                                                                          61F-G@N

Liquid Level Indication and Alarm                                                                                  Compact Model
                                                                                                                   61F-IN

                                                                                                                          Dimensions
                                                                                                                          page 16

Connections                                           Liquid Level Indication and Alarm

Connect to power supply  220-VAC power supply
  terminals.                        RST
  S0-S1: 110 VAC
  S0-S2: 220 VAC              MCCB

                                                                        61F-IN

                                                                                   Tc             U2                                      E1

                                                                            S0                        0V                  61F-11N     U1
                                                                                                                          Relay Unit
                                                                                                             24 V

                                                  B   Alarm Bell                   B                  110 V                               E2

                                                                            S1                               24 V         61F-11N     U2
                                                                                                                          Relay Unit
                                                  PL                               L1
                                                      Lower limit                                 U2                                      E3
                                                                            S2                        220 V  8V

                                                  PL                               L2             U1  Transformer
                                                           Upper limit

                                                  PL                               L3

                                                         Intermediate                           U1

                                                                                                             (See note 1.)

                                                                                                                          Water                       PS-3S  Upper limit
                                                                                                                          tank                                    Intermediate
                                                                                                                                               E1
                                                                                                                                          E2                 Lower limit
                                                                                                                                      E3
                                                                            Water supply
                                                                            source

                           M                      P

                           Note: 1. Be sure to ground the common Electrode E3 (the longest Electrode).
                                   2. The above wiring diagram is for a rated voltage of 110/220 VAC.

Principles of Operation

When the water level drops below E2, the                                         Water tank                                             Relay Unit Layout
  lower-limit indicator turns ON and an alarm is
  given (U2 indicator OFF).                           B LH                  Upper                     (U1 indicator ON)                         UU           Powe r
                                                                            limit                     (U1 indicator OFF)                           21           supply
When the water level reaches E2, the alarm
  turns OFF and the intermediate indicator turns                                              E1      (U2 indicator ON)
  ON (U2 indicator ON).                                                                               (U2 indicator OFF)
                                                                        LM  Interme-
When the water level rises to E1, the upper-                              diate
  limit indicator turns ON and an alarm is given
  (U1 indicator ON).                                                        Lower         E2

                                                      B LL                  limit

                                                                                   E3

                                                                                                                                                                                14
                                                                                                                                       61F-G@N

Two-wire Connection

The wiring between the 61F Controller and the Electrodes can be reduced by removing the self-hold circuit. This arrangement is called a two-wire
connection. Three Electrodes are still required. Both the 61F Controller (including the Relay Unit) and Electrode Holder must be two-wire models.

Two-wire Electrode Holders have an in-built resistor of 6.8 k 1W.

Automatic Water Supply and                                                                                                 Compact Model
Drainage Control                                                                                                           61F-GNR

                                                                                                                            Dimensions
                                                                                                                            page 16

                   Automatic Water Supply Control                                                    Automatic Drainage Control
Connections                                                                    Connections

220-VAC power supply                                                           220-VAC power supply
RST                                                                            RST

MCCB           61F-GNR                                                                     61F-GNR
                                                                               MCCB
                    Ta      0 V 24V                   E1                                                         0 V 24 V              E1
               S0                                                                           Ta
                         U          61F-11NR U                                         S0                    U       61F-11NR U
                    Tc
               S1        110 V      Relay Unit                                              Tc                       Relay Unit
                                                                                       S1
                    Tb                             U                                                         110 V               U
               S2                                                                           Tb
                         220 V 8 V                    E3                               S2                    220 V 8 V                 E3
                               Transformer                                                                         Transformer

Contactor                           (See note 1.)                                 Contactor

                                                                                    (See note 1.)

                                                   PS-3SR
                                                                  R

   Motor                                              Water         E1  Stop      Motor                      R       PS-3SR
   protection                                         tank   E2 E3      Start     protection
   relay         Water                                                            relay       Wastewater
                 supply                                                                       tank
M                source                                                                                          E1  Start
                                                                                                          E2         Stop
               P
                                                                               M              P              E3

                                                                                                                                           Reservoir

Note: 1. Be sure to ground the common Electrode E3 (the longest                Note: 1. Be sure to ground the common Electrode E3 (the
             Electrode).                                                                   longest Electrode).

        2. The above wiring diagram is for a rated voltage of 110/                     2. The above wiring diagram is for a rated voltage of 110/
             220 VAC.                                                                      220 VAC.

Connect contactor coil terminal to Tb.                                        Connect contactor coil terminal to Ta. (Do not connect Tb.)
Connect to power supply terminals.                                           Connect to power supply terminals.

  S0-S1: 100 VAC                                                                 S0-S1: 100 VAC
  S0-S2: 200 VAC                                                                 S0-S2: 200 VAC
The two-wire models require only two cables for the connection                The two-wire models require only two cables for the connection
  between the 61F-GNR and the Electrode Holder, but still                        between 61F-GNR and the Electrode Holder, but still needs
  requires three Electrodes.                                                     three Electrodes.
A Two-wire Electrode Holder must be used. (It has an inbuilt                  A Two-wire Electrode Holder must be used. (It has an inbuilt
  resistance R.)                                                                 resistance R.)
The Relay Unit must also be for two-wire models.                              The Relay Unit must also be for two-wire models.

Principles of Operation                                                        Principles of Operation

     Water supply                                                                 Pump ON                    E1      (U indicator ON)

P                                                  (U indicator ON)
    Pump OFF                        E1

                                                                                  Pump OFF                           (U indicator OFF)
                                                                                                                            P
               Pump ON                      (U indicator OFF)                                            E2                         Water Drainage
                                                                                                     E3
                                E2
                            E3

The pump stops (U indicator ON) when the water level reaches                   The pump starts (U indicator ON) when the water level reaches E1
E1 and starts (U indicator OFF) when water level drops below E2.               and stops (U indicator OFF) when the water level drops below E2.

                                                                                                                                                      15
Dimensions                                                                                                                  61F-G@N

Note: All units are in millimeters unless otherwise indicated.                                                   65
                                                                                                                  54
61F-GN, -GNL, -GNH, -GND, -GNR                                                                                     10
                                                                                                                    3.4
                                                                          25                                                     4 min.
                                                                                                                                   35.4 90
                                                                5 14              14

                                            32                                    Terminal cover
                                                    3                             Nine, M3.5 sems screws

                                     60
                                            11
                                                      5

                                                                   11
                                                           9

                           10 5                                                                           56 50
            100 70

                                                                          40                                     39      4 min.

                                          4                               50                                     43.5

                                     (See note.)

                                                                      Note: Dimensions are with the DIN rail mounting (sliding) bracket attached.

61F-G1N, -G1NL, -G1NH, -G1ND, -G1NR                                   25
61F-G2N, -G2NL, -G2NH, -G2ND, G2NR
61F-IN, - NL, -INH, -IND             5 14                                     14

                                            32                                Terminal cover                     65
                                                    3                         Fifteen, M3.5 sems screws           54
                                                                                                                   10
                                     60                                                                             3.4
                                            11
                                                      5

                                                                    11
                                                            9

                           10 5                                                                           56 50          4 min.
            100 70                                                                                                        35.4 90

                                                                          65                                     39      4 min.

                                          4                               75                                     43.5

                                     (See note.)

                                                                      Note: Dimensions are with the DIN rail mounting (sliding) bracket attached.

                                                                                                                                                   16
61F-G3N, -G3NL, -G3NH, -G3ND, -G3NR, -G3N-NGD                                                                                                                                                             61F-G@N

                                                                                                                                                                 25                                     65
                                                                                                                                                                                                         54
                                                                                                                                                5 14                 14                                   10
                                                                                                                                                                                                           3.4
       32                                                                                                                                                                 Terminal cover                                Min. 4
               3                                                                                                                                                           21, M3.5 sems screws                           35.4 90

60
       11
                 5

                                  11
                          9

               10 5                                                                                                                                                                              56 50
100 70

                                                                                                                                                4                    115                                              Min. 4
                                                                                                                                                                                                          39
                                                                                                                                                (See note.)          125                                43.5

                                                                                                                                                   Note: Dimensions are with the DIN rail mounting (sliding) bracket attached.

61F-G4N, - G4NL, -G4NH, -G4ND, -G4NR, -G4N-KYD

                                                                                                                                                25

5 14                                                                                                                                                         14

       32                                                                                                                                                          Terminal cover                       65
               3                                                                                                                                                 25, M3.5 sems screws                     10
                                                                                                                                                                                                           3.4
60
               5

                               11
                       9

               10 5                                                                                                                                                                              56 50          Min. 4
100 70                                                                                                                                                                                                           35.4 90

                                                                                                                                                                     190                                39      Min. 4

                                                                                                             4                                                       200                                43.5

                                                                                                                                   (See note.)     Note: Dimensions are with the DIN rail mounting (sliding) bracket attached.

Safety Precautions

Refer to Safety Precautions for All Level Controllers.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                  In the interest of product improvement, specifications are subject to change without notice.

                                                                                                                                                                                                                                17
                                                       Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.

                                                      Warranty and Limitations of Liability

WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.

In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

                                                            Application Considerations

SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.

At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:

       Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.

       Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
           safety equipment, and installations subject to separate industry or government regulations.

       Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.

                                                                       Disclaimers

CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.

DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.

ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.

OMRON Corporation                                                                                                                                      2009.12
                               In the interest of product improvement, specifications are subject to change without notice.
Industrial Automation Company
                                                                                   (c)Copyright OMRON Corporation 2009 All Right Reserved.