Alternate Operation Relay

61F-AN/-APN2

                                                                                            CSM_61F-AN_-APN2_DS_E_3_1

Increases Motor Life and Enables Operating
Only One Pump When Cleaning Tanks or as
an Emergency Measure for Pump Failures.

Electronic Relay with the same operation as the G4Q Latching
Relay. Compared with the G4Q, the 61F-AN/-APN2 has a
shorter power supply application time and no restrictions on
mounting direction.

Compact Models (61F-AN) and Compact Plug-in Models (61F-
APN2) available.

Note: A changeover switch must be included in the sequence to enable
        operating only one pump.

        Refer to Safety Precautions for Floatless Level
        Controllers.

Ordering Information

       Type                  Model

Alternate Operation 61F-AN

Relay        61F-APN2

Note: When ordering, specify the desired operating voltage at the end of the model number.
        Example: 61F-AN [220VAC]
                                                   Desired supply voltage

Specifications

Ratings

Supply voltage               100, 110, 200, 220 VAC; 50/60 Hz
Operating voltage range      85% to 110% of rated voltage
Power consumption            3 VA
Accessories                  Hold-down clip PFC-N8 *

* Hold-down clip PFC-N8 is attached only 61F-APN2.

Contact Ratings (with G2RK Keep Relay)

                       Item                  Resistive load (cos = 1)                             Inductive load (cos = 0.4, L/R = 7 ms)
Max. load                    3 A at 250 VAC                                                 1.5 A at 250 VAC
Carry contact                3A
Max. operating current       3A                                                             375 VA
Max. switching capacity      750 VA

Characteristics              Operate: 25 ms max.
                             Release: 30 ms max.
Response time
                             Min. ON time: 40 ms min.
Minimum pulse width          Min. OFF time: 200 ms min.

Insulation resistance        100 M min. at 500 VDC (between each terminal and power supply)
Dielectric strength          2,000 VAC, 50/60 Hz for 1 min (between each terminal and power supply)
Vibration resistance
Shock resistance             10 to 55 Hz, 1-mm double amplitude
Life expectancy
                             10 G (approx. 98 m/s2)
Ambient temperature
Ambient humidity             Mechanical: 1,000,000 operations (at operating frequency of 1,800 operations/hour)
Weight                       Electrical: 100,000 operations min.
                             (rated load)

                             Operating: 10 to 55C
                             Operating: 45% to 85% RH

                             61F-AN: Approx. 215 g
                             61F-APN2: Approx. 190 g

                                                                                                                                          1
                                                                                                                                              61F-AN/-APN2

Time Chart for Alternate Operation of Water Supply

When the 61F-A@ Alternate Operation Relay is combined with a                example, after the control level is reached and the 61F Controllers'
Floatless Level Switch, the Relay output contacts switch (break)            NC contacts turn OFF (break), the Relay's output contacts switch.
while the contactor is engaged. The Relay output contacts will not          The next time the 61F Controller's NC contacts turn ON, the output
switch simultaneously with engaging the contactor. In other words,          contacts have already switched. Thus, only the continuous carry
the contactor or other load is switched with the output contacts from       current needs to be considered for the load capacity of the 61F-
the Floatless Level Switch, not directly with the output contacts from      APN2, enabling application to the rated carry current of 3 A.
the 61F-A@ Alternate Operation Relay. Using water supply as an

                    Ta
            61F

                    Tb

            Power

61F-AN,       Output
     -APN2  Tc1-Ta1

              Output
            Tc1-Tb1

            Contactor 1

            Contactor 2

61F-AN (Compact Model)

Used in combination with a 61F-G@N Floatless Level Switch.

Operation                                                                       S0       Power circuit                                         X              Tb1
                                                                                                       Alternate operation
The 61F-AN is used in combination with a Floatless Level Switch               S2                        control circuit               G2RK        Xc1
  for alternate operation when using two pumps for level control in         (See note.)                                 Output circuit  (61F-AN)
  one location.                                                                                                                                               Ta1
                                                                                                                                                              Tc1
When power is applied to the input terminals S0 and S2, NO                                                                                                  Tb2
  contacts Tc1 and Ta1, and NO contacts Ta2 and Tc2 are turned ON
  via the alternate operation control circuit and the output circuit. This                                                                          Xc2
  state is held with a magnetic lock even if the power supply is turned
  OFF.                                                                                                                                                        Ta2
                                                                                                                                                              Tc2
When power is applied to the input terminals again, the NO
  contacts are turned OFF and the NC contacts Tc1 and Tb1 and NC                   Note: The above diagram is for a rated voltage of 200 or 220 VAC.
  contacts Ta2 and Tc2 are turned ON. This state is held with a                            Power is supplied to S0 and S1 for 100 or 110 VAC.
  magnetic lock even if the power supply is turned OFF.
                                                                            Connections (Refer to connection diagram.)
The above operation is repeated each time the power supply is
  turned ON.
  (Power Supply Pulse Response Method)

61F-APN2 (Compact Plug-in Model)

Used in combination with a Floatless Level Switch.

Operation                                                                                                                                                      4

The 61F-APN2 is used in combination with a Floatless Level Switch                                                                                 Xc1
  for alternate operation when using two pumps for level control in
  one location.                                                                                                                                                  3
                                                                            2
When power is applied to the input terminals 2 and 7, NO contacts                      Power circuit
  1 and 3, and NO contacts 6 and 8 are turned ON via the alternate                                     Alternate operation                          1
  operation control circuit and the output circuit. This state is held                                    control circuit
  with a magnetic lock even if the power supply is turned OFF.                                                         Output circuit         X

When power is applied to the input terminals again, the NO                                                                                                   5
  contacts are turned OFF and the NC contacts 1 and 4 and NC
  contacts 5 and 8 are turned ON. This state is held with a magnetic                                                                                Xc2
  lock even if the power supply is turned OFF.
                                                                            7                                                                       6
The above operation is repeated each time the power supply is
  turned ON.                                                                                                                            G2RK
  (Power Supply Pulse Response Method)
                                                                                                                                        (61F-APN2)

                                                                                                                                                    8

                                                                            Note: Refer to Connecting Sockets, Mounting Brackets, DIN Rails for
                                                                                    the applicable Sockets.

                                                                                                                                                                    2
                                                                     61F-AN/-APN2

Connections (Refer to connection diagram.)
Connect output terminal Ta in the 61F-G example (page 5) to input

  terminal 2 on the 61F-APN2.
Connect coil terminal A on each of the two contactors to the

  switching contact terminals 3 and 4 on the 61F-APN2.
Use the switching contact terminals 5 and 6 on the 61F-APN2 to

  control the operation of the two pumps.
The power supply of the 61F-APN2 is 100, 110, 200, or 220 VAC.

  Be sure to use the correct power supply.

               Output contact between
                               1-3 and 6-8

               Output contact between
                               1-4 and 5-8

                  Power supply voltage
                              between 2-7

                                          40 ms min. 200 ms min.

                                                                                   3
Connections                                                                                                                        61F-AN/-APN2

Combining with the 61F-GN                                                                                                       61F-AN

                                                                                                                                Dimensions:
                                                                                                                                page 17

                                           Combining with the 61F-GN

Water Supply

              Commercial               The relay operation can be monitored if indicators are
              voltage 220 VAC          connected as shown by the dotted line.

               RST                                         61F-AN

                         MCCB                          Tb1              Power                                 Tb1 L1
                                                                           circuit                            Tc1
                                              S0                                 Alternate                    Ta1 L2
                                                   Tc1                              operation
                                                                                       control circuit                To power
                                                                                           Output                     source T
                                                                                              circuit
                                                                                                              E1
                                              S2       Ta1                                                    E2
                                                                                                              E3
                                                                         X

                                              61F-GN                    Transformer

                                                    Ta              0V   24 V       61F-11N             U  U
                                              S0            U                      Relay Unit

                                                     Tc         110 V
                                              S1                               8V

                                                    Tb          220 V
                                              S2

                               A                                A
                                 Contactor 1                          (See note.)

                                                                 Contactor 2

                                                                                       PS-3S

                           Motor           Motor                                               Water                   E1
                           protec-         protection                                            tank         E3 E2
                           tion relay      relay

                           M1          P1     M2                P2

                                           Water supply source

              Note: Be sure to ground the common Electrode E3 (the longest Electrode).

Drainage

              Commercial               The relay operation can be monitored if indicators are
              voltage 220 VAC          connected as shown by the dotted line.

               RST                                        61F-AN

                        MCCB                           Tb1              Power                                 Tb1 L1
                                                                           circuit                            Tc1
                                              S0                                 Alternate                    Ta1 L2
                                                                                    operation
                                                       Tc1                             control circuit                To power
                                                                                           Output                     source T
                                                                                              circuit
                                                                                                              E1
                                              S2                                                              E2
                                                                                                              E3
                                                       Ta1               X

                                              61F-GN                    Transformer

                                                    Ta              0V   24 V       61F-11N             U  U
                                              S0            U                      Relay Unit

                                                     Tc         110 V
                                              S1                               8V

                                                    Tb          220 V
                                              S2

                               A                                   A                                          (See note.)
                                 Contactor 1                Contactor 2

                           Motor           Motor
                           protec-         protection
                           tion relay      relay

                           M1          P1     M2                P2                   PS-3S

                                                                                                           Reservoir

                                           Wastewater tank

                                                                               E1
                                                                        E3 E2

              Note: Be sure to ground the common Electrode E3 (the longest Electrode).

                                                                                                                                                  4
                                                                                                                                     61F-AN/-APN2

Combining with the 61F-G

                                                                                                                                     61F-APN2

                                               Combining with the 61F-G                                                              Dimensions:
                                                                                                                                     page 17
Water Supply
                                                                                                                                     Connection Sockets
              Commercial voltage               The relay operation can be monitored                                                  PF083A (Front-connecting)
              220 VAC                          if indicators are connected as shown                                                  PL08 (Rear-connecting)
                                               by the dotted line.
               RST
                            To power source T

                          MCCB                 L2 L1                                 61F-G
                                                                                          0V
                                                                                                                                  U

                                                                                     110 V                       24 V     61F-11
                                                                                     220 V                              Relay Unit
                                      61F-APN2
                                                                                                                 8V
                                                 654 3                                                                         U

                                                                                                              U
                                                      Electronic
                                                      circuit

                                               7812                                  Ta Tc Tb E2 E1
                                                                                       S0 S1 S2 E3

                                Contactor 1                             (See note.)
                                                               Contactor 2

                                                                                    PS-3S

                          Motor           Motor                                      Water                                E1
                          protec-         protection                                   tank                      E3 E2
                          tion relay      relay

                          M1          P1       M2              P2

                                          Water supply source

              Note: Be sure to ground the common Electrode E3 (the longest Electrode).

Drainage

              Commercial voltage               The relay operation can be monitored
              220 VAC                          if indicators are connected as shown
               RST                             by the dotted line.

                            To power source T

                          MCCB                 L2 L1                                 61F-G
                                                                                          0V
                                                                                                                                  U

                                                                                     110 V                       24  V    61F-11
                                                                                     220 V                              Relay Unit
                                      61F-APN2
                                                                                                                 8V
                                                 6543                                                                          U

                                                                                                              U
                                                      Electronic
                                                      circuit

                                               7812                                  Ta Tc Tb E2 E1                                  Connection Sockets
                                                                                       S0 S1 S2 E3                                   PF083A (Front-connecting)
                                                                                                                                     PL08 (Rear-connecting)

                              Contactor 1

                                                      Contactor 2                                                       (See note.)

                          Motor           Motor
                          protec-         protection
                          tion relay      relay

                          M1          P1       M2              P2                    PS-3S

                                                                                                                 Reservoir

                                          Wastewater tank

                                                                          E1
                                                                   E3 E2

              Note: Be sure to ground the common Electrode E3 (the longest Electrode).

                                                                                                                                                                5
                                                                                                                              61F-AN/-APN2

Combining with the 61F-G1N

                                                                                                                         61F-AN

                                                                                                                              Dimensions:
                                                                                                                              page 17

                                             Combining with the 61F-G1N

Water Supply  Commercial voltage
              220 VAC
                                             The relay operation can be monitored if indicators are
               RST                           connected as shown by the dotted line.
                           MCCB
                                                   61F-AN
                                   B
                                                  Tb1                       Power                                   Tb2 L1
                                      Alarm  S0                                circuit                              Tc2
                                                                                     Alternate                      Ta2 L2
                                                  Tc1                                   operation
                                             S2                                            control circuit
                                                                                                Output
                                                  Ta1                                              circuit
                                                                           X

                                             61F-G1N                                                                     To power
                                                                                                                         source T
                                                  Tc2
                                             S0                   U1
                                                                      Transformer
                                                  Tb2
                                             S1                   0V        24  V   61F-11N                        E1
                                                                                   Relay Unit
                                             S2                                                U1           U2
                                                  Ta1
                                                                  110 V             61F-11N                        E2
                                                  Tb1                              Relay Unit
                                                                            24  V              U2

                                                                  220 V 8 V                                         E3

                                                                  U2                                                E1'

                                                                                                            U1          (E4)

                                                                                                                    E2'

                           Contactor 1                 (See note.)                                          PS-3S

                            Contactor                                                                       Water         E1
                            2                                                                                 tank     E2
                                                                                                                    E3
               Motor          Motor
               protection     protection               P2 PS-3S
               relay          relay

              M1            P1 M2

                                             Water supply source               E1'
                                                                           E2'
                                                                         E3

              Note: Be sure to ground the common Electrode E3 (the longest Electrode).

Drainage
The 61F-G1N is to be used only for supplying water and cannot be used for alternate operation for controlling drainage.

                                                                                                                                            6
                                                                                                           61F-AN/-APN2

Combining with the 61F-G1

                                                                                                 61F-APN2

                                                                                                        Dimensions:
                                                                                                        page 17

                                                Combining with the 61F-G1

Water Supply

              Commercial voltage  To power source T         The relay operation can be monitored if indicators are
              220 VAC                                       connected as shown by the dotted line.

               RST                                          61F-G1

                           MCCB

                                                                    0V         24 V    61F-11    U1
                                                                                     Relay Unit

                                                                    110 V      24 V    61F-11    U2
                                                                    220 V            Relay Unit

                         L2 L1                                                 8V
              61F-APN2

                                  6543

                                                                                     U2          U1

                                                                    U2                   U1

                                                Electronic
                                                circuit

                                                            S0      Tb1 Ta1              Tc2 Tb2

                                  7812                          S1 S2 E3 E2 E1 E2' E1' (E4)

                                                                                                 B

                                                                                                 Alarm

                           Contactor 1                      (See                         PS-3S
                                                            note.)
                                  Contactor                                              Water         E1
                                  2                         P2                             tank     E2
                                                                                                 E3
              Motor                 Motor
              protection            protection
              relay                 relay

               M1                 P1 M2

                                  Water supply source                     E1'
                                                                      E2'
                                                                    E3

                                Note: Be sure to ground the common Electrode E3 (the longest Electrode).

Water Drainage
The 61F-G1N is to be used only for supplying water and cannot be used for alternate operation for controlling drainage.

                                                                                                                         7
                                                                                                                                        61F-AN/-APN2

Combining with the 61F-G2N

                                                                                                                                        61F-AN

                                                                                                                                        Dimensions:
                                                                                                                                        page 17

                                               Combining with the 61F-G2N

Water Supply

              Commercial voltage               The relay operation can be monitored if indicators are
              220 VAC                          connected as shown by the dotted line.

               RST                                          61F-AN

                          MCCB                     Tb1                            Power                                   Tb1 L1
                                                                                     circuit                              Tc1
                                               S0                                          Alternate                      Ta1 L2
                                                    Tc1                                       operation
                                                                                                 control circuit
                                                                                                      Output
                                                                                                         circuit

                                               S2  Ta1

                                                                                      X

                                               61F-G2N                                                                        To power

                                                   Ta2                                                                        source T

                                                                    Transformer

                                               S0                             0V      24  V    61F-11N            U1      E1
                                                                    U1                        Relay Unit
                                         B          Tc2                                                               U2
                                               S1                          110 V
                                        Alarm                                                  61F-11N            U2      E2
                                                    Ta1                                       Relay Unit
                                                                                      24  V

                                               S2                          220 V      8V                                  E3
                                                    Tc1             U2                                                    E4

                                                   Tb1

                                Contactor 1 Contactor 2                           (See note.) PS-4S

                            Motor              Motor                                           Water                           E4
                            protec-            protection                                        tank                       E1
                            tion relay         relay
                                                                                                                      E3 E2

                            M1          P1         M2                             P2

                                               Water supply source

              Note: Be sure to ground the common Electrode E3 (the longest Electrode).

Drainage

              Commercial voltage               The relay operation can be monitored if indicators are
              220 VAC                          connected as shown by the dotted line.

                RST                                           61F-AN

                           MCCB                    Tb1                            Power                                   Tb1 L1
                                                                                     circuit                              Tc1
                                               S0                                          Alternate                      Ta1 L2
                                                    Tc1                                       operation
                                                                                                 control circuit
                                                                                                      Output
                                                                                                         circuit

                                               S2  Ta1

                                                                                      X

                                               61F-G2N                                                                        To power

                                                   Ta2                                                                        source T

                                                                                  Transformer

                                               S0                             0V      24  V     61F-11N           U1      E1
                                                    Tc2             U1                         Relay Unit
                                         B                                                                            U2
                                               S1                          110 V
                                        Alarm       Ta1                                         61F-11N           U2      E2
                                                                                               Relay Unit
                                                                                      24  V

                                               S2                          220 V      8V                                  E3
                                                    Tc1             U2                                                    E4

                                                   Tb1

                                        Contactor 1 Contac-                           (See
                                                             tor 2                    note.)

                            Motor              Motor
                            protec-            protection
                            tion relay         relay

                            M1          P1         M2                                 P2                              PS-4S

                                               Wastewater tank                                          E4
                                                                                                     E1

                                                                                               E3 E2

              Note: Be sure to ground the common Electrode E3 (the longest Electrode).

                                                                                                                                                      8
                                                                                                                                                       61F-AN/-APN2

Combining with the 61F-G2

                                                                                                                                                   61F-APN2

                                                                                                                                                       Dimensions:
                                                                                                                                                       page 17

                                                       Combining with the 61F-G2

Water Supply

              Commercial voltage               The relay operation can be monitored          61F-G2                      24  V    61F-11    U1
              220 VAC                          if indicators are connected as shown                    0V                       Relay Unit
               RST                             by the dotted line.
                                                                                                    110 V
                            To power source T                                                       220 V

                                               L2 L1                                                                     24  V    61F-11    U2
                                                                                                                                Relay Unit

                                                                                                                         8V

              MCCB         61F-APN2

                                      654 3

                                                                                                                             U2

                                                                                                                     U2                     U1

                                                       Electronic
                                                       circuit

                                               7812                                          S0 Ta1 Tc1 Tb1 Ta2 Tc2
                                                                                               S1 S2 E3 E2 E1 E4

                                                                                                                                        B Alarm

                                                                                             (See note.)                                    PS-4S

                           Contactor 1                                                                                               E4         Water
                                        Contactor 2                                                                               E1            tank

                                                                                                                            E3 E2

              Motor                            Motor
                                               protection
              protection                       relay

              relay                                   M2

              M1                  P1                                      P2

                                      Water supply source

              Note: Be sure to ground the common Electrode E3 (the longest Electrode).

Drainage

              Commercial voltage                       The relay operation can be monitored  61F-G2                  24  V    61F-11    U1
              220 VAC                                  if indicators are connected as shown                  0V             Relay Unit
                                                       by the dotted line.
                RST                                                                                       110 V
                                                                                                          220 V
                                    To power source T

                                                       L2 L1                                                         24  V    61F-11    U2
                                                                                                                            Relay Unit

                                                                                                                     8V

              MCCB         61F-APN2

                                                       654 3

                                                                                                                         U2

                                                                                                                 U2                     U1

                                                              Electronic
                                                              circuit

                                                       7812                                  S0 Ta1 Tc1 Tb1 Ta2 Tc2
                                                                                                S1 S2 E3 E2 E1 E4

                                                                                                                                  Alarm

                                                                                                                                  B

                           Contactor 1 Contactor 2                                           (See note.)

                                                       Motor

                                                       protection

                           Motor                       relay

                           protection

                           relay

              M1                               P1                  M2                        P2                                   PS-4S

                                                       Wastewater tank                                                        E4
                                                                                                                           E1

                                                                                                                     E3 E2

              Note: Be sure to ground the common Electrode E3 (the longest Electrode).

                                                                                                                                                                     9
                                                                                                                                        61F-AN/-APN2

Combining with the 61F-G3N

                                                                                                                                        61F-AN

                                                                                                                                        Dimensions:
                                                                                                                                        page 17

                                               Combining with the 61F-G3N

Water Supply  Commercial voltage        The relay operation can be monitored if indicators are
Drainage      220 VAC                   connected as shown by the dotted line.

               RST                             61F-AN                             Power                               Tb1 L1
                                                                                     circuit                          Tc1
                          MCCB                                  Tb1                        Alternate                  Ta1 L2
                                                                                              operation
                                                     S0                                          control circuit             To power
                                                          Tc1                                         Output                 source T
                                                                                                         circuit
                                                                                                                      E1
                                                     S2  Ta1                                                          E2
                                                                                                                      E3
                                                                                      X                               E4
                                                                                                                      E5
                                                     61F-G3N

                                                           Ta                     Transformer
                                                     S0
                                                                                  0V     24 V
                                                           Tc        U2                          To 61F-11N
                                                     S1                                          Relay Unit
                                                                               110 V
                                                           Tb                            24 V
                                                     S2
                                        Upper                        U1  220 V           8V                       U2
                                        limit Lamp   LH
                                                           B1                         61F-11N U1
                                             PL
                                                     Lc              U3               Relay Unit
                                                           B2
                                           B                         U1               61F-11N U2
                                                     LL
                                        Alarm Bell                                    Relay Unit

                                           PL                        U3               61F-11N U3

                                        Lower                                         Relay Unit
                                        limit
                                               Lamp

                            Power supply

                                                                         (See note.)              PS-5S

                                        Contactor 1

                                        Contactor                                                 Water                        E1
                                        2                                                           tank             E4 E3E2
                                                                                                                  E5
                            Motor       Motor
                            protection  protection                   P2
                            relay       relay

                             M1         P1 M2

                                               Water supply source

              Note: Be sure to ground the common Electrode E3 (the longest Electrode).

              Commercial voltage           The relay operation can be monitored if indicators are
              220 VAC                      connected as shown by the dotted line.

              RST                              61F-AN                             Power                               Tb1 L1
                                                                                     circuit                          Tc1
                         MCCB                                   Tb1                        Alternate                  Ta1 L2
                                                                                              operation
                                                     S0                                          control circuit              To power
                                                          Tc1                                        Output                   source T
                                                                                                         circuit
                                                                                                                      E1
                                                     S2  Ta1                                                          E2
                                                                                                                      E3
                                                                                      X                               E4
                                                                                                                      E5
                                                     61F-G3N

                                                         Ta                       Transformer

                                                     S0                           0V     24 V
                                                          Tc                                      To 61F-11N
                                                                     U2
                                                     S1                                           Relay Unit
                                                          Tb             110 V           24 V

                               Upper                 S2                  220 V           8V
                               limit Lamp
                                                                     U1                                           U2
                                    PL
                                                     LH              U3                61F-11N U1
                                    B                                                 Relay Unit
                                                          B1         U1
                                   Alarm Bell        Lc                                61F-11N U2
                                                          B2                          Relay Unit
                                    PL               LL              U3
                                                                                       61F-11N U3
                               Lower                                                  Relay Unit
                               limit Lamp
                            Power supply

                                        Contactor 1                  (See note.)

                                        Contactor

                                        2

                            Motor       Motor                        P2                        PS-5S
                                        protection                                                        Reservoir
                            protection  relay

                            relay       P1 M2

                             M1

                                               Wastewater tank                           E1
                                                                         E5 E4E3E2

              Note: Be sure to ground the common Electrode E3 (the longest Electrode).

                                                                                                                                                      10
                                                                                                                                 61F-AN/-APN2

Combining with the 61F-G3

                                                                                                                                 61F-APN2

                                                                                                                                 Dimensions:
                                                                                                                                 page 17

                                       Combining with the 61F-G3

Water Supply

              Commercial voltage                    The relay operation    61F-G3        24  V   61F-11N    U1
              220 VAC                               can be monitored if              0V         Relay Unit
                                                    indicators are
               RST                                  connected as shown            110 V
                                                    by the dotted line.           220 V
                               To power source T

                           MCCB                   L2 L1                                  24  V   61F-11N    U2
                                                                                                Relay Unit

                                                                                         24  V   61F-11N    U3
                                                                                                Relay Unit
                                       61F-APN2
                                                                                         8V
                                                  654 3

                                                                               U2        U1 U3              U3           U2

                                                           Electronic                           U1
                                                           circuit

                                                                           Ta Tc Tb B1 B2 Lc E1 E3 E5

                                                  7812                         S0 S1 S2         LH LL E2 E4

                                                                                                           Lamp
                                                                                                    Lamp
                                                                                              Alarm
                                                                               Power          Bell
                                                                               supply
                                                                                             B PL PL

                                                                                                            Upper Lower
                                                                                                            limit limit

                                                                           (See note.)          PS-5S

                                       Contactor 1

                                       Contactor                                                Water                        E1
                                       2                                                          tank              E4 E3E2

                           Motor        Motor                                                                  E5
                           protection   protection                     P2
                           relay        relay

                            M1           P1 M2

                                       Water supply source

              Note: Be sure to ground the common Electrode E3 (the longest Electrode).

Drainage

              Commercial voltage                    The relay operation    61F-G3        24  V   61F-11N    U1
              220 VAC                               can be monitored if              0V         Relay Unit
                                                    indicators are
                RST                                 connected as shown            110 V
                                                    by the dotted line.           220 V
                               To power source T

                           MCCB                     L2 L1                                24  V   61F-11N    U2
                                                                                                Relay Unit

                                                                                         24  V   61F-11N    U3
                                                                                                Relay Unit
                                       61F-APN2
                                                                                         8V
                                                  6 54 3

                                                                               U2        U1 U3              U3           U2

                                                           Electronic                           U1
                                                           circuit

                                                                           Ta Tc Tb B1 B2 Lc E1 E3 E5

                                                    7 81 2                     S0 S1 S2         LH LL E2 E4

                                                                                                              Lamp
                                                                                                       Lamp
                                                                                              Alarm
                                                                               Power          Bell
                                                                               supply
                                                                                             B PL PL

                                                                                                            Upper Lower
                                                                                                            limit limit

                                                                       (See
                                                                       note.)

                                       Contactor 1

                                       Contactor
                                       2

                           Motor       Motor
                           protection
                           relay       protection

                            M1         relay                                                    PS-5S

                                       P1 M2                           P2

                                                                                                            Reservoir

                                                  Wastewater tank                          E1
                                                                           E5 E4E3E2

              Note: Be sure to ground the common Electrode E3 (the longest Electrode).

                                                                                                                                              11
                                                                                                                                           61F-AN/-APN2

Combining with the 61F-G4N                                                                                             Alternate Operation Relay

                                                                                                                       61F-AN

                                                                                                                                 Dimensions:
                                                                                                                                 page 17

                                                                  Combining with the 61F-G4N

Water Supply                              The relay operation can be monitored if indicators are
                                          connected as shown by the dotted line.
                  Commercial
                  voltage 220 VAC                      61F-AN

                        RST                                          Tb1            Power                              Tb2       Tb2
           MCCB                                                                        circuit
                                                              S0                               Alternate                         Ta2
     Contactor 1                                                                                  operation
                                                                     Tc1                              control circuit  Tc2       To power
                                                                                                          Output                 source T
                                                                                                             circuit

                                                              S2

                                                                     Ta1                                               Ta2

                                                                                    X

                                                              61F-G4N

                                                              S0          U2          Transformer
                                                                                    0V

                                                              S1                X          24 V
                                                                                                   To 61F-11N
                                                                          MY3 Relay 110 V          Relay Unit

                                                              S2                           24 V

                                                                              X     220 V  8V

                                                              Tc                                                             E1

                                                              Tc2                                                            E2
                                                                                U5
                                                                                                                       U2
                                                              TA
                                                                                                                             E3

                                                              B                                                              E8
                                                                                                                             E4
                                   BH BH 1 Elevated tank                   U4                                                E5
                                                                                                                             E6
                                                                  1                  61F-11N U3                              E7
                                                                                    Relay Unit                               E8
                                          repletion                        U1
                                                                                     61F-11N U2                        U5
                                   BL BL 1 Elevated tank          1                 Relay Unit

                                          water                            U3        61F-11N U4
                                                                                    Relay Unit
                                   BH BH shortage                 2
                                          2 Water supply                             61F-11N U5
                                                                                    Relay Unit
                                          source upper                        X
                                                                                     61F-11N U1
                                          limit                                     Relay Unit
                                          Water supply
                                   BL BL 2                       2

                                          source lower                     U4

                                          limit
                                          Elevated
                                   LH LH 1                        1
                                                        tank

                                          repletion                        U1

                                   LL LL 1 Elevated tank         1

                                          water                            U3

                                   LH LH shortage
                                          2 Water supply         2

                                          source upper                        X

                                          limit
                                          Water supply
                                   LL LL 2                    2

                                          source lower

                                          limit

                                                              (See note.)                                                                                    PS-5S

Motor                      Contactor 2                                                                                           Water                   E4
protection                                                                                                                         tank               E5
relay                         Motor
                              protection                                                                                                          E6
                              relay                                                                                                        E8 E7
            M1 P1
                                                        M2 P2

                                   Water supply source                                              PS-4S

                                                                                               E1
                                                                                           E2
                                                                                       E3
                                                                                    E8

    Note: Be sure to ground the common Electrode E3 (the longest Electrode).

Drainage
The 61F-G4N is to be used only for supplying water and cannot be used alternately for controlling drainage.

                                                                                                                                                                    12
                                                                                                                                         61F-AN/-APN2

Combining with the 61F-G4                                                            Alternate Operation Relay

                                                                                     61F-APN2

                                                                                                                                 Dimensions:
                                                                                                                                 page 17

                                                    Combining with the 61F-G4

Water Supply

                                                     61F-G4

                                                                             0V             24 V     61F-1          U5
                                                                          100 V                   Relay Unit
                                                                          200 V
                                                                                            24 V     61F-1          U1
                                                                                                  Relay Unit

              To power source T                                                                      61F-1          U2
                                                                                                  Relay Unit
                                                                              0V            24 V

                                 L2 L1                                U2                    24 V     61F-1          U3
                                                                                                  Relay Unit
                                                         MK3P      X 110 V
                  61F-APN2                               Relay
                                                                                                                    U4
                                                                                            24 V     61F-1
Commercial                       654 3                                                            Relay Unit
voltage 220 VAC
                                                                                          8V
    RST                                                                   220 V

                                                     U1         X  U4                U3 X U1 U5 X        U4                      U3           U2 U5

MCCB                                    Electronic
                                        circuit

                                 7 812               LL1 LL2 LH1 LH2 BL1 BL2 BH1 BH2 E4 E3 E2 E1
                                                        S0 S1 S2 TC TC2 B TA E8 E7 E6 E5

                                                                     Water           Water        Water                          Water
                                                     Elevated supply Elevated                                                    supply
                                                     tank water source tank          supply Elevated supply Elevated             source
                                                     shortage lower limit repletion                                              upper limit
                                                                                     source tank water source tank

                                                                                     upper limit shortage lower limit repletion

                                                     LL1 LL2 LH1 LH2 BL1 BL2 BH1 BH2

Contactor 1                             (See note.)                                                                                                             PS-5S

Motor             Contactor 2                                                                                                    Water                      E4
protection                                                                                                                         tank                  E5
relay
                                                                                                                                                     E6
                  Motor                                                                                                                       E8 E7

                  protection

              M1  P1 relay              M2 P2

                  Water supply source                                PS-4S

                                                                E1
                                                            E2
                                                        E3
                                                     E8

Note: Be sure to ground the common Electrode E3 (the longest Electrode).

Drainage
The 61F-G4N is to be used only for supplying water and cannot be used alternately for controlling drainage.

                                                                                                                                                                       13
                                                                                                                                             61F-AN/-APN2

At 220 VAC

Water Supply (When Combined with 61F-G1P)

              For example, operation indication is                                                                              Alarm
              possible by the connection as                                                                                 B
              shown by the dotted line.

     Power              L2        L1                                                                                                             61F-G1P
     source
     220 VAC  61F-APN2

     RST

                                                                                                                 7      14  6   5            12                            4  3

                               6  5   4                  3

              Knife                                                                                                                                                    U1
              switch                                                                                                    U2

                                      Electronic                                                                 0V     24 V Control circuit U1
                                      circuit

                                                                                                                        24 V Control circuit U2

                                                                                                                 220 V  8V

                                                                                                                                         U2      U1
                                                                                                                                       1
                        7         8   1                  2                                                    8  9      15  10               11                            2

                        A                                              A                                                                                                   Pushbutton switch

              Electromagnetic switch 1                      Electromagnetic *                                                                PS-3S
                                                    THR
THR                                                         switch 2                                                                             Water
                                 Water supply source                                                                                             tank
                                                                                                       PS-3S                             E1
                                                                                                                                    E2
                                                                                                    E1                          E3
                                                                                               E2
                                                                                           E3

     M1       P1

                                                            M2  P2

*Be sure to ground terminal 15.

                                                                                                                                                                                              14
                                                                                                                                          61F-AN/-APN2

Water Supply (When Combined with 61F-GP-N)

                      For example, operation indication is              61F-GP-N
                      possible by the connection as
                      shown by the dotted line.

     Power                      L2  L1                                                                 8     7             6           5
     source                                                                                              0V
     220 VAC  61F-APN

     RST

                                6   5                   4  3                                                                          4
                                                                                                             U

              Knife                                                                                             24 V Control circuit U
              switch

                                                        Electronic                                                     8V
                                                        circuit                                        220 V

                                                                                                                           U

                                                                                                       9                               3

                                                                                                       10    11            1           2

                                7   8                   1  2

THR                     A                                                  A                                               *                            PS-3S
              Electromagnetic switch 1                              Electromagnetic switch 2
                                                                                                                           Water tank
                                                   THR                            Water supply source
                                                                                                                                                    E1
                              Water supply source                                                                                              E2
                                                                                                                                          E3

     M1               P1                                   M2       P2

*Be sure to ground terminal 4.

                                                                                                                                                               15
                                                                                                                                 61F-AN/-APN2

Water Drainage (When Combined with 61F-G2P)                                                                 Alarm
                                                                                                       B
              For example, operation indication is
              possible by the connection as shown                                                                                   61F-G2P
              by the dotted line.

     Power    61F-ANP2 L2        L1                                        7                   14  6       5             12      4  3
     source
     220 VAC

     RST

                              6  5   4         3                           U2                                                U1
                                                                               0V                                        U1
              Knife
              switch                                                                               24 V Control circuit

                                     Electronic                                                    24 V Control circuit U2
                                     circuit

                                                                                           8V
                                                                           220 V

                                                                                                       U2

                  7              8   1         2                        8  9                   15  10      1             11      2

              A                                         A  *
              Electromagnetic switch 1
                                                        Electromag-
                                          THR
                                                        netic switch 2
                       Water supply source
THR

                                                                                        PS-4S

                                                                             E1 E4
                                                                        E3E2

     M1       P1

                                                    M2     P2

*Be sure to ground terminal 15.

                                                                                                                                               16
Dimensions                                                                                                   61F-AN/-APN2

Note: All units are in millimeters unless otherwise indicated.                                        65
                                                                                                       54
61F-AN                                                                                                  10
                                                                                                         3.4
                                                                     42                                               4 min.
                                                                                                                        35.4 90
                                                                     25
                                                                     14 14
                                                        5

                                      32                                    Terminal cover
                                              3                             Twelve, M3.5 sems screws

                               60
                                      11
                                                5

                                                             11
                                                     9

                                              10 5                                  56 50
                               100 70

                                                                     40                               39  4 min.

                                                             4       50
                                                        (See note.)

                                                                     Note: Dimensions are with the DIN rail mounting (sliding) bracket attached.

61F-APN2                                                                                              Use a PFC-N8 Mounting Bracket to mount the Level
                                                                                                          Controller to a PF083A Rail-mounted Socket.

                                                                                                                                    PFC-N8

          49.4                                                                                                                                                                     4
                           38                                               61F-APN2

                                                                                                   91

                                                                                                                     Approx.

                                                        70                                                                80   83
                                                           84
                                                                            PF083A

                                                                                                                          4.5

                                                                                                                  6            t = 0.3

                                                                                                      Note: PFC-N8 Mounting Bracket (provided with
                                                                                                              the Level Controller)

Safety Precautions

Refer to Safety Precautions for All Level Controllers.

          ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
          To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

                            In the interest of product improvement, specifications are subject to change without notice.

                                                                                                                                                                                      17
                                                       Read and Understand This Catalog

Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.

                                                      Warranty and Limitations of Liability

WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.

OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.

In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.

IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

                                                            Application Considerations

SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.

At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:

       Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.

       Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
           safety equipment, and installations subject to separate industry or government regulations.

       Systems, machines, and equipment that could present a risk to life or property.

Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.

                                                                       Disclaimers

CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.

DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.

ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.

OMRON Corporation                                                                                                                                        2010.3
                               In the interest of product improvement, specifications are subject to change without notice.
Industrial Automation Company
                                                                                   (c)Copyright OMRON Corporation 2010 All Right Reserved.