             CLAMP ON POWER HiTESTER

                               3169-20, 3169-21

                                                                                        Power Measuring Instruments

Measure up to two 3-phase, 3-wire systems (displays
    voltage and current for three lines)
    Measure up to four single-phase,
    2-wire systems

0.5 A to 5000 A range

Compact and light                            The photo shows the 3169-21 combined with CLAMP ON SENSORS 9661 and 9669
    weight                                    (optional) for measuring two systems.
                                              The 3169-20/21 can also be used in combination with CLAMP ON SENSORS (optional) rated
PC card data storage                         up to 5000 A.
Power recording for individual waveforms
Simultaneous recording of demand values and

    harmonics
POWER MEASUREMENT SUPPORT SOFTWARE 9625

               Offering a new approach to energy-related measurement

               such as energy conservation, ISO14001 testing, equipment diagnosis, and harmonics measurement.

Measures power lines of up  CLAMP ON POWER HiTESTERs are 3169-20 and 3169-21 that allow measurement of single-phase to
   to 254 mm in diameter     three-phase 4-wire circuits with a single unit. In addition to measuring standard parameters such as voltage,
                             current, power, power factor, and integrated values, these clamp-on power meters can simultaneously
FLEXIBLE CLAMP               perform demand measurements required for carrying out power management and energy-saving measures,
   ON SENSOR                 as well as harmonic measurements. The two new power meters also feature PC card data storage, and come
                             equipped with an RS-232C interface for PC communications. Further, with greater data processing speeds,
   9667                      it is possible to measure the power of just a few cycles, enabling more detailed and effective energy-saving
                             measures for equipment. The 3169-20 and 3169-21 are ideal for users who want to achieve close control
                             over energy-saving management activities and measures.

MAX. AC 5000A
1

                      Offering a new measurement
                      method for energy saving activities

                                          All in a compact A5-size unit

Example of use in combination with four CLAMP ON SENSOR 9661 (optional)    CLAMP ON POWER HiTESTER 3169-21
                                                                           (Shown with D/A output)
                Simultaneous measurement of two 3-phase,
                3-wire systems.                                                                                    Simultaneous recording
                Select the clamp-on sensor type most                                                               of a variety of signal and
                suited to your measurement needs for each                                                          energy-saving data.
                individual circuit.
                                                                                                            Allows high-speed data transfer to
                                                                                                            a PC card for each waveform or at
                                                                                                            intervals of 0.1, 0.2, or 0.5 second.

CLAMP ON SENSOR 9661 (500 A AC)                                                                          VOLTAGE CORD 9438-03 (4 provided)
CLAMP ON SENSOR 9669 (1000 A AC)
(optional)                                                                  Housed in a compact A5 body size

Features                                                                   The 3169-20 and 3169-21 feature a compact design that makes them
                                                                           portable and easy to use in tight spaces, and are approximately 30%
Measure power lines of up to four systems                                 more compact than the CLAMP ON POWER HiTESTER 3166.
    (with a common voltage)
                                                                            Multi-language Compatibility
One single unit can measure four circuits (single-phase 2-wire), two
circuits (3-phase, 3-wire), or a one circuit (3-phase, 4-wire)system.      Select from nine languages, including Japanese and English.

A wide range of measurement functions                                      Detect incorrect connection using vector
                                                                               diagrams
The 3169-20/21 can simultaneously measure voltage, current, power
(active, reactive, and apparent), integrated power, power factor, and      Use the vector display on the connection confirmation screen to check
frequency. Further, when using 3-phase, 3-wire (3P3W2M) mode, you          the phase, whether a connection is loose, or whether the clamp-on sensor
can display the voltage and current for all three lines by measuring just  connection has been reversed during VT/CT terminal measurement.
two of them. When using the 3-phase, 4-wire (3P4W4I) mode, neutral
line current can be displayed using 4 current measurement.                  Polarity display and measurement using the
                                                                               reactive power measurement method
Equipped with ranges from 0.5 A to 5000 A
                                                                           The units come equipped with a polarity display for checking LAG/
The power meters support seven types of clamp-on current sensors to        LEAD when measuring power factor or reactive power. Further, you
enable measurement for a variety of items, from CT terminals to large      can select the reactive power measurement method, or display the phase
current and thick power lines.                                             factors for RMS values and power comparison.

Supports high-speed data storage from                                      High-speed D/A output
    individual waveforms
                                                                           The 3169-21 comes equipped with 4-channel high-speed D/A output to
When using the standard mode to perform integrated power measurement,      enable analog output of RMS values for individual waveforms.
you can store data in intervals starting from one second, and when
simultaneously measuring integration and harmonics, in intervals starting   Ideal for power and harmonics management
from one minute. When in the fast mode, you can store RMS data for
individual waveforms.                                                      The power meters come equipped with a harmonics measurement
                                                                           function that supports measurement of 3-phase power lines. They can
PC Card compatible plus internal hard drive for                           also perform simultaneous measurement of harmonics and demand
    extra memory                                                           values, enabling both power and harmonics management.

Store valuable measurement data in convenient PC cards. The internal
memory (1 MB) supports measurement over extended periods and detailed
measurement parameters.
                                                                                                                                                                         2

The ultimate in clamp-on power meters!

Sleek Design and Engineering                 Voltage (VOLTAGE CORD 9438-03)  Current (CLAMP ON SENSOR)           D/A output terminal pin placement
                                             input terminal                  input terminal
The photo shows the 3169-21 with
D/A output.                                                                                                      Use the CONNECTION CABLE 9441 to connect
                                                                                                                 to external devices. (Output resistance: 100 )
     Contrast adjust
     volume                                                                                                                  Pin Signal name
      Key lock switch
   Power inlet                                                                                                               1       D/A output ch1

                                                                                                                             2       D/A output ch2

                                                                                                                             3       D/A output ch3

                                                                                                                             4       D/A output ch4

                                                                                                                             5 to 8              GND

                                                                                                                                D/A output terminal
                                                                                                                             External I/O terminal

                                                                                                                             RS-232C port

Power switch

                                                                                                                                     PC card slot

                                                                                      External I/O terminal pin placement

                                                                                      Pin Signal name Pin Signal name

                                                                                      1          Start/stop input         4  Data storage input

                                                                                      2                    Free           5     GND

                                                                                      3                    Status output

Range Configuration Table                                                             Use the CONNECTION CABLE 9440 to connect to external devices.

                                   CLAMP ON SENSOR 9695-02                         CLAMP ON SENSOR 9661

              Current                       (CAT III 300V)                                  (5A, 10A, 50A, 100A, 500A)
                                   (500mA, 1A, 5A, 10A, 50A)
                                                                             CLAMP ON SENSOR 9660, 9695-03
                                   CLAMP ON SENSOR 9694
                                                                                       (CAT III 300V) (5A, 10A, 50A, 100A)
                                   (CAT III 300V) (500mA, 1A, 5A)
                                                                              10.000A 50.000A 100.00A
Voltage Connection 500.00mA 1.0000A                                5.0000A                                                   500.00A
                                                                              1.5000kW 7.5000kW 15.000kW
              Single-phase 2-wire 75.000 W 150.00 W                750.00 W                                                  75.000kW
                                                                              3.0000kW 15.000kW 30.000kW
150.00V Single-phase 3-wire        150.00 W  300.00 W              1.5000kW                                                  150.00kW
                                                                              4.5000kW 22.500kW 45.000kW
               Three-phase 3-wire                                  2.2500kW   3.0000kW 15.000kW 30.000kW                     225.00kW
                                                                   1.5000kW                                                  150.00kW
              Three-phase 4-wire 225.00 W 450.00 W                            6.0000kW 30.000kW 60.000kW
                                                                   3.0000kW                                                  300.00kW
              Single-phase 2-wire 150.00 W 300.00 W                           9.0000kW 45.000kW 90.000kW
                                                                   4.5000kW   6.0000kW 30.000kW 60.000kW                     450.00kW
300.00V       Single-phase 3-wire  300.00 W  600.00 W              3.0000kW                                                  300.00kW
              Three-phase 3-wire                                              12.000kW 60.000kW 120.00kW
                                                                   6.0000kW                                                  600.00kW
              Three-phase 4-wire 450.00 W 900.00 W                            18.000kW 90.000kW 180.00kW
                                                                   9.0000kW                                                  900.00kW
              Single-phase 2-wire 300.00 W 600.00 W

600.00V       Single-phase 3-wire  600.00 W  1.2000kW
              Three-phase 3-wire

              Three-phase 4-wire 900.00 W 1.8000kW

                            CLAMP ON SENSOR 9669                                      Current              FLEXIBLE CLAMP ON SENSOR 9667
              Current
Voltage  Connection 100.00 A 200.00 A 1.0000kA                               Voltage Connection            500.00 A 5.0000kA

              Single-phase 2-wire 15.000kW 30.000kW 150.00kW                          Single-phase 2-wire 75.000kW           750.00kW

150.00V       Single-phase 3-wire  30.000kW  60.000kW              300.00kW  150.00V  Single-phase 3-wire  150.00kW          1.5000MW
              Three-phase 3-wire                                                      Three-phase 3-wire

              Three-phase 4-wire 45.000kW 90.000kW 450.00kW                           Three-phase 4-wire 225.00kW            2.2500MW

              Single-phase 2-wire 30.000kW 60.000kW 300.00kW                          Single-phase 2-wire 150.00kW           1.5000MW

300.00V       Single-phase 3-wire  60.000kW  120.00kW              600.00kW  300.00V  Single-phase 3-wire  300.00kW          3.0000MW
              Three-phase 3-wire                                                      Three-phase 3-wire

              Three-phase 4-wire 90.000kW 180.00kW 900.00kW                           Three-phase 4-wire 450.00kW            4.5000MW

              Single-phase 2-wire 60.000kW 120.00kW 600.00kW                          Single-phase 2-wire 300.00kW           3.0000MW

600.00V       Single-phase 3-wire  120.00kW  240.00kW              1.2000MW  600.00V  Single-phase 3-wire  600.00kW          6.0000MW
              Three-phase 3-wire                                                      Three-phase 3-wire

              Three-phase 4-wire 180.00kW 360.00kW 1.8000MW                           Three-phase 4-wire 900.00kW            9.0000MW

Note 1:The range configuration table displays the full-scale display values for each measurement range. Note 2:In the table, "unit W" has been replaced with "VA" or "var" for the apparent-
power and reactive power measurement ranges. Note 3:Voltage and current input values 0.4% or less than the measurement range are displayed as "zero". When either the voltage or current
for the power line is zero, the power value is displayed as zero. Note 4:You can display measurement values up to 130% of each measurement range.
3 Measure hidden power waste through secure connections, simple measurement
    methods, and detailed data capture.

  Promises reliable measurement for power demand
  requirements!

    Select from a variety of data, including detailed and harmonics data for multiple circuits

To measure multiple systems simultaneously                                                          When measurement accuracy is crucial

A single unit can measure two three-phase, 3-wire systems. Further,                                 The addition of a vector display for viewing the connection status
you can make individual clamp-on sensor and current range settings                                  completes the preparation required for measurement.
for each system.
                                                                                                    Have you ever experienced incorrect measurement results?
Also, in addition to performing simultaneous measurement for up to four systems (single-phase,      The most common cause of incorrect data is a faulty connection. With the 3169-20/21 you can use
2-wire) with a common voltage, you can set the current range individually for each system. Setting  the vector display to check the phase, whether a connection is loose, or whether the clamp-on sensor
the most suitable current range for both large and small loads allows you to acquire more accurate  connection has been reversed.
measurements.                                                                                       Also, you are assured of proper connection when measuring the VT (PT)/CT terminals even if you
                                                                                                    cannot see the line you are measuring.
                Measurement for up to four
                single-phase, 2-wire systems                                                         Checking the connection on
                                                                                                     the vector display

                                                                                                    Accurate and reliable
                                                                                                    results

Measurement for up to two
three-phase, 3-wire systems

                                             Use the 9661 sensor                                    The basic settings are constantly displayed, allowing
                                             to measure a single                                    you to measure with confidence.
                                             system
                                                                                                    During measurement, in addition to displaying the voltage and current ranges, and VT (PT) and CT
                                                          Use the 9669 sensor to                    ratios for each system, the unit can also display items such as the measurement interval. Because
                                                          measure two systems                       the basic settings are constantly visible, you can be confident of obtaining the correct measurement
                                                                                                    results.
Having trouble clamping onto thick power lines?
                                                                                                     Capture facility data quickly
Using the FLEXIBLE CLAMP ON SENSOR 9667, you can measure
power lines that are up to 5000 A AC and up to 245 mm in diameter.                                  By using continuous processing to measure individual waveforms, you
                                                                                                    can accurately measure data in a relatively short amount of time.

                                                                                                    Use the desired measurement method to continuously measure the voltage, current, and power for
                                                                                                    individual waveforms, enabling you to obtain accurate data in one second or less. Further, you can
                                                                                                    record the maximum, minimum and average values.

The FLEXIBLE CLAMP ON SENSOR 9667 ability to measure power lines with good phase
characteristics carrying up to 5000 A AC and measuring up to 254 mm in diameter allows you to
measure the power for large current lines that were previously difficult to measure, such as trunk
lines at factories.

                              254mm (10.0")  Range: AC 500A/5000A
                                             Power supply:

                                             4 AAA alkaline batteries (LR03)
                                             (continuous use:one week or longer)
                                             or the AC adapter 9445-02/03

Simultaneous power and harmonics management                                                         Measure another device simultaneously

Use a single unit to simultaneously measure data for power and                                      Using the external I/O function, you can obtain even more detailed
harmonics.                                                                                          measurements for energy conservation.
All acquired data can be saved onto a PC card.
                                                                                                    In addition to measurement start/stop control through external input, you can use this function to
Power data (including demand data) and harmonics data can be simultaneously saved onto a            output the measurement start/stop signal for the 3169-20/21. Simultaneous recording of a variety
PC card or in the unit's internal memory. Further, data for all of the systems being measured       of signals is also possible for equipment when using multiple devices to perform start control and
can be saved when measuring multiple circuits. Each of these two new unit's offers a                multi-channel recording.
management system for power and harmonic quality.

                                                                                                                                                   Simultaneous  Synchronous
                                                                                                                           Master control operation              with master

                                                                                                    Simultaneous           3169-20                   MEMORY
                                                                                                    control for signals             3169-20  HiCORDER
                                                                                                    from equipment

                                                                                                                                                                                    
                                                                                                                                                  
                                                                                                                           
Large storage capacity to accommodate power and harmonics data for individual 4
waveforms.-Supports energy saving measures that can be carried out from your PC.

Greater flexiblity for energy saving measures through
detailed measurement!

Reduce energy consumption by "1%"! Why not try analyzing your energy saving measures?

Save measurement details to PC card for extended measurements!                                                  Unbalanced loads are an enemy to energy saving activities.
                                                                                                                   Solve your problems with careful management of power lines.
Why not try a shorter data management interval?
With the 3169-20/21, you can set the data recording interval to 1 minute. If you are unsure how                 Unbalanced 3-phase loads can result in a damaged power line.
to proceed with energy conservation, you can use a large capacity PC card to save measurement                   To provide detailed management of measurements, the 3169-20/21 displays voltage and current
details, then use the data to create a load fluctuation graph and analyze this to help reduce wasted            for all three lines even when measuring just two circuits (3P3W2M). Further, because the effective
power consumption.                                                                                              power for each phase is displayed based on a virtual center point when measuring the voltage
Further, because you can save a variety of data, including simultaneous recording of power and                  and current for all three lines (3P3W3M), the units can also be used to implement energy saving
harmonics data, waveform data storage, and print-outs of the screen, these two new units help by                measures and power management systems.
storing measurement details.
                                                                                                                                                                                     When measuring
                Measurement conditions: 1-minute recording interval, when using a PC card (128 MB)                                                                                   3P3W2M systems:
                                                                                                                                                                                             Displays the voltage/
                           Data storage                  1P2W 4 1P3W 2 3P3W2M 2 3P3W3M,3P4W                                                                                            current difference
                                                                                                                                                                                             between each pair of
                Normal measurement (only saves average,  85 days 106 days  100 days  171 days                                                                                                lines and average values
                integrated, and demand values)
                                                                                                                 When measuring with
                Normal measurement (saves all items) 45 days 41 days 37 days         62 days                     3P3W3M systems:
                                                                                                                 Displays the effective
                Normal measurement + harmonics           37 hours 40 hours 30 hours  46 hours                    power for individual
                measurement (saves all items)                                                                    phases and the three-
                                                                                                                 phase power values, as
                Interval    1P2W 4                     1P3W 2          3P3W2M 2 3P3W3M,3P4W                well as the voltage and
                                                                                                                 current for all three lines
When using a   1 minute    45 days (37 hours) 41 days (40 hours) 37 days (30 hours) 62 days (46 hours)
128 MB PC card  2 minutes   91 days (74 hours) 82 days (81 hours) 75 days (60 hours) 125 days (93 hours)         Harmonics cause wasted power

                5 minutes   229 days (186 days) 205 days (203 hours) 188 days (152 hours) 313 days (233 hours)  Did you think that harmonics and energy saving activities were unrelated?
                                                                                                                Due to a spread in equipment that uses semiconductor control devices, such as inverters, power
                10 minutes  365 days (15 days) 365 days (16 days) 365 days (12 days) 365 days (19 days)         quality has decreased. Also, power consumed in harmonic components is all wasted power.
                                                                                                                Harmonic control and management are essential for energy conservation.
                15 minutes  365 days (23 days) 365 days (25 days) 365 days (19 days) 365 days (29 days)

                30 minutes  365 days (46 days) 365 days (50 days) 365 days (38 days) 365 days (58 days)

Measurement conditions: When saving all items using normal measurement, the number of days in
                                  parentheses indicate normal measurement + harmonics measurement,

                            maximum measurement period of one year

Identify even small amounts of power waste using individual waveform measurements

The 3169-20/21 can help turn you into a keen energy saving specialist.
These two new units allow you to measure power data by recording the RMS values for individual
waveforms.
By measuring just a few seconds of machine cycles or changes in operating patterns of facilities
such as manufacturing equipment, you can grasp power fluctuations over a relatively short amount
of time and view improvements in the form of numerical data. Gain unsurpassed energy savings by
achieving simple improvements around the work environment.

                                                                                                                The degree of
                                                                                                                distortion is obvious
                                                                                                                in the voltage/current
                                                                                                                display

Results can be easily processed using software such as Excel.                                                   The current direction
                                                                                                                 of harmonic waves is
Improve energy-saving operations and create an energy-efficient facility                                        obvious

Why not try to improve your energy-saving measures using the 3169-21?                                                     You can switch channels to easily check the harmonics for each circuit
Using the D/A output (4 ch) function on the 3169-21, you can simultaneously record a variety of
measurement and control signals for equipment, such as the power fluctuation and temperature/flow                To identify causal factors with harmonic measurements of multiple systems circuits
for individual waveforms, onto a HIOKI MEMORY HiCORDER or logger.
A slight reduction in power consumption due to changes in the inverter motor operating patterns or              If production equipment malfunctions, power is wasted if repeated manufacture results in defective
temperature settings equals to an energy-saving effect.                                                         products again.
                                                                                                                If you think harmonics are causing malfunctions, you can simultaneously measure the harmonics
                          The 3169-20/21 allows you to view changes that are hard to determine                  of individual circuits using multi-circuit measurement to obtain detailed information about the
                          from numerical data alone.                                                            occurrence of harmonics along with the current direction for each phase. Using the 3169-20/21 you
                                                                                                                can accurately determine the relationship for harmonic inflow and outflow between power lines by
Accurate recording of                                                                                          analyzing the data acquired simultaneously, and then devising energy-saving measures based on the
momentary fluctuations in                                                                                      cause of the occurrence.
power, etc.

Simultaneous recording
of power volume
5

   POWER MEASUREMENT SUPPORT SOFTWARE 9625

   Graphically process measurement data from Model 3169-20/21
     easily on a PC!

   The POWER MEASUREMENT SUPPORT SOFTWARE 9625 application provides easy graphical processing on a
   computer of measurement data saved on CLAMP ON POWER HiTESTERs 3169-20/21 and 3166.
     3169-20/21

                                                                 Power Data & Harmonic Data

                                 3166                        Power Data & Harmonic Data  The 9625 handles both power
                                                                                         and harmonic measurement data
   Features                                                                              simultaneously.

    Time Series Graph Display Function                                          Daily, Weekly and Monthly Report Display
                                                                                  Function
   Measurement data can be displayed as a time series graph.
   Demand data measured in different series can be overlaid on                 Daily, weekly and monthly reports of demand data can be
   the display.                                                                displayed.

    Summary Display Function                                                    Harmonic Analysis Function

   Measurement data can be displayed directly in table form.                   Display harmonic measurement data as a graph, list or
                                                                               waveform. (Also compatible with the harmonic measurement
                                                                               data captured by Model 3166.)

                                                                                Print Function

                                                                               Each screen can be printed.

   Easily display and print various screens such as graphs and spreadsheet tables

   Step 1. Load measurement data

   Load up to 16 data sets from the 3169-20/21 or 3166 at once. Measured
   numerical values and waveform data are recognized and displayed
   automatically.
   1. Loading and deleting data, and changing data names, can be done easily.
   2. Multiple sets of measurement data can be loaded and managed in a single

      file.

   Step 2. Select the display (screen) type

   Select from time series graph, summary, daily, weekly or
   monthly report, harmonic list, harmonic graph, harmonic
   waveform or settings.

   Step 3. Select display items (two-axis display is possible)
   1. Select the data items (up to 16) to display.

      For graph displays, the type of graph (line or bar) can be
      selected.
   2. Enter details for data display. (data item names, levels, etc.)

   Step 4. Set the start/stop times and data interval
   to be displayed
   1. Set the data period to display. (start/stop time and data interval)

       The displayed period can be easily changed by
        scrolling.
Time Series Graph Display Function (two-axes display possible)                                                          6

The displayed graph can be set to suit particular start/stop times and                                        Cursor Value
     data intervals. Harmonic time series graphs can be displayed.

Convenient Functions

(1) The horizontal (time) axis can be easily scrolled to show the
     desired range.

(2) Upper and lower limits (measurement values) of the vertical
     axis can be easily set and changed.

      * Graph type (line, bar or stacked bar), line type (such as solid or dashed),
        color and details of upper and lower numerical values can be set.

(3) Any desired numerical data value on a graph can  Upper/Lower
     be confirmed and displayed by cursor movement.  Limit Setting
                                                     Slider
(4) The display can be switched between 2D and 3D
     graphs.

Summary Display Function

Summary

Displays a summary of the data values between specified start/
     stop times, at the specified data interval.

Convenient Functions

(1) In addition to measurement values within the period being
     displayed, the summary shows period, maximum, minimum
     and average values.

(2) Measurement data names and measurement units can be edited
     in the summary.

Daily, Weekly or Monthly Report Display

Displays a summary covering the total values in daily, weekly
     or monthly reports.

Convenient Functions

(1) The time axis for each total scrolls to easily change the
     totalized period.

(2) The total time range of measurement
     data can be totalized in up to four
     sections per time period.

Harmonic Display Function Harmonic data measured by the 3169-20/21 and 3166 can be displayed in various ways

Harmonic Time Series Display                                                                                   Simultaneously display multiple
                                                                                                               orders to confirm changes in
While displaying a time series graph, select the harmonic                                                     harmonics!
    item for the vertical axis to display a time series graph of                                               Simultaneously display data from
    harmonics.                                                                                                 multiple instruments to confirm
                                                                                                               concurrent series of harmonics!
Convenient Functions

(1) Up to 32 graphs can be displayed simultaneously using
     2-axes display.
     For one circuit measurement, up to 32 orders can be
     graphed. Using multiple instruments, time series of
     harmonics can be easily compared.

(2) Any desired chronological detail can be easily confirmed
     using the cursors on the graph.

Harmonic List Display                     Harmonic Graph Display                               Harmonic Waveform Display

Displays harmonic data for the selected   Displays harmonic data for the selected              Displays the voltage and current
     display item as a list.                   display item as a bar graph.                         waveforms upon which harmonic data
                                                                                                    is based.

View the list to confirm details          View the power graph to confirm trends in harmonics  View the waveforms to confirm distortion conditions
7

    Settings Display Function                                             Print Function

   When you select a data name to be load, the measuring instrument      Reports and screen copies of the displayed screen can be easily printed.
   model and setting conditions at measurement time are displayed.
   Measurement data and measurement conditions can be managed            Convenient Functions
   at the same time.
                                                                         (1) Printing results can be confirmed by print preview.
                                                                         (2) When creating a report, screen data can be copied and pasted into a

                                                                              commercial word processor program.

                                                         Preview printing to confirm print results            Produce daily, weekly or monthly reports by
                                                         before printing                                      one-touch report printing

                                                                                                                              Graph copying is also a one-touch operation

    9625 Specifications                                                                                       Supplied Media  : One CD-R disc

    General Specifications

   Supported instrument : 3169-20, 3169-21 and 3166(CLAMP ON POWER HiTESTERs)
   models
   Operating environment : Computer: PC-AT compatible (DOS/V machine)

                                    CPU: Pentium 200 MHz or higher
                                    Memory: 128 MB or more (recommended)
                                    Hard disk: 128 MB or more free space
                                    Display: XGA (1024768) or higher
                                    Disc device: CD-ROM drive (for installation)
                                    Operating system: Windows 2000, XP (English edition)

    Functional Specifications                            File extension  Data format                                          Data contents
                                                                CSV
   [Data/Setting Load/Save Functions]                                     CSV                        Instantaneous value, average value, maximum value, minimum value,
                     Loading data /Setting                      WUI      Binary                      integrated value, demand value, harmonic
                                                                BIN
                       Data file                                 ITG                                 Instantaneous waveform
                                                                DEM
   3169-20/21 Waveform data file                                HRM      Binary Instantaneous values
                                                                WUI
                       Short-interval data file                 SET      CSV Instantaneous value, integrated value
                       Integrated measurement data file         DAT
                       Demand measurement data file                      CSV                         Instantaneous value, maximum value, minimum value, demand value

       3166 Harmonic measurement data file                               CSV                         Instantaneous value, average value, maximum value

                       Waveform data file                                Binary Instantaneous waveform
                       Setting file
                                                                        
       9625 Combined file
                                                                         Binary

            Saved data /Setting                          File extension Data format

   9625  Combined file                                   DAT             Binary

   Maximum data capacity : Up to 528 MB per data set (total composite data up to 1.5 GB)

   [Time Series Graph    : Voltage, current, active power, reactive power, apparent power,           Reference value setting : Display set standard value
   Display Function]       power factor, frequency, Integrated value(active power, reactive power),
   Graph display item      demand, harmonic (level, content ratio, phase angle, total value, THD)    Graph type selection : Line, bar, 2-axes and 3-dimensional

   Y-axis upper/lower    : The display position (upper and lower display limits) of the vertical     Graph line type & color : Line type and display color can be set for each data set,
   limit setting           (Y) axis of a graph can be set by scroll bar or by specifying values.
   Interval setting                                                                                  setting  and marker display is possible
                         : Select each cycle, or 0.1, 0.2, 0.5, 1, 2, 5, 10, 15 or 30 sec.; 1, 2,
   Display period range    5, 10, 15 or 30 min.; or 1, 2, 3, 4, 6, 8 or 12 h; or 1 day               Stacked bar graph : Up to 16 types of data series (demand value, demand quantity )
   setting
                         : An optional analysis period can be specified from the overall             display  can be displayed in an overlay graph
                           measurement data period
                          (1) Analysis start date and time (YMD, HMS) is specified numerically       Cursor measurement : Measurement values can be displayed by the cursor
                          (2) Analysis stop date and time (YMD, HMS) is specified numerically        Data display units setting : Engineering units (m, k, M, G, etc.) can be selected
                           Display of measurement data period (measurement start
                           and stop date and time)
                                                                                                                                                                                                                                                                              8

[Summary Display                                                                                                                                [Copy Function]
                                                                                                                                                Copies to the clipboard : Each display can be copied to the clipboard
Function]

Display item selection : Select the items to display in the summary
Daily, weekly and
                                  : Displays a report for the specified daily weekly or monthly period                                          [Print Function]

monthly report display                                                                                                                          Printing a displayed time : Previews and prints the contents displayed on a time series graph

Load factor calculation : Calculates the load factor and demand factor as a daily, weekly                                                       series graph

display                           or monthly report, and displays the results                                                                   Printing a displayed : Previews and prints the contents displayed in a summary

Independent time range : Specify up to four time ranges and totalize data for each time                                                         summary

totalizing                        range independently                                                                                           Printing a harmonic : Previews and prints the contents displayed in a harmonic

CO2 conversion display : Display the integrated active power (kWh) in CO2 according to                                                          display                         spreadsheet

                                  the conversion rate.                                                                                          Printing the settings : Previews and prints the contents displayed in the settings

                                                                                                                                                display                         display

[Harmonic Display                                                                                                                               Comment entry                   : Text comments can be entered in any printout

Function]                                                                                                                                       Printing support                : Any color or monochrome printing supported by the operating

Waveform display : Displays waveform data for a specified time                                                                                                                  system
List display
                                  : Displays a list of harmonic data for a specified time                                                       [Display Language]

Graph display                     : Display a bar graph of harmonic data for a specified time                                                   Language                        : English

Cursor measurement : Displays the value at the cursor with waveform and graph displays

[Setting Display                  : Displays a list of the setting conditions                                                                   [CSV Format
Function]                          Loads setting conditions from a data file (3169-20/21)
Setting display                    Loads setting conditions from a settings file (3166)                                                         Conversion Function]

                                                                                                                                                Convertible screens : Time-series graph; Summary; Daily,Weekly and Monthly
                                                                                                                                                                              Report; Harmonic Waveform

3169-20/21 Specifications

Basic Specifications                                                                                                                            Display Specifications

Measurement line type :           Single-phase 2-wire, single-phase 3-wire, three-phase 3-wire, and                                             Instantaneous value :           Voltage, current, active power, reactive power, apparent power,
                                  three-phase 4-wire systems (50/60 Hz)                                                                         display                         power factor, frequency, average voltage, average current, (average
Number of systems :                                                                                                                             Average value display :         values are for each system)
that can be measured              Single-phase: 1P2W . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 systems                                                Voltage, current, active power, reactive power, apparent power,
(for systems that share                                                                                                                         Maximum/minimum :               power factor, frequency, average voltage, average current
the same voltage)                            1P3W. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 systems                    value display                   * The average value from the beginning of time series measurement until the present.
                                                                                                                                                Integrate display :
                                  Three-phase: 3P3W2M (measures the voltage and current for two lines). . . . . . 2 systems                                                     Voltage, current, active power, reactive power, apparent power,
                                                                                                                                                Demand volume display :         power factor, frequency
                                             3P3W3M (measures the voltage and current for all three lines) . . . 1 system                       (Integrated value within
                                                                                                                                                the specified interval)         * The maximum/minimum value from the beginning of time series measurement until the present.
                                             3P4W (measures the voltage and current for three lines). . . . . . . . 1 system                                                    Integrated value
                                                                                                                                                                                Active power (consumption/regeneration)
                                             3P4W4I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 system                                                        Reactive power (lag/lead)

                                                        (measures the voltage for three lines and the current for four lines)                                                   * The total integrated value from the beginning of time series measurement.
                                                                                                                                                                                Integrated value
Item                          :   Voltage, current, active power, reactive power, apparent power,                                                                               Active power volume (consumption/regeneration)
                                                                                                                                                                                Reactive power volume (lag/lead)
                                  power factor, integrated value, frequency, harmonics                                                                                          * The integrated value within each specified interval (latest value).

Measurement range :               For the voltage, current, and active power ranges, see the range

                                  configuration tables on page 2.

Measurement method :              Simultaneous digital sampling of voltage and current, PLL synchronization

                                  or a fixed clock (50/60 Hz)

Input methods                 :   Voltage: Isolated input

                                  Current: Isolated input using a clamp-on sensor                                                               Demand value display :          Active power (consumption), reactive power (lag), power factor
                                                                                                                                                (average value within
Effective measurement area :      Within 5 to 110% of the range                                                                                 the specified interval)         * The demand value within each specified interval (previous value).
Total display area :                                                                                                                            Maximum demand value display :
                                  Voltage and current:       Within 0.4 to 130% of the range                                                    (average value within the       The maximum demand value since the beginning of time series
                                                                                                                                                maximum specified interval)     measurement and the time and date it occurred.
                                                             (zero is suppressed for less than 0.4%)                                            Harmonics list :
                                                                                                                                                                                List of the items measured for the specified harmonic (numerical
                                             Power:          Within 0 to 130% of the range                                                      Harmonics graph :               value).
                                                                                                                                                                                (including the total value and total harmonic distortion factor (THD-F/THD-R))
                                                             (zero is suppressed when the voltage or current is zero)                           Waveform display :              Bar graph or vector diagram of the items measured for the specified
                                                                                                                                                                                harmonic.
                                             Harmonic level: Within 0 to 130% of the range                                                      Measurement value :             (cursor measurement, magnification update, with a linear/LOG axis selection function)
                                                                                                                                                enlargement display             Voltage and current waveforms (with a magnification update
Display                       :   5.7-inch LCD (320 240 dots), with backlight                                                                                                 function)
                                                                                                                                                                                Select and enlarge up to 5 items from the instantaneous value
Range switching method :          Manual (the current range can be set for each system)                                                                                         display.

Display update rate :             Approx. every 0.5 seconds

                                  (except when using a PC card while accessing the internal memory, or when performing RS-232C communications)

Input resistance :                Voltage: 2.0 M 10% (differential input)
(50/60 Hz)
                                  Current: 200 k 10%
Maximum input :
                                  Voltage input: 780 Vrms AC, peak value: 1103 V

                                  Current input: 1.7 Vrms AC, peak value: 2.4 V

Maximum rated voltage to earth :  Voltage input terminals: 600 Vrms AC (50/60 Hz)

Crest factor                  :   Voltage: Less than 2 (for full-scale input)

                                  Current: Less than 4 (for full-scale input. However, less than 2 for the 500 A, 1 kA, and 5 kA ranges)

Internal memory capacity :        1MB

Measurement Specifications

[Voltage/current measurement]                                                                                                                   [Frequency measurement]

Measurement method : True RMS method                                                                                                            Measurement range : 40.000 to 70.000 Hz
Measurement display : Measurement of three voltage lines and 3 or 4 current lines is possible
                                                                                                                                                Input area for           : Within 10 to 110% of the range (for sine wave input)
                               when using three-phase 3-wire and three-phase 4-wire systems
                                                                                                                                                guaranteed accuracy

                                                                                                                                                Measurement source : Voltage U1

[Active power measurement]

Measurement display : For three-phase 3-wire (the 3P3W3M setting), refer to the display for                                                     [Integrated measurement]

                                  phase power values.                                                                                           Measurement range : Active power : 0.00000 mWh to 99999.9 GWh consumption
                                                                                                                                                                                                     -0.00000 mWh to -99999.9 GWh regeneration
Polarity display              : For consumption: no symbol, for regeneration: "-"
                                                                                                                                                                               Reactive power : 0.00000 mvarh to 99999.9 Gvarh lag
[Reactive power measurement]                                                                                                                                                                         -0.00000 mvarh to -99999.9 Gvarh lead

Using the reactive : ON: Measures the reactive power directly using the reactive power                                                          Measurement display : Active power : Displays consumption and regeneration separately
                                                                                                                                                                               Reactive power : Displays lag and lead separately
power measurement                      measurement method

method                            OFF: Calculates the reactive power from the measurement values for

                                       voltage, current, and active power                                                                       [Harmonic measurement]

Polarity display              : For lag phase (LAG : current is slower than voltage): no symbol                                                 Measurement range : Basic wave frequency: 45 to 66 Hz

                                  For lead phase (LEAD: current is faster than voltage) : "-"                                                   Measurement method PLL synchronization

                                  (Reactive power measurement method "ON")                                                                      Order for analysis : Up to the 40th order

                                                                                                                                                Window width             : A single cycle (number of data points analyzed: 128 points)

[Apparent power measurement]                                                                                                                    Window type              : Rectangular

Polarity display              : No polarity                                                                                                     Analysis rate            : 1/16 cycles

                                                                                                                                                Item for analysis : Harmonic level:               The voltage, current, or power level for

[Power factor measurement]                                                                                                                                                                        each harmonic order

Measurement range : -1.0000 (lead) to 0.0000 to +1.0000 (lag)                                                                                                            : Harmonic content percentage: The voltage, current, or power

Polarity display              : For lag phase (LAG: current is slower than voltage) :no symbol                                                                                                    content percentage for each harmonic order

                                  For lead phase (LEAD: current is faster than voltage) : "-"                                                                            : Harmonic phase angle:  The voltage, current, or power phase

                                                                                                                                                                                                  angle for each harmonic order

[Frequency measurement]                                                                                                                                                  : Total value:           The total value for voltage, current, or

Measurement range : 40.000 to 70.000 Hz                                                                                                                                                           power up to the 40th harmonic order

Input area for                : Within 10 to 110% of the range (for sine wave input)                                                                                     : Total harmonic distortion factor: For voltage or current

guaranteed accuracy                                                                                                                                                                               (THD-F or THD-R)

Measurement source : Voltage U1
9

    Setting Specifications

   [Setting contents]               1P2W, 1P3W, 3P3W2M, 3P3W3M, 3P4W, 3P4W4I                                                   [Data output item]             Voltage, current, active power, reactive power, apparent power,
                                    9694, 9660, 9661, 9667, 9669, 9695-02 and 9695-03 (* A                                     Instantaneous values :         power factor, frequency, average voltage, average current, (average
   Measurement line settings :      different sensor can be set for each system.)                                                                             values are for each system)
   Clamp-on sensor settings :       0.01 to 9999.99 (* A different CT ratio can be set for each system.)                                                      * The instantaneous value for interval output.
                                    Manual or time (year, month, day, hour, minute)
   VT (PT) and CT ratio settings :  Manual, time, or timer (1 seconds to 8784 hours)                                                                          Voltage, current, active power, reactive power, apparent power,
                                    Standard or fast (*Maximum measurement period: 1 year)                                                                    power factor, frequency, average voltage, average current, (average
   Measurement start method :       Standard interval: 1, 2, 5, 10, 15, or 30 seconds, or 1, 2, 5, 10, 15, 30,                 Average value     :            values are for each system)
                                                                                                                                                              * The average value for each interval.
   Measurement stop method :                              or 60 minutes
                                    Fast interval: A single waveform, or 0.1, 0.2, or 0.5 seconds                                                             Voltage, current, active power, reactive power, apparent power,
   Output Interval    :             PC card, internal memory, or printer                                                                                      power factor, frequency
                                    Automatically attached, or set the desired name                                                                           * The maximum/minimum value for each interval (no event details provided).
                                    (up to 8 alphanumeric characters)                                                          Maximum/minimum value :
                                                                                                                                                              Active power (consumption/regeneration)
   Data output destination :        OFF, 2, 5, 10, 20 times (for movement averaging)                                                                          Reactive power (lag/lead)
                                                                                                                                                              * The total value since the beginning of time series measurement, and the power volume for each interval.
   File name          :             PC card, internal memory, or printer                                                       Integrated value :
                                    Japanese, English, German, French, Italian, Chinese (Simple, Trad),                                                       Active power (consumption), reactive power (lag), power factor
   Display averaging circuit :      Spanish , Korean                                                                           Demand value      :            * The value for each interval.
   Screen copy destination :        Reactive power measurement method selection, harmonic distortion
   Display language settings :      selection, order display selection, backlight settings, ID settings,                                                      The maximum demand value since the beginning of time series
                                    clock settings, etc.                                                                                                      measurement and the time and date it occurred.
                                                                                                                               Maximum demand value :         Each harmonic order (level, content percentage, and phase angle),
                                                                                                                                                              total value, instantaneous value for THD-F/THD-R
   Other settings     :                                                                                                                                       Each harmonic order (level, content percentage, and phase angle),
                                                                                                                                                              total value, average value for THD-F/THD-R for each interval
                                                                                                                               Harmonic          :            Each harmonic order (level, content percentage, and phase angle),
                                                                                                                                                              total value, maximum/minimum value for THD-F/THD-R within
                                                                                                                                                 :            each interval
                                                                                                                                                              (no event data provided)
   [File operations]
                                                                                                                                                              Waveform (Voltage or current)
   Copy file          :             Copies files from the internal memory to the PC card.                                                        :            Exceeds the voltage/current crest factor, PLL unlock, power failure,
                                                                                                                                                              exceeds the display limit
   Load/Save selected file :        Loads/Saves the file(s) selected from the internal memory or PC card.
   Delete file
                      :             Deletes the file(s) from the PC card.
   Format
                      :             Initializes the PC card or internal memory.
   Storage format                                                                                                              Waveform          :
                      :             Measurement data: CSV format
                                                                                                                               Status information :
                                                        (binary format when using the fast interval setting)

                                    Waveform data:      Binary format

                                    Screen data:        BMP format                                                             [Print items]
                                                                                                                               Numerical values
                                    Settings data:      CSV format                                                                               : Prints the data selected as the data output item (during time series
                                                                                                                               Waveform             measurement).

                                                                                                                                                 : Hard copy of the screen (printing of each interval not available)

    External Interface Specifications                                                                                           Formulae
                                                                                                                                      (for single-phase 2-wire systems)
   [D/A output]
                                                                                                                                                                         U : Inter-line voltage
   (3169-21 only)                                                                                                                                                        I : Line current
                                                                                                                                                                         M : Number of samples
   Number of output channels :      4 channels                                                                                                                           s : Sample count
                                                                                                                                                                         m : 128 samples per cycle
   Output items       :             For instantaneous values: Voltage, current, average voltage, average current,

                                                              Active power, reactive power, apparent power,

                                                              power factor, frequency

                                    For Integrated value: Active power (consumption/regeneration) or

                                                              reactive power (lag/lead)

                                    For harmonics:            Each harmonic order (level, content percentage,

                                                              and phase angle), total value, THD-F/THD-R

   Output level       :             5V DC/f.s.                                                                                 Measurement is also possible using the reactive
                                                                                                                                 power measurement method
   Resolution         :             Polarity + 11 bits
                                                                                                                               In addition to conventional calculation methods that search for reactive power
   Output accuracy :                Measurement accuracy 0.2% f.s.                                                            using voltage, current, and active power, you can select the reactive power
                                                                                                                               measurement method, which derives reactive power directly from voltage and
   Temperature characteristic :     Less than 0.02% f.s./C                                                                   current values, just as with the reactive power volume measurement method
                                                                                                                               used in large-volume power consumers.
   Output resistance :              100 5%
                                                                                                                               When using the reactive power measurement method:
   Output update rate :             For each cycle of measurement input (when a measurement item other than harmonics is set)
                                                                                                                                                                                 Derives reactive power directly from
                                    For every 16 cycles of measurement input (when harmonics is set as the measurement item)                                                     voltage and current values, just as with
                                                                                                                                                                                 the measurement of active power.
   [PC card]                                                                                                                                                                     (The same measurement principle is
                                                                                                                                                                                 the same as that used to determine
                      : Slot:                                 1 PC Card Standard-compliant Type II                                                                             reactive power by large-volume power
                                                                                                                                                                                 consumers.)
                                    Card type:                Flash ATA card
                                                                                                                               When not using the reactive power measurement method:
                                    Compatible memory capacity: Up to 528 MB
                                                                                                                                                                                 Calculates reactive power after
                                    Storage content:          Settings data, measurement data, screen data                                                                       calculating the apparent power using
                                                                                                                                                                                 the voltage, current, and RMS values.
   [RS-232C]

                      : Printer or PC connected to an RS-232C interface

                                    Compliance:               EIA RS-232C-compliant

                                    Transfer method:          Asynchronous communication method,

                                                              full duplex

                                    Baud rate:                2400, 9600, 19200, 38400 bps

                                    Flow control and delimiter settings possible

   [External I/O]

   Control input      : Start/stop control for time series measurement, data storage

   Control output     : LOW level is output during time series measurement.

   Control signal level : A 0/5 V logic signal or a short-circuit/release contact signal

    General Specifications

   Operating environment :          Indoors, up to 2000m(78.74ft) ASL                                                          Conforming standards :         Safety
   Operating temperature :          0 to 40C, 80% RH or less (non-condensating)                                                                           :  EN61010
   and humidity                                                                                                                                               Pollution degree 2,
   Storage temperature :            -10 to 50C, 80% RH or less (non-condensating)                                                                            measurement category (anticipated transient overvoltage 6000V)
   and humidity                                                                                                                                               EMC
   Withstand voltage :              5.55 kVrms AC: Between the voltage input terminal and the 3169                                                            EN61326 Class A
   (50/60 Hz for 15 sec.)                                 casing                                                                                              EN61000 - 3 - 2, EN61000 - 3 - 3

   Power supply voltage rating :    3.32 kVrms AC: Between the voltage input terminal and the                                  Accessories       : voltage cord set 9438-03 (1) (1 cord each of black, red, yellow,
   Maximum rated power :                                  current input terminal/external interface terminal                                        and blue), voltage cord (1), input cord label (1), operating manuals
   Dimensions and weight :                                                                                                                          (2) (Advanced edition and Quick Start Guide), CD-R (1) (Advanced
                                    2.3 kVrms AC: Between the power supply and the 3169 casing                                                      edition , RS-232C interface operating manuals and CSV conversion
                                    1.39 kVrms AC: Between the power supply and the current input                                                   Software), connection cable 9441 (1) (for the 3169-21 only)

                                                          terminal/external interface terminal
                                    100 to 240 V AC, 50/60 Hz
                                    30 VA
                                    Approx.210(8.27)W 160(6.30) H 60D(2.36) mm (excluding
                                    protrusions),
                                    Approx.1.2 kg(42.3oz.) (3169-20, 3169-21)
                                                                                                                                                                                                                                                           10

Measurement accuracy (Guaranteed accuracy period : 1 year)

      Voltage                                                 Current/active power                                          Conditions of guaranteed accuracy :          After 30 minutes of warm-up, sine-wave input, PF=1
0.2%rdg.0.1%f.s.                                  0.2% rdg. 0.1% f.s. + clamp-on sensor accuracy                        Temperature and humidity for :               23C 5C, less than 80% relative humidity
                                                                                                                            guaranteed accuracy
                                                                                                                            Fundamental waveform range for :             45 to 66 Hz
                                                                                                                            guaranteed accuracy
                                                                                                                            Display area for guaranteed accuracy :       Effective measurement area

Table of current and active power accuracy with clamp-on sensor combinations

Current rang 9694                                   9695-02 9660, 9695-03 9661                                                               9669                9667                    Reference: Accuracy of the CLAMP ON SENSORE
                                                                                                                                                                                         9694,9695-02, 9695-03, 9660, 9661, 9667, and 9669
0.5A 0.5%rdg.0.3%f.s. 0.5%rdg.2.1%f.s                                             -                        -                             -                   -
                                                                                                                                                                                          9694 (rated for 5 A) : 0.3%rdg.0.02%f.s.
1A     0.5%rdg.0.2%f.s. 0.5%rdg.1.1%f.s                                           -                        -                             -                   -                        9695-02 (rated for 50 A) : 0.3%rdg.0.02%f.s.
                                                                                                                                                                                          9695-03 (rated for 100 A): 0.3%rdg.0.02%f.s.
5A     0.5%rdg.0.12%f.s. 0.5%rdg.0.3%f.s 0.5%rdg.0.5%f.s. 0.5%rdg.1.1%f.s.                                                           -                   -                        9660 (rated for 100 A) : 0.3%rdg.0.02%f.s.
                                                                                                                                                                                          9661 (rated for 500 A) : 0.3%rdg.0.01%f.s.
10A                        -                        0.5%rdg.0.2%f.s 0.5%rdg.0.3%f.s. 0.5%rdg.0.6%f.s.                                  -                   -                        9669 (rated for 1000 A) : 1.0%rdg.0.01%f.s.
                                                                                                                                                                                          9667 (rated for 5000 A) : 2.0%rdg.1.5mV
50A                        -                        0.5%rdg.0.12%f.s. 0.5%rdg.0.14%f.s. 0.5%rdg.0.2%f.s.                               -                   -
                                                                                                                                                                                                            (500 A range: For 50 to 500 A input)
100A                       -                                       -                  0.5%rdg.0.12%f.s. 0.5%rdg.0.15%f.s.. 1.2%rdg.0.2%f.s.                -                                          (5000 A range: For 500 to 5000 A input)

200A                       -                                       -                  -                        -            1.2%rdg.0.15%f.s.                  -                       * f.s. is the sensor's rated primary current value.

500A                       -                                       -                  -          0.5%rdg.0.11%f.s.                         -             2.2%rdg.0.4%f.s.

1000A                      -                                       -                  -                        -            1.2%rdg.0.11%f.s.                  -

5000A                      -                                       -                  -                        -                             -             2.2%rdg.0.4%f.s.

Note: The table of accuracy for different clamp-on sensor combinations indicates the measurement accuracy for each current range of the
3169-20/21. (The accuracy for each clamp-on sensor is converted and displayed according to the 3169-20/21 current measurement range.)

Apparent power accuracy :  1 dgt. for the calculation obtained from each measurement value                                 Frequency characteristic :           Fundamental waveforms up to the 50th order 3% f.s. + measurement
Reactive power accuracy :  When using the reactive power measurement method                                                 Temperature characteristic :         accuracy (of a 45- to 66-Hz fundamental waveform)
                                                                                                                            Effect of in-phase voltage :         Within 0.03% f.s./C
Integration accuracy :        0.2% rdg. 0.1% f.s. + clamp-on sensor accuracy                                              Effect of external magnetic field :  Within 0.2% f.s.
Power factor accuracy :    When not using the reactive power measurement method                                             Power factor influence :             (600 Vrms AC, 50/60 Hz, between voltage input terminal and case)
Frequency accuracy :                                                                                                        Effect of reactive factor :          Within 1.5% f.s.
                              1 dgt. for the calculation obtained from each measurement value                              Real-time clock accuracy :           (in a magnetic field of 400 A/m rms AC, 50/60 Hz)
                           1 dgt. for the measurement accuracy of effective power, reactive power,                                                              1.0% rdg.
                           and apparent power                                                                                                                    (45 to 66 Hz, power factor = 0.5, for effective power measurement)
                           1 dgt. for the calculation obtained from each measurement value                                                                      1.0% rdg.
                           0.5% rdg. 1dgt.                                                                                                                     (45 to 66 Hz, reactive factor = 0.5, when using the reactive power measurement method)
                                                                                                                                                                 10 ppm 1 second (23C) (within 1.9 sec/day (23C))

Option Specifications

CLAMP ON SENSOR                                                    9694                                        9660                                        9661                                                 9669

     Appearance                                                             Cord length: 3 m                            Cord length: 3 m                             Cord length: 3 m                                 Cord length: 3 m
                                                                                       (9.84ft)                                    (9.84ft)                                    (9.84ft)                                          (9.84ft)

                                                    CAT III 300V                                 CAT III 300V                                CAT III 600V                                CAT III 600V

  Primary current rating                                           AC 5 A                                      AC 100 A                                    AC 500 A                                       AC 1000 A
    Output voltage                                                                                                                                                                                       AC 0.5mV/A
                                                                  AC 10mV/A                                    AC 1mV/A                                    AC 1mV/A                                 1.0%rdg.0.01%f.s.
Accuracy Amplitude (45 to 66 Hz)                                                                                                                                                                          Within 1
                                                    0.3%rdg.0.02%f.s.                          0.3%rdg.0.02%f.s.                            0.3%rdg.0.01%f.s.                       Within 2.0% at 40 Hz to 5 kHz (deviation from accuracy)
                            Phase (45 Hz to 5 kHz)                                                                                                                                        Equivalent to 1 A or less (with a magnetic field of 400 A/m AC)
                                                                   Within 2                                  Within 1                                  Within 0.5                                 Within 1.5%
  Frequency characteristic                                                                                                                                                                         600 V rms (insulated conductor)
Effect of external magnetic field                                                     Within 1.0% at 40 Hz to 5 kHz (deviation from accuracy)                                                       1000 A continuous
Effect of conductor position                                                                                                                                                                         Less than  55 mm(2.17"),
Maximum rated voltage to earth                                                        Equivalent to 0.1 A or less (with a magnetic field of 400 A/m AC)                                          80(3.15") 20 (0.79")mm bus bar
Maximum input (45 to 66 Hz)                                                                                                                                                              99.5W(3.92") 188H(7.40") 42D(1.65")
                                                                                                 Within 0.5%                                                                                           mm, 590g(20.8oz.)

                                                    300 V rms (insulated conductor)              300 V rms (insulated conductor)                600 V rms (insulated conductor)

                                                    50 A continuous                              130 A continuous                                  550 A continuous

Measurable conductor diameter Less than  15 mm(0.59") Less than  15 mm(0.59") Less than  46 mm(1.81")

Dimensions and weight                               46W(1.81") 135H(5.31")                    46W(1.80") 135H(5.31")                      77W(3.03") 151H(5.94")
                                                    21D(0.83") mm, 230g(9.9oz.)                  21D(0.83") mm, 230g(9.9oz.)                    42D(1.65")mm, 380g(12.7oz.)

CLAMP ON SENSOR                                                                       9667                                                      9695-02                                  9695-03

     Appearance                                     Cord length:
                                                    Sensor - circuit: 2 m(6.56ft)
                                                    Circuit - connector: 1 m(3.28ft)

                                                    CAT III 1000V                                                                            CAT III 300V                CAT III 300V

  Primary current rating                                              AC 500 A, 5000A                                                           AC 50 A                                  AC 100 A
    Output voltage                                                     AC 500 mV f.s.
                                                        2.0%rdg.1.5mV(for input 10% or more of the renge)                                  AC 10 mV/A                                  AC 1 mV/A
Accuracy Amplitude (45 to 66 Hz)
                                                                          Within 1                                                                       0.3%rdg.0.02%f.s.
                           Phase (45 Hz to 5 kHz)        Within 3 dB at 10 Hz to 20 kHz (deviation from accuracy)
                                                       Equivalent to 5 A, 7.5 A max. (with a magnetic field of 400 A/m AC)                      Within 2                               Within 1
  Frequency characteristic
Effect of external magnetic field                                        Within 3.0%                                                        Within 1.0% at 40 Hz to 5 kHz (deviation from accuracy)
Effect of conductor position                                       1000 V rms (insulated conductor)
Maximum rated voltage to earth                                                                                                               Equivalent to 0.1 A or less (with a magnetic field of 400 A/m AC)
Maximum input (45 to 66 Hz)                                         10000 A continuous
Measurable conductor diameter                                   Less than  254 mm(10.0")                                                                         Within 0.5%

Dimensions and weight                              Sensor: 910 mm(2.99ft) long, 240g(8.5oz.),                                                             300 V rms (insulated conductor)
                                                    Circuit: 57W(2.24") 86H(3.39") 30D(1.18") mm, 140g(4.9oz.)
     Power supply                                   LR03 alkaline battery 4 (continuous operation max. 168 hours)                          60 A continuous                     130 A continuous

                                                                 or AC ADAPTER 9445(optional)                                                              Less than  15 mm(0.59")

                                                                                                                                             50.5W(1.99") 58H(2.28") 18.7D(0.74")mm, 50g(1.8oz.)
                                                                                                                                                Option : CONNECTION CABLE 9219
11

    Option Specifications

PRINTER 9442                                                                                           PC CARD 9726 to 9728

Print method                                    : Thermal serial dot printing                                                                   Use only PC Cards (9726, 9727, or 9728)
Paper width                                     : 112 mm(4.41ft)                                                                                sold by HIOKI.
Print speed                                     : 52.5cps
Power supply                                    : AC adapter 9443-02/03, or supplied                   CARRYING CASE 9720

Dimensions and                                     nickel-metal hydride battery (approx.                                                        A soft type case for storing the 3169-20/21
weight                                             3000 lines of printing when fully                                                            and its accessories, such as the clamp-on
                                                   charged and used with the 9443-02/03)                                                        sensors.
                                                : Approx.160W (6.30") 66.5H(2.62")                                                                 Dimensions : Approx. 445W(17.52") 340H(13.39")
                                                   17D(0.67") mm,                                                                                    and weight 150D(5.91") mm,
                                                   approx.580g(20.5oz.)
                                                                                                                                                                               approx. 2.2 kg(77.6oz.)
When purchasing the printer 9442, make sure you also purchase the RS-232C
cable 9721and AC adapter 9443-02/03 so that you can connect it to the
3169-20/21.

RS-232C CABLE 9721                              AC ADAPTER 9443-02/03
                                                                    For the 9442
                 Cord length for
                 connecting to the
                 9442: 1.5 m(4.92ft)

                                                Photo: 9443-03

CONNECTION CABLE 9440                         CONNECTION CABLE 9441                                    CLAMP ON ADAPTER 9290-10                         CONNECTION CABLE 9219
           For external I/O
                                                                For D/A output                                              Cord length: 3 m(9.84ft)  For connection to the 9695-02, 9695-03
                                                                (supplied with
                                                                the 3169-21)

Cord length: 2m(2.65ft)          Cord length: 2 m(2.65ft)                                              Max. 1500 A AC (continuous: 1000 A)                           Cord length: 3 m(9.84ft)
                                                                                                       Measurable conductor diameter:
                                                                                                       Bus bar : 55 mm(2.17"), width 80 mm(3.46")
                                                                                                       CT ratio: 10:1

                                                                                                         *Used for expanding the measurement ranges of the 9660 and
                                                                                                          9661 sensors

CLAMP ON POWER HiTESTER 3169-20                                                                         Options

(supplied with the voltage cord 9438-03 (1), and power cord (1))                                       CLAMP ON SENSOR 9660 (AC 100A)
                                                                                                       CLAMP ON SENSOR 9661 (AC 500A)
CLAMP ON POWER HiTESTER                                                                                FLEXIBLE CLAMP ON SENSOR 9667 (AC 5000A)
                             3169-21 (with D/A output)                                                 CLAMP ON SENSOR 9669 (AC 1000A)
                                                                                                       CLAMP ON SENSOR 9694 (AC 5A)
(supplied with the voltage cord 9438-03 (1), connection cable 9441 (1) and                             CLAMP ON SENSOR 9695-02 (AC 50A)
power cord (1))                                                                                        CLAMP ON SENSOR 9695-03 (AC 100A)
                                                                                                       CONNECTION CABLE 9219 (for connection to the 9695-02, 9695-03)
Accessory Specifications                                                                               CLAMP ON ADAPTER 9290-10 (AC 1500A)
                                                                                                       CONNECTION CABLE 9440 (for external I/O)
VOLTAGE CORD 9438-03 (1 cord each of black, red, yellow, and blue, cord length: 3 m(9.84ft))           RS-232C CABLE 9612 (for connection to a PC)
CONNECTION CABLE 9441 (D/A output cable, supplied with the 3169-21)                                    PRINTER 9442

Current and power cannot be measured using the CLAMP ON POWER HiTESTER 3169-20/21 on                   AC ADAPTER 9443-02 (for the 9442, for Europe)
its own. To perform current and power measurement, make sure you also purchase a CLAMP                 AC ADAPTER 9443-03 (for the 9442, for USA)
ON SENSOR (9694, 9660, 9661, 9667, or 9669) (sold separately).                                         RS-232C CABLE 9721 (for connection to the 9442)
Use only PC Cards (9726, 9727or 9728) sold by HIOKI.                                                   RECORDING PAPER 1196 (25 m(82ft)/10 rolls, for the 9442)
Compatibility and performance are not guaranteed for PC cards made by other manufacturers.             CARRYING CASE 9720
You may be unable to read from or save data to such cards.
                                                                                                       POWER MEASUREMENT SUPPORT SOFTWARE 9625
Combination examples
                                                                                                       PC CARD 128M 9726
For single-phase 2-wire systems (one system) : 3169-20 + 9660(100A) 1 +9726(128MB)
                                                                                                       PC CARD 256M 9727
For single-phase 3-wire systems                 : 3169-20 + 9660(100A) 2 +9726(128MB)
                                                                                                       PC CARD 512M 9728
(one system/two single-phase 2-wire systems)

For three-phase 3-wire systems (one system) : 3169-20 + 9661(500A) 2 +9726(128MB)

For three-phase 3-wire systems                  : 3169-20 + 9661(500A) 4 +9726(128MB)

(two systems/four single-phase 2-wire systems)

For three-phase 4-wire systems (one system) : 3169-20 + 9661(500A) 3 +9726(128MB)

                                                                                                       DISTRIBUTED BY

HEAD OFFICE :                                   Shanghai Representative Office :
81 Koizumi, Ueda, Nagano, 386-1192, Japan       1904 Shanghai Times Square Office
TEL +81-268-28-0562 / FAX +81-268-28-0568       93 Huaihai Zhong Road
E-mail: os-com@hioki.co.jp                      Shanghai, 200021, P.R.China
                                                TEL +86-21-6391-0090, 0092
HIOKI USA CORPORATION :                         FAX +86-21-6391-0360
6 Corporate Drive, Cranbury, NJ 08512 USA       E-mail: info@hioki.cn
TEL +1-609-409-9109 / FAX +1-609-409-9108
E-mail: hioki@hiokiusa.com

All information correct as of Nov. 29, 2006. All specifications are subject to change without notice.                                                                3169E7-6YE-03P Printed in Japan
This datasheet has been downloaded from:
             www.EEworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company
小广播

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet 电子工程

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2020 EEWORLD.com.cn, Inc. All rights reserved