                                                                                                                               1151

                                                                                                                         SYSTEM SENSOR
                                                                                                                  LOW PROFILE, IONIZATION
                                                                                                                  PLUG-IN SMOKE DETECTOR

                   DESCRIPTION                                                                   FEATURES
                                                                                    Unique Dual Unipolar Sensor
  The System Sensor 1151 low profile ionization type smoke
detectors are specifically designed to meet the performance                           Provides Exceptional Stability
requirements of fire detection/alarm systems. The 1151 ion-
ization detector uses a state-of-the-art, dual unipolar sensing                     Low Profile Construction
chamber. The detector is designed to provide open area de-
tection and, when installed in a two-wire base, is compatible                      Easy plug-in of the Head to Base
with FCI fire alarm control panels. The detector's operation
and sensitivity can be tested in place.                                             Tamper-resistant Feature

  The 1151 detector is of plug-in construction and plugs into                      Test Switch
the same base as the System Sensor 2151photoelectronic                              360o View Angle Of Alarm LEDs
smoke detector, making both models interchangeable. Bases
are available for two-wire, four-wire, 120 VAC four-wire op-                        Compatible with FCI Control Panels
eration and also with an audible sounder.
                                                                                    Audible Sounder Base (Optional)
  Two visible LEDs on each detector flash every ten seconds
indicating that power is being applied to the detector. The                         Field Metering of Detector Sensitivity
LEDs light steadily when the detector is in alarm. A remote
LED annunciator is available as an optional accessory.                              Removable Insect Screen and Cover
                                                                                      for Field Cleaning
  The 1151 detector is Listed for use inside ducts up to a ve-
locity of 500 FPM.                                                                  Insect-resistant Screening
                                                                                      (.020"/.508 mm openings)
  Functional testing is performed by placing a test magnet
against the cover. The LED on the detector should light
within 30 seconds.

  Field metering of detector sensitivity may be performed
with the aid of a voltmeter and Test Kit, MOD 400R.

                    APPROVALS

Sensitivity            SPECIFICATIONS
Operating voltage
Standby current                 1.9 %/ft. (nominal)
Operating temperature           15 - 32 VDC peak
Relative humidity               200 uA max. avg.
Air velocity                    32 to 120o F (0 to 49o C)
Construction                    10 to 93 % (non-condensing)
Diameter                        500 feet per minute maximum
Height                          Off-white flame retardant plastic
Weight                          4 inches (10.2 cm)
                                1.7 inches (4.2 cm)
                                3.6 oz. (104 g)

Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control

Instruments, Inc. for their use. Specifications subject to change without notice.                                  2003 All Rights Reserved

16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099

                                                                                   An ISO 9001 Certified Company  9020-0582/Ver. 1.1
                  MOUNTING                                                 MAINTENANCE

      On a 4-inch square box with or without plaster         Cleaning programs should be adapted to the individ-
       ring. Minimum depth 1.5 inches.                      ual environment. We recommend at least an annual
                                                            cleaning of the unit. The detector screen and cover as-
      On a 3.5-inch octagonal box. Minimum depth           sembly can be removed, revealing the sensing cham-
       1.5 inches.                                          ber. A vacuum cleaner can be used to remove dust from
                                                            the screen, cover and sensing chamber. For the com-
               INSTALLATION                                 plete procedure, refer to the Installation and Mainte-
                                                            nance Instructions furnished with each detector.
  Place the detector into the detector base. Turn the de-
tector clockwise until the detector locks into place.

  To use the tamper-proof feature, break the smaller tab
on the scribed line in the tamper proof tab located on the
detector mounting bracket. Install the detector. To re-
move the detector from the base when using the tam-
per-proof feature, insert the blade of a small
screwdriver into the hole on the side of the base and
push the plastic lever away from the detector head. This
will allow the detector to be rotated counterclockwise
for removal. NOTE: The decorative ring must be re-
moved in order to remove the head when using the tam-
per-proof feature.

  The tamper-proof feature may be defeated perma-
nently by breaking the plastic lever off the base.

  NOTE: The number of two-wire smoke detectors
which can be accommodated per zone varies with dif-
ferent control panels. Consult the control panel in-
struction manual to determine the capacity.

  Refer to NFPA 72, Chapter 5-3, "Smoke Sensing Fire
Detectors" for spacing, location of detectors and other
guidelines.

                    TESTING

  Detectors may be tested in the following ways:
      Place a test magnet against the detector
       as directed in the installation instructions.
       The detector should go into alarm within
       30 seconds.

      Field metering of detector sensitivity may be
       performed with the aid of a voltmeter and Test
       Kit, MOD 400R. For the complete procedure,
       refer to the Installation and Maintenance
       Instructions furnished with each detector.

               ORDERING AND TECHNICAL INFORMATION

        Model     Contacts        Description
                                  Ionization Detector
        1151                      Base, Two-wire
                                  Base, four-wire, 24 VDC operation
        B110LP                    Base, four-wire, 120 VAC operation
                                  Base, four-wire, with audible sounder
        B112LP Form A & C         Remote Alarm Indicator
                                  End of Line Relay, 24 VDC
        B114LP Form A, C & Supv.  Test Kit

        B401BH

        RA-400Z

        PAM-1 Form B

        MOD 400R

2 of 2                                                                   9020-0582
This datasheet has been downloaded from:
             www.EEworld.com.cn

                 Free Download
           Daily Updated Database
      100% Free Datasheet Search Site
  100% Free IC Replacement Search Site
     Convenient Electronic Dictionary

               Fast Search System
             www.EEworld.com.cn

                                                 All Datasheets Cannot Be Modified Without Permission
                                                                Copyright Each Manufacturing Company

1151器件购买:

About Us 关于我们 客户服务 联系方式 器件索引 网站地图 最新更新 手机版

站点相关: 大学堂 TI培训 Datasheet

北京市海淀区知春路23号集成电路设计园量子银座1305 电话:(010)82350740 邮编:100191

电子工程世界版权所有 京ICP证060456号 京ICP备10001474号 电信业务审批[2006]字第258号函 京公海网安备110108001534 Copyright © 2005-2017 EEWORLD.com.cn, Inc. All rights reserved