Alternate Operation Relay

61F-AN/-APN2

                                                                                                                CSM_61F-AN_-APN2_DS_E_4_1

Increases Motor Life and Enables Operating

Only One Pump When Cleaning Tanks or as

an Emergency Measure for Pump Failures.

• Electronic Relay with the same operation as the G4Q Latching

Relay. Compared with the G4Q, the 61F-AN/-APN2 has a

shorter power supply application time and no restrictions on

mounting direction.

• Compact Models (61F-AN) and Compact Plug-in Models (61F-

APN2) available.

Note: A changeover switch must be included in the sequence to enable

       operating only one pump.

       Refer to Safety Precautions for Floatless Level

       Controllers.

■ Ordering Information

        Type                     Model

Alternate Operation    61F-AN

Relay                  61F-APN2

Note: When ordering, specify the desired operating voltage at the end of the model number.

       Example: 61F-AN [220VAC]

                                 Desired supply voltage

■ Specifications

Ratings

Supply voltage                          100, 110, 200, 220 VAC; 50/60 Hz

Operating voltage range                 85% to 110% of rated voltage

Power consumption                       3 VA

Accessories                             Hold-down clip PFC-N8 *

* Hold-down clip PFC-N8 is attached only 61F-APN2.

Contact Ratings (with G2RK Keep Relay)

                     Item                               Resistive load (cosφ  =  1)         Inductive load (cosφ = 0.4,     L/R  =  7  ms)

Max. load                               3 A at 250 VAC                                      1.5 A at 250 VAC

Carry contact                           3A

Max. operating current                  3A

Max. switching capacity                 750 VA                                              375 VA

Characteristics

Response time                           Operate:        25 ms max.

                                        Release:        30 ms max.

Minimum pulse width                     Min. ON time:   40 ms min.

                                        Min. OFF time: 200 ms min.

Insulation resistance                   100 MΩ min. at 500 VDC (between each terminal and power supply)

Dielectric strength                     2,000 VAC, 50/60 Hz for 1 min (between each terminal and power supply)

Vibration resistance                    10 to 55 Hz, 1-mm double amplitude

Shock resistance                        10 G (approx. 98 m/s2)

Life expectancy                         Mechanical: 1,000,000 operations (at operating frequency of 1,800 operations/hour)

                                        Electrical:     100,000 operations min.

                                        (rated load)

Ambient temperature                     Operating: –10 to 55°C

Ambient humidity                        Operating: 45% to 85% RH

Weight                                  61F-AN: Approx. 215 g

                                        61F-APN2: Approx. 190 g

                                                                                                                                            1
                                                                                                                                                                     61F-AN/-APN2

Time Chart for Alternate Operation of Water Supply

When the 61F-A@ Alternate Operation Relay is combined with a                 example, after the control level is reached and the 61F Controllers’

Floatless Level Switch, the Relay output contacts switch (break)             NC contacts turn OFF (break), the Relay’s output contacts switch.

while the contactor is engaged. The Relay output contacts will not           The next time the 61F Controller’s NC contacts turn ON, the output

switch simultaneously with engaging the contactor. In other words,           contacts have already switched. Thus, only the continuous carry

the contactor or other load is switched with the output contacts from        current needs to be considered for the load capacity of the 61F-

the Floatless Level Switch, not directly with the output contacts from       APN2, enabling application to the rated carry current of 3 A.

the 61F-A@ Alternate Operation Relay. Using water supply as an

                  Ta

          61F

                  Tb

               Power

61F-AN,        Output

   -APN2  Tc1-Ta1

               Output

          Tc1-Tb1

          Contactor 1

          Contactor 2

61F-AN (Compact Model)

Used in combination with a 61F-G@N Floatless                                 Level Switch.

Operation

•  The 61F-AN is used in combination with a Floatless Level Switch                                                                                                                        Tb1

   for alternate operation when using two pumps for level control in                                                                                                       Xc1

   one location.                                                             S0                          Alternate operation                                                              Ta1

•  When power is applied to the input terminals S0 and S2, NO                                                                                                                             Tc1

   contacts Tc1 and Ta1, and NO contacts Ta2 and Tc2 are turned ON                        Power circuit                       control circuit  Output circuit        X

   via the alternate operation control circuit and the output circuit. This                                                                                                               Tb2

   state is held with a magnetic lock even if the power supply is turned                                                                                                   Xc2

   OFF.                                                                      S2                                                                                                           Ta2

• When power is applied to the input terminals again, the NO                 (See note.)                                                                       G2RK

                                                                                                                                                               (61F-AN)

   contacts are turned OFF and the NC contacts Tc1 and Tb1 and NC                                                                                                                         Tc2

   contacts Ta2 and Tc2 are turned ON. This state is held with a

   magnetic lock even if the power supply is turned OFF.

• The above operation is repeated each time the power supply is              Note: The above diagram is for a rated voltage                                                of 200 or 220  VAC.

   turned ON.                                                                             Power is supplied to S0 and S1 for 100 or                                        110 VAC.

   (Power Supply Pulse Response Method)                                      Connections (Refer to connection diagram.)

61F-APN2 (Compact Plug-in Model)

Used in combination with a Floatless Level Switch.

Operation

• The 61F-APN2 is used in combination with a Floatless Level Switch                                                                                                                       4

   for alternate operation when using two pumps for level control in                                                                                                       Xc1

   one location.                                                             2                           Alternate operation                                                              3

• When power is applied to the input terminals 2 and 7, NO contacts                                                                                                                       1

   1 and 3, and NO contacts 6 and 8 are turned ON via the alternate                       Power circuit                       control circuit  Output circuit        X

   operation control circuit and the output circuit. This state is held                                                                                                                   5

   with a magnetic lock even if the power supply is turned OFF.                                                                                                            Xc2

• When power is applied to the input terminals again, the NO                 7                                                                                                            6

   contacts are turned OFF and the NC contacts 1 and 4 and NC                                                                                                  G2RK

                                                                                                                                                               (61F-APN2)

   contacts 5 and 8 are turned ON. This state is held with a magnetic                                                                                                                     8

   lock even if the power supply is turned OFF.

• The above operation is repeated each time the power supply is              Note: Refer to Connecting Sockets, Mounting                                                   Brackets, DIN  Rails  for

   turned ON.                                                                   the applicable Sockets.

   (Power Supply Pulse Response Method)

                                                                                                                                                                                                      2
                                                                     61F-AN/-APN2

Connections (Refer to connection diagram.)

• Connect output terminal Ta in the 61F-G example (page 5) to input

terminal 2 on the 61F-APN2.

• Connect coil terminal A on each of the two contactors to the

switching contact terminals 3 and 4 on the 61F-APN2.

• Use the switching contact terminals 5 and 6 on the 61F-APN2 to

control the operation of the two pumps.

• The power supply of the 61F-APN2 is 100, 110, 200, or 220 VAC.

Be sure to use the correct power supply.

Output contact between

1-3 and 6-8

Output contact between

1-4 and 5-8

Power supply voltage

between 2-7

40 ms min.                   200 ms min.

                                                                                   3
                                                                                                                                                                                                    61F-AN/-APN2

■ Connections

Combining with the  61F-GN

                                                                                                                                                                                                  61F-AN

                                                                                                                                                                                                    Dimensions:

                                                                                                                                                                                                    page 17

                                                       Combining with the 61F-GN

Water Supply

                           Commercial              The relay operation can  be monitored if indicators are

                           voltage 220 VAC         connected as shown by    the dotted line.

                           R  S  T                              61F-AN

                                                                    Tb1                       Power  circuit  Alternate  operation  control circuit  Output  circuit               Tb1      L1

                                                                S0

                                                                    Tc1                                                                                                            Tc1

                                                                S2

                                 MCCB                               Ta1                              X                                                                             Ta1      L2

                                                                61F-GN                                                                                                                  To power

                                                                                                                                                                                        source T

                                                                    Ta                   Transformer

                                                                S0                0V                                                                                  U     U      E1

                                                                    Tc                               24 V                61F-11N

                                                                S1            U                                          Relay Unit                                                E2

                                                                    Tb            110 V

                                                                                                     8V

                                                                S2                220 V                                                                                            E3

                                                                                  A

                                                                                              (See note.)

                                              A                                   Contactor 2

                                                 Contactor 1

                                                                                                                                                     PS-3S

                                       Motor           Motor                                                                                                 Water                      E1

                                       protec-         protection                                                                                                     tank

                                       tion relay      relay                                                                                                                   E3  E2

                                       M1          P1           M2                   P2

                                                       Water supply       source

                    Note:      Be sure to ground the common Electrode E3 (the                                                                                                  longest Electrode).

Drainage

                           Commercial              The relay operation can  be monitored if indicators are

                           voltage 220 VAC         connected as shown by    the dotted line.

                           R  S  T                              61F-AN

                                                                    Tb1                       Power  circuit  Alternate  operation  control circuit  Output  circuit               Tb1      L1

                                                                S0

                                                                    Tc1                                                                                                            Tc1

                                                                S2

                                 MCCB                               Ta1                              X                                                                             Ta1      L2

                                                                61F-GN                                                                                                                  To power

                                                                                                                                                                                        source T

                                                                    Ta                   Transformer

                                                                S0                0V                                                                                  U     U      E1

                                                                    Tc                               24 V                           61F-11N

                                                                S1            U                                          Relay Unit                                                E2

                                                                    Tb            110 V

                                                                                                     8V

                                                                S2                220 V                                                                                            E3

                                                                                  A

                                              A                                                                                                                                (See note.)

                                                   Contactor 1                Contactor 2

                                       Motor           Motor

                                       protec-         protection

                                       tion relay      relay

                                       M1          P1           M2                P2                                                PS-3S

                                                                                                                                                                            Reservoir

                                                       Wastewater       tank

                                                                                                                         E1

                                                                                              E3 E2

                    Note:  Be  sure to ground the common                         Electrode E3 (the longest Electrode).

                                                                                                                                                                                                                  4
                                                                                                                                                 61F-AN/-APN2

Combining     with  the  61F-G

                                                                                                                                                 61F-APN2

                                                                                                                                                 Dimensions:

                                                                                                                                                 page 17

                                                                Combining with the 61F-G

Water Supply

                                Commercial voltage

                                220 VAC                         The relay operation can be      monitored

                                R   S  T                        if indicators are connected     as shown

                                          To power source T     by the dotted line.

                                          MCCB                  L2  L1                                     61F-G

                                                                                                               0V                            U

                                                                                                                         24 V        61F-11

                                                      61F-APN2                                             110 V                 Relay Unit

                                                                6   5    4        3                        220 V         8V

                                                                                                                                         U

                                                                         Electronic                            U

                                                                         circuit

                                                                                                                                                 Connection Sockets

                                                                                                           Ta      Tc      Tb      E2       E1   PF083A (Front-connecting)

                                                                7   8    1        2                        S0          S1      S2      E3        PL08 (Rear-connecting)

                                                                                                  (See     note.)

                                                   Contactor 1                            Contactor 2

                                                                                                           PS-3S

                                          Motor              Motor                                             Water                     E1

                                          protec-            protection                                            tank

                                          tion relay         relay                                                           E3      E2

                                          M1          P1            M2                    P2

                                                             Water supply         source

                         Note:  Be  sure to ground the common Electrode E3 (the longest Electrode).

Drainage

                                Commercial voltage

                                220 VAC                            The relay operation can be   monitored

                                R   S  T                           if indicators are connected  as shown

                                          To power source T        by the dotted line.

                                          MCCB                  L2  L1                                     61F-G

                                                                                                               0V                            U

                                                                                                                           24 V      61F-11

                                                      61F-APN2                                             110 V                 Relay Unit

                                                                6   5    4        3                        220 V           8V

                                                                                                                                         U

                                                                         Electronic                            U

                                                                         circuit

                                                                                                                                                 Connection Sockets

                                                                                                           Ta      Tc        Tb      E2      E1  PF083A (Front-connecting)

                                                                7   8    1        2                            S0        S1      S2      E3      PL08 (Rear-connecting)

                                                   Contactor 1

                                                                                     Contactor 2                                 (See note.)

                                          Motor           Motor

                                          protec-         protection

                                          tion relay      relay

                                          M1          P1            M2                    P2               PS-3S

                                                                                                                         Reservoir

                                                             Wastewater tank

                                                                                                       E1

                                                                                                E3 E2

                         Note:  Be  sure to ground the common Electrode E3 (the longest Electrode).

                                                                                                                                                                            5
                                                                                                                                                                                    61F-AN/-APN2

Combining     with    the 61F-G1N

                                                                                                                                                                           61F-AN

                                                                                                                                                                                Dimensions:

                                                                                                                                                                                page 17

                                                                Combining with the 61F-G1N

Water Supply          Commercial voltage

                      220 VAC                            The relay operation can be monitored if indicators                                                    are

                      R  S   T                           connected as shown by the dotted line.

                                                                61F-AN

                                MCCB

                                                                    Tb1                                           operation  control circuit                          Tb2       L1

                                                                S0                     Power  circuit  Alternate                              Output  circuit

                                                                    Tc1                                                                                               Tc2

                                                                S2

                                                                    Ta1                                                                                               Ta2       L2

                                                                                              X

                                                                61F-G1N                                                                                                    To power

                                                                                                                                                                           source T

                                                                                U1

                                                                    Tc2             Transformer

                                                                S0              0V                     61F-11N                                                        E1

                                            B                       Tb2                24     V        Relay Unit                                     U1       U2

                                       Alarm                    S1              110 V                  61F-11N                                                        E2

                                                                                       24     V        Relay Unit                                     U2

                                                                S2              220 V  8V                                                                             E3

                                                                    Ta1

                                                                                U2                                                                                    E1'

                                                                    Tb1                                                                                        U1         (E4)

                                                                                                                                                                      E2'

                                            Contactor 1                  (See note.)                                                                           PS-3S

                                                                                                                                                                              E1

                                               Contactor                                                                                                       Water      E2

                                               2                                                                                                               tank   E3

                                Motor             Motor

                                protection        protection

                                relay             relay

                                M1             P1        M2              P2     PS-3S

                                                         Water  supply  source                         E1'

                                                                                       E2'

                                                                                       E3

                      Note:  Be sure to ground the common               Electrode E3 (the longest                                             Electrode).

Drainage

The 61F-G1N   is  to  be used only for supplying water and cannot be used for alternate                                                       operation for controlling           drainage.

                                                                                                                                                                                                  6
                                                                                                                                           61F-AN/-APN2

Combining with        the 61F-G1

                                                                                                                               61F-APN2

                                                                                                                                    Dimensions:

                                                                                                                                    page 17

                                                            Combining with the 61F-G1

Water Supply

                      Commercial voltage

                      220 VAC

                      R  S   T                                          The relay operation can be monitored if indicators               are

                                           To power source T            connected as shown by the dotted line.

                                MCCB                                    61F-G1

                                                                                           0V       24 V         61F-11   U1

                                                                                                             Relay Unit

                                                                                       110 V                     61F-11   U2

                                                                                                    24 V     Relay Unit

                                              L2     L1                                220 V

                                                                                                    8V

                                      61F-APN2

                                                6    5      4        3

                                                                                                             U2                U1

                                                                                           U2                        U1

                                                            Electronic

                                                            circuit

                                                                        S0                 Tb1      Ta1              Tc2       Tb2

                                                7    8      1        2          S1     S2       E3       E2      E1       E2'       E1'  (E4)

                                                                                                                               B

                                                                                                                          Alarm

                                           Contactor 1                  (See                                     PS-3S

                                                                        note.)

                                                                                                                 Water                 E1

                                           Contactor                                                                               E2

                                           2                                                                     tank          E3

                               Motor          Motor

                               protection     protection

                               relay          relay

                                M1         P1        M2                 P2

                                                     Water  supply      source                 E1'

                                                                                       E2'

                                                                                       E3

                      Note:  Be sure to    ground the common            Electrode  E3  (the longest  Electrode).

Water Drainage

The 61F-G1N is to be  used only for supplying water and cannot be used for alternate operation for controlling drainage.

                                                                                                                                                         7
                                                                                                                                                                                                      61F-AN/-APN2

Combining     with  the  61F-G2N

                                                                                                                                                                                                      61F-AN

                                                                                                                                                                                                      Dimensions:

                                                                                                                                                                                                      page 17

                                                               Combining with the 61F-G2N

Water Supply

                                Commercial voltage             The relay operation can  be monitored if indicators are

                                220 VAC                        connected as shown by    the dotted line.

                                R   S  T                             61F-AN

                                                                            Tb1                  Power  circuit  Alternate  operation  control circuit  Output  circuit          Tb1        L1

                                                                     S0

                                                                            Tc1                                                                                                  Tc1

                                                                     S2

                                         MCCB                               Ta1                         X                                                                        Ta1        L2

                                                                     61F-G2N                                                                                                                To power

                                                                            Ta2                                                                                                             source T

                                                                                          Transformer

                                                                     S0                   0V            24       V          61F-11N                                      U1      E1

                                                        B                   Tc2   U1                                        Relay Unit                                       U2

                                                        Alarm        S1                   110 V                             61F-11N                                      U2      E2

                                                                            Ta1                         24       V          Relay Unit

                                                                     S2                   220 V         8V                                                                       E3

                                                                            Tc1   U2

                                                                                                                                                                                 E4

                                                                            Tb1

                                                                                                 (See            note.)                                         PS-4S

                                                     Contactor 1     Contactor 2

                                                                                                                                                        Water                               E4

                                            Motor                    Motor                                                                                      tank                    E1

                                            protec-                  protection                                                                                                  E3 E2

                                            tion relay               relay

                                          M1               P1               M2                   P2

                                                               Water supply       source

                         Note:  Be  sure to ground the common Electrode                                          E3 (the longest Electrode).

Drainage

                                Commercial voltage             The relay operation can  be monitored if indicators are

                                220 VAC                        connected as shown by    the dotted line.

                                R   S    T                           61F-AN

                                                                            Tb1                  Power  circuit  Alternate  operation  control circuit  Output  circuit          Tb1        L1

                                                                     S0

                                                                            Tc1                                                                                                  Tc1

                                                                     S2

                                          MCCB                              Ta1                         X                                                                        Ta1        L2

                                                                     61F-G2N                                                                                                                To power

                                                                            Ta2                                                                                                             source T

                                                                                                 Transformer

                                                                     S0                   0V            24       V          61F-11N                                      U1      E1

                                                        B                   Tc2   U1                                        Relay Unit                                       U2

                                                        Alarm        S1                   110 V                             61F-11N                                      U2      E2

                                                                            Ta1                         24       V          Relay Unit

                                                                     S2                   220 V         8V                                                                       E3

                                                                            Tc1   U2

                                                                                                                                                                                 E4

                                                                            Tb1

                                                                                                        (See

                                                        Contactor 1  Contac-                            note.)

                                                                     tor 2

                                            Motor                    Motor

                                            protec-                  protection

                                            tion relay               relay

                                            M1             P1               M2                                   P2                                                          PS-4S

                                                               Wastewater tank                                                                                           E4

                                                                                                                                                                E1

                                                                                                                                                        E3 E2

                         Note:  Be  sure to ground the common                           Electrode E3                                                    (the longest Electrode).

                                                                                                                                                                                                                    8
                                                                                                                                                                        61F-AN/-APN2

Combining     with  the  61F-G2

                                                                                                                                                                        61F-APN2

                                                                                                                                                                        Dimensions:

                                                                                                                                                                        page 17

                                                                     Combining with             the        61F-G2

Water Supply

                           Commercial voltage                                                                      61F-G2

                           220 VAC                        The relay operation can be monitored

                           R  S   T                       if indicators are connected as shown                              0V

                                     To power source T    by the dotted line.                                                         24  V   61F-11         U1

                                                                                                                        110 V                 Relay Unit

                                                          L2  L1                                                                      24  V   61F-11         U2

                                                                                                                        220 V                 Relay Unit

                                                                                                                                      8V

                                    MCCB        61F-APN2

                                                          6   5          4      3

                                                                                                                                          U2

                                                                                                                                 U2                          U1

                                                                     Electronic

                                                                     circuit

                                                                                                                   S0   Ta1      Tc1     Tb1  Ta2     Tc2

                                                          7   8          1      2                                       S1   S2       E3     E2    E1        E4

                                                                                                                                                       B         Alarm

                                                                                                           (See note.)                                       PS-4S

                                           Contactor 1

                                                                                                                                                      E4         Water

                                                        Contactor 2                                                                               E1

                                                                                                                                         E3 E2                   tank

                                                              Motor

                                    Motor                     protection

                                    protection                relay

                                    relay

                                     M1           P1                 M2                         P2

                                                       Water supply            source

                    Note: Be sure to ground the common Electrode E3 (the longest Electrode).

Drainage

                           Commercial voltage                                                              61F-G2

                           220 VAC                                   The relay operation can be monitored

                           R   S    T                                if indicators are connected as shown               0V

                                           To power source T         by the dotted line.                                         24   V   61F-11       U1

                                                                                                                   110 V                  Relay Unit

                                                                     L2     L1                                                   24   V   61F-11       U2

                                                                                                                   220 V                  Relay Unit

                                                                                                                                 8V

                                     MCCB

                                                61F-APN2             6      5      4      3

                                                                                                                                      U2

                                                                                                                            U2                        U1

                                                                                 Electronic

                                                                                 circuit

                                                                                                           S0      Ta1      Tc1  Tb1         Ta2  Tc2

                                                                     7      8      1      2                    S1       S2       E3      E2   E1      E4

                                                                                                                                                      Alarm

                                                                                                                                                   B

                                                                                                           (See note.)

                                                Contactor 1      Contactor 2

                                                                         Motor

                                                                         protection

                                           Motor                         relay

                                           protection

                                           relay

                                       M1                    P1                    M2                          P2                                     PS-4S

                                                                 Wastewater tank                                                              E4

                                                                                                                                          E1

                                                                                                                                 E3 E2

                    Note:  Be  sure to     ground the common Electrode                          E3         (the longest         Electrode).

                                                                                                                                                                                      9
                                                                                                                                                                                                       61F-AN/-APN2

Combining     with  the  61F-G3N

                                                                                                                                                                                                       61F-AN

                                                                                                                                                                                                       Dimensions:

                                                                                                                                                                                                       page 17

                                                                   Combining with the 61F-G3N

Water Supply

                                                            The relay operation can     be monitored if indicators                                             are

                                Commercial voltage          connected as shown by       the dotted line.

                                220 VAC

                                R   S  T                       61F-AN        Tb1                                                              control circuit                       Tb1      L1

                                                                         S0                             Power  circuit  Alternate  operation                   Output  circuit

                                                                             Tc1                                                                                                    Tc1

                                                                         S2

                                                                             Ta1                               X                                                                    Ta1      L2

                                         MCCB

                                                                         61F-G3N                                                                                                           To power

                                                                             Ta                         Transformer                                                                        source T

                                                                         S0                          0V                 24 V

                                                                             Tc         U2                                                                     To 61F-11N

                                                                         S1                 110 V                                                              Relay Unit           E1

                                                                             Tb                                         24 V

                                                     Upper               S2                 220 V                       8V                                                          E2

                                                                                        U1                                                                                      U2

                                                     limit     Lamp                                                                                                                 E3

                                                               PL                                              61F-11N                                         U1

                                                                         LH             U3                     Relay Unit                                                           E4

                                                               B             B1         U1                     61F-11N                                         U2

                                                     Alarm Bell          Lc                                    Relay Unit                                                           E5

                                                                             B2         U3                     61F-11N                                         U3

                                                               PL        LL                                    Relay Unit

                                                     Lower     Lamp

                                                     limit

                                                Power supply

                                                                                            (See note.)                                                        PS-5S

                                                     Contactor 1

                                                                                                                                                                                             E1

                                                            Contactor                                                                                          Water                E4 E3E2

                                                            2                                                                                                          tank

                                         Motor              Motor

                                         protection         protection                                                                                                          E5

                                         relay              relay

                                          M1                   P1    M2                 P2

                                                                   Water supply source

                         Note: Be sure to ground the common Electrode E3 (the longest Electrode).

Drainage                                                       The relay operation can  be monitored if indicators are

                                Commercial voltage             connected as shown by    the dotted line.

                                220 VAC

                                R   S  T                       61F-AN        Tb1                                                              control circuit                       Tb1      L1

                                                                         S0                             Power  circuit  Alternate  operation                   Output  circuit

                                                                             Tc1                                                                                                    Tc1

                                                                         S2

                                                                             Ta1                               X                                                                    Ta1      L2

                                         MCCB

                                                                         61F-G3N                                                                                                             To power

                                                                             Ta                         Transformer                                                                          source T

                                                                         S0                          0  V               24 V

                                                                             Tc         U2                                                                     To 61F-11N

                                                                         S1                 110         V               24 V                                   Relay Unit           E1

                                                                             Tb

                                                     Upper               S2                 220         V               8V                                                          E2

                                                     limit                              U1                                                                                      U2

                                                               Lamp                                                                                                                 E3

                                                               PL                                              61F-11N                                         U1

                                                                         LH             U3                     Relay Unit                                                           E4

                                                               B             B1         U1                     61F-11N                                         U2

                                                     Alarm Bell          Lc                                    Relay Unit                                                           E5

                                                                             B2         U3                     61F-11N                                         U3

                                                               PL        LL                                    Relay Unit

                                                     Lower
                                                               Lamp
                                                     limit

                                                Power supply

                                                     Contactor 1                        (See note.)

                                                            Contactor

                                                            2

                                         Motor              Motor

                                         protection         protection

                                         relay              relay

                                          M1                P1       M2                 P2                                                                     PS-5S

                                                                                                                                                                                Reservoir

                                                                   Wastewater tank                                                 E1

                                                                                            E5          E4 E3E2

                         Note:  Be  sure to ground the common Electrode E3 (the longest Electrode).

                                                                                                                                                                                                                     10
                                                                                                                                                                    61F-AN/-APN2

Combining     with  the  61F-G3

                                                                                                                                                                    61F-APN2

                                                                                                                                                                    Dimensions:

                                                                                                                                                                    page 17

                                                                Combining with the 61F-G3

Water Supply

                                Commercial voltage                 The relay operation      61F-G3

                                220 VAC                            can be monitored if

                                R  S   T                           indicators are

                                                                   connected as shown               0V                                      U1

                                            To power source T      by the dotted line.                          24 V    61F-11N

                                                                                                  110 V                Relay Unit

                                            MCCB                L2     L1                                       24 V    61F-11N             U2

                                                                                                  220 V                Relay Unit

                                                                                                                24 V    61F-11N             U3

                                                      61F-APN2                                                         Relay Unit

                                                                   6   5   4        3                           8V

                                                                                                    U2          U1     U3                U3             U2

                                                                           Electronic                                         U1

                                                                           circuit

                                                                                            Ta    Tc      Tb    B1           B2   Lc         E1     E3      E5

                                                                   7   8   1        2           S0      S1    S2              LH         LL         E2      E4

                                                                                                                    Alarm         Lamp      Lamp

                                                                                                                    Bell

                                                                                                                    B         PL         PL

                                                                                                      Power                       Upper Lower

                                                                                                      supply                      limit      limit

                                                                                              (See note.)                    PS-5S

                                                      Contactor 1

                                                                                                                                                                E1

                                                      Contactor                                                              Water                 E4 E3E2

                                                      2                                                                       tank

                                         Motor        Motor

                                         protection   protection                                                                             E5

                                         relay        relay

                                          M1             P1 M2                          P2

                                                               Water   supply  source

                         Note:  Be sure to ground the common Electrode E3 (the longest Electrode).

Drainage

                                Commercial voltage                 The relay operation      61F-G3

                                220 VAC                            can be monitored if

                                R   S    T                         indicators are

                                                                   connected as shown                 0V                                     U1

                                            To power source T      by the dotted line.                          24 V      61F-11N

                                                                                                  110 V                 Relay Unit

                                            MCCB                   L2  L1                                       24 V      61F-11N            U2

                                                                                                  220 V                 Relay Unit

                                                                                                                24 V      61F-11N            U3

                                                      61F-APN2                                                          Relay Unit

                                                                   6   5       4    3                           8V

                                                                                                      U2        U1      U3               U3             U2

                                                                           Electronic                                         U1

                                                                           circuit

                                                                                              Ta    Tc      Tb      B1       B2         Lc      E1      E3      E5

                                                                   7   8       1    2             S0      S1    S2               LH         LL      E2      E4

                                                                                                                       Alarm      Lamp       Lamp

                                                                                                                       Bell

                                                                                                                    B            PL      PL

                                                                                                      Power                       Upper Lower

                                                                                                        supply                    limit      limit

                                                                                        (See

                                                                                        note.)

                                                      Contactor 1

                                                      Contactor

                                                      2

                                          Motor          Motor

                                          protection     protection

                                          relay          relay

                                            M1           P1     M2                      P2                             PS-5S

                                                                                                                                         Reservoir

                                                                Wastewater tank                                 E1

                                                                                              E5      E4 E3E2

                         Note:  Be  sure to ground the common Electrode E3 (the longest Electrode).

                                                                                                                                                                                  11
                                                                                                                                                                                            61F-AN/-APN2

Combining with the 61F-G4N                                                                                                                                         Alternate Operation Relay

                                                                                                                                                                   61F-AN

                                                                                                                                                                                      Dimensions:

                                                                                                                                                                                      page 17

                                                                Combining with the 61F-G4N

Water Supply                                        The relay operation can be monitored if indicators are

                                                    connected as shown by the dotted line.

                                                            61F-AN

                                                                 Tb1                                                  operation  control circuit                       Tb2  Tb2

                                                            S0                             Power  circuit  Alternate                              Output  circuit

                                                                 Tc1                                                                                                   Tc2

                                                            S2

                                                                 Ta1                                                                                                   Ta2  Ta2

          Commercial                                                                              X

          voltage 220 VAC

             R  S  T                                                                                                                                                        To power

                                                            61F-G4N                                                                                                         source T

                                                            S0        U2                   Transformer

                                                                                       0V

MCCB                                                                            X                                                24 V

                                                            S1                                                                                    To 61F-11N

                                                                      MY3 Relay    110 V                                                          Relay Unit

                                                            S2                                                                   24 V

                                                                            X      220 V                                         8V

                                                            Tc                                                                                                         E1

                                                            Tc2             U5                                                                                         E2

                                                            TA                                                                                                     U2

                                                                                                                                                                       E3

                                                            B                                                                                                          E8

                                      BH1                                   U4                                                                                         E4

                                             Elevated tank  BH1                                   61F-11N                                         U3                   E5

                                             repletion                      U1                    Relay Unit

                                      BL1    Elevated tank  BL1                                                                                                        E6

                                             water                          U3                    61F-11N                                         U2

                                      BH2    shortage       BH2                                   Relay Unit

                                             Water supply                                                                                                              E7

                                             source upper                   X                     61F-11N                                         U4

                                      BL2    limit          BL2

                                             Water supply                                         Relay Unit                                                           E8

                                             source lower                   U4

                                      LH1    limit          LH1                                   61F-11N                                         U5

                                             Elevated tank                                        Relay Unit

                                             repletion                      U1                                                                                     U5

                                      LL1    Elevated tank  LL1                                   61F-11N                                         U1

                                             water                          U3                    Relay Unit

                                      LH2    shortage       LH2

                                             Water supply

                                             source upper                   X

                                      LL2    limit          LL2

                                             Water supply

                                             source lower

                                             limit

Contactor 1                                                 (See    note.)                                                                                                                                     PS-5S

                                                                                                                                                                                                           E4

Motor                          Contactor 2                                                                                                                                       Water                 E5

protection                                                                                                                                                                            tank         E6

relay                                                                                                                                                                                       E8 E7

                               Motor

                               protection

                      M1   P1  relay                    M2      P2

                                                                                                           PS-4S

                               Water supply  source                                               E1

                                                                                           E2

                                                                                   E8  E3

Note: Be sure to ground the common Electrode E3 (the longest Electrode).

Drainage

The 61F-G4N is to be used only for supplying water and cannot be used alternately for controlling drainage.

                                                                                                                                                                                                                      12
                                                                                                                                                                         61F-AN/-APN2

Combining with the 61F-G4                                                                                              Alternate Operation Relay

                                                                                                                       61F-APN2

                                                                                                                                                                 Dimensions:

                                                                                                                                                                 page 17

                                                              Combining with the             61F-G4

Water Supply

                                                                        61F-G4

                                                                                                             0  V                           61F-1           U5

                                                                                                                             24 V      Relay Unit

                                                                                                        100     V

                                                                                                                             24 V           61F-1           U1

                                                                                                        200     V                      Relay Unit

                       To power source T                                                                                                    61F-1           U2

                                                                                                             0  V            24 V      Relay Unit

                                          L2  L1                                                  U2                                        61F-1           U3

                                                                            MK3P             X                               24 V      Relay Unit

                           61F-APN2                                         Relay                       110     V

                                                                                                                             24 V           61F-1           U4

          Commercial                      6   5   4        3                                                                           Relay Unit

          voltage 220 VAC                                                                                                    8V

             R  S  T                                                                                    220 V

                                                                        U1          X             U4         U3    X    U1   U5          X            U4         U3                  U2  U5

                                                  Electronic

MCCB                                              circuit

                                                                        LL1      LL2         LH1          LH2           BL1        BL2           BH1          BH2        E4          E3          E2      E1

                                          7   8   1        2                 S0        S1             S2           TC        TC2            B             TA         E8       E7         E6          E5

                                                                                     Water                      Water                    Water                   Water

                                                                        Elevated     supply       Elevated      supply       Elevated    supply       Elevated   supply

                                                                        tank water   source       tank          source       tank water  source       tank       source

                                                                        shortage     lower limit  repletion     upper limit  shortage    lower limit  repletion  upper limit

                                                                        LL1      LL2         LH1          LH2           BL1        BL2           BH1          BH2

Contactor 1                                                (See note.)                                                                                                                           PS-5S

                                                                                                                                                                                             E4

Motor                          Contactor 2                                                                                                                       Water                   E5

protection                                                                                                                                                       tank                E6

relay                                                                                                                                                                         E8 E7

                               Motor

                               protection

                       M1  P1  relay                  M2      P2

                                                                                             PS-4S

                               Water supply   source                                   E1

                                                                                 E2

                                                                        E8   E3

Note: Be     sure  to  ground the common Electrode         E3 (the longest Electrode).

Drainage

The 61F-G4N is to be used only for supplying water and cannot be used alternately for controlling drainage.

                                                                                                                                                                                                             13
                                                                                                                                               61F-AN/-APN2

At 220 VAC

Water Supply (When Combined with 61F-G1P)

                         For example, operation indication is

                         possible by the connection as

                         shown by the dotted line.                                                                        B   Alarm

     Power

     source

     220 VAC                    L2  L1                                                                                                             61F-G1P

     R    S   T      61F-APN2

                                                                                                         7          14    6          5             12       4  3

                                6   5         4         3

                 Knife                                                                                                                                 U1

                 switch                                                                                         U2

                                              Electronic                                                 0V         24 V  Control circuit      U1

                                              circuit

                                                                                                                    24 V  Control circuit      U2

                                                                                                         220 V      8V

                                                                                                                                        U2             U1

                                7          8  1         2                                             8  9          15    10         1             11       2

                         A                                               A                                                                                 Pushbutton  switch

                                                               Electromagnetic  *

                 Electromagnetic switch 1                      switch 2

                                                                                                                                               PS-3S

THR                                           THR                                                                                                  Water

                                                                                               PS-3S                                               tank

                                Water supply  source                                                                                       E1

                                                                                                                              E3  E2

                                                                                           E1

                                                                                       E2

                                                                                   E3

                 M1         P1

                                                               M2           P2

*Be sure  to  ground terminal 15.

                                                                                                                                                                               14
                                                                                                                                                     61F-AN/-APN2

Water  Supply (When Combined with 61F-GP-N)

                                       For example, operation indication is

                                       possible by the connection as

                                       shown by the dotted line.                                         61F-GP-N

             Power

             source

             220 VAC                       L2        L1                                                  8         7           6        5

             R   S   T      61F-APN

                                                                                                                   U                    4

                                           6         5        4            3

                            Knife                                                                            0V       24 V     Control  circuit  U

                            switch

                                                                  Electronic                             220 V         8V

                                                                  circuit

                                                                                                                            U

                                                                                                         9                              3

                                                                                                         10        11          1        2

                                           7         8        1            2

                                    A                                          A

                                                                                                                            *

                        Electromagnetic switch 1                               Electromagnetic switch 2

       THR                                               THR                                                                                             PS-3S

                                                                                                                           Water tank

                                       Water supply  source                       Water supply source                                            E2  E1

                                                                                                                                           E3

                        M1             P1                                  M2     P2

*Be    sure  to  ground terminal 4.

                                                                                                                                                                   15
                                                                                                                                          61F-AN/-APN2

Water  Drainage (When Combined with 61F-G2P)                                                                             Alarm

                      For example, operation indication is                                                           B

                      possible by the connection as shown

                      by the dotted line.                                                                                                    61F-G2P

       Power

       source

       220 VAC                      L2  L1                                                             14        6       5

       R  S    T      61F-ANP2                                                                     7                              12      4  3

                                    6   5     4           3                                    U2                                     U1

                      Knife                                                                                                       U1

                      switch                                                                       0V      24 V  Control circuit

                                              Electronic                                                                          U2

                                              circuit                                                      24 V  Control circuit

                                                                                               220 V       8V

                                                                                                                     U2

                                    7      8           1  2                                8       9   15        10      1        11      2

                             A                                   A  *

                             Electromagnetic switch 1            Electromag-

                                                                 netic switch 2

THR                                           THR

                                    Water supply source                                        PS-4S

                                                                                       E1  E4

                                                                                 E3E2

                  M1            P1

                                                             M2     P2

*Be       sure    to ground terminal 15.

                                                                                                                                                        16
                                                                                                                                                                                    61F-AN/-APN2

Dimensions

Note: All units are in millimeters  unless  otherwise indicated.

61F-AN

                                                                            42

                                                                            25
                                                                            14 14
                                                                5

                                                            32

                                                        60      3

                                                            11

                                                                   5                                             65

                                                                                   Terminal cover                54

                                                                            11                                   10

                                                                         9         Twelve, M3.5 sems screws          3.4

                                                                                                                                                                                    4 min.

                                                            10  5

                                            100         70                                         56        50                                                                     35.4    90

                                                                            40                                       39                                                             4 min.

                                                                4

                                                            (See note.)     50

                                                                            Note:  Dimensions are  with the DIN rail mounting (sliding) bracket attached.

61F-APN2                                                                                                         Use a PFC-N8 Mounting Bracket to mount the Level

                                                                                                                 Controller to a PF083A Rail-mounted Socket.

                                                                                                                                                                                            PFC-N8

                                                                                   61F-APN2                                                                                                                      4

          49.4                                                                                               91      '$63 /7 & 2(2 8551$ &7((2 3( )5[9$$7&,215(/$<

                                                                                                                                                                                                    Approx.

                                    38                          70                                                                                                                                  80       83

                                                                      84           PF083A

                                                                                                                                                                                                    4.5

                                                                                                                                                                                                6            t = 0.3

                                                                                                                 Note: PFC-N8 Mounting Bracket (provided with

                                                                                                                 the Level Controller)

■ Safety Precautions

Refer to Safety Precautions for All Level Controllers.

          ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

          To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                                    In the interest of product improvement, specifications are subject to change without notice.

                                                                                                                                                                                                                      17
                                                     Terms and Conditions Agreement

Read and understand this catalog.

Please read and understand this catalog before purchasing the products.                 Please consult your OMRON representative if you

have any questions or comments.

Warranties.

(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship

for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron

disclaims all other warranties, express or implied.

(b)  Limitations.      OMRON    MAKES           NO   WARRANTY          OR   REPRESENTATION,         EXPRESS             OR   IMPLIED,      ABOUT

NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER

ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE

PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.

Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the

Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at

Omron’s     election,  to  (i)  replace    (in  the  form  originally  shipped    with  Buyer  responsible  for  labor  charges  for  removal            or

replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount

equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,

repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products

were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate

modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall

not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or

electronic   components,        circuits,  system    assemblies  or    any  other  materials   or   substances   or  environments.    Any  advice,

recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above

warranty.

See http://www.omron.com/global/           or contact your Omron representative for published information.

Limitation on Liability; Etc.

OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,

LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,

WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.

Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.

Suitability of Use.

Omron     Companies    shall    not  be    responsible     for  conformity  with  any   standards,  codes   or  regulations  which  apply  to            the

combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable

third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself

is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,

system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product

with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.

NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE

QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,

AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE

OVERALL EQUIPMENT OR SYSTEM.

Programmable Products.

Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence

thereof.

Performance Data.

Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining

suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate

it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.

Change in Specifications.

Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our

practice to change part numbers when published ratings or features are changed, or when significant construction changes are

made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers

may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at

any time to confirm actual specifications of purchased Product.

Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.

                                                                                                                                           2014.10

                                                           In the interest of product improvement, specifications are subject to change without notice.

OMRON Corporation

Industrial Automation Company

http://www.ia.omron.com/                                                                       (c)Copyright OMRON Corporation 2014 All Right Reserved.
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery  &  Lifecycle  Information:

Omron:

61F-AN AC110  61F-AN AC220  61F-AN AC240

小广播

61F-AN-AC240器件购买:

该厂商的其它器件

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2017 EEWORLD.com.cn, Inc. All rights reserved